20KVA Generator Power Distribution Board:

63A 4P MCCB as Incomer

20A 4P MCB for PDB # 1 for GEB Service # 1 ( Non Critical Load to be cut-off )

20A 4P MCB for PDB # 2 for GEB Service # 2 ( Non Critical Load to be cut-off )

20A 4P MCB for PDB # 3 for GEB Service # 3 ( Non Critical Load to be cut-off )

20A 4P MCB as Spare

Cable Entries Top and Bottom

PDB # 1 for Ground Floor and Common Services ( GEB Service # 1 )


Main Incomer:

63A ATS inside PDB # 1

63A 4P MCCB

Outgoing Feeders:

Critical Load Side - to be backed up by DG Set:

1. 32A/25A 4P MCB for 7.5 KVA UPS ( 3-Phase Input and Single Phase Output )
2. 16A DP MCB as Incomer and Nos. 6A SP MCBs as Outgoing MCBs from R Phase

Non-critical Load Side -to be cut off when DG Set shall be on:

3. 25A 4P MCB for Lift


4. 16A/10A 4P MCB for 1.5HP Bore with DOL Starter
5. 25A 4P MCB as Incomer and 3 Nos. 16A DP MCB as Outgoing MCBs for 1.0TR AC, Xerox
Machine and Water Cooler.
6. 16/10A DP MCB for 1.0HP Water Pump with DOL Starter from R Phase with Starter
7. 16A/10A DP MCB with Timer and Contactor for 20X10 Feet Illuminated Signage located on
Terrace Floor from Y Phase
8. 16A/10A DP MCB Spare

PDB # 2 for First Floor and Second Floor ( GEB Service # 2 )


Main Incomer:

63A ATS

63A 4P MCCB

Outgoing Feeders:

Critical Load Side -to be backed up by DG Set:


1. 20A DP MCB as Incomer for First Floor Lighting from Y Phase
2. 20A DP MCB as Incomer for Second Floor Lighting from B Phase

Non-critical Load Side- to be cut-off when DG Set shall be on:

3. 25A 4P ELMCB 300mA for 10HP AC Outdoor Unit for First and Second Floor
4. 25A 4P ELMCB 300mA for 8HP AC Outdoor Unit for First and Second Floor
5. 6A DP MCB for First Floor AC Indoor Units from Y Phase
6. 6A DP MCB for Second Floor AC Indoor Units from B Phase
7. 6A DP MCB Spare

PDB # 3 for Third Floor, Fourth Floor and Terrace Floor ( GEB Service # 3 )
Main Incomer:

63A ATS

63A 4P MCCB

Outgoing Feeders:

Critical Load Side- to be backed up by DG Set:

1. 20A DP MCB as Incomer for Third Floor Lighting from R Phase


2. 20A DP MCB as Incomer for Fourth Floor Lighting from Y Phase
3. 20A DP MCB as Incomer for Terrace Floor ( Server Room ) and Pantry Lighting from B Phase

Non-critical Load Side- to be cut-off when DG Set shall be on:

4. 25A 4P ELMCB 300mA for 10HP AC Outdoor Unit for First and Second Floor
5. 25A 4P ELMCB 300mA for 8HP AC Outdoor Unit for First and Second Floor
6. 16A/10A 1.0TR AC Split Unit for Server Room AC from B Phase
7. 6A DP MCB for Third Floor AC Indoor Units from R Phase
8. 6A DP MCB for Fourth Floor AC Indoor Unit(s) from Y Phase