Transformers
Fig. 5.1-1 and table 5.1-1 are an overview of how various trans-
formers can be used in a network.
Global Footprint
Emerging countries are not just extended workbenches for
producing goods. First and foremost, they are important future
markets. Through its own local production and sales locations,
Siemens provides service to customers in the most important
global markets. The local presence of Siemens in many coun-
tries also ensures that customers have better access to Siemens
services and that they benet from an efcient and effective
distribution of Siemens resources as part of a global network.
As Siemens factories around the world develop and produce
their products, Siemens also encourages them to share their
expertise.
Generator and System Above 2.5 MVA up to more than 1,000 MVA, above 30 kV up to 1,500 kV (system and system
5
Transformers interconnecting transformers, with separate windings or auto-connected), with on-load tap
changers or off-circuit tap changers, of 3-phase or 1-phase design
Phase Shifters To control the amount of active power by changing the effective phase displacement
Reactors Liquid-immersed shunt and current-limiting reactors up to the highest rated powers
Reactors for HVDC transmission systems
HVDC Transformers Transformers and smoothing reactors for bulk power transmission systems up to 800 kV DC
Transformers for DC coupling of different AC networks
Cast-Resin Distribution and 100 kVA to more than 40 MVA, highest voltage for equipment up to 36 kV, of 3-phase or 1-phase
Power Transformers GEAFOL design, GEAFOL-SL substations
Liquid-immersed Distribution 50 to 2,500 kVA, highest voltage for equipment up to 36 kV, with copper or aluminum windings,
Transformers hermetically sealed or with conservator of 3- or 1-phase design
pole mounted transformers and distribution transformers acc. to IEC with amorphous cores
5 tCustomer integration
tEmbedded quality in processes and projects
Fig. 5.2-1: Cornerstones of quality strategy
tConsequent supplier management
tBusiness-driven quality planning
tFocused quality reporting
tQualication of employees on quality issues
tContinuous improvement
tManagement commitment achieved by a high degree of process standardization. All pro-
tControl and support role of quality manager cesses should be standardized for all employees based on simple
procedures. If this condition is met, it is possible to implement
Elements of quality (mandatory elements) clearly dened work instructions (g. 5.2-2).
Customer integration Quality gates are placed at points in the process at which
Customer integration depends on the consistent use of: quality-relevant decisions are necessary. The following quality
tAnalysis tools for customer requirements and market studies gates are mandatory for the power transformer business.
tAnalysis of customer satisfaction tBid approval
tProfessional management of feedback from and to the tEntry order claried
customer tRelease of design
tComplaint management tRelease of fully assembled transformer
tEvaluation of project
Customer requirements need to be precisely dened in a speci-
cation. And the specication must be continuously updated For each quality gate, there is a clear denition of participants,
throughout the denition phase of a transformer project. The preconditions, results (trafc light) and the escalation process, if
actual requirements must also be available to all responsible necessary. If the result is not acceptable, the process must be
employees. stopped until all requirements are fullled.
Rapid feedback loops in both directions are essential in order Supplier management
to increase customer trust and satisfaction. The quality of the product depends not only on the quality of the
own processes but also on that of the suppliers. Problems and
Siemens resolves customer complaints to the customers satis- costs caused by inadequate supplier quality can only be reduced
faction in a timely manner through its complaint management by a systematic supplier management process that includes:
system. tSelection
tAssessment
Embedded quality in processes and projects tClassication
The quality of the processes used to produce a product has a tDevelopment
signicant impact on the quality of the product that is actually tPhasing out of suppliers as well as the support process Supplier
produced. Process discipline and process stability can be Qualication
A further condition for a high level of supplier quality is close TPD TPD
SIEMENS Core assembly stacking core SIEMENS Core assemblystacking core
cooperation with the suppliers. Joint development of require- PEQ laminates
2.01.02
Page 1/6 PEQ laminates
2.01.02
Page 1/6
1. Purpose/objective
ments for suppliers and processes leads to continuous improve- Process description for the manufacture of transformer core
within the tolerances which are laid down
4. Process sequence
Subprocess 1:
the transformer business. washers, small accessories Job related core drawings
Process report TPD 2.01.01
Planning quality means analyzing possible future scenarios and Process owner
Staff trained in core assembly Adjusting
