1)
1 ()
1. a
2. a Loading Transformer 12.5 MVA 87K1&2,
86K1&2 overall relay KT1A KT2A
3. ab Feeder Overcurrent Relay feeder a
b feeder 1, 2, 3, ...
4. protective device number Loading Transformer 1
4(Rev.1)
1. a
2. P 1 (Primary Protection) - 500 kV
3. S 2 (Secondary Protection) - 500 kV
4. Tie Transformer 230/115 kV P, S
5(Rev.1)
() CT QY1A 3 core
1 Protective Device Number Loading Transformer
6(Rev.1)
() CT QY1A 2 core
1 ()
7(Rev.1)
1. a
2. P 1 (Primary Protection) 500 kV 230 kV
230 kV line
3. S 2 (Secondary Protection) - 500 kV 230 kV
230 kV line
4. 87BP 87BS 87BP low impedance type
87BS high impedance type switching CT low impedance
type 2
5. 115 kV (Breaker and a Half) P, S
6. 115 kV (Main and Transfer Bus) P, S a
7. 86B suffix(b) contact 86B
86B-1
8(Rev.1)
1. BKR Breaker 3
(6 = 69 kV, 7 = 115 kV, 8 = 230 kV 9 = 500 kV) 2 3
Breaker breaker failure protection relay bus arrangement
Main and Transfer Bus, Ring Bus, Double Bus Single Breaker: BKR. 6922, 70082, 80012,
90082 breaker failure protection relay 50BF-602, 50BF-708, 50BF-801, 50BF-
908
Breaker and a Half, Double Bus Double Breaker, Double Bus Double Breaker with Transfer
Bus: BKR. 70112, 80122, 90132 breaker failure protection relay 50BF-711,
50BF-812, 50BF-913
. 10 bay breaker Failure protection relay BKR. bay
10 4 BKR. 701112 breaker failure protection relay
50BF-7111
9(Rev.1)
5 ()
5 ()
1. a 500 kV
a = 1 1 (Primary 1)
a = 2 2 (Primary 2)
2. 115 kV 230 kV a
3. 51L/51LG Backup protection 115 kV Line to PEA
4. Overload Relay Overload single phase
B
5. 51BU de-energize main bus remote substation ()
6. 230 kV Tie Line Line ( single
pole tripping and reclosing)
12(Rev.1)
1. a C-bank 22 kV 33 kV a
2. 60CH 60CL 22 kV 33 kV 2
3. 60CL Fuse Link 1 PT ratio range
14(Rev.1)
3 Drawing List
16(Rev.1)
69 kV 115 kV
69 kV 115 kV bus bus
Main and Transfer Bus, Breaker and a Half, Double Bus Double Breaker Ring Bus
Metering and Relaying Diagram (E-1) 115 kV
bus E-1
1. Main and Transfer Bus Line Bay Tie Bay 4 4 ()
(.) . 4 () . Line to PEA
Loading Transformer 115/22 kV ( 33 kV) 7 Loading Transformer
12.5 MVA BRK. high side low side
8
2. Breaker and a Half 5 2 Line Bay
2.1. EGAT Line PEA Line primary protection Line to PEA
21P Line to PEA core CT 21P EGAT
Line core CT W&VAR TDR FRS ( CT 3 core)
2.2. EGAT Line primary Protection line Bus no.1 line
core CT
3. Ring Bus 6
4. Double Bus Double Breaker E-1 Breaker and a Half
() .
4 Metering and Relaying Diagram 115 kV Line Bay
18(Rev.1)
() .
4 ()
19(Rev.1)
7 Metering and Relaying Diagram Line Loading Transformer 115/22 kV and Line to PEA
22(Rev.1)
() CT QY2A 3 core
8 Metering and Relaying Diagram
Loading Transformer 12.5 MVA
23(Rev.1)
() CT QY2A 2 core
8 ()
24(Rev.1)
() C-bank 69 kV 115 kV
() C-bank 22 kV 33 kV
9 Metering and Relaying Diagram C-Bank 69 kV 115 kV () 22 kV 33 kV ()
25(Rev.1)
230 kV
E-1 230 kV Breaker and a Half 11 11 ()
E-1 . . Tie Line . 11 () .
( Auto Reclosing Relay reclose BKR. . 2 line
reclose BKR. )
E-1 . GIS 12
E-1 C-bank 230 kV 13
500 kV
E-1 500 kV Breaker and a Half 14 GIS Double Bus Single
Breaker 15
26(Rev.1)
()
11 Metering and Relaying Diagram 230 kV Breaker and a Half
27(Rev.1)
()
11 () Metering and Relaying Diagram 230 kV Breaker and a Half
28(Rev.1)
15 () Metering and Relaying Diagram 500 kV GIS Double Bus Single Breaker
33(Rev.1)
15 () Metering and Relaying Diagram 500 kV GIS Double Bus Single Breaker
34(Rev.1)
CT Ratio
1. Distance Relay, Current Differential Relay, Line Overcurrent Relay (PEA) CT ratio
thermal limit fault level Bus
2. Bus Differential Relay CT ratio (full tap)
3. Transformer Differential Relay, Transformer Overcurrent Relay, Loading Overcurrent Relay
C-bank Overcurrent Relay CT ratio Bus fault level (20 IN CT 600
A 20.IN = 12000 A bus fault level )
4. Breaker Failure Relay ratio Main Protection
Core CT Winding PT
1. core CT Primary Protection core zone
Backup Protection core
2. core CT Breaker Failure Relay core
Backup Protection (230 kV 500 kV) High-side Overcurrent Relay (51T/51TG)
3. Breaker Failure Relay CT core Star Point CT core Breaker
4. winding PT Primary Protection winding X Back up Protection
winding Y
5. winding PT Synchronism Check Relay (25) Auto Reclosing Relay (79)
winding X manual control, FRS CCS winding Y
1.
25 79 21BU
16
2. Tie Transformer Station Service ( tertiary winding)
CT tertiary winding 87K restraint winding 87K
3. Tie Transformer Station Service tertiary winding
a. 1 feeder 11 12 ()
b. feeder 16.1 1 source 2 source
35(Rev.1)
115 kV Substation
Main and Transfer Control Panel Relay Panel Panel Duplex
( Front) ( Rear) 17
2 10F/10R 11F/11R 115 kV Line 115 kV Tie Bay
R E-1 bay
auxiliary relay 86B, 94P
Duplex Panel End Trim
-
Line to PEA . bus Main and Transfer Bus, Control and Relay
Panel Duplex 18 Metering Panel
Swingrack