MFC2000-6 Instruction V2.00

MFC2000-6

High-Speed Bus Power Transfer

System

Instruction

Wiscom Electrical Co., Ltd

Wiscom System Co., Ltd

2011.02

Preface

Thanks very much for purchasing MFC2000-6 High-Speed Bus Power Transfer System
manufactured by WiscomStock code: 002090.

http://www.mianfeiwendang.com/

This technical instruction do not purpose to cover all details or variations in


equipment nor provide for every possible contingency to be met with
installation, operation, or maintenance. Thus if further information are desired
or particular problems arise, please refer the matter to Wiscom directly for
further solution.

Also, for more product information, instruction manual updates and services,
please visit the our website .

_____________________________________________________________

Copyright ? Wiscom System Co., Ltd, All rights reserved

Versionhttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dac: MFC2000-6
V2.00 Published2011.02.

This instruction is for reference only.

Table of Contents

1.
Introduction ...................................................................
...............................................................................
1

2. Features & Main Technical


Parameters .....................................................................
................................ 1

http://www.mianfeiwendang.com/
2.1
Features .......................................................................
........................................................................... 1

2.2 Main Technical


Parameters .....................................................................
............................................... 3

3 Transfer
Functions ......................................................................
.............................................................http://www.mianfeiw
endang.com/doc/ad728c1408dd2282601e9dac..... 6

3.1.
Overview .......................................................................
........................................................................ 6

3.2 Initiating
Methods ........................................................................
.......................................................... 6

3.3 Transfer
Modes ..........................................................................
............................................................ 7

3.4 Transfer
Methods ........................................................................
........................................................... 9

3.5 Transfer
Lockout/Blocking ...............................................................
................................................... 10

4. Load

http://www.mianfeiwendang.com/
Shedding .......................................................................
.................http://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dac.....
............................................... 12

5. Initiate After-Accelerated Protection


(AAP) ..........................................................................
.................. 12

6. Other
Functions ......................................................................
.................................................................... 12

6.1 SOE
Log ............................................................................
.................................................................. 12

6.2
Communication ..................................................................
.................................................................. 13

6.3 GPS
Function .......................................................................
................................................................ 13

6.4 Print
..................................................http://www.mianfeiwendang.com/
doc/ad728c1408dd2282601e9dac....................................................
................................................ 13

6.5 Software
Supporting .....................................................................
....................................................... 14

7. Design

http://www.mianfeiwendang.com/
Instructions ...................................................................
.................................................................. 14

7.1
Application ....................................................................
....................................................................... 14

7.2 Input/Output
Terminals ......................................................................
.................................................. 14

7.3 Design Referential


Figures.........................................................................
.......................................... 18

8. Setting
Rehttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacport ...............
................................................................................
.............................................. 20

8.1
Setpoints ......................................................................
......................................................................... 20

8.2
Controls .......................................................................
......................................................................... 21

8.3
Description ....................................................................
....................................................................... 21

9 User Manual
Introduction ...................................................................

http://www.mianfeiwendang.com/
..................................................... 25

9.1 Front-panel
Plan ...........................................................................
..................http://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dac....
.................................. 25

9.2 LCD
Display ........................................................................
................................................................ 25

10
Appendix .......................................................................
..............................................................................
29

1. Introduction

MFC2000 series devices are applicable to power plants in different scales or


some chemical industry, metallurgy industry and coal industry, etc, where bus
power plant transfer is necessary. In these cases, current and voltage impacts
caused by voltage difference between feedback voltage and standby voltage must
be put into consideration so as to avoid the occurrence of some unexpected
situations.

High-speed bus power supply transfer system is an important part of the power
plant auxiliary system. Together with
gehttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacnerator-transformer
protection, excitation regulator and sync device, they play key roles to ensure
a safe and stable operation situation of the whole system.

MFC2000-1 was unveiled in 1997 and it is the first High-speed bus power transfer
device in domestic market. The Synchronization Capture Transfer Theory, also
known as Delayed in-phase Transfer Theory applied in this device is first

http://www.mianfeiwendang.com/
proposed by Southeast University and Wiscom System Company together, which
reinforces the principle of Bus Power Supply Transfer. In January, 1997, the
first set MFC2000-1 was put into operation in No.11 generator (300 MWs) in
Wangting electric power plant. In 1998, MFC2000-1 was awarded Third Class
Science & Technology Advancement Prize of National Power Company and Second
Class Science & Technology Advancement Prize of East China Electric Power Group.
In 2000, MFC 2000-1 was upgraded to MFC2000-2.

Up to now, more than 1000


sehttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacts MFC2000 devices
have been utilized in more than 1000 generator units all over the country, such
as Beijing Shijingshan power plant, Tianjin Panshan power plant, Hebei
Zhangjiakou power plant and Hainan Sanya power plant etc. At the same time,
MFC2000 devices are also exported to India, Iran, Pakistan, Turkey and Vietnam
etc.

Based on MFC2000-2 and MFC2000-3, the multifunctional and high performance


MFC2000-6 is developed. The new generation MFC2000-6 device with 320240 color
LCD display adopts 32-bit DSP, bus backboard and back-inserted structure, which
improve the electromagnetic compatibility and debug effectively.

2. Features & Main Technical Parameters

2.1 Features

Compared with MFC2000-3, MFC2000-6 has further advancements in function and


performance. The main features are as follows:

Practical and Complete Transfer Function.

Manual transfer mode consists of


parallelhttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dac transfer,
simultaneous transfer and sequential transfer. Parallel transfer includes
automatic parallel transfer function and semi-auto parallel transfer function.

http://www.mianfeiwendang.com/
Automatic transfer, which is applied in accident or abnormal instance, consists
of simultaneous

transfer and sequential transfer. Transfer methods include Fast transfer,


Delayed In-Phase transfer, Residual-voltage transfer and Fixed Time transfer,
among which Delayed In-Phase transfer has two methods: constant lead phase-
angle and constant lead time.

Suitable for Cold & Hot Standby Power Mode

Applicable to power supply transfer in cold or hot standby mode.

Advanced DSP Technique

High-speed DSP and 14-bit high performance A/D converter are adopt in MFC2000-6,
which enable automatic frequency tracking, sampling and calculating as well as
fast and accurate amplitude, phase and frequency measurement.