the support
the core-limb laminations
ness factors are considered in planning. That means that quality Measure--
Measure
ment
Clearance support trestles
< 650
support trestles
550
1,000 to 1,200
350
300
Locking the screwed connections in accordance with TPD 3.036.01
activities and quantitative indicators. Measurement of insulation resistance with TUQ 1634 1,200 to 1,500 250
Drawn up by: Matthes Checked/approved: Dr. Knorr As of date: 2004-02 Drawn up by: Matthes Checked/approved: Dr. Knorr As of date: 2004-02
The passing on as well as the duplication of this document. use and communication of its contents is not permitted. nor may thecontents be expressed. Offenders are liable to pay damages. All rights The passing on as well as the duplication of this document. use and communication of its contents is not permitted. nor may thecontents be expressed. Offenders are liable to pay damages. All rights
reserved. in particular for the case of patent granting or GM-entry reserved. in particular for the case of patent granting or GM-entry
E T TR Plant Plant Plant Plant Plant Plant Plant Plant Plant Plant Plant Plant Plant Plant Plant
1 2 3 4 5 6 7* 8 9 10 11 12 13* 14** 15
N 11,278 572 1,704 755 793 774 534 735 1,076 705 649 994 1007 980
SY 51,429 2,358 7,479 3,858 3 4,326 1,996 3,341 4,561 4,17 2,889 4,899 3,781 4,771
nF 91 9 7 10 11 1 11 3 6 2 7 8 3 13
FRe (%) 0.18 0.38 0.09 0.26 0.37 0.02 0.55 0.09 0.13 0.05 0.24 0.16 0.08 0.27
MTBF (yrs) 565 262 1068 386 273 4,326 181 1,114 760 2,085 413 612 1,26 367
* Plant 7 & 13: new plants; ** Plant 14: 9 years 2001 2009
Methods like, Kaizen, 5S and methods and tools from Six Sigma
e.g. DMAIC circle, FMEA, IPO are helpful in supporting this
5.3 Transformer Loss
continuous improvement process (g. 5.2-3). Evaluation
Management commitment
Every manager in a company also bears responsibility for quality. The sharply increased cost of electrical energy has made it
Thus, each managers actions must be characterized by a high almost mandatory for buyers of electrical machinery to carefully
level of quality awareness. evaluate the inherent losses of these items. For distribution and
power transformers, which operate continuously and most
The level of commitment shown by all levels of management in frequently in loaded condition, this consideration is especially
the event of quality problems, the establishment of quality important. As an example, the added cost of loss-optimized
demands and the creation of targeted quality controls in day-to- transformers can in most cases be recovered via savings in
day work together produce a culture in which there is a high energy use in less than three years.
level of quality.
Low-loss transformers use more and better materials for their
Control and support role of the quality manager construction and are thus intially more expensive than low-cost
The role of the quality manager is of fundamental importance transformers. By stipulating loss evaluation gures in the trans-
for well-running processes. The quality manager combines a former inquiry, the manufacturer receives the necessary incen-
supporting role with that of a neutral controller. Quality man- tive to provide a loss-optimized transformer rather than the
agement must be directly involved in processes and projects. low-cost model. Detailed loss evaluation methods for trans-
The independence of the quality department and individual formers have been developed and are described accurately in
Measure
4000
tCost of load loss (CPk) based on the load loss (Pk), the
3000
2000
1000
What must be done What is preventing Note that the lowest purchase price is unlike the total cost of
in order to achieve us to fulll the ownership.
the goal requirements
taking into account the purchase price Cp, the interest rate p, Depreciation period n = 20 years Depreciation
and the depreciation period n Interest rate p = 12 % p. a. factor r = 13.39
Energy charge Ce = 0.25 / kWh
Cc = Cp r / 100 [amount / year]
Demand charge Cd = 350 / (kW . year)
Cp = purchase price
Equivalent annual load factor _ = 0.8
r = p . qn / (qn 1) = depreciation factor
q = p / 100 + 1 = interest factor
p = interest rate in % p.a A. Low-cost transformer B. Loss-optimized transformer
n = depreciation period in years
C Pk = Ce 8,760 h / year a2 Pk
CD = 350 (19 + 167) CD = 350 (16 + 124)
a = constant opperation load / rated load = 65,100 / year = 49,000 / year
Pk = copper loss [kW]
Fig. 5.3-1: Calculation of the individual operation cost of a Fig. 5.3-2: Example for cost saving with optimized distribution
transformer in one year transformer
Specic items
tTransformer design according to national and international
standards (IEC/ANSI) with or without voltage regulation
t3-phase or 1-phase
tTank-attached radiators or separate radiator banks
5.5 Reactors
In AC networks, shunt reactors and series reactors are widely
used in the system to limit the overvoltage or to limit the short-
circuit current. With more high-voltage overhead lines with long
transmission distance and increasing network capacity, both
types of reactors play an important role in the modern network
system.
