D925FireresistanceRatingsANSI/UL263

DesignNo.D925
BXUV.D925
FireresistanceRatingsANSI/UL263

PageBottom

Design/System/Construction/AssemblyUsageDisclaimer
AuthoritiesHavingJurisdictionshouldbeconsultedinallcasesastotheparticularrequirementscoveringtheinstallationanduseofUL
Certifiedproducts,equipment,system,devices,andmaterials.
AuthoritiesHavingJurisdictionshouldbeconsultedbeforeconstruction.
FireresistanceassembliesandproductsaredevelopedbythedesignsubmitterandhavebeeninvestigatedbyULforcompliancewith
applicablerequirements.Thepublishedinformationcannotalwaysaddresseveryconstructionnuanceencounteredinthefield.
Whenfieldissuesarise,itisrecommendedthefirstcontactforassistancebethetechnicalservicestaffprovidedbytheproduct
manufacturernotedforthedesign.UsersoffireresistanceassembliesareadvisedtoconsultthegeneralGuideInformationforeach
productcategoryandeachgroupofassemblies.TheGuideInformationincludesspecificsconcerningalternatematerialsandalternate
methodsofconstruction.
OnlyproductswhichbearUL'sMarkareconsideredCertified.

BXUVFireResistanceRatingsANSI/UL263

BXUV7FireResistanceRatingsCAN/ULCS101CertifiedforCanada
SeeGeneralInformationforFireresistanceRatingsANSI/UL263

SeeGeneralInformationforFireResistanceRatingsCAN/ULCS101CertifiedforCanada

DesignNo.D925
May10,2017

RestrainedAssemblyRatings3/4,1,11/2,2or3Hr(SeeItems1,3A,6and10)

UnrestrainedAssemblyRating0Hr(SeeItems3,3A,4,4Aand10)

UnrestrainedBeamRatings1,11/2,2,3and4Hr(SeeItems4,4Aand10)

RestrictedLoadConditionSeeSupportsandItem4C

ThisdesignwasevaluatedusingaloaddesignmethodotherthantheLimitStatesDesignMethod(e.g.,WorkingStressDesign
Method).ForjurisdictionsemployingtheLimitStatesDesignMethod,suchasCanada,aloadrestrictionfactorshallbeused
SeeGuideBXUVorBXUV7

*IndicatessuchproductsshallbeartheULorcULCertificationMarkforjurisdictionsemployingtheULorcULCertification(such
asCanada),respectively.

http://database.ul.com/cgibin/XYV/template/LISEXT/1FRAME/showpage.html?name=BXUV.D925&ccnshorttitle=Fireresistance+Ratings++ANSI/UL+263&ob 1/9
6/12/2017 BXUV.D925FireresistanceRatingsANSI/UL263

SupportsW8x28,W12x16oralternate(perSectionIV.6inthefrontoftheFireResistanceDirectory)steelbeamor
min8K1steeljoistswhenjoistsubstitutionapplied.

1.NormalWeightorLightweightConcreteNormalweightconcretecarbonateorsiliceousaggregate,3500psi
compressivestrength,vibrated.Lightweightconcrete,expandedshale,orslateaggregatebyrotarykilnmethod,or
expandedclayaggregatebyrotarykilnorsinteredgratemethod,3000psicompressivestrength,vibrated,4to7
percententrainedair.
Restrained Concrete ConcreteUnit Concrete
AssemblyRatingHr (Type) Weightpcf ThknsIn.

1 NormalWeight 147153 31/2

11/2 NormalWeight 147153 4

2 NormalWeight 147153 41/2

3 NormalWeight 147153 51/4

3/4or1 Lightweight 107113 21/2

1 Lightweight 107120 25/8

11/2 Lightweight 107113 3

2 Lightweight 107113 31/4

2 Lightweight 107116 31/4*

2 Lightweight 114120 31/2

3 Lightweight 107113 43/16

3 Lightweight 114120 47/16

*Forusewith2or3in.steelfloorandformunitsonly.

2.WeldedWireFabric6x6,10x10SWG.

2A.NegativeReinforcement(NotShown)OptionalFor3/4,1,11/2and2HrRestrainedAssemblyRating
Only.UsedinlieuofItem2andwithItem2B.Forfloorspanswithconcretecastcontinuousoverthesupportingbeams.
DeformedbarsdesignedtoresistthesupportmomentsoftheconcreteslabinaccordancewiththelatestACIBuilding
CodeSpecifications.