Convenient Debhttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacug

AC analog measurement accuracy adjustment, device settings and debug as well as


DI/DO testing can be done convenient.

Friendly Human-machine Interface

320240 LCD display can show various pictures such as connection diagram, and
action process records and so on.

Strong and Perfect Function of Event Record

At most 16 events records and 55 s sampling waveform can provide objective and
worthy data for accident or abnormal situation analysis. All records can be
held when power is off. Waveform is saved as standard COMTRADE format, so it is
can be analyzed by general analyzing software. Dual-net Communication

http://www.mianfeiwendang.com/
Function

Support dual-net communication and multiple protocols such as MODBUS; can be


connected to DCS system and ECS system conveniently.

GPS Time Calibration function

With two timing methods: Second Pulse and IRIG-B

Advanced Hardware
Crafthttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dac

Main modules adopt large-scale programmable logic chip and SMT technique as well
as multi-layer printed board.

Advanced Cabinet Structure

Employ back-inserted and motherboard configuration and separated heavy and weak
currents to improve the anti-disturbance performance.

Strong PC System Management Software

The device is installed with PC system management software, with main functions
as configuration, waveform reading, COMTRADE waveform analysis, recording event
reading & printing etc,.

2.2 Main Technical Parameters

2.2.1 Ambient Conditions

Normal working temperature: -10 55

Working temperature limit: -25 70



http://www.mianfeiwendang.com/
Humidity: 5%90% (no condensing)

Atmospheric pressure: 80KPa110Kpa

Altitude: 4000m

2.2.2 Working Power

Rated voltageDC220V/DC110V

Permissible variation-20% 15%

Riphttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacple coefficient:
5%

2.2.3 Rated AC Inputs

AC current: 5A

AC voltage: 100V or 57.7 V

Frequency50Hz

2.2.4 Working Range

Current: 0.2A20A

Voltage: 1.0V120V. (Line voltage)

Frequency: 30Hz65Hz

Phase angle: -180? 180?

2.2.5 Measurement Accuracy



http://www.mianfeiwendang.com/

Voltage: Class 0.5

Current: Class 0.5

Frequency0.02Hz

Phase angle0.2

GPS timing: 1ms

2.2.6 Digital Inputs

Interior signal level: 220VDC.

2.2.7 Trip/close Outputs

Output style: Dry contact,

Contact capacity: DC220110V8Apickup.

2.2.8 Signal Outputs

Output style: Dry contact

Contact capacity: DC220110V5Apickup

2.2.9 Transfer Time

The shortest outage time of Accident simultaneous transfer: 10 ms user-


defined delay timehttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dac
standby breaker close time working breaker trip time

The shortest outage time of Accident Sequential transfer: 10 ms standby



http://www.mianfeiwendang.com/
breaker close time working breaker trip time

2.2.10 Main Hardware Standards

CPU bits: 32

DSP number: 1

A/D sampling bits: 14

AI9

DI14

DO (output)12

DOsignal: 20

Communication interface: Dual-net, RS485 and Modbus etc.

GPS: 1-channel timing pulse

LCD display: 320240

2.2.11 Oscillographic Recording

Transfer operation reports: 16

DI records: 64

Warn events: 64 Command Records: 64 Transfer operation reports with


sampling data recording: 5

http://www.mianfeiwendang.com/

Sampling data recording time: 5s.

2.2.12 Load and Power Consumption

AC voltage circuit: 0.5VA/phase

AC current
circuit:0.5VA/phasehttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dac

Working power: total power consumption 50W (normal operation);

total power consumption 60W (Transfer)

2.2.13 Overload Capacity

AC current circuit: Work continuously under 2 times the rated current.

Work continuously for 10 seconds under 10 times the rated current.

Work continuously for 1 second under 40 times the rated current.

AC voltage circuit: Work continuously under 1.5 times the rated voltage.

DC power circuit: Work continuously under 80%~115% rated voltage.

2.2.14 Anti-disturbance performance

Electrostatic Discharge Test under GB/T14598.14 standard.

Radiated Electromagnetic Field Disturbance Test under GB/ T14598.9 standard.

1MHZ Burst Disturbance Test under GB/T14598.13 standard.



http://www.mianfeiwendang.com/
Fast Transient Disturbance Test under GB/T14598.10 standard.

2.2.15 Insulation performance


://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacr The Dielectric
Strength Test regulated in 19th section of GB7261.

The Insulating Resistance Test regulated in 19th section of GB7261.

The Damp-heat Test regulated in 21st section of GB7261.

2.2.16 Mechanical performance

Vibration: The Class I of Vibration Endurance Test regulated in 16.3 section


of GB7261.

Shock: The Class I of Shock Withstand Test regulated in 7.5 section of


GB7261.

Bump: The Class I of Bump Endurance Test regulated in 18 section of GB7261.

2.2.17 Size

Standard 4U insert-cabinet: 442.8W175H290Dmm.

2.2.18 Weight

About 15Kg

3 Transfer Functions

3.1. Overview

http://www.mianfeiwendang.com/
3.2 Initiating Methods

MFC2000-6 provides 3 Initiating methods: Manual Initiated Transfer, Relay


Initiated Transfer and Abnormal Initiated Transfer.

3.2.1 Manual Initiated Transfer


://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacA Manual Initiated
transfer means the transfer is initiated by using the local Human-Machine
Interface (HMI), or from a control/status input manually. The Manual Transfer
allows operation in either direction: from Work Source to Standby Source, and
vice versa. Manual Transfer provides Parallel Transfer, Sequential Transfer and
Simultaneous Transfer. When any lockout/blocking condition occurs, the Manual
Transfer will be blocked. In this case, the device will neither respond to any
transfer command nor send the trip command yet.

3.2.2 Relay Initiated Transfer

Relay Initiated Transfer means the transfer is initiated by an external


protection trip signal using control/status input to the device. Relay Transfer
is single-directional operation: from Work Source to Standby Source. The Relay
Transfer provides Fast Transfer (Sequential or Simultaneous), Delayed In-Phase
Transfer, Residual Voltage Transfer and Fixed
Thttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacime Transfer when any
of the mentioned transfer criteria is satisfied. The Relay Transfer will be
blocked when any lockout/blocking condition occurs and the device will either
respond to any transfer command or send the trip command.

3.2.3 Abnormal Initiated Transfer

Abnormal Initiated Transfer includes two ways: Under-voltage Initiated Transfer


and Auto-trip Initiated Transfer.

