Professional Documents
Culture Documents
Water-Cooled
Liquid Chillers
165-3950 Tons
50 and 60 Hz
165 500
450 1300
325 2000
1200 2500
CDHF Dual Compressor CenTraVac 60 Hz
1500 3950
170 3950
Introduction 2
Features and Benefits 5
Unit Options 12
System Options 19
Application Considerations 24
Selection Procedure 25
Performance Data 27
Jobsite Connections 31
Controls 32
Weights 41
Physical Dimensions 43
Mechanical Specifications 50
Standard Conversion Table 55
CTV-PRC007-EN 3
Introduction The Trane Name
4 CTV-PRC007-EN
Features and
Benefits
CTV-PRC007-EN 5
Features and Chiller
Benefits Controller
DynaView Operator Interface DynaView receives information from and DynaView can be connected to the
communicates information to the other service tool using a standard 9-pin male,
DynaView is the unit-mounted control devices on the chillers communications 9-pin female RS-232 serial cable. The
panel and also serves as the main link. DynaView performs the Leaving serial connection is located at the
processor and operator interface. It has a Chilled Water Temperature and Limit bottom of the DynaView panel behind a
touch-sensitive overlay on a 1/4 VGA Control algorithms, arbitrating capacity sliding door.
display. against any operating limit against which
DynaView presents information through the chiller may find itself working.
an intuitive, tabbed- navigation system. Auto/Stop commands
Alternate languages can be downloaded
to the control panel, which can hold Status (all subsystems)
English plus two other languages at one Setpoint adjustment
time. (daily user points)
10 active diagnostics
Mode overrides
ASHRAE chiller log
6 CTV-PRC007-EN
Features and Control
Benefits Panel
CTV-PRC007-EN 7
Features and Standard and
Benefits Optional Features
Standard Features
The following features are provided as
standard with all Trane CenTraVac
chillers:
Tracer Chiller Control Strategies
Low-pressure operation that minimizes
the chance for outward refrigerant
leaks.
Hermetically sealed and precision
cooled by liquid refrigerant that keeps
the motor, drive, and equipment room
temperatures controlled, monitored
and predictable by design. Taking
predictable reliability to yet another
level, this feature also protects against
motor-destroying elements such as
dust, grit, metal shavings, high
humidity, high ambient operating
temperatures, and process liquids or
gases.
Designed to be rugged and simple, yet
amazingly quiet, the CenTraVac is
directly driven, in low speed, by a Entering condenser water temperature High-pressure (300 psig) water side
motor shaft that is supported by two to 50 degrees F maintaining 3 psi construction
aircraft-turbine-rated bearings. The differential pressure
design includes industrial-grade Energy saving free cooling, heat
components and only one moving Phase voltage sensors (3-phase) recovery, or auxiliary condenser
part. Likewise, the design purposely Meet or exceeds ASHRAE 90.1-1999 Special tubing: smooth bore; CuNi;
excludes speed-increasing gears and various tube wall thickness; and
lightweight parts that, while accessible, Startup and operator instruction service
internally enhanced
have a higher failure rate. Protection - See Control Section
Refrigerant monitor
On-line tolerance for quick changes in Motor control and compressor
refrigerant loop conditions, variable protection Factory-applied thermal insulation
pumping strategies, and other atypical Hot water control and Ice-making Spring isolators
operating requirements. control Building automation systems (BAS)
Purge capability when chiller is off interface
Heat exchanger control Optional Features Chilled water reset based upon outside
Trane offers a selection of optional air temperature
Two-stage or single stage economizer features to augment the standard chiller
Prewired instrument and control panel installation or to modify the chiller for Leaving water temperature to 34
special purpose applications. degrees F w/o glycol
Oil and refrigerant charge
Medium-voltage (over 600 volts) Variable speed drives
Oil heater
compressor motor UL Label
Isolation pads
Complete line of compressor motor Three-pass or one-pass evaporator
Wiring and conduit for purge and oil starters - factory installed prewired if
system interconnection to the main Chiller break apart (disassembly)
you prefer
control panel Special paint and controls for outdoor
Marine waterboxes for evaporators and use or corrosive environments
Installation, operation, and condensers
maintenance instructions Enhanced condenser limit control
Proof of promised performance and
High efficiency purge system with sound pressues Extended operation control for external
automatic regeneration capability ice-building, base loading and making
hot-water
8 CTV-PRC007-EN
Features and
Benefits
CTV-PRC007-EN 9
Features and Refrigeration
Benefits Cycle
CenTraVac Motor Direct Drive Design No Gear Losses evaporator and condenser pressures,
The motor provided in the Trane The direct drive compressor operates significantly increasing chiller efficiency.
CenTraVac chiller is a specially designed without speed increasing gears, thus This improvement in efficiency is not
squirrel-cage, two-pole induction motor eliminating gear energy losses. possible in single-stage chillers since all
suitable for 50 and 60 hertz, three-phase Compressors using gears suffer mesh compression is done by one impeller.
current. losses and extra bearing losses in the Single Stage Economizer
Trane CenTraVac motors are cooled by range of three to five percent at full load. The CVHF CenTraVac chiller has a single-
liquid refrigerant surrounding the motor Since these losses are fairly constant stage economizer providing up to 41/2
windings and rotor. Using liquid over the load range, increasingly larger percent greater efficiency than designs
refrigerant results in uniform low percentage losses result as load with no economizer.
temperatures throughout the motor, decreases.
Since the CVHF CenTraVac uses two
which prolongs the life of the motor. Multiple Stages of Compression impellers, it is possible to flash
Design Simplicity The compressor operates more refrigerant gas at an intermediate
Impellers are keyed directly to the motor efficiently over a wide range of pressure between the evaporator and
shaft for high reliability and performance capacities, virtually eliminating the need condenser pressures, significantly
and low life-cycle costs. for energy wasting hot gas bypass as increasing chiller efficiency. This
typically found on single stage chillers. improvement in efficiency is not possible
Fixed Orifice Flow Control
For proper refrigerant flow control at all The radial component of velocity in single-stage chillers since all
load conditions, the CenTraVac design determines the ability of the chiller to compression is done by one impeller.
incorporates the Trane patented fixed resist interruption of smooth refrigerant Refrigerant/Oil Pump Motor
orifice system. It eliminates float valves, flow when operating at light loads and The oil pump motor is a 120 volt,
thermal expansion valves and other with high condensing temperatures. This 50/60 hertz, 3/4 hp, 1 phase motor with
moving parts. Since there are no moving interruption in flow and unstable protective fusing and panel mounted
parts, reliability is increased. operation, called surge is avoided with contactor.
the two-stage design.
Quiet Operation EarthWise Purge System
With only one moving component the Inlet Guide Vanes The new purge design features a high-
rotor and impeller assembly the Trane Part load performance is further efficiency carbon filter with an automatic
low speed, direct drive design operates improved through use of moveable regeneration cycle. The filter collects and
exceptionally quietly. The smoothly designed variable inlet guide vanes. Inlet scrubs refrigerant and noncondensable
rotating CenTraVac compressor is guide vanes improve performance by gas and returns collected refrigerant
inherently quieter than other compressor throttling refrigerant gas flow to exactly vapor back into the chiller. When the
types. Typical CenTraVac chiller sound meet part load requirements and by tank senses that it is full, the
measurements are among the quietest prerotating refrigerant gas for optimum regeneration cycle begins, and reclaimed
in the industry. Trane can guarantee entry into the impeller. Prerotation of refrigerant is automatically returned to
sound levels with factory testing and refrigerant gas minimizes turbulence and the chiller. This keeps the purge
measurements in accordance with increases efficiency. efficiency at its peak without the need to
ARI standard 575. Two-Stage Economizer exchange carbon cannisters.
The Reliability Standard The CVHE/CVHG CenTraVac chiller has a Normal operating efficiency does not
Just as a multistage turbine is more two-stage economizer providing up to exceed 0.02 lbs. of refrigerant lost per
efficient than a single stage turbine, the seven percent greater efficiency than pound of dry air removed. The purge
CenTraVac multistage compressors are designs with no economizer. Since the system can be operated at any time,
more efficient and reliable than single- CVHE/CVHG uses three impellers, it is independent of chiller operation, per
stage designs. possible to flash refrigerant gas at two ASHRAE Standard 147.
intermediate pressures between the
10 CTV-PRC007-EN
Features and Refrigeration
Benefits Cycle
Figure 1 Three-Stage CenTraVac P-H Compressor First Stage Refrigerant pressure called P1. P1 is between the
Diagram gas is drawn from the evaporator into evaporator and condenser pressures.
the first stage compressor. The first stage Preflashing some liquid refrigerant cools
impeller accelerates the gas increasing the remaining liquid to state point 7.
its temperature and pressure to state Refrigerant leaving the first stage
point 3. economizer flows through the second
Compressor Second Stage Refrigerant orifice and enters the second stage
gas leaving the first stage compressor is economizer. Some refrigerant is
mixed with cooler refrigerant gas from preflashed at intermediate pressure P2.
the low pressure side of the two-stage Preflashing the liquid refrigerant cools
economizer. This mixing lowers the the remaining liquid to state point 8.
enthalpy of the mixture entering the To complete the operating cycle, liquid
second stage. The second stage impeller refrigerant leaving the economizer at
accelerates the gas, further increasing state point 8 flows through a third orifice
its temperature and pressure to state system. Here, refrigerant pressure and
point 4. temperature are reduced to evaporator
Compressor Third Stage For conditions at state point 1.
Figure 2 Two-Stage CenTraVac P-H CenTraVac chillers with three stage
Diagram For two-stage CenTraVac chillers with
compression, the refrigerant gas leaving economizer and refrigerant orifice
the compressor second stage is mixed system-liquid refrigerant leaving the
with cooler refrigerant gas from the high condenser at state point 6 flows through
pressure side of the two-stage the first orifice and enters the
economizer. This mixing lowers the economizer. The purpose of this orifice
enthalpy of the gas mixture entering the and economizer is to preflash a small
third stage compressor. The third stage amount of refrigerant at an intermediate
impeller accelerates the gas, further pressure called P1. P1 is between the
increasing its temperature and pressure evaporator and condenser pressures.
to state point 5, then discharges it to the Preflashing some liquid refrigerant cools
condenser. the remaining liquid to state point 8.
Condenser Refrigerant gas enters the Another benefit of flashing refrigerant is
condenser where the system cooling to increase the total evaporator
refrigeration effect from RE to RE. The
CenTraVac Two-Stage and load and heat of compression are
economizer of two-stage CenTraVac
rejected to the condenser water circuit.
