You are on page 1of 30

Product Description

V100R001
TP48300B

Issue 03

Date 2012-11-02

HUAWEI TECHNOLOGIES CO., LTD.


Copyright Huawei Technologies Co., Ltd. 2012. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior written consent of
Huawei Technologies Co., Ltd.

Trademarks and Permissions

and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective holders.

Notice
The purchased products, services and features are stipulated by the contract made between Huawei and the customer.
All or part of the products, services and features described in this document may not be within the purchase scope or
the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this
document are provided "AS IS" without warranties, guarantees or representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the preparation of
this document to ensure accuracy of the contents, but all statements, information, and recommendations in this
document do not constitute a warranty of any kind, express or implied.

Huawei Technologies Co., Ltd.


Address: Huawei Industrial Base
Bantian, Longgang
Shenzhen 518129
People's Republic of China

Website: http://www.huawei.com

Email: support@huawei.com

Issue 03 (2012-11-02) Huawei Proprietary and Confidential i


Copyright Huawei Technologies Co., Ltd.
TP48300B
Product Description Contents

Contents

About This Document ..................................................................................................................... v


1 Product Positioning and Features .............................................................................................. 1
1.1 Product Positioning .......................................................................................................................................... 1
1.2 Product Features ............................................................................................................................................... 1

2 Product Structure........................................................................................................................... 3
2.1 Overview .......................................................................................................................................................... 3
2.2 Hardware .......................................................................................................................................................... 3
2.2.1 Cabinet .................................................................................................................................................... 4
2.2.2 Rectifier module...................................................................................................................................... 6
2.2.3 PMU ........................................................................................................................................................ 8

3 Application Scenarios ................................................................................................................ 12


4 Operation and Maintenance ..................................................................................................... 14
5 Technical Specifications ............................................................................................................ 15
5.1 Port Specifications ......................................................................................................................................... 15
5.2 Structural Specifications................................................................................................................................. 16
5.3 Electrical Specifications ................................................................................................................................. 17
5.4 EMC and Surge Protection Specifications ..................................................................................................... 19
5.5 Environmental Specifications ........................................................................................................................ 20

6 Design Standard .......................................................................................................................... 22


7 Acronyms and Abbreviations ................................................................................................... 23

Issue 03 (2012-11-02) Huawei Proprietary and Confidential ii


Copyright Huawei Technologies Co., Ltd.
TP48300B
Product Description Figures

Figures

Figure 2-1 Specifications of the TP48300B .......................................................................................................... 3


Figure 2-2 Exterior of the TP48300B .................................................................................................................... 4
Figure 2-3 Internal structure of the TP48300B...................................................................................................... 5
Figure 2-4 Rectifier module .................................................................................................................................. 6
Figure 2-5 Monitoring module .............................................................................................................................. 8
Figure 3-1 Application scenarios of the TP48300B............................................................................................. 12

Figure 3-2 TP48300B power system in a typical site power solution ................................................................. 13

Issue 03 (2012-11-02) Huawei Proprietary and Confidential iii


Copyright Huawei Technologies Co., Ltd.
TP48300B
Product Description Tables

Tables

Table 2-1 Technical parameters of the rectifier module ......................................................................................... 6


Table 2-2 Dimensions of the monitoring module .................................................................................................. 8
Table 2-3 Indicators state introduce ....................................................................................................................... 9
Table 2-4 Functions of the monitoring module...................................................................................................... 9
Table 5-1 Port specifications ............................................................................................................................... 15
Table 5-2 Structural specifications....................................................................................................................... 16

Table 5-3 Electrical specifications of the AC input ............................................................................................. 17


Table 5-4 Electrical specifications of the DC output ........................................................................................... 18
Table 5-5 EMC specifications ............................................................................................................................. 19

Table 5-6 Specifications for reliability ................................................................................................................ 19


Table 5-7 Surge protection specifications ............................................................................................................ 20
Table 5-8 Environmental specifications............................................................................................................... 20

Table 6-1 Design standards of the TP48300B ..................................................................................................... 22


Table 7-1 Acronyms and abbreviations ............................................................................................................... 23

Issue 03 (2012-11-02) Huawei Proprietary and Confidential iv


Copyright Huawei Technologies Co., Ltd.
TP48300B
Product Description About This Document

About This Document

Overview
The TP48300B is an AC/DC indoor power system. The 48 V/30 A rectifier modules or 48
V/50A rectifier modules are used. It supplies stable DC power to -48 V telecom equipment.
The TP48300B product description covers the product positioning and features, product
structure, application scenarios, operation and maintenance, technical specifications, and
acronyms and abbreviations.