Under-voltage Initiated Transfer means the transfer is triggered from Work


Source to Standby

http://www.mianfeiwendang.com/

Source only by a sudden loss of motor bus supply voltage through the internal
bus under-voltage relay. The Under-voltage transfer can be implemented through
Fast Transfer (sequential or simultaneous), Delayed In-Phase Transfer, Residual
Voltage Transfer and Fixed Time Transfer when any of the

mentioned transfer criteria is satisfied. The transfer function will be blocked


when any lockout/blocking condition occurs. In
thttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dachis case the device
will neither respond to any transfer command nor send trip commands.

D_Usyqd: UV Init Vol Amp; D_Iwl: Under-current Value. D_Tsy: UV Init Delay.
D_jxdy:The setting UV Init Check Work Line Vol. Ugz:Work source voltage:
Igz:Work source current .

Umax

D_jxdy=0&&IgzDD_jxdy=1&&Ugz

Auto-trip Initiated Transfer means the transfer is initiated from Work Source to
Standby Source only, when the Work Source circuit breaker is tripped. The Auto-
trip Transfer can be realized through Fast Transfer, Delayed In-Phase Transfer,
Residual Voltage Transfer or Fixed Time Transfer when any of the mentioned
transfer criteria is satisfied. The Transfer will be blocked when any
lockout/blocking condition occurs. In this case, the device will either respond
to any transfer command or send trip

commands. Iwl:

Under-current Value. D_WTWL: AutoTripUnder-



http://www.mianfeiwendang.com/
currehttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacnt CRTA control
number.

3.3 Transfer Modes

MFC2000-6 provides 4 transfer modes: Parallel Transfer, Simultaneous Transfer,


Sequential Transfer and Sequential Mode Transfer.

3.3.1 Parallel Transfer (ParTran)

Parallel transfer is widely used during startup and planned shutdown process.
With this method, the Standby source breaker is closed before Work Source
breaker is opened. The intent is to transfer power sources without interruption.
Prior to the transfer, it must be assumed that both sources are in synchronism
or in an acceptable range, which will prevent the motor bus voltage from
becoming dead if the circuit breaker fails to close and the other breaker is
tripped or overstressing the bus system and cause damage to the equipment.

In parallel transfer, if breaker A has been closed while the other breaker B
still remains closed status and not tripped within the predefined
http://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacparalleling time, the
auto-decoupling feature will open the closed breaker A to ensure a safe
operating environment,when the settingManTran Enable Decouplingis enable.

Parallel Transfer is bidirectional, and can only be used in Manual Initiated


Transfer. According to the operation process, Parallel Transfer can be
classified as Automatic Parallel Transfer and Semiautomatic Parallel Transfer.

Note: On Parallel Transfer occasion, only Fast Transfer method can be attempted.
Parallel Transfer is usually used for two sources with the same frequency and an
acceptable phase angle.

http://www.mianfeiwendang.com/
3.3.1.1 Automatic Parallel Transfer

When an Automatic Parallel Transfer is initiated, MFC2000-6 will close the


standby source circuit break first and after a time delay (can be configured in
settings); the device will trip the work source circuit breaker automatically.

3.3.1.2 Semiautomatic Parallel Transfer


://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacparWhen a Semiautomatic
Parallel Transfer is initiated, the device will close the standby source circuit
breaker first, and then the operator will trip the work source breaker manually
after his confirmation that the standby source has been closed.

3.3.2 Simultaneous Transfer (SimTran)

When a Simultaneous Transfer is initiated manually, the commands to trip work


source breaker and to close standby source breaker will be issued at the same
time. Basically, since natural Close time is longer than Trip time, the Trip
operation is usually completed before closure. However, due to breaker operating
time variations and control voltage variations, temporary unintentional
paralleling of the sources also may occur. Prior to the transfer, the phase
angle and voltages from the motor bus and the standby source must be evaluated
to assure that the motor bus and standby source are in synchronism. After
initiated, all four
http://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dactransfer methods,
Fast, Delayed In-Phase, Residual Voltage and Fixed Time Transfers are enabled.
Whose action criterion is met first, the related transfer method will be
adopted. In Simultaneous Transfer, an auto-decoupling feature is included to
trip the breaker that was closed by the transfer if the breaker that should be
opened has not been opened within the predefined time.

3.3.3 Sequential Transfer (SeqTran)

When a Sequential Transfer is initiated, work source breaker is tripped first


and the closure of standby source breaker will be implemented only upon

http://www.mianfeiwendang.com/
confirmation that the work source breaker has been opened. After receipt of this
confirmation, all four methods, Fast, Delayed In-Phase, Residual Voltage and
Fixed Time Transfer are enabled. Whose action criterion is met first, the
related transfer

method will be adopted to close the standby source breaker.

3.3.4 Sequential Mode


Transferhttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dac

A Sequential Mode Transfer is similar to Sequential Transfer. But it is launched


only by Auto-trip initiated Transfer only from work source to standby source.
When the work source circuit breaker is tripped, the device will issue the close
command. In the whole process, work source and standby source are sequential.
But unlike the standard Sequential Transfer under which the work source breaker
is tripped by some external reasons, this transfer is tripped by the mis-trip of
the work source breaker.

3.4 Transfer Methods

MFC2000-6 provides 4 transfer methods: Fast Transfer, Delayed In-Phase Transfer,


Residual Voltage Transfer and Fixed Time Transfer.

3.4.1 Fast Transfer (FastTran)

Fast Transfer is being used at more and more power plants in an attempt to avoid
the delay involved with Residual Voltage Transfer. With this method, the standby
source breaker is closed almost immediately
afhttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacter the work breaker
is opened. Although the residual motor voltage is still high, the spinning
motors have no time to slip out of phase with the standby source, therefore the
transfer is relatively surge-free.

Fast Transfer assumes that the standby source is in phase with the work source.

http://www.mianfeiwendang.com/
If for any reason it is not, extremely high voltages may be applied across the
motor terminals which are quite possible to destroy either the motor or the
station service transformer. In this case, a high-speed sync-check relay is
employed in MFC2000-6 to verify the phase angle before transferring so as to
avoid the unexpected matters.