2B.FiberReinforcement*(NotShown)For3/4,1,11/2and2HrRestrainedAssemblyRatingOnly.Required
withItem2A.Engineeredsyntheticfibersaddedtoconcretemixtocontrolshrinkagecracksinconcrete.Fibersaddedto
concretemixatrateof5lbsoffiberforeachcubicyardofconcrete.

GCPAPPLIEDTECHNOLOGIESINCTypeStrux90/40.

http://database.ul.com/cgibin/XYV/template/LISEXT/1FRAME/showpage.html?name=BXUV.D925&ccnshorttitle=Fireresistance+Ratings++ANSI/UL+263&ob 2/9
6/12/2017 BXUV.D925FireresistanceRatingsANSI/UL263
3.SteelFloorandFormUnits*CompositeorNonComposite,11/2,15/8,2or3in.deepgalvunitsor41/2in.
deepnoncompositegalvunits.Flutedunitsmaybeuncoatedorphosphatized/painted.Mingaugesare22MSGfor
flutedand20/20MSGforcellularunits.Thefollowingcombinationsofunitsmaybeused:

(1)All18,24,2628or36in.widecellular.

(2)Allfluted.

(3)Oneortwo3in.deep,12in.wide,18/18MSGmincellularunits,alternatingwith3in.deep
flutedorothercellular.

(4)Anyblendofflutedand18,24,26,28,or36in.widecellular.

(5)3in.deep,30in.widecellularwith81/8in.widevalleyalongsidejointsmaybeusedwhen
3/8in.diamreinforcingbarsareplaced11/2in.toeachsideofsidejointsand1in.above
bottomofunits.

(6)Corrugated,15/16in.deep,30in.wide,24MSGmingalvunitswithshearwiresfactory
weldedtodeckcorrugations.Weldedtosupports12in.OC.throughweldingwashers.Forshear
wirespacingof8in.orlessthesteeldeckstressshallnotexceed20KSI.Forshearwire
spacinggreaterthan8in.OC.butlessthanorequalto12in.OC.steeldeckstressshallnot
exceed12KSI.

ASCSTEELDECK,DIVOFASCPROFILESLLC32in.wideTypesNH32,NHN32,NHF32
36in.wideTypesBH36,BHN36,BHN351/4,BHF36,BHF36A,2WH36,2WHS36,2WHF
36,2WHF36A,3WxH36,3WxHF36,3WxHF36A,3WH36,3WHF36,3W36,3WF36,
DG3W36,DG3WF36.AllunitsmaybegalvanizedorPrimeShield.Noncellulardecksmaybe
venteddesignatedwitha"V"suffixtotheproductname.Cellulardecktopandbottomsections
mayberivetedtogether(designatedwith"Fr")vs.arcspotwelded,"F".

CANAMSTEELCORP36in.wideTypeP3623,P3606,P3615and24inwideTypeP2432
composite.

CANAMSTEELCORP24in.wide,Types11/2,2or3in.LOKFloorandLOKFloorCell36
in.wide,Types2or3in.LOKFloorandLOKFloorCells24in.wide,TypesNLOKandNLOK
Cell24,30or36in.wide,Type11/2in.BLOKandBLOKCell.

NEWMILLENNIUMBUILDINGSYSTEMSLLC24in.wideTypesCFD2,CFD324,30or
36in.wideTypeCFD1.524or36in.wideTypesMacLok2,MacLok324in.wide,Types
B2C,B2FC,NC,NFC30in.wideTypeB3C12in.wideMacWaycellular45MOW,2633
MTWA,3633MTWA,3633MTWV,3633MTWV+,24in.wideTypeVersaDek.

DECKWESTINC36in.wideTypeBDW,2DWor3DW.Sidejointsof2DWand3DW
maybefastenedtogetherwithmin1in.longNo.12x14selfdrilling,selftappingsteelscrew
36in.OC.

DESIGNASSISTANCECONSTRUCTIONSYSTEMSINC36in.wideTypeDACS1.5CD,or24
in.wideTypeDACS2.0CD,orDACS3.0CD.

