You are on page 1of 5

How adjustable

speed drives affect


power distribution
Application Note

Adjustable speed drives (ASDs) Voltage distortion inrush current and no voltage sag
can be both a source and a victim If high-voltage distortion shows effect on the rest of the system.
of poor power quality. up as excessive flat-topping, it Secondly, if the drive is of the
will prevent dc link capacitors PWM type, with a diode con-
ASDs as victim loads from charging fully and will verter front-end, the
Although ASDs are usually diminish the ride-through capa- Displacement Power Factor is
depicted as the culprit in the PQ bility of the drive. Thus a voltage high (commonly > 95 % at rated
scenario, there are ways in sag which would not normally load) and more or less constant
which they can be a victim load affect a drive will cause the drive throughout the range. This means
as well. to trip on undervoltage. that drives can reduce energy
Improper grounding will usage and correct for DPF at the
Capacitor switching transients affect the internal control circuits same time. Its a good thing too,
High-energy (relatively low- of the drive, with unpredictable because drives and PF correction
frequency) transients that are results. capacitors dont mix. Caps are
characteristic of utility capacitor vulnerable to the higher fre-
switching can pass through the ASDs as culprit loads quency harmonic currents
service transformer, feeders, and generated by drives, since their
A drive can definitely be a cul-
converter front-end of the drive impedance decreases as fre-
prit load and have a major
directly to the dc link bus, where quency increases.
impact on system PQ. But before
it will often cause a dc link over- The type of drive has a major
we talk of problems, lets put in a
voltage trip. Input diodes could impact on the PQ symptoms,
good word for the positive effects
also be blown out by these tran- because of the different converter
of drives on PQ. First of all, they
sients. designs (converters or rectifiers
offer built-in soft-start capabili-
ties. This means there will be no turn ac to dc and are the first
stage of the drive). There are two
Line-side measurements on ASDs major types of converter design.
Measurement Look for
Voltage waveform Voltage notching (SCR converters) SCR convertor with
Flat-topping Voltage Source Inverter/
Harmonic spectrum Harmonic orders and amplitudes, before and after filter
application
Variable Voltage Inverter
Displacement PF For PWM drives, DPF should remain high even at low speeds
(VSI/VVI) drives
(it will typically decrease slightly) Commonly called six-step drives,
Voltage unbalance Less than drive manufacturer specs, or current overload trips they use SCRs (Silicon -
can result. The drive may have a higher limit for unbalance
than the motor.
Controlled Rectifiers) in their
converter front-ends (the follow-
ing discussion applies to CSI,
Current Source Inverter drives,
which also use SCRs). VSI and
Induction CSI drive designs tended to be
Motor applied on larger drives (> 100
HP). SCR converters control the
M dc link voltage by switching on
(or gating) current flow for a
portion of the applied sine wave
Line and switching off at the zero-
Reactors
crossing points. Unlike diodes,
SCRs require control circuits for
gate firing.

Figure 1. Voltage Source Invertor (VSI) ASD.

From the Fluke Digital Library @ www.fluke.com/library


Diode convertor with If a 12-pulse converter were
Pulse Width Modulation used, the 11th and 13th harmon-
(PWM) drives ics will be generated instead of
the 5th and 6th and, very
The other and more common importantly, for the same load,
converter design uses diodes and the amplitude of the 11th and
is used in the PWM drive. The 13th would be considerably less
diodes require no switching con- than the 5th and 6th. Therefore,
trol circuitry. One of the main the THD would be less. The vast
trends in the industry has been majority of drives, however, are
the proliferation of PWM drives, six-pulse PWM style, which is
mainly due to the continued one reason we see so much 5th
development of fast-switching, harmonic on the system.
efficient IGBTs (Insulated Gate
Figure 2. Voltage notching. Bipolar Transistors) used in the Harmonics solutions
inverter section of the drive
(inverters turn dc to ac). For all There are a number of solutions
For the SCR converter, there practical purposes, PWM drives to mitigating drive-generated
are three main issues that affect are the industry standard. harmonics:
line-side PQ:
Harmonic trap filters (Figure 5)
Commutation notches. SCR These are typically LC networks
switching or commutation is
connected in parallel at the
such that there are brief
source of the harmonics (in other
moments when two phases
words, at the drive input). They
will both be ON. This causes
are tuned to just below the 5th
what is in effect a momentary
harmonic (typically 280 Hz) and
short circuit that tends to col-
will tend to sink both 5th and
lapse the line voltage. This
much of the 7th harmonic.
shows up as notches on the
Obviously, they must be sized to
voltage waveform. These
the harmonic-generating load.
notches cause both high V-
THD and transients. The Phase-shift transformers
solution is to place a reactor This can be as simple as a delta-
coil or isolation transformer in wye transformer feeding one
series with the drives front Figure 3. Typical ASD harmonic waveform. drive(s) and a delta-delta feeding
end to clean up both problems. another drive(s). There is a 30
Displacement Power Factor For the diode converter, the degree phase shift effect
declines as drive speed main PQ issue is harmonics. The between these two configura-
decreases. This is not as seri- actual harmonic orders being tions, which effectively results in
ous a problem as it sounds, generated depend on the number cancellation of harmonics at the
because the power require- of diodes in the front end. For closest upstream PCC (Point of
ment of the drive-motor-load three-phase conversion, a mini- Common Coupling). The cancella-
decreases even more. mum set of six diodes is required. tion effect is optimal when both
Harmonic currents, typically This six-pulse converter will loads are more or less equal.
the 5th and 7th, are generated generate 5th and 7th harmonics.
by VSI drives.