3.4.2 Delayed In-Phase TransferDIP Tran

Delayed In-phase transfer (Synchronization Capture Transfer) is a method that


can be accomplished only through automatic control. When a motor bus is
disconnected with its power supply, the residual voltage will gradually decrease
in both magnihttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dactude and
frequency as the motors slow down. Meanwhile, the standby source frequency
remains constant. The result is that the residual voltage falls in and out of
phase with the standby source voltage at an ever-increasing rate as the motors
slow down. Delayed In-phase Transfer aims to close the standby source breaker
exactly when the two voltages are in phase, with bus voltage as 65%--70% of
rated value.

3.4.3 Residual Voltage Transfer (ResVol Tran)

This kind of transfer waits until the residual voltage on the isolated motor bus
has dropped to about 25% of rated voltage before reconnecting. The reason for a
so low residual voltage is because when

the standby source breaker is closed, the residual voltage maybe happens to be
substantially out of phase with the standby source voltage, the resultant
voltage applied across the spinning motor terminals may be as high as 1.25 times
the rated voltage, which
whttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacould produce a
starting current up to

7.5 times rated current and a starting torque of more than 9 times rated torque.
Any higher residual voltage would put unacceptable mechanical and electrical

http://www.mianfeiwendang.com/
tresses on the system.

3.4.4 Fixed Time Transfer(Fixed Time Tran)

In Fixed Time Transfer, the motor bus is connected to the standby source after a
time delay when the voltage on the coasting motor bus has fallen to less than
0.25pu. In this manner, no matter what degree the phase angle is, the resultant
V/Hz will not exceed 1.33 V/Hz. However, this type of transfer may not be fast
enough to maintain the continuity of the whole process and have negative impact
on the whole system.

3.5 Transfer Lockout/Blocking

A transfer is blocked when any lockout/blocking condition described below is


active.

3.5.1 Lockout

A lockout occurs and MFC2000-6 enters into Wait-For-Reset state when


http://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacany of the following
condition is active. A Wait-For-Reset state will automatically change to Ready-
to-Transfer state when these conditions are all removed.

? Control input contact TranExit (External Transfer)is closed.

? Setting Transfer(Internal Transfer) is set as Disable.

? All transfer methods, including Fast Transfer, Delayed In-Phase Transfer,


Residual-voltage

Transfer and Fixed Time Transfer, are all disabled.

No transfer will be initiated here until all lockout conditions are removed
(suppose no blocking exists).

http://www.mianfeiwendang.com/

3.5.2 Blocking

A blocking occurs and MFC2000-6 enters into Wait-For-Reset state when any of the
following condition is active. A Wait-For-Reset state will not change to Ready-
to-Transfer state, even when these conditions are all removed; an additional
manual reset operation is a must.

3.5.2.1 After-Transfer Blocking(AftTran)

http://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacThis occurs after a


transfer operation. This blocking will not be removed until MFC2000-6 is reset
manually.

3.5.2.2 ProtectBlock

This occurs when control input contact RLYBlock is closed. This blocking
will not be removed until MFC2000-6 is manually reset and the contact
RLYBlock open.

3.5.2.3 Breakers Same Status Blocking(BSS)

Breakers same status blocking includes following conditions:

? Both breakers open.(Auto-trip initiate is an exception)

? Both breakers closed

? Bus PT Isolating switch (PTIS) is open

This blocking will not be removed until MFC2000-6 is reset manually and the two
breaker status contacts are different (one in open state, the other in close )
and the PTIS is closed.

http://www.mianfeiwendang.com/
3.5.2.4 PT Fuse-Loss Blocking(PT Fuse-Loss) Transfer is blocked if the bus PT
fuse loss is detected. This blocking will not be removed until

MFC2000-6 http://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacis manually


reset and no bus PT fuse-loss is detected.

3.5.2.5 Standby-Source-Under-Voltage Blocking (StbLoss Block)

Standby Source in this section is referred to standby source when


transfer direction is from work s to standby, or referred to work source
when transfer direction is from standby to work. If the standby power source
voltage is lower than the setting SSUV Vol Amp, all transfers will be
blocked. This blocking will not be removed until its voltage increases to the
acceptable range.

Note: Manual reset isnt needed under this condition.

Obviously, its meaningless to launch a transfer when the standby power source
actually loses its power. However, when the standby power source PT is under
repair, the standby voltage will not be detected, but as a mater of fact, the
standby source voltage is normal, hence transfer is permitted.

In this case, Standby-


Sourcehttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dac-Under-Voltage
Blocking Enable/Disable function is developed. When the setting SSUVB is Set
as enable, the transfer will be blocked when the standby source voltage is
lower than the setting SSUV Vol Amp. If the setting SSUVB is set as
disable, even the standby power source voltage is detected to be lower than
the setting SSUV Vol Amp; the device can still initiate transfer function.
But the transfer methods can only be Residual Voltage Transfer and Fixed Time
Transfer.

http://www.mianfeiwendang.com/
3.5.2.6 Device Fault Blocking(Device Fault)

After the device is powered on, it will keep on checking some important hardware
such as CPU,

EEPROM. If any abnormal situation is detected, the device will enter into
blocking state. Of course, if CPU does not work completely, no checks will be
done and thus no blocking will be implemented. This kind of blocking will not be
removed until MFC2000-6 is manually reset and no Device
Fahttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacult Blocking is
detected.

4. Load Shedding

Whether motors can be started up successfully after a transfer process, is


mainly effected by 3 factors: the standby transformer capacity, bus voltage at
the time that standby power source is launched and load amount and capacity.
Basically, during this procedure, some insignificant loads will be cut off to
ensure the operation continuity of key loads.

MFC2000-6 provides a two-stage load shedding function. Each stage has its own
voltage limit and time delay limit which can be set in the setting report
respectively. MFC2000-6 will supervise bus voltage after standby source switch
has been closed. If bus voltage and time delay both are beyond their limit
ranges, the device will issue load shedding command to cut off some loads.

Load shedding function is initiated only when the device implement transfer
function.

5. Initiate After-Accelerated
Prhttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacotection (AAP)

MFC2000-6 provides an output contact to initiate the external after-accelerated


protection in the process of a transfer operation.

http://www.mianfeiwendang.com/

6. Other Functions

6.1 SOE Log

Complete SOE logs and transfer oscillographic records are displayed.

