EMPRESA REGIONAL DE SERVICIO PBLICO DE

ELECTRICIDAD DEL NORTE S.A.

ESTUDIO DE OPERATIVIDAD

PROYECTO

PUESTA EN OPERACION DEL TERCER


TRANSFORMADOR DE POTENCIA EN CHICLAYO
OESTE Y CHICLAYO NORTE

FEBRERO 2013
ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE
POTENCIA EN CHICLAYO OESTE Y CHICLAYO NORTE

INDICE

1 ASPECTOS GENERALES ............................................................... 3


1.1 INTRODUCCION ...............................................................................3
1.2 ALCANCES DEL ESTUDIO...................................................................3
2 CONCLUSIONES Y RECOMENDACIONES ...................................... 4
3 ESTUDIO DE FLUJO DE POTENCIA .............................................. 6
3.1 OBJETIVO .......................................................................................6
3.2 DATOS DEL SISTEMA ELECTRICO .......................................................6
3.3 METODOLOGIA ................................................................................8
3.4 SOFTWARE UTILIZADO .....................................................................8
3.5 RESULTADOS ..................................................................................8
4 ESTUDIO DE CORTOCIRCUITO .................................................. 28
4.1 OBJETIVO ..................................................................................... 28
4.2 METODOLOGIA .............................................................................. 28
4.3 RESULTADOS ................................................................................ 28
5 ESTUDIO DE COORDINACION DE LAS PROTECCIONES ............. 33
5.1 CRITERIOS DE AJUSTE .................................................................... 33
5.1.1 CRITERIOS BASICOS DE PROTECCION ................................................... 33
5.1.2 CRITERIOS PARA EL AJUSTE DE LA PROTECCION DIFERENCIAL DE
TRANSFORMADOR (87T) ...................................................................... 33
5.1.3 CRITERIOS PARA EL AJUSTE DE LA PROTECCION DE SOBRECORRIENTE
(50/51 50N/51N) .............................................................................. 34
5.2 CALCULOS JUSTIFICATIVOS ............................................................ 35
5.2.1 SE CHICLAYO OESTE: TRANSFORMADOR DE POTENCIA TR1 Y
TR2 60/10 KV ..................................................................................... 35
5.2.2 SE CHICLAYO OESTE: TRANSFORMADOR DE POTENCIA
TR3 60/22.9/10 KV .............................................................................. 39
5.2.3 SE CHICLAYO OESTE: LINEAS DE TRANSMISION EN 60 KV HACIA
CHICLAYO NORTE L-6012 Y L-6022 ....................................................... 44
5.2.4 SE CHICLAYO NORTE: TRANSFORMADOR DE POTENCIA TR1 Y
TR2 60/10 KV ..................................................................................... 49
5.2.5 SE CHICLAYO NORTE: TRANSFORMADOR DE POTENCIA TR3 60/10 KV ...... 53
5.2.6 SE CHICLAYO NORTE: SALIDA DE ALIMENTADORES EN 10 KV .................. 56
5.2.7 SE CHICLAYO OESTE: TRANSFORMADORES DE POTENCIA T14-260,
T16-260 Y T93-260.............................................................................. 58
5.2.8 SE CHICLAYO OESTE: BARRA 60 KV ...................................................... 61
ANEXOS .................................................................................................... 62
ANEXO I: DIAGRAMAS UNIFILARES. ............................................................. 63
ANEXO II: PARAMETROS ELCTRICOS DE EQUIPOS. ....................................... 66
ANEXO III: RESULTADOS DE FLUJO DE POTENCIA. .......................................... 69
ANEXO IV: RESULTADOS DE CORTOCIRCUITO. ............................................... 82
ANEXO V: PLANILLAS DE AJUSTES ................................................................ 95

DLF SAC Pgina 2 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE
POTENCIA EN CHICLAYO OESTE Y CHICLAYO NORTE

1 ASPECTOS GENERALES

1.1 INTRODUCCION
La empresa elctrica ELECTRONORTE S.A. (ENSA), concesionaria de la
comercializacin y distribucin de la energa elctrica en los departamentos de
Amazonas, Cajamarca y Lambayeque, viene ejecutando el proyecto PUESTA EN
OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA EN CHICLAYO
OESTE Y CHICLAYO NORTE, cuya finalidad es atender la demanda actual y futura
en las SE Chiclayo Oeste y SE Chiclayo Norte.

La subestacin de Chiclayo Oeste cuenta actualmente con dos transformadores de


potencia de 17.5 MVA, 60/10 KV cada uno y la subestacin de Chiclayo Norte cuenta
con tres transformadores de 17.5 MVA, 14 MVA y 30 MVA, 60/10 kV de los cuales el
transformador de 14 MVA se encuentra fuera de servicio.

El tercer transformador a instalar en la SE Chiclayo Oeste es de tres devanados de


30/16/20 MVA (ONAN), 60/22.9/10 kV.

Dentro de los alcances del proyecto se requiere del Estudio de Operatividad para la
puesta en operacin del tercer transformador de potencia en SE Chiclayo Oeste y
SE Chiclayo Norte.

1.2 ALCANCES DEL ESTUDIO


Dentro de los alcances del Estudio de Operatividad del Proyecto se encuentran los
siguientes estudios:

Estudio de Flujo de Potencia.

Estudio de Cortocircuito.

Estudio de Coordinacin de Protecciones.

En el Estudio de Coordinacin de Protecciones los dispositivos de proteccin a ser


analizados son los siguientes:

SE Chiclayo Oeste
Transformador T1 17.5 MVA 60/10 KV
01 u. Rele Diferencial de Transformador
- Marca: Siemens Modelo: 7UT633
Transformador T2 17.5 MVA 60/10 KV
01 u. Rele Diferencial de Transformador
- Marca: Siemens Modelo: 7UT633
Transformador T3 30/16/20 MVA 60/22.9/10 KV
02 u. Reles Diferencial de Transformador
- Marca: ABB Modelo: RET670 (Nuevo)

DLF SAC Pgina 3 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE
POTENCIA EN CHICLAYO OESTE Y CHICLAYO NORTE

SE Chiclayo Norte
Transformador T1 17.5 MVA 60/10 KV
01 u. Rele Diferencial de Transformador
- Marca: GE Modelo: T60
Transformador T2 14 MVA 60/10 KV
01 u. Rele Diferencial de Transformador
- Marca: GE Modelo: T60
Transformador T3 25/30 MVA 60/22.9/10 KV
01 u. Rele Diferencial de Transformador
- Marca: GE Modelo: T60
01 u. Rele Sobrecorriente
- Marca: GE Modelo: F60

Adicionalmente se analizar la coordinacin con las protecciones adyacentes al


proyecto y de ser necesario se modificarn sus ajustes.

En el Anexo I se muestran los diagramas unifilares, general y de protecciones que


forman parte de proyecto.

2 CONCLUSIONES Y RECOMENDACI ONES

DEL FLUJO DE POTENCIA

A. Los niveles de tensin en las barras se encuentran dentro del rango permitido por la
NTCSE (+/- 5% de la tensin nominal) en los distintos escenarios de operacin.

B. En los escenarios Base: No se observan sobrecarga en los transformadores de


potencia. Los trasformadores de la SE. Chiclayo Oeste operan aproximandamente
al 94 % y 92% de su capacidad ONAF, mientras que los trasnformadores de
potencia de la SE. Chiclayo Norte operan aproximadamente al 89% y 90% de su
capacidad ONAF.

C. En los escenarios con Proyecto: No se observan sobrecarga en los transformadores


de potencia. El Nuevo trasformador de potencia de la SE. Chiclayo Oeste operan
aproximandamente al 37% de su capacidad ONAF, mientras que los
transformadores de potencia de la SE. Chiclayo Norte operan aproximadamente al
65% y 66% de su capacidad ONAF debido al ingreso en paralelo del tercer

DLF SAC Pgina 4 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE
POTENCIA EN CHICLAYO OESTE Y CHICLAYO NORTE

transformador de 14 MVA el cual operar aproximadamente al 80% de su


capacidad.

D. En casos de contingencias de salida de servicio de un transformador T1, T2 o T3 en


SET Chiclayo Oeste solo es posible cerrar el acoplamiento de 10 kV en condiciones
de media y minima demanda y no se presentaran sobrecargas en los
transformadores que quedan en servicio.

E. Se ha determinado que la mxima corriente de carga en un tramo de barra 60 kV


de la SET Chiclayo Oeste es de 1222 A y corresponde al tramo que une a las
instalaciones perteneciente a REP con las instalaciones pertenecientes a ENSA,
cuando operan en una barra. As mismo, el valor de 1222 A es la mxima corriente
de carga que podra circular por el interruptor de acoplamiento.

DEL CORTOCIRCUITO

F. Los interruptores de potencia a instalarse en las nuevas bahas 10 kV de la SET


Chiclayo Oeste, tienen una capacidad de ruptura de 25 kA, por lo que no se
recomienda cerrar el acoplamiento de barras de 10kV, debido a que la corriente
mxima de cortocircuito en barras obtenida es de 33.2 kA. Con el acoplamiento
abierto la mxima corriente cortocircuito en barras del nuevo transformador de
potencia es de 17.7 kA.

G. Los interruptores de potencia de la SE. Chiclayo Norte, tienen una capacidad de


ruptura de 25 kA y 31.5 kA, considerando en servicio el transformador de potencia
T2 de 14 MVA se obtine una mxima corriente de cortocircuito de 20.6 kA.

H. En casos de contingencias de salida de servicio de un transformador T1 o T2 en


SET Chiclayo Oeste no es posible cerrar el acoplamiento de 10 kV en condiciones
de mxima demanda, debido a que en dicho escenario la corriente de cortocircuito
supera la capacidad de ruptura de los interruptores existentes.

DE LA COORDINACION DE PROTECCIONES

I. Para la puesta en servicio del nuevo transformador TR3 de SECHO se recomienda


implementar los ajustes propuestos en el tem 5.2.

J. Asimismo, se recomienda modificar los arranques de algunas proteccines que se


detallan en el tem 5.2 debido al incremento de coorreinte de cortocircuito.

DLF SAC Pgina 5 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE
POTENCIA EN CHICLAYO OESTE Y CHICLAYO NORTE

3 ESTUDIO DE FLUJO DE POTENCI A

3.1 OBJETIVO
El objetivo del estudio de flujos de potencia es analizar el comportamiento del
sistema elctrico en condiciones normales de operacin y en contingencia, con la
finalidad de evaluar los niveles de tensin en barras, flujos de potencia activa y
reactiva en las lneas de transmisin y transformadores de potencia para verificar la
capacidad de transmisin de los mismos.

3.2 DATOS DEL SISTEMA ELECTRICO


Para desarrollar los estudios de flujos de potencia se ha considerado toda la red
elctrica del sistema elctrico interconectado nacional (SEIN), cuyos datos de la
configuracin topolgica de la red y los parmetros elctricos del equipamiento que
lo conforman, han sido proporcionado por el COES en formato PFD (archivo
generado por el programa de simulacin de sistemas elctricos de potencia
DigSilent).

Los datos de la red elctrica del sistema de la zona de Chiclayo fueron


poroporcionada por el propietario de las instalaciones.

En el Anexo N II se muestran los parmetros elctricos de los componentes del


sistema elctrico.

La demanda del sistema elctrico de la SE Chiclayo Oeste fue proporcionada por


ENSA.

En la figura N 1 se muestra el diagrama de carga total del sistema elctrico Chiclayo


Oeste donde se puede observar que su mxima demanda alcanza los 100 MW en
horas de mxima demanda y en horas de mnima demanda alcanza los 45 MW.

Total SE Chiclayo Oeste


120.00

100.00

80.00

60.00
MW
40.00

20.00

0.00
19:12 00:00 04:48 09:36 14:24 19:12 00:00

Figura N 1 Diagrama de Carga Total del Sistema Elctrico Chiclayo

DLF SAC Pgina 6 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE
POTENCIA EN CHICLAYO OESTE Y CHICLAYO NORTE

En la figura N 2 se tiene el diagrama de carga de la SE Chiclayo Oeste 60/10 kV


donde se aprecia que la demanda alcanza los 32 MW en horas de mxima demanda
y de 15 MW en horas de mnima demanda.

Total SE Chiclayo Oeste 60/10 kV


35.00

30.00

25.00

20.00

15.00 MW

10.00

5.00

0.00
19:12 00:00 04:48 09:36 14:24 19:12 00:00

Figura N 2 Diagrama de Carga de la SE Chiclayo Oeste 60/10 kV

En la figura N 3 se tiene el diagrama de carga de la SE Chiclayo Norte donde se


aprecia que la demanda alcanza los 40 MW en horas de mxima demanda y de 13
MW en horas de mnima demanda.

Total SE Chiclayo Norte 60/10 kV


45.00
40.00
35.00
30.00
25.00
20.00 MW
15.00
10.00
5.00
0.00
00:00 04:48 09:36 14:24 19:12 00:00 04:48

Figura N 3 Diagrama de Carga de la SE Chiclayo Norte 60/10 kV

Ante el ingreso en servicio del transformador TR3 en SE Chiclayo Oeste 60/10 kV, se
tiene previsto incorporar nuevas cargas de 5 MW en la barra 10 kV y 6 MW en la
barra 22.9 kV en horas de mxima demanda.

DLF SAC Pgina 7 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE
POTENCIA EN CHICLAYO OESTE Y CHICLAYO NORTE

3.3 METODOLOGIA
Para el anlisis en estado estacionario, se han efectuado simulaciones de flujos de
potencia considerando el caso sin proyecto (actual) y el caso con proyecto en
operacin normal.

Caso N 1: Caso base (actual sin proyecto)

Caso N 2. Caso proyectado.

OPERACION NORMAL:

El anlisis se realiza para los escenarios de mxima, media y mnima demanda en


avenida y estiaje para el ao 2014.

Escenario N 1: Avenida Mxima Demanda 2014.

Escenario N 2: Avenida Media Demanda 2014.

Escenario N 3: Avenida Mnima Demanda 2014.

Escenario N 4: Estiaje Mxima Demanda 2014.

Escenario N 5: Estiaje Media Demanda 2014.

Escenario N 6: Estiaje Mnima Demanda 2014.

Para evaluar los resultados de los flujos de potencia en operacin normal se ha


considerado como criterio que los equipos de transmisin no sobrepasen su
capacidad y las tensiones en barras se encuentren dentro del rango permitido por la
NTCSE:

Niveles de tensiones admisibles en barra.

Operacin normal : 5% Vn

Cargas en lneas y transformadores.

Lneas de transmisin : 100% de su potencia nominal.

Transformadores de potencia : 100% de su potencia nominal.

3.4 SOFTWARE UTILIZADO


El software utilizado para realizar las simulaciones de flujos de potencia es el
DigSilent 14.1.

3.5 RESULTADOS
Del anlisis de los resultados de las simulaciones de flujos de potencia en operacin
normal se puede observar lo siguiente:

DLF SAC Pgina 8 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE
POTENCIA EN CHICLAYO OESTE Y CHICLAYO NORTE

RESULTADOS DE OPERACION NORMAL SIN PROYECTO:

Los niveles de tensin en las barras se encuentran dentro del rango permitido por
la NTCSE (+/- 5% de la tensin nominal) en los distintos escenarios de operacin.

No se observan sobrecargas en lneas.

No se observan sobrecarga en los transformadores de potencia. Los


trasformadores de la SE. Chiclayo Oeste operan aproximandamente al 94 % y
92% de su capacidad ONAF, mientras que los trasnformadores de potencia de la
SE. Chiclayo Norte operan aproximadamente al 89% y 90% de su capacidad
ONAF.

Tension ESCENARIO AVENIDA 2014 - BASE


BARRA Nominal MAXIMA DEMANDA MEDIA DEMANDA MINIMA DEMANDA
[kV] [KV] pu [KV] pu [KV] pu
CHICLAYO_OESTE_220 220 215.769 0.981 224.478 1.020 227.332 1.033
CHICL-O6 60 60.096 1.002 61.500 1.025 61.500 1.025
CHICL10A 10 10.146 1.015 10.261 1.026 10.065 1.006
CHICL10B 10 10.146 1.015 10.261 1.026 10.065 1.006
CHICL23 22.9 0.000 0.000 0.000 0.000 0.000 0.000
CHIL10N 10 0.000 0.000 0.000 0.000 0.000 0.000
CT CHICL10 10 10.146 1.015 10.261 1.026 10.065 1.006
CHICL60 60 60.096 1.002 60.510 1.009 61.036 1.017
CHICN10 10 9.979 0.998 10.031 1.003 9.960 0.996
CHICN10B 10 9.979 0.998 10.031 1.003 9.960 0.996
CHICN10C 10 9.979 0.998 10.031 1.003 9.960 0.996
POMAL60 60 59.710 0.995 60.235 1.004 60.884 1.015
TUMAN60 60 59.497 0.992 60.074 1.001 60.772 1.013
CAYAL60 60 59.280 0.988 59.906 0.998 60.657 1.011
ILLIMO60 60 60.369 1.006 60.555 1.009 60.447 1.007
LA_VIA60 60 59.275 0.988 59.492 0.992 59.572 0.993
MOTUP60 60 57.940 0.966 58.211 0.970 58.449 0.974
OLMOS60 60 57.667 0.961 57.984 0.966 58.099 0.968
OCCI60 60 57.833 0.964 58.174 0.970 57.938 0.966
LAMB_SUR_60 60 61.237 1.021 61.064 1.018 61.333 1.022
LAMBA60 60 61.231 1.021 61.015 1.017 61.308 1.022
Cuadro N 1 Niveles de tensin Escenario Avenida 2014 BASE.

DLF SAC Pgina 9 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA EN CHICLAYO OESTE Y CHICLAYO NORTE

ESCENARIO AVENIDA 2014 - BASE


MAXIMA DEMANDA MEDIA DEMANDA MINIMA DEMANDA
BUS1 BUS 2 Terminal
Terminal I Terminal J Terminal I Terminal J Terminal I %
% % J
MW MVAR MW MVAR MW MVAR MW MVAR MW MVAR MW MVAR
L1 Chiclayo Oeste Chiclayo Norte -25.130 -9.374 25.536 9.987 75.787 -19.311 -5.810 19.537 6.116 56.593 -9.402 -2.639 9.454 2.646 27.169
L2 Chiclayo Oeste Chiclayo Norte -25.130 -9.374 25.536 9.987 75.787 -19.311 -5.810 19.537 6.116 56.593 -9.402 -2.639 9.454 2.646 27.169
Chiclayo Norte Pomalca 10.023 3.402 -9.989 -3.379 18.709 7.560 2.319 -7.541 -2.347 13.890 4.648 1.136 -4.641 -1.205 8.343
Pomalca Tuman 5.149 1.474 -5.139 -1.541 9.552 4.086 1.053 -4.080 -1.135 7.468 3.072 0.657 -3.069 -0.751 5.507
Tuman Cayalti 1.984 0.370 -1.980 -0.637 3.717 1.621 0.236 -1.618 -0.513 3.002 1.212 0.088 -1.210 -0.377 2.214
L1 Chiclayo Oeste Illimo 9.740 0.604 -9.587 -0.596 45.934 8.920 0.204 -8.792 -0.272 41.935 6.520 1.308 -6.448 -1.537 31.657
L2 Chiclayo Oeste Illimo 9.740 0.604 -9.587 -0.596 45.934 8.920 0.204 -8.792 -0.272 41.935 6.520 1.308 -6.448 -1.537 31.657
L1 Illimo La Vina 7.226 0.599 -7.108 -0.705 34.787 7.055 0.565 -6.943 -0.681 33.851 5.096 0.953 -5.035 -1.136 25.012
L2 Illimo La Vina 7.654 0.874 -7.534 -1.044 37.041 7.473 0.831 -7.359 -1.012 36.046 5.376 1.171 -5.314 -1.425 26.662
La Vina Motupe 10.105 -0.042 -9.875 0.106 49.214 9.788 -0.085 -9.574 0.126 47.497 6.795 1.209 -6.689 -1.309 33.661
Motupe Olmos -4.169 1.320 4.208 -1.462 22.193 -3.892 1.402 3.926 -1.552 20.936 -2.823 -0.269 2.838 0.094 14.089
Olmos Occidente -1.258 1.704 1.270 -1.925 11.542 -1.136 1.748 1.147 -1.972 11.357 -1.075 -0.168 1.078 -0.067 5.423
Chiclayo Oeste Lambayeque Sur 8.830 1.773 -8.806 -1.803 15.053 13.458 3.361 -13.402 -3.283 23.172 6.621 0.810 -6.608 -0.875 11.145
Lambayeque Sur Lambayeque 2.325 -0.424 -2.324 0.385 3.958 5.432 0.507 -5.428 -0.537 9.168 3.807 -0.066 -3.806 0.030 6.367
Cuadro N 2 Flujo de Potencia a travs de las lneas de transmisin Avenida 2014 - BASE.

ESCENARIO AVENIDA 2014 - BASE


MAXIMA DEMANDA MEDIA DEMANDA MINIMA DEMANDA
Transformador
Terminal i Terminal j Terminal i Terminal j Terminal i Terminal j
% % %
MW MVAR MW MVAR MW MVAR MW MVAR MW MVAR MW MVAR
tr2 chi_675 15.75 5.04 -15.72 -3.58 92.18 11.13 2.55 -11.11 -1.83 63.68 6.83 1.19 -6.80 -0.88 38.95
tr2 chi_676 16.08 5.14 -16.06 -3.65 94.12 11.37 2.60 -11.34 -1.86 65.02 6.97 1.22 -6.95 -0.90 39.77
tr2 chi_672 14.61 5.83 -14.61 -4.48 89.73 11.29 3.57 -11.29 -2.79 67.10 5.15 1.59 -5.15 -1.43 30.64
tr2 chi_671 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
tr2 Chiclayo Nuevo 25.63 9.52 -25.57 -7.17 90.99 19.77 5.73 -19.74 -4.38 68.04 9.01 2.55 -9.00 -2.26 31.07
tr2 La Via 4.54 1.79 -4.53 -1.49 98.74 4.51 1.78 -4.50 -1.48 97.86 3.55 1.35 -3.54 -1.16 76.59
tr2 lam_801 2.32 -0.39 -2.30 0.47 32.98 5.43 0.54 -5.39 -0.18 76.63 3.81 -0.03 -3.78 0.22 54.09
Cuadro N 3 Flujo de Potencia a travs de transformadores de dos devanados Avenida 2014 - BASE.

DLF SAC Pgina 10 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE
POTENCIA EN CHICLAYO OESTE Y CHICLAYO NORTE

ESCENARIO BASE AVENIDA 2014 - BASE


MAXIMA DEMANDA
Transformador
HV MV LV %
MW MVAR MVA MW MVAR MVA MW MVAR MVA HV MV LV
tr3 chi_2671 27.88 3.45 28.09 -27.82 -2.01 27.89 0.00 0.00 0.00 57.29 54.42 0.00
tr3 chi_2672 27.88 3.45 28.09 -27.82 -2.01 27.89 0.00 0.00 0.00 57.29 54.42 0.00
tr3 chi_2672(1) 55.87 8.15 56.46 -55.71 -5.04 55.94 0.00 0.00 0.00 57.57 54.57 0.00
tr3 Chiclayo T3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
tr3 pom_8001 4.84 1.91 5.20 -4.84 -1.59 5.09 0.00 0.00 0.00 74.67 73.18 0.00
tr3 tum_8001 3.15 1.17 3.36 -2.48 -0.82 2.61 -0.67 -0.22 0.71 48.47 36.18 34.54
tr3 cay_8001 1.98 0.64 2.08 -1.98 -0.59 2.06 0.00 0.00 0.00 30.08 29.77 0.00
tr3 illm_8001 4.29 -0.28 4.30 -2.91 1.09 3.11 -1.38 -0.53 1.48 85.56 61.46 58.73
Tr3 Motupe 5.67 1.36 5.83 -4.35 -1.03 4.47 -1.32 0.03 1.32 86.21 62.92 64.87
tr3 Olmos 2.90 0.61 2.96 -1.44 -0.23 1.46 -1.44 -0.23 1.46 34.24 16.69 50.27
tr3 occidente 1.26 -1.70 2.12 -1.26 1.76 2.16 0.00 0.00 0.00 31.39 31.39 0.00
tr3 Lambayeque Sur 7.97 2.78 8.44 0.00 0.00 0.00 -7.94 -2.53 8.34 33.17 0.00 41.35

ESCENARIO BASE AVENIDA 2014 - BASE


MEDIA DEMANDA
Transformador
HV MV LV %
MW MVAR MVA MW MVAR MVA MW MVAR MVA HV MV LV
tr3 chi_2671 23.27 3.90 23.60 -23.23 -2.89 23.41 0.00 0.00 0.00 46.25 45.67 0.00
tr3 chi_2672 23.27 3.90 23.60 -23.23 -2.89 23.41 0.00 0.00 0.00 46.25 45.67 0.00
tr3 chi_2672(1) 46.60 8.88 47.44 -46.46 -6.62 46.93 0.00 0.00 0.00 46.49 45.78 0.00
tr3 Chiclayo T3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
tr3 pom_8001 3.45 1.29 3.69 -3.45 -1.14 3.64 0.00 0.00 0.00 52.50 51.97 0.00
tr3 tum_8001 2.46 0.90 2.62 -1.77 -0.58 1.86 -0.69 -0.23 0.73 37.36 26.85 36.78
tr3 cay_8001 1.62 0.51 1.70 -1.62 -0.48 1.69 0.00 0.00 0.00 24.29 24.29 0.00
tr3 illm_8001 3.06 -0.85 3.17 -1.69 1.53 2.28 -1.37 -0.52 1.46 62.90 44.65 57.48
Tr3 Motupe 5.65 1.43 5.83 -4.09 -0.97 4.21 -1.56 -0.07 1.56 85.78 60.87 78.99
tr3 Olmos 2.74 0.57 2.80 -1.37 -0.21 1.38 -1.37 -0.21 1.38 32.23 16.03 48.27
tr3 occidente 1.14 -1.75 2.08 -1.14 1.80 2.13 0.00 0.00 0.00 30.71 30.71 0.00
tr3 Lambayeque Sur 7.97 2.78 8.44 0.00 0.00 0.00 -7.94 -2.53 8.34 33.17 0.00 41.35

ESCENARIO AVENIDA 2014 - BASE


MINIMA DEMANDA
Transformador
HV MV LV %
MW MVAR MVA MW MVAR MVA MW MVAR MVA HV MV LV
tr3 chi_2671 13.14 4.02 13.74 -13.13 -3.68 13.63 0.00 0.00 0.00 26.60 26.60 0.00
tr3 chi_2672 13.14 4.02 13.74 -13.13 -3.68 13.63 0.00 0.00 0.00 26.60 26.60 0.00
tr3 chi_2672(1) 26.25 8.76 27.68 -26.14 -7.86 27.30 0.00 0.00 0.00 26.78 26.63 0.00
tr3 Chiclayo T3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
tr3 pom_8001 1.57 0.55 1.66 -1.57 -0.52 1.65 0.00 0.00 0.00 23.40 23.40 0.00

DLF SAC Pgina 11 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTE
NORTE

tr3 tum_8001 1.86 0.66 1.97 -1.30 -0.43 1.37 -0.56 -0.18 0.59 27.81 19.66 29.50
tr3 cay_8001 1.21 0.38 1.27 -1.21 -0.36 1.26 0.00 0.00 0.00 17.91 18.09 0.00
tr3 illm_8001 2.42 0.95 2.60 -1.52 -0.50 1.59 -0.91 -0.35 0.97 51.70 32.08 39.28
Tr3 Motupe 3.85 1.21 4.04 -2.70 -0.64 2.78 -1.15 -0.38 1.21 59.20 41.23 63.10
tr3 Olmos 1.74 0.34 1.78 -0.87 -0.14 0.88 -0.87 -0.14 0.88 20.39 10.13 30.46
tr3 occidente 1.08 0.17 1.09 -1.08 -0.15 1.09 0.00 0.00 0.00 16.10 15.94 0.00
tr3 Lambayeque Sur 2.80 0.94 2.95 0.00 0.00 0.00 -2.78 -0.88 2.92 11.56 0.00 14.34
Cuadro N 4 Flujo de Potencia a travs de los transformador de potencia de 3 devanados
Avenida 2014 - BASE.

Tension ESCENARIO ESTIAJE 2014 - BASE


BARRA Nominal MAXIMA DEMANDA MEDIA DEMANDA MINIMA DEMANDA
[kV] [KV] pu [KV] pu [KV] pu
CHICLAYO_OESTE_220 220 223.051 1.014 226.041 1.027 229.962 1.045
CHICL-O6 60 60.066 1.001 62.497 1.042 61.520 1.025
CHICL10A 10 10.100 1.010 10.167 1.017 10.068 1.007
CHICL10B 10 10.100 1.010 10.167 1.017 10.068 1.007
CHICL23 22.9 0.000 0.000 0.000 0.000 0.000 0.000
CHIL10N 10 0.000 0.000 0.000 0.000 0.000 0.000
CT CHICL10 10 10.100 1.010 10.167 1.017 10.068 1.007
CHICL60 60 60.066 1.001 61.509 1.025 61.056 1.018
CHICN10 10 9.815 0.982 9.940 0.994 9.963 0.996
CHICN10B 10 9.815 0.982 9.940 0.994 9.963 0.996
CHICN10C 10 9.815 0.982 9.940 0.994 9.963 0.996
POMAL60 60 59.692 0.995 61.240 1.021 60.904 1.015
TUMAN60 60 59.483 0.991 61.083 1.018 60.792 1.013
CAYAL60 60 59.271 0.988 60.919 1.015 60.677 1.011
ILLIMO60 60 60.351 1.006 61.604 1.027 60.467 1.008
LA_VIA60 60 59.246 0.987 60.571 1.010 59.593 0.993
MOTUP60 60 57.890 0.965 59.329 0.989 58.471 0.975
OLMOS60 60 57.615 0.960 59.120 0.985 58.121 0.969
OCCI60 60 57.780 0.963 59.322 0.989 57.959 0.966
LAMB_SUR_60 60 61.237 1.021 62.071 1.035 61.352 1.023
LAMBA60 60 61.231 1.021 62.024 1.034 61.328 1.022
Cuadro N 5 Niveles de tensin Escenario Estiaje 2014 BASE.

