You are on page 1of 6

Power

Generation

Diesel Powered
Generating Sets
410 kW - 500 kW 60 Hz
QSX15 Series Engine

Typical model with optional sub-base


fuel tank and circuit breaker
Standard Genset Features
Single Source Responsibility Alternator PowerCommand Control System
Design, manufacturer and test of all Brushless Group made machine PCC II
components and accessories are Close voltage regulation Microprocessor control
made by Cummins Power Rotor and exciter impregnated with Integrates governor and voltage
Generation and Cummins companies oil and acid resisting resin regulation systems
International Integrity
12 lead reconnectable Superior alternator and genset
Assurance and strength of a
Exceptional short circuit capability protection system
worldwide, world class corporation
Low waveform distortion with non Accurate battery monitoring system
linear loads Totally reliable and proven system
Global Backing CE Compliant
24 hour spares and service support Ratings
in 72 countries All kW Power ratings based on a 40C
ambient temperature reference
Single Source Warranty
Complete genset covered by Chassis
Cummins Power Generation Built-in anti-vibration system
comprehensive warranty Bonded rubber units tted as standard
BSI
eliminates need for rubber mats or
Packaged Self-Contained Units
RM
REG

spring mountings NATIONAL


ACCREDITATION
Units with built in antivibration
FI

ST OF CERTIFICATION
I

ERED BODIES
systems with provision for base fuel Low Emissions
tank and other accessories
Integral cooling systems which Quality Assurance
Registered Firm Certicate Number FM509 in accordance with:
deliver low NOx, CO, HC, PM and BS EN ISO 9001
Cummins Engine SO2 exhaust emissions Quality Assurance Schedule 3420/1
Heavy duty 4 cycle water cooled
engine One
Sourc
e
ernator
Electronic governor control Alt
Co
Engine

Cooling System
ntrols

40C cooling package (50C option)


en
G

e r a ti n g S e
t

Ready Filled
One
Every set comes lled with lube oil Name

and anti-freeze Cummins Power Generation, Cummins Engines and


Newage Alternators are all part of the same group

60 Hz Ratings
Model Prime Model Standby Engine
Prime kW (kVA) Standby kW (kVA) Model
410 DFEJ 410 (513) 450 DFEJ 450 (563) QSX15G9
455 DFEK 455 (569) 500 DFEK 500 (625) QSX15G9

