increasing contact resistance escalates rapidly, yielding is here the electrical resistivity of the conductors at an
resistances orders of magnitude greater that the initial value. unheated location distant from the contact spots. Resistivity is
An appropriate diagnostic method for GIS should be assumed to increase linearly with increasing temperature T,
sufficiently sensitive to give warnings long before the contact
heating reaches a level where arcing occurs or epoxy insulators r (T2 ) = r (T1 )[1 + a (T2 - T1 )] (3)
disintegrate thermally.
In the present paper a new, non-invasive technique for with a as the temperature coefficient. Fig. 1 shows a plot of
assessing the condition of contacts in GIS is proposed. Similar (2) with values of the material parameters as for aluminium.
to four-point resistance measurements, the method relies on For a given conductor material the temperature rise is solely a
passing electric currents through the section to be tested and function of the voltage drop. Hence, all contact spots in the
record the associated voltage drops. In sections containing same interface are at the same temperature.
degraded contacts certain non-linear and/or irreversible
phenomena will occur, indicating that one or more contacts are 600
poor.
contact spot region. Using material parameter values for other 2.5
common conductors, including copper and silver, gives similar
2
results.
2.5 1.5
R / R0
2 1
1.5 0.5
R / R0
1 0
Dimensionless current
0.5
Fig. 3. Current resistance relationships in a contact calculated from theory
(solid line) and obtained from measurements on a contact between crossed
0 aluminium cylinders (broken line) for voltage drops up to 250 mV
0 0.05 0.1 0.15 0.2 0.25
Voltage drop [V] ship exists between current and voltage as long as currents are
relatively low. By increasing the current and thereby also the
Fig. 2. Ratio between hot (I 0) and cold (I 0) resistance of a voltage drop, a non-linear regime will sooner or later be
aluminium contact calculated from theory (solid line) and measured on a reached.
contact between crossed aluminium 5 mm cylinders (broken line). The bulk At even higher currents the local temperature in the contact
of the conductors is at room temperature.
spot may exceed the melting point of the conductor material
and local melting will occur. This so-called melting voltage
Included in Fig. 2 are also measurements of the resistance
is 300, 430 and 370 mV for contacts of aluminium, copper and
increase obtained on a contact established simply by crossing
silver, respectively [7]. Melting alters the contact spot
two 5 mm solid, circular conductors of aluminium. Currents up
geometries, and will usually cause irreversible changes in the
to approximately 24 A were applied to obtain voltage drops up
contact resistance; it may increase or decrease significantly.
to 250 mV.
Since the mass of metal heated by the constriction
The effect of the local resistivity increase can also be given
resistance is minute, the thermal time constant for a contact
as a current resistance relationship. Introducing (1) and
spot is usually well below 1 ms [7, Chap. 21]. Consequently,
Ohms law R = U/I, into (4), yields
the relationships shown in Figs. 2 and 3 are found for all types
of current excitation, including ac, dc and pulses, provided that
ar 0 I the dominant frequencies are in the kilohertz range or below.
tan
R l 4a (5)
= III. PROPOSED DIAGNOSTIC TECHNIQUE
R0 ar 0 I
l 4a A. Working Principle
The temperature in the contact spots is a good indicator of
The contact resistance ratio is here given as a function of the quality or condition of a contact. From experience it is
dimensionless current. Fig. 3 shows this expression calculated recognized that temperature increase and temperature cycling
for I/a ratios giving a voltage drop in the range 0 250 mV. in these tiny areas over prolonged periods of time may have a
Results from the measurements on crossed aluminium detrimental effect on the contact. Thermo-mechanical strains
cylinders that passed currents sufficiently high to cause contact and stresses, increased corrosion rates and other degradation
voltages up to 250 mV are also shown. mechanisms may then gradually worsen the current carrying
The effect of local heating of the contact spots is clearly ability of the contact spots. As a result, the contact resistance
visible in all the curves in Figs. 2 and 3; although somewhat increases, leading to even higher temperatures and further and
more distinct in those predicted by theory than those found faster deterioration.