Version
The following table lists the product version corresponding to this document.

Product Name Version

TP48300B V100R001

Intended Audience
This document is intended for:
Network planning engineer
System engineer
Site engineers

Change History
Version Change History

01 (2009-07-25) Initial release.


02 (20100310) Secondly release.
03(20121102) Port description is modified.

Issue 03 (2012-11-02) Huawei Proprietary and Confidential v


Copyright Huawei Technologies Co., Ltd.
TP48300B
Product Description About This Document

Organization
1 Product Positioning and Features
The TP48300B is an indoor power system that provides features such as easy module
installation, intelligent module sleep, remote management, and extended AC input voltage
range.
2 Product Structure
This chapter describes the specifications and hardware components of the TP48300B.
3 Application Scenarios
The TP48300B power system can be widely used in scenarios such as indoor BTSs and
indoor central equipment room when proper rectifier modules are configured.
4 Operation and Maintenance
The maintenance designs are optimized to achieve simple and convenient maintenance.
5 Technical Specifications
This section describes the specifications for the ports, structure, power supply, EMC and
surge protection, and environment.
6 Design Standard
This chapter describes the design standards of the TP48300B.
7 Acronyms and Abbreviations
The following table lists the acronyms and abbreviations mentioned in this document.

Conventions
Symbol Conventions
The symbols that may be found in this document are defined as follows.

Symbol Description

Indicates a hazard with a high level of risk that, if not avoided,


will result in death or serious injury.

Indicates a hazard with a medium or low level of risk which, if


not avoided, could result in minor or moderate injury.

Indicates a potentially hazardous situation that, if not avoided,


could cause equipment damage, data loss, and performance
degradation, or unexpected results.
Indicates a tip that may help you solve a problem or save time.
Provides additional information to emphasize or supplement
important points of the main text.

Issue 03 (2012-11-02) Huawei Proprietary and Confidential vi


Copyright Huawei Technologies Co., Ltd.
TP48300B
Product Description 1 Product Positioning and Features

1 Product Positioning and Features

About This Chapter


The TP48300B is an indoor power system that provides features such as easy module
installation, intelligent module sleep, remote management, and extended AC input voltage
range.
1.1 Product Positioning
The TP48300B is an indoor power system.
1.2 Product Features
The TP48300B provides features such as easy module installation, module sleep, and remote
management.

1.1 Product Positioning


The TP48300B is an indoor power system.
The TP48300B is an indoor power system (AC/DC) that is used to supply power for
communication devices of -48 V series. The TP48300B uses 30A rectifier modules (PSUs) or
50A rectifier modules (PSUs) and provides a maximum of 300 A output current.

1.2 Product Features


The TP48300B provides features such as easy module installation, module sleep, and remote
management.

Easy Module Installation


The monitoring module and rectifier module are hot-swappable, thus facilitating the
installation, saving maintenance time, and reducing the OPEX.

Issue 03 (2012-11-02) Huawei Proprietary and Confidential 1


Copyright Huawei Technologies Co., Ltd.
TP48300B
Product Description 1 Product Positioning and Features

Intelligent Sleep Technology


According to the load power, the power system automatically starts the sleep mode of rectifier
modules to save power.

Remote Management
NOTE

All ports in this manual are protected by a security mechanism.

The TP48300B power system provides comprehensive management on itself and storage
batteries. The monitoring module communicates with the rectifier module through the RS-485
serial port and communicates with the Huawei WCDMA main equipment through the
RS-232/422/485 serial port, thus realizing remote management and unattended operations.
This helps to reduce the OPEX.

Extended AC Input Voltage Range


The AC phase input voltage of the system ranges from 90 V AC to 290 V AC.

Highly Safety Design


The TP48600B power system comply with the CE, TLC standards. The power distribution
components comply with the CE, TUV, 3C standards. The rectifier module complies with the
UL, CE, and TUV standards.