Three-Stage P-H Diagram This heat rejection cools and condenses chillers provides a 41/2 percent energy
The pressure-enthalphy (P-H) diagram the refrigerant gas to a liquid at state savings and the two-stage economizer of
describes refrigerant flow through the point 6. the three-stage CenTraVac chillers
major chiller components. The diagrams provides a 7% savings, compared to
For three-stage CenTraVac chillers with chillers with no economizer. To complete
confirm the superior operating cycle
the patented two-stage economizer and the operating cycle, liquid refrigerant
efficiency of the three- stage compressor
refrigerant orifice system-liquid leaving the economizer at state point 8
and two-stage economizer respectively. refrigerant leaving the condenser at state flows through a second orifice system.
Evaporator A liquid-gas refrigerant point 6 flows through the first orifice and Here, refrigerant pressure and
mixture enters the evaporator at state enters the high pressure side of the temperature are reduced to evaporator
point 1. Liquid refrigerant is vaporized to economizer. The purpose of this orifice conditions at state point 1.
state point 2 as it absorbs heat from the and economizer is to preflash a small
system cooling load. The vaporized amount of refrigerant at an intermediate
refrigerant then flows into the
compressor first stage.
CTV-PRC007-EN 11
Unit
Options Starters
y
;
NEMA 1 starter enclosure
120 volt, 60 hertz, 1-phase fused pilot
and safety circuits
Figure 3 Typical Equipment Room Layout Conventional Remote Star-Delta Starter
Control power transformer (4.0 KVA)
with 120 volt, 50 or 60 hertz, single-
yy
;;
phase
One pilot relay to initiate start sequence
from CenTraVac control circuit signal
Starter enclosures capable of being
;;
yy
padlocked
3-phase incoming line terminals
6 output load terminals factory-
connected to the motor
Automatic transfer from wye to delta
on any two-step starter (unit-mounted)
12 CTV-PRC007-EN
Unit Low-Voltage
Options Starters
CTV-PRC007-EN 13
Unit Medium-Voltage
Options Starters
14 CTV-PRC007-EN
Unit Adaptive
Options Frequency Drive
16 CTV-PRC007-EN
Unit
Options Free Cooling
Free Cooling Allows Free Cooling Operation Schematic The suitability of free cooling for any
particular installation depends upon a
Reduced Operating Costs number of factors. The availability of
Consider a CenTraVac chiller option that low temperature condensing water, the
can provide up to 45 percent of the quality of the outside air, the type of
nominal chiller capacity without airside system, the temperature and
operating the compressor. Think of the humidity control requirements, and the
significant energy and cost savings cost of electricity all have a direct impact
possible in many applications. This on the decision to use a free cooling
option is available on all Trane chillers, chiller.
factory installed. The use of CenTraVac free cooling
Free cooling operation is based on the depends on the availability of cold
principle that refrigerant migrates to the condenser water from a cooling tower,
area of lowest temperature. When river, lake, or pond. As a general rule of
condenser water is available at thumb, locations which have a
temperatures lower than the required substantial number of days with
leaving chilled water temperature ambient temperatures below 45F wet
(typically 50 to 55F), the unit control bulb or more than 4000 degree-days per
panel starts the free cooling cycle Reliability year are well suited to free cooling
automatically. Two simple valves are the only moving operation. A cooling tower usually must
parts. be winterized for off-season operation
When the free cooling cycle can no
and the minimum sump temperature is
longer provide sufficient capacity to meet Single-Source Responsibility limited by some cooling tower
cooling requirements, mechanical Free cooling is Trane engineered, manufacturers. Cooling tower
cooling is restarted automatically by the manufactured and installed. manufacturers should be consulted for
unit control panel.
Ease of Operation recommendations on low temperature
For example, a building with a high Changeover on free cooling by single operation. With river, lake or pond
internal cooling load is located in a switch control. supply, condenser water temperatures
climate with cold winters. It is possible to down to freezing levels are possible.
Ease of Installation
cool the building exclusively with free Areas which have badly fouled air may
Completely factory-installed and leak-
cooling three to six months of the year! be more conducive to free cooling
tested components. All valve operators
Free cooling payback can easily be less operation than the use of an outside air
and controls are factory wired.
than a year. economizer.
Application
Free cooling is completely factory Airside systems which both heat and
Modern buildings often require some
installed and requires no more floor cool the air can often effectively use a
form of year-round cooling to handle
space or piping than the standard free cooling chiller. Dual-duct,
interior zones, solar loads, or computer
CenTraVac chiller (unlike plate frame heat multizone, and reheat systems fall into
loads. As the outside air temperature
exchangers). this general category. As the outside
decreases below the inside air design
temperature, it is often possible to use temperature begins to fall, the cool
Benefits
an outside air economizer to satisfy the outside air satisfies the cooling
The Trane patented free cooling
cooling requirements. There are a requirements (through an outside air
accessory for Trane CenTraVac chillers
number of instances, however, where economizer). As the outdoor air
adapts the basic chiller so it may
CenTraVac free cooling offers a number temperature becomes very low, the
function as a simple heat exchanger
of advantages over the use of an outside outdoor air may need to be heated in
using refrigerant as the working fluid.
air economizer. It is possible for the free order to maintain the design supply air
When condenser water is available at
cooling chiller to satisfy the cooling load temperature when it is mixed with
temperatures lower than the desired
for many hours, days, or months during return air. This heating penalty can be
chilled liquid temperature, free cooling
the fall, winter, or spring seasons without eliminated by using CenTraVac free
can provide up to 45 percent of nominal
operation of the compressor motor. This cooling. Warm chilled water
chiller capacity without operation of the
method of satisfying the cooling temperatures provided by the free
compressor. This feature may result in
requirement can result in significant total cooling chiller would allow a warmer air
substantial energy cost savings on many
energy savings over other types of temperature off the chilled water coils,
installations.
systems. The savings available are most eliminating the heating energy required
easily determined through the use of a by using only an outside air economizer.
computer energy analysis and economic With todays high cost electricity in most
program, such as TRACE (Trane Air areas of the country, this heating
Conditioning and Economics). penalty can be very significant.
CTV-PRC007-EN 17
Unit
Options Free Cooling
Temperature and humidity control refrigerant temperature and pressure will The free cooling accessory consists of
requirements are important be higher in the evaporator than in the the following factory-installed or
considerations when evaluating the use condenser, due to the water temperature supplied components:
of CenTraVac free cooling. Low difference, the refrigerant gas boiled off
A refrigerant gas line, including an
temperature outside air (from the in the evaporator will flow to the
electrically actuated shutoff valve,
outside air economizer) often requires a condenser. The gas then condenses and
installed between the evaporator and
large amount of energy for flows by gravity back to the evaporator.
condenser.
humidification purposes. Free cooling This automatic refrigeration cycle is
operation helps to reduce these sustained as long as a temperature A valved liquid return line including an
humidification costs on many difference exists between the condenser electrically activated shutoff valve,
applications. water and evaporator water. between the condenser sump and
evaporator.
It is important to note that those The difference in temperature between
applications which require extremely the condenser and evaporator A liquid refrigerant storage vessel.
precise humidity control typically cannot determines the rate of refrigerant flow Added refrigerant charge.
tolerate warmer than design chilled between the two shells and hence the
water temperatures. Therefore, since free cooling capacity. Manual free cooling controls on the
free cooling chillers normally deliver unit control panel.
If the system load becomes greater than
warmer than design chilled water the free cooling capacity either the For specific information on free cooling
temperatures, free cooling operation is operator manually stops free cooling, a applications, contact the local Trane
usually not applicable with systems binary input from a customer-supplied sales office.
which require precise humidity control. system disables free cooling or the CPM
Also, free cooling is generally not used in can automatically perform this function. Figure 6 Compressor Operation Schematic
conjunction with heat recovery systems, The gas and liquid valves close and the
since mechanical cooling must be used compressor starts. Refrigerant gas is
to recover heat that will be used drawn out of the evaporator by the
elsewhere in the building for compressor, compressed and introduced
simultaneous heating. into the condenser. Most of the
Operation condensed liquid first takes the path of
Free cooling operates on the principle least resistance by flowing into the
that refrigerant flows to the area of storage tank which is vented to the high
lowest temperature in the system. The pressure economizer sump by a small
Tracer system/Chiller Plant Manager bleed line. When the storage tank is
(CPM) can be used for automatic free filled, liquid refrigerant must flow
cooling control. When condenser water through the bleed line restriction. The
is available at a temperature lower than pressure drop through the bleed line is
the required leaving chilled water greater than that associated with the
temperature, the CPM starts the free orifice flow control device, hence liquid
cooling cycle. If the load cannot be refrigerant flows normally from the
satisfied with free cooling, the CPM condenser through the orifice system
or a customer supplied system can and into the economizer.
Figure 7 Free Cooling Operation Schematic
automatically switch to the powered
cooling mode. If desired, the chiller
can be manually switched to the free
cooling mode at the unit control panel.
Upon changeover to free cooling, the
shutoff valves in the liquid and gas lines
are opened and a lockout circuit
prevents compressor energization.
Liquid refrigerant drains by gravity from
the storage tank into the evaporator,
flooding the tube bundle. Since the
18 CTV-PRC007-EN
System
Options Heat Recovery
Heat Recovery The effect of this increased pressure During cooling-only operation, the
differential and decreased refrigeration condensing pressures and temperatures
Use of the Heat Recovery CenTraVac effect is a heat recovery machine which are normally lower than during the heat
can significantly reduce the energy has a higher kW/ton energy recovery operation. So, in essence, the
operating costs of many buildings by consumption during heat recovery impeller diameters were oversized. This
using heat which normally would be operation. would result in a compressor efficiency
rejected to the atmosphere. Typical uses during cooling- only season which was
for this heat are perimeter zone heating, Typical catalog kW/ton for heat recovery
lower than if the impellers had been
reheat air conditioning systems and any machines operating in the heat recovery
mode range from .64 to .84 kW/ton selected for a cooling-only application.
hot water requirements. Any building
with a simultaneous heating and cooling compared to a range of .61 to .79 for a The multistage compressor and
load is a potential candidate. cooling-only machine. Not only can advanced impeller design on the
there be an energy consumption penalty CenTraVac chiller reduce this costly
Most heating applications require water paid due to the inherent differences in energy penalty. Neither the capacity nor
temperatures higher than the operating cycles for heat recovery the power consumption changes
85F to 95F typically sent to the cooling machines, but traditional machine substantially as the heat recovery
tower. Therefore, most heat recovery design can add to that energy handicap. operating conditions divert from the
chillers are required to produce higher In the past, a heat recovery machines cooling-only condition. The multistage
leaving condenser water temperatures, operating efficiency was normally compressor allows a closer match of
and thus will not duplicate the energy penalized year- round by having the impeller size to the operating condition.
efficiencies of cooling-only machines. capability to produce high heating water In addition, the computer designed
Figure 9 illustrates the typical operating temperatures. Impellers are selected to impellers and crossover are designed to
cycles of a cooling-only machine and a produce the maximum required reduce losses as the kinetic energy of the
heat recovery machine. The most refrigerant pressure difference between refrigerant gas is converted to static
noticeable differences are: the evaporator and condenser, pressure.