experimentally. However, when taking into account that the Thus, for power contacts and connectors it is important to
theory assumes circular contact spots, that temperature ensure that the voltage drop created by the maximum rated
dependencies of resistivity and thermal conductivity are rather load current does not cause 100/120 Hz temperature variations
simply modeled, and that the contact spot temperature varies of tens of kelvins or more. For example, the high quality silver
between room temperature and almost 600 oC, some deviations plated contacts often used in the conductor joints in a GIS
have to be anticipated. have a nominal contact resistance of typically 5 mW. Assuming
Figs. 2 and 3 show that the contact resistance is constant for a maximum rated load current of 3150 Arms, this yields voltage
low voltages and currents but that an increasing resistivity in drops with peak values of 22 mV. If the contact resistance
the contact spots results in an upturn of the curves for higher becomes much larger, the local heating is no longer negligible
voltages and currents. Or in other words, a linear relation- and the long-term stability of the contact can be at risk.
4
The proposed diagnostic method relies on this correlation IV. PRACTICAL ASPECTS WHEN APPLIED ON A GIS
between contact spot temperature and the condition of the
contact. Excessive contact spot heating is detected as a slightly A. Connecting the Testing Equipment
increasing contact resistance with increasing current, or as The part of the GIS to be examined has to be taken out of
irreproducible resistance measurements due to local melting. service and be accessible in a similar way as when carrying out
The test procedure is to pass currents of increasing magnitudes conventional four-point resistance measurements.
up to the rated load current of the circuit considered, in the Fig. 4 shows schematically how the excitation current
present context a GIS section, and accurately determine the source and voltage probes can be connected to a single-phase
resistance each time. If the resistance section of a GIS. Current is here fed into the primary circuit at
remains constant for all currents no notable contact spot an SF6-to-air bushing, passes through the center conductor and
heating occurs, and all contacts in the considered section then over to the encapsulation by a grounding switch before it
are good; returns to the source through the encapsulation. The voltage
shows a reproducible increase with increasing currents, the probes are connected as close as possible to the section of the
contact spot temperature in one or more contact interfaces primary circuit to be examined.
in the circuit is substantially higher than the conductor
temperature, indicating that one or more of the contacts are
deteriorating; Ampere-
meter
A
Voltmeter
is irreproducible with significant deviations from one
measurement to the next, this is a clear sign of contact spot V
Current
melting, showing that one or more contacts are severely source
degraded.
This scheme is generally applicable, but primarily of
interest in equipment where the individual contact interfaces
are inaccessible for conventional resistance measurements.
Grounding
The non-linear behavior of poor contacts is well-known and switch
has previously been proposed as a mean for diagnostic testing Contacts
of other types of contacts, predominantly in equipment with
considerably lower ratings [10].
B. General Considerations Fig. 4. Example of set-up for measuring resistance in a section of a GIS.
conductors. A typically GIS section on average has around one C. Current Source
contact per meter conductor, so the resistance in one contact The current source should be able to provide excitation
roughly corresponds to the resistance of one meter conductor. currents up to several kiloamperes, but at the same time be
portable. These are clearly conflicting demands.
TABLE I
Applying dc greatly simplifies the resistance measurements
TYPICAL PARAMETER VALUES FOR A GIS SECTION
Rated current 1250 4000 Arms because various effects related to time-varying currents, such
as inductive voltage drops, non-linear phenomena in the iron
Conductor resistance 5 10 mW/m
cores of instrument transformers, magnetic induction and
Conductor inductance 0.2 mH/m
interaction with nearby conductors etc. are avoided. However,
Conductor impedance 60 mW/m dc sources rated for kiloamperes tend to become very bulky
Contact resistance per joint 5 10 mW and expensive, and dc excitation is for that reason not found to
be a viable option.
The distance between SF6-to-air bushings, grounding 50/60 Hz ac excitation has also been considered. When
switches and other accessible points for current injection and applying a pure sinusoidal current to a poor contact local
voltage measurements varies significantly with the architecture resistivity increase causes the resulting voltage waveform to
of the GIS and with the voltage rating. In a 420 kV GIS it may become distorted with sharper peaks, see Fig. 5. The content
be more than 20 m from an outdoor SF6-to-air bushing to the of 3rd harmonics increases rapidly with voltage drop, and
nearest grounding switch, while a 145 kV GIS with SF6-to- measurement of the content of 3rd harmonics can thus be used
cable bushings only and many grounding switches can be for diagnostic purposes [11].
divided into sections that all are shorter than 10 m.