Issue 03 (2012-11-02) Huawei Proprietary and Confidential 2


Copyright Huawei Technologies Co., Ltd.
TP48300B
Product Description 2 Product Structure

2 Product Structure

About This Chapter


This chapter describes the specifications and hardware components of the TP48300B.
2.1 Overview
This section describes the specifications of the TP48300B.
2.2 Hardware
The TP48300B power system mainly comprises the cabinet, rectifier module, and monitoring
module.

2.1 Overview
This section describes the specifications of the TP48300B.

Figure 2-1 Specifications of the TP48300B

2.2 Hardware
The TP48300B power system mainly comprises the cabinet, rectifier module, and monitoring
module.
2.2.1 Cabinet
This section describes the appearance and features of the cabinet.
2.2.2 Rectifier module

Issue 03 (2012-11-02) Huawei Proprietary and Confidential 3


Copyright Huawei Technologies Co., Ltd.
TP48300B
Product Description 2 Product Structure

This section describes the appearance, technical parameters, and functions of the rectifier
module (PSU).
2.2.3 PMU
This section describes the dimensions, functions, performance specifications, ports, and panel
indicators of the PMU.

2.2.1 Cabinet
This section describes the appearance and features of the cabinet.

Appearance
The dimensions of the power system are 600 mm x 450 mm x 1600 mm (width x depth x
height). Figure 2-2 shows the exterior of the power system. Figure 2-3 shows the internal
structure of the power system.
The cabinet is assembled before the installation. It can be installed on the ground with
expansion bolts. You need not level it.

Figure 2-2 Exterior of the TP48300B

Issue 03 (2012-11-02) Huawei Proprietary and Confidential 4


Copyright Huawei Technologies Co., Ltd.
TP48300B
Product Description 2 Product Structure

Figure 2-3 Internal structure of the TP48300B

(1) Load shutdown (2) BLVD MCB (3) Copper transfer bar (4) PMU
fuse (LLVD fuse)
(5) Rectifier (6) N-type wiring (7) Grounding busbar of the (8) AC input
module (PSU) terminal cabinet MCB
(9) Battery fuse (10) Positive (11) Power Monitoring (12) AC surge
busbar of the DC Interface Board (under the protector
output cover plate)
(13) BLVD switch (14) LLVD switch

Features
The cabinet can be operated from the front, thus facilitating the maintenance.
The cabinet supports transportation with installed boards, thus facilitating the delivery.
The MCBs have high power shutdown capability (10 kA).

Technical Specifications
For details of the technical specifications, see 5.2 Structural Specifications.

Issue 03 (2012-11-02) Huawei Proprietary and Confidential 5


Copyright Huawei Technologies Co., Ltd.
TP48300B
Product Description 2 Product Structure

2.2.2 Rectifier module


This section describes the appearance, technical parameters, and functions of the rectifier
module (PSU).
The rectifier module (PSU) converts the AC input power into stable -48 V DC power.
According to the load, the TP48300B can be configured with 2 to 10 rectifier modules.

Appearance
The front panel of the rectifier module provides the power operating indicator, protection
indicator, and fault indicator. Figure 2-4 shows the exterior of the rectifier module.

Figure 2-4 Rectifier module

Technical Specifications
Table 2-1 lists technical parameters of the rectifier module.

Table 2-1 Technical parameters of the rectifier module

Parameter Specification

Model EPW30-48A
EPW50-48A
Weight EPW30-48A: 2.2kg
EPW50-48A: 2.5kg
Working temperature -33C to +65C
Working humidity 5% to 95%
Transportation temperature -40C to +70C
Storage temperature -40C to +70C
Environmental
Specifications Storage humidity 5% to 95%
Altitude 0 m to 4000 m (at the
altitude from 3,000 m to
4000 m, the temperature
declines by 1C for each
200 m increase in altitude)

Issue 03 (2012-11-02) Huawei Proprietary and Confidential 6


Copyright Huawei Technologies Co., Ltd.
TP48300B
Product Description 2 Product Structure

