You are on page 1of 8

660 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 29, NO.

2, APRIL 2014

Synchrophasor-Assisted Zone 3 Operation


Pratim Kundu and Ashok Kumar Pradhan, Senior Member, IEEE

AbstractZone 3 operation of distance relay serves as a remote unwanted operations. Conventionally, the load encroachment
backup in case of primary failure. Conditions, such as power under normal operating conditions can be avoided by choosing
swing, load encroachment, and voltage and transient instability, the zone 3 settings carefully. A rectangular characteristic pro-
cause incorrect zone 3 operation. The detection of faults during
such stressed conditions poses a further problem. This paper vides resistive fault coverage and avoids overlapping with the
proposes a synchrophasor data-based technique for correct zone load region in the impedance plane [2], [10]. But fixing a shape
3 operations by discriminating the fault from different stressed of the relay characteristic for a large system becomes a com-
situations. This discrimination is accomplished using impedances plex issue. The analysis of the relay decision during voltage in-
calculated from voltage and current signals from synchrophasors stability is another complex task. An adaptive scheme utilizing
placed at strategic locations. The proposed method is tested in the
IEEE 39-bus New England system and found to be accurate. rate of change of voltage with time ( ) is proposed in [3]. It
requires careful analysis for setting the threshold for ( ) to
Index TermsDiscrete Fourier transform (DFT), distance re-
discriminate switching events, such as line switching, capacitor
lays, synchrophasor, zone 3 operation.
switching, reactor switching, etc. Control strategies for relay op-
erations during the voltage instability situation have been pro-
I. INTRODUCTION posed in [11]. A voltage stability index for the relay is sug-
gested in [12] considering it as a static phenomenon. Emergency

B LACKOUTS in power utilities throughout the world have control action during voltage instability is suggested in [13].
raised a concern over zone 3 maloperation of distance re- From the relay operation perspective, these methods are not
lays. A distance relay takes a decision based on local voltage helpful since they cannot discriminate a fault from a voltage in-
and current measurements. During stressed conditions, such as stability situation. In this context, a transient component-based
power swing, load encroachment, and voltage instability, the technique has been proposed in [14] to distinguish the fault from
impedance trajectory enters the zone 3 characteristic and the other power system events. However switching operation in the
relay may misinterpret this situation as a fault. The zone 3 re- system gives rise to a transient component which the algorithm
gion of a distance relay covers a large area and an incorrect deci- may misinterpret as a fault. In addition, training-based methods,
sion increases stress in the system, leading to cascade trippings such as an adaptive neurofuzzy inference system and support
[1][3]. Recent India blackouts in July 2012 were triggered due vector machines, have been applied for assisting the relay deci-
to zone 3 maloperation resulting from load encroachment [4]. sion during fault [15], [16]. These methods need a large number
Power-swing blocking (PSB) schemes use a rate of change of of training patterns to be generated and have limited perfor-
impedance for swing detection [5]. The timer therein is difficult mance to distinguish the fault from other stressed situations. The
to set as the swing frequency varies from 0.1 to 5 Hz. Another wavelet-based detection of fault is proposed in [17] where the
limitation of this technique is the detection of fault during swing choice of wavelet function for various conditions becomes diffi-
conditions. To overcome these issues, the method in [6] uses the cult. Integrating wavelet and modal transform, the symmetrical
r-dot method to identify fault during the power swing but it has fault detection method is proposed [18].
a relatively longer decision time. The rate of change of swing A comprehensive scheme for discriminating a fault from
center voltage is another method [7] where the decision time other stressed events is required to prevent maloperation of the
may be high due to the influence of transient at the initial period zone 3 element of relay. With the power system operation being
of the fault. A fault detector using a superimposed component a dynamic phenomena, analysis based on local information
of current is proposed which has limited performance for the derived by the relay can lead to inaccuracy. With the advent
power angle close to 180 and for a high-resistance fault [8], of a wide-area measurement system (WAMS), which provides
[9]. synchronized data over a large area, it is possible to monitor the
During overload and voltage instability situations, the protec- dynamics of a power system [19], [20]. This becomes a means
tion zone with the longest reach is more susceptible to encroach- today for the operator to study behavior of a system in real time
ment into its operating area which causes maloperation. The and act accordingly.
shape of the relay characteristic is important for avoiding such This paper proposes a method for preventing zone 3 mal-
operation derived from time synchronized data obtained from
strategic locations in a system. The proposed method is car-
Manuscript received January 23, 2013; revised April 30, 2013; accepted July
24, 2013. Date of publication August 21, 2013; date of current version March
ried out in two steps using data obtained from synchrophasor
20, 2014. Paper no. TPWRD-00104-2013. measurements. First, it identifies the possible disturbance region
The authors are with the Department of Electrical Engineering, using a change in measured line currents in the system and then
Indian Institute of Technology, Kharagpur 721302, India (e-mail:
pratimkundu.ee@iitkgp.ac.in; akpradhan@ee.iitkgp.ernet.in).
differentiates a fault from other stressed conditions using ap-
Digital Object Identifier 10.1109/TPWRD.2013.2276071 parent impedance measurements. The algorithm further detects

