Air System Sizing Summary for GF DINING

Project Name: TALAL VILLA 07/31/2017


Prepared by: 555 07:47PM

Air System Information


Air System Name ........................................ GF DINING Number of zones ............................................................. 1
Equipment Class ......................................... SPLT AHU Floor Area ................................................................... 31.0 m
Air System Type ................................................ SZCAV Location .................................................... Masqat, Oman

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s .......................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space L/s ...................... Individual peak space loads Sizing Data ...................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load .......................................................... 11.9 kW Load occurs at ................................................... Jun 1600
Sensible coil load ..................................................... 9.8 kW OA DB / WB ...................................................... 45.2 / 30.0 C
Coil L/s at Jun 1600 ................................................ 802 L/s Entering DB / WB ............................................. 24.0 / 17.8 C
Max block L/s .......................................................... 802 L/s Leaving DB / WB .............................................. 13.9 / 13.3 C
Sum of peak zone L/s ............................................. 802 L/s Coil ADP ..................................................................... 12.8 C
Sensible heat ratio ............................................... 0.821 Bypass Factor .......................................................... 0.100
m/kW ....................................................................... 2.6 Resulting RH ................................................................. 58 %
W/m ..................................................................... 384.0 Design supply temp. ................................................... 13.0 C
Water flow @ 5.6 K rise ......................................... N/A Zone T-stat Check .................................................... 0 of 1 OK
Max zone temperature deviation .................................. 0.1 K

Supply Fan Sizing Data

Actual max L/s ......................................................... 802 L/s Fan motor BHP ........................................................... 0.20 BHP
Standard L/s ............................................................ 801 L/s Fan motor kW ............................................................. 0.15 kW
Actual max L/(s-m) .............................................. 25.87 L/(s-m) Fan static ..................................................................... 100 Pa

Outdoor Ventilation Air Data


Design airflow L/s ...................................................... 47 L/s L/s/person ................................................................... 9.38 L/s/person
L/(s-m) ................................................................... 1.51 L/(s-m)

Hourly Analysis Program v4.50 Page 1 of 1