1. The pressure differential provided by Figure 8. Usually, that meant the impeller
the compressor is much greater for diameters were determined by the heat
the heat recovery cycle. recovery operating conditions.
2. The amount of heat rejected from the
heat recovery condenser is greater Figure 8 Refrigerant Pressure Difference
than that which would be rejected in
cooling-only operation.
3. There is a decrease in the refrigeration
effect. (RE) Higher condensing
pressures increase the intermediate
pressure in the economizer. Therefore,
the liquid in the economizer has a
higher enthalpy during the heat
recovery mode than during standard
chiller operation and the refrigeration
effect is slightly decreased. Because of
this decreased refrigeration effect, the
compressor must pump more gas per
ton of refrigeration.
CTV-PRC007-EN 19
System Heat Recovery
Options (Cont.)
Figure 9 Typical Operating Cycles The reliability of the Heat Recovery so does the refrigerant condensing
CenTraVac chiller has been proven in temperature and pressure difference
installations around the world. This which the compressor is required to
option is completely factory packaged. produce at part load. This increases the
To further reduce the system energy unloading range of the compressor.
requirements, the following design When the supply heating water
considerations should be incorporated temperature to the building system is
into any heat recovery system. maintained and the return heating water
Heating Water Temperatures and temperature to the condenser is allowed
Control It is always desirable to use as to float, the mean heating water
low a heating water temperature as the temperature actually rises as the chiller
application allows. Experience has load decreases and less heat is rejected
shown that a design heating water to the condenser. As Figure 10 illustrates,
temperature of 105 to 110F can satisfy when the compressor unloads, the
most heating requirements. Lower pressure difference that it must oppose
heating water temperatures increase the to prevent surging remains essentially
chiller operating efficiency both in the the same, while the compressors
Simultaneous Heating and Cooling capability to handle the pressure
heating mode and in the cooling mode.
The Trane Heat Recovery CenTraVac difference decreases. Therefore, the
In general, the heat recovery power
chiller is an excellent choice for units capability to unload without the
consumption will increase 7 to 14
applications requiring simultaneous use of hot gas bypass is reduced.
percent for every 10F increase in the
heating and cooling. CenTraVac models
design heating water temperature. A Hot gas bypass artificially increases the
save energy by recovering heat normally
consideration which is just as important load on the compressor (cfm of
rejected to the atmosphere and putting
as the design heating water temperature refrigerant gas) by diverting refrigerant
that energy to use providing space
is how that temperature is controlled. In gas from the condenser back to the
heating, building hot water or process
most cases, the heating water compressor. Although hot gas bypass
hot water. This heat is provided at a
temperature control should be designed increases the units power consumption
fraction of conventional heating systems
to maintain the return heating water by forcing the compressor to pump
cost. A heat recovery CenTraVac can
temperature. By allowing the supply more refrigerant gas, it will increase the
provide 95 to 120F hot water.
water temperature to float, the mean heat available to recover for those
An advanced computer selection water temperature in the system drops applications where significant heating
program chooses a heat recovery as the chiller load decreases and less loads remain as the cooling load
condenser to match your needs. Two heat is rejected to the condenser. As the decreases.
separate condenser shells are used with mean heating water temperature drops,
the Heat Recovery CenTraVac chiller. The
heating circuit and cooling tower circuit
are separate, preventing cross
contamination. Refrigerant gas from the
compressor flows into both condenser
shells allowing heat rejection to one or Figure 10 Heating Water Control
both condenser water circuits.
20 CTV-PRC007-EN
System Auxiliary
Options Condenser
CTV-PRC007-EN 21
System Auxiliary
Options Condenser (Cont.)
Figure 11
22 CTV-PRC007-EN
System
Options Ice Storage
Ice Storage Provides selected for efficient production of The ice storage system is operated in six
chilled fluid at nominal comfort cooling different modes: each optimized for the
Reduced Electrical Demand conditions. The ability of Trane chillers to utility cost of the hour.
Ice storage is the hottest thing in cooling serve double duty in ice production 1. Provide comfort cooling with chiller
today. It has been accepted by building and comfort cooling greatly reduces the
owners and tenants who are concerned capital cost of ice storage systems. 2. Provide comfort cooling with ice
about utility costs. A glycol solution is used to transfer heat 3. Provide comfort cooling with ice and
An ice storage system uses a standard from the ice storage tanks to the chiller
chiller to make ice at night when utilities centrifugal chiller and from the cooling 4. Freeze ice storage
charge less for electricity. The ice coils to either the chiller or ice storage
supplements or even replaces tanks. The use of a freeze protected 5. Freeze ice storage when comfort
mechanical cooling during the day when solution eliminates the design time, field cooling is required
utility rates are at their highest. This construction cost, large refrigerant 6. Off
reduced need for cooling results in big charges, and leaks associated with ice Tracer optimization software controls
utility cost savings. plants. Ice is produced by circulating 22- operation of the required equipment and
Another advantage of ice storage is 24F glycol through modular insulated accessories to easily transition from one
standby cooling capacity. If the chiller is ice storage tanks. Each tank contains a mode of operation to another. For
unable to operate, one or two days of ice heat exchanger constructed of example:
may still be available to provide cooling. polyethylene tubing. Water in each tank
is completely frozen with no need for Even with ice storage systems there are
In that time the chiller can be repaired numerous hours when ice is neither
before building occupants feel any loss agitation. The problems of ice bridging
and air pumps are eliminated. produced or consumed, but saved. In
of comfort. this mode the chiller is the sole source of
The Trane CenTraVac chiller is uniquely When cooling is required, ice chilled cooling. For example, to cool the
suited to low temperature applications glycol is pumped from the ice storage building after all ice is produced but
like ice storage because it provides tanks directly to the cooling coils. No before high electrical demand charges
multiple stages of compression. expensive heat exchanger is required. take effect, Tracer sets the centrifugal
Competitive chillers provide only one The glycol loop is a sealed system, chiller leaving fluid setpoint to its most
stage. This allows the CenTraVac chiller eliminating expensive annual chemical efficient setting and starts the chiller,
to produce ice efficiently, with less stress treatment costs. The centrifugal chiller is chiller pump, and load pump.
on the machine. also available for comfort cooling duty at
nominal cooling conditions and When electrical demand is high, the ice
Simple and smart control strategies are efficiencies. The modular concept of pump is started and the chiller is either
another advantage the CenTraVac chiller glycol ice storage systems and the demand limited or shut down
has for ice storage applications. Trane proven simplicity of Trane Tracer completely. Tracer controls have the
Tracer building management systems controls allow the successful blend of intelligence to optimally balance the
can actually anticipate how much ice reliability and energy saving contribution of ice and chiller in meeting
needs to be made at night and operate performance in any ice storage the cooling load.
the system accordingly. The controls are application. The capacity of the chiller plant is
integrated right into the chiller. Two extended by operating the chiller and ice
wires and preprogrammed software in tandem. Tracer rations the ice,
dramatically reduce field installation cost Figure 12 Ice Storage Demand Cost augmenting chiller capacity while
and complex programming. Savings reducing cooling costs.
Trane centrifugal chillers are well suited When ice is produced, Tracer will lower
for ice production. The unique multi- the centrifugal chiller leaving fluid
stage compressor design allows the setpoint and start the chiller, chiller and
lower suction temperatures required to ice pumps, and other accessories. Any
produce ice and the higher chiller incidental loads that persists while
efficiencies attributed to centrifugal producing ice can be addressed by
chillers. Trane three stage and two stage starting the load pump and drawing
centrifugal chillers produce ice by spent cooling fluid from the ice storage
supplying ice storage vessels with a tanks.
constant supply of 22 to 24F glycol.
Centrifugal chillers selected for these For specific information on ice storage
lower leaving fluid temperatures are also applications, contact your local Trane
sales office.
CTV-PRC007-EN 23
Application
Considerations
Condenser Water Limitations of factors such as load, leaving method of calculating the minimum
evaporator temperature and component circuit ampacity. The minimum circuit
Trane CenTraVac chillers start and combinations. Startup below this ampacity is defined as the sum of two
operate over a range of load conditions differential is possible as well, especially amperages: 125 percent of the
with controlled water temperatures. with the Tracer chiller controllers soft compressor motor Rated Load Amps
Reducing the condenser water start and Adaptive Control features. (RLA), plus the Full Load Amps (FLA) of
temperature is an effective method of all remaining loads on the same circuit.
lowering the chiller power input. Water Flow
Todays technology challenges ARIs For starter to motor wiring, there are no
However, the effect of lowering the other remaining loads. For main power
condenser water temperature may cause traditional design of three gpm per ton
through the condenser. Reduced supply to the starter, there is a remaining
an increase in system power load consisting of the 4 KVA control
consumption. condenser flows are a simple and
effective way to reduce both first and power transformer which supplies power
In many applications Trane CenTraVac operating costs for the entire chiller plant. to the controls, the oil pump motor, oil
chillers can start and operate without This design strategy will require more sump heater and the purge unit motor.
control of the condenser water effort from the chiller. But pump and Therefore, the remaining load FLA
temperature. However, for optimum tower savings will typically offset any equals 4000 divided by the unit design
system power consumption, and for any penalty. This is especially true when the voltage.
applications with multiple chillers, plant is partially loaded or condenser As an example, calculate the minimum
control of the condenser water circuit is relief is available. circuit ampacity of a machine which has
recommended. Integrated control of the a design RLA of 350 amps and is to be
chillers, pumps and towers is easily In new systems, the benefits can include
dramatic savings with: operated on a 460 volt power supply:
accomplished with the onboard Tracer
chiller controller and/or Tracer Summit Size and cost for condenser lines and Minimum Circuit Ampacity =
system. valves
Size and cost of the cooling tower. 4000 VA
(125% x 350 Amps) +
Water Treatment Size and cost of the water pumps. 460 V
The use of untreated or improperly Pump energy (30 to 35% reduction).
treated water in a chiller may result in = 437.5 Amps + 8.7 Amps
Tower fan energy (30 to 35% reduction).
scaling, erosion, corrosion, algae or = 446.2 Amps
slime. It is recommended that the Replacement chiller plants can reap even
greater benefits from low flow After the minimum circuit ampacity has
services of a qualified water treatment
condensers. Because the water lines and been determined, the electrical engineer
specialist be used to determine what
tower are already in place, reduced flows or contractor will refer to the appropriate
treatment, if any, is advisable. Trane
would offer a tremendous energy conductor sizing table in the NEC to
assumes no responsibility for the results
advantage. Theoretically, a 2 GPM/ton determine the exact conductors required.
