You are on page 1of 8

WHEN QUALITY IS AN ISSUE, THE CHOICE IS TETTEX

TYPE 2767

A U T O M AT I C
INSTRUMENT TRANSFORMER
TEST SET

I N S T R U M E N T S
A U T O M AT I C
INSTRUMENT TRANSFORMER TEST SET
COMPLETE
GENERAL MEASUREMENT SYSTEM

The type 2767 automatic current and voltage TETTEX also designs and supplies computer
transformer test set marketed by TETTEX is a controlled current and voltage transformer measu-
modern, fully automatic instrument for fast, rement facilities for specific customer requirements,
accurate measurement of instrument transformer comprising the following:
errors. It is designed for use in laboratories, manu-
facturing processes, quality control procedures and Type 2767 combined test set for current and
TYPE 2767

official metrology stations. Present increasingly voltage instrument transformers.


severe quality control requirements call for a Series 4760 standard current transformer
higher degree of operating comfort and absolute (current comparator).
reliability of the measuring equipment employed. Series 4820 standard voltage instrument trans-
Based on the latest design technology this instru- former or series 4860 electronic voltage divider
ment sets new standards of quality, reliability, standard with high-voltage capacitive divider.
convenient operation and simple maintenance. Series 3600 burdens
Its measurement ranges for current/voltage errors, Series 5260 current supply
phase displacement and current/ voltage excitation Series 5270 voltage supply
are fully up to international standard requirements.
Series 8860 heavy-current connection cables
This measuring instrument has been tested by PTB
(Physical Technical Federal Authority) in Germany. It full- In addition, TETTEX can supply all necessary peri-
fills all requirements according to the PTB test-rules for pherals (e.g. computer and printer) for external
measuring instrument transformers and is approved for control and data recovery. Our engineering
calibration. departement also develops tailor-made software
for automatic test systems and data-processing.

Test Circuit current supply


series 5260
Current
Instrument Transformer

L K device L K standard
under current
X N instrument
test
transformer
l k l k series 4760

burden
series 3600

l k l k
NX NN RS 232C
automatic or series 5930
instrument IEEE 488
transformer computer
test set ND
type 2767
display microprocessor type 5972
RS 232C
printer
keyboard

2
F E AT U R E S DESCRIPTION

Current and voltage transformer Plain-language display of error mes- The type 2767 test set measures
measurements with a single instrument. sages on a 2 x 16 character dot-matrix. transformer ratio errors by the
Fully automatic measurement and Short measurement times. differential method. A major
digital display of current/voltage ratio advantage of this is that balan-
Dynamic averaging. cing of winding turns at the
errors, phase displacement, test current
High accuracy. differential transformer (current
and voltage.
Low inherent burden. comparator) and compensation
Measurements are possible on via an additional winding enable
instrument transformers of practically Connection for external printer
fully accurate measurement al-
any primary and secondary current and (RS 232C interface). though the test and standard
voltage ratings. Front-panel with modern keyboard transformer have different ratios.
Test and standard transformers may (piezocrystal elements). Measurements are initiated simp-
have different ratios. Specifications conform to the ly by entering the rated test and
A cost-effective solution: standards/ recommendations of standard transformer data, for
IEC 185, IEC 618, ANSI/IEEE C57.13- which the built-in microprocessor
- different transformers can be tested has a particulary convenient
using one single standard transformer. 1978 and VDE 0414, part 2 .
man-machine interface.
- different standard and test transformer RS 232C interface for computer Current or voltage error, phase
ratios are matched without use of an connection displacement, test current or test
external divider. Wide range of accessories (see order voltage are measured conti-
Interactive parameter entry simplifies specification). nuously and displayed in digital
operation. form.
A microprocessor monitors all entries A dynamic averaging facility is
and controls the measurement run. provided for measurements at
low current or voltage, which
ensures that accuracy and dis-
play stability are maintained even
at poor signal/noise ratios.