Figure 4. Pulse Width Modulated (PWM) ASD.

2 Fluke Corporation How adjustable speed drives affect power distribution


12-pulse converter Active PF correction
If the delta-wye/delta-delta are Another recent solution is for Line Load
packaged together (delta primary, manufacturers to offer converter
delta and wye secondary) and front ends using fast switching
each secondary feeds one of two technology that generates a mini-
paralleled six-pulse converters, a mum amount of harmonics and
12-pulse front-end is created has near unity power factor (both
with all the benefits mentioned Total PF and DPF).
above. 18-pulse designs are also There is room for discussion
available. Because of the extra on which approach to harmonic
cost, this type of solution tends to mitigation might prove most
only get used on high HP loads. effective and economical in a
particular situation. However,
Active filters
what is often overlooked by the
This relatively new technology is
end-user, and what should be
based on an elegant concept
clear from the information in this
using power electronics to solve
section, is that the total cost of a
the problems created by power
drive system should include both
electronics. It senses the instan-
the cost of the drive itself and the
taneous ac sine wave; it then
harmonic mitigation (whether
actively cancels the harmonics it
part of the drive or
detects by generating equal and
installed separately). Figure 5. Harmonic trap filter.
opposite polarity harmonics, thus
recreating the sine wave.
Commercial packages might pro-
vide voltage regulation as well.

Why True-rms
True-rms test tools are necessary for accurate measurements of
distorted waveforms. For more information, see the Fluke application
note Why True-rms, document number 1260729.

A comparison of average-responding and true-rms multimeters


Multimeter Reading
Waveform Description Average-sensing DMM True-rms DMM
Sine wave Correct Correct

Square wave (flat-top voltage) 10 % high Correct

Current to single phase diode rectifier 40 % low Correct

Current to 3 phase diode rectifier 5-30 % low Correct

3 Fluke Corporation How adjustable speed drives affect power distribution


Power system resonance
Hot vibes can result when harmonics and capacitors get together