0885-8977 2013 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
KUNDU AND PRADHAN: SYNCHROPHASOR-ASSISTED ZONE 3 OPERATION 661

the fault during stressed conditions to support zone 3 operation.


The proposed method is tested for the IEEE 39-bus New-Eng-
land system. For various events, such as different types of New
England fault, power swing, load encroachment and voltage sta-
bility in a system, the performance of the proposed method is
found to be correct.

II. PROPOSED METHOD


Incorrect zone 3 operation occurs in a power system at times
as relays cannot distinguish a fault from other events such as
power swing, load encroachment, and voltage instability. The
impedance seen by a distance relay enters the operating zone
even during a nonfault situation and may cause it to malfunction.
One of the reasons for this is that the relay uses local current and
voltage data to take the decision. Similarly, using local informa-
tion, a relay finds difficulty while discriminating a fault, espe-
cially a three-phase fault, which is balanced in nature, during
such stressed events. Fig. 1. IEEE 39-bus New England system.
Operating regions for various relays in an interconnected
power system overlap and during a fault, a number of relays
TABLE I
will see it in their different zones. For all other stressed con- LIST OF BUSES WITH SYNCHROPHASORS
ditions, such as power swing, load encroachment, and voltage
instability, the impedance trajectories for relays do not enter
their operating regions simultaneously. The proposed technique
utilizes this fact and uses synchrophasor data from strategic Step 5) The aforementioned steps are then repeated for sub-
locations in the system to support zone 3 operation. sequent measurement buses.
A. Synchrophasor Measurement Point Selection B. Disturbance Detection
The IEEE 39-bus New England system as in Fig. 1 is consid- The disturbance detection step in the method aims to identify
ered for explaining the proposed method. Synchrophasor mea- measurement buses close to the disturbance area in the system.
surements are obtained from strategic points in the system as To achieve this, transmission lines in the system are divided into
marked in the figure which are listed in Table I. A bus with a various groups and for each group, synchrophasor measurement
synchrophasor measurement in the system is known as P_bus buses are listed. The process for dividing the network into dif-
and the other buses are known as N_bus. The first measurement ferent groups is as follows. To start, any line connected to a
point can be selected arbitrarily and then the measurement point P_bus is selected for a group. Any other line connected to the
selection depends on network connectivity. Thus, the selection previous one is added to the group, with a preference to a line
of measurement points for a network may vary. The choice of connected to an N_bus at the other end. If there is more than one
measurement points should be such that it fulfills the following line which has the N_bus at both ends, then a separate group is
criteria: formed for each of the lines. Next, lines connected to the subse-
1) Each line in the network should be either connected to a quent line and also connected to P_buses at their other ends are
P_bus or under zone 3 reach of minimum two P_buses in picked up in the group. All of the P_buses in a group should have
the network. a common zone 3 operation region. This process is repeated
2) Selection of buses for synchrophasor measurement points until all lines in the system are enlisted into groups. Table II
at consecutive buses are to be avoided, provided it does not lists the transmission lines for the 39-bus system into various
violate constraint 1. groups along with the measurement buses associated with each
Steps for obtaining measurement buses in a system are as group. As an example, for group 2, line 45 is selected first (bus
follows. 4 being a P_bus). Line 58 connected to the above line is next
Step 1) Select any bus in the system as the first measurement selected for the group. Lines 78 and 98, which are connected
bus. to 58 at one end and to a P_bus at the other end, are also added
Step 2) For a relay corresponding to a line connected to the to the group.
selected bus, the zone 3 region of operation in the Any disturbance in the system leads to a change in line cur-
system is identified. rent values which is proportional to the severity of the event. A
Step 3) Buses in the system with relays, which have an over- line current-based detection technique is suitably applied here.
lapping zone 3 region with the previously identified During normal conditions, the phasor sum of line currents ob-
section, are selected as measurement buses. tained from synchrophasors in a group is constant. The change
Step 4) The steps are repeated for each line connected to a in phasor sum is referred to as the disturbance detection index
measurement bus. . Initiation of any abnormal condition in the system leads to
662 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 29, NO. 2, APRIL 2014

