Professional Documents
Culture Documents
1550
MiCOM P220
CHAPTER 8.2-A
Commissioning of the MiCOM P220
Relay
Technical Guide TG 1.1550
Commissioning CHAPTER 8.2-A
MiCOM P220 Page 1/20
CONTENTS
2.1.4 Communication 4
4. COMMISSIONING 7
4.1 Settings 7
4.2 Measurements 7
4.3 Thermal replica 7
4.3.1 Test wiring diagram 8
4.3.2 Alarm threshold ALARM test, trip threshold test, and thermal constant time Te1 test. 9
4.3.3 Alarm threshold ALARM test, trip threshold test, and thermal constant time Te2 test. 9
When commissioning the MiCOM relay for the first time, 1/4 hour should be allowed
to become familiar with the menu (MENU OF THE HMI section).
With a laptop computer and ALSTOM setting software, the user can configure the
MiCOM P220 relay and save this setting on to a floppy disk. This file can
subsequently be downloaded via the RS232 front port or via the RS 485 link on the
rear of the MiCOM relays.
2.1.4 Communication
For all tests, the records can be made by using either the RS 485 rear port or the
RS232 front port of the relay.
2.2 Commissioning test records
Commissioning test records are available in the end of the Commissioning Chapter.
The presentation of the Commissioning test records follows the sequence of the tests
of this chapter.
The contents of these Commissioning test records enable you to log:
The name of the relay, station and circuit/plant
The characteristics of the MiCOM P220 relay
The various settings
The results of the tests
P1 S1
P2 S2
Other ends
of electrical cables
P1 S1 _
+ mA
+
_
P2 S2
Cortec code Relay auxiliary voltage range Auxiliary voltage range for the
* (Volts) logic inputs * (Volts)
A 24 60 Vdc 19 60 Vdc
F 48 150 Vdc 32 150 Vdc
M 130-250 Vdc 48 250 Vdc
100-250 Vca
* The tolerance on the auxiliary voltage variations is 20/+20%.
Technical Guide TG 1.1550
Commissioning CHAPTER 8.2-A
MiCOM P220 Page 7/20
4. COMMISSIONING
The various operations described in this section are not exhaustive, but combine
functions of MiCOM P220 relay which able to confirm that the relay is operational.
The use of appropriate ALSTOM T&D P&C setting software connected to either the
RS485 rear port or the RS232 front is not obligatory. The various indications
associated with each commissioning module are described for the MiCOM P220
front panel display (LCD and LEDs).
Commissioning covers the following points:
1. Input of settings,
2. Validation of measurements,
3. Validation of the thermal replica : I>, ALARM, FORBID START, Te1, Te2, Tr (49)
4. Validation of phase protection thresholds and time delays : I>>, tI>> (50/51)
5. Validation of earth protection thresholds and time delays : Io>, tIo>, Io>>, t
Io>> (50N/51N)
6. Validation of the Negative Sequence thresholds I2> and I2>> (46)
7. Validation of the automation function: latching of the relay outputs.
4.1 Settings
Input into the Commissioning Test Records file all of the settings of the MiCOM P220
relay.
4.2 Measurements
The MiCOM P220 relay measures phase and earth currents as a True RMS value up
to the 10th harmonic. The value(s) indicated take account of the phase and/or earth
CT ratio.
WARNING:
WARNING
MICOM P220 RELAY HAs 1 AND 5 AMP CURRENT INPUTS.
CHECK THAT THE injectED CURRENT IS compatible WITH THE SELECTED RANGE
Bring forward to the Setting record the values of phase and earth CTs.
Energise the MiCOM P220 relay.
Apply to each current input (as per wiring diagram) a current and check the
values on the LCD display.
Carry forward the results to the Commissioning test records (Applied values and
relay values displayed)
4.3 Thermal replica
Assign the thermal overload protective function to the trip output contact (relay RL1)
and assign the ALARM protective function to an auxiliary output contact, RL2 for
example. Set Ke equal to 3. In order to save time during testing, it is advisible to set
all the thermal time constants to 5 minutes.
TG 1.1550 Technical Guide
CHAPTER 8.2-A Commissioning
Page 8/20 MiCOM P220
INJECTION
TEST SET
33
AUXILIARY +Vaux
SUPPLY - Vaux 34
22
SWITCH 24
L1 Binary input 1
49
A
1A
50
51
CURRENT 1A
MiCOM
52
53
1A 1A
N
P220
54
41
A
5A
42
43
CURRENT 5A
5A 44
45
5A
N 46
37
35
36 WD Watchdog powered on
6
TIMERS Stop 4
2 RL1 Trip output Case earth
12 29
-
Stop 10
RL2
Programmable output * 30
8
31 RS 485
18 +
16 Programmable output Communication port
14 RL3 32 -
4.3.2 Alarm threshold ALARM test, trip threshold test, and thermal constant time Te1 test.
1. The binary input No 1 (terminals 22-24) should be kept energise during this
test.
2. Within the PROCESS menu, reset the thermal status value to 0.
3. Inject a single-phase current equal to 2.7 times the I> threshold value into the
phase A relay current input, this corresponds to an overload ratio of K = 1.8
4. Record the operating times of both alarm and trip threshold.
Checks:
1. ALARM alarm message on the LCD display.
2. Alarm LED flashes.
3. ALARM LED flashes (if programmed).
4. Operation of the RL2 output contact (if ALARM is assigned to RL2).
5. Check RL2 operates at a time equal to Te1. ln [1,82/(1,82 - ALARM)] .
6. Then occurrence of TH OVERLOAD alarm message on the LCD display.
7. Trip LED flashes.
8. THERM OVERLOAD LED flashes (if programmed).
9. Operation of the trip output contact (relay RL1).
10. Check RL1 operates at a time equal to 0.369 .Te1 .
4.3.3 Alarm threshold ALARM test, trip threshold test, and thermal constant time Te2 test.
1. The binary input No 1 (terminals 22-24) should be kept energise during this
test.