Oil lled reactors offer individual solutions: They satisfy all the
specied requirements regarding voltage, rating, type of opera-
tion, low-noise and low loss and type of cooling, as well as trans-
portation and installation.
5 construction of transformers.
Shunt reactors
For extra-high-voltage (EHV) transmission lines, due to the long
Fig. 5.5-1: Reactor
distance, the space between the overhead line and the ground
naturally forms a capacitor parallel to the transmission line,
which causes an increase of voltage along the distance.
Depending on the distance, the prole of the line and the power
being transmitted, a shunt reactor is necessary either at the line
terminals or in the middle. An liquid-immersed shunt reactor is a
solution. The advanced design and production technology will
ensure the product has low loss and low noise level.
Series reactors
When the network becomes larger, sometimes the short-circuit
current on a transmission line will exceed the short-circuit
current rating of the equipment. Upgrading of system voltage,
upgrading of equipment rating or employing high-impedance
transformers are far more expensive than installing liquid-
immersed series reactors in the line. The liquid-immersed design
can also signicantly save space in the substation.
Specication
Typically, 3-phase or 1-phase reactors should be considered rst.
Apart from the insulation level of the reactor, the vector group,
overall loss level, noise level and temperature rise should be
considered as main data for the shunt reactor.
Although the above data are also necessary for series reactors,
the rated current, impedance and thermal/dynamic stability
current should also be specied.
Design options
tDirect or indirect regulation
tOn-load or no-load tap changer (OLTC/NLTC)
tBuilt-in reactor for long arc stability
tSecondary bushing arrangements and designs
tAir or water-cooled
tInternal secondary phase closure (internal delta)
Rectier transformers
Rectier transformers are combined with a diode or Thyristor
rectier. The applications range from very large aluminum
electrolysis to various medium-size operations. The transformers
may have a built-in or a separate voltage regulation unit. Due to
a large variety of applications, they can have various designs up
to a combination of voltage regulation, rectier transformers in
double-stack conguration, phase-shifting, interphase reactors,
transductors and lter-winding (g. 5.6-2).
Specic items
Thyristor rectiers require voltage regulation with a no-load tap
changer, if any. A diode rectier will, in comparison, have a
longer range and a higher number of small voltage steps than an
on-load tap changer. Additionally, an auto-connected regulating
transformer can be built in the same tank (depending on trans-
port and site limitations).
Design options
tThyristor or diode rectier
tOn-load or no-load tap changer (OLTC/NLTC)/lter winding Fig. 5.6-2: Rectier transformer for an aluminum plant
5.7 Phase-Shifting
Transformers
A phase-shifting transformer is a device for controlling the
power ow through specic lines in a complex power transmis-
sion network.The basic function of a phase-shifting transformer
is to change the effective phase displacement between the input
voltage and the output voltage of a transmission line, thus
controlling the amount of active power that can ow in the line.
Design options
The design concept of HVDC transformers is mainly inuenced
by the rated voltage, rated power and transportation require-
ments like dimensions, weight and mode of transportation.
Many large power HVDC converter station are located in rural
areas of low infrastructure. Frequently, special geometrical
Fig. 5.8-1: Converter transformer for UHVDC bipolar transmission
proles have to be fullled in order to move such transformers
system 800 kVDC, 6,400 MW; 2,071 km: single phase;
by railway.
550 kVAC, 816 kVDC; 321 MVA; high pulse wye system
feeding
Typically, HVDC transformers are single phase units containing
5.9 Distribution
Transformers
5.9.1 Liquid-immersed Distribution
Transformers for
European/US/Canadian Standard
On the last transformation step from the power station to the
consumer, distribution transformers (DT) provide the necessary
power for systems and buildings. Accordingly, their operation
must be reliable, efcient and, at the same time, silent.
Sub-bases
To raise the voltage regulator to meet safe operating clearances
from the ground to the lowest live part.