Parameter Specification

Cooling method Forcible cooling by wind


Operating voltage 90 V AC to 290 V AC; rated
voltage: 220 V
Operating frequency 45 Hz to 65 Hz; rated
AC input
frequency: 50/60 Hz
Power factor Not lower than 0.99 at the
rated load
Output voltage 44 V DC to 58 V DC; rated
voltage: 53.5 V
Output power EPW30-48A:
Rated voltage: 1600 W
(input of 176 V AC to
290 V AC)
Rated voltage: 700 W
(input of 150 V AC to
175 V AC)
Rated voltage: 600 W
(input of 90 V AC to 150
V AC)
EPW50-48A:
Rated voltage: 2900 W
DC output (input of 176 V AC to
290 V AC)
Rated voltage: 1200 W
(input of 90 V AC to 175
V AC)
Efficiency index EPW30-48A: 91%
(when the input is 220 V
AC, the voltage is the
rated voltage, and the
current is above 25% of
the rated current)
R4850N1: The peak
point is 92.5%
91.5%(230V
AC,35%80% load)

Protection Function
Input overvoltage/undervoltage protection
Input overcurrent protection
Output overvoltage protection
Output short-circuit protection

Issue 03 (2012-11-02) Huawei Proprietary and Confidential 7


Copyright Huawei Technologies Co., Ltd.
TP48300B
Product Description 2 Product Structure

Output current-limiting protection


Overtemperature protection

Features
High power density
Stable running
Intelligent module sleep
Hot-swappable

2.2.3 PMU
This section describes the dimensions, functions, performance specifications, ports, and panel
indicators of the PMU.

Dimensions
Table 2-2 lists the dimensions of the monitoring module. The monitoring board is installed in
the monitoring module. Figure 2-5 shows the exterior of the monitoring module.

Table 2-2 Dimensions of the monitoring module


Parameter Specification

Model CPMU01
Weight of the monitoring module 0.8 kg
Dimensions of the monitoring module 102 mm x 209 mm x 43 mm
(width x depth x height)

Figure 2-5 Monitoring module

Issue 03 (2012-11-02) Huawei Proprietary and Confidential 8


Copyright Huawei Technologies Co., Ltd.
TP48300B
Product Description 2 Product Structure

Table 2-3 Indicators state introduce

Indicators Normal Abnorma Reason


state lity state

Monitoring OFF PMU fault


module RUN
state Indicators ON PMU work normally; PMU disconnect the
(Green) communication with main equipment.
Flash PMU work normal; PMU normally
slowly communicate with main equipment.
Fault/ALM OFF ON When PMU has severity alarms, the ALM
Indicators indicators on, and buzzer of the monitoring
(Red) module tweet.

Functions
Through the RS232/485 ports and dry contacts, the monitoring module can perform
operations on the power system, BAM (Back Administration Module), or portable terminals
to implement the functions of environment monitoring, exceptional alarm management,
battery management, rectifier module management, power distribution management, and
remote setting. Table 2-4 lists functions of the monitoring module.

Table 2-4 Functions of the monitoring module

Type Function Description

Management of Load high temperature shutdown


load shutdown
Intelligent Battery equalized charging management
management of
batteries Battery floating charging management
Battery discharging testing
Battery temperature compensation
Battery remaining capacity testing
Remote Testing AC input voltage testing
Load current testing
Battery group current testing
DC busbar voltage testing
Battery temperature testing
Ambient humidity testing
Ambient temperature testing (two circuits)
Standby analog value measurement (four circuits)

Issue 03 (2012-11-02) Huawei Proprietary and Confidential 9


Copyright Huawei Technologies Co., Ltd.
TP48300B
Product Description 2 Product Structure

Type Function Description

Remote Startup and shutdown of the rectifier module


management
Rectifier module voltage regulation
Rectifier module current limitation
Connect or disconnect batteries
Connect or disconnect load
Buzzer alarm of the monitoring module
Dry contact (9 outputs)
Remote signaling Without mains supply
Mains phase loss
Mains overvoltage and undervoltage
DC overvoltage
DC undervoltage
Load fuse and MCB disconnection alarm
Battery shutdown (BAM shutdown, shutdown against
overtemperature, shutdown against undervoltage)
Environment overtemperature alarm
Environment undertemperature alarm
Environment overhumidity alarm
Environment underhumidity alarm
No.x module fault alarm
No.x module protection alarm
Reporting of the output current of the rectifier module
Battery loop failure alarm
Surge protector failure alarm
Supporting absolute date information
Supporting the electronic manufacturing information and standby
input Boolean value (seven outputs)

LCD
The LCD can display the operating parameters, operating status, alarm status, setting
parameters, and controlling parameters of the DC power, AC power, modules, and batteries.