0.3
Consider a rather extreme case with a 40 m long GIS 40
section with a conductor resistance of 5 mW/m that contains 40 0.2
contacts, each with a resistance of 5 mW. Thus the total
Voltage drop [V]
0.1 20
Current [A]
resistance of the section is 400 mW, of which each contact
accounts for 1.25% of the total. Assume then that one of these 0 0
contacts for some reason has deteriorated, so that its cold
-0.1 -20
resistance has increased from 5 mW to 25 mW. When passing
4000 A through this section the voltage drop across each of the -0.2
-40
39 good contacts is only 20 mV and their contact spots will
-0.3
have approximately the same temperature as the bulk of the
0 20 40 60 80
conductor. In the last and poor 25 mW contact, on the other
Time [ms]
hand, contact spot heating will influence the resistivity locally.
As a result, when passing 4000 A the contact voltage across
Fig. 5. Voltage drop (solid line) over a very poor / overloaded contact when
this poor contact will be around 150 mV, instead of 100 mV, subjected to a sinusoidal current (broken line). These measurements are the
see Fig. 2. Thus, one third of the voltage drop across this same as those presented in Figs. 2 and 3.
contact originates in resistivity increase due to temperature rise
in the contact spots. This current-depending or non-linear part However, when applying ac to a GIS the relatively large
of the resistance constitutes around 3% of the total resistive inductive voltage drop must be taken into consideration, both
voltage drop of 1730 mV across the entire section when when rating the power supply and when estimating the
4000 A is passed. Consequently, a system capable of accuracy that can be achieved in the resistance measurements.
measuring resistance to a better accuracy than this, both at low The current source, typically a transformer with a single turn
and high currents, will disclose the existence of a poor contact secondary, becomes very heavy, and the resistive part of the
in this 40 m long GIS section. voltage drop is to a large extent masked by the much greater
The non-linear part of the resistance will be significantly inductive voltage drop across the section considered. For these
smaller in a contact that is less aged and with less than the reasons, transformer-based ac excitation is not considered
five-fold resistance increase used in the example above. On the feasible.
other hand, the resistance of an un-aged contact will not in all The third excitation option that has been evaluated is
cases be as low as 5 mW, and even a doubling or tripling of the unipolar current pulses generated by discharging a capacitor
resistance may bring the current resistance relationship well bank. The current rating and weight of a capacitor bank are
into the non-linear region when currents around the rated load essentially determined by the energy density and the internal
current are passed. resistance of the capacitors used. Furthermore, the amplitude
In conclusion, if the resistive part of the voltage drop in a and shape of the discharge current are also determined by the
GIS section can be determined with an accuracy of around 1% resistance and the inductance of the circuit.
a very good sensitivity for detecting contact degradation at an Electrolytic capacitors have very low internal resistance and
early stage is expected. can thus generate current pulses of large amplitudes when
6
Current [kA]
duration when discharged through a typical GIS section.
2
However, similar to when using ac, a current pulse causes
magnetic induction and other phenomena that complicate the
resistance measurements somewhat. 1
V. PROTOTYPE INSTRUMENTATION 0
A first, simplified prototype instrumentation based on the 0 10 20 30 40 50 60
requirements outlined above has been built and tested. Overall Time [ms]
design features and working principles will be briefly
Fig. 7. Current pulses generated in the circuit shown in Fig. 6.
described.
A. Pulsed Current Source The rise time of the pulses is around 8 ms, which is not too
Fig. 6 shows a circuit diagram of the current source, the different from mains frequency time constants. For a given
current leads and the GIS section being measured. circuit, the frequency spectrum of the pulse is virtually
independent of the magnitude of the current, giving the same
Current Current
source leads GIS current penetration depths. This is crucially important when
Air coil the purpose is to carry out accurate resistance measurements of
Thyristor a GIS section at different currents by pulse excitation.
Charger L
C=4F The weight of the capacitor bank is approximately 10 kg.
Diode Thyristor, diode, charging unit, air coil, control circuitry (not
R shown in Fig. 6) etc. bring the weight of the current source up
220
to somewhere between 15 and 20 kg, current leads not
VAC included.