EPICMETALSCORP24in.wideTypesEC150,ECP150,EC300,ECP300,EC366,ECP366,
EC150,EC300inverted,EpicoreA30in.wideTypesECB150,ECBR15036in.wideTypes
EC266.

HHROBERTSONQLTypes,24in.wide3or3inverted,UKX,UKX3,2in.99,AKX,21or
21inverted,121,NKX,TKX24or30in.wideGKX,GKXA36in.wide99,AKX,WKX2426,
94,36in.wideNKX1.5NKC,NKC,AKX,2or3in.TKC12in.widenoncompositeSec.1217
in.wide2126or28in.wideUKX,87.5cmwide.SidejointsofQL,99,121,WKX,TKX,TKC,
andMetricunitsQL77900QLC78900maybeweldedtogether60in.OC.Sidejointsof
99,AKX,WKX,GKX,GKXA,TKXandMetricunitsQL77900andQLC78900maybe
fastenedtogetherwithmin1in.longNo.12x14selfdrilling,selftappingsteelscrews36in.
OC.

HAMBROSTRUCTURALSYSTEMS,DIVOFCANAMSTEELCORP36in.wide,11/2in.
TypeP3615HB.ThemaxsuperimposedloadingsforTypeP3615HBunitsshallnotexceed250
PSF.Forsinglespans,theuseoftheunitsshallbelimitedto5ft.6in.,6ft0in.and6ft6in.
maxspansforthe22,20and18gaugeunits,respectively.Formultiplespans,18gaugeunits
maybeusedonamax7ft6in.spanwithamaxtotalsuperimposedloadingof240PSF.

http://database.ul.com/cgibin/XYV/template/LISEXT/1FRAME/showpage.html?name=BXUV.D925&ccnshorttitle=Fireresistance+Ratings++ANSI/UL+263&ob 3/9
6/12/2017 BXUV.D925FireresistanceRatingsANSI/UL263
KAMINDUSTRIESLTD,DBACORDECK24in.wideTypes2or3in.WDR.

MARLYNSTEELDECKSINCType1.5CF,2.0CFor3.0CF.

NEWMILLENNIUMBUILDINGSYSTEMSLLCType1.5CD,1.5CDI,1.5CDR,2.0CDor
3.0CD.Unitsmaybephos/paintedorgalvanized.

VALLEYJOIST24or36in.wideTypesWVC11/2orWVC2.

VERCODECKINGINCANUCORCOFORMLOKdecktypesPLB,B,BR,PLN3,N3,PLN,
N,PLW2,W2,PLW3,W3.Unitsmaybegalvanized,phos./ptd,ormillfinish.Unitsmaybe
cellularoracousticalcellular,withthesuffix"CD"or"CDAC"addedtotheproductname,
respectively.Allnoncellulardeckmaybeventedornonvented.12in.widePLW2,W2,PLW3or
W3unitsmaybeblendedwith24or36in.widePLW2,W2,PLW3orW3units,respectivelyor
TypesN3,PLN3,N3CD,PLN3CD.

VULCRAFT,DIVOFNUCORCORP24,30or36in.wide,Type1.5VL,1.5VLI,1.5PLVLI,
1.5VLP,1.5PLVLP24or36in.wide.Types2VLI,2.0PLVLI,2VLP,2.0PLVLP,3VLI,3.0PLVLI,3
VLP,3.0PLVLP.36in.wideTypes1.5SB,1.5SBR24or36inwideTypes2.0SB,3.0SB,36
in.wideTypeHighStrength1.5SBI,36in.wideTypeHighStrength1.5SBN.

Componentsforfieldassembledcellularmetalracewayunits:

RacewayBottom24or36in.wideTypes212VS,312VS.

RacewayCoverPlateTypesCP12,CP16.

RacewayDividerTypeDC20,DC25.

RacwayIsolationTroughTypesT20,T25,T30.

Spacingofweldsattachingunitstosupportsshallbe12in.OCfor12,24and36in.wideunits,
fourweldspersheetfor30in.wideunits,6in.OCfor18in.wideandSec.12units.Unless
notedotherwise,adjacentunitsbuttonpunchedorweldedtogether36in.OCalongsidejoints.
Adjacent18in.wideunitsweldedtogether30in.OCalongsidejoints.For3HrRating,units
withoverlappingtypesidejointsweldedtogether24in.OCmax.