Issue 03 (2012-11-02) Huawei Proprietary and Confidential 10


Copyright Huawei Technologies Co., Ltd.
TP48300B
Product Description 2 Product Structure

These parameters are collected by the monitoring module. You can set parameters and control
functions by pressing four buttons.

Issue 03 (2012-11-02) Huawei Proprietary and Confidential 11


Copyright Huawei Technologies Co., Ltd.
TP48300B
Product Description 3 Application Scenarios

3 Application Scenarios

The TP48300B power system can be widely used in scenarios such as indoor BTSs and
indoor central equipment room when proper rectifier modules are configured.

Application Scenarios
The TP48300B is installed on the ground of the equipment room. It can be installed next to
the wall (the distance between the wall and the cabinet is larger than 100 mm). The
TP48300B applies to the -48 V DC scenarios with power supplies lower than 16 kW. For
example:
BTS3900
Indoor BTSs such as the BTS3012
BSC
Indoor central equipment room

Figure 3-1 Application scenarios of the TP48300B

Issue 03 (2012-11-02) Huawei Proprietary and Confidential 12


Copyright Huawei Technologies Co., Ltd.
TP48300B
Product Description 3 Application Scenarios

Typical Application
The TP48300B power system, AC power supply, ATS, storage batteries, and related devices
constitutes the site power solution. Figure 3-2 shows the application of the TP48300B power
system in a typical site power solution.

Figure 3-2 TP48300B power system in a typical site power solution

Issue 03 (2012-11-02) Huawei Proprietary and Confidential 13


Copyright Huawei Technologies Co., Ltd.
TP48300B
Product Description 4 Operation and Maintenance

4 Operation and Maintenance

The maintenance designs are optimized to achieve simple and convenient maintenance.
The cabinet supports top inlet and top outlet of cables.
The cabinet supports front maintenance.
The monitoring module and rectifier module are hot-swappable. Thus, the power supply
is not interrupted during the maintenance of the monitoring module or rectifier module.
All internal modules can be removed and maintained separately.

Issue 03 (2012-11-02) Huawei Proprietary and Confidential 14


Copyright Huawei Technologies Co., Ltd.
TP48300B
Product Description 5 Technical Specifications

5 Technical Specifications

About This Chapter


This section describes the specifications for the ports, structure, power supply, EMC and
surge protection, and environment.
5.1 Port Specifications
This section describes the port specifications of the TP48300B.
5.2 Structural Specifications
This section describes the structural specifications of the TP48300B.
5.3 Electrical Specifications
This section describes the electrical features of the AC input and DC output of the TP48300B.
5.4 EMC and Surge Protection Specifications
This section describes the EMC and surge protection specifications of the TP48300B.
5.5 Environmental Specifications
This section describes the requirements for the TP48300B, such as the operating temperature,
operating humidity, transportation temperature, storage temperature, storage humidity, and
altitude.

5.1 Port Specifications


This section describes the port specifications of the TP48300B.

Table 5-1 Port specifications


Port Type Port Description

Monitoring Port RJ45 One circuit for


Communicating with the
BAM, RS232/RS485, 9600
or 19200 bit/s

Issue 03 (2012-11-02) Huawei Proprietary and Confidential 15


Copyright Huawei Technologies Co., Ltd.
TP48300B
Product Description 5 Technical Specifications

Port Type Port Description

Dry contact port Nine outputs (three standby


ports)
Electrical Port AC input MCB Three-phase 63 A AC input
MCB x 1. One reserved
MCB installation position
(interlocking design of two
MCBs)
Battery fuse port Two circuits, 160 A
LLVD 100 A x 3 (NT00 FUSE)
BLVD 32 A x 2 MCB, 10 A x 2
MCB, two reserved 63 A
MCB installation position
Installation Port Antistatic floor installation The installation holes
port support the current antistatic
installation rack.
Ground installation port The cabinet is installed on
the ground with expansion
bolts.