5.9.3 GEAFOL Cast-Resin Transformers GEAFOL transformers are installed wherever oil-lled units
cannot be used or where use of liquid-immersed transformers
GEAFOL transformers have been in successful service since would require major constructive efforts such as inside build-
1965. Many licenses have been granted to major manufacturers ings, in tunnels, on ships, cranes and offshore platforms, inside
throughout the world since then. Over 100,000 units have wind turbines, in groundwater catchment areas and in food
proven themselves in power distribution or converter operation processing plants. For outdoor use, specially designed sheet
all around the globe. metal enclosures are available.
Advantages and applications Often these transformers are combined with their primary and
GEAFOL distribution and power transformers in ratings from 100 secondary switchgear and distribution boards into compact
to approximately 50,000 kVA and lightning impulse (LI) values substations that are installed directly at their point of use.
up to 250 kV are full substitutes for liquid-immersed trans-
formers with comparable electrical and mechanical data. They When used as static converter transformers for variable speed
are designed for indoor installation close to their point of use at drives, they can be installed together with the converters at the
the center of the major load consumers. The exclusive use of drive location. This reduces construction requirements, cable
ame-retardant insulating materials frees these transformers costs, transmission losses and installation costs.
from all restrictions that apply to oil-lled electrical equipment,
such as the need for oil collecting pits, re walls, re extin- GEAFOL transformers are fully LI-rated. Their noise levels are
guishing equipment. For outdoor use, specially designed sheet comparable to oil-lled transformers. Taking into account the
metal enclosures are available. indirect cost reductions just mentioned, they are also mostly
5
LV terminals Three-leg core
Normal arrangement: Made of grain-oriented,
Top, rear low-loss electrolaminations
Special version: insulated on both sides
Bottom, available on
request at extra charge Resilient spacers
To insulate core and
windings from mechanical
vibrations, resulting in low
noise emissions
HV terminals HV winding
Variable arrangements, Consisting of vacuum-potted
for optimal station design. single foil-type aluminum coils.
HV tapping links for See enlarged detail
adjustment to system in g. 5.9-5
conditions, reconnectable
in de-energized state*
HV winding
The high-voltage windings are wound from aluminum foil
interleaved with high-grade insulating foils. The assembled and
connected individual coils are placed in a heated mold and are
potted in a vacuum furnace with a mixture of pure silica (quartz
sand) and specially blended epoxy resins. The only connections
to the outside are casted brass nuts that are internally
bonded to the aluminum winding connections.
operating conditions.
The properties laid down in the standards for ratings within the
category relating to environment (humidity), climate and re
behavior have to be demonstrated by means of tests.
These tests are described for the environmental category Fig. 5.9-6: Flammability test of cast-resin transformer
(code numbers E0, E1 and E2) and for the climatic category
(code numbers C1 and C2) in IEC 60076-11. According to this
5
standard, the tests are to be carried out on complete trans-
formers. The tests of re behavior (re category code numbers
F0 and F1) are limited to tests on a duplicate of a complete
transformer that consists of a core leg, a low-voltage winding
and a high-voltage winding.
Insulation class and temperature rise Fig. 5.9-7: Radial cooling fans on GEAFOL transformer for AF cooling
The high-voltage winding and the low-voltage winding utilize
class F insulating materials with a mean temperature rise of
100 K (standard design).
Um (kV) LI (kV) AC (kV)
Overload capability 1.1 3
GEAFOL transformers can be overloaded permanently up to 50 % 12 75 28
(with a corresponding increase in impedance voltage and load 24 95* 50
losses) if additional radial cooling fans are installed (dimensions
36 145* 70
can increase by approximately 100 mm in length and width.)
* other levels upon request
Short-time overloads are uncritical as long as the maximum
winding temperatures are not exceeded for extended periods of Table 5.9-1: Standard insulation levels of GEAFOL
time (depending on initial load and ambient air temperature).
Temperature monitoring
Each GEAFOL transformer is tted with three temperature
sensors installed in the LV winding, and a solid-state tripping ating voltages of the LV winding of 3.6 kV and higher, special
device with relay output. The PTC thermistors used for sensing temperature measuring equipment can be provided.
are selected for the applicable maximum hot-spot winding
temperature. Auxiliary wiring is run in a protective conduit and terminated in
a central LV terminal box (optional). Each wire and terminal is
Additional sets of sensors can be installed, e.g. for fan control identied, and a wiring diagram is permanently attached to the
purposes. Alternatively, Pt100 sensors are available. For oper- inside cover of this terminal box.