DLF SAC Pgina 12 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA EN CHICLAYO OESTE Y CHICLAYO NORTE

ESCENARIO ESTIAJE 2014 - BASE


MAXIMA DEMANDA MEDIA DEMANDA MINIMA DEMANDA
BUS1 BUS 2
Terminal I Terminal J Terminal I Terminal J Terminal I Terminal J
% % %
MW MVAR MW MVAR MW MVAR MW MVAR MW MVAR MW MVAR
L1 Chiclayo Oeste Chiclayo Norte -25.03 -9.93 25.44 10.55 76.12 -19.61 -5.87 19.84 6.18 56.52 -9.40 -2.64 9.45 2.65 27.16
L2 Chiclayo Oeste Chiclayo Norte -25.03 -9.93 25.44 10.55 76.12 -19.61 -5.87 19.84 6.18 56.52 -9.40 -2.64 9.45 2.65 27.16
Chiclayo Norte Pomalca 9.81 3.28 -9.78 -3.26 18.30 7.56 2.29 -7.54 -2.32 13.65 4.65 1.14 -4.64 -1.20 8.34
Pomalca Tuman 5.046 1.4323 -5.036 -1.501 9.3589 4.086 1.0344 -4.08 -1.121 7.338 3.072 0.6569 -3.069 -0.751 5.5051
Tuman Cayalti 1.9525 0.3591 -1.948 -0.626 3.6578 1.6211 0.2244 -1.618 -0.512 2.9518 1.2116 0.0882 -1.21 -0.377 2.2128
L1 Chiclayo Oeste Illimo 9.7405 0.6651 -9.588 -0.657 45.969 8.907 0.0658 -8.784 -0.161 41.17 6.5195 1.3067 -6.448 -1.536 31.645
L2 Chiclayo Oeste Illimo 9.7405 0.6651 -9.588 -0.657 45.969 8.907 0.0658 -8.784 -0.161 41.17 6.5195 1.3067 -6.448 -1.536 31.645
L1 Illimo La Vina 7.2278 0.657 -7.109 -0.762 34.839 7.0458 0.4966 -6.938 -0.627 33.201 5.0956 0.9522 -5.035 -1.135 25.002
L2 Illimo La Vina 7.6531 0.9356 -7.533 -1.105 37.097 7.4654 0.757 -7.356 -0.957 35.354 5.3758 1.17 -5.314 -1.424 26.652
La Vina Motupe 10.105 0.0769 -9.876 -0.012 49.246 9.7799 -0.183 -9.574 0.2061 46.618 6.7953 1.2087 -6.689 -1.308 33.648
Motupe Olmos -4.169 1.3101 4.2079 -1.452 22.197 -3.892 1.4932 3.9257 -1.651 20.722 -2.823 -0.269 2.8384 0.094 14.083
Olmos Occidente -1.258 1.7005 1.2696 -1.921 11.536 -1.136 1.8253 1.1475 -2.058 11.507 -1.075 -0.168 1.0781 -0.067 5.4208
Chiclayo Oeste Lambayeque Sur 8.8296 1.7733 -8.806 -1.803 15.053 13.455 3.2928 -13.4 -3.225 22.773 6.6208 0.8088 -6.608 -0.874 11.141
Lambayeque Sur Lambayeque 2.325 -0.424 -2.324 0.3855 3.9578 5.4311 0.4552 -5.428 -0.487 9.0103 3.8071 -0.067 -3.806 0.0309 6.3645
Cuadro N 6 Flujo de Potencia a travs de las lneas de transmisin Estiaje 2014 - BASE.

ESCENARIO ESTIAJE 2014 - BASE


MAXIMA DEMANDA MEDIA DEMANDA MINIMA DEMANDA
Transformador
Terminal i Terminal j Terminal i Terminal j Terminal i Terminal j
% % %
MW MVAR MW MVAR MW MVAR MW MVAR MW MVAR MW MVAR
tr2 chi_675 12.72 3.20 -12.70 -2.24 73.14 11.13 2.56 -11.11 -1.83 63.27 6.83 1.19 -6.80 -0.88 38.93
tr2 chi_676 12.99 3.27 -12.96 -2.29 74.67 11.37 2.62 -11.34 -1.86 64.60 6.97 1.22 -6.95 -0.90 39.76
tr2 chi_672 14.60 6.28 -14.60 -4.86 90.73 11.51 3.63 -11.51 -2.81 68.11 5.15 1.59 -5.15 -1.43 30.63
tr2 chi_671 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
tr2 Chiclayo Nuevo 25.64 10.31 -25.58 -7.84 92.00 20.15 5.83 -20.12 -4.40 69.07 9.01 2.55 -9.00 -2.26 31.06
tr2 La Via 4.54 1.79 -4.53 -1.49 98.79 4.51 1.77 -4.50 -1.48 96.05 3.55 1.35 -3.54 -1.16 76.56
tr2 lam_801 2.32 -0.39 -2.30 0.47 32.98 5.43 0.49 -5.39 -0.14 75.31 3.81 -0.03 -3.78 0.22 54.07
Cuadro N 7 Flujo de Potencia a travs de transformadores de dos devanados Estiaje 2014 - BASE.
DLF SAC Pgina 13 de 132 Revisin: 1
ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE
POTENCIA EN CHICLAYO OESTE Y CHICLAYO NORTE

ESCENARIO ESTIAJE 2014


MAXIMA DEMANDA
Transformador
HV MV LV %
MW MVAR MVA MW MVAR MVA MW MVAR MVA HV MV LV
tr3 chi_2671 26.40 14.83 30.28 -26.34 -13.22 29.47 0.00 0.00 0.00 59.74 57.50 0.00
tr3 chi_2672 26.40 14.83 30.28 -26.34 -13.22 29.47 0.00 0.00 0.00 59.74 57.50 0.00
tr3 chi_2672(1) 52.52 30.96 60.96 -52.35 -27.49 59.13 0.00 0.00 0.00 60.13 57.68 0.00
tr3 Chiclayo T3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
tr3 pom_8001 4.74 1.83 5.08 -4.74 -1.56 4.99 0.00 0.00 0.00 72.89 67.79 0.00
tr3 tum_8001 3.08 1.14 3.29 -2.41 -0.79 2.54 -0.67 -0.22 0.71 47.38 35.15 34.54
tr3 cay_8001 1.95 0.63 2.05 -1.95 -0.58 2.03 0.00 0.00 0.00 29.60 29.30 0.00
tr3 illm_8001 4.29 -0.28 4.30 -2.91 1.09 3.11 -1.38 -0.53 1.48 85.58 61.47 58.75
Tr3 Motupe 5.67 1.46 5.85 -4.35 -1.03 4.47 -1.32 -0.03 1.32 86.67 67.17 69.28
tr3 Olmos 2.90 0.61 2.96 -1.44 -0.23 1.46 -1.44 -0.23 1.46 34.29 17.06 51.37
tr3 occidente 1.26 -1.70 2.12 -1.26 1.76 2.16 0.00 0.00 0.00 31.38 31.38 0.00
tr3 Lambayeque Sur 7.97 2.77 8.44 0.00 0.00 0.00 -7.94 -2.53 8.34 32.63 0.00 40.67

ESCENARIO ESTIAJE 2014


MEDIA DEMANDA
Transformador
HV MV LV %
MW MVAR MVA MW MVAR MVA MW MVAR MVA HV MV LV
tr3 chi_2671 23.54 13.65 27.21 -23.49 -12.39 26.55 0.00 0.00 0.00 52.97 50.99 0.00
tr3 chi_2672 23.54 13.65 27.21 -23.49 -12.39 26.55 0.00 0.00 0.00 52.97 50.99 0.00
tr3 chi_2672(1) 46.81 28.50 54.80 -46.65 -25.72 53.27 0.00 0.00 0.00 53.34 51.14 0.00
tr3 Chiclayo T3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
tr3 pom_8001 3.45 1.29 3.69 -3.45 -1.14 3.64 0.00 0.00 0.00 51.61 51.09 0.00
tr3 tum_8001 2.46 0.90 2.62 -1.77 -0.58 1.86 -0.69 -0.23 0.73 36.73 26.40 36.15
tr3 cay_8001 1.62 0.51 1.70 -1.62 -0.48 1.69 0.00 0.00 0.00 23.88 23.88 0.00
tr3 illm_8001 3.06 -0.93 3.20 -1.69 1.61 2.33 -1.37 -0.52 1.46 62.26 44.85 56.46
Tr3 Motupe 5.65 1.45 5.83 -4.09 -0.97 4.21 -1.56 -0.08 1.56 84.23 61.60 79.97
tr3 Olmos 2.74 0.57 2.80 -1.37 -0.21 1.38 -1.37 -0.21 1.38 31.60 15.72 47.32
tr3 occidente 1.14 -1.83 2.15 -1.14 1.88 2.20 0.00 0.00 0.00 31.06 31.06 0.00
tr3 Lambayeque Sur 7.97 2.77 8.44 0.00 0.00 0.00 -7.94 -2.53 8.34 32.63 0.00 40.67

ESCENARIO ESTIAJE 2014


MINIMA DEMANDA
Transformador
HV MV LV %
MW MVAR MVA MW MVAR MVA MW MVAR MVA HV MV LV
tr3 chi_2671 13.24 10.30 16.77 -13.22 -9.80 16.45 0.00 0.00 0.00 32.09 32.09 0.00
tr3 chi_2672 13.24 10.30 16.77 -13.22 -9.80 16.45 0.00 0.00 0.00 32.09 32.09 0.00
tr3 chi_2672(1) 26.23 21.39 33.84 -26.11 -20.16 32.99 0.00 0.00 0.00 32.38 32.17 0.00
tr3 Chiclayo T3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
tr3 pom_8001 1.57 0.55 1.66 -1.57 -0.52 1.65 0.00 0.00 0.00 23.39 23.39 0.00
tr3 tum_8001 1.86 0.66 1.97 -1.30 -0.43 1.37 -0.56 -0.18 0.59 27.80 19.65 29.49
tr3 cay_8001 1.21 0.38 1.27 -1.21 -0.36 1.26 0.00 0.00 0.00 17.90 18.08 0.00
tr3 illm_8001 2.42 0.95 2.60 -1.52 -0.50 1.59 -0.91 -0.35 0.97 51.68 32.06 39.27

DLF SAC Pgina 14 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

Tr3 Motupe 3.85 1.21 4.04 -2.70 -0.64 2.78 -1.15 -0.38 1.21 59.18 41.22 63.07
tr3 Olmos 1.74 0.34 1.78 -0.87 -0.14 0.88 -0.87 -0.14 0.88 20.38 10.13 30.45
tr3 occidente 1.08 0.17 1.09 -1.08 -0.15 1.09 0.00 0.00 0.00 16.10 15.93 0.00
tr3 Lambayeque Sur 2.80 0.94 2.95 0.00 0.00 0.00 -2.78 -0.88 2.92 11.56 0.00 14.33
Cuadro N 8 Flujo de Potencia a travs de los transformador de potencia de 3 devanados
Estiaje 2014 - BASE.

RESULTADOS DE OPERACION NORMAL CON PROYECTO:

Los niveles de tensin en las barras se encuentran dentro del rango permitido por la
NTCSE (+/- 5% de la tensin nominal) en los distintos escenarios de operacin.

No se observan sobrecargas en lneas.

No se observan sobrecarga en los transformadores de potencia. El Nuevo trasformador


de potencia de la SE. Chiclayo Oeste operan aproximandamente al 37% de su
capacidad ONAF, mientras que los transformadores de potencia de la SE. Chiclayo
Norte opera aproximadamente al 65% y 66% de su capacidad ONAF debido al ingreso
en paralelo del tercer transformador de 14 MVA, el cual operar aproximadamente al
80% de su capacidad.

Tension ESCENARIO AVENIDA 2014 CON PROYECTO


BARRA Nominal MAXIMA DEMANDA MEDIA DEMANDA MINIMA DEMANDA
[kV] [KV] pu [KV] pu [KV] pu
CHICLAYO_OESTE_220 220 213.726 0.971 224.292 1.020 227.253 1.033
CHICL-O6 60 60.133 1.002 61.500 1.025 61.500 1.025
CHICL10A 10 10.012 1.001 10.129 1.013 10.065 1.006
CHICL10B 10 10.012 1.001 10.129 1.013 10.065 1.006
CHICL23 22.9 23.242 1.015 23.324 1.019 23.117 1.009
CHIL10N 10 10.175 1.017 10.202 1.020 10.102 1.010
CT CHICL10 10 10.012 1.001 10.129 1.013 10.065 1.006
CHICL60 60 60.133 1.002 60.526 1.009 61.038 1.017
CHICN10 10 10.075 1.007 10.088 1.009 9.985 0.998
CHICN10B 10 10.075 1.007 10.088 1.009 9.985 0.998
CHICN10C 10 10.075 1.007 10.088 1.009 9.985 0.998
POMAL60 60 59.757 0.996 60.251 1.004 60.886 1.015
TUMAN60 60 59.549 0.992 60.090 1.002 60.775 1.013
CAYAL60 60 59.336 0.989 59.922 0.999 60.659 1.011
ILLIMO60 60 60.369 1.006 60.555 1.009 60.447 1.007
LA_VIA60 60 59.275 0.988 59.492 0.992 59.572 0.993
MOTUP60 60 57.940 0.966 58.211 0.970 58.449 0.974
OLMOS60 60 57.667 0.961 57.984 0.966 58.099 0.968
OCCI60 60 57.833 0.964 58.174 0.970 57.938 0.966
LAMB_SUR_60 60 61.237 1.021 61.064 1.018 61.333 1.022
LAMBA60 60 61.231 1.021 61.015 1.017 61.308 1.022
Cuadro N 9 Niveles de tensin Escenario Avenida 2014 CON PROYECTO

DLF SAC Pgina 15 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA EN CHICLAYO OESTE Y CHICLAYO NORTE

ESCENARIO AVENIDA 2014 CON PROYECTO


MAXIMA DEMANDA MEDIA DEMANDA MINIMA DEMANDA
BUS1 BUS 2
Terminal I Terminal J Terminal I Terminal J Terminal I Terminal J
% % %
MW MVAR MW MVAR MW MVAR MW MVAR MW MVAR MW MVAR
L1 Chiclayo Oeste Chiclayo Norte -25.03 -8.80 25.43 9.40 74.92 -19.32 -5.53 19.55 5.83 56.38 -9.42 -2.59 9.47 2.60 27.17
L2 Chiclayo Oeste Chiclayo Norte -25.03 -8.80 25.43 9.40 74.92 -19.32 -5.53 19.55 5.83 56.38 -9.42 -2.59 9.47 2.60 27.17
Chiclayo Norte Pomalca 9.81 3.31 -9.78 -3.29 18.29 7.56 2.32 -7.54 -2.35 13.89 4.65 1.14 -4.64 -1.20 8.34
Pomalca Tuman 5.05 1.43 -5.04 -1.50 9.35 4.09 1.05 -4.08 -1.13 7.47 3.07 0.66 -3.07 -0.75 5.51
Tuman Cayalti 1.95 0.36 -1.95 -0.63 3.65 1.62 0.24 -1.62 -0.51 3.00 1.21 0.09 -1.21 -0.38 2.21
L1 Chiclayo Oeste Illimo 9.74 0.60 -9.59 -0.60 45.93 8.92 0.20 -8.79 -0.27 41.94 6.52 1.31 -6.45 -1.54 31.66
L2 Chiclayo Oeste Illimo 9.74 0.60 -9.59 -0.60 45.93 8.92 0.20 -8.79 -0.27 41.94 6.52 1.31 -6.45 -1.54 31.66
L1 Illimo La Vina 7.23 0.60 -7.11 -0.70 34.79 7.05 0.56 -6.94 -0.68 33.85 5.10 0.95 -5.04 -1.14 25.01
L2 Illimo La Vina 7.65 0.87 -7.53 -1.04 37.04 7.47 0.83 -7.36 -1.01 36.05 5.38 1.17 -5.31 -1.42 26.66
La Vina Motupe 10.11 -0.04 -9.88 0.11 49.21 9.79 -0.08 -9.57 0.13 47.50 6.80 1.21 -6.69 -1.31 33.66
Motupe Olmos -4.17 1.32 4.21 -1.46 22.19 -3.89 1.40 3.93 -1.55 20.94 -2.82 -0.27 2.84 0.09 14.09
Olmos Occidente -1.26 1.70 1.27 -1.92 11.54 -1.14 1.75 1.15 -1.97 11.36 -1.08 -0.17 1.08 -0.07 5.42
Chiclayo Oeste Lambayeque Sur 8.83 1.77 -8.81 -1.80 15.05 13.46 3.36 -13.40 -3.28 23.17 6.62 0.81 -6.61 -0.88 11.15
Lambayeque Sur Lambayeque 2.32 -0.42 -2.32 0.39 3.96 5.43 0.51 -5.43 -0.54 9.17 3.81 -0.07 -3.81 0.03 6.37
Cuadro N 10 Flujo de Potencia a travs de las lneas de transmisin Avenida 2014 CON PROYECTO.

ESCENARIO AVENIDA 2014 CON PROYECTO


MAXIMA DEMANDA MEDIA DEMANDA MINIMA DEMANDA
Transformador
Terminal i Terminal j Terminal i Terminal j Terminal i Terminal j
% % %
MW MVAR MW MVAR MW MVAR MW MVAR MW MVAR MW MVAR
tr2 chi_675 15.75 5.07 -15.72 -3.58 92.24 11.13 2.57 -11.11 -1.83 63.70 6.83 1.19 -6.80 -0.88 38.95
tr2 chi_676 16.08 5.18 -16.06 -3.65 94.18 11.37 2.62 -11.34 -1.86 65.04 6.97 1.22 -6.95 -0.90 39.77
tr2 chi_672 10.76 3.96 -10.76 -3.24 65.38 8.32 2.44 -8.32 -2.03 49.10 3.79 1.13 -3.79 -1.04 22.51
tr2 chi_671 10.62 3.89 -10.58 -3.16 80.61 8.21 2.40 -8.18 -1.96 60.57 3.76 1.11 -3.72 -0.99 27.53
tr2 Chiclayo Nuevo 18.87 6.43 -18.84 -5.19 66.30 14.56 3.89 -14.54 -3.17 49.79 6.64 1.80 -6.64 -1.65 22.83
tr2 La Via 4.54 1.79 -4.53 -1.49 98.74 4.51 1.78 -4.50 -1.48 97.86 3.55 1.35 -3.54 -1.16 76.59
tr2 lam_801 2.32 -0.39 -2.30 0.47 32.98 5.43 0.54 -5.39 -0.18 76.63 3.81 -0.03 -3.78 0.22 54.09
Cuadro N 11 Flujo de Potencia a travs de transformadores de dos devanados Avenida 2014 CON PROYECTO.

DLF SAC Pgina 16 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE
POTENCIA EN CHICLAYO OESTE Y CHICLAYO NORTE

ESCENARIO AVENIDA 2014 CON PROYECTO


MAXIMA DEMANDA
Transformador
HV MV LV %
MW MVAR MVA MW MVAR MVA MW MVAR MVA HV MV LV
tr3 chi_2671 30.59 5.55 31.09 -30.52 -3.79 30.75 0.00 0.00 0.00 64.00 60.00 0.00
tr3 chi_2672 30.59 5.55 31.09 -30.52 -3.79 30.75 0.00 0.00 0.00 64.00 60.00 0.00
tr3 chi_2672(1) 61.25 12.45 62.50 -61.07 -8.71 61.69 0.00 0.00 0.00 64.33 60.18 0.00
tr3 Chiclayo T3 11.02 3.17 11.46 -6.00 -1.50 6.18 -5.00 -1.25 5.15 37.28 38.09 25.33
tr3 pom_8001 4.74 1.86 5.09 -4.74 -1.56 4.99 0.00 0.00 0.00 72.97 71.51 0.00
tr3 tum_8001 3.08 1.14 3.29 -2.41 -0.79 2.54 -0.67 -0.22 0.71 47.33 35.11 34.50
tr3 cay_8001 1.95 0.63 2.05 -1.95 -0.58 2.03 0.00 0.00 0.00 29.56 29.27 0.00
tr3 illm_8001 4.29 -0.28 4.30 -2.91 1.09 3.11 -1.38 -0.53 1.48 85.56 61.46 58.73
Tr3 Motupe 5.67 1.36 5.83 -4.35 -1.03 4.47 -1.32 0.03 1.32 86.21 62.92 64.87
tr3 Olmos 2.90 0.61 2.96 -1.44 -0.23 1.46 -1.44 -0.23 1.46 34.24 16.69 50.27
tr3 occidente 1.26 -1.70 2.12 -1.26 1.76 2.16 0.00 0.00 0.00 31.39 31.39 0.00
tr3 Lambayeque Sur 7.97 2.78 8.44 0.00 0.00 0.00 -7.94 -2.53 8.34 33.17 0.00 41.35

ESCENARIO AVENIDA 2014 CON PROYECTO


MEDIA DEMANDA
Transformador
HV MV LV %
MW MVAR MVA MW MVAR MVA MW MVAR MVA HV MV LV
tr3 chi_2671 25.48 3.45 25.71 -25.43 -2.24 25.53 0.00 0.00 0.00 50.44 49.81 0.00
tr3 chi_2672 25.48 3.45 25.71 -25.43 -2.24 25.53 0.00 0.00 0.00 50.44 49.81 0.00
tr3 chi_2672(1) 51.05 8.05 51.69 -50.90 -5.41 51.19 0.00 0.00 0.00 50.70 49.94 0.00
tr3 Chiclayo T3 8.82 2.06 9.05 -4.80 -0.97 4.90 -4.00 -0.81 4.08 29.44 30.05 20.00
tr3 pom_8001 3.45 1.29 3.69 -3.45 -1.14 3.64 0.00 0.00 0.00 52.48 51.96 0.00
tr3 tum_8001 2.46 0.90 2.62 -1.77 -0.58 1.86 -0.69 -0.23 0.73 37.35 26.84 36.77
tr3 cay_8001 1.62 0.51 1.70 -1.62 -0.48 1.69 0.00 0.00 0.00 24.29 24.29 0.00
tr3 illm_8001 3.06 -0.85 3.17 -1.69 1.53 2.28 -1.37 -0.52 1.46 62.90 44.65 57.48
Tr3 Motupe 5.65 1.43 5.83 -4.09 -0.97 4.21 -1.56 -0.07 1.56 85.78 60.87 78.99
tr3 Olmos 2.74 0.57 2.80 -1.37 -0.21 1.38 -1.37 -0.21 1.38 32.23 16.03 48.27
tr3 occidente 1.14 -1.75 2.08 -1.14 1.80 2.13 0.00 0.00 0.00 30.71 30.71 0.00
tr3 Lambayeque Sur 7.97 2.78 8.44 0.00 0.00 0.00 -7.94 -2.53 8.34 33.17 0.00 41.35

ESCENARIO AVENIDA 2014 CON PROYECTO


MINIMA DEMANDA
Transformador
HV MV LV %
MW MVAR MVA MW MVAR MVA MW MVAR MVA HV MV LV
tr3 chi_2671 14.52 3.81 15.02 -14.51 -3.39 14.90 0.00 0.00 0.00 29.07 29.07 0.00
tr3 chi_2672 14.52 3.81 15.02 -14.51 -3.39 14.90 0.00 0.00 0.00 29.07 29.07 0.00
tr3 chi_2672(1) 29.04 8.38 30.22 -28.93 -7.34 29.84 0.00 0.00 0.00 29.26 29.12 0.00
tr3 Chiclayo T3 5.52 0.92 5.59 -3.00 -0.43 3.03 -2.50 -0.36 2.53 18.18 18.76 12.50
tr3 pom_8001 1.57 0.55 1.66 -1.57 -0.52 1.65 0.00 0.00 0.00 23.40 23.40 0.00

DLF SAC Pgina 17 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

tr3 tum_8001 1.86 0.66 1.97 -1.30 -0.43 1.37 -0.56 -0.18 0.59 27.81 19.66 29.49
tr3 cay_8001 1.21 0.38 1.27 -1.21 -0.36 1.26 0.00 0.00 0.00 17.91 18.09 0.00
tr3 illm_8001 2.42 0.95 2.60 -1.52 -0.50 1.59 -0.91 -0.35 0.97 51.70 32.08 39.28
Tr3 Motupe 3.85 1.21 4.04 -2.70 -0.64 2.78 -1.15 -0.38 1.21 59.20 41.23 63.10
tr3 Olmos 1.74 0.34 1.78 -0.87 -0.14 0.88 -0.87 -0.14 0.88 20.39 10.13 30.46
tr3 occidente 1.08 0.17 1.09 -1.08 -0.15 1.09 0.00 0.00 0.00 16.10 15.94 0.00
tr3 Lambayeque Sur 2.80 0.94 2.95 0.00 0.00 0.00 -2.78 -0.88 2.92 11.56 0.00 14.34
Cuadro N 12 Flujo de Potencia a travs de los transformador de potencia de 3 devanados
Estiaje 2014 CON PROYECTO.

Tension ESCENARIO ESTIAJE 2014 CON PROYECTO


BARRA Nominal MAXIMA DEMANDA MEDIA DEMANDA MINIMA DEMANDA
[kV] [KV] pu [KV] pu [KV] pu
CHICLAYO_OESTE_220 220 222.889 1.013 225.527 1.025 229.811 1.045
CHICL-O6 60 60.099 1.002 62.288 1.038 61.500 1.025
CHICL10A 10 10.100 1.010 10.132 1.013 10.065 1.006
CHICL10B 10 10.100 1.010 10.132 1.013 10.065 1.006
CHICL23 22.9 23.242 1.015 23.331 1.019 23.117 1.009
CHIL10N 10 10.175 1.017 10.205 1.020 10.102 1.010
CT CHICL10 10 10.100 1.010 10.132 1.013 10.065 1.006
CHICL60 60 60.099 1.002 61.313 1.022 61.038 1.017
CHICN10 10 9.918 0.992 9.963 0.996 9.985 0.998
CHICN10B 10 9.918 0.992 9.963 0.996 9.985 0.998
CHICN10C 10 9.918 0.992 9.963 0.996 9.985 0.998
POMAL60 60 59.724 0.995 61.043 1.017 60.886 1.015
TUMAN60 60 59.516 0.992 60.885 1.015 60.774 1.013
CAYAL60 60 59.303 0.988 60.720 1.012 60.659 1.011
ILLIMO60 60 60.351 1.006 61.382 1.023 60.447 1.007
LA_VIA60 60 59.246 0.987 60.343 1.006 59.572 0.993
MOTUP60 60 57.890 0.965 59.090 0.985 58.449 0.974
OLMOS60 60 57.615 0.960 58.878 0.981 58.099 0.968
OCCI60 60 57.780 0.963 59.077 0.985 57.938 0.966
LAMB_SUR_60 60 61.237 1.021 61.860 1.031 61.333 1.022
LAMBA60 60 61.231 1.021 61.813 1.030 61.308 1.022
Cuadro N 13 Niveles de tensin Escenario Estiaje 2014 CON PROYECTO.

DLF SAC Pgina 18 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA EN CHICLAYO OESTE Y CHICLAYO NORTE

ESCENARIO ESTIAJE 2014 CON PROYECTO


MAXIMA DEMANDA MEDIA DEMANDA MINIMA DEMANDA
BUS1 BUS 2
Terminal I Terminal J Terminal I Terminal J Terminal I Terminal J
% % %
MW MVAR MW MVAR MW MVAR MW MVAR MW MVAR MW MVAR
L1 Chiclayo Oeste Chiclayo Norte -25.03 -9.38 25.43 9.99 75.53 -19.62 -5.59 19.85 5.89 56.50 -9.42 -2.59 9.47 2.60 27.18
L2 Chiclayo Oeste Chiclayo Norte -25.03 -9.38 25.43 9.99 75.53 -19.62 -5.59 19.85 5.89 56.50 -9.42 -2.59 9.47 2.60 27.18
Chiclayo Norte Pomalca 9.81 3.28 -9.78 -3.26 18.29 7.56 2.30 -7.54 -2.33 13.70 4.65 1.14 -4.64 -1.20 8.34
Pomalca Tuman 5.05 1.43 -5.04 -1.50 9.35 4.09 1.04 -4.08 -1.12 7.36 3.07 0.66 -3.07 -0.75 5.51
Tuman Cayalti 1.95 0.36 -1.95 -0.63 3.66 1.62 0.23 -1.62 -0.51 2.96 1.21 0.09 -1.21 -0.38 2.21
L1 Chiclayo Oeste Illimo 9.74 0.67 -9.59 -0.66 45.97 8.91 0.10 -8.79 -0.19 41.33 6.52 1.31 -6.45 -1.54 31.66
L2 Chiclayo Oeste Illimo 9.74 0.67 -9.59 -0.66 45.97 8.91 0.10 -8.79 -0.19 41.33 6.52 1.31 -6.45 -1.54 31.66
L1 Illimo La Vina 7.23 0.66 -7.11 -0.76 34.84 7.05 0.52 -6.94 -0.64 33.34 5.10 0.95 -5.04 -1.14 25.01
L2 Illimo La Vina 7.65 0.94 -7.53 -1.10 37.10 7.47 0.78 -7.36 -0.97 35.50 5.38 1.17 -5.31 -1.42 26.66
La Vina Motupe 10.11 0.08 -9.88 -0.01 49.25 9.78 -0.15 -9.57 0.18 46.80 6.80 1.21 -6.69 -1.31 33.66
Motupe Olmos -4.17 1.31 4.21 -1.45 22.20 -3.89 1.47 3.93 -1.63 20.77 -2.82 -0.27 2.84 0.09 14.09
Olmos Occidente -1.26 1.70 1.27 -1.92 11.54 -1.14 1.81 1.15 -2.04 11.47 -1.08 -0.17 1.08 -0.07 5.42
Chiclayo Oeste Lambayeque Sur 8.83 1.77 -8.81 -1.80 15.05 13.46 3.31 -13.40 -3.24 22.86 6.62 0.81 -6.61 -0.88 11.15
Lambayeque Sur Lambayeque 2.32 -0.42 -2.32 0.39 3.96 5.43 0.47 -5.43 -0.50 9.04 3.81 -0.07 -3.81 0.03 6.37
Cuadro N 14 Flujo de Potencia a travs de las lneas de transmisin Estiaje 2014 CON PROYECTO.

ESCENARIO ESTIAJE 2014 CON PROYECTO


MAXIMA DEMANDA MEDIA DEMANDA MINIMA DEMANDA
Transformador
Terminal i Terminal j Terminal i Terminal j Terminal i Terminal j
% % %
MW MVAR MW MVAR MW MVAR MW MVAR MW MVAR MW MVAR
tr2 chi_675 12.72 3.20 -12.70 -2.24 73.14 11.13 2.57 -11.11 -1.83 63.49 6.83 1.19 -6.80 -0.88 38.95
tr2 chi_676 12.99 3.27 -12.96 -2.29 74.67 11.37 2.62 -11.34 -1.86 64.83 6.97 1.22 -6.95 -0.90 39.77
tr2 chi_672 10.76 4.28 -10.76 -3.53 66.06 8.48 2.48 -8.48 -2.04 50.01 3.79 1.13 -3.79 -1.04 22.52
tr2 chi_671 10.62 4.21 -10.58 -3.44 81.45 8.37 2.44 -8.33 -1.97 61.41 3.76 1.11 -3.72 -0.99 27.53
tr2 Chiclayo Nuevo 18.87 6.99 -18.84 -5.69 66.99 14.84 3.96 -14.82 -3.19 50.72 6.64 1.81 -6.64 -1.65 22.83
tr2 La Via 4.54 1.79 -4.53 -1.49 98.79 4.51 1.77 -4.50 -1.48 96.42 3.55 1.35 -3.54 -1.16 76.59
tr2 lam_801 2.32 -0.39 -2.30 0.47 32.98 5.43 0.50 -5.39 -0.15 75.58 3.81 -0.03 -3.78 0.22 54.09
Cuadro N 15 Flujo de Potencia a travs de transformadores de dos devanados Estiaje 2014 CON PROYECTO.