5.2 Structural Specifications


This section describes the structural specifications of the TP48300B.
Table 5-2 lists the structural specifications for the TP48300B power system.

Table 5-2 Structural specifications


Parameter Specification

Dimensions (width x depth x height) of the 600mm x 450mm x 1,600mm


cabinet
Color NC Huawei gray
Number of modules to be installed When use 30A PSU support 2 to 10
When use 50A PSU support 2 to 6
Weight Not heavier than 110 kg (without installed
modules)
Cabling mode Top inlet and top outlet
Maintenance mode Supporting frontal access and installation
against the wall (distance from the wall
300 mm)

Issue 03 (2012-11-02) Huawei Proprietary and Confidential 16


Copyright Huawei Technologies Co., Ltd.
TP48300B
Product Description 5 Technical Specifications

Parameter Specification

Protection level IP20

5.3 Electrical Specifications


This section describes the electrical features of the AC input and DC output of the TP48300B.

AC input
The main MCB for the AC input of the TP48300B power system provides protection against
overcurrent. Table 5-3 lists the electrical specifications of the AC input.

Table 5-3 Electrical specifications of the AC input

Parameter Specification

AC input Input voltage 90 V AC to 290 V AC phase voltage


(220 V AC by default)
Input frequency 45 Hz to 65 Hz (50 Hz by default)
Power factor Not lower than 0.99 at the rated load
Input cabling mode Three-phase four-line mode (L1, L2,
L3, and N) or single-phase mode
Three-phase four-line mode by
default
If the power supply is in
single-phase mode, connect the
three lines (L1, L2, and L3) of the
AC input MCB, and then connect
them to the L line.
Protection Overvoltage protection The system performs protection when
the single-phase input voltage
exceeds the AC overvoltage alarm
threshold (300 V by default). The
system resumes power output when
the voltage restores to 290 V AC.
Undervoltage protection The system performs protection when
the single-phase input voltage is
lower than the AC undervoltage
alarm threshold (85 V by default).
The system resumes power output
when the voltage restores to 90 V
AC.
Input overcurrent protection The main MCB for the AC input
provides protection against
overcurrent.

Issue 03 (2012-11-02) Huawei Proprietary and Confidential 17


Copyright Huawei Technologies Co., Ltd.
TP48300B
Product Description 5 Technical Specifications

Parameter Specification

Providing AC input Three-phase 63 A AC input MCB x


AC power 1, C-level lightning protection, one
distributio reserved MCB installation position
n (interlocking design of two MCBs)

DC output
Table 5-4 lists the electrical specifications for the DC power of the TP48300B power system.

Table 5-4 Electrical specifications of the DC output

Parameter Specification

DC output Output voltage range 43.2 V to 57.6 V


Rated output voltage 53.5 V
range
Maximum output power When use 30 A PSUs:
16000 W for single-phase input voltage
between 176 V AC and 290 V AC
7000 W for single-phase input voltage between
150 V AC and 175 V AC
6000 W for single-phase input voltage between
90 V AC and 150 V AC
When use 50 A PSUs:
17400 W for single-phase input voltage
between 176 V AC and 290 V AC
7200 W for single-phase input voltage between
90 V AC and 175 V AC
Protection Overvoltage protection The system generates an alarm when the output
voltage exceeds the DC overvoltage alarm
threshold (58.5 V to 60.5 V by default). In the
case of output overvoltage, the rectifier modules
are locked automatically.
Output short-circuit The system recovers after the short-circuit is
protection cleared.
Overtemperature The system can recover automatically when the
protection temperature is lower than 65C.
Providing LLVD 100 A x 3 (NT00 fuse)
DC power
distributio BLVD 32 A x 2, 10 A x 2, (two reserved 63 A MCB
n installation position)
Battery branch 160 A x 2 (fuse)

Issue 03 (2012-11-02) Huawei Proprietary and Confidential 18


Copyright Huawei Technologies Co., Ltd.
TP48300B
Product Description 5 Technical Specifications

5.4 EMC and Surge Protection Specifications


This section describes the EMC and surge protection specifications of the TP48300B.

EMC
Table 5-5 lists the EMC specifications for the TP48300B power system.