of untreated, or improperly treated water.
design applied to a system that originally A typical table for 75F conductors is
Water Pumps used 3 GPM/ton would offer a 70% included in the Trane submittal. The
Avoid specifying or using 3600 rpm reduction in pump energy. At the same selection of conductors is based on a
condenser and chilled water pumps. time, the original tower would require a number of jobsite conditions (i.e. type of
Such pumps may operate with nozzle change but would then be able to conductor, number of conductors, length
objectionable noises and vibrations. In produce about two degrees colder of conductors, ambient temperature
addition, a low frequency beat may occur condenser water than before. These two rating of conductors).
due to the slight difference in operating benefits would again typically offset any Branch-Circuit Short-Circuit and Ground
rpm between water pumps and extra effort required by the chiller. Fault Protection
CenTraVac motors. Where noise and
Contact your local Trane Sales Office for Circuit breakers and fused disconnects
vibration-free operation are important,
information regarding optimum should be sized by the electrical engineer
Trane encourages the use of 1750 rpm
condenser water temperatures and flow or contractor in strict accordance with
pumps.
rates for a specific application. NEC Article 440-21 and in accordance
Chillers are designed to ARI conditions of with all local codes. This protection
85F, but Trane CenTraVac chillers can should be for motor type loads and
operate with a 3 psig pressure differential
Electrical Information
should not be less than 150 percent of
between the condenser and evaporator Minimum Circuit Ampacity the compressor motor rated load amps
at any steady state load without oil loss, To properly size field electrical wiring, the (RLA).
oil return, motor cooling, refrigerant electrical engineer or contractor on a
hang-up or purge problems. And this project needs to know the minimum
differential can equate to safe minimum circuit ampacity of the CenTraVac
entering condenser water temperatures machine. The National Electrical Code
at or below 55F, dependent on a variety (NEC), in Article 440-33, defines the
24 CTV-PRC007-EN
Selection
Procedure
CTV-PRC007-EN 25
Selection
Procedure
Roughing-in Dimensions Full Load and Part Load There are a number of variables that
The dimensional drawings illustrate should be considered in developing an
overall measurements of the chiller. The
Performance accurate chiller load profile to use for
recommended space envelope indicates The CenTraVac chiller possesses measuring how one machine compares
clearances required to easily service the excellent performance characteristics with another machine at part load. The
CenTraVac chiller. A view of the unit is over its full range of operation. The use of outdoor air economizers,
superimposed on this drawing with unit multistage direct-drive compressor variations in chiller sequencing and
support feet shown. enables stable and efficient operation chiller plant load optimization strategies
over a wide range of capacities, virtually should be considered. Decoupled,
All catalog dimensional drawings are
eliminating the need for energy wasting primary/secondary water loops or
subject to change. Current submittal
hot gas bypass typically found on single variable primary flow designs are more
drawings should be referred to for
stage chillers. efficient ways to control multiple chiller
detailed dimensional information.
Contact the local Trane sales office for An in-depth examination of project- water plants. These control strategies
submittal and template information, or specific conditions and energy rate result in one chiller operating at a more
generate Trane product templates online: structures should be performed to fully loaded condition rather than
www.trane.com/commercial/equipment/ appropriately evaluate total energy costs multiple chillers operating at part load,
product-templates over a period of time. TRACE, Tranes which would require more pumping
unique energy analysis program, is energy.
Evaporator and Condenser
particularly well suited for this type of ARI Standard 550/590 provides chiller
Data Tables
analysis, as well as for economic performance certification for the full load
Evaporator and condenser data is shown
evaluation of equipment and system condition and the NPLV (non-standard
in the Performance Data section. It
alternatives. part load value). The NPLV uses a
includes minimum and maximum water
flow limits and water connection sizes for Local utilities may offer substantial generic weighted chiller load profile to
all standard pass configurations and tube monetary rebates for centrifugal chillers simplify certification of part load
type. Pressure drops are calculated by with specific operating kW ratings. performance data. Although these
the CenTraVac computer selection Contact your local utility representative values are not necessarily a precise
program. or Trane sales office for further indicator of actual energy use, they do
information. provide a basis for comparison.
The electrical rate structure is a key
component of an economic evaluation.
Most power bills are constituted of a
significant demand charge in addition to
the usage charge. The full load power
consumption of the chiller plant is likely
to set the kW peak and demand charge
for the billing period. This places an
increased emphasis on the need to keep
the full load consumption of the chiller
plant low.
26 CTV-PRC007-EN
Performance Evaporator
Data Flow Rates
CTV-PRC007-EN 27
Performance Evaporator
Data Flow Rates
28 CTV-PRC007-EN
Performance Condenser
Data Flow Rates
CTV-PRC007-EN 29
Performance Condenser
Data Flow Rates
30 CTV-PRC007-EN
Jobsite
Connections
and Connections
Copper conductors only should be
connected to the compressor motor due
to the possibility of galvanic corrosion as
a result of moisture if aluminum
conductors are used. Copper conductors
are recommended for supply leads in the
starter panel.
Suggested starter panel line and load
side lug sizes (when lugs are provided)
are noted in the starter submittals. These
submitted lug sizes should be carefully
reviewed for compatibility with
conductor sizes specified by the electrical
engineer or contractor. If they are not
compatible, the electrical engineer or
contractor should specify the required Shipment and Assembly
lug sizes for the particular application. All style hermetic CenTraVac units ship
Ground lugs are provided in the motor as a factory assembled, factory tested
terminal box and starter panel. The package, ready to rig into place on
motor terminals are supplied with factory supplied isolation pads.
connection pads which will
accommodate bus bars or standard
terminal lugs (crimp type
recommended). Terminal lugs are field-
supplied. These connection pads provide
additional surface area to minimize
improper electrical connections. Also,
a 3/8-inch bolt is provided on all
connection pads for mounting the lugs.
Figure 9 illustrates the connection
between the motor connection pads and
the terminal lugs.
CTV-PRC007-EN 31
Tracer Control
Controls Features
Tracer CH530 Predictive Whenever the controller senses that it Using the optional variable flow
can no longer meet its primary objective compensation, the Tracer chiller
Control Strategies without triggering a protective controller reliably accommodates
Todays CenTraVac chillers offer shutdown, it focuses on the most critical variable evaporator water flow and
predictive controls that anticipate and secondary objective. When the virtually eliminates its effect on the
compensate for load changes. Other secondary objective is no longer critical, chilled-water temperature.
control strategies made possible with the controller reverts to its primary Variable Flow Compensation
the Tracer CH530 controls are: objective. Variable flow compensation is a new,
Feedforward Adaptive Control Fast Restart optional, control feature that includes
Feedforward is an open-loop, predictive The controller allows the CenTraVac to water pressure-sensor transducers.
control strategy designed to anticipate restart while the inlet guide vanes are Variable flow compensation improves
and compensate for load changes. It closing and also during the postlube the ability of the chiller to accommodate
uses evaporator entering-water process. If the chiller shuts down on a variable flow, even in combination with
temperature as an indication of load nonlatching diagnostic, the diagnostic an Adaptive Frequency Drive (AFD).
change. This allows the controller to has 3060 seconds to clear itself and
respond faster and maintain stable initiate a fast restart. This includes VPF with an AFD
leaving-water temperatures. momentary power losses. Previous controllers sometimes had
difficulties with variable water flow in
Soft Loading Adaptive Frequency Drive Control combination with variable-speed drives.
The chiller controller uses soft loading The combination of speed control and Variable flow compensation reacts so
except during manual operation. Large inlet guide-vane position is now quickly that this energy-saving
adjustments due to load or setpoint optimized mathematically and controlled combination is now possible.
changes are made gradually, preventing simultaneously. The increased
the compressor from cycling performance of the microprocessor 34F Leaving-Water Temperature
unnecessarily. It does this by internally allows the chiller to operate longer at Another benefit of Feedforward Adaptive
filtering the setpoints to avoid reaching higher efficiency and with greater Control is the ability to operate the
the differential-to-stop or the current stability. CenTraVac chiller at low leaving
limit. Soft loading applies to the leaving evaporator-water temperatures without
Variable-Primary Flow (VPF) the use of glycol.
chilled-water temperature and current-
Chilled-water systems that vary the
limit setpoints. Colder water is generally used in wide
water flow through chiller evaporators
Multi-Objective Limit Arbitration have caught the attention of engineers, delta-T systems, reducing the pumping
There are many objectives that the contractors, building owners, and energy required and making it less
controller must meet, but it cannot operators. Varying the water flow expensive to deliver cooling capacity
satisfy more than one objective at a time. reduces the energy consumed by over long distances. For this reason, 34F
Typically, the controllers primary pumps, while requiring no extra energy leaving-water temperatures are
objective is to maintain the evaporator for the chiller. This strategy can be a frequently used in district cooling
leaving-water temperature. significant source of energy savings, applications, but can also be used in
depending on the application. comfort cooling applications.
Your local Trane office can assist in
making chiller two- or three-pass
selections using 34F to 36F leaving-
water temperatures. Special installation
procedures may be required for
implementing low leaving-water
temperatures.
32 CTV-PRC007-EN
Chiller Plant
Controls Control
Building Automation and Component failure alarm. with a wide range of building
Critical alarm messages. In this automation systems. To take full
Chiller Plant Control latter case, the message is advantage of the capabilities of the
For a preprogrammable and flexible displayed until the operator chiller, incorporate your chiller into a
building automation and chiller plant acknowledges the receipt of the Tracer Summit building automation
control, Trane has developed the Tracer information. From the remote system.
Summit. It can control the operation of station it is also possible to access
But the benefits do not stop at the chiller
the complete installation: chillers, and modify the chiller plants
plant. At Trane, we realize that all energy
pumps, cooling towers, isolating valves, control parameters.
used in your cooling system is
air handlers and terminal units. Trane Remote communication through a
important. That is why we worked
can undertake full responsibility for an modem: As an option, a modem can be
closely with other equipment
optimized automation and energy connected to communicate the plant
manufacturers to predict the energy
management for the entire chiller plant. operation parameters through voice
required by the entire system. We used
The main functions are: grade phone lines.
this information to create patented
Chiller sequencing: equalizes the The remote terminal is a PC workstation control logic for optimizing the HVAC
number of running hours of the chillers. equipped with a modem and software to system efficiency.
Different control strategies are available display the remote plant parameters.