6.1.1 Logs and Oscillographic records

16 transfer logs, among which the recent 5 transfer records are supplied with
5s oscillographic

recording;

64 DI status records stamped with time and DI name

64 device abnormal events:

Abnormal Events include following types:

Breakers all open when electrify, breakers all closed when electrify, breaker
all closed when close standby, breakers all closed when closed work, breakers
all open when trip standby, PT isolating switch open, PT fuse loss, device
fault, work fake open, etc.

64 device command records:

Command Records
incluhttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacde following
types: Modify SysSetting, Modify TranSetting,Modify ComSetting, The set point
over range when modifying

6.1.2 Contents of SOE



http://www.mianfeiwendang.com/
Content of logs listed below can be displayed on LCD or printed by a printer.

Transfer time (year, month, day ,hour, minute, second, millisecond)

Initiating method

Transfer mode

Issued trip and close commands

Transfer method

Lockout/blocking and faults conditions

Time, delta frequency, delta phase angle, bus voltages and branch current
when a transfer is

initiated

Time, delta frequency, delta phase angle, bus voltages and branch current
when a trip command

is issued

Time, delta frequency, delta phase angle, bus voltages and branch current
when a circuit

breaker has opened

Time, delta frequency, delta phase angle, bus voltages and branch
curhttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacrent when a close

command is issued.

http://www.mianfeiwendang.com/
Time, delta frequency, delta phase angle, bus voltages and branch current
when a circuit

breaker has closed

These logs are stored in MFC2000-6 and will not be lost when device is reset or
powered on.

6.1.3 Content of Oscillographic Recording

Up to 5 records with 5s waveform each

recording formats:

For three-phase bus voltage, work source voltage, standby source voltage and
branch current: 12data samples per cycle for2.5s (from100ms before initiating to
2400ms after initiating) and then, one effective value per 20ms will be recorded
within 2.5seconds.

6.2 Communication

The device has two RS485 ports connecting with DCS and ECS. Default protocol:
supporting MODBUS. Default baud rate: 38400bps.

6.3 GPS Function

With two timing methods: Second Pulse and IRIG-B

6.4 Print
://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacparAll events can be
printed for analysis, research or archive.

6.5 Software Supporting



http://www.mianfeiwendang.com/
The device can install MFC2000-6 system management software to upload data and
analyze oscillographic recordings etc,.

7. Design Instructions

7.1 Application

Every auxiliary system branch of each generator unit should be equipped with one
separated MFC2000-6 device.

Station service transformer may be in either hot-standby state or cold-standby


state. If transfer happens in cold-standby state, the device can close the
breakers together in high voltage side and low voltage side. To ensure a Fast
Transfer, low-voltage-side and high-voltage-side breakers must be high-speed
breakers (close time should be shorter than 0.1 second). Otherwise, Fast
Transfer can not be assured, but Delayed In-Phase Transfer can be implemented.

Every standard cabinet can accommodate four MFC2000-6


deviceshttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dac, one printer,
one printer sharer and 4 raw press plates at most. Basically, two or three
MFC2000-6 devices in one cabinet are recommended.

7.2 Input/Output Terminals

Figure 7.2 Backboard Terminal Diagram

Name Remarks Module

DC220V/110V Ground Power DC24V Output Motor bus line voltage



http://www.mianfeiwendang.com/
Work source voltage AC voltage Input Standby source voltage Reserved voltage
terminals Work branch current AC current Input Standby branch current Relay
initiate contact.

Connected with output

contacts of generator, transformer or generator-

transformer unit. Pickup

mode is closed short-pulse.

Relay blocking contact.

Connected with some

protection output contacts.

When these protections

work, the transfer system will

be blocked. Pickup mode is

closed short-pulse. Control/


Auxiliaryhttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dac make contact
of Status work circuit breaker Input Auxiliary make contact of standby circuit
breaker

Auxiliary make contact of bus PT isolating switch

Manual Initiate terminal.

Closed short pulse input. The signal is valid only when



http://www.mianfeiwendang.com/

Remote/local is remote.

Manual transfer mode

selection terminal.

Open- parallel transfer, auto

or semi-auto is decided by

the setting;

PWR Power Module AC AI Module DI DI Module

Name Remarks Module Signal

Output

Closed-sequential or simultaneous transfer, which is decided by setting. It is


valid only when the Control mode is remote. Enable/disable transfer function
manually. Open- enabledClosed-disabled. 509 RSV1 Reserved DI terminal Closed
short pulse input. After-transfer blocking/lockout, users should clear fault or
abnormity first and then reset the device and clear
signahttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacls. 511 RSV2
Reserved DI terminal 512 RSV3 Reserved DI terminal 513 RSV4 Reserved DI
terminal 514 RSV5 Reserved DI terminal. NULL Connected with external KM-
Closed-local; Open - Parallel transferPar/ Sim Closed-Simultaneous or 603/604
Par/Seq sequential transfer that is decided by control words 605/606 NULL2 Not
yet used SO 607/608 NULL3 Not yet used Signal Module Break contact, separated
connection is a must. 611/612 NULL4 Not yet used 613/614 RSV Signal 1 615/616
RSV Signal 2 Reserved signals 617/618 RSV Signal 3 619/620 RSV Signal 4
Successful transfer Failed transfer

http://www.mianfeiwendang.com/
A general single for all TrBlock 705/706 disabled transfers. Separate
connection is a must.

All transfer functions are TrExit 707/708 disabled manually.

709/710 Break contact, separated SO PWROff connection is a must. Signal Module


711/712 Breakers same status signal

BSS terminal.Included in TrBlock

singlehttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dac

Valid only when SSUVB is

enabled. Its included in

TrBlock single;

715/716 PT Fuse-loss signal terminal. PTFL Included in TrBlock single

Name Remarks Module

Device fault signal.Included

in TrBlock single.

Initiating after accelarated protection signal terminal.

Reserved outputs 1 Under-voltage load shedding

2 Under-voltage load Trip/Close shedding Output



http://www.mianfeiwendang.com/

807/808 NULL1 not yet used

Reserved outputs or signals

NET1A/NET1B Net 1 port Communic304/305/306

ation ports 307/308/309 NET2A/NET2B Net 2 port

GPS 310/311/312 GPS /GPS- GPS pulse signal

Table 9.1 Input and Output Terminal Instructions DO Output ModuleDO Output
ModuleCPU CPU Module

7.3 Design Referential Figures

Figure 7.1 Horizontal Mounting Dimension

Figure 7.2 Panel Mount


Cutouhttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dact Dimension

Figure 7.1 Horizontal Mounting Dimension


http://www.mianfeiwendang.com/
Figure 7.2 Panel Mount Cutout Dimension

8. Setting Report

All settings can be set manually through LCD screen. Before any modification,
users should input the correct password to ensure a valid operation.