TheUnrestrainedAssemblyRatingisequaltotheUnrestrainedBeamRatingforamax
of3Hrandislimitedtothefollowingfloorunitsandspans:

(a)11/2,2and3in.deep,24in.wide,22MSGorthickerflutedwithclearspansnotmore
than7ft,8in.

(b)11/2,2and3in.deep,24in.wide,20MSGorthickerflutedwithclearspansnotmore
than8ft,8in.

(c)11/2and2in.deep,24in.wide,16MSGorthickerflutedand18/18MSGorthicker
cellularwithclearspansnotmorethan9ft,11in.

(d)3in.deep,36in.wide,18MSGorthickerflutedand24in.wide,20/18MSGorthicker
cellularwithclearspansnotmorethan13ft,2in.

Forassembliesutilizing31/4in.lightweightconcretetoppingwithamaxRestrainedAssembly
Ratingof2Hr,theUnrestrainedAssemblyRatingisequaltotheUnrestrainedBeamRatingand
islimitedtothefollowingfloorunitsandspans:

(a)11/2,2,and3in.deep,24or36in.wide,22MSGflutedand20/20MSGcellularwithclear
spansnotmorethan9ft,6in.

(b)2and3in.deep,24or36in.wide20MSGflutedand20/20MSGcellularwithclearspans
notmorethan10ft,0in.

(c)3in.deep,24in.wide,20MSGflutedand20/20MSGcellularwithclearspansnotmore
than13ft,2in.

3A.SteelFloorandFormUnits*(notShown)For1Hr,11/2Hrand2HrratingsandasanalternatetoItem3.
ThetopflangeofthesteelbeamandorjoistshallbeprotectedwithSprayAppliedFireProtectionMaterialItem4,and
thethethicknessoftheprotectionshallbetothefinalthicknessrequiredfortheratingforthatmember.Composite,
galvsteelunits.Mingauge20MSG.Sidejointsofadjacentunitsfullyoverlapping,fastenedtogetherbyusing11/4in.
longselfdrilling,selftappingsteelscrewsdriventhroughShearBondClipsat133/4in.OC.Steelendclosures
flashingsmadeofmingauge16MSGgalvsteel,fixedtothesteelworkbeforedeckingisplaced.Lightweightconcrete
loadingshallbegovernedbynormalweightconcreteloadtables."Consultthebelowlisteddeckmanufacturerfor
comprehensiveloadtablesanddesignparametersassociatedwiththisassembly."
MinNormalor MinNormal MinNormal MinLightweight

http://database.ul.com/cgibin/XYV/template/LISEXT/1FRAME/showpage.html?name=BXUV.D925&ccnshorttitle=Fireresistance+Ratings++ANSI/UL+263&ob 4/9
6/12/2017 BXUV.D925FireresistanceRatingsANSI/UL263
Lightweight WeightConcrete WeightConcrete Concrete
ConcreteTopping Toppingoverthe Toppingoverthe Toppingover
overthetopof topofthesteel topofthesteel thetopofthe
thesteeldeck= deck=39/16 deck=41/2in. steeldeck=3
21/2in. in. 1/4in.

Restrained 1 11/2 2 2
Assembly
Rating,h

Unrestrained 1 11/2 2 2
Assembly
Rating,h
(SteelDeck
Span 32ft,
95/8in.)

Unrestrained 0 0 0 0
Assembly
Rating,h
(SteelDeck
Span>32ft,
95/8in.)

RibSteelReinforcementRefertoULDesignD930.Steelreinforcementdesignedin
accordancewithACI318latestspecifications.MinimumCoverbelowthesteelreinforcement
shallbe119/32in.for1and11/2Hr.Ratingand43/4in.for2Hr.rating.
WeldedWireFabric6X6MinwirethicknessW2.9XW2.9.placedintheconcrete
topping.