The building owners challenge is to tie
depending on the configuration of the Chiller-Tower Optimization components and applications expertise
installation. Tracer Summit chiller-tower into a single reliable system that
Control of the auxiliaries: includes optimization extends Adaptive Control provides maximum comfort, control and
input/output modules to control the to the rest of the chiller plant. Chiller- efficiency. Tranes Integrated Comfort
operation of the various auxiliary tower optimization is a unique control systems (ICS) are a concept that
equipments (water pumps, valves, algorithm for managing the chiller and combines system components, controls
cooling towers, etc.) cooling-tower subsystem. It considers and engineering applications expertise
the chiller load and real-time ambient into a single, logical and efficient system.
Time of day scheduling: allows the end conditions, then optimizes the tower These advanced controls are fully
user to define the occupancy period, i.e. setpoint temperature to maximize the commissioned and available on every
time of the day, holiday periods and efficiency of the subsystem. piece of Trane equipment, from the
exception schedules. largest chiller to the smallest VAV box.
Integrated Comfort System (ICS)
Optimization of the start/stop time of The onboard Tracer chiller controller is As a manufacturer, only Trane offers this
the installation: based on the designed to be able to communicate universe of equipment, controls and
programmed schedule of occupancy factory installation and verification.
and on the historical record of the
behavior of the temperatures,
calculates the optimal time of start and
stop of the installation to get the best
compromise between energy savings
and comfort of the occupants.
Soft loading: the soft loading function
minimizes the number of chillers that
are operated to satisfy the building
morning pull down, thus preventing an
overshoot of the actual capacity
required. Unnecessary starts are
avoided and the peak current demand
is lowered.
Communication capabilities: several
communication levels are provided:
local, through a PC workstation
keyboard. Summit can be
programmed to send messages to
local or remote workstations and or
a pager in the following cases:
Analog parameter exceeding a
programmed value.
Maintenance warning.
CTV-PRC007-EN 33
Controls Standard Features
Standard Features protection to both the motor and the evaporator pressure reduces the
compressor. pressure differential the compressor
Field Connection must generate while in the heat recovery
The field-connected elements are EarthWise Purge Control
The purge control function provides all mode. Chilled-water reset is also used in
involved in physically turning the chiller combination with the hot-water control.
on or off. This involves ensuring that the the inputs and outputs to control the
purge, optimizing both purge and chiller By resetting the chilled-water
chiller is not in an emergency or external temperature upward, the compressor
stop condition, starting the pumps, and efficiency. The purge controller
communicates with DynaView over the can generate a higher condenser
verifying that flow has been established. pressure, resulting in higher leaving hot-
The optional, factory-supplied flow IPC3 bus communications link,
uploading setpoints and downloading water temperatures.
switch or a customer-supplied
differential- pressure switch can be used data and diagnostics. Hot-Water Control
to prove flow. Phase Voltage Sensors 3 phase In the hot-water mode, the chiller
Includes factory-installed potential produces hot water as its primary
External auto stop (enable/disable) objective, rather than chilled water. As an
transformers in the starter for
Emergency stop monitoring and displaying phase voltage option, the Extended Operation package
and provides over/ undervoltage allows an external controller to enable,
Chilled-water flow contacts
protection. DynaView, TechView and disable, and modulate this mode. It can
Condenser-water flow contacts be performed with or without a
Tracer Summit display the following:
Chilled-water pump relay secondary condenser. See also Heat
Compressor phase voltage Recovery/Auxiliary Condenser option.
Condenser-water pump relay (a-b, b-c, c-a)
Ice-Making Control
Heat Exchanger Control Kilowatts For chillers that have been selected to
Fundamental internal variables that are allow for ice-making operation, the
Power factor (uncorrected)
necessary to control the chiller are standard control package includes the
gathered and acted upon by the heat Chilled-Water Reset ice-making mode. As an option, the
exchanger control function. Chilled-water reset reduces energy Extended Operation package allows an
consumption during periods of the year external controller to enable, disable,
Motor Control and Compressor
when heating loads are high and cooling and modulate this mode.
Protection
loads are reduced. It is based on return
This includes all functions that start, run,
chilled-water temperature. Resetting the
and stop the motor. The starter module
chilled-water temperature reduces the
provides the interface and control of Y-
amount of work that the compressor
delta, across-the-line, primary reactor,
must do by increasing the evaporator
autotransformer, and solid-state starters.
refrigerant pressure. This increased
Analog and binary signals are used to
interface with the solid state starter. An
AFD output signal, included in the AFD
option, controls the Adaptive Frequency Figure 14 Chilled Water Reset
drive. The motor control also provides
34 CTV-PRC007-EN
Optional
Controls Features
Enhanced Protection Package Base-Loading Control While the standard controller is fully
This feature allows an external controller capable of running the chiller in ice-
This optional package includes sensors to directly modulate the capacity of the making mode, installation savings and
and transducers that enable the chiller. It is typically used in applications additional energy savings can be
following protection features: where virtually infinite sources of realized by using the Chiller Plant Control
Enhanced Condenser-Limit Control evaporator load and condenser capacity module of the Tracer building
Includes factory-installed condenser- are available and it is desirable to control automation system. Chiller Plant Control
pressure transducer and interconnecting the loading of the chiller. Two examples anticipates how much ice needs to be
piping and wiring. Provides enhanced are industrial process applications and made at night and operates the system
high-pressure cutout avoidance by cogeneration plants. Industrial process accordingly. The controls are integrated
energizing a relay to initiate head relief. applications might use this feature to with the chillertwo wires and
Note: This option is in addition to the impose a specific load on the facilitys preprogrammed software reduce field-
standard high refrigerant-pressure safety electrical system. Cogeneration plants installation cost and complex custom
contact. might use this feature to balance the programming.
systems heating, cooling, and electrical The CenTraVac chiller is uniquely suited
Compressor-Discharge Refrigerant-
generation. for low-temperature applications like ice
Temperature Protection (optional)
Includes a factory-installed sensor and All chiller safeties and Adaptive Control storage, because it provides multiple
safety cutout on high compressor- functions are in full effect when Base stages of compression. This allows the
discharge temperature. Allows the Loading is enabled. If the chiller chiller to produce ice efficiently, while
chiller controller to monitor compressor approaches full current, the evaporator experiencing less stress than a single-
discharge temperature, which is temperature drops too low, or the stage compression chiller.
displayed at DynaView, TechView, and condenser pressure rises too high, the Hot-Water Control
Tracer Summit. Note: When the chiller is controllers Adaptive Control logic limits This feature allows an external controller
selected with HGBP, this sensor and its the loading of the chiller to prevent the to enable/disable and modulate the hot-
associated protection are included. chiller from shutting down on a safety water control mode. Occasionally,
limit. These limits may prevent the chiller CenTraVac chillers are used to provide
Individual Sensing of Leaving Oil Set
from reaching the load requested by the heating as a primary mission. In this
Temperature For Each Bearing
Base Loading signal. case the external controller or operator
Optional factory-installed sensors allow
high-temperature safety cutouts to An alternative and less radical approach would select a hot-water temperature
monitor the leaving bearing-oil to Base Loading indirectly controls chiller setpoint and the chiller capacity would
temperatures. The chiller controller and capacity. Artificially load the chiller by be modulated to maintain the setpoint.
Tracer Summit display the temperatures. setting the chilled-water setpoint lower Heating is the primary mission and
The high bearing-temperature cutout is than it is capable of achieving. Then, cooling is a waste product or a
fixed at 180F (82.2C). If either bearing modify the chillers load by adjusting the secondary mission. This technique
temperature violates the cutout, a current-limit setpoint. This approach provides application flexibility, especially
latching diagnostic will be generated. provides greater safety and control in multiple-chiller plants in conjunction
stability because it leaves the chilled- with undersized heating plants.
Extended Operation Package water temperature-control logic in effect. The chiller needs only one condenser for
The chilled-water temperature control hot-water control, whereas Heat
Select the extended-operation package responds more quickly to dramatic
for chillers that require external ice- Recovery uses a secondary condenser.
system changes and limits chiller
building control, hot water control, and/ loading prior to reaching an Adaptive Refrigerant Monitor
or base-loading capabilities. This Control limit. The Extended Operation package allows
package also includes a 4-20 mA or 0-10 for a refrigerant monitor to send a 4-20
Vdc analog input for a refrigerant Ice-Making Control mA signal to the DynaView display. It
monitor. This feature allows an external controller can be calibrated to correspond to either
to control the chiller in an ice-storage 0-100 ppm or 0-1,000 ppm concentration
External Ice-building control system. Ice storage is typically used in
External Ice-building relay levels. The concentration level is
areas where high electrical-demand displayed at DynaView, but the chiller
External base-loading control charges can be offset by shifting building
External base-loading relay will not take any action based on the
energy use to off-peak (typically input from the refrigerant monitor.
External hot-water control relay nighttime) hours.
Refrigerant monitor input Alternatively, a refrigerant monitor can
be connected to Tracer Summit, which
has the ability to increase ventilation in
the equipment room in response to high
refrigerant concentrations.
CTV-PRC007-EN 35
Standard
Controls Protections
Tracer Chiller Controller auxiliary contacts. When this input does High-Vacuum Lockout Protection
not prove flow within a fixed time during The controller inhibits a compressor
The chiller controller uses proportional- the transition from Stop to Auto modes start with a latching diagnostic whenever
integral-derivative (PID) control for all of the chiller, or if the flow is lost while the evaporator pressure is less than or
limitsthere is no dead band. This the chiller is in the Auto mode of equal to 3.1 psia for R123. This protects
removes oscillation above and below operation, the chiller will be inhibited the motor by locking out chiller
setpoints and extends the capabilities of from running by a nonlatching operation while the unit is in a high
the chiller. diagnostic. vacuum, to prevent starting when the
Some of the standard protection features Evaporator Limit Protection evaporator is in a high-vacuum state.
of the chiller controller are described in Evaporator Limit is a control algorithm Oil-Temperature Protection
this section. There are additional that prevents the chiller tripping on its Low oil temperature when the oil pump
protection features not listed here. low refrigerant-temperature cutout. The and/or compressor are running may be
High Condenser-Pressure Protection machine may run up to the limit but not an indication of refrigerant diluting the
The chiller controllers condenser limit trip. Under these conditions the intended oil. If the oil temperature is at or below
keeps the condenser pressure under a chilled-water setpoint may not be met, the low oil-temperature setpoint, the
specified maximum pressure. The chiller but the chiller will do as much as it can. compressor is shut down on a latching
runs all the way up to 100 percent of the The chiller will deliver as much cold diagnostic and cannot be started. The
setpoint before reducing capacity using water as possible even under adverse diagnostic is reported at the user
its adaptive control mode. conditions. interface. The oil heater is energized in
Low Evaporator-Water Temperature an attempt to raise the oil temperature
Starter-Contactor Failure Protection above the low oil-temperature setpoint.