2. Within the PROCESS menu, reset the thermal status value to 0.
3. Inject a single-phase current equal to 3.9 times the I> threshold value into the
phase A relay current input, this corresponds to an overload ratio of K = 2.6.
4. Record the operating times of both alarm threshold and trip threshold.
Checks :
1. ALARM alarm message on the LCD display.
2. Alarm LED flashes.
3. ALARM LED flashes (if programmed).
4. Operation of the RL2 output contact (if ALARM is assigned to RL2).
5. Check RL2 operates at a time equal to Te2 . ln [2.62/(2.62 - ALARM)] .
6. Then occurrence of TH OVERLOAD alarm message on the LCD display.
7. Trip LED flashes.
8. THERM OVERLOAD LED flashes (if programmed).
9. Operation of the trip output contact (relay RL1).
10. Check RL1 operates at a time equal to 0.160 . Te2 .
TG 1.1550 Technical Guide
CHAPTER 8.2-A Commissioning
Page 10/20 MiCOM P220
Checks :
1. FORBIDDEN START alarm message on the LCD display.
2. Alarm LED flashes.
3. FORBIDDEN START LED flashes (if programmed).
4. Operation of the RL3 output contact (if FORBIDDEN START is assigned to RL3) after a
time equal to Tr. ln [2.62/(2.62 FORBID START)] .
Caution : The thermal base start inhibition is self-reset when the value
falls under the FORBID START threshold, so the checking of the above
item shall be done quickly after the current injection stoppage.
Technical Guide TG 1.1550
Commissioning CHAPTER 8.2-A
MiCOM P220 Page 11/20
INJECTION
TEST SET
33
AUXILIARY +Vaux
-Vaux
SUPPLY 34
49
A
1A
50
51
1A
CURRENT
MiCOM
52
53
1A 1A
N
P220
54
41
A 5A
42
43
CURRENT 5A
5A 44
45
5A
N 46
37
35 Case earth
36 WD Watchdog powered on
29
6 -
TIMER Stop 4
2 RL1 Trip output * 30
12 31
+ RS 485 communication port
10
RL2 Programmable output 32
8 -
INJECTION
TEST SET
33
AUXILIARY +Vaux
SUPPLY -Vaux 34
A
P1 S1
CURRENT 55
1A
1A 56
P2 S2 MiCOM
N
A
P220
P1 S1
CURRENT 47
5A
5A 48
P2 S2
N 37
35
Case earth
36 WD Watchdog powered on
29
6 -
TIMER Stop
4
RL1 Trip output * 30
2
12 31
+ RS 485 communication port
10
RL2 Programmable output 32
8
-
INJECTION
TEST SET
33
AUXILIARY +Vaux
-Vaux
SUPPLY 34
49
A
1A
N 50
51
CURRENT
MiCOM
52
53
1A
P220
54
41
A 5A
N 42
43
CURRENT
5A 44
45
46
37
35 Case earth
36 WD Watchdog powered on
29
6 -
TIMER Stop 4
2 RL1 Trip output * 30
12 31
+ RS 485 communication port
10
RL2 Programmable output 32
8 -
Reminder: the MiCOM P220 relay calculates the negative phase sequence
component using the formula:
I2 = 1/3 (Ia + a2 Ib + a Ic)
With a = cos (2/3) + j sin (2/3)
With a single phase injection such as the proposed figure 5: Ib = 0 and Ic = 0
And thus I2 = 1/3 Ia
In this case, the negative sequence current measured by the MiCOM P220 is equal to
one third of the injected current.
4.6.2 I2> threshold
Values to be recorded:
1. I2> threshold
2. Time delay tI2>.
I2> threshold check:
1. If the time delay tI2> is short, gradually increase the injection current up to the
value of the I2> threshold.
2. If the time delay tIo> is long, inject 0.95 x I threshold and check that there is no
tripping. Then inject 1.1 x I threshold and check the trip.
3. Gradually decreases the injected current and record the value of the drop out
I2> threshold.
Checks:
1. Alarm message on the LCD display.
2. Alarm LED flashes.
3. Trip LED flashes.
4. I2> threshold LED flashes (if programmed).
5. Trip output closes.
6. I2> threshold output closes (if programmed).
TI2> time delay check:
1. Apply a current on to the earth input and measure the time delay tI2> by pre-
setting the current above the I2> threshold (I injected > 2 x I threshold).
2. Apply a current on to the earth input and measure the time delay tI2> by pre-
setting the current above the I2> threshold (I injected > 10 x I threshold).
4.6.3 I2>> threshold
Values to be recorded:
1. I2>> threshold
2. Time delay tI2>>.
Technical Guide TG 1.1550
Commissioning CHAPTER 8.2-A
MiCOM P220 Page 17/20
INJECTION
TEST SET
33
AUXILIARY +Vaux
SUPPLY -Vaux 34
13
SWITCH 15
L3 Binary input 3
A
P1 S1
MiCOM
55
CURRENT 1A
1A 56
P2 S2 P220
N
A
P1 S1
CURRENT 47
5A
5A 48
P2 S2
37
35
N 36 WD Watchdog powered on
Case earth
29
6 -
TIMER Stop 4
RL1 Trip output
* 30
2
31
+ RS 485 communication port
32
-
BLANK PAGE