Fan Application

FA/106-00

product
application guide
A technical bulletin for engineers, contractors and students in the air movement and control industry.

A guide to disconnect switches for ventilation products


Fan-mounted disconnect switches NEMA ratings range from NEMA
are a recommended and 1 through NEMA 12 and are based
necessary safety feature for every on the switch enclosures' ability to
fan. Mounted directly on the fan, protect against moisture, dust,
within sight and reach, disconnect corrosion or explosion.
switches provide the best
protection against accidental Non-Hazardous NEMA
startup during service or Nema 1 Disconnect Enclosures
inspection. The following NEMA electrical
enclosures are recommended for
Disconnect switches come in a non-hazardous locations:
multitude of shapes and sizes,
and they are classified under NEMA 1: Enclosure constructed
many different NEMA ratings. for indoor use to provide a degree
Understanding the similarities of protection to personnel against
and differences in disconnect incidental contact with the
switches will offer dollar savings enclosed equipment and to
to you and your customers. Nema 4 Toggle Switch provide a degree of protection
against falling dust. The NEMA 1
Although there are different types enclosure meets the rod entry and
of disconnect switches, toggle and the indoor corrosion protection
heavy duty disconnects switches design tests. The rod entry test is
are most commonly used. Toggle intended to simulate incidental
switches are flipped on and off contact with enclosure equipment.
like a light switch, and heavy
duty switches have a push button NEMA 3R: Enclosure constructed
or a flip arm knife blade design. for either indoor or outdoor use to
Nema 3R Heavy Duty provide a degree of protection to
They may be visible or enclosed Switch
in some type of housing. personnel against incidental
contact with the enclosed
Disconnect switches are available equipment: to provide a degree of
in many enclosures and duties, protection against falling dirt,
and are classified under several rain, sleet, snow, and windblown
different National Electrical dust. The enclosed equipment will
Manufacturers Association be undamaged by the external
(NEMA) ratings based upon the formation of ice on the enclosure.
special applications and The NEMA 3R enclosure meets
production conditions they are Nema 12 the rod entry, rain, external icing,
installed in. Heavy Duty Switch outdoor corrosion protection and
gasket design tests.


P.O. Box 410 Schofield, WI 54476 715.359.6171 Fax 715.355.2399
Copyright 2000 Greenheck Fan Corp.
Greenheck Product Application Guide