DLF SAC Pgina 19 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE
POTENCIA EN CHICLAYO OESTE Y CHICLAYO NORTE

ESCENARIO ESTIAJE 2014 CON PROYECTO


MAXIMA DEMANDA
Transformador
HV MV LV %
MW MVAR MVA MW MVAR MVA MW MVAR MVA HV MV LV
tr3 chi_2671 29.15 14.43 32.52 -29.07 -12.57 31.67 0.00 0.00 0.00 64.20 61.79 0.00
tr3 chi_2672 29.15 14.43 32.52 -29.07 -12.57 31.67 0.00 0.00 0.00 64.20 61.79 0.00
tr3 chi_2672(1) 58.04 30.24 65.45 -57.86 -26.28 63.54 0.00 0.00 0.00 64.60 61.99 0.00
tr3 Chiclayo T3 11.02 3.17 11.46 -6.00 -1.50 6.18 -5.00 -1.25 5.15 37.28 38.09 25.33
tr3 pom_8001 4.74 1.83 5.08 -4.74 -1.56 4.99 0.00 0.00 0.00 72.85 67.75 0.00
tr3 tum_8001 3.08 1.14 3.29 -2.41 -0.79 2.54 -0.67 -0.22 0.71 47.36 35.13 34.52
tr3 cay_8001 1.95 0.63 2.05 -1.95 -0.58 2.03 0.00 0.00 0.00 29.58 29.28 0.00
tr3 illm_8001 4.29 -0.28 4.30 -2.91 1.09 3.11 -1.38 -0.53 1.48 85.58 61.47 58.75
Tr3 Motupe 5.67 1.46 5.85 -4.35 -1.03 4.47 -1.32 -0.03 1.32 86.67 67.17 69.28
tr3 Olmos 2.90 0.61 2.96 -1.44 -0.23 1.46 -1.44 -0.23 1.46 34.29 17.06 51.37
tr3 occidente 1.26 -1.70 2.12 -1.26 1.76 2.16 0.00 0.00 0.00 31.38 31.38 0.00
tr3 Lambayeque Sur 7.97 2.77 8.44 0.00 0.00 0.00 -7.94 -2.53 8.34 32.74 0.00 40.81

ESCENARIO ESTIAJE 2014 CON PROYECTO


MEDIA DEMANDA
Transformador
HV MV LV %
MW MVAR MVA MW MVAR MVA MW MVAR MVA HV MV LV
tr3 chi_2671 25.76 14.20 29.41 -25.70 -12.71 28.67 0.00 0.00 0.00 57.38 55.23 0.00
tr3 chi_2672 25.76 14.20 29.41 -25.70 -12.71 28.67 0.00 0.00 0.00 57.38 55.23 0.00
tr3 chi_2672(1) 51.24 29.67 59.21 -51.07 -26.45 57.52 0.00 0.00 0.00 57.76 55.41 0.00
tr3 Chiclayo T3 8.82 2.06 9.05 -4.80 -0.97 4.90 -4.00 -0.81 4.08 29.07 30.04 20.00
tr3 pom_8001 3.45 1.29 3.69 -3.45 -1.14 3.64 0.00 0.00 0.00 51.78 51.26 0.00
tr3 tum_8001 2.46 0.90 2.62 -1.77 -0.58 1.86 -0.69 -0.23 0.73 36.85 26.48 36.27
tr3 cay_8001 1.62 0.51 1.70 -1.62 -0.48 1.69 0.00 0.00 0.00 23.96 23.96 0.00
tr3 illm_8001 3.06 -0.91 3.19 -1.69 1.59 2.32 -1.37 -0.52 1.46 62.39 44.81 56.67
Tr3 Motupe 5.65 1.45 5.83 -4.09 -0.97 4.21 -1.56 -0.09 1.56 84.60 61.86 80.33
tr3 Olmos 2.74 0.57 2.80 -1.37 -0.21 1.38 -1.37 -0.21 1.38 31.73 15.78 47.52
tr3 occidente 1.14 -1.81 2.14 -1.14 1.86 2.18 0.00 0.00 0.00 30.99 30.99 0.00
tr3 Lambayeque Sur 7.97 2.77 8.44 0.00 0.00 0.00 -7.94 -2.53 8.34 32.74 0.00 40.81

ESCENARIO ESTIAJE 2014 CON PROYECTO


MINIMA DEMANDA
Transformador
HV MV LV %
MW MVAR MVA MW MVAR MVA MW MVAR MVA HV MV LV
tr3 chi_2671 14.62 10.08 17.75 -14.59 -9.51 17.42 0.00 0.00 0.00 33.99 33.99 0.00
tr3 chi_2672 14.62 10.08 17.75 -14.59 -9.51 17.42 0.00 0.00 0.00 33.99 33.99 0.00
tr3 chi_2672(1) 29.00 20.99 35.80 -28.89 -19.63 34.93 0.00 0.00 0.00 34.27 34.08 0.00
tr3 Chiclayo T3 5.52 0.92 5.59 -3.00 -0.43 3.03 -2.50 -0.36 2.53 18.18 18.76 12.50
tr3 pom_8001 1.57 0.55 1.66 -1.57 -0.52 1.65 0.00 0.00 0.00 23.40 23.40 0.00

DLF SAC Pgina 20 de 132


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

tr3 tum_8001 1.86 0.66 1.97 -1.30 -0.43 1.37 -0.56 -0.18 0.59 27.81 19.66 29.49
tr3 cay_8001 1.21 0.38 1.27 -1.21 -0.36 1.26 0.00 0.00 0.00 17.91 18.09 0.00
tr3 illm_8001 2.42 0.95 2.60 -1.52 -0.50 1.59 -0.91 -0.35 0.97 51.70 32.08 39.28
Tr3 Motupe 3.85 1.21 4.04 -2.70 -0.64 2.78 -1.15 -0.38 1.21 59.20 41.23 63.10
tr3 Olmos 1.74 0.34 1.78 -0.87 -0.14 0.88 -0.87 -0.14 0.88 20.39 10.13 30.46
tr3 occidente 1.08 0.17 1.09 -1.08 -0.15 1.09 0.00 0.00 0.00 16.10 15.94 0.00
tr3 Lambayeque Sur 2.80 0.94 2.95 0.00 0.00 0.00 -2.78 -0.88 2.92 11.56 0.00 14.34
Cuadro N 16 Flujo de Potencia a travs de los transformador de potencia de 3 devanados
Estiaje 2014 CON PROYECTO.

Los resultados de las simulaciones de flujo de potencia en operacin normal se presentan


en el Anexo N III del presente documento.

RESULTADOS DE OPERACION EN CONTINGENCIA CON PROYECTO:

Se evalua la operacin de los transformadores T1, T2 y T3 de la S.E. Chiclayo Oeste ante


la contingenicia de salida de servicio de uno de ellos. Con la finalidad de no desatender el
suministro elctrico a las cargas en 10 kV se plantea la operacin de las barras 10 kV
como barra nica ante las contingencias sealadas. Los resultados son los siguientes:

En mxima demanda sin ningn grupo generador de la CT Chiclayo en servicio se


observa sobrecarga en el transformador T3 de 18.3% y 19.3% de su capacidad ante la
salida de servicio de del transformador T1 y T2 respectivamente (Fig. 4 y Fig. 5). Asi
tambin, ante la salida de servicio del transformador T3 se observa sobrecarga en los
tranformadores T1 y T2 del 7.3% y 9.5% respectivamente (Fig. 6).

En mxima demanda con tres grupos generadores de la CT Chiclayo en servicio (6.12


MW) no se observa sobrecarga en los transformadores que quedan en servicio (Fig. 13,
Fig. 14 y Fig. 15).
60.13
1.00
-69.68

En media y mnima demanda no se presentan sobrecargas ante dichas contingencias.


-25.03 -25.03
-8.80 -8.80
ZZ CTChicl 74.92 74.92
Chicl G1 Chicl G2 Chicl G3 Chicl G4 Chicl G5
~ ~ ~ ~ ~
G G G G G
SE. CHICLAYO OESTE
0.00
0.00

CT CHICL10 -9.59 -9
Lne ChiclayoOeste-ChiclayoNorte_L2

-0.60 -0
Lne ChiclayoOeste-ChiclayoNorte_L1

10.05 45.93 45
1.00
137.28 ILLIMO60
lod chicl23 lod chicl10n 60.37
1.01
17.00 14.78 -71.18
IN1007

L-6012

L-6022

L-6032

L-6033

3.83 3.40

6.00 5.00
Breaker/S..

Breaker/S..

1.50 1.25

CHICL23 CHIL10N CHICL10B


10.05 -2.91
22.94 10.05 1.09
1.00
1.00
-73.46
1.00
137.28 137.28 CHICL10A 85.56
-6.00 -23.18 Breaker/S.. 0.00 IN - 1008 -13.60
-1.50 -5.32 0.00 -3.16 10.05
118.34 118.34 79.57 1.00 ILLIMO23
tr3 Chiclayo T3 137.28 23.17
1.01
-74.67
-0.00 2.91
0 0 -2.05 0.96

0.
29.20
T3 ZZ Chicl
T1 13.62
T2 25.43 25.43 9.74 9.74
1

9.19 4.27 9.40 9.40 0.60 0.60


CHICL-O6 118.34 79.57 74.92 74.92 45.93 45.93

61.50
1.02
-68.61

-30.51 -30.51 -61.06 0.09 8.83


-3.79 -3.79 -8.71 -18.93 1.77 LAMB_SUR_60
63.99 63.99 64.32 61.91 15.05

Fig. 4: Transformador T1 SECHO F/S AV14MAX


-5. -5. -5.
61.24
1.02
-69.07
-8.81 6.48 2.32
tr2 chi_674

-1.80 2.23 -0.42


-0.00 -0.00 -0.00 15.05 33.46 3.96
0.00 0.00 0.00
DLF SAC tr3 chi_2671 63.99 63.99 tr3 chi_2672
Pgina 21 de 132 64.32 tr3 chi_2672(1) Revisin: 1
30.58 30.58 61.23 0.
10.27 10.27 10.25
5.55
63.99 SECHO1A 1.03 1.03 SECHO1B 5.55
63.99 1.03 SECHO1C 12.45
64.32
L-6037
-38.46 -38.46 -38.82 0.00
20.23
33.46
-0.00

61.91
0.00
ESTUDIO DE OPERATIVIDAD
60.13
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
1.00
-69.68 NORTE
-25.03 -25.03
-8.80 -8.80
ZZ CTChicl 74.92 74.92
Chicl G1 Chicl G2 Chicl G3 Chicl G4 Chicl G5
~ ~ ~ ~ ~
G G G G G
SE. CHICLAYO OESTE
0.00
0.00

CT CHICL10 -9.59 -9.5

Lne ChiclayoOeste-ChiclayoNorte_L2
-0.60 -0.6

Lne ChiclayoOeste-ChiclayoNorte_L1
10.05 45.93 45.9
1.00
137.25 ILLIMO60
lod chicl23 lod chicl10n 60.37
1.01
17.00 14.78 -71.18

IN1007

L-6012

L-6022

L-6032

L-6033
3.83 3.40

6.00 5.00

Breaker/S..

Breaker/S..
1.50 1.25

CHICL23 CHIL10N CHICL10B


10.05 -2.91
22.94 10.05 1.09
1.00
1.00
-73.49
1.00
137.25 137.25 CHICL10A 85.56
-6.00 -23.38 Breaker/S.. 0.00 -13.40 IN - 1008
-1.50 -5.36 0.00 -3.12 10.05
119.35 119.35 78.46 1.00 ILLIMO23
tr3 Chiclayo T3 137.25 23.17
1.01
-74.67
-0.00 2.91
0 0 -2.05 0.96

0.
29.39
T3 ZZ Chicl
13.43
T1 T2 25.43 25.43 9.74 9.74
1

9.27 4.21 9.40 9.40 0.60 0.60


CHICL-O6 119.35 78.46 74.92 74.92 45.93 45.93

61.50
1.02
-68.61

60.13
-30.51 -30.51 -61.06 0.09 8.83
1.00
-3.79 -3.79 -8.71 -18.95 1.77 LAMB_SUR_60
-68.37
63.99 63.99 64.32 61.98 15.05
61.24
Fig. 5: Transformador T2 SECHO F/S AV14MAX
-5. -5. -5.
-25.03 -25.03
1.02
-69.07
-8.81 6.48 2.32

tr2 chi_674
-8.80 -8.80 -1.80 2.23 -0.42
-0.00 -0.00 ZZ CTChicl 15.05 33.46 3.96
Chicl G1-0.00
Chicl G2 Chicl G3 Chicl G4 Chicl G5 74.92 74.92
0.00 0.00 0.00
tr3 chi_2671 63.99 63.99 tr3 chi_2672 ~ 64.32 tr3~chi_2672(1)
~ ~ ~
G G G G G
SE. CHICLAYO OESTE
30.58 30.58 61.23 0.
10.27 10.27 0.00 10.25
5.55
63.99 SECHO1A 1.03 1.03 SECHO1B 5.55
63.99
0.00 1.03 SECHO1C 12.45
64.32
L-6037
-38.46 -38.46 -38.82 0.00 -9.59 -9.59
CT CHICL10

Lne ChiclayoOeste-ChiclayoNorte_L2
20.26 -0.60 -0.60

Lne ChiclayoOeste-ChiclayoNorte_L1

33.46
-0.00
61.98 45.93 45.93

0.00
9.96
1.00
137.03 ILLIMO60
lod chicl23 lod chicl10n -6.46 60.37
-2.05 1.01
17.00 14.78 33.46 -69.87

IN1007

L-6012

L-6022

L-6032

L-6033
3.83 3.40

0.00 5.00
Breaker/S..

Breaker/S..
0.00 1.25

CHICL23 CHIL10N CHICL10B


9.96 -2.91
0.00 9.96 1.09
1.00
0.00
0.00
1.00
137.03 137.03 CHICL10A 85.56
Breaker/S.. 0.00 -18.20 IN - 1008 -18.58
0.00 -4.20 -4.28 9.96
107.31 109.57 1.00 ILLIMO23
tr3 Chiclayo T3 137.03 23.17
1.01
-73.36
-0.00 2.91
0 0 -2.05 0.96

0. T3 ZZ Chicl
18.22
T1 18.61
T2 25.43 25.43 9.74 9.74
1

6.20 6.33 9.40 9.40 0.60 0.60


CHICL-O6 107.31 109.57 74.92 74.92 45.93 45.93

61.50
1.02
-67.30

-29.02
60.53 -29.02 -58.03 0.07 8.83
1.01-4.35 -4.35 -9.78 -15.81 1.77 LAMB_SUR_60
-64.9561.07 61.07 61.39 51.77 15.05

Fig. 6: Transformador T3 SECHO F/S AV14MAX


61.24
-5. -5. -5. 1.02
-67.76
-8.81 6.48 2.32
-19.32 -19.32
tr2 chi_674

-1.80 2.23 -0.42


-5.53 -5.53 15.05 33.46 3.96
-0.00 -0.00 ZZ CTChicl -0.00 56.38 56.38
-0.00 -0.00 Chicl G1-0.00
Chicl G2 Chicl G3 Chicl G4 Chicl G5
tr3 chi_2671 61.07 61.07 tr3 chi_2672 61.39 tr3 chi_2672(1)
~ ~ ~ ~ ~
G G G G G
29.08
SE. CHICLAYO OESTE 29.08 58.20 0.
10.27 10.27 10.25
5.95
61.07 SECHO1A 1.03 1.03 SECHO1B 5.95 0.00
61.07 0.00 1.02 SECHO1C 13.21
61.39
L-6037
-37.16 -37.16 -37.50 0.00
CT CHICL10 16.76 -8.79 -8
Lne ChiclayoOeste-ChiclayoNorte_L2

33.46
-0.27 -0

-0.00
51.77

0.00
Lne ChiclayoOeste-ChiclayoNorte_L1

10.14 41.94 41
1.01
142.94 -6.46 ILLIMO60
lod chicl23 lod chicl10n -2.05 60.55
33.46 1.01
12.15 10.30 -66.46
IN1007

L-6012

L-6022

L-6032

L-6033

1.94 1.75

4.80 4.00
Breaker/S..

Breaker/S..

0.97 0.81

CHICL23 CHIL10N CHICL10B


10.14 -1.69
23.18 10.14 1.53
1.01
1.01
-67.62
1.01
142.94 142.94 CHICL10A 62.90
-4.80 -16.51 Breaker/S.. 0.00 IN - 1008 -9.94
-0.97 -2.78 0.00 -1.72 10.14
82.56 82.56 57.02 1.01 ILLIMO23
tr3 Chiclayo T3 142.94 23.40
1.02
-68.92
-0.00 1.69
0 0 -2.09 0.56

0.
21.33
T3 ZZ Chicl
T1 9.96
T2 19.55 19.55 8.92 8.92
1

4.99 2.31 5.83 5.83 0.20 0.20


CHICL-O6 82.56 57.02 56.38 56.38 41.94 41.94

61.50
1.02
-64.08

-25.42 -25.42 -50.89 0.06 13.46


-2.24 -2.24 -5.41 -12.83 3.36 LAMB_SUR_60
50.43 50.43 50.68 42.08 23.17

Fig. 7: Transformador T1 SECHO F/S AV14MED


61.06
-1. -1. -1. 1.02
-64.77
-13.40 7.97 5.43
tr2 chi_674

-3.28 2.78 0.51


-0.00 -0.00 -0.00 23.17 41.35 9.17
0.00 0.00 0.00
tr3 chi_2671 50.43 50.43 tr3 chi_2672 50.68 tr3 chi_2672(1)

25.47 25.47 51.04 0.


10.26 10.26 10.25
3.45
50.43 SECHO1A 1.03 1.03 SECHO1B 3.45
50.43 1.03 SECHO1C 8.05
50.68
L-6037
-33.96 -33.96 -34.26 -0.00
13.49
41.35
-0.00
-0.00

42.08

DLF SAC Pgina 22 de 132 Revisin: 1 -7.94


-2.53
41.35
ESTUDIO DE OPERATIVIDAD
60.53
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
1.01
-64.95 NORTE
-19.32 -19.32
-5.53 -5.53
ZZ CTChicl 56.38 56.38
Chicl G1 Chicl G2 Chicl G3 Chicl G4 Chicl G5
~ ~ ~ ~ ~
G G G G G
SE. CHICLAYO OESTE
0.00
0.00

CT CHICL10 -8.79 -8

Lne ChiclayoOeste-ChiclayoNorte_L2
-0.27 -0

Lne ChiclayoOeste-ChiclayoNorte_L1
10.14 41.94 41
1.01
142.92 ILLIMO60
lod chicl23 lod chicl10n 60.55
1.01
12.15 10.30 -66.46

IN1007

L-6012

L-6022

L-6032

L-6033
1.94 1.75

4.80 4.00

Breaker/S..

Breaker/S..
0.97 0.81

CHICL23 CHIL10N CHICL10B


10.14 -1.69
23.18 10.14 1.53
1.01
1.01
-67.64
1.01
142.92 142.92 CHICL10A 62.90
-4.80 -16.65 Breaker/S.. 0.00 -9.80 IN - 1008
-0.97 -2.81 0.00 -1.69 10.14
83.27 83.27 56.22 1.01 ILLIMO23
tr3 Chiclayo T3 142.92 23.40
1.02
-68.92
-0.00 1.69
0 0 -2.09 0.56

0.
21.47
T3 ZZ Chicl
9.82
T1 T2 19.55 19.55 8.92 8.92
1

5.03 2.28 5.83 5.83 0.20 0.20


CHICL-O6 83.27 56.22 56.38 56.38 41.94 41.94

61.50
1.02
-64.08

-25.42 -25.42 -50.89 0.06 13.46


-2.24 -2.24 -5.41 -12.85 3.36 LAMB_SUR_60
50.43 50.43 50.68 42.12 23.17

Fig. 8: Transformador T2 SECHO F/S AV14MED


61.06
-1. -1. -1. 1.02
-19.32 -19.32 -64.77
-13.40 7.97 5.43
-5.53 -5.53

tr2 chi_674
ZZ CTChicl -3.28 2.78 0.51
Chicl G1 -0.00
Chicl G2 Chicl G3 Chicl G4 Chicl G5 56.38 56.38 23.17 41.35 9.17
-0.00 -0.00
0.00 0.00 0.00
tr3 chi_2671 50.43 50.43 tr3 chi_2672 ~ ~
50.68 tr3 chi_2672(1) ~ ~ ~
G G G G G
SE. CHICLAYO OESTE
25.47 25.47 0.00 51.04 0.
10.26 10.26 3.45 0.00 10.25
3.45
50.43 SECHO1A 1.03 1.03 SECHO1B 50.43 1.03 SECHO1C 8.05
50.68
L-6037
-33.96 -33.96 CT CHICL10 -34.26 -8.79 -8.79
-0.00

Lne ChiclayoOeste-ChiclayoNorte_L2
-0.27 -0.27

Lne ChiclayoOeste-ChiclayoNorte_L1
13.51 41.94 41.94

41.35
10.10

-0.00
42.12

0.00
1.01
142.88 ILLIMO60
lod chicl23 lod chicl10n 60.55
-7.94 1.01
12.15 10.30 -2.53 -65.47

IN1007
41.35

L-6012

L-6022

L-6032

L-6033
1.94 1.75

0.00 4.00
Breaker/S..

Breaker/S..
0.00 0.81

CHICL23 CHIL10N CHICL10B


10.10 -1.69
0.00 10.10 1.53
1.01
0.00
0.00
1.01
142.88 142.88 CHICL10A 62.90
Breaker/S.. 0.00 -13.09 IN - 1008 -13.36
0.00 -2.23 -2.27 10.10
75.30 76.88 1.01 ILLIMO23
tr3 Chiclayo T3 142.88 23.40
1.02
-67.94
-0.00 1.69
0 0 -2.09 0.56

0. T3 ZZ Chicl
13.11
T1 13.39
T2 19.55 19.55 8.92 8.92
1

3.24 3.31 5.83 5.83 0.20 0.20


CHICL-O6 75.30 76.88 56.38 56.38 41.94 41.94

61.50
1.02
-63.10

-24.23 -24.23 -48.48 0.05 13.46


-2.60 -2.60 -6.08 -10.70 3.36 LAMB_SUR_60
48.15 48.15 48.40 35.16 23.17

Fig. 9: Transformador T3 SECHO F/S AV14MED


61.06
-1. -1. -1. 1.02
-63.79
-13.40 7.97 5.43
tr2 chi_674

61.04 -3.28 2.78 0.51


1.02 -0.00 -0.00 -0.00 23.17 41.35 9.17
-53.06 0.00 0.00 0.00
tr3 chi_2671 48.15 48.15 tr3 chi_2672 48.40 tr3 chi_2672(1)

-9.42 -9.42 0.
24.28 24.28 48.62 -2.59 -2.59
3.70 10.26 10.26 ZZ CTChicl
3.70 10.25 8.51Chicl G4 Chicl G5 L-6037
48.15 SECHO1A 1.03 1.03 SECHO1B 48.15
Chicl 1.03
G1 Chicl G2 Chicl G3
SECHO1C
48.40
27.17 27.17
-32.98 -32.98 -33.26 -0.00
~ ~ ~ 11.20 ~ ~
G G G G G
SE. CHICLAYO OESTE

41.35
-0.00
-0.00
35.16

224.39 0.00
1.02 0.00 8.49
-60.55 CHICLAYO_OESTE_220 1.06
-7.94
-2.53
CT CHICL10 -93.21 41.35 -6.45 -6
Lne ChiclayoOeste-ChiclayoNorte_L2

-1.54 -1
Lne ChiclayoOeste-ChiclayoNorte_L1

10.07 SVCCHI 31.66 31


1.01
155.49 ILLIMO60
lod chicl23 lod chicl10n 60.45
1.01
6.25 7.50 -54.27
IN1007

L-6012

L-6022

L-6032

L-6033

0.86 0.92

3.00 2.50
Breaker/S..

Breaker/S..

0.43 0.36

CHICL23 CHIL10N CHICL10B


10.07 -1.52
23.05 10.07 -0.50
1.01
1.01
-54.86
1.01
155.49 155.49 CHICL10A 51.70
-3.00 -10.13 Breaker/S.. 0.00 IN - 1008 -6.12
-0.43 -1.36 0.00 -0.78 10.07
50.72 50.72 35.01 1.01 ILLIMO23
tr3 Chiclayo T3 155.49 22.77
0.99
-56.27
1.52
1 1 0.50

1.
13.14
T3 ZZ Chicl
T1 6.15
T2 9.47 9.47 6.52 6.52
1

2.28 1.04 2.60 2.60 1.31 1.31


CHICL-O6 50.72 35.01 27.17 27.17 31.66 31.66

61.50
1.02
-52.64

-14.50 -14.50 -28.92 0.03 6.62


-3.40 -3.40 -7.34 2.19 0.81 LAMB_SUR_60
29.06 29.06 29.25 7.14 11.15
61.33

Fig. 10: Transformador T1 SECHO F/S AV14MIM


0. 0. 0. 1.02
-52.99
-6.61 2.80 3.81
tr2 chi_674

-0.88 0.94 -0.07


-0.00 -0.00 -0.00 11.15 14.34 6.37
-0.00 -0.00 0.00
tr3 chi_2671 29.06 29.06 tr3 chi_2672 29.25 tr3 chi_2672(1)

14.52 14.52 29.03 0.


10.26 10.26 10.25
3.81
29.06 SECHO1A 1.03 1.03 SECHO1B 3.81
29.06 1.02 SECHO1C 8.39
29.25
L-6037
DLF SAC -22.57 Pgina -22.57
23 de 132 -22.74 Revisin:
-0.00 1
-2.08
14.34
-0.00
-0.00

7.14

-2.78
-0.88
14.34
ESTUDIO DE OPERATIVIDAD
61.04
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
1.02
-53.06 NORTE
-9.42 -9.42
-2.59 -2.59
ZZ CTChicl 27.17 27.17
Chicl G1 Chicl G2 Chicl G3 Chicl G4 Chicl G5
~ ~ ~ ~ ~
G G G G G
SE. CHICLAYO OESTE
0.00
0.00

CT CHICL10 -6.45 -6.

Lne ChiclayoOeste-ChiclayoNorte_L2
-1.54 -1.

Lne ChiclayoOeste-ChiclayoNorte_L1
10.07 31.66 31
1.01
155.48 ILLIMO60
lod chicl23 lod chicl10n 60.45
1.01
6.25 7.50 -54.27

IN1007

L-6012

L-6022

L-6032

L-6033
0.86 0.92

3.00 2.50

Breaker/S..

Breaker/S..
0.43 0.36

CHICL23 CHIL10N CHICL10B


10.07 -1.52
23.05 10.07 -0.50
1.01
1.01
-54.88
1.01
155.48 155.48 CHICL10A 51.70
-3.00 -10.22 Breaker/S.. 0.00 -6.03 IN - 1008
-0.43 -1.37 0.00 -0.77 10.07
51.16 51.16 34.52 1.01 ILLIMO23
tr3 Chiclayo T3 155.48 22.77
0.99
-56.27
1.52
1 1 0.50

1.
13.23
T3 ZZ Chicl
6.06
T1 T2 9.47 9.47 6.52 6.52
1

2.30 1.03 2.60 2.60 1.31 1.31


CHICL-O6 51.16 34.52 27.17 27.17 31.66 31.66

61.50
1.02
-52.64

-14.50 -14.50 -28.92 0.03 6.62


-3.40 -3.40 -7.34 2.19 0.81 LAMB_SUR_60
29.06 29.06 29.25 7.12 11.15

Fig. 11: Transformador T2 SECHO F/S AV14MIM


61.33
0. 0. 0. 1.02
-52.99
-9.42 -9.42 -6.61 2.80 3.81

tr2 chi_674
-2.59 -2.59 -0.88 0.94 -0.07
-0.00 -0.00 ZZ CTChicl 11.15 14.34 6.37
Chicl G1 -0.00
Chicl G2 Chicl G3 Chicl G4 Chicl G5 27.17 27.17
0.00 0.00 -0.00
tr3 chi_2671 29.06 29.06 tr3 chi_2672 ~ 29.25 tr3~ chi_2672(1)
~ ~ ~
G G G G G
SE. CHICLAYO OESTE
14.52 14.52 0.00 29.03 0.
10.26 10.26 10.25
3.81
29.06 SECHO1A 1.03 1.03 SECHO1B 3.81 0.00
29.06 1.02 SECHO1C 8.39
29.25
L-6037
-22.57 -22.57 -22.74 -0.00 -6.45 -6.45
CT CHICL10

Lne ChiclayoOeste-ChiclayoNorte_L2
-2.07 -1.54 -1.54

Lne ChiclayoOeste-ChiclayoNorte_L1

14.34
-0.00
7.12

0.00
10.05 31.66 31.66
1.01
155.42 ILLIMO60
lod chicl23 lod chicl10n -2.78 60.45
-0.88 1.01
6.25 7.50 14.34 -53.69

IN1007

L-6012

L-6022

L-6032

L-6033
0.86 0.92

0.00 2.50
Breaker/S..

Breaker/S..
0.00 0.36

CHICL23 CHIL10N CHICL10B


10.05 -1.52
0.00 10.05 -0.50
1.01
0.00
0.00
1.01
155.42 155.42 CHICL10A 51.70
Breaker/S.. 0.00 -8.04 IN - 1008 -8.21
0.00 -1.06 -1.08 10.05
46.10 47.07 1.01 ILLIMO23
tr3 Chiclayo T3 155.42 22.77
0.99
-55.70
1.52
1 1 0.50

1. T3 ZZ Chicl
8.07
T1 8.23
T2 9.47 9.47 6.52 6.52
1

1.47 1.51 2.60 2.60 1.31 1.31


CHICL-O6 46.10 47.07 27.17 27.17 31.66 31.66

61.50
1.02
-52.06

-13.76
60.10 -13.76 -27.41 0.03 6.62
-3.55
1.00 -3.55 -7.62 3.12 0.81 LAMB_SUR_60
27.72
-59.48 27.72 27.91 10.16 11.15

Fig. 12: Transformador T3 SECHO F/S AV14MIM


61.33
0. 0. 0. 1.02
-52.41
-6.61 2.80 3.81
-25.03 -25.03
tr2 chi_674

-0.88 0.94 -0.07


-9.38 -9.38
-0.00 -0.00 ZZ CTChicl 11.15 14.34 6.37
0.00 0.00 Chicl G1-0.00
Chicl G2 Chicl G3 Chicl G4 Chicl G5
-0.00
75.53 75.53
tr3 chi_2671 27.72 27.72 tr3 chi_2672 27.91 tr3 chi_2672(1)
~ ~ ~ ~ ~
G G G G G
13.77
SE. CHICLAYO OESTE 13.77 27.52 0.
10.26 10.26 10.25
3.92
27.72 SECHO1A 1.03 1.03 SECHO1B 3.92 0.00
27.72 0.00
2.04
1.02
0.83
2.04
SECHO1C
0.83
2.04 8.59
0.8327.91
L-6037
-22.00 -22.00 -22.16
30.93 30.93 35.15 -0.00
CT CHICL10 -2.99 -9.59 -9
Lne ChiclayoOeste-ChiclayoNorte_L2

-0.66 -0

14.34
-0.00
-0.00
10.16
Lne ChiclayoOeste-ChiclayoNorte_L1

10.10 45.97 45
227.30 1.01
1.03 148.06 8.11 ILLIMO60
-50.63
lod chicl23 CHICLAYO_OESTE_220
lod chicl10n 1.01
-2.78
-0.88 60.35
-82.03 14.34 1.01
17.00 14.78 -60.99
IN1007

SVCCHI
L-6012

L-6022

L-6032

L-6033

3.83 3.40

6.00 5.00
Breaker/S..

