A. Signs
86
2. Any door, passage, or stairway, which is neither an exit nor a way of
exit access and which is so located or arranged as likely to be
mistaken for an exit, shall be identified by a sign reading "NOT AN EXIT"
and shall be identified by a sign indicating its actual character, such
as "TO BASEMENT, "STOREROOM", "LINEN CLOSET", or the like.
5. Every sign shall be distinctive in color and shall provide contrast with
decorational interior finish, or other signs.
B. Illumination of Signs
C. Size of Signs
Every exit shall have the word "EXIT" in plainly legible letters not less than
fifteen centimeters (15 cm) high with the principal strokes of letters not less
than nineteen millimeters (19 mm) wide, except that in existing building
externally illuminated exit signs therein having the word "EXIT" in plainly
visible letters not less than eleven and one half centimeters (11.5 cm) high,
other than in places of assembly, may be continued in use. Other
signages required by this rule shall be of the same dimension unless
otherwise provided.
87
SECTION 10.2.5.13 EMERGENCY EVACUATION PLAN
B. Appropriate provisions of PD 1096 and its IRR (National Building Code) shall
be used to determine the requirements for the construction classification.
A. General
1. Every stairway, elevator shaft, light and ventilation shaft, chute and
other opening between storeys shall be enclosed or protected to
prevent the spread of fire or smoke, except openings of building
protected by automatic fire suppression system as permitted by other
Section of this Rule.
88
c. The entire area, including all communicating floor levels, is
sufficiently open and unobstructed so that it may be assumed that
a fire or other dangerous condition in any part will be immediately
obvious to the occupants of all communicating levels and areas;
a. New buildings four storeys or more in height - two (2) hours fire
resistance rating.
b. New buildings below four storeys - One (1) hour fire resistance
rating.
3. Operation of the exhaust system for any floor opening shall be initiated
by an approved device in the storey involved and shall be any one of
the following means in addition to a manual means of opening and
testing the system.
4. Electric power supply to all parts of the exhaust system and its control
devices shall be designed and installed for maximum reliability.
6. Periodic tests, not less frequently than quarterly, shall be made of the
automatic exhaust system to maintain the system and the control de-
vices in good working conditions.
90
L/min) per linear meter of water curtain, measured horizontally around
the opening.
a. Spray nozzles shall be in the open type and shall have a solid coni-
cal spray pattern with discharged angles between forty-five (45)
and ninety (90) degrees. The number of nozzles, their discharge
angles and their location shall be such that the escalator opening
between the top of the wellway housing and the treadway will be
completely filled with the dense spray on operation of the system.
b. The number and size of nozzles and water supply shall be sufficient
to deliver a discharge of one and four-tenths (1.4) liters of water
per square meter per second through the wellway, area to be
figured perpendicular to treadway.
91
e. Control valves shall be readily accessible to minimize water dam-
age.
h. Control valves for the spray nozzle system and approved smoke
detection or thermostatic devices shall be supervised in
accordance with applicable provisions of Section 10.2.6.4 of this
IRR.
92
a flame-spread rating greater than Class A as defined in Section
10.2.6.3 of this IRR are exposed, shall be effectively fire-stopped as
provided below, with approved materials, unless the space is sprinkled
in accordance with Section 10.2.6.5 of this IRR.
c. Any concealed space between the ceiling and the floor or roof
above shall be firestopped for the full depth of the space along
the line of support of the floor or roof structural members and, if
necessary at other locations to form areas not to exceed ninety
three square meters (93 m2) for any space between the ceiling
and floor and two hundred eighty square meters (280 m2) for any
space between the ceiling and the roof.
A. General
93
b. Class B Interior Finish
Flame Spread over 500. Includes any material classified at over 500
on the test scale described in paragraph (4) below.
C. Automatic Sprinklers
94
class of lower flame spread rating shall be permitted; e.g., where Class
B is specified, Class A may be used.
3. Interior finish of Class E shall not be used in any room space subject to
human occupancy, except to such extent as may be specifically
permitted by the City/Municipal Fire Marshal having jurisdiction on the
basis of finding that such use does not significantly increase the life
hazard, provided, however, that such use of Class E interior finish shall
not in any case exceed ten (10%) percent of the aggregate interior
surface of the walls and ceiling of the room or space in which such
Class E material is located.
A. General
2. When a required fire alarm system is out of service for more than 4
hours in a 24-hour period, the City/Municipal Fire Marshal having
jurisdiction shall be notified within 24 hours, and a fire watch shall be
assigned until the fire alarm system has been returned to service.
B. Signal Initiation
a. Manual initiation.
b. Automatic detection.
c. Extinguishing system operation.
95
2. Manual fire alarm boxes shall be used only for fire protective signaling
purposes.
4. Additional fire alarm boxes shall be so located that from any part of
the building not more than thirty meters (30 m) horizontal distance on
the same floor must be traversed in order to reach a fire alarm box.