NEMA 4: Enclosure constructed for either indoor or Explosion resistant enclosures are designed to
outdoor use to provide a degree of protection to contain an explosion, not prevent one. They are
personnel against incidental contact with the constructed of cast iron or aluminum, and provide
enclosure equipment; to provide a degree of limited access rendering them unsuitable as control
protection against falling dirt, rain, sleet, snow, system enclosures.
windblown dust, splashing water, and hose-
NEMA 7: Explosion resistant. Not weatherproof.
directed water; and that will be undamaged by the
Intended for indoor use in locations classified as
external formation of ice on the enclosure. The
Class I, Groups A, B, C or D, as defined in the
NEMA 4 enclosure meets the external icing,
National Electrical Code (NEC). It is capable of
hosedown, outdoor corrosion protection, and the
withstanding the pressures resulting from an
gasket design tests.
internal explosion of specified gases and contain
NEMA 4X: - The NEMA 4X enclosure has the same such that an explosive gas-air mixture existing in
protection as the NEMA 4 but it also includes the atmosphere surrounding enclosure will not be
protection against corrosion. The NEMA 4X ignited. Enclosure heat generating devices shall not
enclosure meets the external icing, hosedown, cause external surfaces to reach temperatures
outdoor corrosion protection, 4X corrosion capable of igniting explosive gas-air mixtures in the
protection, and the gasket design tests. 4X corrosion surrounding atmosphere. The NEMA 7 meets
protection is the indoor corrosion protection test explosion, hydrostatic, and temperature design
(24-hour salt spray test). The 24-hour test assures tests.
the switch to withstand 200 hours.
NEMA 9: Class II, Group E, F, or G hazardous
NEMA 12: Is a heavy duty enclosure constructed locations. Not weatherproof. Intended for indoor
(without knockouts) for indoor use to provide a use and has an enclosure that is capable of
degree of protection to personnel against incidental preventing the entrance of dust. Enclosed heat
contact with the enclosed equipment; to provide a generating devices shall not cause external surfaces
degree of protection against falling dust; against to reach temperatures capable of igniting or
circulation dust, lint, fibers, and flyings; and against discoloring dust on the enclosure or igniting dust
dripping and light air mixtures in the surrounding atmosphere. The
splashing of Left:. Closed NEMA 9 meets dust penetration and temperature
liquids. The NEMA NEMA 9 design tests, and aging of gaskets.
12 enclosure meets Disconnect Switch
Below: Top portion The class, division, and group specifications on
the circulating
of a NEMA 9 these hazardous enclosures are designated by the
dust, indoor
Disconnect Switch NEC. The Class number specifies acceptable
corrosion
with a toggle working conditions of the disconnect switch in a
protection, and the switch mounted. specific mounting location. Below are specific
gasket design tests.
explanations of Class and Division groupings.
Hazardous
Class I, Division 1, rating states that it is acceptable
NEMA
to operate in locations where flammable gases or
Enclosures
vapors are (or may be) present under normal
The following conditions and may ignite, explode or cause failure
NEMA electrical of electrical equipment. This Class I, Division 1,
enclosures are locations are termed "normally hazardous".
designed for use in Below: Open NEMA 9 Disconnect
switch disassembled
hazardous Class I, Division 2, disconnects are termed "not
environments. normally hazardous" because, unlike the Division 1
Most hazardous disconnect, it is normally contained within closed
environments containers or a closed system, or are adjacent to
require an Class I, Division 1 areas.
explosion resistant
enclosure.

Fan Application No. FA/106-00


Greenheck Product Application Guide

Class II, Division 1, covers locations where For Nema-3R, 4, 4X, and 12 switches, the disconnect
combustible dust in sufficient levels is (or could be) box will be mounted on the exterior in the
present in the air under normal following locations:
operating conditions to Centrifugal roof fans on the windband. (photo)
produce explosive or ignitable Hooded propeller roof fans on fan base.
mixtures or interfere with the
Sidewall propeller fan on wall housing.
normal operation of electrical
Requires special considerations: wall housing
equipment.
will not pass through the wall opening.
Class II, Division 2, covers Sidewall propeller fans on wall collar. Requires
locations where combustible special consideration: wall collar will not pass
dust is not normally present in through wall opening.
the air in sufficient quantities Greenhecks CUBE-180 up- Sidewall propeller fans - on wall fan panel if no
to produce explosive or blast roof fan shown with a
housing or collar is present. (photo)
NEMA 3R disconnect,
ignitable mixtures, and dust
exterior mounted and
accumulations are normally factory wired to the motor Wiring terminology
insufficient to interfere with with non-metallic liquid When ordering disconnects, it is helpful to
the normal operation of tight conduit. understand the different wiring
electrical equipment or other terminology, i.e. loose, mounted
apparatus. and wired, or mounted, wired,
and connected. If requested as
For a more specific explanation of explosion loose the disconnect will be
resistant disconnect switches please refer to the shipped with the fan. The box
National Electric Code of Greenhecks Product will not be mounted and the
Application article FA/107-00. wiring will not be connected.
Mounting locations for fan mounted Mounted and wired means that
disconnects the disconnect box will be
The mounting locations of the disconnect mounted on the unit and the
switches depend on the fan type and the wiring will be connected and
Sidewall propeller fans
disconnect enclosure. commonly use a dust-tight run from the motor to the
NEMA 4 disconnect. disconnect box. The wires at the
Mounting locations, wiring terminology, etc.
disconnect box will NOT be
vary by manufacturer. For purposes of explaining,
connected to the load side of the switch. The switch
we will describe Greenhecks approach.
is shipped in a bag attached to the fan. This allows
For a Nema-1, 7, and 9 switches, the disconnect box external wiring to be run to and connected in the
will be interior mounted on the disconnect box without having to remove
fan listed in the following the switch. This is the standard Greenheck
locations: method of wiring uses on its fans.
Centrifugal roof fans on
Mounted, wired and connected applies
the support pan. (see photo
only when an extended wiring pigtail is
on page 4)
specified. This means the disconnect box
Hooded propeller roof fans
will be mounted on the unit, the wiring
on fan base next to the
will be run from the motor to the
access door.
disconnect box, and the wire will be
Sidewall propeller fan with
connected to the load side of the switch.
wall housing on inside of
Centrifugal fans commonly use The extended wiring pigtail is also
wall housing.
NEMA 12 disconnects switches connected to the supply side of the switch.
Sidewall propeller fans that are often shipped loose. Fan At Greenheck, the fan is then factory
without housing on fan shown is Greenhecks Centrifugal tested with power connected to the
panel (also when a wall Model 36-BISW-21.
extended wiring pigtail.
collar is used).