TABLE II seen impedance of all P_buses in a group does not enter the
DISTURBANCE DETECTION GROUPS operating characteristics simultaneously.
The index is calculated for each line connected to selected
measurement buses using (3). has a value of less than 1 if the
apparent impedance calculated using synchrophasor measure-
ment is less than the corresponding relay setting. During a fault,
the index value for all the measurement buses will be less than
1.

(3)

if
where if , where ,
if
and correspond to settings of zone 1, zone 2, and
zone 3, respectively, for the th line connected to a th measure-
ment bus of the selected group. is calculated individually for
each line connected to all measurement buses in a group.
The fault detector index is obtained as follows:

a sudden change in its value. A line can be assigned to more (4)


than one group depending on the position of synchrophasors in
the system affecting the phasor sum of each group
if
(1) if
where weights
if &
if & .
where refers to the group number, is the positive-se- The fault detector index is calculated using all measure-
quence current phasor measurement at the th instant, and is ments in a selected group by using (4). A weight is asso-
the number of measurement buses in that group. ciated with each measurement which depends on the apparent
The disturbance detector index for each group is calculated impedance. A negative weight is associated with the index
as if the apparent impedance is less than the relay setting. The ab-
solute value of the weight is highest if the apparent impedance
(2) calculated from synchrophasor measurements is less than zone
1, followed by zone 2 and then zone 3 characteristics of the relay
The index is calculated continuously using synchrophasor connected to those lines. The weight is positive when the calcu-
measurements. For normal conditions, the index value for all lated apparent impedance is greater than the relay zone 3 char-
groups in the system is 0. Any change in the system affects acteristics. During a fault condition, the value of becomes
the value for one or more groups. The disturbance index negative since all of the relays in the selected group see the ap-
threshold is selected in such a way in order to identify any small parent impedance less than their relay settings. In case of other
change in current resulting from variation in system condition events, the index value is positive. During a fault, if any P_bus
and is set as 1% of the predisturbance value. This calculation is in a group sees it in zone 1/zone 2, all other P_buses in the group
obtained for each group. may not see the fault in their respective relay operating regions.
For this reason, a high weight is associated for a zone 1/zone 2
C. Impedance-Based Fault Detector ( )
fault situation. The algorithm detects a fault condition when
Discrimination of a fault from other stressed conditions is becomes negative whereas has a positive value for a nonfault
performed next. Group(s) with changes in their are selected situation.
and analyzed for the detection of faults by using the apparent The selection of weights is based on the fact that the zone
impedance measurement-based fault detector. A group with the 3 reach extends up to the end of the adjacent line. The zone
highest deviation is given preference. The impedance is calcu- 2 reach is up to 100%120% of the line and zone 1 is limited
lated using voltage and current obtained from synchrophasor to 80%90%. Considering such a division for the zones, the
measurements. weights for each zone are assigned differently for subsequent
The measurement points in the system are such that the relay discrimination. The objective of this paper is to prevent zone
operating zones for various measurement points overlap. As a 3 maloperations. Therefore, when a relay sees any disturbance
result, during a zone 3 fault for any P_bus in a group, impedance in lower zones, the algorithm gives higher priority to such dis-
trajectories seen from all other P_buses in that group enter their turbances which is likely to be a fault. Zone 1 and zone 2 are
respective zone 3 operating characteristics. Further, for cases weighted high considering that the possibility of disturbance,
of power swing, load encroachment, and voltage instability, the such as power swing, load encroachment, or voltage instability,
KUNDU AND PRADHAN: SYNCHROPHASOR-ASSISTED ZONE 3 OPERATION 663

Fig. 2. Block diagram of the proposed method.