Test Circuit
Voltage
Instrument Transformer
U device U electronic standard C1
under voltage divider standard
voltage test standard series 4860 capacitor
u u
supply voltage series 3370 NK
~ instrument
series transformer
V
5270 v series 4820 v V air capacitor
series 3330
C2

burden
series 3600

uX vX uN vN
RX RN
NN
NX RS 232C
automatic or series 5930
instrument IEEE 488
transformer computer
test set ND
type 2767
display microprocessor type 5972
RS 232C
printer
keyboard

3
T E C H N I C A L S P E C I F I C AT I O N
CURRENT TRANSFORMER V O LTA G E T R A N S F O R M E R
M E A S U R E M E N T PA R T M E A S U R E M E N T PA R T

X-input (test transformer) X and N-inputs


Rated secondary currents (test and standard transformers)
ISXR 0.1 - 1 - 2 - 5A
Max. operating range 1210% ISXR Rated secondary voltage
Inherent burden < 1 VA (max. rated range values)
USXR, USNR 140, 300 V
TYPE 2767

(at rated current) additional with factors x 1/3, x 1/3


Max. operating range (USX, USN)
N-input (standard transformer) at USXR = 3...140 V: 3280 V:
Rated secondary current ISNR 5A > 140...300 V: 10 ...400 V
Max. operating range 1210% ISNR
Inherent burden
Inherent burden < 2.5 VA
at USXR, USNR = 100 V < 1 VA
(at rated current) > 140 V < 0.5 VA

Ratio matching factor Ratio matching factor


of test and standard transformers (correction) of test and standard transformers (correction)

I PXR I PNR U PXR U PNR


k= : k= :
I SXR I SNR U SXR U SNR

Permissible limits for k Permissible limits for k


at max. accuracy 0.5 k 2
ISXR max. accuracy reduced accuracy at reduced accuracy 2 < k 10
5A 0.5 k 1.6
All entered values for UPR and USR are checked
2A 1.6 k 3 and the optimum input parameters (NN, RX, RN)
are set by a microprocessor.
1A 3 k 10 10 < k 25

0.1 A 25 k 100 100 < k 500 Input limit values


Rated primary voltage
All entered values for IPR and ISR are checked and UPXR, UPNR 3 V...10,000 kV
the optimum input parameters (NX, NN), are set Rated secondary voltage
by a microprocessor. USXR, USNR 3...300 V
(continuously adjustable)
Input limit values
Rated primary current
IPXR, IPNR 50 mA...1000 kA
Rated secondary current
lSXR, ISNR 50 mA5 A
(continuously adjustable)

4
CURRENT AND VOLTAGE
TRANSFORMER MEASUREMENT PART

Measurement ranges for Measurement frequency ranges


current/voltage errors (RATIO ERROR) 1518 Hz / 4565 Hz
and Ratio Correction Factor (RCF) Resolution
Current/voltage error 0.0001%
F [%] 19.99 1.999 0.1999 = 10-6 (1ppm)
Phase angle  0.001 min
RCF 0.83341.2499 0.980401.02040 0.998001.00200 or 0.0001 crad
Test current 0.001 A
Display of F [%] or RCF as required or 0.1% ISNR
Test voltage 0.1 V
Conversion or 0.1% USNR
Measurement frequency
1 F[%]
RCF = = (F = ) Limits of error at current transformer
1+ F 100
mesurements
For operating range 1...210 % of
Measurement ranges for phase displacement rated current
(PHASE ANGLE) Measurement frequency 50 or 60 Hz
Reference conditions as per IEC 359
[min] 680 199.9 19.99 1.999
Limits of error at voltage transformer
[crad] 19.99 1.999 0.1999 measurements
For operating range Usp = 3...400 V
Measurement frequency 50 or 60 Hz
Reference conditions as per IEC 359
Display of [min] or [crad], as required.
Conversion 1 crad = 34.4 min Minimum limits of errors ()*The greater of both values applies