A Single Source for all Power System Solutions


Specications May Change Without Notice 01/02 CPG QSX15/C/60
Specifications

Generator Set Performance Generator Set Options


Voltage Regulation Waveform Engine
Maintains voltage output to within 1.0%. Total harmonic distortion open circuit voltage o Heavy duty air cleaner
At any power factor between 0.8 lagging and waveform in the order of 1.5%. Three-phase o Coolant heater and thermostat
unity. balanced load in the order of 5.0%. o Tool kit
At any variations from No load to Full load. Telephone Inuence Factor (TIF) o Lead acid batteries, cable and tted tray
At any variations from Cold to Hot. TIF better than 50. o NiCad batteries
At speed droop variations up to 4.5%. THF to BS4999 Part 40 better than 2%. o Sump drain pump
Frequency Regulation Alternator Temperature Rise o Oil and water drain taps
Isochronous under varying loads from no Class H insulation. Temperature rise up to o CE Compliance (guarding)
load to 100% full load. 125C permitted. o Exhaust temperature monitoring
Random Frequency Variation Radio Interference Cooling
Will not exceed 0.25% of its mean value for In compliance with BS800 and VDE levels o Oil temperature indication
constant loads no load to full load. G and N. Alternator
o Anti-Condensation heater
Engine o Thermistors
o PMG Exciter and MX321 AVR
Cummins QSX15G9 direct injection engines. Fuel System
Six-cylinder, in-line. 14.9 litres. 24 volt fail safe fuel actuator. Spin-on Exhaust System
element fuel lters. Cummins HPI - TP fuel o Industrial type silencer
Type o Residential type silencer
Water cooled, four cycle, turbo charged and injection system with integral electronic
governor. Dual exible fuel lines and o Length of exible exhaust and bellows
aftercooled.
connectors. Fuel/water separator. Fuel System
Construction o Sub-base tanks
Four valves per cylinder, forged steel Filters
Dry element air lters with restriction o Hand fuel transfer pump
crankshaft and connecting rods, cast iron
indicator and spin-on combination element o Automatic fuel transfer pump
block, replaceable wet liners.
oil lter with full ow and bypass lteration. o Free-standing 450, 900 and 1350 litre
Starting Spin on corrosion resistor lter. fuel tanks with stand
24 volt negative earth. Battery charging o Fuel tank level switch
35 amp alternator. Cranking current Cooling
40C radiator as standard with 50C ambient o High fuel level warning
900 amps at 0C. o Low fuel level warning
as option.
o Low fuel level shutdown
Generator Set
Alternator o Silenced enclosures
Type Exciter o Super silenced enclosures
Brushless, single bearing, revolving eld, Triple dipped in moisture, oil and acid Control Panel
4-pole, drip proof, screen protected. resisting polyester varnish and coated with o See separate list on Control Panel pages
Class H insulation. anti-tracking varnish. o 3 or 4 pole circuit breaker
Enclosed to IP22 (NEMA 1) standard. Sealed solid state automatic voltage o Battery charger 5 amp or 10 amp
IC 01 cooling system. regulator self-exciting, self-regulating. o Cable entrance box
Fully interconnected damper winding. Output windings with 2/3 pitch for improved
AC exciter and rotating rectier unit. harmonics and paralleling ability.
Epoxy coated stator winding. Close coupled engine/alternator for perfect
Rotor and exciter impregnated with tropical alignment.
grade insulating oil and acid resisting
polyester resin. Dynamically balanced rotor
to BS5625 grade 2.5.
Sealed for life bearings.
Layer wound mechanically wedged rotor.

Compliance Standards Chassis


To BS4999/5000 pt 99, Fabricated and welded steel chassis
VDE 0530, UTE5100, Built-in anti-vibration mountings
NEMA MG1-22, CEMA, Optional sub-base fuel tank with eight hour
IEC 34, CSA A22.2, capacity, dual exible fuel lines, dial type
AS1359, BSS5514, fuel gauge and drain bung
ISO 3046, ISO 8528 Finish
Etch undercoated and nished in high gloss
durable green
General
Complete set of operating and instruction
manuals

Specications May Change Without Notice 01/02 CPG QSX15/C/60


PowerCommand
Digital
Generator Set
Control
PCC II

Operator Panel Features


Emergency stop switch
Indicating lamps for remote start, not in
auto, common shutdown, and common
warning
Fault reset switch
Panel lamp/lamp test switch
Exercise switch and indicating lamp
Manual run/stop switch
Off/Manual/Auto mode select switch
Graphical display panel with pushbutton
switches capable of displaying up to 9
lines of data approximately 26 characters
wide, as well as graphical characters
Analog AC metering panel for Major Control Features Generator Set Output Frequency
simultaneous monitoring of 3-phase AC Generator Set Power Output
Include: Generator Set kWh Power Output
voltage and current, kW, powerfactor, and

frequency. Voltage, current and kW are Digital full authority electronic engine Digital Synchroscope
scaled in % of nominal values, and all controls for Cummins HPI-PT fuel system, Engine Starting Battery Voltage
values are color coded to indicate normal, including engine monitoring and Engine Lube Oil Pressure
warning, and abnormal operating protection, and governing. These Engine Coolant Temperature
conditions functions are integrated with voltage Engine Coolant Pressure
Single membrane front panel with regulation, synchronizing, and load Engine Fuel Rail Temperature and
enclosure rated NEMA 3R/IP53 sharing controls, including import/export Pressure
controls for paralleling with an innite Engine Fuel Input and Output
(utility/mains) bus Temperature
Control Functions AmpSentry Protection for true Intake Manifold Temperature and
Isochronous governing alternator overcurrent protection Pressure
3-phase sensing voltage regulation with Analog and Digital AC Output Metering Engine Fuel Consumption
single and three phase fault current Battery Monitoring System to sense and Ambient Air Pressure
regulation warn against a weak battery condition Crankcase Blowby Flow
AC output protection including over/under Digital Alarm and Status Message Display Aftercooler Inlet Coolant Temperature
voltage, over/under frequency, Generator set Monitoring: Displays status Engine Exhaust Temperature (optional)
overcurrent, short circuit, and over load of all critical engine and alternator
(kW) generator set functions
Smart Starting Control System: Integrated Internal Control Functions
Engine control and monitoring system
with displays for oil pressure, oil fuel ramping to limit black smoke and
temperature, engine coolant temperature, frequency overshoot, in addition to General Functions
engine speed, battery voltage and other optimized cold weather starting
Advanced Serviceability using InPower, a
Emergency Start Mode
values Non-Emergency Start Mode
Generator set protection system including PC-based software service tool
PowerCommand Communications
Sleep Mode
AC output protection alarms, engine Data Logging
pressure, temperature warning, Network Capability (optional)
Fault Simulation Mode
Shutdown functions, low coolant Built In Test
temperature, low coolant level, low fuel Control Switches and First Start Sensor System
level, failure to crank, failure to start and Functions Synchronizer
overspeed Load Demand Mode
Operator adjustments for time delay, OFF/MANUAL/AUTO Mode Control
Switch
Load Govern Mode
start/stop, engine speed, and overspeed Manual (Semi-Automatic) Parallel Mode
Technician setup menu MANUAL RUN/STOP Control Switch and
Status and data display functions Indicating LED
including engine operating hours, kW EXERCISE Control Switch and Indicating Engine Control
hour productions, AC metering functions LED Engine Starting
and fault history PANEL LAMP/LAMP TEST Control Cycle Cranking
Switch Programmable Idle Speed Control
EMERGENCY STOP Control Switch Time Delay Start and Stop (cooldown)
Control Options Graphical Operator Panel
Alternator temperature alarms Engine Governing
Audible alarm module Graphical Display Panel
Automatic mains failure control
Isochronous Governing
Generator Set Hardware Data Droop Governing
Control anti-condensation heater Data Logs
Digital paralleling controls
Temperature Dynamics
Adjustment History Idle Mode
Echelon LonWorks interface Fault History
Generator running relay contacts
Isochronous (kW) Load Sharing Control
Load Prole Data
Key-type mode control switch Generator Set Output Voltage
Generator Set Output Current