Optimum compromise
Fig. 5.9-8: GEAFOL transformer with plug-type cable connections The GEAFOL Basic distribution transformer represents an
optimum compromise between performance, safety and small
dimensions. In addition, the high degree of standardization
ensures the best possible cost-benet ratio. Thanks to their
compact shape and comprehensive safety certication, GEAFOL
Basic distribution transformers can be used in almost every
environment.
5 4
6
2
5
8
Siemens offers suitable transformers in its GEAFOL design The effects of such conversion equipment on transformers and
(g. 5.9-10), which has proved successful over many years and additional construction requirements are as follows:
is available in ratings of up to 50 MVA. The range of rated tIncreased load by harmonic currents
voltage extends to 36 kV, and the maximum impulse voltage is tBalancing of phase currents in multiple winding systems
200 kV (250 kV). The main applications of this type of trans- (e.g., 12-pulse systems)
former are in modern industrial plants, hospitals, ofce and tOverload capability
apartment blocks and shopping centers. tTypes for 12-pulse systems, if required
Linking 1-pole tap changer modules together by means of Siemens supplies oil-lled converter transformers of all ratings
insulating shafts produces a 3-pole on-load tap changer for and congurations known today, and dry-type cast-resin con-
regulating the output voltage of 3-phase GEAFOL transformers. verter transformers up to 50 MVA and 250 kV LI (g. 5.9-11).
Fig. 5.9-10: 16/22-MVA GEAFOL cast-resin transformer with oil-free on-load tap changer
5
Transformers for Silicon-reactor power feeding
These special transformers are an important component in
plants for producing polycrystalline silicon, which is needed
particularly by the solar industry for the manufacture of collec-
tors.
5 Characterization
tVarious cooling media for all ratings: mineral oil, silicone or
ester uid for highest environmental compatibility
Technically, traction transformers are in general characterized as
follows: In case of customer request:
t1-phase transformers tWith cooling plant integrated in one frame together with the
tRatings up to 10 MVA and above transformer or stand-alone solution
tOperating frequencies from 16 to 60 Hz tNomex insulation for highest energy density
tVoltages: 1.5 kV DC, 3 kV DC, 15 kV, 25 kV, 11.5 kV
or other specic solutions Examples
tWeight: < 15 t The examples shown in the table are typical applications where
tAuxiliary windings and/or heater windings according to traction transformers from Siemens were used (table 5.10-1).
customer specication
tSingle or multiple system operation
tUnder oor, machine room or roof assembly
tTraction windings to be used as line lters
High speed train AVE S102 for RENFE Spain Electric locomotive for BB Austria Worlds most powerful series-production
(1216 Series) for cross-european haulage freight locomotive for China
Operation: Madrid Barcelona 4 system operation 6 axle machine
Travel time: 2 h 30 min for 635 km AC 15 kV: 16 Hz 9,600 kW on 6 axles
Number of cars: 8 AC 25 kV 50 Hz hauling of 20,000 t trains
Power system: 25 kV/50 Hz DC 3 kV
Maximum power at wheel: 8,800 kW DC 1.5 kV
Max. speed: 350 km/h Speed: 200 230 km/h
Number of seats: 404 Weight 87 t
Table 5.10-1: Siemens develops and produces traction transformers for rolling stock applications of all relevant ratings and voltage levels
What is TLM?
Siemens Transformer Lifecycle Management (TLM) includes
highly experienced transformer experts who provide the most
effective lifecycle solutions for power transformers of any age
and any brand.
The SITRAM DIAG program consists of three layers and provides Fig. 5.11-2: SITRAM DIAG provides diagnostic modules for
diagnostic modules for individual transformer and for the assess- individual transformers and for the assessment of
ment of complete installed eets and transformer populations. complete eets
The repair facilities handle all problems that arise over the
lifecycle of a transformer, including installation of new on-load
tap changers and tapping switches, increasing performance, as
well as completely replacement of windings. In addition, all
components can be reconditioned and retrotted with the latest
materials as needed. For everything from design to the latest
modern winding techniques to nal inspection and testing, the
manufacturing processes at our renowned transformer plants
are continuously being improved. These improvements support Fig. 5.11-6: Repair shop in Nuremberg, Germany
the maintenance and repair of your transformers (g. 5.11-6).