8.1 Setpoints No.

10

11

12

http://www.mianfeiwendang.com/

13

14

15 Parameter name ParTran Delta Vol ParTran Delta Freq ParTran Delta Phase
ParTran Trip Delay SimTran Close Delay Standby Close Delay FastTran Delta Freq
FastTran Delta Phase DIP Tran Delta Freq Lead Phase of DIP Lead Time of DIP
ResVol Tran Vol Amp UV Init Vol Amp. UV Init Delay SSUV Vol Amp Unit Full
Name Parallel Transfer Delta 0 20 Voltage Limit Hz Parallel Transfer
Delthttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9daca 0.02 0.50
Frequency Limit Parallel Transfer Delta 0.5 20.0 Phase Limit s Parallel
Transfer Trip 0.015.00 Delay Ms Simultaneous Transfer 1500 Close Delay Ms 0
120 Hz Fast Transfer Delta 0.12.0 Frequency Fast Transfer Delta Phase 0.5
60.0 Hz Delayed In-phase Transfer 0.1 5.0 Delta Frequency Lead Phase of
Delayed In- 30 120 Phase Transfer Ms Lead Time of Delayed In-1 150 Phase
Transfer Residual Voltage Transfer 20 60 Voltage Amplitude Under-voltage
Initiating 20 90 Voltage Amplitude s Under-voltage Initiating 0.10 5.00
Delay Standby-Source-Under- 5090 voltage Voltage Amplitude

ms Standby Source Under-200-500 voltage Delay

1 Loadshedding 2080 Voltage

2 Loadshedding 2080 Voltage

s 1 loadshedding Delay 0.020.0

s 2 loadshedding Delay 0.020.0

Compensation Delta Phase Angle1

Compensation Delta Phase Angle2



http://www.mianfeiwendang.com/
A

Ranges Delhttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacay st
Loadshed Vol nd Loadshed Vol st Loadshed Delay nd Loadshed Delay 21 22 Comp
Delta Phase 1 Comp Delta Phase 2 Value 24 Fixed Time Delay 0.5-10.0 Fixed Time
Transfer DelayNote:

Lead Time of DIPUsually adopt Total Close time.

Comp Delta Phase 1, Comp Delta Phase 2Depend on practical connections.

8.2 Controls No. Parameter name 1 Remote Control Mode

6 Relay Init Sequen Mode UV Init Sequen Mode Local ManTran Auto Mode Local
ParTran Mode value 10 10 10 10 10 10

10

1,0

1, 0

1, 0

http://www.mianfeiwendang.com/
1, 0

1, 0

1, 0

1, 0

1, 0

1, 0

1, 0

1, 0

1, 0

1, 0 Full name Remote Control Mode Relay Initiated Seqential Transfer ModeUnder-
voltage Initiated Seqential Transfer ModeLocal Manual Transfer Auto ModeLocal
Parallel TransferMode Remote Parallel
Thttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacransferAuto
ModeRemote Parallel Seqential Transfer GroupUnder-voltage InitiatingFast
TransferLead Phase Transfer (Delayed In-Phase)Lead Time Transfer (Delayed In-
Phase)Residual-voltage Transfer1 load shedding2 load sheddingStandby Source
Under-voltage BlockingTransfer DevotedUnder-current Criteria Remote ParTran Auto
Mode Remote ParSequenTran 7 Group 9 Fast Tran 10 11 12 DIP Lead Phase Tran DIP
Lead Time Tran ResVol Tran st Loadshed nd Loadshed 15 StbLoss Block
AutoTripUnder-current 17 CRTA 18 Fixed Time Tran 19 20 UV Init Check Work Line
Vol ManTran Enable

Decoupling Fixed Time TransferLine Voltage Manual Transfer Enable Decoupling


Function 8.3 Description

http://www.mianfeiwendang.com/
ParTran Delta Vol, ParTran Delta Freq, ParTran Delta Phase and ParTran Trip
Delay

ParTran means Manual Parallel Transfer, the transfer method of which must be
Fast Transfer.

When the voltage difference, frequency difference and phase


diffhttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacerence between
work power

and standby power are lower than their separate setpoints, the device will issue
command to

close the standby(work) breaker, and after the ParTran Trip Delay time, it
will trip the

work(standby) breaker.

SimTran Close DelayUnder simultaneous transfer mode, after the Trip command is
issued,

the close command will be sent after this time delay.

Standby Close Delay After the command to close the standby high-voltage side
breaker is issued, the command to close the standby Low-voltage side breaker
will be issued after this

delayed time.

FastTran Delta Freq and Delta Phase Under fast transfer, if the frequency
difference and

phase difference between work power and standby power are lower than the two
setpoints,

http://www.mianfeiwendang.com/

the device will issue Close command. These setpoints are decided by the residual
voltage

characterhttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacistic and
standby breaker closing performance. If users want a high transfer success rate,
the setpoints could be set larger. If users need a high motor security, then the
setpoint

should be smaller.

DIP Tran Delta Freq: This is the prerequisite of Lead Phase Transfer. Default is
5HZ.

Lead Phase of DIPIf the frequency difference is lower than the setting DIP
Tran Delta

Freq, and the phase angle difference is within this range, the device will
issue closing

command. This setting is decided by the residual voltage characteristic and


standby breaker closing performance.

Lead Time of DIPIt depends on the total closing delay of standby breaker.

ResVol Tran Vol Amp Under residual voltage transfer, if the bus voltage is
lower than this

setpoint, the device will issue Close command. Default value is 25.

UV Init Vol Amp and UV Init Delay When the bus


vhttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacoltage is lower than
the setpoint and

http://www.mianfeiwendang.com/
the duration exceeds the time delay, Under-voltage Initiated Transfer could be
implemented.

Default values are 40 and 1s respectively.

SSUV Vol Amp and Delay When the standby source voltage is lower than the set

amplitude and duration exceeds the delayed time, at the same time, the setting
SSUVB is

enabled, the device will block the transfer function. The default value is
80and 200ms separately.

