You are on page 1of 14

Color profile: Generic CMYK printer profile

Composite Default screen

CHAPTER 7

SANITARY DRAINAGE

SECTION 701
GENERAL TABLE 702.1
ABOVE-GROUND DRAINAGE AND VENT PIPE
701.1 Scope. The provisions of this chapter shall govern the
materials, design, construction and installation of sanitary MATERIAL STANDARD
drainage systems. Acrylonitrile butadiene styrene ASTM D 2661; ASTM F 628;
701.2 Sewer required. Every building in which plumbing fix- (ABS) plastic pipe CSA B181.1
tures are installed and all premises having drainage piping shall Brass pipe ASTM B 43
be connected to a public sewer, where available, or an approved
private sewage disposal system in accordance with the Interna- ASTM A 74; ASTM A 888;
Cast-iron pipe
CISPI 301
tional Private Sewage Disposal Code.
Coextruded composite ABS
701.3 Separate sewer connection. Every building having DWV schedule 40 IPS pipe ASTM F 1488
plumbing fixtures installed and intended for human habitation, (solid)
occupancy or use on premises abutting on a street, alley or
easement in which there is a public sewer shall have a separate Coextruded composite ABS
connection with the sewer. Where located on the same lot, mul- DWV schedule 40 IPS pipe ASTM F 1488
tiple buildings shall not be prohibited from connecting to a (cellular core)
common building sewer that connects to the public sewer. Coextruded composite PVC
DWV schedule 40 IPS pipe ASTM F 1488
701.4 Sewage treatment. Sewage or other waste from a
(solid)
plumbing system that is deleterious to surface or subsurface
waters shall not be discharged into the ground or into any Coextruded composite PVC
waterway unless it has first been rendered innocuous through DWV schedule 40 IPS pipe ASTM F 891; ASTM F 1488
subjection to an approved form of treatment. (cellular core)

701.5 Damage to drainage system or public sewer. Wastes Coextruded composite PVC
ASTM F 1488
detrimental to the public sewer system or to the functioning of IPS-DR, PS140, PS200 DWV
the sewage-treatment plant shall be treated and disposed of in Copper or copper-alloy pipe ASTM B 42; ASTM B 302
accordance with Section 1003 as directed by the code official.
Copper or copper-alloy tubing ASTM B 75; ASTM B 88;
701.6 Tests. The sanitary drainage system shall be tested in (Type K, L, M or DWV) ASTM B 251; ASTM B 306
accordance with Section 312.
Galvanized steel pipe ASTM A 53
701.7 Connections. Direct connection of a steam exhaust,
blowoff or drip pipe shall not be made with the building drain- Glass pipe ASTM C 1053
age system. Wastewater when discharged into the building Polyolefin pipe CSA B181.3
drainage system shall be at a temperature not higher than 140F
Polyvinyl chloride (PVC) ASTM D 2665; ASTM D 2949;
(60C). When higher temperatures exist, approved cooling plastic pipe (Type DWV) ASTM F 1488; CSA B181.2
methods shall be provided.
Stainless steel drainage
701.8 Engineered systems. Engineered sanitary drainage sys- ASME A112.3.1
systems, Types 304 and 316L
tems shall conform to the provisions of Sections 105.4 and 714.
701.9 Drainage piping in food service areas. (Section
deleted) 702.4 Fittings. Pipe fittings shall be approved for installation
with the piping material installed and shall conform to the
respective pipe standards or one of the standards listed in Table
SECTION 702 702.4.
MATERIALS
702.5 Chemical waste system. A chemical waste system shall
702.1 Above-ground sanitary drainage and vent pipe. be completely separated from the sanitary drainage system.
Above-ground soil, waste and vent pipe shall conform to one of The chemical waste shall be treated in accordance with Section
the standards listed in Table 702.1. 803.2 before discharging to the sanitary drainage system. Sep-
702.2 Underground building sanitary drainage and vent arate drainage systems for chemical wastes and vent pipes shall
pipe. Underground building sanitary drainage and vent pipe be of an approved material that is resistant to corrosion and
shall conform to one of the standards listed in Table 702.2. degradation for the concentrations of chemicals involved.
702.3 Building sewer pipe. Building sewer pipe shall conform 702.6 Lead bends and traps. Lead bends and traps shall not be
to one of the standards listed in Table 702.3. less than 0.125 inch (3.2 mm) wall thickness.

2006 VIRGINIA PLUMBING CODE 7-1

07_Va_Plumb_2006.pS 1
M:\data\CODES\STATE CODES\Virginia\2006\Plumbing Code\Final VP\07_Va_Plumb_2006.vp
Thursday, February 14, 2008 9:22:08 AM
Color profile: Generic CMYK printer profile
Composite Default screen

SANITARY DRAINAGE

TABLE 702.2 TABLE 702.3


UNDERGROUND BUILDING DRAINAGE AND VENT PIPE BUILDING SEWER PIPE
MATERIAL STANDARD MATERIAL STANDARD

Acrylonitrile butadiene styrene ASTM D 2661; ASTM F 628; Acrylonitrile butadiene styrene ASTM D 2661; ASTM D 2751;
(ABS) plastic pipe CSA B181.1 (ABS) plastic pipe ASTM F 628
Asbestos-cement pipe ASTM C 428 Asbestos-cement pipe ASTM C 428
ASTM A 74; ASTM A 888; ASTM A 74; ASTM A 888;
Cast-iron pipe Cast-iron pipe
CISPI 301 CISPI 301
Coextruded composite ABS Coextruded composite ABS
DWV schedule 40 IPS pipe ASTM F 1488 DWV schedule 40 IPS pipe ASTM F 1488
(solid) (solid)
Coextruded composite ABS Coextruded composite ABS
DWV schedule 40 IPS pipe ASTM F 1488 DWV schedule 40 IPS pipe ASTM F 1488
(cellular core) (cellular core)
Coextruded composite PVC Coextruded composite PVC
DWV schedule 40 IPS pipe ASTM F 1488 DWV schedule 40 IPS pipe ASTM F 1488
(solid) (solid)
Coextruded composite PVC Coextruded composite PVC
DWV schedule 40 IPS pipe ASTM F 891; ASTM F 1488 DWV schedule 40 IPS pipe ASTM F 891; ASTM F 1488
(cellular core) (cellular core)
Coextruded composite PVC Coextruded composite
IPS-DR, PS140, PS200 ASTM F 1488 PVC IPS-DR, PS140, ASTM F 1488
DWV PS200, DWV
Copper or copper-alloy tubing ASTM B 75; ASTM B 88; Coextruded composite ABS
(Type K, L, M or DWV) ASTM B 251; ASTM B 306 sewer and drain DR-PS in
ASTM F 1488
PS35, PS50, PS100, PS140,
Polyolefin pipe ASTM F 1412; CSA B181.3 PS200
Polyvinyl chloride (PVC) ASTM D 2665; ASTM D 2949; Coextruded composite PVC
plastic pipe (Type DWV) CSA B181.2 sewer and drain DR-PS in
ASTM F 1488
Stainless steel drainage PS35, PS50, PS100, PS140,
ASME A112.3.1 PS200
systems, Type 316L
Coextruded PVC sewer and
drain PS25, PS50, PS100 ASTM F 891
(cellular core)
ASTM C14; ASTM C76; CSA
Concrete pipe
A257.1M; CSA A257.2M
Copper or copper-alloy tubing ASTM B 75; ASTM B 88; ASTM
(Type K or L) B 251
Polyethylene (PE) plastic pipe
ASTM F 714
(SDR-PR)
Polyvinyl chloride (PVC)
ASTM D 2665; ASTM D 2949;
plastic pipe (Type DWV,
ASTM D 3034; CSA B182.2;
SDR26, SDR35, SDR41,
CSA B182.4
PS50 or PS100)
Stainless steel drainage
ASME A112.3.1
systems, Types 304 and 316L
Vitrified clay pipe ASTM C 4; ASTM C 700