BAILEYMETALPRODUCTSLTDTypeCOMSLAB210andCOMSLAB225,SteelEndClosureFlashing

4.SprayAppliedFireResistiveMaterialsAppliedbymixingwithwaterandsprayinginoneormorecoatstoa
finalthicknessasshowninthetablesbelow,tosteelbeamsurfaceswhichmustbecleanandfreeofdirt,loosescale
andoil.Minavgandmininddensityof15/14pcf,respectivelyforTypesMK6/HY,MK6/HYExtendedSet,MK6/HB,
MK6s,MK6GF,MK6GFExtendedSet,MK10HB,MK10HBExtendedSet,MK1000/HB,MK1000/HBExtendedSet,
RG.Minavgandmininddensityof22/19,respectivelyforTypesZ106,Z106/G.Formethodofdensity
determination,refertoDesignInformationSection.
W8x28Beam
Supporting
(seeNote#1)
W12x16
All Fluted Beam
Restrained Unrestrained Unrestrained Fluted Floor Supporting
Assembly Assembly Beam W8x28 Floor Units W12x16 AllFluted
RatingHr RatingHr RatingHr Beam Units and Beam FloorUnit
(see w/Light Normal (see (seeNote
Note weight Weight Note #1)
#1) Concrete Concrete #1)
Only

1 1 1 1/2, 5/16, 5/16 11/16, 5/8,

11/16# 11/16# 11/8# 1#

11/2 1 1 1/2, 5/16, 5/16 11/16, 5/8,

11/16# 11/16# 11/8# 1#

11/2 11/2 11/2 13/16, 11/16, 5/8 11/8, 1,

1 1# 17/16# 13/8#
1/16#

2 1 1 1/2, 5/16, 5/16 11/16, 5/8,

11/16# 11/16# 11/8# 1#

2 2 2 11/16, 1, 7/8 17/16, 13/8,

1 13/16# 1 19/16#
5/16# 13/16#

3 11/2 11/2 13/16 11/16 5/8 11/8 1

3 3 3 19/16 15/16 17/16 21/8 13/4

3 3 4 2 15/8 2 211/16 23/16

http://database.ul.com/cgibin/XYV/template/LISEXT/1FRAME/showpage.html?name=BXUV.D925&ccnshorttitle=Fireresistance+Ratings++ANSI/UL+263&ob 5/9
6/12/2017 BXUV.D925FireresistanceRatingsANSI/UL263
Note#1:JoistsfromtheNseriesdesignsmaybesubstitutedforthelistedbeam.Whenjoistsare
substituted,therestrainedratingofthejoistmustbeequaltoorgreaterthattherestrainedratingofthe
assembly.AdditionaljoistsubstitutionrequirementsarecontainedinthefrontoftheFireResistance
Directory.

#ThisthicknessapplieswhenoptionalItem10isusedover31/4in.lightweightconcretetopping.

ThethicknessesofSprayAppliedFireResistiveMaterialsshowninthetablebelowareapplicablewhenthethickness
appliedtothebeams'lowerflangeedgesisreducedtoonehalfthatshowninthetable.

W8x28
Beam
Supporting
AllFluted
Restrained Unrestrained Unrestrained FloorUnits W12x16
Assembly Assembly Beam W8x28 w/Lightweight W12x16 Beam
RatingHr RatingHr RatingHr Beam Concrete Beam Supporting
AllFluted
FloorUnit

1 1 1 9/16 7/16+ 3/4 5/8

11/2 1 1 9/16 7/16+ 3/4 5/8

11/2 11/2 11/2 7/8 3/4 13/16 1

2 1 1 9/16 7/16+ 3/4 5/8

2 2 2 13/16 1 15/8 13/8

3 11/2 11/2 7/8 3/4 13/16 1

3 3 3 13/4 19/16 23/8 21/8

3 3 4 25/16 21/16 31/8 23/4

+Thicknessappliedtobeams'lowerflangeedgesshallbeaminimumof1/4in.

ARABIANVERMICULITEINDUSTRIESTypesMK6/HY,MK6/HYExtendedSet,MK6/HB,MK6s,MK6GF,MK6
GFExtendedSet,MK10HB,MK10HBExtendedSet,MK1000/HB,MK1000/HBExtendedSet,Z106,Z106/G.

GCPKOREAINCTypesMK6/HY,MK6/HYExtendedSet,MK6/HB,MK6s,MK6GF,MK6GFExtendedSet,MK10
HB,MK10HBExtendedSet,MK1000/HB,MK1000/HBExtendedSet,Z106/G,Z106.

GCPAPPLIEDTECHNOLOGIESINCTypesMK6/HY,MK6/HYExtendedSet,MK6/HB,MK6s,MK6GF,MK6GF
ExtendedSet,MK10HB,MK10HBExtendedSet,MK1000/HB,MK1000/HBExtendedSet,RG,Z106/G,Z106.

4A.AlternateSprayAppliedFireResistiveMaterialsAppliedbymixingwithwaterandsprayinginoneormore
coatstoafinalthicknessasshowninthetablesbelowtosteelbeamsurfaceswhichmustbecleanandfreeofdirt,
loosescaleandoil.Thethicknessesshowninthetablebelowareapplicabletobeamssupportingallflutedfloororform
units.Minavgandmininddensityof22/19pcfrespectivelyforZ106/HY.FordensitydeterminationrefertoDesign
InformationSection.
W8x28Beam
Supporting
(seeNote#1)
Restrained Unrestrained Unrestrained
Assembly Assembly Beam AllFluted Fluted
RatingHr RatingHr RatingHr FloorUnits FloorUnitsand
w/Lightweight NormalWeight
Concrete ConcreteOnly

1 1 1 5/16,11/16## 5/16

11/2 11/2 11/2 11/16,1## 5/8

2 1 1 5/16,11/16## 5/16

2 2 2 1,13/16## 7/8

3 11/2 11/2 11/16 5/8

3 3 3 15/16 17/16

3 3 4 15/8 2

http://database.ul.com/cgibin/XYV/template/LISEXT/1FRAME/showpage.html?name=BXUV.D925&ccnshorttitle=Fireresistance+Ratings++ANSI/UL+263&ob 6/9
6/12/2017 BXUV.D925FireresistanceRatingsANSI/UL263
Note#1:JoistsfromtheNseriesdesignsmaybesubstitutedforthelistedbeam.Whenjoistsare
substituted,therestrainedratingofthejoistmustbeequaltoorgreaterthattherestrainedratingofthe
assembly.AdditionaljoistsubstitutionrequirementsarecontainedinthefrontoftheFireResistance
Directory.

##ThisthicknessapplieswhenoptionalItem10isusedover31/4in.lightweightconcretetopping.

ARABIANVERMICULITEINDUSTRIESTypesZ106/HY

GCPAPPLIEDTECHNOLOGIESINCTypeZ106/HY.

GCPKOREAINCTypeZ106/HY.

4B.AlternateSprayAppliedFireResistiveMaterialsAppliedbymixingwithwaterandsprayinginoneormore
coatstoafinalthicknessasshowninthetablesbelowtosteelbeamsurfaceswhichmustbecleanandfreeofdirt,
loosescaleandoil.Thethicknessesshowninthetablebelowareapplicabletobeamssupportingallflutedfloororform
units.Minavgandmininddensityof40/36pcfrespectivelyforTypesAV650,Z146,Z146PCandZ146T
cementitiousmixture.Minavgandmininddensityof50/45pcfrespectivelyforTypesAV800,Z156,Z156TandZ
156PC.FordensitydeterminationrefertoDesignInformationSection.
W8x28
BeamSupporting
(seeNote#1)

AllFluted FlutedFloor
Restrained Unrestrained Unrestrained FloorUnits Unitsand
Assembly Assembly Beam w/Lightweight NormalWeight
RatingHr RatingHr RatingHr Concrete ConcreteOnly

1 1 1 5/16,11/16## 5/16

11/2 11/2 11/2 11/16,1## 5/8

2 1 1 5/16,11/16## 5/16

2 2 2 1,13/16## 7/8

3 11/2 11/2 11/16 5/8

3 3 3 15/16 17/16

3 3 4 15/8 2

Note#1:JoistsfromtheNseriesdesignsmaybesubstitutedforthelistedbeam.Whenjoistsare
substituted,therestrainedratingofthejoistmustbeequaltoorgreaterthattherestrainedratingofthe
assembly.AdditionaljoistsubstitutionrequirementsarecontainedinthefrontoftheFireResistance
Directory.

##ThisthicknessapplieswhenoptionalItem10isusedover31/4in.lightweightconcretetopping.

ARABIANVERMICULITEINDUSTRIESTypesAV650,AV800andZ146investigatedforexterioruse.

GCPAPPLIEDTECHNOLOGIESINCTypeZ146,Z146T,Z146PC,Z156,Z156TandZ156PCinvestigatedfor
exterioruse.

GCPKOREAINCTypeZ146investigatedforexterioruse.

5.ShearConnectorStudsOptionalStuds3/4in.diamby3in.long,for11/2in.deepformunitsto51/4in.
longfor3in.deepformunits,headedtypeorequivalentperAISCspecifications.Weldedtothetopflangeofthebeam
throughthesteelformunits.

6.ElectricalInserts(Notshown)Classifiedas"OutletBoxesandFittingsClassifiedforFireResistance".

HHROBERTSONPresetInserts.

Forusewith21/2in.lightweightconcretetoppingoverQLWKXsteelfloorunits.Installedoverfactorypunchedholes
infloorunitsperaccompanyinginstallationinstructions.Spacingshallnotbemorethanoneinsertineach14sqftof
floorareawithspacingalongfloorunitsnotlessthan48in.OC.Theholescutininsertcoverforpassageofwiresshall
benomorethan1/8in.largerdiamthanwire.RestrainedAssemblyRatingis3/4hrwithTapmateIIFS1and1hr
withTapmateIIFS2inserts.

HHROBERTSONTapmateIIFS1,IIFS2SeriesKEB.
http://database.ul.com/cgibin/XYV/template/LISEXT/1FRAME/showpage.html?name=BXUV.D925&ccnshorttitle=Fireresistance+Ratings++ANSI/UL+263&ob 7/9
6/12/2017 BXUV.D925FireresistanceRatingsANSI/UL263

WIREMOLDCOAftersetInserts.Singleserviceaftersetinsertsinstalledperaccompanyinginstallationinstructions
in21/2in.diamholecoredrilledthroughmin31/4in.thickconcretetoppingtotopofcellofanymin3in.deep
cellularsteelfloorunitspecifiedunderItem3.Spacingshallbenomorethanoneinsertineach10sqftoffloorareain
eachspanwithamincentertocenterspacingof16in.Ifthehighpotentialandlowpotentialracewaysofthecellular
steelfloorunitareseparatedbyavalleyfilledwithconcrete,thecentertocenterspacingofthehighpotentialandlow
potentialsingleserviceaftersetinsertsmaybereducedtoaminof71/2in.RestrainedAssemblyRatingis2hror
lesswithinternallyprotectedType436aftersetinsertwithTypeM4,M6orM8Seriessingleserviceactivationfitting.

WIREMOLDCOInternallyprotectedType436aftersetinsertwithTypeM4,M6orM8Seriessingleservice
activationfitting.

7.RoofCoveringMaterials*(Optional,notshown)Consistingofmaterialscompatiblewithinsulationsdescribed
hereinwhichprovideClassA,BorCcoverings.SeeRoofingMaterialsandSystemsDirectoryRoofCoveringMaterials
(TEVT).

8.InsulatingConcrete(notshown)Optional.Varioustypesofinsulatingconcretepreparedandappliedinthe
thicknessindicated:

A.VermiculiteConcrete(notshown)Optional.

1.Blend6to8cuftofVermiculiteAggregate*to94lbPortlandCement
andairentrainingagent.Minthicknessof2in.asmeasuredtothetop
surfaceofthestructuralconcreteorfoamedplastic(Item9)whenitis
used.

SIPLASTINC

VERMICULITEPRODUCTSINC

2.Blend3.5cuft.ofTypeNVCConcreteAggregate*orTypeNVS
VermiculiteAggregate*to94lbPortlandCement.Slurrycoat,1/8in.
thicknessbeneathfoamedplastic(Item9)whenused,1in.mintopping
thickness.

SIPLASTINC

VERMICULITEPRODUCTSINC

VermiculiteconcretemaybecoveredwithRoofCoveringMaterials(Item
7).

B.CellularConcreteRoofToppingMixture*ConcentratemixedwithwaterandPortland
Cementpermanufacturersspecifications.Min.thicknessof2in.asmeasuredtothetopsurface
ofthestructuralconcreteorfoamedplastic(Item9)whenused.28daymincompressive
strengthof190psiasdeterminedwithASTMC49566.

CELCOREINCTypeCelcorewithcastdrydensityof31(+or3.0)pcforTypeCelcoreMF
withcastdrydensityof29(+or3.0)pcf.