Fan Application No. FA/106-00



3
Greenheck Product Application Guide

Characteristics of disconnects end switch voltage must be 120 volts. This applies
In addition to determining a mounting style, switch to single speed, either single phase or three phase
type, and NEMA enclosure, it's necessary to motors, OR two speed, single phase
distinguish the disconnect by various motors.
characteristics:
Greenhecks Disconnect
Speed: Disconnect switches are selected to match Offerings
the number of speeds the fan motor is capable of
Greenheck offers a wide
operating at.
range of NEMA rated
Phase: Disconnects are categorized like motors, disconnect switches
either single or three phase, and are factory accommodating all fan
selected to match the fan motor. mounted applications. By
allowing mounting and
Voltage: Disconnects could be single or two speed wiring options you have the
with high or low voltages. The high voltage ratings ability to order disconnects exactly
for single phase the way they are
Above: Example shown is
applications are 208, 220, Greenhecks Model GB-120, roof specified.
230, 240, and 277, and fan with a mounted NEMA 1
the low voltage disconnect switch. Greenhecks CAPS
ratings are; 110, 115, program will assist you
120, and 127. The in selecting the proper
three phase high disconnect for your
Left:
voltages are 380, application. Simpy select
Example shown is Greenhecks
400, 460, and 575, CUBE-180 up-blast roof fan with SWITCHES under the
and low voltages are a mounted and wired NEMA 1 ACCESSORIES tab and
190, 200, 208, 220,230, and disconnect switch. choose the NEMA rating,
240. overload protection, type
of switch, mounting style, and explosion resistant
Overload: Thermal and fused overloads are wiring (if applicable). Greenhecks CAPS program
available as safety features with disconnects. insures the switch will be compatible with the
Horsepower: There is a maximum and minimum selected fan and motor. If the switch you desire is
horsepower designations for each disconnect. The not available, contact the factory and a special
horsepower must fall between these values. The design request can be initiated.
proper disconnect will be selected by Greenheck
depending on the fan's motor horsepower.
Disconnects and One-Point Wiring
One-point wiring is a convenient optional method of
adding value with a time- and money-saving
service. By factory-wiring the damper actuator, fan
motor, and damper end switch to a single point, we
can make the installation of propeller fans faster
and easier for the contractor. The option of a
NEMA 1 and a NEMA 3R disconnect are available
with one-point wiring. If you are looking to use a References
different disconnect, contact the fan manufacturer. NEMA Standards Publication, NEMA 250,
Enclosures For Electrical Equipment, Published by:
The following guidelines should be used when National Electrical Manufacturers Association,
using disconnects with one-point wiring. The rule Copyright 1998, Section 2 Enclosure Types, Features,
states that the fan motor voltage can be whatever is and Applications.
specified, but the damper actuator voltage and the

4 Fan Application No. FA/106-00