1st Loadshed Vol and Delay, 2nd Loadshed Vol and Delay: Whether motors can be
started up

successfully after the transfer, is mainly decided by standby transformer


capacity, bus voltage

and the amount and capacity of all motors that will self-start. It is helpful to
cut off some

insignificant motors in order to maintain the continuity of important load.


Default values are

60%0.5s609.0s respectively
://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacarComp Delta Phase 1 To
compensate the phase difference between standby voltage and bus

voltage. Default value is 0. For example, supposed bus voltage and standby
voltage are in

phase, if UAN is adopted as standby voltage and bus voltage, then the initial
phase angle is

http://www.mianfeiwendang.com/

0if UAN and UAB are adopted, the phase angle is 330; while if they are UAC
and UAB,

then the phase angle is 300.

Comp Delta Phase 2To compensate the phase difference between work voltage and
bus

voltage. Default value is 0.

Under-current Value In Auto-trip Initiate logic, if setting AutoTripUnder-


current CRTA

is set as Enable, the work breaker is tripped as well as the work branch
current is smaller

than this setpoint, the device enters Auto-trip logic. Default value is 0.5A

Fixed Time DelayWhen Fixed Time Transfer is initiated, after this delay time,
the device://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacpar
will issue a Close command without voltage difference, current difference and
phase difference analysis. The default value is 9s.

Remote Control ModeWhen it is set as 1, users can implement operations in


console or

DCS system, and the local operations are prohibited. Vice versa. The default
value is 1.

Relay Init Sequen ModeThis control word decides the transfer method initiated
by external

protection. Default value is 1 Seq. 0: Sim



http://www.mianfeiwendang.com/

UV Init Tran Sequen ModeThis control word decides the transfer mode initiated
by

Under-voltage. Default value is 1 Seq. 0: Sim

Local ManTran Auto ModeThis control word decides the local manual Par transfer
mode

Auto or Semi-auto. Default value is 1 Auto.

Local ParTran Mode This control word decides the local manual transfer mode.
The default

value is 1 parallel transfer


mode.http://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dac 0:
sequential transfer mode

Remote ParTran Auto Mode This control word decides the remote manual parallel
transfer

mode Auto or Semi-auto. Default value is 1 Auto.

Remote ParSequenTran Group When the control word is 1, the remote manual
transfer can only be parallel or sequential transfer. When the control word is
0, the remote manual transfer

can only be parallel or simultaneous transfer. Default value is 1.

UV Init This word will decide whether the under-voltage initiated transfer is
enabled.

Default value is 1. 0:Disable,1: Enable



http://www.mianfeiwendang.com/
Fast TranThis word will decide whether Fast Transfer is enabled. Default value
is 1.

0:Disable,1: Enable

DIP Lead Phase Tran It will decide whether this kind of transfer is enabled,
and the default

value is 0. 0:Disable,1: Enable

DIP Lead Time Tran It will decide whether this kind


ohttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacf transfer is
enabled, and the default value is 1. 0:Disable,1: Enable

ResVol Tran It will decide whether this kind of transfer is enabled, and the
default value is 1. 0:Disable,1: Enable

1st Loadshed, 2nd LoadshedIt will decide whether this function is enabled, the
default value

is 0. 0:Disable,1: Enable

SSUVB: when this word is adopted, if the Standby-Source-Under-Votage blocking


conditions

are met, the device will block the transfer function. On the occasion that
standby PT is out of

service for maintenance, the word should be disabled temporarily. In this case,
even the

blocking conditions are met, the device can still implement transfer operation.
When the standby source is under-voltage without blocking, only Residual Voltage
transfer and Fixed

http://www.mianfeiwendang.com/

Time transfer can be adopted. The default value is 1. 0:Disable,1: Enable

Transfer When it http://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacis


set as 0, the transfer function is blocked. The default value is 1.

AutoTripUnder-current CRTAUnder-current Criteria is used to decide whether the

judgement of work branch current is needed in Auto-trip Initiated logic. If it


is set as 0,

when work breaker trips, Auto-trip Initiated transfer will be implemented. If it


is set as 1,

work breaker trips as well as the work branch current is smaller than the
setting Under-

current Value, then transfer initiated. Otherwise, transfer can not be


initiated even the work

breaker is tripped and the device enters into the status of work fake open.

Fixed Time Tran It will decide whether this kind of transfer is enabled, the
default value is

0. 0:Disable,1: Enable

Note: Seq=Seqential Sim=Simultaneous Par=Parallel SAuto=Semi-auto

UV Init Check Work Line Vol It will decide whether


http://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacthe work source under
votage criteria

is enabled when a sudden loss of motor bus voltage. 0:Disable,1: Enable. If it



http://www.mianfeiwendang.com/
is set as 0,

when the motor bus loss voltage, Under-current Criteria is used. If it is set as
1, when the

motor bus loss voltage, Under-Votage Criteria is used.

ManTran Enable DecouplingIt will decide whether decoupling function is enabled


in

manual transfer, 0:Disable,1: Enable, the default value is 1.

Note: Seq=Seqential Sim=Simultaneous Par=Parallel SAuto=Semi-auto

9 User Manual Introduction

9.1 Front-panel Plan

Figure 9.2 Front-panel Plan

RUNThe LED illuminates when the device runs normally, the LED will be blacked
out

when the device is wrong or CPU doesnt work.

BLOCKTransfer Blocking Indicator. The LED illuminates when the device is in

lockout/blocking status, no
trahttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacnsfer is permitted.

ACT The LED illuminates when the device has finished the transfer operation
just now and

http://www.mianfeiwendang.com/

it extinguish after resetting.

WORKThe status indicator illuminates when the work power source works.

STANDBYThe status indicator illuminates when the standby power source works.

REMOTE The LED illuminates when the device is in remote operation mode,
otherwise, in

local mode.

TESTThe LED illuminates when the device is in test status.

RESERVEReserve for future use.

9.2 LCD Display

MFC2000-6 device displays system diagram in graphics stamped with related


measured parameters. In the following diagram, except some real-time measured
quantities, the position status of work breaker, standby breaker and PT
isolating switch also are displayed practically.

Figure 9.2 Wring Display Interface (Default)

MFC2000-http://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dac6 menu
structure is as follows

Following parameters and states are displayed on LCD of HMI.

