You are on page 1of 75

Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery

Brief Introduction for Automated Relay Testing


(Relay type DUOBIAS-M)
Kamin Dave
Manager Sales & Applications
South Asia & Middle East
DOBLE ENGINEERING COMPANY
Protection Relay Testing:

Testing of Differential Protection


Relay type DUOBIAS-M

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: DUOBIAS-M
Two/Three Winding Differential Protection
relays
Inbuilt IDMTL & Inst. O/C function for backup
Protection
Low Impedance Restricted Earth Fault
Protection
Automatic calculation for TAP values based on
CTR
Settings for Transformer & CT vector group
compensations
2nd Harmonic content setting during inrush
period due to point on wave switching
DFT (Independent or Cross Blocking)

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: DUOBIAS-M
MAKE : REYROLLE
MODEL : DUOBIAS-M
Relay Settings:
Differential Element:
MVA = 20
VWDG1 = 110KV
VWDG2 = 11KV
TRCON = DYn11.
CTCON = YY
ID> = 0.2
Bias Slope Limit = 4.0PU
ID>> = 8.0PU
m1 = 20% (0.2pu)
(2f0) / I(f0) = 20.0%
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: DUOBIAS-M
MAKE : REYROLLE
MODEL : DUOBIAS-M
Location : 220KV Kavoor SS, KPTCL
Relay Settings:
Differential Element:
CTR1 = 200
CTR2 = 1200
W1 = 1.9057
W2 = 1.14345
In = 1A
Star winding is earthed
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: DUOBIAS-M
FLC on TR Primary side:
IFLC = (20*1000) / (1.7325*110)
= 104.94 Ampere
FLC on TR Secondary side:
IFLC = (20*1000) / (1.7325*11)
= 1049.45 Ampere
CF1 = (1*104.94) / (200*1) = 0.699
W1 = (1 / CF1) = (1/0.699) = 1.9057
CF2 = (1*1049.45) / (1200*1) = 0.874
W2 = (1/CF2) = (1/0.874) = 1.14345

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Setting: REYDISP

Diff Settings

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Setting: REYDISP

CT Ratio for WDG1 & WDG2

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Characteristic: Dual Slope

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Characteristic on Settings:

m2
m1=20%

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Test Equipment
Make : DOBLE
Model : F6150
Software
F6TesT Version 2.19-1064

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Test Circuit:
Source Configurations:
Six current sources

Winding 1 currents

Winding 2 currents

I1
IA
DUOBIAS
IB I2

IC I3

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Tests conducted:
Pickup test for Winding1
Pickup test for winding2
Slope Characteristic test
2nd Harmonic test

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Winding1 Pickup Test
Use RAMP Module

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Winding Pickup Test:
Pickup Test for Winding1 (WDG1):-
Ipickup = (ID)*CF1
= (0.2)*0.524
= 0.11A

Pickup Test for Winding2 (WDG2):-


Ipickup = (ID)*CF2
= (0.2)*0.944
= 0.17A

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
How to Create Test Plan in
Software???

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Right click on Mouse & Click on Append
to Create new location in location level

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Right click on Mouse & Click on Append
to Create new relay in Relay level

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Right click on Mouse & Click on Append
to add New Testplan in Testplan level

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Right click on Mouse & Click on Append
to add New Testplan in Testplan level

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Click on Test Type
& select Ramp module

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Double click on
Test name & create
New test definition
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Click on Pulldown arrow &
Select 6 Currents (Right bank)

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Click on Yes

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Now, it is showing
6 Current sources for test

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Pickup Test: WDG1
Select Trigger Open to Close

Pickup value

WDG1 current sources

Expected value = 0.1A


Actual Test value = 0.11A

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Pickup Test: WDG1

Save & Close module

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Winding2 Pickup Test
Use RAMP Module

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Right click on Mouse & Click on Append
to add New Testplan in Testplan level

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Click on Test Type
& select Ramp module

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Double click on
Test name & create
New test definition
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Click on Pulldown arrow &
Select 6 Currents (Right bank)

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Click on Pulldown arrow &
Select 6 Currents (Right bank)

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Click on Yes

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Now, it is showing
6 Current sources for test

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Pickup Test: WDG2
Select Trigger Open to Close

Pickup value

WDG2 current sources

Expected value = 0.17A


Actual Test value = 0.18A

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Slope Characteristic Test
Use DiffChar Module

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Slope Characteristic Test:

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Slope Characteristic Test:
Vector Compensation

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Slope Characteristic Test:

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Slope Characteristic Test:
Vector Compensation

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Slope Characteristic Test:
Vector Compensation
YD11

0o +30o

YDY0 YD1

0o 0o
Relay

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
How to create testplan???

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Click on Add button

Select Differential Function, enter Function name


And Click on Next button

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Bias current Formula:
Ibias = (IP+IS) / 2

Select Bias Formula from list

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Amplitude Compensation

DYn11

YDY0 YD1

Enter YDY0 & YD1 R

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Click on Modify button

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Enter Pickup value

How to Adjust
Slope?

SLP2

SLP1=20%

Enter Slope SLP1 = 20% & SLP2 based on relay setting


Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Click on Close button
After setting Slope curve

Bias current Formula:


Ibias = (IP+IS) / 2

Select Bias current (Ibias) formula from list

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Click on Append button to
Create new test module

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Select DiffChar module

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Select relay settings from list

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Select Test elements

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Enter Max test current 15A

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Select Trigger Open to Close

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Select test points for test & click on Add Point to List
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Blue line shows
Expected curve

White line shows


Actual results on
Selected points

Test results

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Export report in PDF, MS Word, Text format

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Second Harmonics Test
Use DATC 6.38 Module

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
%2nd Harmonics are
more during TR
Energization

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
2nd Harmonic Test : Test Method

50Hz +100Hz
Combine signal

I1
IA
DUOBIAS
IB I2

IC I3

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
How to Set Harmonics in
DATC 6.38 Module??

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Select 2nd Harmonic

Enter 2nd Harmonic


Content 18% in
All three phases

Click on Harmonic
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Click on
Time Configuration

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Select contact status
OC

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Enter trip time value

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Click on
Oscillogram

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Click on Start Transient button

18% 2nd Harmonics in all three phases

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Harmonic Analysis bar
Shows Fundamental
Current is 100%

Harmonic Analysis bar


Shows % of 2nd Harmonic
is 18%

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
2nd Harmonic Test : Trip/Block

Relay issued
Trip command
Because injected value
Of 2nd harmonic
Content is less than
Set value

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Select 2nd Harmonic

Enter 2nd Harmonic


Content 22% in
All three phases

Click on Harmonic
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Click on Oscillogram

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
2nd Harmonic Test : Trip/Block

Start Transient

22% 2nd Harmonics in all three phases

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
2nd Harmonic Test : Trip/Block

Relay Issued Trip command when 2nd Harmonic components


(18%) Less than set value (20%)

Relay blocked trip command when 2nd Harmonic components


(22%) more than set value (20%)

Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery