Chiller selection Software

Version 4.53 (16-JAN-2013) - Copyright 2000-2013, Carrier Corp.

* Project Trial
Date 5/19/2017 11:33:28 AM
Location Lahore
Company name
Contact name
CARRIER reference

* Product 30HXC175-PH3
Unit performance in accordance with
EUROVENT
Range 30HXC Phase3 (Standard)

* List of the options selected :


Option 92 (Compressor suction shut off valve)

Net Cooling Cap. 543 kW


Unit absorbed power 144 kW
Compres. Input power 140 kW
Evaporator Pump power 1.98 kW
C.O.P. 3.76
No of capacity steps 6
Minimum step 21 %
Refrigerant R134a
Expansion valve EXV

* Evaporator
Fluid Water
Leaving T. 7 C
Delta T. 5 K
Entering T. 12 C
Flow rate 26 L/s
Evaporator pressure drop 47 kPa
Fouling factor 0.088 m-K/kW
Max operating pressure 1000 kPa

* Condenser
Fluid Water
Entering T. 32.2 C
Delta T. 5.6 K
Leaving T. 37.8 C
Flow rate 28.9 L/s
Pressure drop 39 kPa
Fouling factor 0.176 m-K/kW
Max operating pressure 1000 kPa
T.H.R. 680 kW

* No of compressors 2
Compressor type screw
Compressor motor speed 49 r/s
Starter type WYE/DELTA
* Volts/Phases/Hertz 400-3-50
Power Factor (at max power) 0.87
Maximum current drawn 312 A (U nom.)
Maximum starting current 382 A
Voltage limits 360/440 V
* Operating weight 3083.0 kg
Refrigerant charge 104 kg
Length/Width/Height 3275 mm
980 mm
1940.5 mm
* Part Load
NON EUROVENT COMPLIANCE (pumps not included)
-1- -2- -3- -4- -5- -6- -7-
100 32.2 543 100 144 100 3.76
86 29.9 470 86 129 92 3.64
71 27.5 399 73 108 77 3.68
50 24.1 293 54 64 45.7 4.55
36 21.8 211 38.8 48.4 34.4 4.37
21 19.4 174 31.9 37.9 26.9 4.6
-1- Theoretical Unloading step (%)
-2- Entering Condenser Temperature (C)
-3- Gross capacity (kW)
-4- (%)
-5- Unit absorbed power (kW)
-6- (%)
-7- COP

* Acoustic power (dB ref. 1e-12 W) (Full load)


Octave band (Hz)
125 250 500 1K 2K 4K 8K Global
Lw 79 84 83 96 97 91 82 100
Lw(A) 63 75 80 96 98 92 81 101
Global Acoustic power dB(A), according to EUROVENT standard = 101

Average acoustic pressure (dB ref. 2e-5 Pa). Distance 5 m


Octave band (Hz)
125 250 500 1K 2K 4K 8K Global
Lp 52 57 56 69 70 64 55 74
Lp(A) 36.1 48.6 53 69 71 65 54 74
Global pressure level in dB(A) = 74

Estimated average sound pressure Lp at a given distance on a reflective surface in a free field environment.
Estimated Sound Power levels given above are assumed to originate at the acoustic center of the chiller.

* FULL-LOAD calculation. The EUROVENT standard defines that :


1 The Net Unit capacity is the Gross Unit capacity corrected
for heat generated by the pump against the internal pressure
drop in the unit.
2 The Unit kW input includes Compressor, Fan (when Fan), Pump
(when Hydronic Module), and the proportional power input of the
pumps for ensuring the transport of the water against the internal
flow resistance of the unit.
3 The Unit COP is the Net Unit capacity divided by the Unit kW
input.

* PART-LOAD calculation :
The calculation is NOT based upon EUROVENT. This means that:
1 The Unit capacity is the Gross Unit capacity.
2 The Unit kW input includes Compressor and Fan (when Fan).
3 The Unit COP is the Unit capacity divided by the Unit kW input.

*Tolerance at full-load in accordance with EUROVENT :


Cooling or heating capacity : 5%
Effective power input : 5%
Water pressure drop : 15%
A-weighted sound pressure level : 3dB(A)

*Tolerance of variation on the C.O.P. at part-load in accordance


with EUROVENT :
15.35 - 0.07 * step + 830 / (delta_T_at_full-load * step)
Example : step=50%, delta T at full-load=5K :
15.35 - 0.07 * 50 + 830 / (5 * 50) = 15.17%

* EUROVENT standards :
EN12055, EN255, ISO3744, Eurovent 8/1, ISO9614-1