N30U DIGITAL PANEL METER

Measurement: temperature, resistance, standard signals.


3-colour display (14 mm high), programmable in 3 ranges
FeATUReS: of the measured value.
Meter programming from keyboard or through the RS-485
LPConfig interface by means of the free LPConfig program.
Program 4 alarm outputs with signalling on LED diodes,
working in 6 dierent modes.
MOD Conversion of any measured value into an analog signal
BUS RTC 0/4...20 mA or 0...10 V.
21 points
Storage of minimal and maximal values for all measured
charact. Password
protection quantities.
Supply of object transducers (ver. N30U-1XXXXXXX).
21-point individual characteristic for the measured value.
IP65

Example of Application
INPUTS: Measurement and
Alarms visualization of analog
RS485, standard signals: Pt100,
Modbus TC, 20 mA, 60 mV, 10 V.
Wireless transmission
SM7 modules
HMI panel Measured parameters
N30U
-10..10 -20..20 digital
are transmitted to the
V mA meter HMI operator panel
through radio modules.
RS485/USB
converter PC Computer/programming
60 mV (e.g. PD10) using the LPConfig
Temperature program
Pt100 probe
oUTPUTS: Shunt

0 .. 20 0..10
mA V Input
Input kind Maximal measuring range Class Additional error
Pt100 - due to automatic com-
Pt500 -205...855C (-200...850C) pensation of the reference
junction temperature
Pt1000 1C
2x 400 0...410 (0...400 )
4000 0...4010 (0...4000 ) - due to automatic com-
Thermocouple of J type -200..1200 C (-100..1200 C) pensation of the cable resi-
Thermocouple of K type -200..1370 C (-100..1370 C) stance for thermoresistors
RS Thermocouple of N type -200..1300 C (-100..1300 C) 0.1 0,5C
485 Thermocouple of E type -200..1000 C (-100..1000 C)
- due to automatic com-
Thermocouple of R type -50..1768 C (-50..1760 C) pensation of the cables for
GAlVANIC Thermocouple of S type -50..1768 C (-50..1760 C) resistance measurement
ISolATIoN: Voltage input 0...10 V -13...13 V (-10...10 V) 0,2
Current input -24...24 mA (-20...20 mA)
- from temperature changes
Voltage input -10...63 mV (0...60 mV) 100 % of the class / 10 K
Current time 00.00...23.59 0.5 sec./ 24h

Outputs
RS Output kind Properties Remarks
Supply 485 2 x relays, voltageless NOC contacts
Relay load-carrying capacity 250 V a.c./ 0.5 A a.c.
Export department: output 2 x relays, voltageless switched contacts
+48 68 45 75 302 / 321 / load-carrying capacity 250 V a.c./ 0.5 A a.c.
276 / 386 / 233
current programmable 0/4..20mA, Error of analog output: 0.2% of the set range
Analog
Fax: +48 68 32 54 091 load resistance 500 Additional error from temperature changes: 50% of the
output
e-mail: export@lumel.com.pl voltage programmable 0...10 V load resistance 500 class/10K
OC output typu OC, passive npn, 30 V d.c./30 mA Voltageless output
LUMEL S.A. Auxiliary
ul. Subicka 1 24 V d.c./ 30mA only for meter version: N30U-1XXXXXXX
supply
65-127 Zielona Gra
POLAND Digital Interface
WWW.LUMEL.COM.PL Interface type transmission protocol modes baud rates
RS-485 MODBUS RTU 8N2, 8E1, 8O1, 8N1 4.8, 9.6, 19.2, 38.4, 57.6, 115.2 kbit/s
N30U DIGITAL PANEL METER
External Features
5 digit LED display -
three-color display (colour changes depending on
Readout field indication range -19999..99999
displayed value): red, green, orange
digit height: 14 mm
Weight < 0.2 kg See Also:
Dimensions 96 48 93 mm Panel cut-out: 92+0,6 45+0,6 mm
Protection grade (acc. to EN 60529) from frontal side: IP65 from rear side: IP 10
Rated Operating Conditions
Supply voltage 85...253 V a.c. (40...400 Hz) or d.c., power consumption < 6 VA
Free LPConfig
20...40 V a.c. (40...400 Hz), 20...60 V d.c. software for easy
Temperature ambient: -25...23...55C storage: -30...70C programming of
Relative humidity 25...95% condensation inadmissible LUMEL's products.
Available on our
Operating position any
website
External magnetic field 0...400 A/m

Safety And Compatibility Requirements


Noise immunity acc. to EN 61000-6-2
Electromagnetic compatibility
Noise emissions acc. to EN 61000-6-4
Isolation between circuits basic
Pollution grade 2
Installation category III
acc. to EN 61010-1
for the supply circuit: 300 V
Maximal phase-to-earth operating voltage
for remaining circuits: 50 V
Altitude above sea level < 2000 m KD7 recorder with
MODBUS master
Connection Diagrams protocol for recording
data measured by
N30U.

Shunts for
measurement DC
Supply Supply Supply current from 5A up
to 15 kA. For more
details see our
ANALOG METERS
Fig. 1 Description of signals on connection Fig. 2 Ways of the meter connection.
catalogue.
strips.
OUR OFFER
Ordering
Table 1. Ordering codes: Table 2. Codes of highlighted unit:
N30U - X X XX XX X X Code Unit Code Unit Code Unit
Supply: 00 lack of unit 20 kVAh 40 szt.
85...253 V a.c./d.c. 1 01 V 21 MVAh 41 imp
20...40 V a.c., 20...60 V d.c. 2 02 A 22 Hz 42 rps
Additional outputs: 03 mV 23 kHz 43 m/s
lack 0
04 kV 24 44 l/s www.lumel.com.pl
OC output, RS-485, analog outputs 1
05 mA 25 k 45 obroty/min For more information
OC output, RS-485, analog outputs
switched-over relay outputs 2 06 kA 26 C 46 rpm about LUMEL's
Unit: 07 W 27 F 47 mm/min products please visit
unit code acc. to the table 2 XX 08 kW 28 K 48 m/min our website:
Version: 09 MW 29 % 49 l/min www.lumel.com.pl
standard 00
10 var 30 %RH 50 m3/min
custom-made* XX
11 kvar 31 pH 51 pcs/h
Language:
Polish P 12 Mvar 32 kg 52 m/h Export department:
English E 13 VA 33 bar 53 km/h +48 68 45 75 302 / 321 /
other* X 14 kVA 34 m 54 m3/h 276 / 386 / 233
Acceptance tests: 15 MVA 35 l 55 kg/h
without extra requirements 0 Fax: +48 68 32 54 091
16 kWh 36 s 56 l/h e-mail: export@lumel.com.pl
with an extra quality inspection certificate 1
17 MWh 37 h
acc. to customers request* X
18 kvarh 38 m3 XX on order*
Order example: The code N30U - 1 0 26 00 E 0 means LUMEL S.A.
19 Mvarh 39 obroty ul. Subicka 1
N30U - programmable N30U digital panel meter
1 - supply: 85...253 V a.c./d.c. 65-127 Zielona Gra
0 - lack of additional outputs POLAND
26 - unit "C" acc. to tabel 2 * - after agreeing with the manufacturer
00 - standard option WWW.LUMEL.COM.PL
E - English language
0 - without extra requirements
N30U-19A/2