Breaker/S..

1.50 1.25

CHICL23 CHIL10N CHICL10B


10.10 -2.91
23.06 10.10 1.09
1.01
1.01
-62.63
1.01
148.06 148.06 CHICL10A 85.58
-6.00 -18.99 Breaker/S.. 0.00 IN - 1008 -11.67
-1.50 -3.62 0.00 -2.38 10.10
95.72 95.72 67.56 1.01 ILLIMO23
tr3 Chiclayo T3 148.06 23.16
1.01
-64.49
-0.00 2.91
0 0 -2.05 0.96

0.
25.01
T3 ZZ Chicl
T1 11.69
T2 25.43 25.43 9.74 9.74
1

6.85 3.19 9.99 9.99 0.67 0.67


CHICL-O6 95.72 67.56 75.53 75.53 45.97 45.97

61.50
1.02
-58.43

-29.06 -29.06 -57.84 0.09 8.83


-12.57 -12.57 -26.28 18.30 1.77 LAMB_SUR_60
64.19 64.19 64.59 59.50 15.05

Fig. 13: Transformador T1 SECHO F/S ES14MAX


61.24
-3. -3. -3. 1.02
-58.89
-8.81 6.48 2.32
tr2 chi_674

-1.80 2.23 -0.42


-0.00 -0.00 -0.00 15.05 33.46 3.96
-0.00 -0.00 -0.00
tr3 chi_2671 64.19 64.19 tr3 chi_2672 64.59 tr3 chi_2672(1)

29.14 29.14 58.02 0.


10.27 10.27 10.24
14.43
64.19 SECHO1A 1.03 1.03 SECHO1B 14.43
64.19 1.02 SECHO1C 30.25
64.59
L-6037
-28.30 -28.30 -28.63 0.00
-17.09
33.46
-0.00

59.50
0.00

DLF SAC Pgina 24 de 132 Revisin: 1 -6.46


-2.05
33.46
ESTUDIO DE OPERATIVIDAD
60.10
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
1.00
-59.48 NORTE
-25.03 -25.03
-9.38 -9.38
ZZ CTChicl 75.53 75.53
Chicl G1 Chicl G2 Chicl G3 Chicl G4 Chicl G5
~ ~ ~ ~ ~
G G G G G
SE. CHICLAYO OESTE
0.00 2.04 2.04 2.04
0.00 0.85 0.85 0.85
31.04 31.04 35.29
CT CHICL10 -9.59 -9.

Lne ChiclayoOeste-ChiclayoNorte_L2
-0.66 -0.

Lne ChiclayoOeste-ChiclayoNorte_L1
10.10 45.97 45
1.01
148.04 ILLIMO60
lod chicl23 lod chicl10n 60.35
1.01
17.00 14.78 -60.99

IN1007

L-6012

L-6022

L-6032

L-6033
3.83 3.40

6.00 5.00

Breaker/S..

Breaker/S..
1.50 1.25

CHICL23 CHIL10N CHICL10B


10.10 -2.91
23.06 10.10 1.09
1.01
1.01
-62.66
1.01
148.04 148.04 CHICL10A 85.58
-6.00 -19.16 Breaker/S.. 0.00 -11.50 IN - 1008
-1.50 -3.61 0.00 -2.32 10.10
96.51 96.51 66.58 1.01 ILLIMO23
tr3 Chiclayo T3 148.04 23.16
1.01
-64.49
-0.00 2.91
0 0 -2.05 0.96

0.
25.18
T3 ZZ Chicl
11.53
T1 T2 25.43 25.43 9.74 9.74
1

6.86 3.13 9.99 9.99 0.67 0.67


CHICL-O6 96.51 66.58 75.53 75.53 45.97 45.97

61.50
1.02
-58.43

-29.06 -29.06 -57.84 0.09 8.83


-12.57 -12.57 -26.28 18.35 1.77 LAMB_SUR_60
64.19 64.19 64.59 59.66 15.05

Fig. 14: Transformador T2 SECHO F/S ES14MAX


61.24
-3. -3. -3. 1.02
-58.89
-25.03 -25.03 -8.81 6.48 2.32

tr2 chi_674
-9.38 -9.38 -1.80 2.23 -0.42
-0.00 -0.00 ZZ CTChicl 15.05 33.46 3.96
Chicl G1 -0.00
Chicl G2 Chicl G3 Chicl G4 Chicl G5 75.53 75.53
-0.00 -0.00 -0.00
tr3 chi_2671 64.19 64.19 tr3 chi_2672 64.59 tr3 chi_2672(1)
~ ~ ~ ~ ~
G G G G G
SE. CHICLAYO OESTE
29.14 29.14 0.00 0.
10.27 10.27 2.04
10.24 2.04 2.04 58.02
14.43
64.19 SECHO1A 1.03 1.03 SECHO1B 14.43 0.00
64.19
1.44
1.02 1.44
SECHO1C 1.44 30.25 L-6037
-28.30 -28.30 35.07
-28.63 35.07 39.86 64.59
0.00 -9.59 -9.59
CT CHICL10

Lne ChiclayoOeste-ChiclayoNorte_L2
-17.14 -0.66 -0.66

Lne ChiclayoOeste-ChiclayoNorte_L1

33.46
-0.00
59.66

0.00
10.10 45.97 45.97
1.01
147.93 ILLIMO60
lod chicl23 lod chicl10n -6.46 60.35
-2.05 1.01
17.00 14.78 33.46 -59.97

IN1007

L-6012

L-6022

L-6032

L-6033
3.83 3.40

0.00 5.00
Breaker/S..

Breaker/S..
0.00 1.25

CHICL23 CHIL10N CHICL10B


10.10 -2.91
0.00 10.10 1.09
1.01
0.00
0.00
1.01
147.93 147.93 CHICL10A 85.58
Breaker/S.. 0.00 -15.17 IN - 1008 -15.49
0.00 -2.06 -2.10 10.10
86.79 88.62 1.01 ILLIMO23
tr3 Chiclayo T3 147.93 23.16
1.01
-63.46
-0.00 2.91
0 0 -2.05 0.96

0. T3 ZZ Chicl
15.20
T1 15.52
T2 25.43 25.43 9.74 9.74
1

3.39 3.46 9.99 9.99 0.67 0.67


CHICL-O6 86.79 88.62 75.53 75.53 45.97 45.97

61.50
1.02
-57.40

61.31
-27.58 -27.58 -54.85 0.12 8.83
1.02
-12.93 -12.93 -26.95 22.87 1.77 LAMB_SUR_60
-61.5261.75 61.75 62.14 74.38 15.05

Fig. 15: Transformador T3 SECHO F/S ES14MAX


61.24
-3. -3. -3. 1.02
-57.86
-8.81 6.48 2.32
-19.62 -19.62
tr2 chi_674

-1.80 2.23 -0.42


-5.59 -5.59
-0.00 -0.00 ZZ CTChicl 15.05 33.46 3.96
0.00 0.00 Chicl G1-0.00
Chicl G2 Chicl G3 Chicl G4 Chicl G5
0.00
56.51 56.51
tr3 chi_2671 61.75 61.75 tr3 chi_2672 62.14 tr3 chi_2672(1)
~ ~ ~ ~ ~
G G G G G
SE. CHICLAYO OESTE 0.
27.65 27.65 55.03
10.27 10.27 10.24
14.65
61.75 SECHO1A 1.03 1.03 SECHO1B 14.65 0.00
61.75 0.00 1.02 SECHO1C 30.64
62.14
L-6037
-27.29 -27.29 -27.60 -0.00
CT CHICL10 -21.04 -8.79 -8
Lne ChiclayoOeste-ChiclayoNorte_L2

-0.19 -0

33.46
-0.00
-0.00
74.38
Lne ChiclayoOeste-ChiclayoNorte_L1

10.14 41.33 41
222.98 1.01
1.01 146.35 7.58 ILLIMO60
-54.61
lod chicl23 CHICLAYO_OESTE_220
lod chicl10n 0.95
-6.46
-2.05 61.38
-87.16 33.46 1.02
12.15 10.30 -62.99
IN1007

SVCCHI
L-6012

L-6022

L-6032

L-6033

1.94 1.75

4.80 4.00
Breaker/S..

Breaker/S..

0.97 0.81

CHICL23 CHIL10N CHICL10B


10.14 -1.69
23.18 10.14 1.59
1.01
1.01
-64.21
1.01
146.35 146.35 CHICL10A 62.39
-4.80 -16.51 Breaker/S.. 0.00 IN - 1008 -9.94
-0.97 -2.78 0.00 -1.72 10.14
82.53 82.53 56.82 1.01 ILLIMO23
tr3 Chiclayo T3 146.35 23.73
1.03
-65.39
-0.00 1.69
1 1 -2.15 0.56

1.
21.33
T3 ZZ Chicl
T1 9.96
T2 19.85 19.85 8.91 8.91
1

4.99 2.31 5.89 5.89 0.10 0.10


CHICL-O6 82.53 56.82 56.51 56.51 41.33 41.33

62.28
1.04
-60.67

-25.69 -25.69 -51.06 0.18 13.46


-12.73 -12.73 -26.48 29.34 3.31 LAMB_SUR_60
57.39 57.39 57.77 94.23 22.86

Fig. 16: Transformador T1 SECHO F/S ES14MED


61.86
-3. -3. -3. 1.03
-61.34
-13.40 7.97 5.43
tr2 chi_674

-3.24 2.77 0.47


-0.00 -0.00 -0.00 22.86 40.81 9.04
0.00 0.00 -0.00
tr3 chi_2671 57.39 57.39 tr3 chi_2672 57.77 tr3 chi_2672(1)

25.75 25.75 51.23 0.


10.40 10.40 10.37
14.21
57.39 SECHO1A 1.04 1.04 SECHO1B 14.21
57.39 1.04 SECHO1C 29.70
57.77
L-6037
-30.57 -30.57 -30.85 -0.00
-26.47
40.81
-0.00

94.23
0.00

DLF SAC Pgina 25 de 132 Revisin: 1 -7.94


-2.53
40.81
ESTUDIO DE OPERATIVIDAD
61.31
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
1.02
-61.52 NORTE
-19.62 -19.62
-5.59 -5.59
ZZ CTChicl 56.51 56.51
Chicl G1 Chicl G2 Chicl G3 Chicl G4 Chicl G5
~ ~ ~ ~ ~
G G G G G
SE. CHICLAYO OESTE
0.00
0.00

CT CHICL10 -8.79 -8

Lne ChiclayoOeste-ChiclayoNorte_L2
-0.19 -0

Lne ChiclayoOeste-ChiclayoNorte_L1
10.14 41.33 41
1.01
146.33 ILLIMO60
lod chicl23 lod chicl10n 61.38
1.02
12.15 10.30 -62.99

IN1007

L-6012

L-6022

L-6032

L-6033
1.94 1.75

4.80 4.00

Breaker/S..

Breaker/S..
0.97 0.81

CHICL23 CHIL10N CHICL10B


10.14 -1.69
23.18 10.14 1.59
1.01
1.01
-64.23
1.01
146.33 146.33 CHICL10A 62.39
-4.80 -16.65 Breaker/S.. 0.00 -9.80 IN - 1008
-0.97 -2.81 0.00 -1.69 10.14
83.25 83.25 56.01 1.01 ILLIMO23
tr3 Chiclayo T3 146.33 23.73
1.03
-65.39
-0.00 1.69
1 1 -2.15 0.56

1.
21.47
T3 ZZ Chicl
9.82
T1 T2 19.85 19.85 8.91 8.91
1

5.03 2.28 5.89 5.89 0.10 0.10


CHICL-O6 83.25 56.01 56.51 56.51 41.33 41.33

62.28
1.04
-60.67

-25.69 -25.69 -51.06 0.18 13.46


-12.73 -12.73 -26.49 29.34 3.31 LAMB_SUR_60
57.39 57.39 57.77 94.23 22.86

Fig. 17: Transformador T2 SECHO F/S ES14MED


61.86
-3. -3. -3. 1.03
-61.34
-13.40 7.97 5.43

tr2 chi_674
-19.62 -19.62 -3.24 2.77 0.47
-5.58 -5.58 22.86 40.81 9.04
-0.00 -0.00 ZZ CTChicl -0.00
56.39 56.39
-0.00 -0.00 Chicl G1 -0.00
Chicl G2 Chicl G3 Chicl G4 Chicl G5
tr3 chi_2671 57.39 57.39 tr3 chi_2672 57.77 tr3 chi_2672(1)
~ ~ ~ ~ ~
G G G G G
25.75
SE. CHICLAYO OESTE 25.75 51.23 0.
10.40 10.40 10.37
14.22
57.39 SECHO1A 1.04 1.04 SECHO1B 14.22 0.00
57.39 0.00 1.04 SECHO1C 29.71
57.77
L-6037
-30.57 -30.57 -30.85 -0.00
CT CHICL10 -26.46 -8.79 -8.79

Lne ChiclayoOeste-ChiclayoNorte_L2
-0.18 -0.18

40.81
-0.00
-0.00
Lne ChiclayoOeste-ChiclayoNorte_L1
94.23
10.12 41.25 41.25
1.01
146.14 ILLIMO60
-7.94
lod chicl23 lod chicl10n -2.53 61.50
40.81 1.02
12.15 10.30 -62.16

IN1007

L-6012

L-6022

L-6032

L-6033
1.94 1.75

0.00 4.00
Breaker/S..

Breaker/S..
0.00 0.81

CHICL23 CHIL10N CHICL10B


10.12 -1.69
0.00 10.12 1.60
1.01
0.00
0.00
1.01
146.14 146.14 CHICL10A 62.32
Breaker/S.. 0.00 -13.09 IN - 1008 -13.36
0.00 -2.23 -2.27 10.12
74.95 76.53 1.01 ILLIMO23
tr3 Chiclayo T3 146.14 23.78
1.03
-64.55
-0.00 1.69
1 1 -2.16 0.56

1. T3 ZZ Chicl
13.11
T1 13.39
T2 19.85 19.85 8.91 8.91
1

3.24 3.31 5.88 5.88 0.08 0.08


CHICL-O6 74.95 76.53 56.39 56.39 41.25 41.25

62.40
1.04
-59.85

-24.49
61.04 -24.49 -48.66 0.18 13.46
-12.56
1.02 -12.56 -26.10 29.45 3.30 LAMB_SUR_60
-56.7955.00 55.00 55.36 94.40 22.81

Fig. 18: Transformador T3 SECHO F/S ES14MED


61.97
-3. -3. -3. 1.03
-60.52
-13.40 7.97 5.43
-9.42 -9.42
tr2 chi_674

-3.23 2.77 0.46


-2.59 -2.59 22.81 40.73 9.03
-0.00 -0.00 ZZ CTChicl -0.00
27.18 27.18
0.00 0.00 Chicl G10.00Chicl G2 Chicl G3 Chicl G4 Chicl G5
tr3 chi_2671 55.00 55.00 tr3 chi_2672 55.36 tr3 chi_2672(1)
~ ~ ~ ~ ~
G G G G G
24.55
SE. CHICLAYO OESTE 24.55 48.82 0.
10.42 10.42 10.39
13.92
55.00 SECHO1A 1.04 1.04 SECHO1B 13.92 0.00
55.00 0.00 1.04 SECHO1C 29.08
55.36
L-6037
-29.76 -29.76 -30.02 -0.00
CT CHICL10 -26.56 -6.45 -6
Lne ChiclayoOeste-ChiclayoNorte_L2

40.73
-1.54 -1

-0.00
94.40

0.00
Lne ChiclayoOeste-ChiclayoNorte_L1

10.07 31.66 31
225.80 1.01
1.03
CHICLAYO_OESTE_220 151.76 7.53 -7.94 ILLIMO60
-57.44
lod chicl23 lod chicl10n 0.94 -2.53 60.45
-89.55 40.73 1.01
6.25 7.50 -58.00
SVCCHI
IN1007

L-6012

L-6022

L-6032

L-6033

0.86 0.92

3.00 2.50
Breaker/S..

Breaker/S..

0.43 0.36

CHICL23 CHIL10N CHICL10B


10.07 -1.52
23.05 10.07 -0.50
1.01
1.01
-58.60
1.01
151.76 151.76 CHICL10A 51.70
-3.00 -10.13 Breaker/S.. 0.00 IN - 1008 -6.12
-0.43 -1.36 0.00 -0.78 10.07
50.72 50.72 35.01 1.01 ILLIMO23
tr3 Chiclayo T3 151.76 22.77
0.99
-60.01
1.52
1 1 0.50

1.
13.14
T3 ZZ Chicl
T1 6.15
T2 9.47 9.47 6.52 6.52
1

2.28 1.04 2.60 2.60 1.31 1.31


CHICL-O6 50.72 35.01 27.18 27.18 31.66 31.66

61.50
1.03
-56.37

-14.59 -14.59 -28.87 0.16 6.62


-9.52 -9.52 -19.64 26.72 0.81 LAMB_SUR_60
33.98 33.98 34.26 86.90 11.15
61.33

Fig. 19: Transformador T1 SECHO F/S ES14MIM


0. 0. 0. 1.02
-56.72
-6.61 2.80 3.81
tr2 chi_674

-0.88 0.94 -0.07


-0.00 -0.00 -0.00 11.15 14.34 6.37
-0.00 -0.00 -0.00
tr3 chi_2671 33.98 33.98 tr3 chi_2672 34.26 tr3 chi_2672(1)

14.61 14.61 28.99 0.


10.26 10.26 10.24
10.08
33.98 SECHO1A 1.03 1.03 SECHO1B 10.08
33.98 1.02 SECHO1C 20.99
34.26
L-6037
-26.32 -26.32 -26.48 0.00
-24.26
14.34
-0.00

86.90
0.00

DLF SAC Pgina 26 de 132 Revisin: 1 -2.78


-0.88
14.34
ESTUDIO DE OPERATIVIDAD
61.04
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
1.02
-56.79 NORTE
-9.42 -9.42
-2.59 -2.59
ZZ CTChicl 27.18 27.18
Chicl G1 Chicl G2 Chicl G3 Chicl G4 Chicl G5
~ ~ ~ ~ ~
G G G G G
SE. CHICLAYO OESTE
0.00
0.00

CT CHICL10 -6.45 -6

Lne ChiclayoOeste-ChiclayoNorte_L2
-1.54 -1

Lne ChiclayoOeste-ChiclayoNorte_L1
10.07 31.66 31
1.01
151.74 ILLIMO60
lod chicl23 lod chicl10n 60.45
1.01
6.25 7.50 -58.00

IN1007

L-6012

L-6022

L-6032

L-6033
0.86 0.92

3.00 2.50

Breaker/S..

Breaker/S..
0.43 0.36

CHICL23 CHIL10N CHICL10B


10.07 -1.52
23.05 10.07 -0.50
1.01
1.01
-58.61
1.01
151.74 151.74 CHICL10A 51.70
-3.00 -10.22 Breaker/S.. 0.00 -6.03 IN - 1008
-0.43 -1.37 0.00 -0.77 10.07
51.16 51.16 34.52 1.01 ILLIMO23
tr3 Chiclayo T3 151.74 22.77
0.99
-60.01
1.52
1 1 0.50

1.
13.23
T3 ZZ Chicl
6.06
T1 T2 9.47 9.47 6.52 6.52
1

2.30 1.03 2.60 2.60 1.31 1.31


CHICL-O6 51.16 34.52 27.18 27.18 31.66 31.66

61.50
1.03
-56.37

-14.59 -14.59 -28.87 0.16 6.62


-9.52 -9.52 -19.64 26.72 0.81 LAMB_SUR_60
33.98 33.98 34.26 86.89 11.15

Fig. 20: Transformador T2 SECHO F/S ES14MIM


61.33
0. 0. 0. 1.02
-56.72
-6.61 2.80 3.81
-9.42 -9.42

tr2 chi_674
-0.88 0.94 -0.07
-2.59 -2.59 11.15 14.34 6.37
-0.00 -0.00 ZZ CTChicl
0.00 0.00 Chicl G1 -0.00
Chicl G2 Chicl G3 Chicl G4 Chicl G5
-0.00
27.18 27.18
tr3 chi_2671 33.98 33.98 tr3 chi_2672 34.26 tr3 chi_2672(1)
~ ~ ~ ~ ~
G G G G G
SE. CHICLAYO OESTE 0.
14.61 14.61 0.00 28.99
10.26 10.26 10.24
10.08
33.98 SECHO1A 1.03 1.03 SECHO1B 10.08 0.00
33.98 1.02 SECHO1C 20.99
34.26
L-6037
-26.32 -26.32 -26.48 0.00
CT CHICL10 -6.45 -6.45

Lne ChiclayoOeste-ChiclayoNorte_L2
-24.26 -1.54 -1.54

Lne ChiclayoOeste-ChiclayoNorte_L1

14.34
-0.00
-0.00
86.89 31.66 31.66
10.05
1.01
151.64 ILLIMO60
lod chicl23 lod chicl10n -2.78 60.45
-0.88 1.01
6.25 7.50 14.34 -57.48

IN1007

L-6012

L-6022

L-6032

L-6033
0.86 0.92

0.00 2.50
Breaker/S..

Breaker/S..
0.00 0.36

CHICL23 CHIL10N CHICL10B


10.05 -1.52
0.00 10.05 -0.50
1.01
0.00
0.00
1.01
151.64 151.64 CHICL10A 51.70
Breaker/S.. 0.00 -8.04 IN - 1008 -8.21
0.00 -1.06 -1.08 10.05
46.10 47.07 1.01 ILLIMO23
tr3 Chiclayo T3 151.64 22.77
0.99
-59.48
1.52
1 1 0.50

1. T3 ZZ Chicl
8.07
T1 8.23
T2 9.47 9.47 6.52 6.52
1

1.47 1.51 2.60 2.60 1.31 1.31


CHICL-O6 46.10 47.07 27.18 27.18 31.66 31.66

61.50
1.03
-55.85

-13.84 -13.84 -27.38 0.17 6.62


-9.70 -9.70 -19.98 27.77 0.81 LAMB_SUR_60
32.98 32.98 33.27 90.31 11.15

Fig. 21: Transformador T3 SECHO F/S ES14MIM


61.33
0. 0. 0. 1.02
-56.20
-6.61 2.80 3.81
tr2 chi_674

-0.88 0.94 -0.07


-0.00 -0.00 -0.00 11.15 14.34 6.37
-0.00 -0.00 -0.00
tr3 chi_2671 32.98 32.98 tr3 chi_2672 33.27 tr3 chi_2672(1)

13.87 13.87 27.49 0.


10.26 10.26 10.24
10.23
SECHO1A SECHO1B 10.23 21.26 L-6037
RESULTADOS DE CORRIENTE DE CARGA
32.98
EN BARRASECHO1C
60 KV: 1.03
-25.80
1.03
-25.80
32.98 1.02
-25.95
33.27
0.00
-25.12

14.34
-0.00
90.31

0.00
229.87
A continuacin se evaluaCHICLAYO_OESTE_220
1.04
-54.45la mxima corriente de carga a travs de los tramos de barra 60 7.44
0.93
-85.56
-2.78
-0.88
14.34
SVCCHI
kV de la SET Chiclayo Oeste.

La disposicin fsica de las bahas en 60 kV de la SET Chiclayo Oeste muestra que los
transformadores de potencia 220/60 kV y el transformador del SVC de REP se encuentran
a un lado (lado fuente) y las lneas en 60 kV y transformadores 60/10 kV de ENSA se
encuentran al otro extremo (lado carga). Esto facilita determinar que la mxima corriente de
carga que circula por un tramo de barra corresponde al tramo de barra que une ambas
propiedades y es la corriente de carga total de la distribucin.

La potencia de carga total de la SET Chiclayo Oeste es de 122.11 MW y 35.19 MVAR que
es igual a 1222 A de corriente de carga que es la mxima corriente de carga en un tramo
cuando se opera con una sola barra. Asi mismo, el valor de 1222 A es la mxima corriente
carga que podra circular por el interruptor de acoplamiento.

DLF SAC Pgina 27 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

4 ESTUDIO DE CORTOCIRCUITO

4.1 OBJETIVO
Verificar la capacidad trmica de los equipos, capacidad de ruptura de los interruptores de
potencia y la clase de precisin de los transformadores de corriente nuevos a ser instalados
en la SE Chiclayo Oeste 60/10 kV y SE Chiclayo Norte 60/10 kV.

4.2 METODOLOGIA
Para el estudio de cortocircuito se ha seguido el siguiente procedimiento:

Para obtener las corrientes de cortocircuito en operacin normal se han simulado fallas
trifsicas y monofsicas en las principales barras del sistema en estudio teniendo como
base los escenarios de flujos de potencia analizados.

Las corrientes de cortocircuito se han calculado de acuerdo al mtodo IEC 60909.

4.3 RESULTADOS
Los resultados de los clculos de las corrientes de cortocircuito se presentan en el Anexo
N IV, donde se muestran en cada barra:

Potencia de cortocircuito inicial Sk (en MVA),

Corriente de cortocircuito inicial Ik (en kA),

Corriente de cortocircuito pico Ip (en kA) y

Corriente de neutro 3xI0 (en kA) (para cortocircuitos monofsicos)

A modo de resumen se presentan los siguientes cuadros donde se muestran la corriente de


cortocircuito inicial Ik en barras, mximos y mnimos:

MAXIMAS CORRIENTES DE CORTOCIRCUITO


Tension ESCENARIO: ESTIAJE 2014 MAXIMA DEMANDA - BASE
BARRA Nominal TRIFASICO BIFASICO MONOFASICO
[kV] Skss Ikss Ip SkssB IkssB IpB SkssA 3xI0 IpA
[MVA] [kA] [kA] [MVA] [kA] [kA] [MVA] [kA] [kA]
CHICLAYO_OESTE_220 220 1770.7 4.6 11.1 505.8 4.0 9.6 669.6 5.3 12.6
CHICL-O6 60 1052.6 10.1 25.5 301.4 8.7 21.9 472.9 13.7 34.4
CHICL10A 10 401.7 23.2 62.3 114.0 19.8 53.0 3.3 0.6 1.5
CHICL10B 10 401.7 23.2 62.3 114.0 19.8 53.0 3.3 0.6 1.5
CHICL23 22.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
CHIL10N 10 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
CT CHICL10 10 401.7 23.2 62.3 114.0 19.8 53.0 3.3 0.6 1.5
CHICL60 60 701.2 6.7 14.2 201.2 5.8 12.3 268.0 7.7 16.3
CHICN10 10 302.4 17.5 42.5 87.1 15.1 36.7 2.2 0.4 0.9
CHICN10B 10 302.4 17.5 42.5 87.1 15.1 36.7 2.2 0.4 0.9

DLF SAC Pgina 28 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

CHICN10C 10 302.4 17.5 42.5 87.1 15.1 36.7 2.2 0.4 0.9
POMAL60 60 421.7 4.1 8.4 121.3 3.5 7.2 134.3 3.9 8.0
TUMAN60 60 289.0 2.8 5.7 83.2 2.4 4.9 88.8 2.6 5.2
CAYAL60 60 153.3 1.5 3.0 44.2 1.3 2.6 46.1 1.3 2.7
ILLIMO60 60 305.1 2.9 6.1 87.9 2.5 5.2 96.7 2.8 5.8
LA_VIA60 60 206.6 2.0 3.7 59.5 1.7 3.2 73.5 2.1 3.9
MOTUP60 60 124.2 1.2 2.1 35.8 1.0 1.8 46.3 1.3 2.3
OLMOS60 60 92.7 0.9 1.5 26.7 0.8 1.3 35.8 1.0 1.7
OCCI60 60 70.3 0.7 1.1 20.3 0.6 1.0 27.6 0.8 1.3
LAMB_SUR_60 60 526.7 5.1 11.3 151.4 4.4 9.7 194.1 5.6 12.5
LAMBA60 60 442.2 4.3 9.3 127.2 3.7 8.0 151.3 4.4 9.5
Cuadro N17 - Resultados de Cortocircuito Maximo Escenario ES14MAX BASE.

MINIMAS CORRIENTES DE CORTOCIRCUITO


Tension ESCENARIO: ESTIAJE 2014 MINIMA DEMANDA - BASE
BARRA Nominal TRIFASICO BIFASICO MONOFASICO
[kV] Skss Ikss Ip SkssB IkssB IpB SkssA 3xI0 IpA
[MVA] [kA] [kA] [MVA] [kA] [kA] [MVA] [kA] [kA]
CHICLAYO_OESTE_220 220 1057.5 2.8 6.7 304.4 2.4 5.8 438.7 3.5 8.3
CHICL-O6 60 724.0 7.0 17.3 208.6 6.0 15.0 336.7 9.7 24.2
CHICL10A 10 260.3 15.0 40.5 75.1 13.0 35.1 2.6 0.4 1.2
CHICL10B 10 260.3 15.0 40.5 75.1 13.0 35.1 2.6 0.4 1.2
CHICL23 22.9 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
CHIL10N 10 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
CT CHICL10 10 260.3 15.0 40.5 75.1 13.0 35.1 2.6 0.4 1.2
CHICL60 60 539.0 5.2 11.3 155.3 4.5 9.8 218.4 6.3 13.7
CHICN10 10 267.5 15.4 37.6 77.2 13.4 32.5 1.5 0.3 0.6
CHICN10B 10 267.5 15.4 37.6 77.2 13.4 32.5 1.5 0.3 0.6
CHICN10C 10 267.5 15.4 37.6 77.2 13.4 32.5 1.5 0.3 0.6
POMAL60 60 357.3 3.4 7.3 103.0 3.0 6.3 120.6 3.5 7.3
TUMAN60 60 257.3 2.5 5.1 74.2 2.1 4.4 82.6 2.4 5.0
CAYAL60 60 143.9 1.4 2.8 41.5 1.2 2.4 44.3 1.3 2.6
ILLIMO60 60 269.9 2.6 5.5 77.9 2.2 4.7 89.4 2.6 5.4
LA_VIA60 60 190.2 1.8 3.5 54.9 1.6 3.0 69.3 2.0 3.8
MOTUP60 60 118.3 1.1 2.0 34.1 1.0 1.7 44.6 1.3 2.2
OLMOS60 60 89.5 0.9 1.5 25.8 0.7 1.3 34.8 1.0 1.7
OCCI60 60 68.4 0.7 1.1 19.7 0.6 0.9 27.0 0.8 1.3
LAMB_SUR_60 60 429.3 4.1 9.3 123.8 3.6 8.1 166.5 4.8 10.9
LAMBA60 60 371.5 3.6 7.9 107.1 3.1 6.9 134.1 3.9 8.6
Cuadro N18 - Resultados de Cortocircuito Mnimo Escenario ES14MIN BASE.

A continuacin se muestran los resultados de las simulaciones de las mximas corrientes


de cortocircuito para la SE. Chilcayo Oeste, considerando en servicio el nuevo
transformador de potencia y el acoplamiento de barras en 10 kV cerrado.