affecting them is less compared to zone 3. The set of weights


remains the same for different networks.
The block diagram in Fig. 2 shows the main steps involved
in the proposed algorithm. Synchrophasor data can be obtained
from the phasor measurement unit (PMU) or distance relay with
GPS-based time synchronization [21]. The data obtained from
synchrophasors are assumed to be error free. Line current data
are used to detect any abnormal situation in the system and fol-
lowing that, the impedance-based fault detector data are used to
ensure whether it is a fault situation. Line currents and voltages
are obtained from synchrophasor data from strategic locations Fig. 3. (a) Disturbance detector during power swing for group 12.
(b) Impedance trajectory for measurement buses in group 12. (c) Fault
in the system. It identifies the group where the fault has occurred detector result during the power swing for group 12.
and thereby provides support to zone 3 of all relays of the group
and of the connecting lines from the group to other groups. After
a decision has been derived, the relays, as mentioned, are com- 1.2 s, following a three-phase fault at 1 s in the line, has led to
manded, depending on the output of the algorithm. In case of a oscillation in the system.
fault in the group, the output of such a unit should allow the zone From Table II, it can be seen that line 2629 is in group
3 operation of relays in that group. Zone 3 operation is a backup 12. Line currents from each of the three measurementsbus
protection and the time frame of operation is on the order of 1 s. 25 for line 2526, bus 27 for line 2726 and bus 29 for line
The latency associated with the synchrophasor measurements 2928are used for calculating using relation (2) and
due to communication is assumed to not be a problem with this plotted in Fig. 3(a). The initiation and clearance of the fault
method. results in index to have a sudden change in its value. The
two spikes in the figure show the change in the index. A change
III. RESULTS in index for group 12 indicates a disturbance in that group.
To ascertain whether it is an actual fault, the fault detector
The method is tested for the IEEE 39 bus of Fig. 1 with data
index ( ) is calculated using synchrophasor measurements
generated using EMTDC/PSCAD. Positive-sequence voltage
buses in group 12 using (4). The impedance trajectories during
and current are estimated from sample values using 1-cycle
the power swing condition using the synchrophasor measure-
DFT. The sampling rate for voltage and current measurements
ment at bus 25 for line 2526, at bus 27 for line 2726, and at
is maintained at 1 kHz. The results show the application of
bus 29 for line 2928 are shown in Fig. 3(b). The impedance
the algorithm for distinguishing faults from other events, such
plots are obtained by using synchrophasor measurements while
as power swing, load encroachment, and voltage instability.
the operating characteristics are for relays corresponding to the
Further, performance of the algorithm for faults during various
measurement buses for those lines. The impedance trajectory
stressed conditions is also presented.
for bus 29 enters its zone 3 region due to the power-swing
condition. This may result in unwanted zone 3 operation if not
A. Performance During the Power Swing
blocked. calculated using relation (3) for the measurement
During a power-swing condition, current and voltage in the at bus 29 for line 2928 is less than 1 and for the other two
system oscillate. As a result, the impedance seen by the relay measurements in the group, it is greater than 1. The fault
enters into different zones resulting in malfunction. To avoid detector index , calculated using of all measurements in
such an event, the relays need to be blocked. A blocking scheme the group, becomes positive. The plot for of group 12 for the
should be able to verify whether it is a fault situation or not. power-swing condition is shown in Fig. 3(c) where it is positive
In this case, clearance of the line connecting bus 26 and 29 at throughout, which confirms that there is no fault in group 12.
664 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 29, NO. 2, APRIL 2014

Fig. 4. (a) Impedance trajectory for the three-phase symmetrical fault during Fig. 5. (a) Impedance trajectory for the SLG fault during the power swing.
the power swing. (b) Fault detector result for the three-phase symmetrical fault (b) Fault detector result for the SLG fault during the power swing for group 12.
during the power swing for group 12.