MeasureDisp(AC Input Values)



http://www.mianfeiwendang.com/
Motor bus voltage: Uab, Ubc, Uca;

Work source voltage: Ugz;

Standby source voltage: Uby;

Frequency of Uab Ubc Uca and Ugz Uby: fab fbc fca fgz fby;

Delta frequency between Uab and Ugz (or Uby):df;

Delta phase angle between Uab and Ugz (or Uby):dq;

Work source current Igz;

Standby source current: Ira, Irb, Irc;

Motor bus positive sequence voltage:U1m; negative sequence voltage:U2m.

DIDisp(Control/Status Inputs)

All control/status inputs states are displayed (including status of two circuit
breakers, PT isolating switch etc).

ActRPT

Action report covers the following information

InitTime: Initiating time.

InitMeth Initiating method. Relay,


Mahttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacnual, Under-voltage
and Auto-trip etc,.

TranDir:Transfer direction(Work-to-Bak,Bak-to-Work)

http://www.mianfeiwendang.com/

TranMeth: Transfer method Sequential, Auto parallel, Semi-auto parallel and


Simultaneous RealMeth:Realize method(Fast, Lead angle, Lead time, ResVol
(Residual voltage), Fixed-Time Transfer and so on

TranResu:Transfer result (TranSuccess ConditionFail BK-NOT-CLOSE BK-NOT-


OPENBAK-OPENOverTime)

Phase: Health phase.

Close/trip command records.

Time, frequency difference, phase difference, bus 3-phase voltage and branch
current when the device is initiated.

Time, frequency difference, phase difference, bus 3-phase voltage and branch
current when tripping command is issued.

Time, frequency difference, phase difference, bus 3-phase voltage and branch
current when breaker is tripped.

Time, frequency difference, phase difference, bus 3-phase voltage and branch
chttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacurrent when closing
command is issued.

Time, frequency difference, phase difference, bus 3-phase voltage and branch
current when breaker is closed.

WarnRPT

Abnormal events include following types :

Type(shown on device)

http://www.mianfeiwendang.com/
StbLoss Block

BKS Open.E

BKS Closed.E

BKS Closed.CW

BKS Closed.CS

BKS Open.TS PTIS Open

PT Fuse-Loss

Work Fake Open

TranExit Corresponding Full Name Standby-Source Under-Voltage Breakers All Open


when Electrified Breakers All Closed when Electirfied Breakers All Closed when
Close Work Breakers All Closed when Close Standby Breakers All Open when Trip
Standby PT Isolating Switch Open PT Fuse-Loss Work Fake Open if digital input
contact TranExit is closed,or the setting

blocked.

Fre Abnormal

TranMethodExit

DIAbnormal Frequency Abnormal All transfer methods are


http://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacdisabled if digital
input contact RelayInitor ManInit is closed

when Electrified.

http://www.mianfeiwendang.com/
Note Work Fake Open means the device detects the work switch auxiliary
contact is open, but the work branch current is higher than the setting Under-
current Value.

CMDRecord

Command Record events include following types :

Corresponding Full Name

events

SysSetting

TranSetting

ComSetting

SetSlop

Print

Print submenu has 5 options: Setting, ActReport, WarnRPT,


DIRecord VerInfo.

Press , , keys to choose the wanted option, and then press


Confirm key to print the content. If want to print the waveform of action
report, users are suggested to download the curves to PC through MFC2000-6
management software and then print it.

Setting

SysSetting: OutKeepTime is Trip/Close Output hold time.


Resehttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacrveOut is a 8-

http://www.mianfeiwendang.com/
bit binary

The set point over range when modifying

control number, bit 0 means associating CloseWork output to RSV1 output ;


bit 1 means

associating TripWork output to RSV2 output ; bit 2 means associating


CloseStb-L output to RSVOUT1 output ; bit 3 means associating TripStb
output to RSVOUT2 output ; bit 4 means associating APP signal to RSV
Signal 1 ; bit 5 means associating APP signal to RSV Signal 2 ;. bit 6
means associating Success signal to RSV Signal 3 ;. bit 7 means
associating Fail signal to RSV Signal 4 ;.DITimeis digital inputs
confirm time.WorkIndex is the index of work circuit breaker. BakIndex is
the index of standby circuit breaker.PT-Line means PT

connected in line connector.DebugOn is the TEST module in use.

ComSetting.(Communication Parameters): PrintBaudRate 0 4800 bps 1 9600 bps


219200

bps 3 38400bps
485http://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacNet1BaudRate 0
9600 bps 119200 bps 238400 bps 3: 115200bps485Net2BaudRate 09600
bps 119200 bps 238400 bps 3: 115200bps

Debug

Add 57.74V to 3-phase voltages and 5A to currents, Choose PrecisionAuto to


adjust.

PrecisionManual (Manual Adjust Presicion Coefficient): the method is the same as


above.

http://www.mianfeiwendang.com/
ManTran

Manual transfer, which is bidirectional, can be classified as local and remote


manual transfer. Local manual transfer means to implement transfer operation in
the device itself(through ManTran interface to operate);remote transfer
means the operation is implemented in console or DCS system. Local manual
transfer mode includes: Auto parallel transfer, Semi-auto parallel transfer,
Sequential transfer.

Take the Local semi-auto parallel transfer from work to standby as an example.

Preparation

Set RemoteControlmode in TranSetting submenu


ahttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dacs 0

Set LocalManTranAutoMode in TranSetting submenu as 0

Set LocalParTranMode in TranSetting submenu as 1

Ensure the device is in normal running status. (no blocking situations)

Operation

Enter ManTran submenu.

Input the correct passport and press Confirm key

Press Confirm key to close standby breaker, After the implementation, a


successful closing operation message is displayed, if it failed, the transfer is
disabled.

Press Confirm key to trip work breaker.



http://www.mianfeiwendang.com/
10 Appendix

For the reason of screen size, we adopt abbreviation in some interface. The
contrast table is as flowing: Name

Transfer

Information

Time

Method

Direction

BSS Breakers Same Status

ResVShedding

Accelerated Protection

DIDisp

BAK or BK DI Status Display Standby-


Sourcehttp://www.mianfeiwendang.com/doc/ad728c1408dd2282601e9dac Setting

Setting

ComSetting Communication Setting



http://www.mianfeiwendang.com/

word

http://www.mianfeiwendang.com/