Table 5-5 EMC specifications

Item Specification

EMI CE/RE Complying with the CISPR 22/EN 55022 class A


Harmonic Complying with the IEC 61000-3-12 (the current of each
phase must be greater than 16 A)
Fluctuation Complying with the IEC 61000-3-11 (the current of each
and flicker phase must be greater than 16 A)
EMS ESD The voltage for contact discharge is 6 kV and the voltage
for air discharge is 8 kV (criterion B); the voltage for
contact discharge is 8 kV and the voltage for air discharge
is 15 kV (criterion R).
EFT The voltage at signal ports is 1 kV, and the voltage at the
power ports is 2 kV (criterion B).
RS 10 V/m (criterion A)
CS The voltage at signal ports and power ports is 10 V
(criterion A).
SURGE The voltage at the AC power ports in differential mode is
2 kV; the voltage at the AC power ports in common mode
is 4 kV (criterion B).

Safety Specification Design


The safety specification design of the TP48300B complies with the IEC 60950-1/GB 4943
and CE.

Reliability
Table 5-6 lists the reliability specifications.

Table 5-6 Specifications for reliability


Item Specification

MTBF: Mean Time Between Failure 250 thousand hours

Issue 03 (2012-11-02) Huawei Proprietary and Confidential 19


Copyright Huawei Technologies Co., Ltd.
TP48300B
Product Description 5 Technical Specifications

Surge Protection Design


Table 5-7 lists the surge protection specifications for the TP48300B power system.

Table 5-7 Surge protection specifications


Parameter Specification

Lightning protection for AC input Class C surge protection


Standard lightning discharge current: 20
kA, 8/20 us
Maximum lightning discharge current:
40 kA, 8/20 us
Lightning protection for DC output Differential mode: 10 kA, 8/20 s
Common mode: 15 kA, 8/20 s
Lightning protection for storage battery Differential mode: 500 V, Common
temperature sensor mode:1000 V
Lightning protection for temperature sensor Differential mode: 500 V, Common
mode:1000 V
Lightning protection for standby input Impact current 250A for ground earth, 8/20
Boolean value s

5.5 Environmental Specifications


This section describes the requirements for the TP48300B, such as the operating temperature,
operating humidity, transportation temperature, storage temperature, storage humidity, and
altitude.
Table 5-8 lists the environmental specifications for the TP48300B power system.

Table 5-8 Environmental specifications


Parameter Specification

Working temperature -20C to +50C (working for a short period


when the temperature is between 50C and
55C)
Working humidity 5% to 95%
Transportation temperature -40C to +70C
Storage temperature -40C to +70C
Storage humidity 5% to 95%
Altitude 0 m to 4000 m (at the altitude from 2000 m
to 4000 m, the temperature declines by 1C
for each increase of 200 m in altitude)

Issue 03 (2012-11-02) Huawei Proprietary and Confidential 20


Copyright Huawei Technologies Co., Ltd.
TP48300B
Product Description 5 Technical Specifications

Short period means a period of less than 96 hours each time, or less than 15 days in a year.

Issue 03 (2012-11-02) Huawei Proprietary and Confidential 21


Copyright Huawei Technologies Co., Ltd.
TP48300B
Product Description 6 Design Standard

6 Design Standard

This chapter describes the design standards of the TP48300B.

Table 6-1 Design standards of the TP48300B


Component Certification or Standard

TP48300B power CE, TLC, Rohs


system
Rectifier module UL, TUV, and CE
Power distribution Certified by the CE, TUV, and 3C
component

Issue 03 (2012-11-02) Huawei Proprietary and Confidential 22


Copyright Huawei Technologies Co., Ltd.
TP48300B
Product Description 7 Acronyms and Abbreviations

7 Acronyms and Abbreviations

The following table lists the acronyms and abbreviations mentioned in this document.

Table 7-1 Acronyms and abbreviations


Acronyms and Abbreviations Full Spelling

PSU Power Supply Unit


PMU Power Monitoring Unit
SPD Surge Protection Device
ATS Auto Transfer Switching
BTS Base Transceiver Station
BSC Base Station Controller
MTBF Mean Time Between Failures
OPEX Operational Expenditure
VRLA Valve Regulated Lead Acid
AGM Absorbed Glass Mat

Issue 03 (2012-11-02) Huawei Proprietary and Confidential 23


Copyright Huawei Technologies Co., Ltd.

You might also like