RATIO ERROR Current ratio error 0.5% rdg 10 ppm 1 Dig


[%] or RCF
Current measurement ranges (EXITATION)
Voltage ratio error 0.5% rdg 50 ppm 1 Dig
Display of test specimen current IPX or ISX as
absolute values in [A] or [%] of rated current. PHASE ANGLE Phase angle 0.5% rdg 0.034 min 1 Dig
[min], [crad] (Current instrument 0.5% rdg 10 u Rad 1 Dig
transformer)
IX [A] 0.0001.999 2.0019.99 20.0199.9 2001999
Phase angle 0.5% rdg 0.17 min 1 Dig
(Voltage instrument 0.5% rdg 50 u Rad 1 Dig
IX [kA] 2.0019.99 20.0199.9 2001999
transformer)
IX [%] 0.000199.9 200210
EXCITATION Measuring current
0.5% rdg 0.5 % fs
[A], [V], [%] Measuring voltage
Voltage measurement ranges (EXCITATION)
Display of test specimen voltage UPX or USX as Explanation of limit of errors specification
absolute values in [V] or [%] of rated voltage. ...% rdg = % error of reading
...% fs = % error of value full-scale

UX [V] 0.0199.9 2001999 The above limits of error also apply for test and
standard transformers of different ratios. Limits of
UX [kV] 2.0019.99 20.0199.9 2001999 error at rated operating conditions, see specifications
as per instruction manual. Reference and rated
UX [%] Determined by UPXR, USXR and operating conditions as per IEC 359, rated range
operating range 3400 V of use 1.

5
Displays
6-digit LCD measured-value displays
(height 18 mm) of:
RATIO ERROR (current/voltage error)
PHASE ANGLE (phase displacement)
EXCITATION (test current/voltage)
LCD dot-matrix, 2 x16 characters (height 7 mm)
TYPE 2767

for measurement frequency, entry instructions


and error messages.

Measurement times at 50 Hz
First measurement <3s
Subsequent measurements <1s

Mains supply 230 V or 115 V,


50/60 Hz
Power input approx. 35 VA
Temperature range + 5...+40 C

Dimensions 500 x 310 x 470 mm


(W x H x D) (19.7 x 12.2 x 18.5 in)

Weight 40 kg (88 Ib)

This instrument is designed in accordance with the


safety requirements of VDE 0411/part 1 and
IEC 348 (safety class 1).

Example of a test certificate

6
O R D E R S P E C I F I C AT I O N

Standard supply
Type 2767 automatic instrument current and
voltage transformer test set in a 19" case
(including RS 232C printer interface).
Ground cable 16 mm2, 10 m
Power cable
Power voltage 230 V or 115 V
(please specify with order)
Type 2763 is a test set for current
instrument transformers only
Type 2769 is a test set for
voltage instrument transformers only

Accessories
Matrix printer type 5972
Personal computer series 5930
IEEE 488 Interface 2767/1
Cable data-link for
RS 232C interface, 3 m type 5991
Fibre optic data-link for
RS 232C interface, 30 m type 5992
Bus cable for
IEEE 488 interface, 4 m type 5993
Standard current transformers
(current comparators), current ratings as follows:
-up to 1000 A/1- 5A type 4761
-up to 5000 A/1- 5 A type 4764
-up to 10000 A/100 A *) type 4766
-up to 100 kA/ 100 A *) series 4760
*) In addition to type 4764
Standard voltage transformers
up to 220 kV/100V series 4820
Electronic voltage divider
standard series 4860
Programmable electronic
current burden type 3691
Programmable electronic
voltage burden type 3695
Current and voltage burdens
(to VDE and ANSI/IEEE
standards) series 3600
Current supplies
(up to 10 kA) series 5260
High-voltage supplies series 5270
Heavy-current connection
cables series 8860
Set of spare parts
(type 2767) no. 016695-00
Interface RS 232C/IEEE 488 type 5945

7
TYPE 2767

E192.10
Subject to change
without notice 03-.0.

Haefely Test AG
Tettex & Haefely EMC Division
Lehenmattstrasse 353, PO Box
CH-4052 Basel
Switzerland
www.tettex.com
Phone: +41 61 373 4111 I N S T R U M E N T S
Fax.: +41 61 373 4912
e-mail: sales@tettex.com