Specications May Change Without Notice 01/02 CPG QSX15/C/60


Low Oil Level warning Verify functional operation of the
Low coolant temperature (warning) control by simulating fault conditions
Low Fuel Daytank (warning, within the control, and manipulating
external input signal) input parameters in the control
High coolant temperature (shutdown) Conveniently adjust operating
parameters of the generator set, and
Control Interface protective equipment set points
Generate standard reports describing
Input signals to the PowerCommand
generator set settings, test report
control include:
data
Remote Start signal Establish and maintain passwords for
Remote Emergency Stop
users and system administrators.
Congurable Customer Inputs
InPower also offers the ability to
Low Main Fuel Level warning
bypass passwords (by qualied user)
Remote Alarm Reset
in the event that a password is lost or
Load Demand Stop
forgotten
Utility Parallel (Load Govern) Mode Allows the active testing of all
command
warning and shutdown devices.
Output signals from the control include: Provide control simulations to allow
Alternator Control Generator Set Running signal testing of the generator set or transfer
Digital Output Voltage Regulation Generator Set Common Shutdown switch without operation of the device
Torque-Matched Volts/Hz Overload signal Allows operation of the engine with
Control Load Shed signal the excitation switched off for some
Fault Current Regulation Ready to Load signal service modes
Isochronous (kVar) Load Sharing Modem Control signal
Control Network connections include: PowerCommand for Windows
Droop (kVar) Load Sharing Control Serial Interface. Features include:
Echelon LonWorks Interface (Option) Ability to locally or remotely monitor
Protective Functions Paralleling Breaker Interface on-site power systems from a
Ground Fault Warning (option- personal computer
600VAC class generator sets) Certifications Data logging
Congurable Alarm and Status Inputs PowerCommand meets or exceeds the
Noties user of alarm conditions in
Breaker Fail To Close and Breaker requirements of the following codes and the power system, and forwards
Auxiliary Contact Warning or standards: alarm conditions to a paging system
Shutdown NFPA110 for level 1 systems. when needed
Breaker Fail To Open Warning UL508 Listed, Category NIWT7 for
Provides multiple level security
Bus or Generator Set PT Input US and Canada. access
Calibration Error CSA C282-M1999 Compliance
Stores system data in encrypted
Emergency Stop CSA 22.2 No. 14 M91 Industrial secure formats
Controls.
Allows easy report generation
AmpSentry ISO 8528-4: 1993 Compliance,
Over Current Warning Controls and Switchgear
Options and Accessories
Over Current Shutdown NFPA99: Standard for Health Care Key-type Mode Select Switch
Short Circuit Shutdown Facilities Ground Fault Alarm Module
High AC Voltage Shutdown EC Marking Semi-Automatic Paralleling
Low AC Voltage Shutdown EN 50081-1 Residential, commercial, Isolated Bus Paralleling
Under Frequency Shutdown light industrial Full Function Paralleling
Over Frequency Shutdown/Warning EN 50081-2 Industrial Exhaust Temperature Monitoring
Over Load (kW) Warning EN 50082-1 Residential, commercial, Alternator Temperature Monitoring
Reverse Power Shutdown light industrial Digital Remote Annunciator
Sync Check EN 50082-2 Industrial Digital Output Relay Module
Fail To Synchronize Warning or ISO 7637, pulses #2b, 4; DC supply
Shutdown surge voltage test
Phase Sequence Sensing Shutdown Mil Std 202C, Method 101 Salt Fog
Reverse Var Shutdown test
Breaker Fail to Close ANSI C62.41 Surge Withstand
High Alternator Temperature (Option) Mil Std 461
IEC 801.2, 3, 4, 5
Engine Protection IEEE 587
Overspeed Shutdown
Low Lube Oil Pressure Shutdown Software
Low Lube Oil Pressure Warning
High Lube Oil Temperature
Warning/Shutdown InPower
High Coolant Temperature Shutdown Software Functions:
High Coolant Temperature Warning View active and inactive faults, time
Low Coolant Pressure stamp for last fault, number of times
Warning/Shutdown each fault has occurred. Clear
Low Coolant Level inactive faults (this also can be done
Warning/Shutdown with the control operator interface, but
Low and High Battery Voltage is easier to do with the service tool.)
Warning Display snapshot data for all the
Discharged Battery Protection latest active and inactive faults.
Weak battery warning Information on the last 20 fault
Fail to Start (Overcrank) Shutdown conditions is displayed. Produce "strip
Fail to Crank Shutdown chart" recordings for up to 6
Redundant Starter Disconnect monitored functions at a time
Redundant Speed Sensors Perform control simulations
Low Fuel Day Tank and Low Fuel Download calibrations and feature
Main Tank warning changes. Allows the user to save
Cranking Lockout generator set conguration data for
Sensor Failure Indication use in other machines. This is
High Crankcase Blowby Level particularly useful in transfer switch
warning and paralleling applications where
High Fuel Temperature Warning multiple machines may be set up in
High Intake Manifold the same way
Temperature/Pressure Display generator set data plate
Aftercooler Cooler Inlet Over information, including model, serial
Temperature number

