U#2 WB DEFECT LIST FROM 01.06.

20
S NO DATE WB NO DEFECT AS PER OPERATION
1 05.06.2017 74 OVER LOAD
2 05.06.2017 75 OVER LOAD
3 05.06.2017 88 NTC
4 05.06.2017 38 NTC
5 05.06.2017 55 NOT OK

1 06.06.2017 38 NTC
2 06.06.2017 55 AUTO START
3 06.06.2017 118 OLR
4 06.06.2017 127 OLR
5 06.06.2017 128 OLR/NTC
6 06.06.2017 129 OLR
7 06.06.2017 130 OLR
8 06.06.2017 123 TRAVERSE MOTOR NOT ROTATE

1 08.06.2017 35 OVER RUN


2 08.06.2017 63 OVER RUN
3 08.06.2017 87 OVER RUN
4 08.06.2017 54 OVER RUN
5 08.06.2017 75 OVER RUN
6 08.06.2017 41 MANUAL RECTRACT
7 08.06.2017 64 MANUAL RECTRACT
8 08.06.2017 55 O/L
9 08.06.2017 86 OVER RUN

1 10.06.2017 38 NOT STARTED


2 10.06.2017 110 NTC
3 10.06.2017 114 NTC

1 13.06.2017 10 OLR
2 13.06.2017 18 NTC
3 13.06.2017 38 NTC
4 13.06.2017 55 NTC
5 13.06.2017 54 110V AC FAIL
6 13.06.2017 63 AUTO PICK UP
7 13.06.2017 65 110V AC FAIL
8 13.06.2017 66 110V AC FAIL
9 13.06.2017 118 OLR
10 13.06.2017 128 OLR
11 13.06.2017 130 OLR

1 14.06.2017 132 NOT START


2 14.06.2017 18 NTC
3 14.06.2017 55 L/R
4 14.06.2017 62 L/R
5 14.06.2017 75 L/R
6 14.06.2017 87 L/R
7 14.06.2017 38 NTC

1 15.06.2017 18 MR
2 15.06.2018 54 LIMIT SWITCH PROBLEM
3 15.06.2019 55 LIMIT SWITCH PROBLEM
4 15.06.2020 75 LR
5 15.06.2021 87 LR
U#2 WB DEFECT LIST FROM 01.06.2017 TO 15.06.2017
ACTUAL DEFECT LOCAL TRIAL
LSTE PROBLEM SO REPLACE IT OK
ELECTRICALLY CHECK OK OK
ELECTRICALLY CHECK OK OK
LSTE PROBLEM -
CF PICK UP CONTINUE -

LSTE & MODULE SLIDING CONTACT PROBLEM RECTIFIED OK


DCS COMMOND CONTINUE COMING -
CR CONTACTOR FAULTY SO REPLACE IT OK
ELECTRICALLY CHECK OK OK
FIELD PUSH PROBLEM OK
TREVERSE & ROTORY FUSE OUT PUT LOOSE OK
PSS SWITCH R PHASE SUPPLY NOT COMING OK
TRAVERSE MOTOR OUT PUT TB R PHASE CABLE OPEN OK

ADJUST LSTR OK
ADJUST LSTR OK
ADJUST LSTR OK
ADJUST LSTR OK
ADJUST LSTR OK
LSTR N/A -
LSTR N/A -
CHECK & RESET OK
LSTS REPLACE BY NEW OK

ELECTRICALLY OK -
ELECTRICALLY OK OK
RECTRACT PUSH BUTTOM PROBLEM RECTIFIED OK

ROTORY MOTOR FUSE FAIL SO REPLACE IT OK


ELECTRICALLY OK -
ELECTRICALLY OK -
ELECTRICALLY OK -
CHECKED FOUND TB-13 WIRE REMOVED OK
ELECTRICALLY OK OK
ELECTRICALLY OK OK
ELECTRICALLY OK OK
ELECTRICALLY OK PENDING
POWER CABLE REMOVED FROM FIELD WITH OUT PERMIT -
ELECTRICALLY OK PENDING

ELECTRICALLY OK PENDING
SLIDING CONTACT PROBLEM OK
ELECTRICALLY OK OK
ELECTRICALLY OK OK
ELECTRICALLY OK OK
ELECTRICALLY OK OK
SLIDING & LSTE PROBLEM RECTIFIED OK

U/P U/P
U/P U/P
U/P U/P
U/P U/P
U/P U/P
2017
DCS TRIAL REMARKS
PENDING
PENDING
PENDING
- WORK U/P
- WORK U/P

PENDING
PENDING AFTER C&I CHECK OK
PENDING
PENDING
PENDING
PENDING
PENDING
PENDING

PENDING
PENDING
PENDING
PENDING
PENDING
- WORK PENDING
-
PENDING
PENDING

CONTROL TRIAL OK
PENDING
PENDING

PENDING
CONTROL TRIAL OK
CONTROL TRIAL OK
CONTROL TRIAL OK
PENDING
PENDING
PENDING
PENDING
PENDING
-
PENDING

PENDING
PENDING
PENDING
PENDING
PENDING
PENDING
PENDING

U/P
U/P
U/P
U/P
U/P