The chiller will protect itself from a Low evaporator-water temperature
starter failure that prevents the protection, also known as Freeze Stat High oil-temperature protection is used
compressor motor from disconnecting protection, avoids water freezing in the to avoid overheating the oil and the
from the line to the limits of its evaporator by immediately shutting bearings.
capabilities. down the chiller and attempting to Low Differential Oil-Pressure Protection
operate the chilled-water pump. This Oil pressure is indicative of oil flow and
The controller starts and stops the chiller protection is somewhat redundant with
through the starter. If the starter active oil-pump operation. A significant
the Evaporator Limit protection, and drop in oil pressure indicates a failure of
malfunctions and does not disconnect prevents freezing in the event of extreme
the compressor motor from the line the oil pump, oil leakage, or other
errors in the evaporator- refrigerant blockage in the oil-circuit.
when requested, the controller will temperature sensor.
recognize the fault and attempt to The differential pressure during oil
protect the chiller by operating the The cutout setting should be based on pump, compressor prelube mode
evaporator-and condenser-water pumps the percentage of antifreeze used in the should not fall below 12 psid. A failure
and attempting to unload the customers water loop. The chillers on this parameter generates a shutdown
compressor. operation and maintenance diagnostic within 2 seconds of the
documentation provides the necessary differential pressure falling below 2/3 of
Loss of Water-Flow Protection information for percent antifreeze and
DynaView has an input that will accept a the low differential oil pressure cutout.
suggests leaving-water temperature- When the compressor is running, the
contact closure from a proof-of-flow cutout settings for a given chilled-water
device such as a flow switch or pressure diagnostic is issued when the differential
temperature setpoint. pressure falls below the cutout setpoint
switch. Customer wiring diagrams also
suggest that the flow switch be wired in for more than (cutout x 3) seconds.
series with the cooling-water
(condenser-water) pump starters
36 CTV-PRC007-EN
Standard
Controls Protections
Excessive Purge Detection Phase-Loss Protection may result in different levels at which
Pump-out activity is indicative of the The controller will shut down the chiller this may occur. It is difficult to define an
amount of air leaking into the chiller if any of the three phase currents feeding exact voltage sag or voltage level at
refrigerant system. The operator should the motor drop below 10 percent RLA. which a particular motor will no longer
be informed when the air-leakage rate The shutdown will result in a latching consume power, but we are able to
changes. Through this setpoint, the phase-loss diagnostic. The time to trip is make some general statements
operator can indicate the expected 1 second at minimum, 3 seconds concerning MPL protection:
leakage rate, and can be notified though maximum. The chiller will remain running under the
a diagnostic if the rate is higher than
Phase Reversal/Rotation Protection following conditions:
expected.
The controller detects reverse phase Line-voltage sag of 1.5 line cycles or
Occasionally, when a service technician rotation and provides a latching less for any voltage magnitude sag
performs a mechanical repair on the diagnostic when it is detected. The time
chiller, an unusually high pump-out rate to trip is 0.7 seconds. Phase-rotation Control-voltage sags of less than 3 line
is expected for a certain period of time protection can be disabled in TechView. cycles for any magnitude sag
following the procedure. The service Control-voltage sags of 40 percent or
excessive pump-out override allows the Momentary Power Loss and Distribution
Fault Protection less for any amount of time
technician to specify a time period for
the purge system to rid the chiller of air Three-phase momentary power loss Second-order or lower harmonic
in the system. This temporarily suspends (MPL) detection gives the chiller content on the line
excessive purge detection. improved performance through many
The chiller may shut down under the
different power anomalies. MPLs of 2.5
Phase-Unbalance Protection following conditions:
cycles or longer will be detected and
Phase-unbalance protection is based on cause the unit to shut down. The unit will Line-voltage sags of 1.5 or more line
an average of the three phase-current be disconnected from the line within 6 cycles for voltage dips of 30 percent or
inputs. The ultimate phase-unbalance line cycles of detection. If enabled, MPL more
trip point is 30 percent. In addition, the protection will be active any time the Control-voltage sags of 3 or more line
RLA of the motor is derated by resetting compressor is running. MPL is not active cycles for voltage dips of 40 percent or
the active current-limit setpoint based on on reduced-voltage starters from the more
the current unbalance. The RLA derate initial start signal through transition. The
protection can be disabled in the field- MPL diagnostic is an automatic reset Third-order or higher harmonic content
startup menu. diagnostic. MPL protection can be on the line
The following derates apply when the disabled in TechView.
phase-unbalance limit is enabled: An MPL has occurred when the motor
10% unbalance = 100% RLA derate no longer consumes power. An MPL
15% unbalance = 90% RLA derate may be caused by any drop or sag in the
20% unbalance = 85% RLA derate voltage that results in a change in the
25% unbalance = 80% RLA derate direction of power flow. Different
30% unbalance = Shutdown operating conditions, motor loads, motor
size, inlet guide vane (IGV) position, etc.
CTV-PRC007-EN 37
Standard
Controls Protections
38 CTV-PRC007-EN
Variable Water-Flow
Controls Compensation Option
Variable Flow Compensation Another benefit is disturbance rejection. 1.5F variation in chilled-water
This option includes transducers for the Figure 17 shows the test results from temperature. It is unlikely that a chiller
differential evaporator-and condenser- step changes in water flow with application would be making water-flow
water pressures (psid). Flow switches or increasing magnitudes. The leaving changes of this magnitude. The results
some other means to prove flow are still chilled-water temperature remains demonstrate that the chiller is more than
required and must be field connected. largely unaffected. Even the most severe capable of supporting variable water-
One type of sensor handles all pressure changedropping water flow 66 percent flow applications.
ranges up to 300 psig. in 30 seconds caused only a small,
The following data will be shown at the
DynaView and TechView displays and at
Figure 15 Capacity Control with Variable Flow Compensation
Tracer Summit.
Evaporator and condenser differential
water pressures (psid)
Evaporator and condenser gpm
Evaporator tons
How It Works
The Tracer chiller controller uses a
patented, variable, water-flow
compensation algorithm to maintain
stable, precise capacity control. Variable
flow compensation is a new optional
control feature for CTV chillers.
It will automatically adjust capacity
control to:
Maintain control stability at low flow.
Reject variable-flow disturbance.
If the water-pressure transducer fails and
the flow switch continues to prove flow,
water-flow compensation will be
disabled and the design delta T will be
used.
For applications designed to operate
with variable-primary (VPF) water-flow,
variable flow compensation allows the
chiller to respond quickly to accelerating
or decelerating water. By automatically
adjusting the control gain, large changes
in the water-flow rate can be tolerated.
Data shown on Figure 15 demonstrates
water-temperature control with flow
compensation enabled. The chilled-
water temperature remains stable, even
when the water-flow rate drops 50
percent in 30 seconds. In contrast, Figure
16 demonstrates water-temperature
control without flow compensation.
CTV-PRC007-EN 39
Variable Water-Flow
Controls Compensation Option
Figure 17 Capacity Control with Flow Changes and Variable Flow Compensation
40 CTV-PRC007-EN
60 Hz Compressor
Weights (IP & SI Units)
The weight information provided here should be used for general information purposes only. Trane does not recommend using
this weight information for considerations relative to chiller handling. The large number of variances between chiller selections
drives variances in chiller weights that are not recognized in this table.
Table 5 Weights 60 Hz Compressors
Without With Starters
Operating Weights Shipping Weights Operating Weights Shipping Weights
MODL NTON CPK EVSZ CDSZ lbs kg lbs kg lbs kg lbs kg
350 - 485 453 050L 050L 21152 9595 18617 8445 22234 10085 19699 8935
350 - 485 453 050S 050L 19814 8988 17668 8014 20896 9478 18750 8505
350 - 485 453 050S 050S 18925 8584 16937 7683 20007 9075 18019 8173
350 - 485 453 080L 080L 30751 13949 26866 12186 31833 14439 27948 12677
350 - 485 453 080S 080L 28589 12968 25254 11455 29671 13459 26336 11946
350 - 485 453 080S 080S 26876 12191 23787 10790 27958 12682 24869 11281
555 - 640 588 050L 050L 21620 9807 19085 8657 23094 10475 20559 9326
555 - 640 588 050S 050L 20282 9200 18136 8226 21756 9869 19610 8895
C 555 - 640 588 050S 050S 19393 8797 17405 7895 20867 9465 18879 8564
V 555 - 640 588 080L 080L 31219 14161 27334 12399 32693 14830 28808 13067
H 555 - 640 588 080S 080L 29057 13180 25722 11667 30531 13849 27196 12336
F 555 - 640 588 080S 080S 27344 12403 24255 11002 28818 13072 25729 11671
650 - 910 957 080L 080L 32688 14827 28803 13065 34249 15535 30364 13773
650 - 910 957 080S 080L 30526 13847 27191 12334 32087 14555 28752 13042
650 - 910 957 080S 080S 28813 13070 25724 11668 30374 13778 27285 12376
650 - 910 957 142L 142L 42739 19386 36476 16546 44300 20094 38037 17254
650 - 910 957 142M 142L 41548 18846 35653 16172 43109 19554 37214 16880
1060 - 1280 1228 142E 142L 44713 20282 38063 17265 46130 20925 39480 17908
1060 - 1280 1228 142L 142L 43436 19703 37173 16862 44853 20345 38590 17504
1060 - 1280 1228 142M 142L 42245 19162 36350 16488 43662 19805 37767 17131
1060 - 1280 1228 210L 210L 52882 23987 44876 20356 54299 24630 46293 20999
1470 1340 210L 210L 56217 25500 48211 21869 57299 25991 49293 22359
1470 - 1720 1340 250E 250L 68393 31023 57807 26221 69475 31514 58889 26712
230 - 320 287 032L 032L 16691 7571 15145 6870 17773 8062 16227 7361
230 - 320 287 032S 032L 15795 7165 14484 6570 16877 7655 15566 7061
230 - 320 287 032S 032S 14960 6786 13730 6228 16042 7277 14812 6719
C 230 - 320 287 050L 050L 20650 9367 18081 8202 21732 9858 19163 8692
V 230 - 320 287 050S 050L 19312 8760 17132 7771 20394 9251 18214 8262
H 230 - 320 287 050S 050S 18278 8291 16248 7370 19360 8782 17330 7861
E 360 - 500 453 050L 050L 22187 10064 19618 8899 23269 10555 20700 9390
360 - 500 453 050S 050L 20849 9457 18669 8468 21931 9948 19751 8959
360 - 500 453 050S 050S 19815 8988 17785 8067 20897 9479 18867 8558
360 - 500 453 080L 080L 30758 13952 26806 12159 31840 14443 27888 12650
360 - 500 453 080S 080L 28595 12971 25194 11428 29677 13461 26276 11919
360 - 500 453 080S 080S 27155 12318 24016 10894 28237 12808 25098 11384
C 1500 - 2000 745 210D 210D 82345 37352 70434 31949 84211 38198 72300 32795
D 2100 - 2500 1062 250D 250D 91786 41634 77908 35339 92900 42139 79022 35844
H 3000 1340 250M 250M 115613 52442 98544 44700 N/A N/A N/A N/A
F 3500 1340 250X 250X 119662 54279 100297 45495 N/A N/A N/A N/A
These values represent chiller weights that include the following:
Heaviest possible bundle and heaviest possible motor voltage combination for the applicable family of chillers
Applicable compressor
TECU .028 tubes
150 psig non-marine waterboxes
Chillers-with-starter values include the weight of the heaviest possible starter
Operating weights include the heaviest possible refrigerant charge weight
CTV-PRC007-EN 41
50 Hz Compressor
Weights (IP & SI Units)
The weight information provided here should be used for general information purposes only. Trane does not recommend using
this weight information for considerations relative to chiller handling. The large number of variances between chiller selections
drives variances in chiller weights that are not recognized in this table.