B. Resistance Measurement
Fig. 6. Simplified diagram of current source and test circuit.
A standard PC-based data acquisition system is applied.
Two differential channels record corresponding current and
The 4 F capacitor bank is charged to a predetermined
voltage drop across the GIS section being examined. Current is
voltage using a charger unit supplied from a 220 VAC outlet.
measured using a Hall-effect open loop current measuring
When fully charged to 35 V, 2,5 kJ of energy is stored in the
device that gives out a voltage proportional to the magnitude
capacitors. The energy is discharged through the GIS by firing
of the current at any time. The sampling rate is 50 kHz and 16
the thyristor. The resulting current pulse rapidly reaches its
bits analogue-to-digital (A/D) converters are used. Both
maximum amplitude; how fast depends on the circuit
current and voltage time series are stored as data files.
parameters, including the capacitance of the bank. When the
High frequency noise is removed from these time series by
current pulse is at its peak value the capacitor bank voltage is
using a finite impulse response (FIR) digital band stop filter
approximately equal to the resistive voltage drop in the circuit.
with a cut-off frequency of 250 Hz.
The current will then start decreasing and dies eventually out,
Dc-offset in the A/D converters and power frequency noise
as the capacitor bank is completely discharged.
are removed by taking advantage of the fact that these
The bypass diode prevents the capacitors from being
disturbances are highly predictable. By starting the data
damaged by reverse charging, and does also prevent
acquisition 60 ms (three power cycles) before the thyristor is
oscillations in the circuit. The air-core coil serves as a current
fired, the periodic noise and dc-offset is measured. These
limiter if the terminals of the source are unintentionally short-
7
initial parts of the current and voltage time series are then measurement is always taken as the value found at the same
shifted 60 ms and then simply subtracted from subsequent point of the current pulse, namely as the current pulse is at its
parts of the time series, i.e. the parts obtained as the pulse peak value.
current is passed through the GIS. Fig. 8 shows typical current Thus, a section of a GIS is examined by passing current
and voltage recordings after filtering. pulses of different magnitudes, and each time calculate the
resistance when the current pulse is at its peak value. And, as
2.5 4 described earlier, if the resistance varies, this indicates that one
or more of the contacts have a too high resistance.
2.0
3 When the current pulse is at its maximum di/dt equals zero,
Voltage drop [V]
Current [kA]
1.5
to (6). Hence, the procedures described above for calculating L
2
1.0
and subtracting the inductive voltage drop are in principle not
required to determine the resistance. By simply dividing
1 voltage drop with current when the current has its maximum
0.5
value should give the resistance. In practice however, it turns
0.0 0 out very difficult to determine at what time the current has its
0 10 20 30 40 maximum with sufficient accuracy. As Fig. 8 shows, the
Time [ms] voltage drops rather rapidly around this point, and a minor
error in determining when di/dt equals zero causes a
Fig. 8. Voltage drop measured across a GIS section (solid line) when a significant error in the resistance value. The applied procedure
current pulse (broken line) is passed through.
is considerably more robust.
If the GIS section examined contains instrument
The relationship between voltage drop u(t) and current i(t)
transformers with iron cores surrounding the conductor,
across the GIS section is determined by the equation
saturation phenomena in the iron may interfere with the
voltage measurements. Such disturbances are avoided by
di(t )
u (t ) = R(i, t ) i(t ) + L (6) opening the secondary windings of the instrument transformers
dt and installing surge arrestors across their terminals.
Furthermore, in very compact GIS the return current back
where R and L are the resistance and inductance, respectively, to the source may take other paths than through the
of the part of the circuit between the voltage probes, see Figs. encapsulation of the section being examined. This may induce
4 and 6. currents out of phase with the current pulse in the center
As can be seen from Fig. 8, in the first milliseconds where conductor. Hence, these induced currents will not have their
the derivative of the current is large and positive, the inductive maximum at the same time as the injected current, and
part of voltage drop is significantly greater than the resistive consequently, they may induce a voltage drop also when di/dt
part. When the current has its maximum value, di/dt equals = 0 for the pulse. This source of miscalculation is avoided by
zero and the voltage drop is purely resistive. not using the enclosure as a return path, but instead connecting
The inductance L is the only quantity in (6) that remains the current leads directly to the ends of the section being
constant both during the course of a pulse and between pulses examined. Since this type of induction phenomenon only has
of different amplitudes. Using discrete-time representation and been experienced on very compacts GIS, there is no need for
reformulating (6) yields extra long current leads to deal with this.