plot is shown in Fig. 5(b). The fault status for group 12 be-
B. Performance for Fault During the Power Swing comes high with the inception of the fault as the index be-
comes negative. The apparent impedance in this case is calcu-
Next, the algorithm is evaluated for various faults during an lated, considering the availability of each phase measurement
ongoing power-swing condition and the results are provided from synchrophasor data.
below.
C. Performance During Load Encroachment
1) Three-Phase Fault During Swing: For a fault during a
power-swing condition, a relay may fail in clearing it due to the An increase in loading condition in a system results in the
PSB action. To avoid this, the algorithm must be able to detect impedance trajectories of some relays to enter into their zone
the fault even during the power swing also. 3 characteristics, referred to as load encroachment. The relay
The power-swing condition simulated for this is the same as may apprehend this situation as a fault and issue a trip signal.
in case A. Another three-phase symmetrical fault is created in To avoid relay maloperation, the load encroachment situation
the line connecting bus 26 and 28 at 1.5 s after clearance of the should be distinguished from a fault situation. For this, the
first fault. The impedance trajectories for the case are shown in system is operated at a stressed condition with heavy loading in
Fig. 4(a). A fault in line 2628 results in impedance trajectories many buses. In addition, a sudden change in the loading at bus
calculated by synchrophasor measurements entering the zone 3 17 at 3.2 s is accomplished. The change in the loading condition
regions for corresponding relays at bus 25 for line 2526, at bus results in a change in the index value. As a case, the plot
27 for line 2726 and at bus 29 for line 2928. This results in for the index for group 9 (Table II) is shown in Fig. 6(a).
of each measurement calculated using (3) to be less than 1. For Impedance trajectories for the load encroachment situation
the power-swing case , calculated for the measurement, bus using synchrophasor measurements are shown in Fig. 6(b).
29 is less than 1, but in this case, for all measurements are The impedance trajectories calculated using synchrophasor
less than 1. The weight associated with each measurement for measurements at bus 18 for line 18 17 and at bus 27 for line
calculating thus becomes negative. The fault detector index 27 17 enter the zone 3 region for relays in those buses. In
, which was positive during the power swing, becomes neg- this case, if the operation of the relays is not blocked, then it
ative with the inception of the fault shown in Fig. 4(b). This will result in maloperation. Impedance characteristics at bus
confirms a fault condition in group 12 of the system. 15 for line 1516 are beyond the zone 3 operation region of
2) Single-Line-to-Ground Fault During the Swing: A single- the relay at that bus as shown in the figure. Similarly, for other
line-to-ground fault, in an unbalanced fault case, is created in the two measurements in the group at bus 19 for line 1916 and at
line connecting bus 26 and 28, 1.5 s after clearance of the first bus 24 for line 2416 (not shown in the figure), the impedance
fault. Similar to the previous case, impedance trajectories at bus trajectory does not enter the relay operating region.
25 for line 2526, at bus 27 for line 2726, and at bus 29 for line After the detection of disturbance in group 9, the fault
2928 for the fault in line 2628 calculated using synchrophasor detector index for the group is calculated in order to see
measurements are shown in Fig. 5(a). The fault detector index whether the disturbance is due to any fault or not. For this,
KUNDU AND PRADHAN: SYNCHROPHASOR-ASSISTED ZONE 3 OPERATION 665

Fig. 7. (a) Impedance trajectory for the fault during load encroachment.
(b) Fault detector result for the fault during load encroachment for group 9.

impedance trajectory plot), the fault is beyond its zone 3 region.


The fault detector result for group 9 is plotted in Fig. 7(b).
During the load encroachment issue in case C, the impedance
trajectories for two measurements in group 9 were in zone 3 re-
Fig. 6. (a) Result for the disturbance detector during load encroachment for gions and, therefore, the weights (W) associated during calcu-
group 9. (b) Impedance trajectory for load encroachment. (c) Fault detector re- lation of index are small. With the fault in the zone 1 region
sult during load encroachment for group 9.
for one measurement bus, the weight associated becomes high.
This results in the fault detector index to be negative. Before
the fault condition, index shows a positive value and with the
the fault detector index is calculated for all measurements inception of a fault, the index becomes negative. This confirms
in the group. Index for two measurements which enter the a fault situation by the method in group 9 of the system. This
relay operation zone, is less than 1 and has negative weights result shows that the algorithm can successfully detect the fault
while the other three are positive. Thus, the fault detector index situation in any line of a group even during load encroachment.
becomes positive. The plot for index , shown in Fig. 6(c), is
positive throughout confirming a nonfault situation. Thus, the
zone 3 relay operation in group 9 can be blocked effectively by E. Performance During Voltage Instability
such a strategy in order to avoid unwanted tripping due to load
encroachment. During voltage instability, voltage at various buses in the
system declines rapidly [3]. Due to the LV level in buses, the
D. Performance for the Fault During Load Encroachment impedance trajectory may enter into the zone 3 region causing
it to maloperate. The performance of the proposed algorithm
A fault during the load encroachment situation should be de- during a voltage instability situation is evaluated here. An in-
tected for proper relay operation. A three-phase fault is simu- crease in the reactive load in some selected buses over a period
lated in the line connecting bus 17 and 27 at 5 s during a load of time leads to a drop in the voltage level of the system. The
encroachment situation as in case C. The impedance trajectory positive-sequence voltage plot for some of the buses is shown
plots for the situation are shown in Fig. 7(a). in Fig. 8 at such a condition. The impedance trajectory for syn-
It can be seen that initially due to load encroachment, chrophasor measurements at bus 27 for line 2726 is shown in
impedance trajectory calculated using synchrophasor measure- Fig. 9. It is seen that due to a drop in the voltage of bus 27, the
ments at bus 18 for line 1817 and at bus 27 for line 2717 impedance trajectory enters the zone 3 region of the relay at that
enters the zone 3 region. A fault in line 1727 is created at 5 s bus.
which results in bus 27 for line 2717 to see the fault in its zone As shown in Fig. 8, many buses in the system are affected
1 region, and for line 1817 at bus 18 in the zone 3 region for during a voltage instability situation due to which most of
the situation. For measurements at bus 15 for line 1516, at bus the groups listed in Table II will be affected. In this case,
19 for line 1916 and at bus 24 for line 2416 (not shown in the index for two measurement groups 9 and 12 is shown
666 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 29, NO. 2, APRIL 2014