AERIXINDUSTRIESCastdrydensityof37(+or)3.0pcf.

ELASTIZELLCORPOFAMERICATypeII.Mix#1ofcastdrydensity39(+or)3.0pcf,
Mix#2ofcastdrydensity40(+or)3.0pcf,Mix#3ofcastdrydensity47(+or)3.0pcf.

LITECRETEINCCastdrydensityof29(+or)3.0pcf.

SIPLASTINCMixNo.1or2.Castdrydensityof32+3(MixNo.1)or36+3(mixNo.2)pcf.

C.PerliteConcreteMixconsistsof6.2cuftPerliteAggregate*to94lbsofPortlandcement
and11/2ptairentrainingagent.Compressivestrength80psimin.

SeePerliteAggregate(CFFX)categoryfornamesofClassifiedcompanies.

D.CellularConcreteRoofToppingMixture*FoamConcentratemixedwithwater,Portland
CementandULClassifiedVermiculiteAggregatepermanufacturer'sapplicationinstructions.
Castdrydensityof33(+or)3.0pcfand28daycompressivestrengthofmin250psias
determinedinaccordancewithASTMC49586.

AERIXINDUSTRIESMixNo.3.

http://database.ul.com/cgibin/XYV/template/LISEXT/1FRAME/showpage.html?name=BXUV.D925&ccnshorttitle=Fireresistance+Ratings++ANSI/UL+263&ob 8/9
6/12/2017 BXUV.D925FireresistanceRatingsANSI/UL263
SIPLASTINCMixNo.3.

E.FloorToppingMixture*(Optional,notshown)Approx4.5galofwaterto41lbsof
NVSPremixfloortoppingmixture.Slurrycoat1/8in.thicknessbeneathfoamedplastic(Item9)
whenused,1in.mintoppingthickness.

SIPLASTINC

FloorToppingMixturemaybecoveredwithBuiltUporSingleMembraneRoofCovering.

9.FoamedPlastic*(Optionalnotshown)ForuseonlywithvermiculateorcellularconcretesorFloorTopping
mixture(Item8E)Rigidpolystyrenefoamedplasticinsulationhavingslotsand/orholessandwichedbetween
vermiculiteconcreteslurrywhichisappliedtothenormalorlightweightconcretesurfaceandconcretetopping.

SIPLASTINC

VERMICULITEPRODUCTSINC

10.RoofInsulationMineralandFiberBoards*orFoamedPlastic*(Optional,notshown)Mineralandfiber
boardsorpolyisocyanurateroofinsulationappliedoverconcretefloorwithnorestrictiononboardthickness.When
mineralandfiberboardsorpolyisocyanurateroofinsulationareusedtheunrestrainedbeamratingshallbeincreasedby
aminof1/2hr.SeeMineralandFiberBoards(CERZ)orFoamedPlastic(CCVW)categoryfornamesofManufacturers.

*IndicatessuchproductsshallbeartheULorcULCertificationMarkforjurisdictionsemployingtheULorcULCertification
(suchasCanada),respectively.

LastUpdatedon20170510

Questions? Printthispage TermsofUse PageTop

2017ULLLC

Theappearanceofacompany'snameorproductinthisdatabasedoesnotinitselfassurethatproductssoidentifiedhavebeenmanufactured
underUL'sFollowUpService.OnlythoseproductsbearingtheULMarkshouldbeconsideredtobeCertifiedandcoveredunderUL'sFollowUp
Service.AlwayslookfortheMarkontheproduct.

ULpermitsthereproductionofthematerialcontainedintheOnlineCertificationDirectorysubjecttothefollowingconditions:1.TheGuide
Information,Assemblies,Constructions,Designs,Systems,and/orCertifications(files)mustbepresentedintheirentiretyandinanon
misleadingmanner,withoutanymanipulationofthedata(ordrawings).2.Thestatement"ReprintedfromtheOnlineCertificationsDirectory
withpermissionfromUL"mustappearadjacenttotheextractedmaterial.Inaddition,thereprintedmaterialmustincludeacopyrightnoticein
thefollowingformat:"2017ULLLC".

http://database.ul.com/cgibin/XYV/template/LISEXT/1FRAME/showpage.html?name=BXUV.D925&ccnshorttitle=Fireresistance+Ratings++ANSI/UL+263&ob 9/9