Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: DUOBIAS-M
Two/Three Winding Differential Protection
relays
Inbuilt IDMTL & Inst. O/C function for backup
Protection
Low Impedance Restricted Earth Fault
Protection
Automatic calculation for TAP values based on
CTR
Settings for Transformer & CT vector group
compensations
2nd Harmonic content setting during inrush
period due to point on wave switching
DFT (Independent or Cross Blocking)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: DUOBIAS-M
MAKE : REYROLLE
MODEL : DUOBIAS-M
Relay Settings:
Differential Element:
MVA = 20
VWDG1 = 110KV
VWDG2 = 11KV
TRCON = DYn11.
CTCON = YY
ID> = 0.2
Bias Slope Limit = 4.0PU
ID>> = 8.0PU
m1 = 20% (0.2pu)
(2f0) / I(f0) = 20.0%
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: DUOBIAS-M
MAKE : REYROLLE
MODEL : DUOBIAS-M
Location : 220KV Kavoor SS, KPTCL
Relay Settings:
Differential Element:
CTR1 = 200
CTR2 = 1200
W1 = 1.9057
W2 = 1.14345
In = 1A
Star winding is earthed
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: DUOBIAS-M
FLC on TR Primary side:
IFLC = (20*1000) / (1.7325*110)
= 104.94 Ampere
FLC on TR Secondary side:
IFLC = (20*1000) / (1.7325*11)
= 1049.45 Ampere
CF1 = (1*104.94) / (200*1) = 0.699
W1 = (1 / CF1) = (1/0.699) = 1.9057
CF2 = (1*1049.45) / (1200*1) = 0.874
W2 = (1/CF2) = (1/0.874) = 1.14345
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Setting: REYDISP
Diff Settings
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Setting: REYDISP
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Characteristic: Dual Slope
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Characteristic on Settings:
m2
m1=20%
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Test Equipment
Make : DOBLE
Model : F6150
Software
F6TesT Version 2.19-1064
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Test Circuit:
Source Configurations:
Six current sources
Winding 1 currents
Winding 2 currents
I1
IA
DUOBIAS
IB I2
IC I3
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Tests conducted:
Pickup test for Winding1
Pickup test for winding2
Slope Characteristic test
2nd Harmonic test
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Winding1 Pickup Test
Use RAMP Module
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Winding Pickup Test:
Pickup Test for Winding1 (WDG1):-
Ipickup = (ID)*CF1
= (0.2)*0.524
= 0.11A
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
How to Create Test Plan in
Software???
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Right click on Mouse & Click on Append
to Create new location in location level
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Right click on Mouse & Click on Append
to Create new relay in Relay level
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Right click on Mouse & Click on Append
to add New Testplan in Testplan level
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Right click on Mouse & Click on Append
to add New Testplan in Testplan level
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Click on Test Type
& select Ramp module
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Double click on
Test name & create
New test definition
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Click on Pulldown arrow &
Select 6 Currents (Right bank)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Click on Yes
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Now, it is showing
6 Current sources for test
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Pickup Test: WDG1
Select Trigger Open to Close
Pickup value
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Pickup Test: WDG1
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Winding2 Pickup Test
Use RAMP Module
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Right click on Mouse & Click on Append
to add New Testplan in Testplan level
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Click on Test Type
& select Ramp module
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Double click on
Test name & create
New test definition
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Click on Pulldown arrow &
Select 6 Currents (Right bank)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Click on Pulldown arrow &
Select 6 Currents (Right bank)
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Click on Yes
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Now, it is showing
6 Current sources for test
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Pickup Test: WDG2
Select Trigger Open to Close
Pickup value
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Slope Characteristic Test
Use DiffChar Module
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Slope Characteristic Test:
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Slope Characteristic Test:
Vector Compensation
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Slope Characteristic Test:
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Slope Characteristic Test:
Vector Compensation
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Slope Characteristic Test:
Vector Compensation
YD11
0o +30o
YDY0 YD1
0o 0o
Relay
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
How to create testplan???
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Click on Add button
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Bias current Formula:
Ibias = (IP+IS) / 2
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Amplitude Compensation
DYn11
YDY0 YD1
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Click on Modify button
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Enter Pickup value
How to Adjust
Slope?
SLP2
SLP1=20%
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Click on Append button to
Create new test module
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Select DiffChar module
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Select relay settings from list
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Select Test elements
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Enter Max test current 15A
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Select Trigger Open to Close
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Select test points for test & click on Add Point to List
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Blue line shows
Expected curve
Test results
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Export report in PDF, MS Word, Text format
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Second Harmonics Test
Use DATC 6.38 Module
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
%2nd Harmonics are
more during TR
Energization
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
2nd Harmonic Test : Test Method
50Hz +100Hz
Combine signal
I1
IA
DUOBIAS
IB I2
IC I3
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
How to Set Harmonics in
DATC 6.38 Module??
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Select 2nd Harmonic
Click on Harmonic
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Click on
Time Configuration
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Select contact status
OC
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Enter trip time value
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Click on
Oscillogram
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Click on Start Transient button
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Harmonic Analysis bar
Shows Fundamental
Current is 100%
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
2nd Harmonic Test : Trip/Block
Relay issued
Trip command
Because injected value
Of 2nd harmonic
Content is less than
Set value
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Select 2nd Harmonic
Click on Harmonic
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
Click on Oscillogram
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
2nd Harmonic Test : Trip/Block
Start Transient
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
2nd Harmonic Test : Trip/Block
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery
DOBLE ENGINEERING COMPANY
305-SAKAR, O.P. ROAD
NR. ABS TOWER
VADODARA-390 015
INDIA. Tel:- +91 265 655 77 15
EMAIL ID:- kdave@doble.com
Website:- www.doble.com
Knowledge Is Power SM
Apparatus Maintenance and Power Management
for Energy Delivery