Is it possible to install Power Displacement power Harmonics and


Factor Correction Capacitors and factor capacitors
have PF get worse? It certainly is,
and a starting place to under- Lower DPF is caused by motor Harmonics have had a dramatic
standing this puzzle lies in the loads which introduce the need impact on our approach to Power
distinction between Displacement for Reactive Power (Volt-Amp Factor correction. The motor and
PF (DPF) and Total Power Factor Reactive or VARs). The system capacitor loads described above
(PF). The penalty for not under- has to have the capacity, meas- are all linear and for all practical
standing the difference can be ured in Volt-Amps (VA) to supply purposes generate no harmonics.
blown capacitors and wasted both VARs and Watts. The more Non-linear loads such as ASDS,
investment. VARs needed, the larger the VA on the other hand, do generate
Total PF and Displacement PF requirement and the smaller the harmonic currents.
are the same in one basic sense: DPF. The cost of VARs is Take a plant which is step-by-
they are the ratio of Real Power accounted for in a power factor step putting adjustable speed
to Apparent Power, or Watts to penalty charge. Utilities often drives on its motor loads. ASDs
VA. DPF is the classic concept of levy additional charges for DPF generate significant harmonic
power factor. It can be considered below a certain level; the actual currents (5th and 7th on six-
as the power factor at the funda- number varies widely, but typical pulse converter drives). Suddenly
mental frequency. Total Power numbers are 0.90 to 0.95. the fuses on existing PF correc-
Factor, abbreviated to Power To reduce VARs caused by tion caps start blowing. Since
Factor (PF), now includes the motor loads, power factor correc- these are three-phase caps, only
effects of fundamental and of tion capacitors are installed. one of the three fuses might
harmonic currents (it is also Upstream system capacity, both blow. Now youve got unbalanced
referred to as True PF or in the plant and at the utility currents, possibly unbalanced
Distortion PF, Figure 7). It follows level, is released and available voltages. The electrician replaces
that with the presence of har- for other uses. (Figure 6) the fuses. They blow again. He
monics, PF is always lower than Historically, this has been the puts in larger fuses. Now the
DPF and is also a more accurate gist of the PF story: a relatively fuses survive, but the capacitor
description of total system effi- well-known problem with a rela- blows. He replaces the capacitor.
ciency than DPF alone. tively straightforward solution. Same thing happens. Whats
Strictly speaking, the term going on? Harmonics are higher
Power Factor refers to Total PF, frequency currents. The higher
but in practice can also be used the frequency, the lower the
to refer to DPF. Needless to say, impedance of a cap (XC = 1/2fC).
this introduces some confusion The cap acts like a sink for
into discussions of power factor. harmonic currents.
You have to be clear which one
youre talking about.

Before: PF = 42 % After: PF = 100 %


1.4 A

3.3 A

Reactive
Reactive
Active Active 360 VAR
360 VAR
165 Watts 165 Watts

Capacitor
60 F

1/6 HP Motor 1/6 HP Motor

Figure 6. Capacitor corrects Displacement Power Factor (DPF).

4 Fluke Corporation How adjustable speed drives affect power distribution


Power system resonance many times greater than the Imagine coming to work on a
exciting current. This so-called Monday and seeing the insulation
In a worst-case scenario, the on your cables melted off. How
tank circuit can severely dam-
inductive reactance (XL) of the can this happen over a weekend
age equipment, and it will also
transformer and the capacitive when there was hardly any load
cause a drop in power factor.
reactance (XC) of the PF correction on the system? Has Ohms Law
Perversely, this resonant condi-
cap form a parallel resonant been overruled? Not quite. Your
tion often appears only when the
circuit: XL = XC at a resonant power system just spent the
system is lightly loaded, because
frequency which is the same as weekend tanked out on the
the damping effect of resistive
or close to a harmonic frequency. Harmonics. It was quite a party,
loads is removed. In other words,
The harmonic current generated but now comes the clean-up.
we have what the audio buffs
by the load excites the circuit into
call a high Q circuit. (Figure 8)
oscillation. Currents then circulate Start with harmonics
within this circuit which are
mitigation
The correct solution path starts
with measuring and mitigating
the harmonics generated by the
A. System Diagram B. Equivalent Circuit drives. Harmonic trap filters
XS would generally be called for.
These trap filters are installed
locally on the line side of the
XT drive. Their effect is very much
XT
like the traditional PF correction
XC cap, in two senses: they reduce
XS DPF as well as PF, and also they
Harmonic
XC source localize the circulation of the
problem harmonics (generally the
5th). Harmonics mitigation and
traditional DPF correction should
Figure 8. Resonant circuit when XC = (XT + XS) be addressed as one systems
issue. In other words, manage
Total PF, not just DPF.

kvar
(nonwork producing)

VA

Harmonics
(nonwork
producing)

Fluke. Keeping your world


up and running.

Fluke Corporation
kW PO Box 9090, Everett, WA USA 98206
(work producing)
Fluke Europe B.V.
PO Box 1186, 5602 BD
Figure 7. Total Power Factor increases with harmonics. Eindhoven, The Netherlands
For more information call:
In the U.S.A. (800) 443-5853 or
Fax (425) 446-5116
In Europe/M-East/Africa (31 40) 2 675 200 or
Fax (31 40) 2 675 222
In Canada (800) 36-FLUKE or
Fax (905) 890-6866
From other countries +1 (425) 446-5500 or
Fax +1 (425) 446-5116
Web access: http://www.fluke.com
2004 Fluke Corporation. All rights reserved.
Printed in U.S.A. 10/2004 2403028 A-US-N Rev A
5 Fluke Corporation How adjustable speed drives affect power distribution

You might also like