Professional Documents
Culture Documents
Nonventilated dry-type transformers are similar to the ventilated type but are
totally enclosed. This type can be installed in areas with corrosive or dirty
atmospheric conditions where it would be impossible to use a ventilated-type
transformer.
Application types
There are different ways in which transformers are installed and used as part
of a commercial building electrical system. These application types include:
Indoor distribution transformers are used with panelboards and are separately
mounted to supply the specific electrical load requirements in a system-
specific application within the system distribution. Several transformer types
rated higher than 600 V for oil insulated type, higher than 35,000 V for dry
type, and other transformers rated higher than 600 V are required to be
located in vault rooms, which must be built with fire-rated enclosures
depending on the transformer type and applicable local authority
requirements, when indoors. Transformers that are not over 600 V and are
part of the indoor building electrical system distribution have both primary and
secondary voltages below 600 V with the most common voltage level change
from 480 V to 208 Y/120 V.
Pad-mounted transformers are installed outside and are considered the first
option for supplying service entrance voltage to the building electrical system
based on the project size and requirements. They typically have primary
voltages higher than 600 V and secondary voltages lower than 600 V with
compartments for the associated protective devices assembled in an integral
tamper-resistant and weatherproof unit.
In addition, the size of the commercial facility will determine the appropriate
approach for designing the electrical distribution system for the specific
application. In this electrical system design, the transformer can be used as
part of a substation, primary unit substation, secondary unit substation, or
network configuration.
Sizing
The electrical size of the transformer load is rated in kVA. This rating provides
the associated power output delivered for a specific period by the loads
connected to the transformer on the secondary side of the equipment. The
loads, which are calculated as part of the building electrical system design
phase, are shown in the construction documents respective equipment
schedules in VA or kVA.
The above simple calculation meets the intent to achieve the normal life
expectancy of a transformer, which is based on the following basic conditions:
The transformer is equal to or less than its rated kVA and rated voltage.
The average temperature of the cooling air during a 24-hour period is 86
F.
The temperature of the cooling air at no time exceeds 104 F.
Selecting
Transformer selection starts with the kVA rating required to supply the loads
connected in the electrical system. Another consideration for indoor
distribution transformers is the type of load: linear or nonlinear. Linear loads
include resistive heating and induction motors; nonlinear loads are produced
by electronic equipment that contributes to the distortion of the electrical
power signals by generating harmonics. The harmonics resulting from
nonsinusoidal currents generate additional losses and heating of the
transformer coils, which reduce the transformer life expectancy.
Indoor transformers for nonlinear loads can be selected with a K rating, which
allows the transformer to withstand nonlinear conditions in the electrical
system. K-rated transformers do not mitigate or eliminate harmonics.
However, they do protect the transformer itself from damage caused by
harmonics. For harmonic mitigation, K-rated transformers can be combined
with harmonic filters or chokes. For linear load applications, transformers
should be selected with lower core losses. Other factors that should be
considered in selecting transformers are voltage ratings for both primary and
secondary, voltage taps, efficiency, impedance value, type of cooling and
temperature rise, voltage insulation class, basic impulse level, and sound
level.
Practical applications
In the past two years, two large projects in Miami Dade County have been
built: the Florida International University football stadium and Miami
International Airport South Terminal. Both projects included dry-type 480 V, 3-
phase to 208 Y/120V V step-down transformers (in NEMA 2 enclosures),
ranging from 15 kVA to 112.5 kVA in the electrical system distribution design.
The 18,688-seat FIU football stadium was designed with about 12
transformers as part of the electrical system distribution in order to supply
general-use receptacles, small motors, and other loads in the stadium building
structure and the attached field house building. The MIA South Terminal
expansion was designed with about 50 transformers with similar intent as the
stadiums but a more diverse group of loads for the 208 Y/120 V 3-phase, 4-
wire system, which also included lighting loads, signage, telecommunication,
security systems, and other loads part of this building project (Figure 1).
Installation
Looking ahead
Related News:
HOK hires director of engineering services - 08.05.2012 10:31
Understanding standby power system grounding - 14.12.2011 00:00
Avoid hidden dangers when applying 30-cycle-rated transfer
switches - 12.12.2011 00:00
Quick connect tap box generators restores power after outage -
07.10.2011 11:31
Circuit protection in hospitals - 08.07.2011 00:00
Hospital includes sophisticated electrical system - 08.07.2011 00:00
Tall order for super high-rises - 23.05.2011 00:00