7-2 2006 VIRGINIA PLUMBING CODE

07_Va_Plumb_2006.pS 2
M:\data\CODES\STATE CODES\Virginia\2006\Plumbing Code\Final VP\07_Va_Plumb_2006.vp
Thursday, February 14, 2008 9:22:08 AM
Color profile: Generic CMYK printer profile
Composite Default screen

SANITARY DRAINAGE

TABLE 702.4 703.4 Existing building sewers and drains. Existing building
PIPE FITTINGS
sewers and drains shall connect with new building sewer and
MATERIAL STANDARD drainage systems only where found by examination and test to
Acrylonitrile butadiene ASTM D 2661; ASTM D 3311; conform to the new system in quality of material. The code offi-
styrene (ABS) plastic pipe CSA B181.1 cial shall notify the owner to make the changes necessary to
conform to this code.
ASME B 16.4; ASME B 16.12;
Cast iron ASTM A 74; ASTM A 888; 703.5 Cleanouts on building sewers. Cleanouts on building
CISPI 301 sewers shall be located as set forth in Section 708.
Coextruded composite ABS 703.6 Nonmetallic building sewer location. Nonmetallic san-
ASTM D 2661; ASTM D 3311; itary sewer piping installed and located within 6 feet (1829
DWV schedule 40 IPS pipe
ASTM F 628
(solid or cellular core) mm) of finished grade that discharges to public systems shall
be locatable. An insulated copper tracer wire, 18 AWG mini-
Coextruded composite PVC
DWV schedule 40 IPS-DR, ASTM D 2665; ASTM D 3311; mum in size and suitable for direct burial or an equivalent prod-
PS140, PS200 (solid or ASTM F 891 uct, shall be utilized. The wire shall be installed in the same
cellular core) trench as the sewer within 12 inches (305 mm) of the pipe and
shall be installed to within 5 feet (1524 mm) of the building
Coextruded composite ABS wall where the building sewer intersects with the public sys-
sewer and drain DR-PS in tem. The ends of the wire shall terminate above grade in an
ASTM D 2751
PS35, PS50, PS100, PS140,
PS200
accessible location that is not subject to physical damage, such
as with a cleanout or at the building wall. Only one accessible
Coextruded composite PVC location is required to be provided for the wire terminations on
sewer and drain DR-PS in either end of each sewer installation.
ASTM D 3034
PS35, PS50, PS100, PS140,
PS200
ASME B 16.15; ASME B 16.18; SECTION 704
Copper or copper alloy ASME B 16.22; ASME B 16.23; DRAINAGE PIPING INSTALLATION
ASME B 16.26; ASME B 16.29
704.1 Slope of horizontal drainage piping. Horizontal drain-
Glass ASTM C 1053 age piping shall be installed in uniform alignment at uniform
Gray iron and ductile iron AWWA C 110
slopes. The minimum slope of a horizontal drainage pipe shall
be in accordance with Table 704.1.
Malleable iron ASME B 16.3
TABLE 704.1
Polyolefin ASTM F 1412; CSA B181.3 SLOPE OF HORIZONTAL DRAINAGE PIPE
SIZE MINIMUM SLOPE
Polyvinyl chloride (PVC) ASTM D 2665; ASTM D 3311; (inches) (inch per foot)
plastic ASTM F 1866
21/2 or less 1/
4
Stainless steel drainage
3 to 6 1/
systems, Types 304 and ASME A 112.3.1 8
316L 8 or larger 1/
16
ASME B 16.9; ASME B 16.11; For SI: 1 inch = 25.4 mm, 1 inch per foot = 83.3 mm/m.
Steel
ASME B 16.28
704.2 Change in size. The size of the drainage piping shall not
be reduced in size in the direction of the flow. A 4-inch by
SECTION 703 3-inch (102 mm by 76 mm) water closet connection shall not be
BUILDING SEWER considered as a reduction in size.
703.1 Building sewer pipe near the water service. Where the 704.3 Connections to offsets and bases of stacks. Horizontal
building sewer is installed within 5 feet (1524 mm) of the water branches shall connect to the bases of stacks at a point located
service, the installation shall comply with the provisions of not less than 10 times the diameter of the drainage stack down-
Section 603.2. stream from the stack. Except as prohibited by Section 711.2,
horizontal branches shall connect to horizontal stack offsets at
703.2 Drainage pipe in filled ground. Where a building sewer
a point located not less than 10 times the diameter of the drain-
or building drain is installed on filled or unstable ground, the
age stack downstream from the upper stack.
drainage pipe shall conform to one of the standards for ABS
plastic pipe, cast-iron pipe, copper or copper-alloy tubing, or 704.4 Future fixtures. Drainage piping for future fixtures
PVC plastic pipe listed in Table 702.3. shall terminate with an approved cap or plug.
703.3 Sanitary and storm sewers. Where separate systems of 704.5 Dead ends. In the installation or removal of any part of a
sanitary drainage and storm drainage are installed in the same drainage system, dead ends shall be prohibited. Cleanout
property, the sanitary and storm building sewers or drains shall extensions and approved future fixture drainage piping shall
be permitted to be laid side by side in one trench. not be considered as dead ends.

2006 VIRGINIA PLUMBING CODE 7-3

07_Va_Plumb_2006.pS 3
M:\data\CODES\STATE CODES\Virginia\2006\Plumbing Code\Final VP\07_Va_Plumb_2006.vp
Thursday, February 14, 2008 9:22:08 AM
Color profile: Generic CMYK printer profile
Composite Default screen

SANITARY DRAINAGE

SECTION 705 705.5.2 Compression gasket joints. Compression gaskets


JOINTS for hub and spigot pipe and fittings shall conform to ASTM
705.1 General. This section contains provisions applicable to C 564 and shall be tested to ASTM C 1563. Gaskets shall be
joints specific to sanitary drainage piping. compressed when the pipe is fully inserted.

705.2 ABS plastic. Joints between ABS plastic pipe or fittings 705.5.3 Mechanical joint coupling. Mechanical joint cou-
shall comply with Sections 705.2.1 through 705.2.3. plings for hubless pipe and fittings shall comply with CISPI
310, ASTM C 1277 or ASTM C 1540. The elastomeric seal-
705.2.1 Mechanical joints. Mechanical joints on drainage ing sleeve shall conform to ASTM C 564 or CSA B602 and
pipes shall be made with an elastomeric seal conforming to shall be provided with a center stop. Mechanical joint cou-
ASTM C 1173, ASTM D 3212 or CSA B602. Mechanical plings shall be installed in accordance with the manufac-
joints shall be installed only in underground systems unless turers installation instructions.
otherwise approved. Joints shall be installed in accordance
with the manufacturers instructions. 705.6 Concrete joints. Joints between concrete pipe and fit-
tings shall be made with an elastomeric seal conforming to
705.2.2 Solvent cementing. Joint surfaces shall be clean ASTM C 443, ASTM C 1173, CSA A257.3M or CSA B602.
and free from moisture. Solvent cement that conforms to
ASTM D 2235 or CSA B181.1 shall be applied to all joint 705.7 Coextruded composite ABS pipe, joints. Joints
surfaces. The joint shall be made while the cement is wet. between coextruded composite pipe with an ABS outer layer or
Joints shall be made in accordance with ASTM D 2235, ABS fittings shall comply with Sections 705.7.1 and 705.7.2.
ASTM D 2661, ASTM F 628 or CSA B181.1. Sol-
vent-cement joints shall be permitted above or below 705.7.1 Mechanical joints. Mechanical joints on drainage
ground. pipe shall be made with an elastomeric seal conforming to
ASTM C1173, ASTM D 3212 or CSA B602. Mechanical
705.2.3 Threaded joints. Threads shall conform to ASME joints shall not be installed in above-ground systems, unless
B1.20.1. Schedule 80 or heavier pipe shall be permitted to otherwise approved. Joints shall be installed in accordance
be threaded with dies specifically designed for plastic pipe. with the manufacturers instructions.
Approved thread lubricant or tape shall be applied on the
male threads only. 705.7.2 Solvent cementing. Joint surfaces shall be clean
and free from moisture. Solvent cement that conforms to
705.3 Asbestos cement. Joints between asbestos-cement pipe ASTM D 2235 or CSA B181.1 shall be applied to all joint
or fittings shall be made with a sleeve coupling of the same surfaces. The joint shall be made while the cement is wet.
composition as the pipe, sealed with an elastomeric ring con- Joints shall be made in accordance with ASTM D 2235,
forming to ASTM D 1869. ASTM D 2661, ASTM F 628 or CSA B181.1. Sol-
705.4 Brass. Joints between brass pipe or fittings shall comply vent-cement joints shall be permitted above or below
with Sections 705.4.1 through 705.4.4. ground.
705.4.1 Brazed joints. All joint surfaces shall be cleaned. 705.8 Coextruded composite PVC pipe. Joints between
An approved flux shall be applied where required. The joint coextruded composite pipe with a PVC outer layer or PVC fit-
shall be brazed with a filler metal conforming to AWS A5.8. tings shall comply with Sections 705.8.1 and 705.8.2.
705.4.2 Mechanical joints. Mechanical joints shall be 705.8.1 Mechanical joints. Mechanical joints on drainage
installed in accordance with the manufacturers instruc- pipe shall be made with an elastomeric seal conforming to
tions. ASTM D 3212. Mechanical joints shall not be installed in
705.4.3 Threaded joints. Threads shall conform to ASME above-ground systems, unless otherwise approved. Joints
B1.20.1. Pipe-joint compound or tape shall be applied on shall be installed in accordance with the manufacturers
the male threads only. instructions.