DLF SAC Pgina 29 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

MAXIMAS CORRIENTES DE CORTOCIRCUITO


Tension ESCENARIO: ESTIAJE 2014 MAXIMA DEMANDA
BARRA Nominal TRIFASICO BIFASICO MONOFASICO
[kV] Skss Ikss Ip SkssB IkssB IpB SkssA 3xI0 IpA
[MVA] [kA] [kA] [MVA] [kA] [kA] [MVA] [kA] [kA]
CHICLAYO_OESTE_220 220 1778.6 4.7 11.2 507.9 4.0 9.6 674.1 5.3 12.7
CHICL-O6 60 1061.1 10.2 25.7 303.6 8.8 22.1 480.0 13.9 34.9
CHICL10A 10 574.7 33.2 88.0 163.8 28.4 75.2 3.3 0.6 1.5
CHICL10B 10 574.7 33.2 88.0 163.8 28.4 75.2 3.3 0.6 1.5
CHICL23 22.9 307.6 7.8 21.1 88.1 6.7 18.2 126.9 9.6 26.2
CHIL10N 10 547.3 31.6 83.8 156.0 27.0 71.7 3.2 0.5 1.5
CT CHICL10 10 574.7 33.2 88.0 163.8 28.4 75.2 3.3 0.6 1.5
Cuadro N19 - Resultados de Cortocircuito Maximo Escenario ES14MAX SET. Chiclayo Oeste.

A continuacin se muestran los resultados de las simulaciones de las mximas corrientes


de cortocircuito para la SE. Chilcayo Oeste, considerando en servicio los transformadores
de potencia T1 y T3 y el acoplamiento de barras en 10 kV cerrado.

MAXIMAS CORRIENTES DE CORTOCIRCUITO


Tension ESCENARIO: ESTIAJE 2014 MAXIMA DEMANDA
BARRA Nominal TRIFASICO BIFASICO MONOFASICO
[kV] Skss Ikss Ip SkssB IkssB IpB SkssA 3xI0 IpA
[MVA] [kA] [kA] [MVA] [kA] [kA] [MVA] [kA] [kA]
CHICLAYO_OESTE_220 220 1776.0 4.7 11.2 507.2 4.0 9.6 672.5 5.3 12.7
CHICL-O6 60 1058.4 10.2 25.6 302.9 8.7 22.0 477.3 13.8 34.7
CHICL10A 10 480.5 27.7 74.0 136.8 23.7 63.2 3.2 0.5 1.5
CHICL10B 10 504.5 29.1 77.7 143.6 24.9 66.4 3.3 0.6 1.5
CHICL23 22.9 283.1 7.1 19.5 81.0 6.1 16.7 118.3 8.9 24.4
CHIL10N 10 480.5 27.7 74.0 136.8 23.7 63.2 3.2 0.5 1.5
CT CHICL10 10 504.5 29.1 77.7 143.6 24.9 66.4 3.3 0.6 1.5
Cuadro N20 - Resultados de Cortocircuito Maximo Escenario ES14MAX SET. Chiclayo Oeste. Con T1 y
T3 en servicio y acoplamiento cerrado.

A continuacin se muestran los resultados de las simulaciones de las mximas corrientes


de cortocircuito para la SE. Chilcayo Oeste, considerando en servicio los transformadores
de potencia T2 y T3 y el acoplamiento de barras en 10 kV cerrado.

MAXIMAS CORRIENTES DE CORTOCIRCUITO


Tension ESCENARIO: ESTIAJE 2014 MAXIMA DEMANDA
BARRA Nominal TRIFASICO BIFASICO MONOFASICO
[kV] Skss Ikss Ip SkssB IkssB IpB SkssA 3xI0 IpA
[MVA] [kA] [kA] [MVA] [kA] [kA] [MVA] [kA] [kA]
CHICLAYO_OESTE_220 220 1776.1 4.7 11.2 507.2 4.0 9.6 672.5 5.3 12.7
CHICL-O6 60 1058.4 10.2 25.6 302.9 8.7 22.0 477.4 13.8 34.7
CHICL10A 10 506.1 29.2 77.9 144.1 25.0 66.6 3.3 0.6 1.5

DLF SAC Pgina 30 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

CHICL10B 10 482.0 27.8 74.2 137.2 23.8 63.4 3.2 0.5 1.5
CHICL23 22.9 283.7 7.2 19.5 81.2 6.1 16.8 118.5 9.0 24.5
CHIL10N 10 482.0 27.8 74.2 137.2 23.8 63.4 3.2 0.5 1.5
CT CHICL10 10 506.1 29.2 77.9 144.1 25.0 66.6 3.3 0.6 1.5
Cuadro N21 - Resultados de Cortocircuito Maximo Escenario ES14MAX SET. Chiclayo Oeste. Con T2 y
T3 en servicio y acoplamiento cerrado.

A continuacin se muestran los resultados de las simulaciones de las mximas corrientes


de cortocircuito para la SE. Chilcayo Oeste, considerando en servicio el nuevo
transformador de potencia y el acoplamiento de barras en 10 kV abierto.

MAXIMAS CORRIENTES DE CORTOCIRCUITO


Tension ESCENARIO: ESTIAJE 2014 MAXIMA DEMANDA
BARRA Nominal TRIFASICO BIFASICO MONOFASICO
[kV] Skss Ikss Ip SkssB IkssB IpB SkssA 3xI0 IpA
[MVA] [kA] [kA] [MVA] [kA] [kA] [MVA] [kA] [kA]
CHICLAYO_OESTE_220 220 1770.7 4.6 11.1 505.8 4.0 9.6 672.0 5.3 12.7
CHICL-O6 60 1052.6 10.1 25.5 301.4 8.7 21.9 476.8 13.8 34.6
CHICL10A 10 401.7 23.2 62.3 114.0 19.8 53.0 3.3 0.6 1.5
CHICL10B 10 401.7 23.2 62.3 114.0 19.8 53.0 3.3 0.6 1.5
CHICL23 22.9 208.1 5.2 14.5 60.0 4.5 12.5 91.3 6.9 19.1
CHIL10N 10 307.3 17.7 48.4 88.5 15.3 41.8 0.0 0.0 0.0
CT CHICL10 10 401.7 23.2 62.3 114.0 19.8 53.0 3.3 0.6 1.5
Cuadro N22 - Resultados de Cortocircuito Maximo Escenario ES14MAX SET. Chiclayo Oeste.

A continuacin se muestran los resultados de las simulaciones de las mximas corrientes


de cortocircuito para la SE. Chilcayo Norte, considerando en servicio el transformador de
potencia T2 y el acoplamiento de barras en 10 kV cerrado:

MAXIMAS CORRIENTES DE CORTOCIRCUITO


Tension ESCENARIO: ESTIAJE 2014 MAXIMA DEMANDA
BARRA Nominal TRIFASICO BIFASICO MONOFASICO
[kV] Skss Ikss Ip SkssB IkssB IpB SkssA 3xI0 IpA
[MVA] [kA] [kA] [MVA] [kA] [kA] [MVA] [kA] [kA]
CHICLAYO_OESTE_220 220 1770.7 4.6 11.1 505.8 4.0 9.6 672.0 5.3 12.7
CHICL60 60 701.2 6.7 14.2 201.2 5.8 12.3 277.0 8.0 16.9
CHICN10 10 356.2 20.6 49.1 102.5 17.8 42.4 2.2 0.4 0.9
CHICN10B 10 356.2 20.6 49.1 102.5 17.8 42.4 2.2 0.4 0.9
CHICN10C 10 356.2 20.6 49.1 102.5 17.8 42.4 2.2 0.4 0.9
Cuadro N23 - Resultados de Cortocircuito Maximo Escenario ES14MAX SET. Chiclayo Norte.

DLF SAC Pgina 31 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

Del anlisis de los resultados de cortocircuito se tienen las siguientes observaciones:

Los interruptores de potencia a instalarse en las nuevas bahas 10 kV de la SET


Chiclayo Oeste, tienen una capacidad de ruptura de 25 kA, por lo que no se
recomienda cerrar el acoplamiento de barras de 10kV, debido a que la corriente
mxima de cortocircuito en barras obtenida es de 33.2 kA. Con el acoplamiento abierto
la mxima corriente cortocircuito en barras del nuevo transformador de potencia es de
17.7 kA.

Para condiciones de contingencias con el transformador T1 y T3 (o T2 y T3) en servicio,


con el acoplamiento cerrado en la SET Chiclayo Oeste, se obtiene una corriente de
cortocircuito en barra 10 kV de 27.7 kA, valor que supera la capacidad de ruptura de los
interruptores por lo que no se recomienda operar con el acoplamiento cerrado aun en
dichas contingencias, en condiciones de mxima demanda.

Los interruptores de potencia de la SE. Chiclayo Norte, tienen una capacidad de ruptura
de 25 kA y 31.5 kA, considerando en servicio el transformador de potencia T2 de 14
MVA se obtine una mxima corriente de cortocircuito de 20.6 kA.

DLF SAC Pgina 32 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

5 ESTUDIO DE COORDINACION DE LAS PROTECCIONES

5.1 CRITERIOS DE AJUSTE

5.1.1 CRITERIOS BASICOS DE PROTECCION


El objetivo principal del sistema de Proteccin es proporcionar, en forma rpida, el
aislamiento de un rea de falla en el sistema y, de este modo, poder mantener en
funcionamiento la mayor parte del sistema elctrico restante. Dentro de este contexto
existen seis requerimientos bsicos para la aplicacin del rel de proteccin:

a) Fiabilidad.- Seguridad de que la proteccin se llevar a cabo correctamente,


tiene dos componentes: confianza y seguridad.

b) Selectividad.- Continuidad mxima del servicio con mnima desconexin del


sistema.

c) Rapidez de operacin.- Duracin mnima de una falla, as como un menor


dao en los equipos del sistema.

d) Simplicidad.- Menor equipo de proteccin y circuitos asociados para lograr los


objetivos de proteccin.

e) Economa.- Mayor proteccin a menor costo total.

El trmino proteccin no implica que el equipo de proteccin pueda prevenir fallas o


deficiencia de los equipos. Los rels de proteccin slo se ponen en funcionamiento
despus que haya ocurrido una condicin insostenible. Sin embargo, su funcin es
minimizar los daos a equipos fallados, reducir el tiempo y costo de interrupcin as
como el de reparacin y problemas afines que pudieran ocurrir.

La proteccin del sistema elctrico y de los equipos es muy importante, en vista que
una falla en cualquiera de ellos puede dejar sin suministro un rea entera, adems de
poner en riesgo la estabilidad del sistema de potencia.

5.1.2 CRITERIOS PARA EL AJUSTE DE LA PROTECCION DIFERENCIAL DE


TRANSFORMADOR (87T)

La proteccin diferencial compara las corrientes de entrada y salida del transformador


por fase, las cuales dejan de ser iguales si hay fallas internas que deriven corrientes por
caminos no previstos.

El ajuste de la funcin de proteccin diferencial porcentual debe evitar que se


produzcan actuaciones indeseadas ante corrientes diferenciales que puedan aparecer
cuando ocurran fallas externas cercanas al transformador. Para esto se determinan las
mximas corrientes a travs de los transformadores de corriente simulando fallas
externas, tanto en el lado de alta como en el lado de baja tensin del transformador y se
avala el impacto que podran tener sobre la proteccin diferencial.

DLF SAC Pgina 33 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

Uno de los parmetros ms importantes a ser ajustado, que es la corriente diferencial,


se halla a partir de la diferencia entre los valores de corriente presente en los
secundarios de los transformadores de corriente en ambos lados del equipo a proteger.

Otro de los parmetros a ser ajustado es la pendiente de estabilizacin la cual


compensa los errores insertados al rel por los transformadores de corriente y por el
cambiador automtico de taps.

5.1.3 CRITERIOS PARA EL AJUSTE DE LA PROTECCION DE SOBRECORRIENTE (50/51


50N/51N)
La proteccin de sobrecorriente mide la corriente que circula por el circuito protegido y
emite su disparo al interruptor asociado cuando la corriente medida supera el umbral de
arranque (corriente de arranque) ajustado y una vez agotado su tiempo de ajuste.

La corriente de arranque de la proteccin sobrecorriente de fases se ajusta como


mnimo al 130% de la mxima corriente de carga del circuito a proteger, la curva de
operacin y el dial de tiempo se seleccionan para coordinar con las protecciones
adyacentes.

La corriente de arranque de la proteccin sobrecorriente de tierra debe ser como


mnimo el 10% de la corriente nominal del transformador de corriente, la curva de
operacin y el dial de tiempo se seleccionan para coordinar con las protecciones
adyacentes.

Para la determinacin de los tiempos de actuacin se evaluar la coordinacin entre


rels de proteccin teniendo en cuenta que se garantice un tiempo de coordinacin
mnimo de 0.2 segundos.

DLF SAC Pgina 34 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

5.2 CALCULOS JUSTIFICATIVOS

5.2.1 SE CHICLAYO OESTE: TRANSFORMADOR DE POTENCIA TR1 Y TR2 60/10 KV


Datos del Transformador de Potencia TR1:

Potencia Nominal : 14-17.5 MVA (ONAN-ONAF)


Tensin Nominal : 60 8x1.25% / 10 KV
Corriente Nominal : 134.71-168.4 / 808.3-1010.36 A (ONAN-ONAF)
Datos del Transformador de Potencia TR2:

Potencia Nominal : 14-17.5 MVA (ONAN-ONAF)


Tensin Nominal : 60 8x1.25% / 10 KV
Corriente Nominal : 134.71-168.4 / 808.3-1010.36 A (ONAN-ONAF)
Datos de los Transformadores de Corriente:

TC de Fases AT : 200 / 5 A
TC de Fases BT : 1000 / 5 A
Datos del Rel de Proteccin Diferencial:

Marca y modelo : Siemens 7UT633


Datos del Rel de Proteccin Sobrecorriente:

Marca y modelo : Siemens 7SJ642

PROTECCION DIFERENCIAL DE TRANSFORMADOR SIEMENS 7UT633

Los ajustes actuales se consideran adecuados y por ser una proteccin unitaria no
requiere su coordinacin con otras protecciones.

PROTECCION DE SOBRECORRIENTE DE FASES

En el siguiente cuadro se muestran los ajustes actuales de las protecciones de


sobrecorriente de fases de los transformadores TR1 y TR2, donde se muestra resaltado
en color amaillo el incremento de corriente de arranque del umbral 2 del lado 60 kV,
para evitar operar ante fallas en 10 kV en 250 ms.
Proteccin Ajuste Umbral 1 Ajuste Umbral 2
Direcc
Ubicacin Rel TC I> T> Curva1 I>> T>> Curva2

SECHO SIEMENS
200/5 240 0.16 IEC NI 2000 0.25 DT --
TR1 - 60KV 7UT633

SECHO SIEMENS
200/5 240 0.16 IEC NI 2000 0.25 DT --
TR2 - 60KV 7UT633

SECHO SIEMENS
1000/5 1040 0.14 IEC NI -- -- -- --
TR1 - 10KV 7SJ642

DLF SAC Pgina 35 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

SECHO SIEMENS
1000/5 1040 0.14 IEC NI -- -- -- --
TR2 - 10KV 7SJ642

SECHO SIEMENS
500/5 450 0.10 IEC NI 5000 0.0 DT --
C217 10KV 7SJ642

SECHO SIEMENS
500/5 450 0.10 IEC NI 5000 0.0 DT --
C215 10KV 7SJ642

SECHO SIEMENS
250/5 300 0.12 IEC NI 5000 0.0 DT --
C216 10KV 7SJ642

SECHO SIEMENS
250/5 300 0.12 IEC NI 5000 0.0 DT --
C214 10KV 7SJ642

SECHO SIEMENS
500/5 400 0.10 IEC NI 5000 0.0 DT --
C211 10KV 7SJ642

SECHO SIEMENS
250/5 250 0.12 IEC NI 5000 0.0 DT --
C221 10KV 7SJ642

SECHO SIEMENS
250/5 300 0.16 IEC NI 5000 0.0 DT --
C212 10KV 7SJ642

SECHO SIEMENS
500/5 400 0.10 IEC NI 5000 0.0 DT --
C219 10KV 7SJ642

SECHO SIEMENS
1200/5 480 0.08 IEC NI 3500 0.0 DT FORW
CT 10KV 7SJ642

Cuadro N24 - Ajustes de sobrecorriente de fases TR1 y TR2 en SECHO 60/10 kV.

DIgSILENT
I I=1279.251
=1279.270
=1306.189pri.A
=1306.208 pri.A
10

SECHO C211 10KV


IEC 255-3 inverse SECHO C215 10KV
Ipset: 400.00 pri.A IEC 255-3 inverse
Tpset: 0.10 Ipset: 450.00 pri.A Transformer Damage Curve
Tripping T ime: 9999.999 s Tpset: 0.10 Srat: 17.50 MVA
Tripping T ime: 9999.999 s uk: 9.70 %
Ipeak: 12.00/0.10 s
SECHO C212 10KV
IEC 255-3 inverse SECHO CT 10KV
Ipset: 300.00 pri.A IEC 255-3 inverse
Tpset: 0.16 Ipset: 480.00 pri.A
Tripping T ime: 9999.999 s Tpset: 0.08
Tripping T ime: 9999.999 s

SECHO C214 10KV


IEC 255-3 inverse
Ipset: 300.00 pri.A
Tpset: 0.12
Tripping T ime: 9999.999 s

SECHO C221 10KV


[s] IEC 255-3 inverse
Ipset: 250.00 pri.A
Tpset: 0.12
Tripping T ime: 9999.999 s

0.658
0.650ss

0.481
0.475ss

SECHO CT 10KV
Ipset: 3499.20 pri.A
Tset: 0.00 s
Tripping T ime: 9999.999 s

SECHO C221 10KV


Ipset: 5000.00 pri.A
Tset: 0.00 s
Tripping T ime: 9999.999 s

0.1
60.00 kV 10 100 1000 [pri.A] 10000

10.00 kV 100 1000 10000


CHICL-O6\Cub_11(1)\SECHO T 1 60KV CHICL-O6\Cub_12(1)\SECHO T 2 60KV
CHICL10B\Cub_9\SECHO T 1 10KV CHICL10A\Cub_10(1)\SECHO T 2 10KV
Transformer Damage Curve CHICL10B\Cub_12\SECHO C214 10KV
CHICL10B\Cub_12\SECHO C215 10KV CHICL10B\Cub_12\SECHO C211 10KV
CHICL10B\Cub_12\SECHO C212 10KV CHICL10B\Cub_12\SECHO C221 10KV
CHICL10B\Cub_12\SECHO CT 10KV

Figura N 22 - Tiempos de actuacin para una falla trifsica franca en barra 10 kV en


operacin normal.

DLF SAC Pgina 36 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

DIgSILENT
I =1497.289
=1497.312 pri.A
10

SECHO C211 10KV


IEC 255-3 inverse SECHO C215 10KV
Ipset: 400.00 pri.A IEC 255-3 inverse
Tpset: 0.10 Ipset: 450.00 pri.A Transformer Damage Curve
Tripping T ime: 9999.999 s Tpset: 0.10 Srat: 17.50 MVA
Tripping T ime: 9999.999 s uk: 9.70 %
Ipeak: 12.00/0.10 s
SECHO C212 10KV
IEC 255-3 inverse SECHO CT 10KV
Ipset: 300.00 pri.A IEC 255-3 inverse
Tpset: 0.16 Ipset: 480.00 pri.A
Tripping T ime: 9999.999 s Tpset: 0.08
Tripping T ime: 9999.999 s

SECHO C214 10KV


IEC 255-3 inverse
Ipset: 300.00 pri.A
Tpset: 0.12
Tripping T ime: 9999.999 s

SECHO C221 10KV


[s] IEC 255-3 inverse
Ipset: 250.00 pri.A
Tpset: 0.12
Tripping T ime: 9999.999 s

0.601 s

0.445 s

SECHO CT 10KV
Ipset: 3499.20 pri.A
Tset: 0.00 s
Tripping T ime: 9999.999 s

SECHO C221 10KV


Ipset: 5000.00 pri.A
Tset: 0.00 s
Tripping T ime: 9999.999 s

0.1
60.00 kV 10 100 1000 [pri.A] 10000

10.00 kV 100 1000 10000


CHICL-O6\Cub_11(1)\SECHO T 1 60KV CHICL-O6\Cub_12(1)\SECHO T 2 60KV
CHICL10B\Cub_9\SECHO T 1 10KV CHICL10A\Cub_10(1)\SECHO T 2 10KV
Transformer Damage Curve CHICL10B\Cub_12\SECHO C214 10KV
CHICL10B\Cub_12\SECHO C215 10KV CHICL10B\Cub_12\SECHO C211 10KV
CHICL10B\Cub_12\SECHO C212 10KV CHICL10B\Cub_12\SECHO C221 10KV
CHICL10B\Cub_12\SECHO CT 10KV

Figura N 23 - Tiempos de actuacin para una falla trifsica franca en barra 10 kV en


contingencia TR2 F/S.

PROTECCION DE SOBRECORRIENTE DE TIERRA

En el siguiente cuadro se muestran los ajustes actuales de las protecciones de


sobrecorriente de tierra de los transformadores TR1 y TR2. Las protecciones del lado
60 kV con independientes del lado 10 kV por el tipo de conexionado de los
transformadores. Se consideran adecuados los ajustes actuales.
Proteccin Ajuste Umbral 1 Ajuste Umbral 2
Direcc
Ubicacin Rel TC I> T> Curva1 I>> T>> Curva2

SECHO SIEMENS
200/5 50 0.40 IEC NI 600 0.10 DT --
TR1 - 60KV 7UT633

SECHO SIEMENS
200/5 50 0.40 IEC NI 600 0.10 DT --
TR2 - 60KV 7UT633

SECHO SIEMENS
240/1 60 0.11 IEC NI -- -- -- --
TR1 - 10KV 7SJ642

SECHO SIEMENS
240/1 60 0.11 IEC NI -- -- -- --
TR2 - 10KV 7SJ642

SECHO SIEMENS
50/1 7.5 0.75 DT 75 0.0 DT --
C217 10KV 7SJ642

SECHO SIEMENS
50/1 7.5 0.75 DT 75 0.0 DT --
C215 10KV 7SJ642

SECHO SIEMENS
50/1 7.5 0.75 DT 180 0.5 DT --
C216 10KV 7SJ642

DLF SAC Pgina 37 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

SECHO SIEMENS
50/1 7.5 0.75 DT 180 0.5 DT --
C214 10KV 7SJ642

SECHO SIEMENS
50/1 7.5 0.75 DT 75 0.0 DT --
C211 10KV 7SJ642

SECHO SIEMENS
50/1 7.5 0.75 DT 180 0.5 DT --
C221 10KV 7SJ642

SECHO SIEMENS
50/1 7.5 0.75 DT 180 0.5 DT --
C212 10KV 7SJ642

SECHO SIEMENS
50/1 7.5 1.0 DT 75 0.0 DT --
C219 10KV 7SJ642

SECHO SIEMENS
50/1 60 0.11 IEC NI -- -- -- FORW
CT 10KV 7SJ642

Cuadro N25 - Ajustes de sobrecorriente de tierra TR1 y TR2 en SECHO 60/10 kV.

DIgSILENT
3*I0
3*I0=459.262
=468.934pri.A
pri.A
10

SECHO T1 60KV
IEC 255-3 inverse
Ipset: 50.00 pri.A
Tpset: 0.40 Transformer Damage Curve
Tripping T ime: 1.235 s Srat: 17.50 MVA
SECHO T2 60KV uk: 9.70 %
IEC 255-3 inverse Ipeak: 12.00/0.10 s
Ipset: 50.00 pri.A
Tpset: 0.40
Tripping T ime: 1.223 s

SECHO T1 10KV
IEC 255-3 inverse
Ipset: 60.00 pri.A
Tpset: 0.11
Tripping T ime: 9999.999 s

SECHO T2 10KV
[s] IEC 255-3 inverse
Ipset: 60.00 pri.A
Tpset: 0.11
Tripping T ime: 9999.999 s

1.235
1.223ss

SECHO T2 60KV
Ipset: 600.00 pri.A
Tset: 0.10 s
Tripping T ime: 9999.999 s

0.1
60.00 kV 10 100 1000 [pri.A] 10000

10.00 kV 100 1000 10000


CHICL-O6\Cub_11(1)\SECHO T 1 60KV CHICL-O6\Cub_12(1)\SECHO T 2 60KV
CHICL10B\Cub_9\SECHO T 1 10KV CHICL10A\Cub_10(1)\SECHO T 2 10KV
Transformer Damage Curve

Figura N 24 - Tiempos de actuacin para una falla monofsica franca en barra 60 kV


SE SECHO en operacin normal.

DLF SAC Pgina 38 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

DIgSILENT
10

ZZ SECHO
Ipset: 30.00 pri.A
Tset: 1.00 s

SECHO T1 10KV
IEC 255-3 inverse
Ipset: 60.00 pri.A
Tpset: 0.11
SECHO C211 10KV
Ipset: 7.50 pri.A
Tset: 0.75 s

[s]

SECHO C212 10KV


Ipset: 7.50 pri.A
Tset: 0.75 s

SECHO C211 10KV


Ipset: 360.00 pri.A
Tset: 0.50 s

SECHO C212 10KV


Ipset: 180.00 pri.A
Tset: 0.50 s

0.1
10.00 kV 1 10 100 1000 [pri.A] 10000
CHICL10A\Cub_10(1)\SECHO T 2 10KV CHICL10B\Cub_12\SECHO C211 10KV
CHICL10B\Cub_12\SECHO C212 10KV CHICL10B\Cub_12\SECHO CT 10KV
CHICL10B\Cub_9\SECHO T 1 10KV CHICL10B\Cub_10\ZZ SECHO

Figura N 25 - Tiempos de actuacin para una falla monofsica franca en alimentador


10 kV SE SECHO en operacin normal.

5.2.2 SE CHICLAYO OESTE: TRANSFORMADOR DE POTENCIA TR3 60/22.9/10 KV


Datos del Transformador de Potencia:

Potencia Nominal : 30/16/20 MVA (ONAN)


Tensin Nominal : 60 8x1.25% / 22.9/ 10 KV
Corriente Nominal : 288.68 / 403.39 / 1154.70 A (ONAN)
Datos de los Transformadores de Corriente:

TC de Fases AT : 200-400 / 5 A
TC de Fases MT : 250-500 / 5 A
TC de Fases BT : 600-1200 / 5 A
Datos del Rel de Proteccin Diferencial:

Marca y modelo : ABB RET 670


Datos de los Rels de Proteccin de Sobrecorriente Lado 60 kV:

Marca y modelo : ABB REC 670

PROTECCION DIFERENCIAL DE TRANSFORMADOR ABB RET 670

A continuacin se muestran los ajustes propuestos:

DLF SAC Pgina 39 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

UMBRAL DIFERENCIAL - IdMin:


El umbral de corriente diferencial ser ajustada en 30 % de la corriente nominal (0.3 In).
IdMin = 0.3
PENDIENTE DE RESTICCION - Slope:
El rel ABB RET 670 dispone de dos pendientes de restriccin las cuales sern
ajustadas de la siguiente manera:
La primera pendiente de restriccin del rel diferencial viene determinada por la
siguiente expresin:

P = % T + %eCT + %er + MS

Donde:

P : Pendiente de restriccin.

%T : Error de variacin del cambiador de tomas (en este caso este


error es de 8%).

%eCT : Mximo error de los TCs para la clase de exactitud


especificada (5%).

%er : Mximo error de la relacin de transformacin entre la


transformacin del transformador y la de los TCs (5%).

MS : Margen de seguridad (5%)

P = 8% + 5% + 5% + 5% = 23 %

Por lo tanto la primera pendiente de restriccin ser ajustada en:

Slope Section 2 = 25

La segunda pendiente se ajustar con la finalidad de incrementar la seguridad


cuando las corrientes de corto circuito externas sean altas, por lo que el error de
los transformadores de corriente es alto:

Slope Section 3= 50

LIMITE DE CORRIENTE DE NO RESTRICCION - IdUnre:


A partir de este valor de corriente diferencial la proteccin diferencial emitir su disparo
sin tomar en cuenta la corriente de restriccin.

IdUnre = 10

BLOQUEO DEL 2DO ARMONICO I2/I1 Ratio:


Durante el proceso de energizacin del transformador se produce temporalmente una
corriente insercin (corriente inrush) en un lado del transformador sin presentarse esto

DLF SAC Pgina 40 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

en los otros lados. Por lo que esta diferencia de corrientes podra provocar una mala
actuacin de la proteccin diferencial. La corriente de insercin contiene mayormente
corrientes de segundo armnico que corrientes de falla por lo que el rel deber
bloquear el elemento de restriccin diferencial porcentual si la relacin corriente 2do
armnico sobre corriente fundamental (I2/I1) supere el valor de ajuste (en %) que ser:

I2/I1 Ratio = 15

BLOQUEO DEL 5TO ARMONICO I5/I1 Ratio:


La sobreexitacin del transformador causa armnicos de este orden provocando la
mala actuacin de la proteccin diferencial si no es bloqueada. Se habilita esta opcin
con el ajuste de:

I5/I1 Ratio = 25

SECUENCIA NEGATIVA IminNegSeq:


Se habilita esta funcin para detectar fallas entre espiras. Se habilita esta opcin con el
ajuste de:

NegSeqDiff = On

IminNegSeq = 0.1

NegSeqROA=60 deg

PROTECCION DE SOBRECORRIENTE DE FASES

La corriente de arranque de la etapa de tiempo inverso se ajusta al 130% de la corriente


nominal de cada devanado del transformador de potencia. La curva selecciona es IEC
NORMAL INVERSE y el dial de tiempo es seleccionado de tal forma que coordinen
entre protecciones.
Proteccin Ajuste Umbral 1 Ajuste Umbral 2
Direcc
Ubicacin Rel TC I> T> Curva1 I>> T>> Curva2

SECHO ABB RET670


400/5 376 0.15 IEC NI 3640 0.1 DT --
TR3 - 60KV ABB REC670

SECHO
ABB RET670 500/5 525 0.14 IEC NI -- -- -- --
TR3 22.9KV
SECHO
ABB RET670 1200/5 1500 0.11 IEC NI -- -- -- --
TR3 - 10KV
SECHO SIEMENS
500/5 600 0.08 IEC NI 4000 0.0 DT --
ALIM 22.9KV 7SJ64

SECHO SIEMENS
500/5 600 0.10 IEC NI 4000 0.0 DT --
ALIM 10KV 7SJ64

Cuadro N26 - Ajustes de sobrecorriente de fases TR3 en SECHO 60/22.9/10 kV.