Fig. 8. Bus voltage plot for the voltage instability case.

Fig. 11. (a) Fault detector result for the fault during voltage instability for group
Fig. 9. Impedance plot for bus 27 during voltage instability. 9. (b) Fault detector result for the fault during voltage instability for group 12.

group 12 while for group 9, it is still positive, thus ensuring no


fault there. This ensures the accuracy of the algorithm in distin-
guishing a voltage instability condition from a fault and, thus,
preventing relay maloperation.

IV. CONCLUSION
Relay maloperation may disrupt the smooth operation of a
power system. Distinguishing the fault condition from other
stressed events to prevent relay maloperation becomes imper-
ative. The method proposed for such an objective is based on
the application of synchrophasor data. Synchrophasor measure-
ments are obtained from strategic locations in the system. The
lines in the system are divided into various groups and for each
group, synchrophasor measurement buses are listed. A current
phasor-based detector is used to identify any change in the
system due to the initiation of any disturbance. This detector
helps to identify measurement buses close to the disturbance in
the system. Another index calculated from synchrophasor data
is used to distinguish a fault from other power system-stressed
conditions. The fault detector index is applied to groups where
Fig. 10. (a) Fault detector result during voltage instability for group 9. (b) Fault the disturbance detector detects abnormal behavior. Test results
detector result during voltage instability for group 12.
on the IEEE 39-bus system show the capability of the proposed
method to enhance the protection decision for zone 3 operation.
in Fig. 10(a) and (b), respectively. In both figures, the fault ACKNOWLEDGMENT
detector index is positive, confirming a nonfault situation.
The authors would like to thank the Department of Science
F. Performance of the Fault During Voltage Instability and Technology (DST), New Delhi, India, for sponsoring the
project Protecting power systems using wide-area measure-
A three-phase fault at 3.05 s in line connecting buses 26 ments- SR/33EECE009/2009, through which the research was
and 27 during the voltage instability situation as in the afore- conducted.
mentioned case is used to test the algorithm. The index for
two measurement groups 9 and 12 are shown for this case in REFERENCES
Fig. 11(a) and (b), respectively. The index becomes nega- [1] S. Horowitz and A. G. Phadke, Third zone revisited, IEEE Trans.
tive with the inception of fault at 3.05 s, confirming a fault in Power Del., vol. 21, no. 1, pp. 2329, Jan. 2006.
KUNDU AND PRADHAN: SYNCHROPHASOR-ASSISTED ZONE 3 OPERATION 667