705.4.4 Welded joints. All joint surfaces shall be cleaned. 705.8.2 Solvent cementing. Joint surfaces shall be clean
The joint shall be welded with an approved filler metal. and free from moisture. A purple primer that conforms to
ASTM F 656 shall be applied. Solvent cement not purple in
705.5 Cast iron. Joints between cast-iron pipe or fittings shall color and conforming to ASTM D 2564, CSA B137.3, CSA
comply with Sections 705.5.1 through 705.5.3. B181.2 or CSA B182.1 shall be applied to all joint surfaces.
705.5.1 Caulked joints. Joints for hub and spigot pipe shall The joint shall be made while the cement is wet and shall be
be firmly packed with oakum or hemp. Molten lead shall be in accordance with ASTM D 2855. Solvent-cement joints
poured in one operation to a depth of not less than 1 inch (25 shall be permitted above or below ground.
mm). The lead shall not recede more than 0.125 inch (3.2 705.9 Copper pipe. Joints between copper or copper-alloy
mm) below the rim of the hub and shall be caulked tight. pipe or fittings shall comply with Sections 705.9.1 through
Paint, varnish or other coatings shall not be permitted on the 705.9.5.
jointing material until after the joint has been tested and
approved. Lead shall be run in one pouring and shall be 705.9.1 Brazed joints. All joint surfaces shall be cleaned.
caulked tight. Acid-resistant rope and acidproof cement An approved flux shall be applied where required. The joint
shall be permitted. shall be brazed with a filler metal conforming to AWS A5.8.

7-4 2006 VIRGINIA PLUMBING CODE

07_Va_Plumb_2006.pS 4
M:\data\CODES\STATE CODES\Virginia\2006\Plumbing Code\Final VP\07_Va_Plumb_2006.vp
Thursday, February 14, 2008 9:22:09 AM
Color profile: Generic CMYK printer profile
Composite Default screen

SANITARY DRAINAGE

705.9.2 Mechanical joints. Mechanical joints shall be joint shall be at least as thick as the lead being joined. The
installed in accordance with the manufacturers instruc- filler metal shall be of the same material as the pipe.
tions.
705.13.2 Wiped. Joints shall be fully wiped, with an
705.9.3 Soldered joints. Solder joints shall be made in exposed surface on each side of the joint not less than 0.75
accordance with the methods of ASTM B 828. All cut tube inch (19.1 mm). The joint shall be at least 0.325 inch (9.5
ends shall be reamed to the full inside diameter of the tube mm) thick at the thickest point.
end. All joint surfaces shall be cleaned. A flux conforming
to ASTM B 813 shall be applied. The joint shall be soldered 705.14 PVC plastic. Joints between PVC plastic pipe or fit-
with a solder conforming to ASTM B 32. tings shall comply with Sections 705.14.1 through 705.14.3.
705.9.4 Threaded joints. Threads shall conform to ASME 705.14.1 Mechanical joints. Mechanical joints on drainage
B1.20.1. Pipe-joint compound or tape shall be applied on pipe shall be made with an elastomeric seal conforming to
the male threads only. ASTM C 1173, ASTM D 3212 or CSA B602. Mechanical
705.9.5 Welded joints. All joint surfaces shall be cleaned. joints shall not be installed in above-ground systems, unless
The joint shall be welded with an approved filler metal. otherwise approved. Joints shall be installed in accordance
with the manufacturers instructions.
705.10 Copper tubing. Joints between copper or copper-alloy
tubing or fittings shall comply with Sections 705.10.1 through 705.14.2 Solvent cementing. Joint surfaces shall be clean
705.10.3. and free from moisture. A purple primer that conforms to
ASTM F 656 shall be applied. Solvent cement not purple in
705.10.1 Brazed joints. All joint surfaces shall be cleaned. color and conforming to ASTM D 2564, CSA B137.3, CSA
An approved flux shall be applied where required. The joint B181.2 or CSA B182.1 shall be applied to all joint surfaces.
shall be brazed with a filler metal conforming to AWS A5.8. The joint shall be made while the cement is wet and shall be
705.10.2 Mechanical joints. Mechanical joints shall be in accordance with ASTM D 2855. Solvent-cement joints
installed in accordance with the manufacturers instruc- shall be permitted above or below ground.
tions.
705.14.3 Threaded joints. Threads shall conform to
705.10.3 Soldered joints. Solder joints shall be made in ASME B1.20.1. Schedule 80 or heavier pipe shall be per-
accordance with the methods of ASTM B 828. All cut tube mitted to be threaded with dies specifically designed for
ends shall be reamed to the full inside diameter of the tube plastic pipe. Approved thread lubricant or tape shall be
end. All joint surfaces shall be cleaned. A flux conforming applied on the male threads only.
to ASTM B 813 shall be applied. The joint shall be soldered
with a solder conforming to ASTM B 32. 705.15 Vitrified clay. Joints between vitrified clay pipe or fit-
tings shall be made with an elastomeric seal conforming to
705.11 Borosilicate glass joints. Glass-to-glass connections ASTM C 425, ASTM C 1173 or CSA B602.
shall be made with a bolted compression-type stainless steel
(300 series) coupling with contoured acid-resistant elastomeric 705.16 Polyethylene plastic pipe. Joints between polyethyl-
compression ring and a fluorocarbon polymer inner seal ring; ene plastic pipe and fittings shall be underground and shall
or with caulked joints in accordance with Section 705.11.1. comply with Section 705.16.1 or 705.16.2.
705.11.1 Caulked joints. Every lead-caulked joint for hub 705.16.1 Heat-fusion joints. Joint surfaces shall be clean
and spigot soil pipe shall be firmly packed with oakum or and free from moisture. All joint surfaces shall be cut,
hemp and filled with molten lead not less than 1 inch (25 heated to melting temperature and joined using tools specif-
mm) deep and not to extend more than 0.125 inch (3.2 mm) ically designed for the operation. Joints shall be undisturbed
below the rim of the hub. Paint, varnish or other coatings until cool. Joints shall be made in accordance with ASTM D
shall not be permitted on the jointing material until after the 2657 and the manufacturers instructions.
joint has been tested and approved. Lead shall be run in one
pouring and shall be caulked tight. Acid-resistant rope and 705.16.2 Mechanical joints. Mechanical joints in drainage
acidproof cement shall be permitted. piping shall be made with an elastomeric seal conforming to
ASTM C 1173, ASTM D 3212 or CSA B602. Mechanical
705.12 Steel. Joints between galvanized steel pipe or fittings joints shall be installed in accordance with the manufac-
shall comply with Sections 705.12.1 and 705.12.2. turers instructions.
705.12.1 Threaded joints. Threads shall conform to
ASME B1.20.1. Pipe-joint compound or tape shall be 705.17 Polyolefin plastic. Joints between polyolefin plastic
applied on the male threads only. pipe and fittings shall comply with Sections 705.17.1 and
705.17.2.
705.12.2 Mechanical joints. Joints shall be made with an
approved elastomeric seal. Mechanical joints shall be 705.17.1 Heat-fusion joints. Heat-fusion joints for
installed in accordance with the manufacturers instructions. polyolefin pipe and tubing joints shall be installed with
socket-type heat-fused polyolefin fittings or electrofusion
705.13 Lead. Joints between lead pipe or fittings shall comply polyolefin fittings. Joint surfaces shall be clean and free
with Sections 705.13.1 and 705.13.2. from moisture. The joint shall be undisturbed until cool.
705.13.1 Burned. Burned joints shall be uniformly fused Joints shall be made in accordance with ASTM F 1412 or
together into one continuous piece. The thickness of the CSA B181.3.