DLF SAC Pgina 41 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

DIgSILENT
I =2802.138
=2802.485 pri.A
10

SECHO T3 60KV
Normal Inverse
SECHO ALIM10KV Ipset: 376.00 pri.A
Normal Inverse Tpset: 0.15
Ipset: 600.00 pri.A Tripping T ime: 0.512 s
Tpset: 0.10 Transformer Damage Curve
Tripping T ime: 0.227 s Srat: 20.00 MVA
uk: 5.00 %
Ipeak: 12.00/0.10 s

SECHO T3 10KV
Normal Inverse
Ipset: 1500.00 pri.A
Tpset: 0.11
Tripping T ime: 0.311 s

[s]

0.512 s

0.311 s

SECHO ALIM10KV
Ipset: 4000.00 pri.A
Tset: 0.00 s
Tripping T ime: 0.000 s

SECHO T3 60KV
Ipset: 3640.00 pri.A
Tset: 0.10 s
Tripping T ime: 9999.999 s

0.000 s
0.1
60.00 kV 100 1000 [pri.A] 10000

10.00 kV 1000 10000


CHICL-O6\Cub_16\SECHO T3 60KV CHIL10N\Cub_4\SECHO T3 10KV
Transformer Damage Curve CHIL10N\Cub_4\SECHO ALIM10KV

Figura N 26 - Tiempos de actuacin para una falla trifsica franca en barra 10 kV de


TR3 en operacin normal.

DIgSILENT
I =1881.910
=1885.830 pri.A
10

SECHO T3 22.9KV
Normal Inverse Transformer Damage Curve
Ipset: 525.00 pri.A SECHO T3 60KV Srat: 30.00 MVA
Tpset: 0.14 Normal Inverse uk: 6.76 %
Tripping T ime: 0.428 s Ipset: 376.00 pri.A Ipeak: 12.00/0.10 s
Tpset: 0.15
Tripping T ime: 0.641 s

[s]

SECHO ALIM 22.9KV


Normal Inverse
Ipset: 525.00 pri.A
Tpset: 0.08
Tripping T ime: 0.244 s

0.641 s

0.428 s

SECHO T3 60KV
Ipset: 3640.00 pri.A
Tset: 0.10 s
SECHO ALIM 22.9KV Tripping T ime: 9999.999 s
Ipset: 4000.00 pri.A
Tset: 0.00 s
Tripping T ime: 0.000 s

0.000 s
0.1
60.00 kV 100 1000 [pri.A] 10000

22.90 kV 1000 10000


CHICL-O6\Cub_16\SECHO T3 60KV CHICL23\Cub_3\SECHO T3 22.9KV
Transformer Damage Curve CHICL23\Cub_3\SECHO ALIM 22.9KV

Figura N 27 - Tiempos de actuacin para una falla trifsica franca en barra 22.9 kV de
TR3 en operacin normal.

DLF SAC Pgina 42 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

PROTECCION DE SOBRECORRIENTE DE TIERRA

La corriente de arranque de la etapa de tiempo inverso se ajusta al 40% de la corriente


nominal de cada devanado del transformador de potencia. La curva selecciona es IEC
NORMAL INVERSE y el dial de tiempo es seleccionado de tal forma que coordinen
entre protecciones.
Proteccin Ajuste Umbral 1 Ajuste Umbral 2
Direcc
Ubicacin Rel TC I> T> Curva1 I>> T>> Curva2

SECHO ABB RET670


400/5 116 0.16 IEC NI 2312 0.1 DT --
TR3 - 60KV ABB REC670

SECHO
ABB RET670 500/5 160 0.15 IEC NI -- -- -- --
TR3 22.9KV
SECHO SIEMENS
500/5 160 0.07 IEC NI 2000 0.0 DT --
ALIM 22.9KV 7SJ64

(*) Para el caso de operar la barra nueva 10 kV conectada a las barras 10 kV existentes se activar la
siguiente proteccin de tierra en el alimentador 10 kV:
SECHO (*) SIEMENS
50/1 7.5 0.75 DT 180 0.5 DT --
ALIM 10KV 7SJ64

Cuadro N27 - Ajustes de sobrecorriente de tierra TR3 en SECHO 60/22.9/10 kV.

DIgSILENT
3*I0 =137.271 pri.A 3*I0 =2484.745 pri.A
10

Transformer Damage Curve


SECHO T3 22.9KV Srat: 30.00 MVA
Normal Inverse uk: 6.76 %
6.641 s Ipeak: 12.00/0.10 s
Ipset: 160.00 pri.A
Tpset: 0.15 SECHO T3 60KV
Tripping T ime: 0.340 s Normal Inverse
Ipset: 116.00 pri.A
Tpset: 0.16
Tripping T ime: 6.641 s

SECHO ALIM 22.9KV


Normal Inverse
Ipset: 160.00 pri.A
[s] Tpset: 0.07
Tripping T ime: 0.159 s

0.340 s

SECHO T3 60KV
Ipset: 2312.00 pri.A
Tset: 0.10 s
Tripping T ime: 9999.999 s

SECHO ALIM 22.9KV


Ipset: 2000.00 pri.A
Tset: 0.00 s
Tripping T ime: 0.000 s

0.000 s
0.1
60.00 kV 10 100 1000 [pri.A] 10000

22.90 kV 100 1000 10000


CHICL-O6\Cub_16\SECHO T3 60KV CHICL23\Cub_3\SECHO T3 22.9KV
Transformer Damage Curve CHICL23\Cub_3\SECHO ALIM 22.9KV

Figura N 28 - Tiempos de actuacin para una falla monofsica franca en barra 22.9 kV
de TR3 en operacin normal.

DLF SAC Pgina 43 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

PROTECCION DE SOBRECORRIENTE DE TIERRA SEF

Se propone los siguientes ajustes para las protecciones de sobrecorriente de tierra SEF
del alimentador en 10 kV:
Proteccin Ajuste Umbral 1 Ajuste Umbral 2
Direcc
Ubicacin Rel TC I> T> Curva1 I>> T>> Curva2

SECHO SIEMENS
50/1 0.5 1.0 DT 1.00 0.5 DT FORW
ALIM 10KV 7SJ64

Cuadro N28 - Ajustes de sobrecorriente de tierra SEF.

5.2.3 SE CHICLAYO OESTE: LINEAS DE TRANSMISION EN 60 KV HACIA CHICLAYO


NORTE L-6012 Y L-6022
Datos de las Lneas de Transmisin:

L= 6.686 Km
RL1= 2.039 ohm primarios.
XL1= 3.483 ohm primarios.
RL0= 6.111 ohm primarios.
XL0= 10.457 ohm primarios.

Datos de los Transformadores de Corriente:

TC de Fases : 400 / 1 A
Datos de los Transformadores de tensin:

TT de Fases : 603 / 0.103 kV

Datos del Rel de Proteccin:

Marca y modelo : SIEMENS 7SD532

Los rels Siemens 7SD532 que protegen las lneas de transmisin en 60 kV L-6012 y L-
6022 cuentan como proteccin principal a la funcin diferencial de lnea 87L y como
respaldo se encuentran activados las funciones de distancia 21/21N, las funciones de
sobrecorriente de fases no direccionales 50/51 y las funciones de sobrecorriente
direccional de tierra 67N por lo que es necesario revisar sus alcances y tiempos de
actuacin.

PROTECCION DE DISTANCIA SIEMENS 7SD532

Los ajustes actuales de las zonas de proteccin hacia delante son los siguientes:
ZONA 1: Forward

X1 = 2.26 ohm primarios.


R1Ph-Ph = 6.79 ohm primarios.

DLF SAC Pgina 44 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

R1Ph-G = 10.19 ohm primarios.

T1 = 0.00 segundos

ZONA 2: Forward

X2 = 5.92 ohm primarios.


R2Ph-Ph = 17.77 ohm primarios.

R2Ph-G = 26.65 ohm primarios.

T2 = 0.20 segundos

ZONA 3: Forward

Z3Ph-Ph = 8.36 ohm primarios.


R3Ph-Ph = 25.08 ohm primarios.

R3Ph-G = 31.98 ohm primarios.

T3 = 0.50 segundos

En operacin normal, la impedancia vista por la proteccin ante una falla trifsica franca
en la barra 10 kV de la SE Chiclayo Norte, se encuentra fuera del alcance de las zonas
de operacin incluso cuando se opera con una de las lneas de transmisin en paralelo
fuera de servicio.

DIgSILENT
27.0
[pri.Ohm]
25.5

24.0

22.5

21.0

19.5

18.0

16.5
SECHO L-6012
Zl A 14.497 pri.Ohm 80.79
15.0 Zl B 14.497 pri.Ohm 80.79
Zl C 14.497 pri.Ohm 80.79
Z A 14.497 pri.Ohm 80.79
Z B 14.497 pri.Ohm 80.79
13.5 Z C 14.497 pri.Ohm 80.79
Faulttype: ABC (Starting)
Tripping T ime: 0.47 s

12.0

10.5

9.00

7.50

6.00

4.50

3.00

1.50

-15.0 -13.5 -12.0 -10.5 -9.00 -7.50 -6.00 -4.50 -3.00 -1.50 1.50 3.00 4.50 6.00 7.50 9.00 10.5 12.0 13.5 15.0 16.5 18.0 19.5 21.0 22.5 24.0 25.5 27.0 28.5 30.0 31.5 33.0 34.5 36.0 37.5 39.0 40.5 [pri.Ohm]

-1.50

-3.00

-4.50

-6.00

-7.50

-9.00

-10.5

-12.0

-13.5

-15.0

CHICL-O6\Cub_15\SECHO L-6012

Figura N 29 - Falla trifsica franca en barra 10 kV de SECHONOR en operacin


normal.

DLF SAC Pgina 45 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

DIgSILENT
27.0
[pri.Ohm]
25.5

24.0

22.5

21.0

19.5

18.0

16.5
SECHO L-6012
Zl A 9.158 pri.Ohm 76.2
15.0 Zl B 9.158 pri.Ohm 76.2
Zl C 9.158 pri.Ohm 76.2
Z A 9.158 pri.Ohm 76.2
Z B 9.158 pri.Ohm 76.2
13.5 Z C 9.158 pri.Ohm 76.2
Faulttype: ABC (Starting)
Tripping T ime: 0.47 s

12.0

10.5

9.00

7.50

6.00

4.50

3.00

1.50

-15.0 -13.5 -12.0 -10.5 -9.00 -7.50 -6.00 -4.50 -3.00 -1.50 1.50 3.00 4.50 6.00 7.50 9.00 10.5 12.0 13.5 15.0 16.5 18.0 19.5 21.0 22.5 24.0 25.5 27.0 28.5 30.0 31.5 33.0 34.5 36.0 37.5 39.0 40.5 [pri.Ohm]

-1.50

-3.00

-4.50

-6.00

-7.50

-9.00

-10.5

-12.0

-13.5

-15.0

CHICL-O6\Cub_15\SECHO L-6012

Figura N 30 - Falla trifsica franca en barra 10 kV de SECHONOR en contingencia L-


6022 F/S.

PROTECCION DE SOBRECORRIENTE DE FASES

Los ajustes actuales de la funcin de sobrecorriente de fases son los siguientes:


IPH > = 360 A primarios.
IPH > = 0.9 A secundarios.
Curva = IEC-NI
Dial = 0.16
IPH >> = 2100 A primarios.
IPH >> = 5.25 A secundarios.
t>> = 0.45 s
Los ajustes actuales de la funcin de sobrecorriente de fases coordinan
adecuadamente con las protecciones de sobrecorriente de los transformadores de
potencia de la SE Chiclayo Norte ante una falla trifsica franca en el nivel 10 kV en
operacin normal. En contingencia, donde L-6022 esta fuera de servicio, se tienen los
siguientes tiempos:

DLF SAC Pgina 46 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

DIgSILENT
I =750.106 pri.A I =1303.971 pri.A I =2807.986 pri.A
10

[s]
SECHO L-6012
IEC Normal Inverse
Ipset: 360.00 pri.A
Tpset: 0.16
Tripping T ime: 0.534 s

SECHONOR T3 60KV
IEC Curve A
Ipset: 350.10 pri.A
Tpset: 0.06
Tripping T ime: 0.315 s

SECHONOR T1 60KV
IEC Curve A
Ipset: 220.00 pri.A
Tpset: 0.08
Tripping T ime: 0.451 s

SECHO L-6012
Ipset: 2100.00 pri.A
Tset: 0.45 s
Tripping T ime: 0.470 s
0.470 s
0.451 s

SECHONOR T3 60KV
Ipset: 1101.00 pri.A
Tset: 0.25 s
Tripping T ime: 0.250 s

0.250 s
SECHONOR T1 60KV
Ipset: 1000.00 pri.A
Tset: 0.25 s
Tripping T ime: 9999.999 s

0.1
60.00 kV 10 100 1000 10000 [pri.A] 100000
CHICL-O6\Cub_15\SECHO L-6012 CHICL60\Cub_4\SECHONOR T1 60KV
CHICL60\Cub_6(1)\SECHONOR T 3 60KV

Figura N 31 - Tiempos de actuacin para una falla trifsica franca en barra 10 kV en


contingencia L-6022 F/S con ajustes actuales.

Se recomienda los siguientes ajustes:


IPH > = 360 A primarios.
IPH > = 0.9 A secundarios.
Curva = IEC-NI
Dial = 0.20
IPH >> = oo A primarios.
IPH >> = oo A secundarios.
t>> = oo s

DLF SAC Pgina 47 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

DIgSILENT
I =750.106 pri.A I =1303.971 pri.A I =2807.986 pri.A
10

[s]
SECHO L-6012
IEC Normal Inverse
Ipset: 360.00 pri.A
Tpset: 0.20
Tripping T ime: 0.668 s

SECHONOR T3 60KV
IEC Curve A
Ipset: 350.10 pri.A
Tpset: 0.06
Tripping T ime: 0.315 s

SECHONOR T1 60KV
IEC Curve A
Ipset: 220.00 pri.A
Tpset: 0.08
Tripping T ime: 0.451 s

0.668 s

0.451 s

SECHONOR T3 60KV
Ipset: 1101.00 pri.A
Tset: 0.25 s
Tripping T ime: 0.250 s

0.250 s
SECHONOR T1 60KV
Ipset: 1000.00 pri.A
Tset: 0.25 s
Tripping T ime: 9999.999 s

0.1
60.00 kV 10 100 1000 10000 [pri.A] 100000
CHICL-O6\Cub_15\SECHO L-6012 CHICL60\Cub_4\SECHONOR T1 60KV
CHICL60\Cub_6(1)\SECHONOR T 3 60KV

Figura N 32 - Tiempos de actuacin para una falla trifsica franca en barra 10 kV en


contingencia L-6022 F/S con ajustes recomendado.

PROTECCION DE SOBRECORRIENTE DE TIERRA

Se mantiene los ajustes de la funcin de sobrecorriente de tierra con los siguientes


ajustes:
IE > = 60 A primarios.
IE > = 0.15 A secundarios.
Curva = IEC-NI
Dial = 0.28
IE >> = 600 A primarios.
IE >> = 1.5 A secundarios.
t>> = 0.30 s

DLF SAC Pgina 48 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

5.2.4 SE CHICLAYO NORTE: TRANSFORMADOR DE POTENCIA TR1 Y TR2 60/10 KV


Datos del Transformador de Potencia TR1:

Potencia Nominal : 14-17.5 MVA (ONAN-ONAF)


Tensin Nominal : 60 8x1.25% / 10 KV
Corriente Nominal : 134.71-168.4 / 808.3-1010.36 A (ONAN-ONAF)
Datos del Transformador de Potencia TR2:

Potencia Nominal : 14 MVA (ONAN)


Tensin Nominal : 60 8x1.25% / 10 KV
Corriente Nominal : 134.71 / 808.3 A (ONAN)
Datos de los Transformadores de Corriente:

TC de Fases AT : 100-200 / 5 A (Para el rel T60)


TC de Fases BT : 600-1200 / 5 A (Para el rel T60)
Datos del Rel de Proteccin Diferencial:

Marca y modelo : GE T60

PROTECCION DIFERENCIAL DE TRANSFORMADOR GE T60

Los ajustes propuestos son los siguientes:


Id> Pick Up = 0.20 pu
Slope 1 = 25%
Slope 2 = 80 %
Id>> Pick Up = 8.00 pu

DLF SAC Pgina 49 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

Figura N 33 - Curva de Operacin de la Proteccin Diferencial 87T


Los ajustes de compensacin de relacin de transformacin no son necesarios
calcularlos, debido a que el rel efecta estos clculos internamente.
El ajuste de la restriccin por 2do o 5to armnico es necesario para evitar que el rel
dispare por corrientes de insercin al momento de la energizacin y por sobre-
excitacin del transformador. El valor recomendado es del 15% de la corriente
fundamental para el 2do armnico y de 25% de la corriente fundamental para el 5to
armnico:
Inrush Inhibit (2nd Harm) : 15.0 %
OverExcit Inhibit (5th Harm) : 25.0 %

PROTECCION DE SOBRECORRIENTE DE FASES

A continuacin se muestra los ajustes actuales de las protecciones de sobrecorriente de


fases. Se consideran adecuados los ajustes y se mantienen:
Proteccin Ajuste Umbral 1 Ajuste Umbral 2
Direcc
Ubicacin Rel TC I> T> Curva1 I>> T>> Curva2

SECHONOR
GE T60 200/5 220 0.08 IEC NI 1000 0.25 DT --
TR1 - 60KV
SECHONOR
GE T60 1200/5 1320 0.08 IEC NI 5700 0.25 DT --
TR1 - 10KV
SECHONOR
GE T60 200/5 220 0.08 IEC NI 1000 0.25 DT --
TR2 - 60KV
SECHONOR
GE T60 1200/5 1320 0.08 IEC NI 5700 0.25 DT --
TR2 - 10KV

Cuadro N29 - Ajustes de sobrecorriente de fases TR1 y TR2 en SECHONOR 60/10 kV.

DLF SAC Pgina 50 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

DIgSILENT
I I=866.392
=877.359 pri.A
pri.A
10

Transformer Damage Curve


Srat: 17.50 MVA
uk: 10.10 %
Ipeak: 12.00/0.10 s

SECHONOR T1 60KV
IEC Curve A
Ipset: 220.00 pri.A
Tpset: 0.08
Tripping T ime: 0.399 s

[s]

SECHONOR T1 10KV
IEC Curve A
Ipset: 1320.00 pri.A
Tpset: 0.08
Tripping T ime: 0.403 s

0.403
0.399 ss SECHONOR T1 60KV
Ipset: 1000.00 pri.A
Tset: 0.25 s
Tripping T ime: 9999.999 s

SECHONOR T1 10KV
Ipset: 5700.00 pri.A
Tset: 0.25 s
Tripping T ime: 9999.999 s

0.1
60.00 kV 10 100 1000 [pri.A] 10000

10.00 kV 100 1000 10000


CHICL60\Cub_4\SECHONOR T1 60KV CHICN10\Cub_1\SECHONOR T 1 10KV
Transformer Damage Curve

Figura N 34 - Tiempos de actuacin para una falla trifsica franca en barra 10 kV en


operacin normal.

DIgSILENT
I I=1143.106
=1157.576 pri.A
pri.A
10

Transformer Damage Curve


Srat: 17.50 MVA
uk: 10.10 %
Ipeak: 12.00/0.10 s

SECHONOR T1 60KV
IEC Curve A
Ipset: 220.00 pri.A
Tpset: 0.08
Tripping T ime: 0.332 s

[s]

SECHONOR T1 10KV
IEC Curve A
Ipset: 1320.00 pri.A
Tpset: 0.08
Tripping T ime: 0.334 s

SECHONOR T1 60KV
Ipset: 1000.00 pri.A
Tset: 0.25 s
Tripping T ime: 0.250 s

0.250
0.250 ss

SECHONOR T1 10KV
Ipset: 5700.00 pri.A
Tset: 0.25 s
Tripping T ime: 0.250 s

0.1
60.00 kV 10 100 1000 [pri.A] 10000

10.00 kV 100 1000 10000


CHICL60\Cub_4\SECHONOR T1 60KV CHICN10\Cub_1\SECHONOR T 1 10KV
Transformer Damage Curve

Figura N 35 - Tiempos de actuacin para una falla trifsica franca en barra 10 kV en


contingencia TR3 F/S.

DLF SAC Pgina 51 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

PROTECCION DE SOBRECORRIENTE DE TIERRA

A continuacin se muestra los ajustes actuales de las protecciones de sobrecorriente de


tierra. Se consideran adecuados los ajustes y se mantienen:
Proteccin Ajuste Umbral 1 Ajuste Umbral 2
Direcc
Ubicacin Rel TC I> T> Curva1 I>> T>> Curva2

SECHONOR
GE T60 200/5 68 0.15 IEC NI 1800 0.10 DT --
TR1 - 60KV
SECHONOR
GE T60 1200/5 120 0.50 DT -- -- -- --
TR1 - 10KV
SECHONOR
GE T60 200/5 68 0.15 IEC NI 1800 0.10 DT --
TR2 - 60KV
SECHONOR
GE T60 1200/5 120 0.50 DT -- -- -- --
TR2 - 10KV

Cuadro N30 - Ajustes de sobrecorriente de tierra TR1 y TR2 en SECHONOR 60/10 kV.

DIgSILENT
3*I0 =1064.126 pri.A
10

SECHONOR T1 60KV
IEC Curve A
Ipset: 68.00 pri.A
Tpset: 0.15
Tripping T ime: 0.371 s
Transformer Damage Curve
Srat: 17.50 MVA
uk: 10.10 %
Ipeak: 12.00/0.10 s

[s]

SECHONOR T1 10KV
Ipset: 120.00 pri.A
Tset: 0.50 s
Tripping T ime: 9999.999 s

0.371 s

SECHONOR T1 60KV
Ipset: 1800.00 pri.A
Tset: 0.10 s
Tripping T ime: 9999.999 s

0.1
60.00 kV 10 100 1000 [pri.A] 10000

10.00 kV 100 1000 10000


CHICL60\Cub_4\SECHONOR T1 60KV CHICN10\Cub_1\SECHONOR T 1 10KV
Transformer Damage Curve

Figura N 36 - Tiempos de actuacin para una falla monofsica franca en barra 60 kV


en operacin normal.

DLF SAC Pgina 52 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

5.2.5 SE CHICLAYO NORTE: TRANSFORMADOR DE POTENCIA TR3 60/10 KV


Datos del Transformador de Potencia:

Potencia Nominal : 20-30 MVA (ONAN-ONAF)


Tensin Nominal : 60 8x1.25% / 10 KV
Corriente Nominal : 240.56-288.68 / 1443.38-1732.05 A (ONAN-ONAF)
Datos de los Transformadores de Corriente:

TC de Fases AT : 150-300 / 5 A (Para el rel T60)


TC de Fases AT : 150-300 / 5 A (Para el rel F60)
TC de Fases BT : 1000-2000 / 5 A (Para el rel T60)
TC de Fases BT : 1000-2000 / 5 A (Para el rel F60)
Datos del Rel de Proteccin Diferencial:

Marca y modelo : GE T60


Datos de los Rels de Proteccin de Sobrecorriente:

Marca y modelo : GE F60

PROTECCION DIFERENCIAL DE TRANSFORMADOR GE T60

Los ajustes actuales se consideran adecuados y por ser una proteccin unitaria no
requiere su coordinacin con otras protecciones.

PROTECCION DE SOBRECORRIENTE DE FASES

A continuacin se muestra los ajustes actuales de las protecciones de sobrecorriente de


fases. Se consideran adecuados los ajustes y se mantienen:
Proteccin Ajuste Umbral 1 Ajuste Umbral 2
Direcc
Ubicacin Rel TC I> T> Curva1 I>> T>> Curva2

SECHONOR GE T60
300/5 350.1 0.06 IEC NI 1101 0.25 DT --
TR3 - 60KV GE F60

SECHONOR GE T60
2000/5 2100 0.06 IEC NI 6300 0.25 DT --
TR3 - 10KV GE F60

Cuadro N31 - Ajustes de sobrecorriente de fases TR3 en SECHONOR 60/10 kV.

DLF SAC Pgina 53 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

DIgSILENT
II=1506.120
=1525.185 pri.A
pri.A
10

Transformer Damage Curve


Srat: 25.00 MVA
uk: 8.30 %
Ipeak: 12.00/0.10 s

SECHONOR T3 60KV
IEC Curve A
Ipset: 350.10 pri.A
Tpset: 0.06
Tripping T ime: 0.281 s

SECHONOR T3 10KV
[s] IEC Curve A
Ipset: 2100.00 pri.A
Tpset: 0.06
Tripping T ime: 0.284 s

SECHONOR T3 60KV
Ipset: 1101.00 pri.A
Tset: 0.25 s
Tripping T ime: 0.250 s

0.250
0.250 ss

SECHONOR T3 10KV
Ipset: 6300.00 pri.A
Tset: 0.25 s
Tripping T ime: 0.250 s

0.1
60.00 kV 10 100 1000 [pri.A] 10000

10.00 kV 100 1000 10000


CHICL60\Cub_6(1)\SECHONOR T 3 60KV CHICN10C\Cub_1\SECHONOR T3 10KV
Transformer Damage Curve

Figura N 37 - Tiempos de actuacin para una falla trifsica franca en barra 10 kV en


operacin normal.

DIgSILENT
II =1748.556
=1770.690 pri.A
pri.A
10

Transformer Damage Curve


Srat: 25.00 MVA
uk: 8.30 %
Ipeak: 12.00/0.10 s

SECHONOR T3 60KV
IEC Curve A
Ipset: 350.10 pri.A
Tpset: 0.06
Tripping T ime: 0.255 s

SECHONOR T3 10KV
[s] IEC Curve A
Ipset: 2100.00 pri.A
Tpset: 0.06
Tripping T ime: 0.257 s

SECHONOR T3 60KV
Ipset: 1101.00 pri.A
Tset: 0.25 s
Tripping T ime: 0.250 s

0.250
0.250 ss

SECHONOR T3 10KV
Ipset: 6300.00 pri.A
Tset: 0.25 s
Tripping T ime: 0.250 s

0.1
60.00 kV 10 100 1000 [pri.A] 10000

10.00 kV 100 1000 10000


CHICL60\Cub_6(1)\SECHONOR T 3 60KV CHICN10C\Cub_1\SECHONOR T3 10KV
Transformer Damage Curve

Figura N 38 - Tiempos de actuacin para una falla trifsica franca en barra 10 kV en


contingencia TR1 F/S.

DLF SAC Pgina 54 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

PROTECCION DE SOBRECORRIENTE DE TIERRA

A continuacin se muestra los ajustes actuales de las protecciones de sobrecorriente de


tierra. Se incrementa el segundo umbral de la proteccin de tierra del lado 60 kV para
no operar en 100 ms ante fallas en 60 kV:
Proteccin Ajuste Umbral 1 Ajuste Umbral 2
Direcc
Ubicacin Rel TC I> T> Curva1 I>> T>> Curva2

SECHONOR GE T60
300/5 68 0.15 IEC NI 2400 0.10 DT --
TR3 - 60KV GE F60

SECHONOR GE T60
2000/5 120 0.50 DT -- -- -- --
TR3 - 10KV GE F60

Cuadro N32 - Ajustes de sobrecorriente de tierra TR1 y TR2 en SECHONOR 60/10 kV.

DIgSILENT
3*I0 =1849.858 pri.A
10

SECHONOR T3 60KV
IEC Curve A
Ipset: 115.50 pri.A Transformer Damage Curve
Tpset: 0.15 Srat: 25.00 MVA
Tripping T ime: 0.368 s uk: 8.30 %
Ipeak: 12.00/0.10 s

SECHONOR T3 10KV
Ipset: 120.00 pri.A
Tset: 0.50 s
Tripping T ime: 9999.999 s

[s]

0.368 s

SECHONOR T3 60KV
Ipset: 2400.00 pri.A
Tset: 0.10 s
Tripping T ime: 9999.999 s

0.1
60.00 kV 10 100 1000 [pri.A] 10000

10.00 kV 100 1000 10000


CHICL60\Cub_6(1)\SECHONOR T 3 60KV CHICN10C\Cub_1\SECHONOR T3 10KV
Transformer Damage Curve

Figura N 39 - Tiempos de actuacin para una falla monofsica franca en barra 60 kV


en operacin normal.