C. Smoke Alarms
D. Occupant Notification
2. A presignal system may be permitted where the initial fire alarm signal
is automatically transmitted without delay either to the nearest fire
station, a fire brigade or to an on-site staff person trained to respond to
a fire emergency.
96
City/Municipal Fire Marshal having jurisdiction.
c. proprietary system
b. All hospitals;
F. Emergency Control
97
b. stairwell or elevator shaft pressurization;
c. smoke management or smoke control systems; and
d. unlocking of doors
G. Location of Controls
H. Annunciation
7. Where the system serves more than one building, each building shall
be considered separately.
98
SECTION 10.2.6.5 AUTOMATIC SPRINKLERS AND OTHER EXTINGUISHING
EQUIPMENT
A. General
B. Supervision
1. Supervisory Signals
99
C. Other Automatic Extinguishing Equipment
1. In any occupancy where the character of the potential fuel fire is such
that extinguishment or control of fire will be more effectively
accomplished by a type of automatic extinguishing systems other than
automatic sprinkler system such as but not limited to carbon dioxide,
dry chemical, foam, or water spray, a standard extinguishing system of
appropriate type shall be installed subject to the approval of the
City/Municipal Fire Marshal having jurisdiction.
100
iv. In covered mall buildings, at the entrance to each exit
passageway or exit corridor, and at exterior public entrances to
the mall;
C. Dry Standpipes
101
4. Detailed Requirements
c. Size. The size of the standpipe shall have a diameter of at least 102
mm (4 in.) in buildings in which the highest outlet is twenty three
(23) meters or less above the fire service connections and shall not
be less than 153 mm (6 in.) where the highest outlet is higher than
twenty three meters (23 m) above the fire service connection.
All one hundred two millimeters (102 mm) dry standpipes shall
be equipped with a four-way fire service connection. All fire
service connections shall be located on a street front, not less
than forty six centimeters (46cm) or more than one hundred
twenty two centimeters (122cm) above grade and shall be
equipped with an approved straight way check valve and
substantial plugs or caps. All fire service connections shall be
protected against mechanical injury and shall be visible and
accessible. More than on fire service connection may be
required.
102
(61 cm) nor more than one hundred twenty two centimeters (122
cm) above the floor of each storey. All dry standpipe shall be
equipped with a two way sixty four millimeters (64 mm) outlet
above the roof line of the building when the roof has a slope of less
than thirty centimeters (30 cm) long wrench may be used in
connecting the hose with clearance for the wrench on all sides of
the outlet. Standpipes located in smokeproof enclosures shall have
outlets located in the vestibule or on the balcony. Standpipes
outlets in stairway enclosures or smoke towers shall be so located
that the exit doors do not interfere with the use of the outlet. All
outlets shall be equipped with an approved valve cap and chains.
D. Wet Standpipes
1. Wet standpipe system extending from the cellar or basement into the
topmost storey shall be required in the following:
3. Location
103
b. In theaters, auditoriums and other assembly occupancies where
the occupant load is more than one thousand (1,000), outlets shall
be located on each side of any stage, on each side of the rear of
the auditorium and on each side of the balcony.
4. Detailed Requirements
b. Size. The size of the standpipes shall not be less than 64 mm (2 in.)
in diameter.
d. Water Supply. The wet standpipe shall deliver not less than one
hundred thirty two liters (132 ) of water per minute at not less than
one and eight-tenths (1.8) kilos per square centimeters residual
pressures from each of any two outlets flowing simultaneously for
thirty (30) minutes. When more than one interior wet standpipe is
required in the building, such standpipes may be connected at
their bases or highest points by pipes of equal size. Where
combination standpipes are installed, the thirty eight millimeters (38
mm) outlet system may be supplied from the combination system
with a fifty one millimeters (51 mm) connecting line.
104
under the bottom of an adjacent construction. Approved pressure
gauges shall be provided at pressure tanks and t the fire pump.
f. Fire Pumps. Fire pumps shall be approved and shall deliver not
less than the required fire flow and pressure. Such pumps shall be
supplied with adequate power source and shall be automatic in
operation. Where the wet standpipe system is supplied with water
from the domestic supply of building, approved fire pumps shall not
be required provided the domestic pump used delivers the
required fire flow.
g. Hose and Hose Reels. Each wet standpipe outlet shall be supplied
with a hose not less than thirty eight millimeters (38 mm) in
diameter. Such hose shall be equipped with an approved variable
for nozzle. An approved hose reel rack or cabinet shall be provided
and shall be located so as to make the hose accessible. The hose
reel rack or cabinet shall be recessed in the wall or protected by
suitable cabinet.
105
Standpipe Pressure
at House Outlet Size of Orifice
(Kilograms per (millimeter)
square centimeter)
11.97 16.7
12.68 15.9
14.08 15.1
15.85 14.3
17.61 13.5
19.72 12.7
E. Combination Standpipes
3. Location
4. Detailed Requirements
106