2006 VIRGINIA PLUMBING CODE 7-5

07_Va_Plumb_2006.pS 5
M:\data\CODES\STATE CODES\Virginia\2006\Plumbing Code\Final VP\07_Va_Plumb_2006.vp
Thursday, February 14, 2008 9:22:09 AM
Color profile: Generic CMYK printer profile
Composite Default screen

SANITARY DRAINAGE

705.17.2 Mechanical and compression sleeve joints. TABLE 705.20


CAULKING FERRULE SPECIFICATIONS
Mechanical and compression sleeve joints shall be installed
in accordance with the manufacturers instructions. PIPE SIZES INSIDE DIAMETER LENGTH
(inches) (inches) (inches) MINIMUM WEIGHT EACH
705.18 Joints between different materials. Joints between
2 21 / 4 41 / 2 1 pound
different piping materials shall be made with a mechanical
joint of the compression or mechanical-sealing type conform- 3 3 1/ 4 41 / 2 1 pound 12 ounces
ing to ASTM C 1173, ASTM C 1460 or ASTM C 1461. Con- 4 4 1/ 4 41 / 2 2 pounds 8 ounces
nectors and adapters shall be approved for the application and
For SI: 1 inch = 25.4 mm, 1 ounce = 28.35 g, 1 pound = 0.454 kg.
such joints shall have an elastomeric seal conforming to ASTM
C 425, ASTM C 443, ASTM C 564, ASTM C 1440, ASTM D
1869, ASTM F 477, CSA A257.3M or CSA B602, or as 705.21 Soldering bushings. Soldering bushings shall be of red
required in Sections 705.18.1 through 705.18.7. Joints brass and shall be in accordance with Table 705.21.
between glass pipe and other types of materials shall be made TABLE 705.21
with adapters having a TFE seal. Joints shall be installed in SOLDERING BUSHING SPECIFICATIONS
accordance with the manufacturers instructions. PIPE SIZES MINIMUM WEIGHT
(inches) EACH
705.18.1 Copper or copper-alloy tubing to cast-iron hub
pipe. Joints between copper or copper-alloy tubing and 11 / 4 6 ounces
cast-iron hub pipe shall be made with a brass ferrule or com- 1 1/
2 8 ounces
pression joint. The copper or copper-alloy tubing shall be 2 14 ounces
soldered to the ferrule in an approved manner, and the fer-
1/
rule shall be joined to the cast-iron hub by a caulked joint or 2 2 1 pound 6 ounces
a mechanical compression joint. 3 2 pounds
705.18.2 Copper or copper-alloy tubing to galvanized 4 3 pounds 8 ounces
steel pipe. Joints between copper or copper-alloy tubing For SI: 1 inch = 25.4 mm, 1 ounce = 28.35 g, 1 pound = 0.454 kg.
and galvanized steel pipe shall be made with a brass con-
verter fitting or dielectric fitting. The copper tubing shall be
705.22 Stainless steel drainage systems. O-ring joints for
soldered to the fitting in an approved manner, and the fitting
stainless steel drainage systems shall be made with an
shall be screwed to the threaded pipe.
approved elastomeric seal.
705.18.3 Cast-iron pipe to galvanized steel or brass pipe.
Joints between cast-iron and galvanized steel or brass pipe
shall be made by either caulked or threaded joints or with an SECTION 706
approved adapter fitting. CONNECTIONS BETWEEN DRAINAGE
705.18.4 Plastic pipe or tubing to other piping material. PIPING AND FITTINGS
Joints between different types of plastic pipe or between 706.1 Connections and changes in direction. All connections
plastic pipe and other piping material shall be made with an and changes in direction of the sanitary drainage system shall
approved adapter fitting. Joints between plastic pipe and be made with approved drainage fittings. Connections between
cast-iron hub pipe shall be made by a caulked joint or a drainage piping and fixtures shall conform to Section 405.
mechanical compression joint. 706.2 Obstructions. The fittings shall not have ledges, shoul-
705.18.5 Lead pipe to other piping material. Joints ders or reductions capable of retarding or obstructing flow in
between lead pipe and other piping material shall be made the piping. Threaded drainage pipe fittings shall be of the
by a wiped joint to a caulking ferrule, soldering nipple, or recessed drainage type.
bushing or shall be made with an approved adapter fitting. 706.3 Installation of fittings. Fittings shall be installed to
705.18.6 Borosilicate glass to other materials. Joints guide sewage and waste in the direction of flow. Change in
between glass pipe and other types of materials shall be direction shall be made by fittings installed in accordance with
made with adapters having a TFE seal and shall be installed Table 706.3. Change in direction by combination fittings, side
in accordance with the manufacturers instructions. inlets or increasers shall be installed in accordance with Table
706.3 based on the pattern of flow created by the fitting. Dou-
705.18.7 Stainless steel drainage systems to other mate-
ble sanitary tee patterns shall not receive the discharge of
rials. Joints between stainless steel drainage systems and
back-to-back water closets and fixtures or appliances with
other piping materials shall be made with approved
pumping action discharge.
mechanical couplings.
Exception: Back-to-back water closet connections to dou-
705.19 Drainage slip joints. Slip joints shall comply with Sec-
ble sanitary tees shall be permitted where the horizontal
tion 405.8.
developed length between the outlet of the water closet and
705.20 Caulking ferrules. Ferrules shall be of red brass and the connection to the double sanitary tee pattern is 18 inches
shall be in accordance with Table 705.20. (457 mm) or greater.