Table 6 Weights 50 Hz Compressors
Without With Starters
Operating Weights Shipping Weights Operating Weights Shipping Weights
MODL NTON CPK EVSZ CDSZ lbs kg lbs kg lbs kg lbs kg
480 - 565 489 050L 050L 23384 10607 20815 9442 24466 11098 21897 9932
480 - 565 489 050S 050L 22046 10000 19866 9011 23128 10491 20948 9502
480 - 565 489 050S 050S 21323 9672 19324 8765 22405 10163 20406 9256
480 - 565 489 080L 080L 31955 14495 28003 12702 33037 14986 29085 13193
C 480 - 565 489 080S 080L 29792 13514 26391 11971 30874 14004 27473 12462
V 480 - 565 489 080S 080S 29154 13224 26065 11823 30236 13715 27147 12314
H 670 - 780 621 080L 080L 33266 15089 29314 13297 34348 15580 30396 13788
G 670 - 780 621 080S 080L 31103 14108 27702 12566 32185 14599 28784 13056
670 - 780 621 080S 080S 30465 13819 27376 12418 31547 14310 28458 12909
670 - 780 621 142L 142L 44705 20278 38442 17437 45787 20769 39524 17928
670 - 780 621 142M 142L 43514 19738 37619 17064 44596 20229 38701 17555
920 - 1067 621 142L 142L 45545 20659 39282 17818 46627 21150 40364 18309
920 - 1067 621 142M 142L 44354 20119 38459 17445 45436 20610 39541 17936
920 - 1067 621 210L 210L 57319 26000 49375 22397 58401 26491 50457 22887
190 - 270 242 032L 032L 16719 7584 15173 6882 17801 8075 16255 7373
190 - 270 242 032S 032L 15823 7177 14512 6583 16905 7668 15594 7073
190 - 270 242 032S 032S 14988 6799 13758 6241 16070 7289 14840 6731
C 190 - 270 242 050L 050L 20678 9380 18109 8214 21760 9870 19191 8705
V 190 - 270 242 050S 050L 19340 8773 17160 7784 20422 9263 18242 8275
H 190 - 270 242 050S 050S 18306 8304 16276 7383 19388 8794 17358 7874
E 300 - 420 379 050L 050L 21569 9784 19000 8618 22651 10274 20082 9109
300 - 420 379 050S 050L 20231 9177 18051 8188 21313 9668 19133 8679
300 - 420 379 050S 050S 19197 8708 17167 7787 20279 9199 18249 8278
300 - 420 379 080L 080L 30140 13672 26188 11879 31222 14162 27270 12370
300 - 420 379 080S 080L 27977 12690 24576 11148 29059 13181 25658 11638
300 - 420 379 080S 080S 26537 12037 23398 10613 27619 12528 24480 11104
CD 1250 - 1750 621 210D 210D 86267 39131 74805 33932 88431 40112 76969 34913
HG 2150 621 250D 250D 97424 44192 83035 37665 97862 44390 83473 37863
These values represent chiller weights that include the following:
Heaviest possible bundle and heaviest possible motor voltage combination for the applicable family of chillers
TECU .028 tubes
Applicable compressor
150 psig non-marine waterboxes
Chillers-with-starter values include the weight of the heaviest possible starter
Chillers-without-starter values do not include a weight-add for the starter
Operating weights include the heaviest possible refrigerant charge weight
42 CTV-PRC007-EN
Physical Piping
Dimensions Connections
CTV-PRC007-EN 43
Physical 50 & 60 Hz Compressor
Dimensions (IP & SI Units)
Table 8 for Figure 18 Physical Dimensions 50 Hz Compressor Chillers (IP and SI Units)
IP UNITS
Envelope Clearance Unit Dimensions
W/O Unit With Unit W/O Unit With Unit
Shell Mounted Mounted Tube Mounted Mounted
Shell Arrange- Starters Starters Pull Starters Starters
COMP Size ment EL EW EW CL1 CL2 Length Height Width Width
190-270 320 SS
26' 5 10' 6 1/4 11' 7 1/2
11' 9 3' 5 11' 3 7' 9 3/4 5 9 1/4 6' 7 1/2
190-270 320 33' 11 1/4
SL & LL 10' 6 1/4 11' 7 1/2
15' 6 3' 5 15' 0 1/4 7' 9 3/4 5 9 1/4 6' 7 1/2
190-270 500 26' 6 3/8
SS 11' 4 5/8 12' 9 7/8
11' 9 3' 6 3/8 11' 3 8' 2 1/4 6' 7 5/8 7' 9 7/8
C 190-270 500 34' 0 5/8
SL & LL 11' 4 5/8 12' 9 7/8
15' 6 3' 6 3/8 15' 0 1/4 8' 2 1/4 6' 7 5/8 7' 9 7/8
V 300-420 500 26' 6 3/8
SS 11' 4 5/8 12' 8 1/2
11' 9 3' 6 3/8 11' 3 8' 2 1/2 6' 7 5/8 7' 8 1/2
H 300-420 500 34' 0 5/8
SL & LL 11' 4 5/8 12' 8 1/2
15' 6 3' 6 3/8 15' 0 1/4 8' 2 1/2 6' 7 5/8 7' 8 1/2
1
E 300-420 800 SS
27' 4 /4 12' 5 1/4 13' 9 1/4
11' 9 1
4' 4 /4 11' 3 9' 6 3/8 7' 11 1/4 8' 7 5/8
300-420 800 34' 10 1/2
SL & LL 12' 5 1/4 13' 9 1/4
15' 6 4' 4 1/4 15' 0 1/4 9' 6 3/8 7' 11 1/4 8' 7 5/8
480-565 500 26' 6 3/8
SS 11' 4 5/8 13' 7 5/8
11' 9 3' 6 3/8 11' 3 8' 7 1/4 6' 7 5/8 7' 8 3/4
480-565 500 34' 0 5/8
SL & LL 11' 4 5/8 13' 7 5/8
15' 6 3' 6 3/8 15' 0 1/4 8' 7 1/4 6' 7 5/8 7' 8 3/4
480-565 800 27' 4 1/4
SS 12' 5 1/4 13' 1 5/8
11' 9 4' 4 1/4 11' 3 9' 8 7' 11 1/4 8' 7 5/8
C 480-565 800 34' 10 1/2
SL & LL 12' 5 1/4 13' 1 5/8
15' 6 4 4 1/4 15' 0 1/4 9' 8 7' 11 1/4 8' 7 5/8
V 670-780 800 27' 4 1/4
SS 12' 10 13' 10 11' 9 4' 4 1/4 11' 3 9' 6 3/4 8' 4 9' 1 3/4
H 670-780 800 34' 10 1/2
SL & LL 12' 10 13' 10 15' 6 4' 4 1/4 15' 0 1/4 9' 6 3/4 8' 4 9' 1 3/4
1
G 670-780 1420 ML & LL
35' 5 /4 14' 5 3/4 14' 4 1/2
15' 6 4' 11 15' 0 1/4 1
10' 1 /8 9' 11 3/4 10' 3 7/8
920-1067 1420 35' 5 1/4
ML & LL 14' 5 3/4 14' 4 1/2
15' 6 4' 11 15' 0 1/4 1
10' 1 /8 9' 11 3/4 10' 3 7/8
920-1067 2100 35' 5 1/4
LL 15 3 3/4 15' 8 3/8
15' 6 4' 11 15' 0 1/4 11' 0 7/8 10' 9 3/4 10' 10
SI UNITS (mm)
190-270 320 SS 8052 3207 3543 3581 1041 3429 2380 1759 2019
190-270 320 SL & LL 10344 3207 3543 4724 1041 4578 2380 1759 2019
190-270 500 SS 8087 3470 3909 3581 1076 3429 2494 2022 2384
C 190-270 500 SL & LL 10379 3470 3909 4724 1076 4578 2494 2022 2384
V 300-420 500 SS 8087 3470 3874 3581 1076 3429 2502 2022 2350
H 300-420 500 SL & LL 10379 3470 3874 4724 1076 4578 2502 2022 2350
E 300-420 800 SS 8338 3867 4198 3581 1327 3429 2905 2419 2632
300-420 800 SL & LL 10630 3867 4198 4724 1327 4578 2905 2419 2632
480-565 500 SS 8087 3470 4156 3581 1076 3429 2624 2022 2356
480-565 500 SL & LL 10379 3470 4156 3581 1076 4578 2624 2022 2356
480-565 800 SS 8338 3867 4003 4724 1327 3429 2946 2419 2632
C 480-565 800 SL & LL 10630 3867 4003 4724 1327 4578 2946 2419 2632
V 670-780 800 SS 8338 3912 4216 3581 1327 3429 2915 2540 2788
H 670-780 800 SL & LL 10630 3912 4216 4724 1327 4578 2915 2540 2788
G 670-780 1420 ML & LL 10754 4413 4381 4724 1499 4578 3077 3042 3146
920-1067 1420 ML & LL 10754 4413 4381 4724 1499 4578 3077 3042 3146
920-1067 2100 LL 10801 4667 4667 4724 1499 4578 3375 3296 3302
CL1 CAN BE AT EITHER END OF MACHINE AND IS REQUIRED FOR TUBE PULL CLEARANCE.
CL2 IS ALWAYS AT THE OPPOSITE END OF MACHINE FROM CL1 AND IS REQUIRED FOR SERVICE CLEARANCE.
44 CTV-PRC007-EN
Physical 60 Hz Compressor
Dimensions (IP Units)
CL1 CAN BE AT EITHER END OF MACHINE AND IS REQUIRED FOR TUBE PULL CLEARANCE.
CL2 IS ALWAYS AT THE OPPOSITE END OF MACHINE FROM CL1 AND IS REQUIRED FOR SERVICE CLEARANCE.