120 on a 420 kV GIS that had been in service for 15 years. The
GIS has a full double breaker and double bus arrangement, and
110 only one bus was taken out of service during the
measurements. Currents were injected and voltages were
100 measured through the same insulated grounding switches.
According to the manufacturers representative the grounding
90 switches were equipped with silver plated contacts of the same
0 1000 2000 3000 type as in the disconnector switches in the main circuit.
Current [A] 550
Fig. 9. Resistance as a function of current for two sections in a 145 kV GIS.
The resistances remain constant for all currents showing that there are no poor 540
contacts in these sections.
Resitance [mW]
530
Similar results were obtained on other GIS, demonstrating that
520
the applied test instruments and procedures make it possible to
measure resistance with very good reproducibility and linearity 510
in the rather noisy environment of an energized substation.
This is of crucial importance as the sensitivity of this 500
diagnostic method is directly related to the quality of the
490
resistance measurements.
Tests were also carried out on 8 m long laboratory mock up 0 1000 2000 3000 4000 5000
2.5
400
2
395
Resitance [mW]
390 1.5
0 5 10 15
Time [ms]
385
Fig. 12. Part of the resistive voltage recordings obtained from a section of a
420 kV GIS when applying two different current pulses. The inductive
380 voltage drops are removed. The small, abrupt changes in voltage curves are
indications of contact spot melting.
0 1000 2000 3000 4000
GIS, see for example Fig. 9. Moreover, a systematically to the accuracy of the resistance measurements. In full-
increasing resistance with increasing current is not observed. scale testing under realistic operating conditions on 145
Results with the same poor reproducibility were obtained also 420 kV GIS using prototype instrumentation a very good
on other sections, and it was suggested that the these sections sensitivity was obtained.
contained one or more contacts with such a high resistance that
local melting occurred in the contact spots. VIII. REFERENCES
Close examinations of the voltage measurements supported [1] A.R. Salinas, Detecting trouble through diagnostic testing,
this assumption. Fig. 12 shows two voltage recordings that Transmission & Distribution World, pp. 60-70, May 2001.
[2] Report on the secondary international survey on high voltage gas
contain evidence of sudden resistance changes, which is a clear insulated substations (GIS) service experience, Brochure no. 150,
sign of contact spot melting. As outlined earlier, the Paris: CIGR, 2000.
measurements cannot ascertain whether the poor contact(s) are [3] H. Fujinami, T. Takuma and T. Kawamoto, Development of detection
in the circuit-breaker, disconnector switches, grounding method with a magnetic field sensor for incomplete contacts in gas
insulated switches and bus connecting parts, IEEE Trans. Power
switches or in the conductor joints. Consequently, further Delivery, vol. 10, pp. 229-236, Jan. 1995.
examinations were carried out, including dismantling parts of [4] Y. Ohshita, A. Hashimoto and Y. Kurosawa, A diagnostic technique to
the GIS to perform resistance measurements across individual detect abnormal conditions of contacts measuring vibrations in metal
enclosures of gas insulated substations, IEEE Trans. Power Delivery,
contact interfaces. vol. 4, pp. 2090-2094, Oct. 1989.
The outcome of these investigations was somewhat [5] Y. Mukaiyama, I. Takagi, J, Izumi, T. Sekiguchi, A. Kobayashi and T.
unexpected. First, it turned out that the information given Sumikawa. Investigation on abnormal phenomena of contacts using
disconnecting switch and detachable bus in 300 kV GIS, IEEE Trans.
about the contacts in the grounding switches was incorrect. Power Delivery, vol. 5, pp. 189-195, Jan. 1990.
The grounding switches contained only arcing contacts, with [6] M. Runde, O. Lillevik, V. Larsen, B. Skyberg, and A. Mjelve
no silver plated, low-resistance contacts in parallel. The arcing Diagnostic testing of contacts in in gas insulated substations, in Proc.