7-6 2006 VIRGINIA PLUMBING CODE

07_Va_Plumb_2006.pS 6
M:\data\CODES\STATE CODES\Virginia\2006\Plumbing Code\Final VP\07_Va_Plumb_2006.vp
Thursday, February 14, 2008 9:22:09 AM
Color profile: Generic CMYK printer profile
Composite Default screen

SANITARY DRAINAGE

TABLE 706.3 shall conform to the requirements of Section 702.4. Plugs shall
FITTINGS FOR CHANGE IN DIRECTION have raised square or countersunk square heads. Countersunk
CHANGE IN DIRECTION heads shall be installed where raised heads are a trip hazard.
TYPE OF FITTING Horizontal to Vertical to Horizontal to
Cleanout plugs with borosilicate glass systems shall be of
PATTERN vertical horizontal horizontal borosilicate glass.
Sixteenth bend X X X 708.3 Where required. Cleanouts shall be located in accor-
dance with Sections 708.3.1 through 708.3.6.
Eighth bend X X X
708.3.1 Horizontal drains within buildings. All horizon-
Sixth bend X X X
tal drains shall be provided with cleanouts located not more
Quarter bend X Xa Xa than 100 feet (30 480 mm) apart.
Short sweep X Xa,b Xa 708.3.2 Building sewers. Building sewers shall be pro-
vided with cleanouts located not more than 100 feet (30 480
Long sweep X X X mm) apart measured from the upstream entrance of the
Sanitary tee Xc cleanout. For building sewers 8 inches (203 mm) and larger,
manholes shall be provided and located not more than 200
Wye X X X feet (60 960 mm) from the junction of the building drain and
Combination wye building sewer, at each change in direction and at intervals
X X X of not more than 400 feet (122 m) apart. Manholes and man-
and eighth bend
hole covers shall be of an approved type.
For SI: 1 inch = 25.4 mm.
a. The fittings shall only be permitted for a 2-inch or smaller fixture drain. 708.3.3 Changes of direction. Cleanouts shall be installed
b. Three inches or larger. at each change of direction greater than 45 degrees (0.79
c. For a limitation on double sanitary tees, see Section 706.3.
rad) in the building sewer, building drain and horizontal
706.4 Heel- or side-inlet quarter bends. Heel-inlet quarter waste or soil lines. Where more than one change of direction
bends shall be an acceptable means of connection, except occurs in a run of piping, only one cleanout shall be required
where the quarter bend serves a water closet. A low-heel inlet for each 40 feet (12 192 mm) of developed length of the
shall not be used as a wet-vented connection. Side-inlet quarter drainage piping.
bends shall be an acceptable means of connection for drainage,
wet venting and stack venting arrangements. 708.3.4 Base of stack. A cleanout shall be provided at the
base of each waste or soil stack.
708.3.5 Building drain and building sewer junction.
SECTION 707 There shall be a cleanout near the junction of the building
PROHIBITED JOINTS AND CONNECTIONS drain and the building sewer. The cleanout shall be either
707.1 Prohibited joints. The following types of joints and inside or outside the building wall and shall be brought up to
connections shall be prohibited: the finished ground level or to the basement floor level. An
approved two-way cleanout is allowed to be used at this
1. Cement or concrete joints.
location to serve as a required cleanout for both the building
2. Mastic or hot-pour bituminous joints. drain and building sewer. The cleanout at the junction of the
3. Joints made with fittings not approved for the specific building drain and building sewer shall not be required if the
installation. cleanout on a 3-inch (76 mm) or larger diameter soil stack is
located within a developed length of 10 feet (3048 mm) of
4. Joints between different diameter pipes made with the building drain and building sewer connection. The mini-
elastomeric rolling O-rings. mum size of the cleanout at the junction of the building drain
5. Solvent-cement joints between different types of plastic and building sewer shall comply with Section 708.7.
pipe.
708.3.6 Manholes. Manholes serving a building drain shall
6. Saddle-type fittings. have secured gas-tight covers and shall be located in accor-
dance with Section 708.3.2.
SECTION 708 708.4 Concealed piping. Cleanouts on concealed piping or
CLEANOUTS piping under a floor slab or in a crawl space of less than 24
inches (610 mm) in height or a plenum shall be extended
708.1 Scope. This section shall govern the size, location, through and terminate flush with the finished wall, floor or
installation and maintenance of drainage pipe cleanouts. ground surface or shall be extended to the outside of the build-
708.2 Cleanout plugs. Cleanout plugs shall be brass or plastic, ing. Cleanout plugs shall not be covered with cement, plaster or
or other approved materials. Brass cleanout plugs shall be uti- any other permanent finish material. Where it is necessary to
lized with metallic drain, waste and vent piping only, and shall conceal a cleanout or to terminate a cleanout in an area subject
conform to ASTM A 74, ASME A112.3.1 or ASME to vehicular traffic, the covering plate, access door or cleanout
A112.36.2M. Cleanouts with plate-style access covers shall be shall be of an approved type designed and installed for this pur-
fitted with corrosion-resisting fasteners. Plastic cleanout plugs pose.

2006 VIRGINIA PLUMBING CODE 7-7

07_Va_Plumb_2006.pS 7
M:\data\CODES\STATE CODES\Virginia\2006\Plumbing Code\Final VP\07_Va_Plumb_2006.vp
Thursday, February 14, 2008 9:22:10 AM
Color profile: Generic CMYK printer profile
Composite Default screen

SANITARY DRAINAGE

708.5 Opening direction. Every cleanout shall be installed to TABLE 709.2


DRAINAGE FIXTURE UNITS FOR FIXTURE DRAINS OR TRAPS
open to allow cleaning in the direction of the flow of the drain-
age pipe or at right angles thereto. FIXTURE DRAIN OR TRAP SIZE
(inches) DRAINAGE FIXTURE UNIT VALUE
708.6 Prohibited installation. Cleanout openings shall not be
11 / 4 1
utilized for the installation of new fixtures, except where
approved and where another cleanout of equal access and 1 1/ 2 2
capacity is provided. 2 3
708.7 Minimum size. Cleanouts shall be the same nominal 2 1/
2 4
size as the pipe they serve up to 4 inches (102 mm). For pipes
larger than 4 inches (102 mm) nominal size, the minimum size 3 5
of the cleanout shall be 4 inches (102 mm). 4 6
Exceptions: For SI: 1 inch = 25.4 mm.
1. P trap connections with slip joints or ground joint
connections, or stack cleanouts that are not more than
SECTION 710
one pipe diameter smaller than the drain served, shall
DRAINAGE SYSTEM SIZING
be permitted.
710.1 Maximum fixture unit load. The maximum number of
2. Cast-iron cleanout sizing shall be in accordance with drainage fixture units connected to a given size of building
referenced standards in Table 702.4, ASTM A 74 for sewer, building drain or horizontal branch of the building drain
hub and spigot fittings or ASTM A 888 or CISPI 301 shall be determined using Table 710.1(1). The maximum num-
for hubless fittings. ber of drainage fixture units connected to a given size of hori-
708.8 Clearances. Cleanouts on 6-inch (153 mm) and smaller zontal branch or vertical soil or waste stack shall be determined
pipes shall be provided with a clearance of not less than 18 using Table 710.1(2).
inches (457 mm) for rodding. Cleanouts on 8-inch (203 mm) 710.1.1 Horizontal stack offsets. Horizontal stack offsets
and larger pipes shall be provided with a clearance of not less shall be sized as required for building drains in accordance
than 36 inches (914 mm) for rodding. with Table 710.1(1), except as required by Section 711.4.
708.9 Access. Access shall be provided to all cleanouts. 710.1.2 Vertical stack offsets. Vertical stack offsets shall
be sized as required for straight stacks in accordance with
Table 710.1(2), except where required to be sized as a build-
SECTION 709
ing drain in accordance with Section 711.1.1.
FIXTURE UNITS
709.1 Values for fixtures. Drainage fixture unit values as 710.2 Future fixtures. Where provision is made for the future
given in Table 709.1 designate the relative load weight of dif- installation of fixtures, those provided for shall be considered
ferent kinds of fixtures that shall be employed in estimating the in determining the required sizes of drain pipes.
total load carried by a soil or waste pipe, and shall be used in
connection with Tables 710.1(1) and 710.1(2) of sizes for soil,
SECTION 711
waste and vent pipes for which the permissible load is given in
OFFSETS IN DRAINAGE PIPING IN
terms of fixture units.
BUILDINGS OF FIVE STORIES OR MORE
709.2 Fixtures not listed in Table 709.1. Fixtures not listed in 711.1 Horizontal branch connections above or below verti-
Table 709.1 shall have a drainage fixture unit load based on the
cal stack offsets. If a horizontal branch connects to the stack
outlet size of the fixture in accordance with Table 709.2. The
within 2 feet (610 mm) above or below a vertical stack offset,
minimum trap size for unlisted fixtures shall be the size of the
and the offset is located more than four branch intervals below
drainage outlet but not less than 1.25 inches (32 mm).
the top of the stack, the offset shall be vented in accordance
709.3 Values for continuous and semicontinuous flow. with Section 915.
Drainage fixture unit values for continuous and semicontinu-
711.1.1 Omission of vents for vertical stack offsets. Vents
ous flow into a drainage system shall be computed on the basis
for vertical offsets required by Section 711.1 shall not be
that 1 gpm (0.06 L/s) of flow is equivalent to two fixture units.
required where the stack and its offset are sized as a building
709.4 Values for indirect waste receptor. The drainage fix- drain [see Table 710.1(1)].
ture unit load of an indirect waste receptor receiving the dis-
711.2 Horizontal branch connections to horizontal stack
charge of indirectly connected fixtures shall be the sum of the
offsets. Where a horizontal stack offset is located more than
drainage fixture unit values of the fixtures that discharge to the
four branch intervals below the top of the stack, a horizontal
receptor, but not less than the drainage fixture unit value given
branch shall not connect within the horizontal stack offset or
for the indirect waste receptor in Table 709.1 or 709.2.
within 2 feet (610 mm) above or below such offset.