[2] M. Jin and T. S. Sidhu, Adaptive load enchroachment scheme for [16] K. Seethalekshmi, S. N. Singh, and S. C. Srivastava, A classifica-
distance protection, Elect. Power Syst. Res., vol. 78, no. 10, pp. tion approach using support vector machines to prevent distance relay
16931700, 2008. maloperation under power swing and voltage instability, IEEE Trans.
[3] M. Jonsson and J. Daalder, An adaptive scheme to prevent undesirable Power Del., vol. 27, no. 3, pp. 11241133, Jul. 2012.
distance protection operation during voltage instability, IEEE Trans. [17] S. M. Brahma, Distance relay with out-of-step blocking function
Power Del., vol. 18, no. 4, pp. 11741180, Oct. 2003. using wavelet transform, IEEE Trans. Power Del., vol. 22, no. 3, pp.
[4] Powergrid, Report of the enquiry committee on grid disturbance 13601366, Jul. 2007.
in northern region on 30th July 2012 and in Northern, Eastern and [18] C. Pang and M. Kezunovic, Fast distance relay scheme for detecting
North-Eastern Region on 31st July 2012, New Delhi, India, Tech symmetrical fault during power swing, IEEE Trans. Power Del., vol.
Rep. GRID_ENQ_REP_16_8_12, 2012. 25, no. 4, pp. 22052212, Oct. 2010.
[5] P. Kundur, Power System Stability and Control. New York: Mc- [19] I. Kamwa, A. K. Pradhan, and G. Joos, Fuzzy partitioning of a real
Graw-Hill, 1994. power system for dynamic vulnerability assessment, IEEE Trans.
[6] Z. D. Gao and G. B. Wang, A new power swing block in distance Power Syst., vol. 24, no. 3, pp. 13561365, Aug. 2009.
protection based on a microcomputer-principle and performance [20] A. G. Phadke and J. S. Thorpe, Synchronized Phasor Measurements
analysis, in Proc. Int. Conf. Advances Power Syst. Control, Oper. and Their Applications. New York: Springer, 2008.
Manage., Nov. 1991, vol. 2, pp. 843847. [21] A. Guzman, S. Samineni, and M. Bryson, Protective relay syn-
[7] IEEE Power Syst. Relay Committee Working Group D6, Power swing chrophasor measurements during fault conditions, Schweitzer
and out-of-step considerations on transmission lines, Tech. Rep., Jul. Engineering Laboratories, Pullman, WA, Tech. Rep. 20050920
2005. TP621401, 2006.
[8] A. P. Apostolov, D. Tholomier, and S. H. Richards, Superimposed
components based sub-cycle protection of transmission lines, in Proc.
IEEE Power Eng. Soc. Power Syst. Conf. Expo., Oct. 2004, vol. 1, pp. Pratim Kundu received the B.Tech degree in elec-
592597. trical engineering from West Bengal University of
[9] H. K. Zadeh, Evaluation and performance comparison of power swing Technology, Kolkata, India, in 2009 and the M.S. de-
detection algorithms, in Proc. Power Eng. Soc. Gen. Meeting, Jun. gree in electrical engineering from the Indian Insti-
2005, vol. 2, pp. 18421848. tute of Technology Kharagpur, Kharagpur, India, in
[10] T. Seegers and E. Krizauskas, Transmission line protective systems 2013, where he is currently pursuing the Ph.D. de-
loadability, Power System Relay Committee of Power Eng. Soc., gree in electrical engineering.
Tech. Rep., 2001. [Online]. Available: http://www.pes-psrc.org/Re- His current research area is the protection of power
ports/D6_Loadability.pdf systems using wide-area measurements.
[11] H. Song, B. Lee, and V. Ajarappu, Control strategies against voltage
collapse considering undesired relay operations, in Proc. Inst. Eng.
Technol., Gen. Transm. Distrib., 2009, vol. 3, pp. 164172.
[12] L. D. Arya, S. C. Choube, and M. Shrivastava, Technique for voltage
stability assessment using newly developed line voltage stability
index, Energy Convers. Manage., vol. 49, no. 2, pp. 267275, 2008. Ashok Kumar Pradhan (M94SM10) received
[13] M. M. Begovic and A. G. Phadke, Power system emergency control the Ph.D. degree in electrical engineering from
near voltage instability, in Proc. IEEE 28th Dec. Control, Dec. 1989, Sambalpur University, Sambalpur, India, in 2001.
vol. 3, pp. 21792180. He has been with the Department of Electrical En-
[14] C. H. Kim, J. Y. Heo, and R. K. Aggarwal, An enhanced zone 3 al- gineering, Indian Institute of Technology, Kharagpur,
gorithm of a distance relay using transient components and state dia- India, since 2002, where he is currently a Professor.
gram, IEEE Trans. Power Del., vol. 20, no. 1, pp. 3946, Jan. 2005. His research interests include power system relaying
[15] H. K. Zadeh and Z. Li, A novel power swing blocking scheme using and monitoring.
adaptive neuro-fuzzy inference system, Elect. Power Syst. Res., vol. Prof. Pradhan is a Fellow with the Indian National
78, no. 7, pp. 11381146, 2008. Academy of Engineering.

You might also like