BATTERY SIZING CALCULATIONS

BATTERY SIZING CALCULATION

DATA CONSIDERED
UPS RATING 100 KVA Power Factor 0.80
Inverter efficiency 0.965
ECV 1.75 V/cell capacity factor 0.53
Back Up Time 15 min DCVoltage 42.00

No. of Cells = 252.00

Max Load Current = KVA x 1000 x P. F 100 x 1000 x 0.8


No of cells x ECV x Inverter Eff 252 x 1.75 x 0.965

= 187.99 Amps

= 0.53 X 187.99
= 99.63 AH 50

Offered 12V 12AH x 46 no's x 2 Strings for 15 kva to provide 30 min back up
NO of
KVA 1000 PF KW ECV Efficiency Total Voltage Current
Bat
250 1000 0.9 225000 10.5 40 0.952 403.2 562.73
250 1000 0.9 225000 10.5 41 0.952 413.28 549.00
250 1000 0.9 225000 10.5 42 0.952 423.36 535.93
250 1000 0.9 225000 10.5 43 0.952 433.44 523.47
250 1000 0.9 225000 10.5 44 0.952 443.52 511.57
250 1000 0.9 225000 10.5 45 0.952 453.6 500.20
250 1000 0.9 225000 10.5 46 0.952 463.68 489.33
250 1000 0.9 225000 10.5 47 0.952 473.76 478.91
250 1000 0.9 225000 10.5 48 0.952 483.84 468.94
250 1000 0.9 225000 10.5 49 0.952 493.92 459.37
250 1000 0.9 225000 10.5 50 0.952 504 450.18
175 1000 0.9 157500 10.5 40 0.952 403.2 393.91
175 1000 0.9 157500 10.5 41 0.952 413.28 384.30
175 1000 0.9 157500 10.5 42 0.952 423.36 375.15
175 1000 0.9 157500 10.5 43 0.952 433.44 366.43
175 1000 0.9 157500 10.5 44 0.952 443.52 358.10
175 1000 0.9 157500 10.5 45 0.952 453.6 350.14
175 1000 0.9 157500 10.5 46 0.952 463.68 342.53
175 1000 0.9 157500 10.5 47 0.952 473.76 335.24
175 1000 0.9 157500 10.5 48 0.952 483.84 328.26
175 1000 0.9 157500 10.5 49 0.952 493.92 321.56
175 1000 0.9 157500 10.5 50 0.952 504 315.1261