7-8 2006 VIRGINIA PLUMBING CODE

07_Va_Plumb_2006.pS 8
M:\data\CODES\STATE CODES\Virginia\2006\Plumbing Code\Final VP\07_Va_Plumb_2006.vp
Thursday, February 14, 2008 9:22:10 AM
Color profile: Generic CMYK printer profile
Composite Default screen

SANITARY DRAINAGE

TABLE 709.1
DRAINAGE FIXTURE UNITS FOR FIXTURES AND GROUPS
DRAINAGE FIXTURE UNIT MINIMUM SIZE OF TRAP
FIXTURE TYPE VALUE AS LOAD FACTORS (inches)

Automatic clothes washers, commerciala,g 3 2


Automatic clothes washers, residentialg 2 2
Bathroom group as defined in Section 202 (1.6 gpf water closet)f 5
Bathroom group as defined in Section 202 (water closet flushing
6
greater than 1.6 gpf)f
Bathtubb (with or without overhead shower or whirlpool attachments) 2 11/2
Bidet 1 11/4
Combination sink and tray 2 11/2
Dental lavatory 1 11/4
Dental unit or cuspidor 1 11/4
Dishwashing machine,c domestic 2 11/2
Drinking fountain 0.5 11/4
Emergency floor drain 0 2
Floor drains 2 2
Kitchen sink, domestic 2 11/2
Kitchen sink, domestic with food waste grinder and/or dishwasher 2 11/2
Laundry tray (1 or 2 compartments) 2 11/2
Lavatory 1 11/4
Shower 2 11/2
Service sink 2 11/2
Sink 2 11/2
Urinal 4 Note d
Urinal, 1 gallon per flush or less 2e Note d
Urinal, nonwater supplied 0.5 Note d
Wash sink (circular or multiple) each set of faucets 2 11/2
Water closet, flushometer tank, public or private 4e Note d
Water closet, private (1.6 gpf) 3e Note d
Water closet, private (flushing greater than 1.6 gpf) 4e Note d
Water closet, public (1.6 gpf) 4e Note d
Water closet, public (flushing greater than 1.6 gpf) 6e Note d
For SI: 1 inch = 25.4 mm, 1 gallon = 3.785 L (gpf = gallon per flushing cycle).
a. For traps larger than 3 inches, use Table 709.2.
b. A showerhead over a bathtub or whirlpool bathtub attachment does not increase the drainage fixture unit value.
c. See Sections 709.2 through 709.4 for methods of computing unit value of fixtures not listed in this table or for rating of devices with intermittent flows.
d. Trap size shall be consistent with the fixture outlet size.
e. For the purpose of computing loads on building drains and sewers, water closets and urinals shall not be rated at a lower drainage fixture unit unless the lower val-
ues are confirmed by testing.
f. For fixtures added to a dwelling unit bathroom group, add the dfu value of those additional fixtures to the bathroom group fixture count.
g. See Section 406.3 for sizing requirements for fixture drain, branch drain, and drainage stack for an automatic clothes washer standpipe.

2006 VIRGINIA PLUMBING CODE 7-9

07_Va_Plumb_2006.pS 9
M:\data\CODES\STATE CODES\Virginia\2006\Plumbing Code\Final VP\07_Va_Plumb_2006.vp
Thursday, February 14, 2008 9:22:10 AM
Color profile: Generic CMYK printer profile
Composite Default screen

SANITARY DRAINAGE

TABLE 710.1(1)
BUILDING DRAINS AND SEWERS
MAXIMUM NUMBER OF DRAINAGE FIXTURE UNITS CONNECTED TO ANY PORTION OF THE BUILDING DRAIN OR THE
BUILDING SEWER, INCLUDING BRANCHES OF THE BUILDING DRAINa

Slope per foot


DIAMETER OF PIPE
1 1 1 1
(inches) /16 inch /8 inch /4 inch /2 inch

11 / 4 1 1
1/
1 2 3 3
2 21 26
1/
2 2 24 31
3 36 42 50
4 180 216 250
5 390 480 575
6 700 840 1,000
8 1,400 1,600 1,920 2,300
10 2,500 2,900 3,500 4,200
12 3,900 4,600 5,600 6,700
15 7,000 8,300 10,000 12,000
For SI: 1 inch = 25.4 mm, 1 inch per foot = 83.3 mm/m.
a. The minimum size of any building drain serving a water closet shall be 3 inches.

TABLE 710.1(2)
HORIZONTAL FIXTURE BRANCHES AND STACKSa
MAXIMUM NUMBER OF DRAINAGE FIXTURE UNITS (dfu)
Stacksb
DIAMETER OF PIPE Total discharge into one Total for stack of three Total for stack greater than
(inches) Total for horizontal branch branch interval branch Intervals or less three branch intervals

11 / 2 3 2 4 8
2 6 6 10 24
1/
2 2 12 9 20 42
3 20 20 48 72
4 160 90 240 500
5 360 200 540 1,100
6 620 350 960 1,900
8 1,400 600 2,200 3,600
10 2,500 1,000 3,800 5,600
12 3,900 1,500 6,000 8,400
15 7,000 Note c Note c Note c
For SI: 1 inch = 25.4 mm.
a. Does not include branches of the building drain. Refer to Table 710.1(1).
b. Stacks shall be sized based on the total accumulated connected load at each story or branch interval. As the total accumulated connected load decreases, stacks are
permitted to be reduced in size. Stack diameters shall not be reduced to less than one-half of the diameter of the largest stack size required.
c. Sizing load based on design criteria.