*Dimensions for low-voltage unit-mounted starters. Medium-voltage starters are also available for unit mounting.
CTV-PRC007-EN 45
Physical 50 & 60 Hz
Dimensions (IP Units)
WIDTH
SPACE ENVELOPE
1 6 (457 mm)
RECOMMENDED
CLEARANCE
EW WIDTH
EL
Table 10 Physical Dimensions Dual 50 and 60 Hz Compressor Units (IP and SI Units)
Envelope Clearance Unit Dimensions
IP Units
W/O Unit With Unit W/O Unit With Unit
Shell Mounted Mounted
Tube Mounted Mounted
Shell Arrange- Starters Starters
Pull Starters Starters
Type NTON Size ment EL EW EW
CL1 CL2 Length Height Width Width
CDHF 3500 250X XX 67' 6" 16' 3" N/A
30' 6" 7' 0" 30' 0" 11' 9 3/8" 11' 5 1/4" N/A
CDHF 3000 250M MM 59' 6" 16' 3" N/A
26' 6" 7' 0" 26' 0" 11' 9 3/8" 11' 5 1/4" N/A
CDHF 2100-2500 250D DD 50' 6" 16' 9" 16'9"
22' 0" 7' 0" 21' 6" 11'4 7/8" 11' 10 1/2" 11' 10 1/2"
CDHG 2150 250D DD 50' 6" 16' 9" 16' 9"
22' 0" 7' 0" 21' 6" 11' 4 7/8" 11' 10 1/2" 11' 10 1/2"
CDHF 1500-2000 210D DD 50' 6" 15' 9" 15' 11"
22' 0" 7' 0" 21' 6" 11' 0 3/4" 10' 11 1/2" 11' 1 5/8"
CDHG 1250-1750 210D DD 50' 6" 15' 9" 15' 11"
22' 0" 7' 0" 21' 6" 11' 0 3/4" 10' 11 1/2" 11' 1 5/8"
SI Units
CDHF 3500 250X XX 20574 4953 N/A 9297 2134 9144 3591 3487 N/A
CDHF 3000 250M MM 18136 4953 N/A 8078 2134 7925 3591 3487 N/A
CDHF 2100-2500 250D DD 15392 5105 5105 6706 2134 6553 3477 3620 3620
CDHG 2150 250D DD 15392 5105 5105 6706 2134 6553 3477 3620 3620
CDHF 1500-2000 210D DD 15392 4801 4851 6706 2134 6553 3372 3340 3395
CDHG 1250-1750 210D DD 15392 4801 4851 6706 2134 6553 3372 3340 3395
CL1 CAN BE AT EITHER END OF MACHINE AND IS REQUIRED FOR TUBE PULL CLEARANCE.
CL2 IS ALWAYS AT THE OPPOSITE END OF MACHINE FROM CL1 AND IS REQUIRED FOR SERVICE CLEARANCE.
46 CTV-PRC007-EN
Physical Waterbox Connection
Dimensions Arrangement
These graphics are intended to help you visualize the possible connections/combinations that may be available for your unit. You must contact
your local Trane office who can configure your selection as an as-built drawing to confirm it is available and to provide appropriate dimensions.
CTV-PRC007-EN 47
Physical Waterbox Lengths
Dimensions (IP & SI Units)
48 CTV-PRC007-EN
Physical Dual Compressor
Dimensions Chillers
CTV-PRC007-EN 49
Mechanical
Specifications
50 CTV-PRC007-EN
Mechanical
Specifications
CTV-PRC007-EN 51
Mechanical
Specifications
52 CTV-PRC007-EN
Mechanical
Specifications
The panel features machine protection The controller is capable of receiving Insulation
shutdown requiring manual reset for: signals from a variety of control sources
(which are not mutually exclusive i.e. Factory applied insulation is available on
low evaporator refrigerant temperature all units. All low temperature surfaces
high condenser refrigerant pressure any combination of control sources can
coexist simultaneously) and of being are covered with 3/4-inch Armaflex II or
low differential oil pressure equal (thermal conductivity = 0.28 Btu/hr-
low oil flow programmed at the keypad as to which
control source has priority. Control ft2), including the evaporator, waterboxes
low oil temperature and suction elbow. The economizer and
excessive loss of communication sources can be:
motor cooling lines are insulated with 3/
critical sensor or detection circuit faults The local operator interface (standard) 8 and
free-cooling valve closure failure (free- The remote operator interface 1
/2 insulation respectively.
cooling applications only) (optional)
extended compressor surge A 4-20 mA or 2-10 vdc signal from an
actuator drive circuit fault external source (interface optional,
Refrigerant Pumpout/
control source not supplied by chiller Reclaim Connections
The display also provides reports that are
organized into six groupings: Evaporator manufacturer) Connections are factory provided as
, Condenser, Compressor, Motor, Purge, Tracer Summit building automation standard to facilitate refrigerant reclaim/
and the ASHRAE Chiller Log. Each report system (interface optional) removal required during maintenance or
contains data that is accessed by Process computer (interface optional, overhaul in accordance with ANSI/
scrolling through the menu items. control source not supplied by chiller ASHRAE 15.
Each grouping will have a heading which manufacturer)
describes the type of data in that Generic BAS (interface optional, control Painting
grouping. This data includes: source not supplied by chiller
manufacturer) All painted CenTraVac surfaces are
All water temperatures and setpoints coated with two coats of air-dry beige
Current chiller operating mode The control source with priority will then primer-finisher prior to shipment.
Last 10 diagnostics determine the active setpoints via the
signal that is sent to the control panel.
Control source (i.e. local panel, external Unit Mounted Starter Options
source, remote BAS)
Current limit setpoint Isolation Pads Low-voltage (200 - 600 V) unit-mounted
starters can either be star-delta or solid-
Water flows (optional) Isolation pads are supplied with each state in a NEMA 1 enclosure.
Water pressure drops (optional) CenTraVac chiller for placement under
Outdoor air temperature (optional) all support points. They are constructed Medium-voltage starters (2300 - 6600 V)
Saturated refrigerant temperatures and of molded neoprene. are available to unit mount on most sizes
pressures in full-voltage, primary reactor, or auto
Purge suction temperature transformer.
Refrigerant and Oil Charge
Evaporator refrigerant liquid level
Condenser liquid refrigerant A full charge of refrigerant and oil is
temperature supplied with each unit. The oil ships in
Compressor starts and hours running the units oil sump and the refrigerant
Phase currents ships directly to the jobsite from
Phase voltages refrigerant suppliers.
Watts and power factor (optional)
Oil temperature and flow Thermometer Wells and Sight
Motor winding temperatures Glasses
Bearing temperatures (optional)
Refrigerant detection external to chiller In addition to the thermowells provided
in ppm (optional) for use with the standard unit safety
controls, a well is provided for
measurement of the liquid refrigerant
condensing temperature and a coupling
for the evaporating temperatures. Sight
glasses are provided for monitoring oil
charge level, oil flow, compressor
rotation and purge condenser drum.
CTV-PRC007-EN 53
Mechanical
Specifications
Trane Adaptive Frequency Motor thermal overload protection Overvoltage, undervoltage protection
102% continuous, 140% for 1.5
Drive (AFD) seconds, 108% for 60 seconds.
Digitally displayed on the chiller
controller: output speed in hertz, output
The Trane AFD is a closed-loop, liquid- Minimum efficiency of 97% at rated speed in rpm, input line voltage, input
cooled, microprocessor-based PWM load and 60 hertz. line kW, output/load amps, average
design. The AFD is both voltage- and current in % RLA, load power factor,
current-regulated. The output power Soft start, linear acceleration, coast to
stop. fault, AFD transistor temperature
devices are IGBT transistors.
Adjustable frequency from 38 to 60 Environmental ratings:
The AFD is factory-mounted on the 32F to 104 (0C to 40) operating ambient
chiller and ships completely assembled, hertz.
temperature
wired and tested. Patented Trane AFD All control circuit voltages are
control logic is specifically designed to physically and electrically isolated from Altitude to 3300 feet (1000m),
interface with the centrifugal water power circuit voltage. amperage derate of 1% per every 300
chiller controls. AFD control adapts to feet above 3300 feet
the operating ranges and specific 150% instantaneous torque available
for improved surge control. Humidity, 95% non-condensing
characteristics of the chiller and chiller
efficiency is optimized by coordinating Output line-to-line and line-to-ground Refrigerant-Cooled Trane AFD Design
compressor motor speed and short circuit protection. features
compressor inlet guide vane position. Integrated active rectification control of
Line dip ride through. the building AC power assures low line-
The chilled-water control and AFD
control work together to maintain the AFD can be started without a motor generated harmonics back to the users
chilled-water setpoint, improve efficiency connected. power grid. This Trane AFD has 5% or
and avoid surge. If a surge is detected, less current harmonic distortion (TDD)
Chiller Unit Controller Features for all at the AFD.
AFD surge avoidance logic makes Trane AFDs
adjustments to move away from and The chiller unit controller capabilities Active input rectifier will regulate a
avoid surge at similar conditions in the provide for the control/configuration unity displacement power factor of .99
future. interface to, and the retrieval/display of or better.
Standard Design Features for All Trane AFD-related data. AFD standard design Full motor voltage is applied regardless
AFDs features controlled through the chiller of the input voltage.
NEMA 1 ventilated enclosure with a controller include:
Water-Cooled Trane AFD Design
hinged, locking door is tested to a short Current limited to 100% features
circuit withstand rating of 65,000 amps. DC bus filter choke to limit harmonic
It includes a padlockable door-mounted Output speed reference via IPC3
communication bus from the chiller distortion
circuit breaker/shunt trip with AIC rating
of 65,000 amps. The entire package is controller to the AFD Input displacement power factor will
UL/CUL listed. Motor overload protection exceed .96 regardless of speed and
load.
Simple modular construction. Motor overtemperature protection
Input Line Reactor Option (water-cooled
The drive is rated for 480/60/3 input Automatic restart after a power outage AFD only)
power, +/-10%, with a drive overload or power dip
capability of 100% continuous to 150% Field-installed option is located on the
Loss of follower signal in the event of input side of the AFD to reduce harmonic
for five seconds. loss of input speed signal the AFD will distortion and help meet IEEE 519
default to 38 hertz or hold speed based guidelines. NEMA 1 enclosure, 5%
on last reference received. impedance.
Phase loss, reversal, imbalance
protection
54 CTV-PRC007-EN
Standard
Conversion
Table
CTV-PRC007-EN 55
Trane is a participant
in the Green Seal
Program
For more information contact your local sales office Trane has a policy of continuous product and product data improvement and reserves the right to change
or e-mail us at comfort@trane.com design and specifications without notice.