IEEE Power Engineering Society Transmission and Distribution Conf.
contacts are primarily designed to be able to withstand arcing,
and Exposition 2002: Asia Pacific, (in press).
and have a rather high resistance, typically 100 - 200 mW. [7] R. Holm, Electric Contacts, New York: Springer, 1967.
Second, an incorrect type of contacting compound [8] R. Timsit, Electrical Contact Resistance, Fundamental Principles in
(grease) had been applied on the main, silver plated contacts Electrical Contacts: Principles and Applications, P. G. Slade, Ed. New
York: Marcel Dekker, 1999, pp. 1-88.
in the circuit-breaker during the manufacturing or erection of [9] M. Runde, Mass transport in stationary contact points, IEEE Trans.
the GIS. After some years the compound hardened to form a Components, Hybrids, Manuf. Technol., vol. CHMT-10, pp. 89-99,
partially solid and insulating barrier that led to a significant Mar. 1987.
[10] J. H. Whitney, Method and means for measuring constriction
increase in the contact resistance across the circuit-breaker. resistance based on non-linearity, U.S. Patent 3 500 188, Mar. 1970.
Whether the observed contact spot melting occurred in the [11] M. Runde, A. Gjelsvik and A. Rein, Method for detecting degraded
circuit-breaker or in the arcing contacts of the grounding contacts in gas insulated substations in Proc. 17th Int. Conf. on
Electrical Contacts, pp. 699-704, 1994
switches or both places, is not clear. However, this full-scale
test demonstrates that the applied instruments and procedures
IX. BIOGRAPHIES
are sufficiently sensitive to detect contact spot melting under
realistic conditions. Furthermore, it is also very obvious that
Magne Runde was born in Skien, Norway in 1958. He received the M.S. and
knowledge about the design and construction of the GIS being Dr. Ing. degrees from the Norwegian Institute of Technology in 1984 and
examined is essential. On this GIS current injection and 1987, respectively. Since 1988 he has been with SINTEF Energy Research in
voltage measurements should not have been done Trondheim, Norway. From 1996 he also holds an adjunct professor position
in high voltage technology at the Norwegian University of Science and
simultaneously using the same grounding switch.
Technology. His fields of interest include electric contacts, circuit-breakers,
diagnostic testing, and power application of superconductivity. He is
VII. CONCLUSIONS presently a member of CIGR Study Committee 13: Switching Equipment.
The following conclusions can be drawn from the present
Odd Lillevik graduated from Department of Electrical Engineering,
work: Norwegian Institute of Technology (NTH) in Trondheim, Norway in 1978.
The contact resistance in degraded or overstressed After a short period as a teaching assistant at NTH, he was employed by the
electrical contacts varies slightly when currents of different Electric Utilities of Oslo in 1979. Since 1980 he has been with SINTEF
Energy Research in Trondheim, initially in the Electrical Heating group, and
magnitudes are passed. This non-linear current resistance since 1986 in the Power Engineering department.
relationship can be used to detect contact degradation in
GIS at an early stage. The GIS does not need be Vegard Larsen was born in Sotra, Norway, in 1955. He received a M.S.
dismantled, and no previous measurements or manufacturer degree from the Department of Electrical Engineering, Norwegian Institute of
Technology in 1979. From 1979 to 1985 he was with the Norwegian Electric
specifications are required. Power Research Institute (EFI) in Trondheim, where he was working with
For diagnostic testing of the contacts in large GIS, insulation coordination, transient analyses, and computer software develop-
excitation currents of several thousand amperes are ment. From 1985 to 1989 he was with the Norwegian State Oil Company as a
Senior Engineer, doing market studies and project planning. Since 1989 Mr.
required. By using a capacitor-based current supply, such Larsen has been with TransiNor, first as Manager for software products, later
ratings can be achieved with a portable source. as President of the company. At present he is Vice President and Sales
The sensitivity of the diagnostic method is directly related Manager at TransiNor.
10
Asgeir Mjelve was born in Oslo in 1959, and received his B.Sc. degree in
Electrical Engineering from stfold University College in 1980. Since 1982
he has been with Viken Nett, the electricity utility for the city of Oslo and
surrounding areas and also the largest distribution grid company in Norway.
He has been working primarily with issues related to planning, design and
maintenance of substations.