7-10 2006 VIRGINIA PLUMBING CODE

07_Va_Plumb_2006.pS 10
M:\data\CODES\STATE CODES\Virginia\2006\Plumbing Code\Final VP\07_Va_Plumb_2006.vp
Thursday, February 14, 2008 9:22:10 AM
Color profile: Generic CMYK printer profile
Composite Default screen

SANITARY DRAINAGE

711.3 Horizontal stack offsets. A stack with a horizontal off- 712.3.2 Sump pit. The sump pit shall be not less than 18
set located more than four branch intervals below the top of the inches (457 mm) in diameter and 24 inches (610 mm) deep,
stack shall be vented in accordance with Section 915 and sized unless otherwise approved. The pit shall be accessible and
as follows: located such that all drainage flows into the pit by gravity.
1. The portion of the stack above the offset shall be sized as The sump pit shall be constructed of tile, concrete, steel,
for a vertical stack based on the total number of drainage plastic or other approved materials. The pit bottom shall be
fixture units above the offset. solid and provide permanent support for the pump. The
sump pit shall be fitted with a gas-tight removable cover
2. The offset shall be sized in accordance with Section adequate to support anticipated loads in the area of use. The
710.1.1. sump pit shall be vented in accordance with Chapter 9.
3. The portion of the stack below the offset shall be sized as 712.3.3 Discharge piping. Discharge piping shall meet the
for the offset or based on the total number of drainage requirements of Section 712.2.
fixture units on the entire stack, whichever is larger [see
Table 710.1(2), Column 5]. 712.3.4 Maximum effluent level. The effluent level control
shall be adjusted and maintained to at all times prevent the
711.3.1 Omission of vents for horizontal stack offsets. effluent in the sump from rising to within 2 inches (51 mm)
Vents for horizontal stack offsets required by Section 711.3 of the invert of the gravity drain inlet into the sump.
shall not be required where the stack and its offset are one
pipe size larger than required for a building drain [see Table 712.3.5 Ejector connection to the drainage system.
710.1(1)] and the entire stack and offset are not less in Pumps connected to the drainage system shall connect to the
cross-sectional area than that required for a straight stack building sewer or shall connect to a wye fitting in the build-
plus the area of an offset vent as provided for in Section 915. ing drain a minimum of 10 feet (3048 mm) from the base of
Omission of offset vents in accordance with this section any soil stack, waste stack or fixture drain. Where the dis-
shall not constitute approval of horizontal branch connec- charge line connects into horizontal drainage piping, the
tions within the offset or within 2 feet (610 mm) above or connector shall be made through a wye fitting into the top of
below the offset. the drainage piping.
711.4 Offsets below lowest branch. Where a vertical offset 712.4 Sewage pumps and sewage ejectors. A sewage pump
occurs in a soil or waste stack below the lowest horizontal or sewage ejector shall automatically discharge the contents of
branch, a change in diameter of the stack because of the offset the sump to the building drainage system.
shall not be required. If a horizontal offset occurs in a soil or 712.4.1 Macerating toilet systems. Macerating toilet sys-
waste stack below the lowest horizontal branch, the required tems shall comply with CSA B45.9 or ASME A112.3.4 and
diameter of the offset and the stack below it shall be determined shall be installed in accordance with the manufacturers
as for a building drain in accordance with Table 710.1(1). installation instructions.
712.4.2 Capacity. A sewage pump or sewage ejector shall
SECTION 712 have the capacity and head for the application requirements.
Pumps or ejectors that receive the discharge of water closets
SUMPS AND EJECTORS
shall be capable of handling spherical solids with a diameter
712.1 Building subdrains. Building subdrains that cannot be of up to and including 2 inches (51 mm). Other pumps or
discharged to the sewer by gravity flow shall be discharged into ejectors shall be capable of handling spherical solids with a
a tightly covered and vented sump from which the liquid shall diameter of up to and including 1 inch (25.4 mm). The mini-
be lifted and discharged into the building gravity drainage sys- mum capacity of a pump or ejector based on the diameter of
tem by automatic pumping equipment or other approved the discharge pipe shall be in accordance with Table 712.4.2.
method. In other than existing structures, the sump shall not
receive drainage from any piping within the building capable of Exceptions:
being discharged by gravity to the building sewer. 1. Grinder pumps or grinder ejectors that receive the
712.2 Valves required. A check valve and a full open valve discharge of water closets shall have a minimum
located on the discharge side of the check valve shall be discharge opening of 1.25 inches (32 mm).
installed in the pump or ejector discharge piping between the 2. Macerating toilet assemblies that serve single
pump or ejector and the gravity drainage system. Access shall water closets shall have a minimum discharge
be provided to such valves. Such valves shall be located above opening of 0.75 inch (19 mm).
the sump cover required by Section 712.1 or, where the dis- TABLE 712.4.2
charge pipe from the ejector is below grade, the valves shall be MINIMUM CAPACITY OF SEWAGE PUMP OR SEWAGE EJECTOR
accessibly located outside the sump below grade in an access DIAMETER OF THE DISCHARGE CAPACITY OF PUMP OR EJECTOR
pit with a removable access cover.
PIPE (inches) (gpm)

712.3 Sump design. The sump pump, pit and discharge piping 2 21
shall conform to the requirements of Sections 712.3.1 through 1/
712.3.5. 2 2 30

712.3.1 Sump pump. The sump pump capacity and head 3 46


shall be appropriate to anticipated use requirements. For SI: 1 inch = 25.4 mm, 1 gallon per minute = 3.785 L/m.

2006 VIRGINIA PLUMBING CODE 7-11

07_Va_Plumb_2006.pS 11
M:\data\CODES\STATE CODES\Virginia\2006\Plumbing Code\Final VP\07_Va_Plumb_2006.vp
Thursday, February 14, 2008 9:22:11 AM
Color profile: Generic CMYK printer profile
Composite Default screen

SANITARY DRAINAGE

SECTION 713 713.7.2 Velocity. The velocity of airflow in a central vac-


HEALTH CARE PLUMBING uum (fluid suction) system shall be less than 5,000 feet per
minute (25 m/s).
713.1 Scope. This section shall govern those aspects of health
care plumbing systems that differ from plumbing systems in 713.8 Vent connections prohibited. Connections between
other structures. Health care plumbing systems shall conform local vents serving bedpan washers or sterilizer vents serving
to this section in addition to the other requirements of this code. sterilizing apparatus and normal sanitary plumbing systems are
The provisions of this section shall apply to the special devices prohibited. Only one type of apparatus shall be served by a
and equipment installed and maintained in the following occu- local vent.
pancies: nursing homes; homes for the aged; orphanages; infir-
713.9 Local vents and stacks for bedpan washers. Bedpan
maries; first aid stations; psychiatric facilities; clinics;
washers shall be vented to open air above the roof by means of
professional offices of dentists and doctors; mortuaries; educa-
one or more local vents. The local vent for a bedpan washer
tional facilities; surgery, dentistry, research and testing labora-
shall not be less than a 2-inch-diameter (51 mm) pipe. A local
tories; establishments manufacturing pharmaceutical drugs
vent serving a single bedpan washer is permitted to drain to the
and medicines; and other structures with similar apparatus and
fixture served.
equipment classified as plumbing.
713.9.1 Multiple installations. Where bedpan washers are
713.2 Bedpan washers and clinical sinks. Bedpan washers located above each other on more than one floor, a local vent
and clinical sinks shall connect to the drainage and vent system stack is permitted to be installed to receive the local vent on
in accordance with the requirements for a water closet. Bedpan the various floors. Not more than three bedpan washers shall
washers shall also connect to a local vent. be connected to a 2-inch (51 mm) local vent stack, not more
than six to a 3-inch (76 mm) local vent stack and not more
713.3 Indirect waste. All sterilizers, steamers and condensers
than 12 to a 4-inch (102 mm) local vent stack. In multiple
shall discharge to the drainage through an indirect waste pipe
installations, the connections between a bedpan washer
by means of an air gap. Where a battery of not more than three
local vent and a local vent stack shall be made with tee or
sterilizers discharges to an individual receptor, the distance
tee-wye sanitary pattern drainage fittings installed in an
between the receptor and a sterilizer shall not exceed 8 feet
upright position.
(2438 mm). The indirect waste pipe on a bedpan steamer shall
be trapped. 713.9.2 Trap required. The bottom of the local vent stack,
except where serving only one bedpan washer, shall be
713.4 Vacuum system station. Ready access shall be provided drained by means of a trapped and vented waste connection
to vacuum system station receptacles. Such receptacles shall be to the sanitary drainage system. The trap and waste shall be
built into cabinets or recesses and shall be visible. the same size as the local vent stack.
713.5 Bottle system. Vacuum (fluid suction) systems intended 713.9.3 Trap seal maintenance. A water supply pipe not
for collecting, removing and disposing of blood, pus or other less than 1/4 inch (6.4 mm) in diameter shall be taken from
fluids by the bottle system shall be provided with receptacles the flush supply of each bedpan washer on the discharge or
equipped with an overflow prevention device at each vacuum fixture side of the vacuum breaker, shall be trapped to form
outlet station. not less than a 3-inch (76 mm) water seal, and shall be con-
nected to the local vent stack on each floor. The water sup-
713.6 Central disposal system equipment. All central vac- ply shall be installed so as to provide a supply of water to the
uum (fluid suction) systems shall provide continuous service. local vent stack for cleansing and drain trap seal mainte-
Systems equipped with collecting or control tanks shall pro- nance each time a bedpan washer is flushed.
vide for draining and cleaning of the tanks while the system is
in operation. In hospitals, the system shall be connected to the 713.10 Sterilizer vents and stacks. Multiple installations of
emergency power system. The exhausts from a vacuum pump pressure and nonpressure sterilizers shall have the vent connec-
serving a vacuum (fluid suction) system shall discharge sepa- tions to the sterilizer vent stack made by means of inverted wye
rately to open air above the roof. fittings. Access shall be provided to vent connections for the
purpose of inspection and maintenance.
713.7 Central vacuum or disposal systems. Where the waste
from a central vacuum (fluid suction) system of the baromet- 713.10.1 Drainage. The connection between sterilizer vent
ric-lag, collection-tank or bottle-disposal type is connected to or exhaust openings and the sterilizer vent stack shall be
the drainage system, the waste shall be directly connected to designed and installed to drain to the funnel or basket-type
the sanitary drainage system through a trapped waste. waste fitting. In multiple installations, the sterilizer vent
stack shall be drained separately to the lowest sterilizer fun-
713.7.1 Piping. The piping of a central vacuum (fluid suc- nel or basket-type waste fitting or receptor.
tion) system shall be of corrosion-resistant material with a
713.11 Sterilizer vent stack sizes. Sterilizer vent stack sizes
smooth interior surface. A branch shall not be less than 0.5-
shall comply with Sections 713.11.1 through 713.11.4.
inch (12.7 mm) nominal pipe size for one outlet and shall be
sized in accordance with the number of vacuum outlets. A 713.11.1 Bedpan steamers. The minimum size of a steril-
main shall not be less than 1-inch (25 mm) nominal pipe izer vent serving a bedpan steamer shall be 1.5 inches (38
size. The pipe sizing shall be increased in accordance with mm) in diameter. Multiple installations shall be sized in
the manufacturers instructions as stations are increased. accordance with Table 713.11.1.