Specications May Change Without Notice 01/02 CPG QSX15/C/60


Technical Data

QSX15G9 Generating Sets 60 Hz

Prime Standby Prime Standby


Model 410 DFEJ 450 DFEJ 455 DFEK 500 DFEK
Ratings 410 kW 450 kW 455 kW 500 kW
513 kVA 563 kVA 569 kVA 625 kVA
Engine Model QSX15G9 QSX15G9 QSX15G9 QSX15G9
Aspiration: Turbo-charged with air-to-air Yes Yes Yes Yes
aftercooling
Gross Engine Power 506 kWm 562 kWm 506 kWm 562 kWm
Break Mean Effective Pressure 2006 kPa 2213 kPa 2193 kPa 2433 kPa
Bore 137 mm 137 mm 137 mm 137 mm
Stroke 169 mm 169 mm 169 mm 169 mm
Piston Speed 10.1 m/s 10.1 m/s 10.1 m/s 10.1 m/s
Compression Ratio 17:1 17:1 17:1 17:1
Lubricating Oil Capacity 83 Litres 83 Litres 83 Litres 83 Litres
Overspeed Limit 2150 rpm 50 2150 rpm 50 2150 rpm 50 2150 rpm 50
Dry Weight 4082 kg 4082 kg 4309 kg 4309 kg
Wet Weight 4218 kg 4218 kg 4445 kg 4445 kg
Fuel Consumption Load 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full
Fuel Consumption L/hr 37 60 81 104 40 55 88 114 41 65 89 115 42 59 96 132
Maximum Fuel Flow 424 L/hr 424 L/hr 424 L/hr 424 L/hr
Maximum Fuel Inlet Restriction 127 mm Hg 127 mm Hg 127 mm Hg 127 mm Hg
Maximum Fuel Return Restriction 77 mm Hg 77 mm Hg 77 mm Hg 77 mm Hg
Fan Load 26 kW 26 kW 26 kW 26 kW
Coolant Capacity 58 Litres 58 Litres 58 Litres 58 Litres
Coolant Flow 485 L/Min 485 L/Min 485 L/Min 485 L/Min
Heat Rejection to Eng Jacket Coolant 144 kW 155 kW 153 kW 182 kW
Heat Rejected to Ambient 54 kW 60 kW 59 kW 67 kW
Combustion Air 34 m3/min 36 m3/min 36 m3/min 41 m3/min
Maximum Air Cleaner Restriction 6.2 kPa 6.2 kPa 6.2 kPa 6.2 kPa
Alternator Cooling Air 62 m3/min 62 m3/min 62 m3/min 62 m3/min
Radiator Cooling Air 707 m3/min 707 m3/min 707 m3/min 707 m3/min
2
Minimum Air Opening to Room 2.3 m 2.3 m2 2.3 m2 2.3 m2
Minimum Discharge Opening 1.6 m2 1.6 m2 1.6 m2 1.6 m2
Maximum Static Restriction 13 mm Wg 13 mm Wg 13 mm Wg 13 mm Wg
Exhaust Gas Flow (Full Load) 82 m3/min 89 m3/min 88 m3/min 102 m3/min
Exhaust Gas Temperature 468C 477C 473C 498C
Maximum Exhaust Back Pressure 6.7 kPa 6.7 kPa 6.7 kPa 6.7 kPa
Derate RTF RTF RTF RTF
Typical gures only, based on an engine at full working temperature.
Load acceptance performance varies with site conditions.

Ratings
Standby
Applicable for supplying emergency power for the duration of normal power interruption. No sustained overload capability is available for this rating.
Nominally Rated (equivalent to fuel stop power in accordance with ISO 3046).
Prime
Applicable for supplying power in lieu of commercially purchased power. Prime power is the maximum power available at a variable load for an
unlimted number of hours. A 10% overload capability is available for limited time. Nominally rated.

Specications May Change Without Notice 01/02 CPG QSX15/C/60


Dimensions and Weights 50 Hz

A B

Dimensions and Weights (mm/kg) Set Weight Set Weight


Model Engine A B C kg Dry kg Wet
DFEJ QSX15G9 3868 1524 1534 4082 4218
DFEK QSX15G9 3868 1524 1534 4309 4445
RTF = Refer to Factory.
Set weights are without sub-base tank.
Dimensions and weights are for guidance only. Do not use for installation design. Ask for certied drawings on your specic application.
Specications may change without notice.

Power See your distributor for more information.


Generation

Cummins Power Generation Limited


Manston Park, Columbus Avenue
Manston, Ramsgate
Kent CT12 5BF, UK
Telephone: +44 (0)1843 255000
Fax: +44 (0)1843 255902
Email: cpg.uk@cummins.com
www.cumminspower.com
www.cummins.com

Cummins is a registered trademark of Cummins Inc.

Specications May Change Without Notice 01/02 CPG QSX15/C/60

You might also like