7-12 2006 VIRGINIA PLUMBING CODE

07_Va_Plumb_2006.pS 12
M:\data\CODES\STATE CODES\Virginia\2006\Plumbing Code\Final VP\07_Va_Plumb_2006.vp
Thursday, February 14, 2008 9:22:11 AM
Color profile: Generic CMYK printer profile
Composite Default screen

SANITARY DRAINAGE

TABLE 713.11.1 SECTION 714


STACK SIZES FOR BEDPAN STEAMERS AND
BOILING-TYPE STERILIZERS
COMPUTERIZED DRAINAGE DESIGN
(Number of Connections of Various Sizes
Permitted to Various-sized Sterilizer Vent Stacks) 714.1 Design of drainage system. The sizing, design and lay-
CONNECTION SIZE out of the drainage system shall be permitted to be designed by
STACK SIZE approved computer design methods.
(inches) 11/2 2

11/2a 1 or 0 714.2 Load on drainage system. The load shall be computed


2a 2 or 1 from the simultaneous or sequential discharge conditions from
fixtures, appurtenances and appliances or the peak usage
2b 1 and 1 design condition.
3a 4 or 2
3b 2 and 2 714.2.1 Fixture discharge profiles. The discharge profiles
for flow rates versus time from fixtures and appliances shall
4a 8 or 4 be in accordance with the manufacturers specifications.
4b 4 and 4
714.3 Selections of drainage pipe sizes. Pipe shall be sized to
For SI: 1 inch = 25.4 mm.
prevent full-bore flow.
a. Total of each size.
b. Combination of sizes.
714.3.1 Selecting pipe wall roughness. Pipe size calcula-
713.11.2 Boiling-type sterilizers. The minimum size of a tions shall be conducted with the pipe wall roughness factor
sterilizer vent stack shall be 2 inches (51 mm) in diameter (ks), in accordance with the manufacturers specifications
where serving a utensil sterilizer and 1.5 inches (38 mm) in and as modified for aging roughness factors with deposits
diameter where serving an instrument sterilizer. Combina- and corrosion.
tions of boiling-type sterilizer vent connections shall be
sized in accordance with Table 713.11.1. 714.3.2 Slope of horizontal drainage piping. Horizontal
drainage piping shall be designed and installed at slopes in
713.11.3 Pressure sterilizers. Pressure sterilizer vent accordance with Table 704.1.
stacks shall be 2.5 inches (64 mm) minimum. Those serving
combinations of pressure sterilizer exhaust connections
shall be sized in accordance with Table 713.11.3.

TABLE 713.11.3
STACK SIZES FOR PRESSURE STERILIZERS SECTION 715
(Number of Connections of Various Sizes Permitted BACKWATER VALVES
to Various-sized Vent Stacks)

STACK SIZE
CONNECTION SIZE 715.1 Sewage backflow. Where the flood level rims of plumb-
(inches) 3
/4 1 11/4 11/2 ing fixtures are below the elevation of the manhole cover of the
next upstream manhole in the public sewer, such fixtures shall
11/2a 3 or 2 or 1
be protected by a backwater valve installed in the building
11/2b 2 and 1 drain, branch of the building drain or horizontal branch serving
2 a 6 or 3 or 2 or 1 such fixtures. Plumbing fixtures having flood level rims above
the elevation of the manhole cover of the next upstream man-
2b 3 and 2
hole in the public sewer shall not discharge through a back-
2b 2 and 1 and 1 water valve.
b
2 1 and 1 and 1
3 a 15 or 7 or 5 or 3
715.2 Material. All bearing parts of backwater valves shall be
of corrosion-resistant material. Backwater valves shall comply
1 and 2 with ASME A112.14.1, CSA B181.1 or CSA B181.2.
3b 1 and 2 and
5 and 1
For SI: 1 inch = 25.4 mm. 715.3 Seal. Backwater valves shall be so constructed as to pro-
a. Total of each size. vide a mechanical seal against backflow.
b. Combination of sizes.

713.11.4 Pressure instrument washer sterilizer sizes. 715.4 Diameter. Backwater valves, when fully opened, shall
The minimum diameter of a sterilizer vent stack serving an have a capacity not less than that of the pipes in which they are
instrument washer sterilizer shall be 2 inches (51 mm). Not installed.
more than two sterilizers shall be installed on a 2-inch (51
mm) stack, and not more than four sterilizers shall be 715.5 Location. Backwater valves shall be installed so that
installed on a 3-inch (76 mm) stack. access is provided to the working parts for service and repair.

2006 VIRGINIA PLUMBING CODE 7-13

07_Va_Plumb_2006.pS 13
M:\data\CODES\STATE CODES\Virginia\2006\Plumbing Code\Final VP\07_Va_Plumb_2006.vp
Thursday, February 14, 2008 9:22:11 AM
Color profile: Generic CMYK printer profile
Composite Default screen

7-14 2006 VIRGINIA PLUMBING CODE

07_Va_Plumb_2006.pS 14
M:\data\CODES\STATE CODES\Virginia\2006\Plumbing Code\Final VP\07_Va_Plumb_2006.vp
Thursday, February 14, 2008 9:22:11 AM

You might also like