DLF SAC Pgina 55 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

5.2.6 SE CHICLAYO NORTE: SALIDA DE ALIMENTADORES EN 10 KV


Datos de los Alimentadores Existentes:

Alimentador TC (Fase--Neutro) Rel


C-233 500/5 A GE F650
C-234 500/1 A -- 100/1 A GE F650
C-236 500/5 A GE F650
C-238 250/5 A GE F650
C-245 500/1 A -- 50/1 A GE F650
C-246 400/5 A GE F650
C-247 500/5 A GE F650
C-248 500/5 A GE F650
N-110 250/1 A GE F650

Datos de los Alimentadores Nuevos:

Alimentador TC (Fase--Neutro) Rel


Salida 01 500/5 A -- 100/1 A GE F650
Salida 02 500/5 A -- 100/1 A GE F650
Salida 03 500/5 A -- 100/1 A GE F650
Salida 04 500/5 A -- 100/1 A GE F650
Salida 05 500/5 A -- 100/1 A GE F650

PROTECCION DE SOBRECORRIENTE DE FASES

En vista que se mantienen los ajustes de las protecciones de sobrecorriente de fases


de los transformadores TR1, TR2 y TR3, los ajustes actuales de la funcin de
sobrecorriente de fases de los alimentadores existentes y nuevos se mantienen:
Alimentadores existentes:
1 er Umbral 2do Umbral
Alimentador TC
I> (A) Dial Curva 1 I>> (A) T>> (S)
C-233 500/5 A 400 0.15 IEC-VI 5000 0.00
C-234 500/1 A 400 0.15 IEC-VI 5000 0.00
C-236 500/5 A 400 0.15 IEC-VI 5000 0.00
C-238 250/5 A 250 0.15 IEC-VI 5000 0.00
C-245 500/1 A 400 0.15 IEC-VI 5000 0.00
C-246 400/5 A 400 0.15 IEC-VI 5000 0.00
C-247 500/5 A 400 0.15 IEC-VI 5000 0.00
C-248 500/5 A 400 0.15 IEC-VI 5000 0.00
N-110 250/1 A 150 0.10 IEC-NI 3000 0.00

DLF SAC Pgina 56 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

Alimentadores nuevos:
1 er Umbral 2do Umbral
Alimentador TC
I> (A) Dial Curva 1 I>> (A) T>> (S)
Salida 1 500/5 A 400 0.15 IEC-VI 5000 0.00
Salida 2 500/5 A 400 0.15 IEC-VI 5000 0.00
Salida 3 500/5 A 400 0.15 IEC-VI 5000 0.00
Salida 4 500/5 A 400 0.15 IEC-VI 5000 0.00
Salida 5 500/5 A 400 0.15 IEC-VI 5000 0.00

PROTECCION DE SOBRECORRIENTE DE TIERRA


Asi mismo los ajustes actuales de la funcin de sobrecorriente de tierra de los
alimentadores existentes y nuevos se mantienen:
Alimentadores existentes:
1 er Umbral 2do Umbral
Alimentador TC
I> (A) T> (S) Curva 1 I>> (A) T>> (S)
C-233 500/5 A 5 0.75 DT 200 0.50
500/1 A 25 0.75 DT 1000 0.50
C-234
100/1 A * 5 0.75 DT 200 0.50
C-236 500/5 A 6 0.75 DT 200 0.50
C-238 250/5 A 8 0.75 DT 200 0.50
500/1 A -- -- -- 200 0.50
C-245
50/1 A * 6 0.75 DT -- --
C-246 400/5 A 6.4 0.75 DT 200 0.50
C-247 500/5 A 6 0.75 DT 200 0.25
C-248 500/5 A 5 0.75 DT 200 0.50
N-110 250/1 A 12.5 0.50 DT 150 0.10
* Ajustes de la funcin sensitivo de tierra.
Alimentadores nuevos:

1 er Umbral 2do Umbral


Alimentador TC
I> (A) T> (S) Curva 1 I>> (A) T>> (S)
Salida 1 100/1 A 5 0.75 DT 200 0.50
Salida 2 100/1 A 5 0.75 DT 200 0.50
Salida 3 100/1 A 5 0.75 DT 200 0.50
Salida 4 100/1 A 5 0.75 DT 200 0.50
Salida 5 100/1 A 5 0.75 DT 200 0.50

DLF SAC Pgina 57 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

5.2.7 SE CHICLAYO OESTE: TRANSFORMADORES DE POTENCIA T14-260, T16-260 Y


T93-260
Datos del Transformador de Potencia T14-260:

Potencia Nominal : 50/50/10 MVA


Tensin Nominal : 220 8x1.25% / 60 / 10 KV
Corriente Nominal : 131.2 / 481.1 / 577.3 A

Datos de los Transformadores de Corriente:

TC de Fases AT (220kV) : 200 / 1 A


TC de Fases MT (60kV) : 600 / 1 A
Datos de los Rels de Proteccin de Sobrecorriente Lado 220 kV:

Marca y modelo : ASEA RX1DF-2H


Datos de los Rels de Proteccin de Sobrecorriente Lado 60 kV:

Marca y modelo : ABB SPAJ140C

Datos del Transformador de Potencia T16-260:

Potencia Nominal : 50/50/10 MVA


Tensin Nominal : 220 8x1.25% / 60 / 10 KV
Corriente Nominal : 131.2 / 481.1 / 577.3 A
Datos de los Transformadores de Corriente:

TC de Fases AT (220kV) : 200 / 1 A


TC de Fases MT (60kV) : 600 / 1 A
Datos de los Rels de Proteccin de Sobrecorriente Lado 220 kV:

Marca y modelo : ABB SPAJ140C


Datos de los Rels de Proteccin de Sobrecorriente Lado 60 kV:

Marca y modelo : ABB SPAJ140C


Datos del Transformador de Potencia T93-260:

Potencia Nominal : 100/100/33.33 MVA


Tensin Nominal : 220 8x1.25% / 60 / 10 KV
Corriente Nominal : 262.4 / 962.25 / 1924.31 A
Datos de los Transformadores de Corriente:

TC de Fases AT (220kV) : 400 / 1 A


TC de Fases MT (60kV) : 1200 / 1 A

DLF SAC Pgina 58 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

Datos de los Rels de Proteccin de Sobrecorriente Lado 220 kV:

Marca y modelo : ABB RET670


Datos de los Rels de Proteccin de Sobrecorriente Lado 60 kV:

Marca y modelo : ABB RET670

Los ajustes actuales de las protecciones de sobrecorriente de los transformadores


TR14-260 y TR16-260 y T93-260 son los siguientes:

1 er Umbral 2do Umbral


TR / Lado TC
I>/In T> (S) Curva 1 I>>/In T>> (S)
TR16 / 220 200/1 A 0.86 0.20 IEC-NI 6.00 0.10
TR16 / 60 600/1 A 1.04 0.15 IEC-NI -- --
TR93 / 220 400/1 A 0.85 0.18 IEC-NI 6.00 0.10
TR93 / 60 1200/1 A 1.042 0.12 IEC-NI -- --

Para la verificacin de coordinacin de los rels de sobrecorriente se consideran los


ajustes de las protecciones del transformador TR16-260 y TR93-260 y se analiza en
primera instancia con ajustes actuales de las protecciones de las lneas de transmisin
en 60 kV L-6012 y L-6022 para la condicin crtica:
Condicin crtica: Transformador TR14 y la CT Chiclayo se encuentren fuera de
servicio:
En la figura N 18 se muestra los tiempos de actuacin para una falla trifsica en la
barra 60 kV de la SE Chiclayo Norte donde se observa que la proteccin de
sobrecorriente del lado 60 kV del transformador TR93 acta en 752 ms y la proteccin
de sobrecorriente de las lneas L-6012 y L-6022 actan en 675 ms. Este caso se podra
dar si no actan las zonas 2 de las protecciones de distancia de las lneas L-6012 y L-
6022 que actan en 200 ms.

DLF SAC Pgina 59 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

DIgSILENT
I =512.708
I =532.684pri.A
pri.AI =749.349 pri.A
I =1029.878
I =1070.433pri.A
pri.A
10

SECHO REP T2 220


Normal Inverse
Ipset: 172.00 pri.A
Tpset: 0.20
Tripping T ime: 1.225 s

SECHO REP T2 60
Normal Inverse
Ipset: 624.00 pri.A
Tpset: 0.15
Tripping T ime: 0.942 s

[s]

SECHO L-6012
IEC Normal Inverse
Ipset: 360.00 pri.A
Tpset: 0.20
Tripping T ime: 0.675 s

SECHO REP T3 220


Normal Inverse
Ipset: 340.00 pri.A
Tpset: 0.18
Tripping T ime: 1.086 s

1.225 s

1.086 s

1
0.942 s
SECHO REP T3 60
Normal Inverse
Ipset: 1250.40 pri.A
Tpset: 0.12
Tripping T ime: 0.752 s
0.752 s

0.675 s

SECHO REP T2 220


Ipset: 1200.00 pri.A
Tset: 0.10 s
Tripping T ime: 9999.999 s

SECHO REP T3 220


Ipset: 2400.00 pri.A
Tset: 0.10 s
Tripping T ime: 9999.999 s

0.1
220.00 kV 10 100 1000 [pri.A] 10000

60.00 kV 100 1000 10000


CHICLAYO_OESTE_220\Cub_3(1)\SECHO REP T3 220 CHICLAYO_OESTE_220\tr3 chi_2672\SECHO REP T2 220
CHICL-O6\Cub_9\SECHO REP T3 60 CHICL-O6\tr3 chi_2672\SECHO REP T2 60
CHICL-O6\Cub_15\SECHO L-6012

Figura N 40 - Tiempos de actuacin para una falla trifsica franca en barra 60 kV


Chiclayo Norte cuando TR14 y CT Chiclayo F/S con ajustes actuales.

Tambien se verifica la coordinacin ante una falla en la barra 10 kV de la SE Chiclayo


Norte primero actuaran las protecciones de los alimentadores en un tiempo instantneo,
y como respaldo las protecciones de los transformadores de 60/10 KV.

DIgSILENT
I =223.763 pri.A
I =297.591
I =309.185pri.A
I pri.A
=388.986
I =418.621
pri.A
pri.A I =597.788
I =621.600pri.A
pri.A
10

SECHO REP T2 220


Normal Inverse
Ipset: 172.00 pri.A
Tpset: 0.20
Tripping T ime: 2.373 s

SECHO REP T2 60
Normal Inverse
Ipset: 624.00 pri.A
Tpset: 0.15
Tripping T ime: 1.868 s

[s]

SECHO L-6012
IEC Normal Inverse 2.373 s
Ipset: 360.00 pri.A
Tpset: 0.20
Tripping T ime: 0.951 s 2.076 s

1.868 s
SECHO REP T3 220
Normal Inverse
Ipset: 340.00 pri.A
SECHONOR T1 60KV 1.488 s Tpset: 0.18
IEC Curve A Tripping T ime: 2.076 s
Ipset: 220.00 pri.A
Tpset: 0.08
Tripping T ime: 0.420 s

1
0.951 s
SECHO REP T3 60
SECHONOR T3 60KV Normal Inverse
IEC Curve A Ipset: 1250.40 pri.A
Ipset: 350.10 pri.A Tpset: 0.12
Tpset: 0.06 Tripping T ime: 1.488 s
Tripping T ime: 0.295 s

0.420 s

SECHO REP T2 220


0.250 s Ipset: 1200.00 pri.A
Tset: 0.10 s
Tripping T ime: 9999.999 s

SECHO REP T3 220


Ipset: 2400.00 pri.A
Tset: 0.10 s
Tripping T ime: 9999.999 s

0.1
220.00 kV 10 100 1000 [pri.A] 10000

60.00 kV 100 1000 10000


CHICLAYO_OESTE_220\Cub_3(1)\SECHO REP T3 220 CHICLAYO_OESTE_220\tr3 chi_2672\SECHO REP T2 220
CHICL-O6\Cub_9\SECHO REP T3 60 CHICL-O6\tr3 chi_2672\SECHO REP T2 60
CHICL-O6\Cub_15\SECHO L-6012 CHICL60\Cub_6(1)\SECHONOR T 3 60KV
CHICL60\Cub_4\SECHONOR T1 60KV

Figura N 41 - Tiempos de actuacin para una falla trifsica franca en barra 10 kV


Chiclayo Norte cuando TR14 y CT Chiclayo F/S con ajustes propuestos.

DLF SAC Pgina 60 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

5.2.8 SE CHICLAYO OESTE: BARRA 60 KV


Datos de los Rels de Proteccin de Barra 60 kV:

Marca y modelo : ABB REB 670

PROTECCION DE BARRAS
La corriente de arranque de la proteccin de barras de Chiclayo Oeste 60 kV es:
DiffOperLev = 580 A primarios.
Dicho ajuste tiene como criterio de ajuste ser mayor a la corriente de carga por los
circuitos. Considerando que la corriente nominal del nuevo transformador T3 60/22.9/10
kV es de 288 A en el nivel 60 kV, se considera adecuado el ajuste actual y se mantiene.

PROTECCION FALLA INTERRUPTOR


Se recomienda activar la proteccin de falla interruptor en la nueva baha del
transformador T3 considerando los siguientes ajustes:
= &
=>
>0.20
1=0.15 .
2=0.25 .

DLF SAC Pgina 61 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

ANEXOS

DLF SAC Pgina 62 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

ANEXO I:
DIAGRAMAS UNIFILARES.

DLF SAC Pgina 63 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

ANEXO II:
PARAMETROS ELCTRICOS DE EQUIPOS.

DLF SAC Pgina 66 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

LINEA DE TRASMISION

TRANSFORMADOR DE POTENCIA

Tensin Potencia % VCC


SE Conexin
kV MVA HV-LV
Chiclayo Oeste 9.7
608x1.25%/10 14/17.5 YNd5
TR1 (17.5MVA)
Chiclayo Oeste 9.5
608x1.25%/10 14/17.5 YNd5
TR2 (17.5MVA)
Chiclayo Norte 10.1
608x1.25%/10 14/17.5 YNd5
TR1 (17.5MVA)
Chiclayo Norte 8.2
608x1.25%/10 14 YNd5
TR2 (14MVA)
Chiclayo Norte 8.3
608x1.25%/10 25/30 YNd5
TR3 (25MVA)

Tensin Potencia % VCC


SE Conexin
kV MVA HV-MV HV-LV MV-LV
Chiclayo 608x1.25%/ 30/16/20 6.76 5.0 2.28 YNyn0d5
Oeste TR3 22.9/10 ONAN (16MVA) (20MVA) (16MVA)

DLF SAC Pgina 67 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

TRANSFORMADOR ZIG ZAG

Tensin Potencia Impedancia Corriente


R puesta
SE mx en 60 s
a tierra
kV KVA Ohm/fase A
SECHO 10 200 28.13 256 26.6
SECHONOR 10 200 28.0 256 22.6

DLF SAC Pgina 68 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA E
NORTE

ANEXO III:

RESULTADOS DE FLUJO DE POTENCIA.

OPERACION NORMAL SIN PROYECTO

Avenida 2014 Mxima Demanda


Avenida 2014 Media Demanda
Avenida 2014 Mnima Demanda

Estiaje 2014 Mxima Demanda


Estiaje 2014 Media Demanda
Estiaje 2014 Mnima Demanda

OPERACION NORMAL SIN PROYECTO

Avenida 2014 Mxima Demanda


Avenida 2014 Media Demanda
Avenida 2014 Mnima Demanda

Estiaje 2014 Mxima Demanda


Estiaje 2014 Media Demanda
Estiaje 2014 Mnima Demanda

DLF SAC Pgina 69 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA EN CHICLAYO OESTE Y CHICLAYO
NORTE

DIgSILENT
CAYAL60 TUMAN60
59.51 9.94 22.79 57.94
59.30 0.99 0.99 0.97
0.99 0.99
-68.18
POMAL10 138.62 POMAL23 -71.09 MOTUP60 -71.75
-68.52
1.95 -1.95 1.95 3.08 -5.04
0.63 -0.63 0.36 1.14 -1.50
29.58 3.66 3.66 47.36 9.35
-0.00 tr3 pom_8001 -4.74 4.74 -9.88 5.67 4.21
lne TUM_C.. 0.00 -1.56 1.56 0.11 1.36 -1.46
73.01 73.01 49.21 86.21 22.19
-1 -5 Lne 60KV-ILLIMO-LA VIA

lne POM_TUM_81 -2
-6
1.95 -1.95 -0.00 2.41 -2.41 -0.67 0.67 -7.53 -7.11 10.11
0.58 -0.58 0.00 0.79 -0.79 -0.22 0.22 -1.04 -0.70 -0.04
29.58 tr3 cay_8001 29.58 47.36 tr3 tum_8001 47.36 37.04 34.79 49.21 59.27
5.05 4.74
1.43 1.86 0.99
9.35 73.01 -70.02 Tr3 Motup..
-1.32 -4.35
22.70 9.90 23.62 10.28 0.03 -1.03
0.99 CAYAL23 0.99 CAYAL10 TUMAN23 1.03 1.03 TUMAN10 LA_VIA60 86.21 86.21
-69.87 140.01 -70.18 139.30
59.72 4.54
POMAL60 1.00 1.79 MOTUP10 MOTUP23
-67.87 98.74
-9.78 10.15 23.25
-3.29

tr2 La Via
lne CHIC_POM_81 1.01 1.02
9.84 18.31 7.23 7.65 134.23 -75.01
1.32 0.00 4.35
0.98
137.79
CHICN10 0.60 0.87 0
0.43 -0.46 1.03
34.79 37.04
ILLIMO60

L-6051
1
40.10 0.00 -14.56 -25.54 60.37 -4.53
11.67 0.00 -4.45 -7.22 1.01 -1.49
89.80 91.00 -68.89 98.74
-9.59 -9.59 4.29
Lod motup23
-0.60 -0.60 -0.28 LA_VIA10
45.93 45.93 85.56
-1 9.68
-1 -1 0.97
136.72 -4.17
4.53
ZZ chicln T1 T2 T3 1.49
1.32
22.19
14.60 25.59 9.81 57.67
5.89 9.63 3.31 OLMOS60 0.96
-72.53
89.80 91.00 18.31
0
60.10
1.00 -2.91 -1.38 1.27 2.90
-67.37 1.09 -0.53 -1.92 0.61
85.56 85.56 11.54 50.27
-25.00 -25.00 -2
-9.41 -9.41 ILLIMO23 ILLIMO10
75.49 75.49
23.17 10.09
1.01 1.01
lod chicl23 lod chicl10n Chicl G1 Chicl G2 Chicl G3 Chicl G4 Chicl G5 -72.38 -42.99

L-6032

L-6033
-0.00 2.91 1.38
-2.05 0.96 0.53
~ ~ ~ ~ ~

Lne ChiclayoOeste-ChiclayoNorte_L1

Lne ChiclayoOeste-ChiclayoNorte_L2
Breaker/S.. G G G G G -1.44
-0.23
-1.44
-0.23
1 50.27 50.27

OLMOS10 OLMOS22.9

L-6012

L-6022
CHICL23 CHIL10N 9.69
0.97
22.26
0.97
134.30 -74.68
10.08 1.44 1.44
1.01 0.23 0.23
137.64 32.43 0.00 -15.81 -16.62
7.18 0.00 -3.50 -3.68 L-6037
CHICL10 93.22 97.94
tr3 Chiclayo T3
-8.81 2.32 -2.32
-1.80 -0.42 0.39
15.05 3.96 3.96
-1.26
ZZ Chicl -1 -1
LAMB_SUR_60 LAMBA60 1.70
-1
11.54
61.24 57.83
T3 T1 T2 1.02
-66.78
61.23
1.02
OCCI60 0.96
-73.02
15.84 16.64 25.41 25.41 9.74 9.74 8.83
CHICL-O6 5.36 5.63 10.02 10.02 0.60 0.60 1.77
6.48 2.32 -66.83
2.23 -0.39
93.22 97.94 75.49 75.49 45.93 45.93 15.05 33.46 32.98
61.50
1.02 1.26

tr2 lam_801
-66.32 -1.70
0 31.39
-2

-27.59 -27.59 -56.56 0.14


0
-2.79 -2.79 -4.32 -24.10

33.46
-0.00
-0.00
56.96 56.96 58.25 78.73 6.46 -6.46 -2.30
2.05 -2.05 0.47
tr2 chi_674

33.46 32.98 10.44


1.04 -1.26 -0.00
LAMBA10 141.70 1.76 0.00
-4
0 -0.00 0 0 LAMB_SUR_10 31.39 31.39
-0.00 -0.00
0.00 0.00 -0.00 10.13
56.96 56.96 0 58.25 1.01 OCCI23 OCCI10
-0.00 142.08
0.00 0.00 2.30 0.00 0.00 22.56 9.85
26.15 0.00 0.00 0.73 -1.20 0.00
tr3 chi_2671 tr3 chi_2672 tr3 chi_2672(1) 78.73 0.99 0.98
27.59 27.59 56.63 8.86 -73.93 136.08
0.39 0.39 10.25 1.11 0.00 1.26
4.25 4.25 7.29
56.96 SECHO1A 1.03 1.03 SECHO1B 56.96 1.03 SECHO1C 58.25 -96.58 1 -1.94 0.18
-64.83 -64.83 -36.51
215.65 1
0.98
-63.35 -0.00 SVCCHI
0.00 zz lamsur zz lam
10.63 -36.77
CHICLAYO_OESTE_220
Load Flow Balanced
1
Nodes Branches SVS ESTUDIO DE OPERAT IVIDAD Project:
Line-Line Voltage, Magnitude [kV]
Active Power [MW]
SE CHICLAYO OEST E Y SE CHICLAYO NORTE Graphic: SECHO
Voltage, Magnitude [p.u.] Reactive Power [Mvar] Estudio de Flujo de Potencia Date:
Voltage, Angle [deg] Maximum Loading [%] PowerFactory 14.1.3 AV14MAX - Caso Base Annex:

DLF SAC Pgina 70 de 132 Revisin: 0


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA EN CHICLAYO OESTE Y CHICLAYO
NORTE

DIgSILENT
CAYAL60 TUMAN60
60.59 10.07 23.09 58.21
60.42 1.01 1.00 0.97
1.01 1.01
-63.68
POMAL10 144.06 POMAL23 -65.74 MOTUP60 -67.75
-63.95
1.62 -1.62 1.62 2.46 -4.08
0.51 -0.51 0.23 0.90 -1.13
24.08 2.98 2.98 37.03 7.40
-0.00 tr3 pom_8001 -3.45 3.45 -9.57 5.65 3.93
lne TUM_C.. 0.00 -1.14 1.14 0.13 1.43 -1.55
52.04 52.04 47.50 85.78 20.94
0 0 Lne 60KV-ILLIMO-LA VIA

lne POM_TUM_81 -1
-3
1.62 -1.62 -0.00 1.77 -1.77 -0.69 0.69 -7.36 -6.94 9.79
0.48 -0.48 -0.00 0.58 -0.58 -0.23 0.23 -1.01 -0.68 -0.08
24.08 tr3 cay_8001 24.08 37.03 tr3 tum_8001 37.03 36.05 33.85 47.50 59.49
4.09 3.45
1.04 1.29 0.99
7.40 52.04 -66.08 Tr3 Motup..
-1.56 -4.09
22.92 10.01 22.88 9.96 -0.07 -0.97
1.00 CAYAL23 1.00 CAYAL10 TUMAN23 0.99 1.00 TUMAN10 LA_VIA60 85.78 85.78
-65.05 144.85 -65.39 144.08
60.75 4.51
POMAL60 1.01 1.78 MOTUP10 MOTUP23
-63.44 97.86
-7.54 9.86 22.61
-2.33

tr2 La Via
lne CHIC_POM_81 0.99 0.99
10.07 13.77 7.05 7.47 137.91 -71.19
1.56 0.00 4.09
1.01
143.35
CHICN10 0.56 0.83 0
0.51 -0.44 0.97
33.85 36.05
ILLIMO60

L-6051
1
30.97 0.00 -11.24 -19.73 60.55 -4.50
9.19 0.00 -3.50 -5.69 1.01 -1.48
67.90 68.79 -64.98 97.86
-8.79 -8.79 3.06
Lod motup23
-0.27 -0.27 -0.85 LA_VIA10
41.94 41.94 62.90
-1 9.72
-1 -1 0.97
140.70 -3.89
4.50
ZZ chicln T1 T2 T3 1.48
1.40
20.94
11.28 19.76 7.56 57.98
4.34 7.07 2.30 OLMOS60 0.97
-68.49
67.90 68.79 13.77
0
61.02
1.02 -1.69 -1.37 1.15 2.74
-63.06 1.53 -0.52 -1.97 0.57
62.90 62.90 11.36 48.27
-10.05 -10.05 0
-2.57 -2.57 ILLIMO23 ILLIMO10
28.88 28.88
23.40 10.19
1.02 1.02
lod chicl23 lod chicl10n Chicl G1 Chicl G2 Chicl G3 Chicl G4 Chicl G5 -67.44 -38.00

L-6032

L-6033
-0.00 1.69 1.37
-2.09 0.56 0.52
~ ~ ~ ~ ~

Lne ChiclayoOeste-ChiclayoNorte_L1

Lne ChiclayoOeste-ChiclayoNorte_L2
Breaker/S.. G G G G G -1.37
-0.21
-1.37
-0.21
1 48.27 48.27

OLMOS10 OLMOS22.9

L-6012

L-6022
CHICL23 CHIL10N 9.55
0.95
21.94
0.96
138.43 -70.58
10.32 1.37 1.37
1.03 0.21 0.21
143.02 24.35 0.00 -11.87 -12.48
4.87 0.00 -2.37 -2.50 L-6037
CHICL10 68.98 72.48
tr3 Chiclayo T3
-13.40 5.43 -5.43
-3.28 0.51 -0.54
23.17 9.17 9.17
-1.14
ZZ Chicl -2 -2
LAMB_SUR_60 LAMBA60 1.75
0
11.36
61.06 58.17
T3 T1 T2 1.02
-63.29
61.01
1.02
OCCI60 0.97
-68.96
11.90 12.50 10.11 10.11 8.92 8.92 13.46
CHICL-O6 3.39 3.56 2.59 2.59 0.20 0.20 3.36
7.97 5.43 -63.40
2.78 0.54
68.98 72.48 28.88 28.88 41.94 41.94 23.17 41.35 76.63
61.50
1.02 1.14

tr2 lam_801
-62.60 -1.75
0 30.71
0

-23.33 -23.33 -47.88 0.05


0
-3.46 -3.46 -5.90 -11.64

41.35
-0.00
-0.00
46.61 46.61 47.66 38.19 7.94 -7.94 -5.39
2.53 -2.53 -0.18
tr2 chi_674

41.35 76.63 10.08


1.01 -1.14 -0.00
LAMBA10 143.02 1.80 0.00
-1
0 -0.00 0 0 LAMB_SUR_10 30.71 30.71
-0.00 -0.00
-0.00 -0.00 0.00 10.08
46.61 46.61 0 47.66 1.01 OCCI23 OCCI10
-0.00 145.29
0.00 3.65 1.74 0.00 0.00 22.70 9.91
12.20 0.00 0.74 0.55 -1.12 0.00
tr3 chi_2671 tr3 chi_2672 tr3 chi_2672(1) 38.19 0.99 0.99
23.33 23.33 47.94 8.52 -69.77 140.24
0.39 0.39 10.25 1.06 0.00 1.14
4.52 4.52 8.05
46.61 SECHO1A 1.03 1.03 SECHO1B 46.61 1.03 SECHO1C 47.66 -92.73 1 -1.96 0.16
-61.34 -61.34 -32.77
224.35 1
1.02
-60.09 -0.00 SVCCHI
0.00 zz lamsur zz lam
21.81 -34.01
CHICLAYO_OESTE_220
Load Flow Balanced
1
Nodes Branches SVS ESTUDIO DE OPERAT IVIDAD Project:
Line-Line Voltage, Magnitude [kV]
Active Power [MW]
SE CHICLAYO OEST E Y SE CHICLAYO NORTE Graphic: SECHO
Voltage, Magnitude [p.u.] Reactive Power [Mvar] Estudio de Flujo de Potencia Date:
Voltage, Angle [deg] Maximum Loading [%] PowerFactory 14.1.3 AV14MED - Caso Base Annex:

DLF SAC Pgina 71 de 132 Revisin: 0


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA EN CHICLAYO OESTE Y CHICLAYO
NORTE

DIgSILENT
CAYAL60 TUMAN60
61.06 10.13 23.20 58.45
60.95 1.01 1.01 0.97
1.02 1.02
-52.23
POMAL10 156.82 POMAL23 -53.09 MOTUP60 -54.91
-52.43
1.21 -1.21 1.21 1.86 -3.07
0.38 -0.38 0.09 0.66 -0.75
18.00 2.20 2.20 29.35 5.48
-0.00 tr3 pom_8001 -1.57 1.57 -6.69 3.85 2.84
lne TUM_C.. 0.00 -0.52 0.52 -1.31 1.21 0.09
23.28 23.28 33.66 63.10 14.09
1 1 Lne 60KV-ILLIMO-LA VIA

lne POM_TUM_81 0
0
1.21 -1.21 -0.00 1.30 -1.30 -0.56 0.56 -5.31 -5.04 6.80
0.36 -0.36 -0.00 0.43 -0.43 -0.18 0.18 -1.42 -1.14 1.21
18.00 tr3 cay_8001 18.00 29.35 tr3 tum_8001 29.35 26.66 25.01 33.66 59.57
3.07 1.57
0.65 0.55 0.99
5.48 23.28 -53.93 Tr3 Motup..
-1.15 -2.70
22.93 10.01 22.89 9.97 -0.38 -0.64
1.00 CAYAL23 1.00 CAYAL10 TUMAN23 1.00 1.00 TUMAN10 LA_VIA60 63.10 63.10
-53.26 156.67 -53.53 156.06
61.17 3.55
POMAL60 1.02 1.35 MOTUP10 MOTUP23
-52.05 76.59
-4.64 9.58 22.03
-1.20

tr2 La Via
lne CHIC_POM_81 0.96 0.96
10.05 8.30 5.10 5.38 151.93 -57.38
1.15 2.70
1.00
156.58
CHICN10 0.95 1.17 0
0.38 0.64
25.01 26.66
ILLIMO60

L-6051
1
13.52 0.00 -4.91 -8.61 60.45 -3.54
1.77 0.00 -0.69 -1.08 1.01 -1.16
28.22 28.77 -53.21 76.59
-6.45 -6.45 2.42
Lod motup23
-1.54 -1.54 0.95 LA_VIA10
31.66 31.66 51.70
1 9.77
1 1 0.98
153.56 -2.82
3.54
ZZ chicln T1 T2 T3 1.16
-0.27
14.09
4.95 8.61 4.65 58.10
0.88 1.33 1.13 OLMOS60 0.97
-55.30
28.22 28.77 8.30
0
61.32
1.02 -1.52 -0.91 1.08 1.74
-51.81 -0.50 -0.35 -0.07 0.34
51.70 51.70 5.42 30.46
-4.67 -4.67 0
-0.42 -0.42 ILLIMO23 ILLIMO10
12.98 12.98
22.77 9.92
0.99 0.99
lod chicl23 lod chicl10n Chicl G1 Chicl G2 Chicl G3 Chicl G4 Chicl G5 -55.21 -25.62

L-6032

L-6033
1.52 0.91
0.50 0.35
~ ~ ~ ~ ~

Lne ChiclayoOeste-ChiclayoNorte_L1

Lne ChiclayoOeste-ChiclayoNorte_L2
Breaker/S.. G G G G G -0.87
-0.14
-0.87
-0.14
1 30.46 30.46

OLMOS10 OLMOS22.9

L-6012

L-6022
CHICL23 CHIL10N 9.61
0.96
22.06
0.96
152.76 -56.62
10.06 0.87 0.87
1.01 0.14 0.14
155.56 14.95 0.00 -7.29 -7.66
1.48 0.00 -0.72 -0.76 L-6037
CHICL10 41.62 43.74
tr3 Chiclayo T3
-6.61 3.81 -3.81
-0.88 -0.07 0.03
11.15 6.37 6.37
-1.08
ZZ Chicl 1 1
LAMB_SUR_60 LAMBA60 -0.17
0
5.42
61.33 57.94
T3 T1 T2 1.02
-51.93
61.31
1.02
OCCI60 0.97
-55.49
7.31 7.69 4.68 4.68 6.52 6.52 6.62
CHICL-O6 1.14 1.20 0.36 0.36 1.31 1.31 0.81
2.80 3.81 -52.01
0.94 -0.03
41.62 43.74 12.98 12.98 31.66 31.66 11.15 14.34 54.09
61.50
1.02 1.08

tr2 lam_801
-51.58 0.17
0 16.10
2

-12.63 -12.63 -27.77 0.13


-1
2.04 2.04 -37.14 24.25

14.34
-0.00
0.00
24.97 24.97 47.01 78.87 2.78 -2.78 -3.78
0.88 -0.88 0.22
tr2 chi_674

14.34 54.09 10.00


1.00 -1.08 -0.00
LAMBA10 155.40 -0.15 0.00
0
0 -0.00 0 0 LAMB_SUR_10 16.10 16.10
-0.00 -0.00
0.00 0.00 -0.00 10.19
24.97 24.97 0 47.01 1.02 OCCI23 OCCI10
-0.00 157.58
0.00 2.80 0.98 -0.00 0.00 22.29 9.73
-22.21 0.00 0.57 0.31 -1.10 0.00
tr3 chi_2671 tr3 chi_2672 tr3 chi_2672(1) 78.87 0.97 0.97
12.63 12.63 27.82 7.54 -56.27 153.74
0.39 0.39 10.23 0.94 1.08
-1.73 -1.73 39.13
24.97 SECHO1A 1.02 1.02 SECHO1B 24.97 1.02 SECHO1C 47.01 -81.32 1 0.15
-50.89 -50.89 -21.69
224.69 1
1.02
-50.21 0.00 SVCCHI
-0.00 zz lamsur zz lam
48.85 -26.64
CHICLAYO_OESTE_220
Load Flow Balanced
1
Nodes Branches SVS ESTUDIO DE OPERAT IVIDAD Project:
Line-Line Voltage, Magnitude [kV]
Active Power [MW]
SE CHICLAYO OEST E Y SE CHICLAYO NORTE Graphic: SECHO
Voltage, Magnitude [p.u.] Reactive Power [Mvar] Estudio de Flujo de Potencia Date:
Voltage, Angle [deg] Maximum Loading [%] PowerFactory 14.1.3 AV14MIN - Caso Base Annex:

DLF SAC Pgina 72 de 132 Revisin: 0


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA EN CHICLAYO OESTE Y CHICLAYO
NORTE

DIgSILENT
CAYAL60 TUMAN60
60.32 10.64 24.41 57.89
60.11 1.06 1.06 0.96
1.00 1.01
-57.28
POMAL10 149.95 POMAL23 -59.80 MOTUP60 -61.30
-57.61
1.95 -1.95 1.95 3.08 -5.04
0.62 -0.62 0.35 1.14 -1.49
29.18 3.61 3.61 46.71 9.22
-0.00 tr3 pom_8001 -4.74 4.74 -9.88 5.67 4.21
lne TUM_C.. -0.00 -1.56 1.56 -0.01 1.46 -1.45
71.85 71.85 49.25 86.67 22.20
-1 -5 Lne 60KV-ILLIMO-LA VIA

lne POM_TUM_81 -7
0
1.95 -1.95 -0.00 2.41 -2.41 -0.67 0.67 -7.53 -7.11 10.11
0.58 -0.58 -0.00 0.79 -0.79 -0.22 0.22 -1.10 -0.76 0.08
29.18 tr3 cay_8001 29.18 46.71 tr3 tum_8001 46.71 37.10 34.84 49.25 59.25
5.05 4.74
1.42 1.82 0.99
9.22 71.85 -59.59 Tr3 Motup..
-1.32 -4.35
23.01 10.04 23.95 10.43 -0.03 -1.03
1.00 CAYAL23 1.00 CAYAL10 TUMAN23 1.04 1.04 TUMAN10 LA_VIA60 86.67 86.67
-58.93 150.96 -59.23 150.26
60.52 4.54
POMAL60 1.01 1.79 MOTUP10 MOTUP23
-56.99 98.79
-9.78 9.50 21.78
-3.23

tr2 La Via
lne CHIC_POM_81 0.95 0.95
10.03 18.03 7.23 7.65 144.12 -65.01
1.32 0.00 4.35
1.00
148.81
CHICN10 0.66 0.94 0
0.43 -0.41 1.03
34.84 37.10
ILLIMO60

L-6051
1
40.10 0.00 -14.58 -25.52 60.35 -4.53
11.67 0.00 -3.72 -5.94 1.01 -1.49
87.08 88.24 -58.46 98.79
-9.59 -9.59 4.29
Lod motup23
-0.66 -0.66 -0.28 LA_VIA10
45.97 45.97 85.58
-1 9.67
-1 -1 0.97
147.15 -4.17
4.53
ZZ chicln T1 T2 T3 1.49
1.31
22.20
14.61 25.58 9.81 57.61
5.07 8.21 3.25 OLMOS60 0.96
-62.09
87.08 88.24 18.03
0
60.89
1.01 -2.91 -1.38 1.27 2.90
-56.50 1.09 -0.53 -1.92 0.61
85.58 85.58 11.54 51.37
-13.00 -13.00 0
-3.02 -3.02 ILLIMO23 ILLIMO10
37.22 37.22
23.16 10.08
1.01 1.01
lod chicl23 lod chicl10n Chicl G1 Chicl G2 Chicl G3 Chicl G4 Chicl G5 -61.96 -32.57

L-6032

L-6033
-0.00 2.91 1.38
-2.05 0.96 0.53
~ ~ ~ ~ ~

Lne ChiclayoOeste-ChiclayoNorte_L1

Lne ChiclayoOeste-ChiclayoNorte_L2
Breaker/S.. G G G G G -1.44
-0.23
-1.44
-0.23
1 51.37 51.37
2.04 2.04 2.04 2.04 2.04
0.15
28.73
0.15
28.73
0.15
32.65
0.15
32.65
0.15
32.73
OLMOS10 OLMOS22.9

L-6012

L-6022
CHICL23 CHIL10N 9.48
0.95
21.79
0.95
144.61 -64.33
10.00 1.44 1.44
1.00 0.23 0.23
149.88 32.43 0.00 -10.84 -11.39
7.18 0.00 -3.14 -3.30 L-6037
CHICL10 64.70 67.98
tr3 Chiclayo T3
-8.81 2.32 -2.32
-1.80 -0.42 0.39
15.05 3.96 3.96
-1.26
ZZ Chicl 0 0
LAMB_SUR_60 LAMBA60 1.70
0
11.54
61.24 57.78
T3 T1 T2 1.02
-56.35
61.23
1.02
OCCI60 0.96
-62.58
10.86 11.42 13.10 13.10 9.74 9.74 8.83
CHICL-O6 4.08 4.29 3.11 3.11 0.67 0.67 1.77
6.48 2.32 -56.41
2.23 -0.39
64.70 67.98 37.22 37.22 45.97 45.97 15.05 33.46 32.98
61.50
1.02 1.26

tr2 lam_801
-55.90 -1.70
0 31.38
-2

-24.82 -24.82 -51.45 0.16


0
-14.04 -14.04 -27.46 27.24

33.46
-0.00
0.00
57.80 57.80 59.11 88.59 6.46 -6.46 -2.30
2.05 -2.05 0.47
tr2 chi_674

33.46 32.98 10.44


1.04 -1.26 -0.00
LAMBA10 152.12 1.76 -0.00
-3
0 -0.00 0 0 LAMB_SUR_10 31.38 31.38
-0.00 -0.00
-0.00 -0.00 -0.00 10.13
57.80 57.80 0 59.11 1.01 OCCI23 OCCI10
-0.00 152.50
0.00 0.00 2.30 0.00 0.00 22.54 9.84
-24.69 0.00 0.00 0.73 -1.20 0.00
tr3 chi_2671 tr3 chi_2672 tr3 chi_2672(1) 88.59 0.98 0.98
24.82 24.82 51.53 7.46 -63.49 146.52
0.39 0.39 10.24 0.93 0.00 1.26
15.58 15.58 30.60
57.80 SECHO1A 1.04 1.04 SECHO1B 57.80 1.02 SECHO1C 59.11 -85.61 1 -1.94 0.18
-54.57 -54.57 -26.08
223.04 1
1.01
-53.28 -0.00 SVCCHI
-0.00 zz lamsur zz lam
50.75 -26.06
CHICLAYO_OESTE_220
Load Flow Balanced
1
Nodes Branches SVS ESTUDIO DE OPERAT IVIDAD Project:
Line-Line Voltage, Magnitude [kV]
Active Power [MW]
SE CHICLAYO OEST E Y SE CHICLAYO NORTE Graphic: SECHO
Voltage, Magnitude [p.u.] Reactive Power [Mvar] Estudio de Flujo de Potencia Date:
Voltage, Angle [deg] Maximum Loading [%] PowerFactory 14.1.3 ES14MAX - Caso Base Annex:

DLF SAC Pgina 73 de 132 Revisin: 0


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA EN CHICLAYO OESTE Y CHICLAYO
NORTE

DIgSILENT
CAYAL60 TUMAN60
61.59 10.24 23.48 59.29
61.43 1.02 1.02 0.99
1.02 1.03
-60.41
POMAL10 147.40 POMAL23 -62.41 MOTUP60 -64.36
-60.68
1.62 -1.62 1.62 2.46 -4.08
0.51 -0.51 0.22 0.89 -1.11
23.68 2.93 2.93 36.41 7.27
-0.00 tr3 pom_8001 -3.45 3.45 -9.57 5.65 3.93
lne TUM_C.. -0.00 -1.14 1.14 0.20 1.45 -1.65
51.17 51.17 46.65 84.30 20.73
0 0 Lne 60KV-ILLIMO-LA VIA

lne POM_TUM_81 -1
0
1.62 -1.62 -0.00 1.77 -1.77 -0.69 0.69 -7.36 -6.94 9.78
0.48 -0.48 0.00 0.58 -0.58 -0.23 0.23 -0.96 -0.63 -0.18
23.68 tr3 cay_8001 23.68 36.41 tr3 tum_8001 36.41 35.38 33.23 46.65 60.53
4.09 3.45
1.03 1.29 1.01
7.27 51.17 -62.74 Tr3 Motup..
-1.56 -4.09
23.31 10.18 23.27 10.13 -0.09 -0.97
1.01 CAYAL23 1.02 CAYAL10 TUMAN23 1.01 1.01 TUMAN10 LA_VIA60 84.30 84.30
-61.75 148.16 -62.07 147.42
61.75 4.51
POMAL60 1.03 1.77 MOTUP10 MOTUP23
-60.18 96.12
-7.54 9.73 22.32
-2.31

tr2 La Via
lne CHIC_POM_81 0.97 0.97
10.03 13.53 7.05 7.47 141.19 -67.88
1.56 0.00 4.09
1.00
146.54
CHICN10 0.50 0.76 0
0.51 -0.43 0.97
33.23 35.38
ILLIMO60

L-6051
1
30.97 0.00 -11.26 -19.71 61.56 -4.50
9.19 0.00 -2.76 -4.42 1.03 -1.48
66.06 67.17 -61.67 96.12
-8.78 -8.78 3.06
Lod motup23
-0.17 -0.17 -0.93 LA_VIA10
41.20 41.20 62.28
1 9.89
1 1 0.99
144.15 -3.89
4.50
ZZ chicln T1 T2 T3 1.48
1.49
20.73
11.29 19.75 7.56 59.08
3.58 5.77 2.28 OLMOS60 0.98
-65.08
66.06 67.17 13.53
0
62.02
1.03 -1.69 -1.37 1.15 2.74
-59.81 1.61 -0.52 -2.05 0.57
62.28 62.28 11.50 47.35
-10.01 -10.01 0
-2.05 -2.05 ILLIMO23 ILLIMO10
27.96 27.96
23.81 10.37
1.04 1.04
lod chicl23 lod chicl10n Chicl G1 Chicl G2 Chicl G3 Chicl G4 Chicl G5 -64.05 -34.59

L-6032

L-6033
-0.00 1.69 1.37
-2.16 0.56 0.52
~ ~ ~ ~ ~

Lne ChiclayoOeste-ChiclayoNorte_L1

Lne ChiclayoOeste-ChiclayoNorte_L2
Breaker/S.. G G G G G -1.37
-0.21
-1.37
-0.21
1 47.35 47.35

OLMOS10 OLMOS22.9

L-6012

L-6022
CHICL23 CHIL10N 9.73
0.97
22.36
0.98
141.95 -67.10
10.08 1.37 1.37
1.01 0.21 0.21
146.06 24.35 0.00 -11.87 -12.48
4.87 0.00 -2.37 -2.50 L-6037
CHICL10 68.64 72.12
tr3 Chiclayo T3
-13.40 5.43 -5.43
-3.23 0.46 -0.49
22.79 9.02 9.02
-1.14
ZZ Chicl 1 1
LAMB_SUR_60 LAMBA60 1.82
0
11.50
62.03 59.28
T3 T1 T2 1.03
-60.03
61.99
1.03
OCCI60 0.99
-65.55
11.90 12.50 10.06 10.06 8.91 8.91 13.46
CHICL-O6 3.43 3.61 2.06 2.06 0.07 0.07 3.30
7.97 5.43 -60.14
2.77 0.49
68.64 72.12 27.96 27.96 41.20 41.20 22.79 40.69 75.36
62.46
1.04 1.14

tr2 lam_801
-59.36 -1.82
0 31.05
0

-23.23 -23.23 -48.16 0.18


0
-13.05 -13.05 -25.51 29.51

40.69
-0.00
-0.00
53.19 53.19 54.40 94.49 7.94 -7.94 -5.39
2.53 -2.53 -0.14
tr2 chi_674

40.69 75.36 10.24


1.02 -1.14 -0.00
LAMBA10 146.40 1.88 0.00
-3
0 -0.00 0 0 LAMB_SUR_10 31.05 31.05
-0.00 -0.00
0.00 0.00 0.00 10.24
53.19 53.19 0 54.40 1.02 OCCI23 OCCI10
-0.00 148.60
0.00 3.65 1.74 0.00 0.00 23.13 10.10
-26.61 0.00 0.74 0.55 -1.15 0.00
tr3 chi_2671 tr3 chi_2672 tr3 chi_2672(1) 94.49 1.01 1.01
23.23 23.23 48.23 7.54 -66.32 143.68
0.40 0.40 10.40 0.94 0.00 1.14
14.35 14.35 28.17
53.19 SECHO1A 1.05 1.05 SECHO1B 53.19 1.04 SECHO1C 54.40 -89.06 1 -2.04 0.16
-58.15 -58.15 -29.53
225.90 1
1.03
-56.98 -0.00 SVCCHI
-0.00 zz lamsur zz lam
53.23 -26.61
CHICLAYO_OESTE_220
Load Flow Balanced
1
Nodes Branches SVS ESTUDIO DE OPERAT IVIDAD Project:
Line-Line Voltage, Magnitude [kV]
Active Power [MW]
SE CHICLAYO OEST E Y SE CHICLAYO NORTE Graphic: SECHO
Voltage, Magnitude [p.u.] Reactive Power [Mvar] Estudio de Flujo de Potencia Date:
Voltage, Angle [deg] Maximum Loading [%] PowerFactory 14.1.3 ES14MED - Caso Base Annex:

DLF SAC Pgina 74 de 132 Revisin: 0


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA EN CHICLAYO OESTE Y CHICLAYO
NORTE

DIgSILENT
CAYAL60 TUMAN60
61.31 10.17 23.30 58.72
61.20 1.02 1.01 0.98
1.02 1.02
-56.15
POMAL10 152.90 POMAL23 -57.01 MOTUP60 -58.81
-56.35
1.21 -1.21 1.21 1.86 -3.07
0.38 -0.38 0.08 0.66 -0.74
17.93 2.19 2.19 29.23 5.46
-0.00 tr3 pom_8001 -1.57 1.57 -6.69 3.85 2.84
lne TUM_C.. -0.00 -0.52 0.52 -1.30 1.21 0.09
23.19 23.19 33.50 62.80 14.02
1 1 Lne 60KV-ILLIMO-LA VIA

lne POM_TUM_81 0
0
1.21 -1.21 -0.00 1.30 -1.30 -0.56 0.56 -5.31 -5.03 6.79
0.36 -0.36 0.00 0.43 -0.43 -0.18 0.18 -1.42 -1.13 1.20
17.93 tr3 cay_8001 17.93 29.23 tr3 tum_8001 29.23 26.54 24.89 33.50 59.83
3.07 1.57
0.65 0.55 1.00
5.46 23.19 -57.84 Tr3 Motup..
-1.15 -2.70
23.03 10.05 22.99 10.02 -0.38 -0.64
1.00 CAYAL23 1.01 CAYAL10 TUMAN23 1.00 1.00 TUMAN10 LA_VIA60 62.80 62.80
-57.17 152.76 -57.44 152.15
61.42 3.55
POMAL60 1.02 1.35 MOTUP10 MOTUP23
-55.97 76.24
-4.64 9.63 22.13
-1.20

tr2 La Via
lne CHIC_POM_81 0.96 0.97
10.09 8.27 5.09 5.37 148.06 -61.26
1.15 2.70
1.01
152.66
CHICN10 0.94 1.16 0
0.38 0.64
24.89 26.54
ILLIMO60

L-6051
1
13.52 0.00 -4.91 -8.61 60.70 -3.54
1.77 0.00 -0.69 -1.08 1.01 -1.16
28.11 28.65 -57.12 76.24
-6.45 -6.45 2.42
Lod motup23
-1.53 -1.53 0.95 LA_VIA10
31.51 31.51 51.47
1 9.82
1 1 0.98
149.67 -2.82
3.54
ZZ chicln T1 T2 T3 1.16
-0.27
14.02
4.95 8.61 4.65 58.37
0.88 1.33 1.12 OLMOS60 0.97
-59.20
28.11 28.65 8.27
0
61.57
1.03 -1.52 -0.91 1.08 1.74
-55.74 -0.50 -0.35 -0.07 0.34
51.47 51.47 5.40 30.32
-4.67 -4.67 0
-0.42 -0.42 ILLIMO23 ILLIMO10
12.93 12.93
22.87 9.96
0.99 1.00
lod chicl23 lod chicl10n Chicl G1 Chicl G2 Chicl G3 Chicl G4 Chicl G5 -59.11 -29.51

L-6032

L-6033
1.52 0.91
0.50 0.35
~ ~ ~ ~ ~

Lne ChiclayoOeste-ChiclayoNorte_L1

Lne ChiclayoOeste-ChiclayoNorte_L2
Breaker/S.. G G G G G -0.87
-0.14
-0.87
-0.14
1 30.32 30.32

OLMOS10 OLMOS22.9

L-6012

L-6022
CHICL23 CHIL10N 9.66
0.97
22.17
0.97
148.87 -60.51
10.10 0.87 0.87
1.01 0.14 0.14
151.66 14.95 0.00 -7.29 -7.66
1.48 0.00 -0.72 -0.76 L-6037
CHICL10 41.45 43.56
tr3 Chiclayo T3
-6.61 3.81 -3.81
-0.86 -0.08 0.04
11.10 6.34 6.34
-1.08
ZZ Chicl 1 1
LAMB_SUR_60 LAMBA60 -0.17
0
5.40
61.58 58.21
T3 T1 T2 1.03
-55.86
61.56
1.03
OCCI60 0.97
-59.39
7.31 7.69 4.68 4.68 6.52 6.52 6.62
CHICL-O6 1.14 1.20 0.35 0.35 1.29 1.29 0.80
2.80 3.81 -55.94
0.94 -0.04
41.45 43.56 12.93 12.93 31.51 31.51 11.10 14.28 53.87
61.75
1.03 1.08

tr2 lam_801
-55.51 0.17
0 16.03
2

-13.01 -13.01 -27.07 0.18


-1
-9.46 -9.46 -18.68 28.84

14.28
-0.00
0.00
31.25 31.25 31.96 93.42 2.78 -2.78 -3.78
0.88 -0.88 0.23
tr2 chi_674

14.28 53.87 10.04


1.00 -1.08 -0.00
LAMBA10 151.50 -0.15 0.00
0
0 -0.00 0 0 LAMB_SUR_10 16.03 16.03
-0.00 -0.00
-0.00 -0.00 0.00 10.23
31.25 31.25 0 31.96 1.02 OCCI23 OCCI10
-0.00 153.66
0.00 2.80 0.98 -0.00 0.00 22.40 9.78
-26.01 0.00 0.57 0.31 -1.11 0.00
tr3 chi_2671 tr3 chi_2672 tr3 chi_2672(1) 93.42 0.98 0.98
13.01 13.01 27.09 7.45 -60.16 149.85
0.39 0.39 10.28 0.93 1.08
9.94 9.94 19.67
31.25 SECHO1A 1.04 1.04 SECHO1B 31.25 1.03 SECHO1C 31.96 -85.21 1 0.15
-54.81 -54.81 -25.61
230.49 1
1.05
-54.13 0.00 SVCCHI
-0.00 zz lamsur zz lam
52.02 -26.01
CHICLAYO_OESTE_220
Load Flow Balanced
1
Nodes Branches SVS ESTUDIO DE OPERAT IVIDAD Project:
Line-Line Voltage, Magnitude [kV]
Active Power [MW]
SE CHICLAYO OEST E Y SE CHICLAYO NORTE Graphic: SECHO
Voltage, Magnitude [p.u.] Reactive Power [Mvar] Estudio de Flujo de Potencia Date:
Voltage, Angle [deg] Maximum Loading [%] PowerFactory 14.1.3 ES14MIN - Caso Base Annex:

DLF SAC Pgina 75 de 132 Revisin: 0


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA EN CHICLAYO OESTE Y CHICLAYO
NORTE

DIgSILENT
CAYAL60 TUMAN60
59.55 9.94 22.81 57.94
59.33 0.99 0.99 0.97
0.99 0.99
-70.58
POMAL10 136.22 POMAL23 -73.49 MOTUP60 -74.14
-70.92
1.95 -1.95 1.95 3.08 -5.04
0.63 -0.63 0.36 1.14 -1.50
29.56 3.65 3.65 47.33 9.35
-0.00 tr3 pom_8001 -4.74 4.74 -9.88 5.67 4.21
lne TUM_C.. 0.00 -1.56 1.56 0.11 1.36 -1.46
72.97 72.97 49.21 86.21 22.19
-1 -5 Lne 60KV-ILLIMO-LA VIA

lne POM_TUM_81 -2
-6
1.95 -1.95 -0.00 2.41 -2.41 -0.67 0.67 -7.53 -7.11 10.11
0.58 -0.58 -0.00 0.79 -0.79 -0.22 0.22 -1.04 -0.70 -0.04
29.56 tr3 cay_8001 29.56 47.33 tr3 tum_8001 47.33 37.04 34.79 49.21 59.27
5.05 4.74
1.43 1.86 0.99
9.35 72.97 -72.41 Tr3 Motup..
-1.32 -4.35
22.71 9.91 23.63 10.29 0.03 -1.03
0.99 CAYAL23 0.99 CAYAL10 TUMAN23 1.03 1.03 TUMAN10 LA_VIA60 86.21 86.21
-72.27 137.61 -72.59 136.90
59.75 4.54
POMAL60 1.00 1.79 MOTUP10 MOTUP23
-70.28 98.74
-9.78 10.15 23.25
-3.29

tr2 La Via
lne CHIC_POM_81 1.01 1.02
9.94 18.30 7.23 7.65 131.84 -77.40
1.32 0.00 4.35
0.99
136.70
CHICN10 0.60 0.87 0
0.43 -0.46 1.03
34.79 37.04
ILLIMO60

L-6051
1
40.10 0.00 -10.72 -10.58 -18.80 60.37 -4.53
11.67 0.00 -3.22 -3.22 -5.23 1.01 -1.49
65.42 80.50 66.27 -71.28 98.74
-9.59 -9.59 4.29
Lod motup23
-0.60 -0.60 -0.28 LA_VIA10
45.93 45.93 85.56
-1 9.68
-1 -1 0.97
134.33 -4.17
4.53
ZZ chicln T1 T2 T3 1.49
1.32
22.19
10.75 10.58 18.83 9.81 57.67
4.00 3.95 6.51 3.31 OLMOS60 0.96
-74.92
65.42 80.50 66.27 18.30
0
60.13
1.00 -2.91 -1.38 1.27 2.90
-69.78 1.09 -0.53 -1.92 0.61
85.56 85.56 11.54 50.27
-24.99 -24.99 -2
-8.88 -8.88 ILLIMO23 ILLIMO10
74.90 74.90
23.17 10.09
1.01 1.01
lod chicl23 lod chicl10n Chicl G1 Chicl G2 Chicl G3 Chicl G4 Chicl G5 -74.77 -45.38

L-6032

L-6033
-0.00 2.91 1.38
-2.05 0.96 0.53
~ ~ ~ ~ ~

Lne ChiclayoOeste-ChiclayoNorte_L1

Lne ChiclayoOeste-ChiclayoNorte_L2
Breaker/S.. G G G G G -1.44
-0.23
-1.44
-0.23
1 50.27 50.27
6.00 5.00
1.50 1.25 OLMOS10 OLMOS22.9

L-6012

L-6022
CHICL23 CHIL10N 9.69
0.97
22.26
0.97
131.91 -77.07
23.42 10.06 10.06 1.44 1.44
1.02 1.01 1.01 0.23 0.23
-69.28 137.20 137.20
-6.00 -15.79 32.43 0.00 -10.55 -11.09
-1.50 -3.56 7.18 0.00 -2.37 -2.50 L-6037
80.49 80.49 CHICL10 61.66 64.79
tr3 Chiclayo T3
-8.81 2.32 -2.32
-1.80 -0.42 0.39
15.05 3.96 3.96
-1.26
ZZ Chicl 0 0
LAMB_SUR_60 LAMBA60 1.70
0
11.54
61.24 57.83
T3 T1 T2 1.02
-69.17
61.23
1.02
OCCI60 0.96
-75.41
21.81 10.58 11.11 25.39 25.39 9.74 9.74 8.83
CHICL-O6 6.37 3.24 3.40 9.48 9.48 0.60 0.60 1.77
6.48 2.32 -69.22
2.23 -0.39
80.49 61.66 64.79 74.90 74.90 45.93 45.93 15.05 33.46 32.98
61.50
1.02 1.26

tr2 lam_801
-68.71 -1.70
0 31.39
-2

-30.33 -30.33 -62.11 0.18


0
-1.87 -1.87 -2.30 -28.90

33.46
-0.00
0.00
62.41 62.41 63.82 94.34 6.46 -6.46 -2.30
2.05 -2.05 0.47
tr2 chi_674

33.46 32.98 10.44


1.04 -1.26 -0.00
LAMBA10 139.31 1.76 0.00
-4
0 -0.00 0 0 LAMB_SUR_10 31.39 31.39
-0.00 -0.00
0.00 0.00 -0.00 10.13
62.41 62.41 0 63.82 1.01 OCCI23 OCCI10
0.00 139.69
0.00 0.00 2.30 0.00 0.00 22.56 9.85
31.80 0.00 0.00 0.73 -1.20 0.00
tr3 chi_2671 tr3 chi_2672 tr3 chi_2672(1) 94.34 0.99 0.98
30.33 30.33 62.19 8.99 -76.32 133.69
0.39 0.39 10.25 1.12 0.00 1.26
3.62 3.62 5.87
62.41 SECHO1A 1.03 1.03 SECHO1B 62.41 1.03 SECHO1C 63.82 -99.02 1 -1.94 0.18
-67.07 -67.07 -38.92
215.33 1
0.98
-65.44 -0.00 SVCCHI
0.00 zz lamsur zz lam
6.07 -37.87
CHICLAYO_OESTE_220
Load Flow Balanced
1
Nodes Branches SVS ESTUDIO DE OPERAT IVIDAD Project:
Line-Line Voltage, Magnitude [kV]
Active Power [MW]
SE CHICLAYO OEST E Y SE CHICLAYO NORTE Graphic: SECHO
Voltage, Magnitude [p.u.] Reactive Power [Mvar] Estudio de Flujo de Potencia Date:
Voltage, Angle [deg] Maximum Loading [%] PowerFactory 14.1.3 AV14MAX - Caso Proyectado Annex:

DLF SAC Pgina 76 de 132 Revisin: 0


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA EN CHICLAYO OESTE Y CHICLAYO
NORTE

DIgSILENT
CAYAL60 TUMAN60
60.60 10.07 23.09 58.21
60.43 1.01 1.00 0.97
1.01 1.01
-65.49
POMAL10 142.25 POMAL23 -67.55 MOTUP60 -69.56
-65.77
1.62 -1.62 1.62 2.46 -4.08
0.51 -0.51 0.23 0.90 -1.13
24.08 2.98 2.98 37.03 7.40
-0.00 tr3 pom_8001 -3.45 3.45 -9.57 5.65 3.93
lne TUM_C.. 0.00 -1.14 1.14 0.13 1.43 -1.55
52.03 52.03 47.50 85.78 20.94
0 0 Lne 60KV-ILLIMO-LA VIA

lne POM_TUM_81 -1
-3
1.62 -1.62 -0.00 1.77 -1.77 -0.69 0.69 -7.36 -6.94 9.79
0.48 -0.48 -0.00 0.58 -0.58 -0.23 0.23 -1.01 -0.68 -0.08
24.08 tr3 cay_8001 24.08 37.03 tr3 tum_8001 37.03 36.05 33.85 47.50 59.49
4.09 3.45
1.04 1.29 0.99
7.40 52.03 -67.89 Tr3 Motup..
-1.56 -4.09
22.93 10.01 22.89 9.96 -0.07 -0.97
1.00 CAYAL23 1.00 CAYAL10 TUMAN23 1.00 1.00 TUMAN10 LA_VIA60 85.78 85.78
-66.87 143.04 -67.21 142.27
60.75 4.51
POMAL60 1.01 1.78 MOTUP10 MOTUP23
-65.25 97.86
-7.54 9.86 22.61
-2.33

tr2 La Via
lne CHIC_POM_81 0.99 0.99
10.14 13.76 7.05 7.47 136.10 -73.00
1.56 0.00 4.09
1.01
142.50
CHICN10 0.56 0.83 0
0.51 -0.44 0.97
33.85 36.05
ILLIMO60

L-6051
1
30.97 0.00 -8.27 -8.17 -14.52 60.55 -4.50
9.19 0.00 -2.52 -2.54 -4.13 1.01 -1.48
49.63 61.03 50.25 -66.79 97.86
-8.79 -8.79 3.06
Lod motup23
-0.27 -0.27 -0.85 LA_VIA10
41.94 41.94 62.90
-1 9.72
-1 -1 0.97
138.89 -3.89
4.50
ZZ chicln T1 T2 T3 1.48
1.40
20.94
8.31 8.17 14.54 7.56 57.98
2.99 2.96 4.87 2.30 OLMOS60 0.97
-70.30
49.63 61.03 50.25 13.76
0
61.03
1.02 -1.69 -1.37 1.15 2.74
-64.87 1.53 -0.52 -1.97 0.57
62.90 62.90 11.36 48.27
-10.04 -10.04 0
-2.42 -2.42 ILLIMO23 ILLIMO10
28.73 28.73
23.40 10.19
1.02 1.02
lod chicl23 lod chicl10n Chicl G1 Chicl G2 Chicl G3 Chicl G4 Chicl G5 -69.26 -39.81

L-6032

L-6033
-0.00 1.69 1.37
-2.09 0.56 0.52
~ ~ ~ ~ ~

Lne ChiclayoOeste-ChiclayoNorte_L1

Lne ChiclayoOeste-ChiclayoNorte_L2
Breaker/S.. G G G G G -1.37
-0.21
-1.37
-0.21
1 48.27 48.27
4.80 4.00
0.97 0.81 OLMOS10 OLMOS22.9

L-6012

L-6022
CHICL23 CHIL10N 9.55
0.95
21.94
0.96
136.62 -72.39
23.44 10.12 10.12 1.37 1.37
1.02 1.01 1.01 0.21 0.21
-64.90 142.51 142.51
-4.80 -11.98 24.35 0.00 -7.98 -8.39
-0.97 -2.41 4.87 0.00 -1.60 -1.68 L-6037
60.37 60.37 CHICL10 46.15 48.49
tr3 Chiclayo T3
-13.40 5.43 -5.43
-3.28 0.51 -0.54
23.17 9.17 9.17
-1.14
ZZ Chicl 0 0
LAMB_SUR_60 LAMBA60 1.75
0
11.36
61.06 58.17
T3 T1 T2 1.02
-65.10
61.01
1.02
OCCI60 0.97
-70.77
16.80 8.01 8.41 10.09 10.09 8.92 8.92 13.46
CHICL-O6 4.14 2.10 2.21 2.44 2.44 0.20 0.20 3.36
7.97 5.43 -65.22
2.78 0.54
60.37 46.15 48.49 28.73 28.73 41.94 41.94 23.17 41.35 76.63
61.50
1.02 1.14

tr2 lam_801
-64.41 -1.75
0 30.71
0

-25.52 -25.52 -52.32 0.07


0
-2.88 -2.88 -4.61 -14.98

41.35
-0.00
0.00
50.74 50.74 51.89 49.08 7.94 -7.94 -5.39
2.53 -2.53 -0.18
tr2 chi_674

41.35 76.63 10.08


1.01 -1.14 -0.00
LAMBA10 141.21 1.80 -0.00
-1
0 -0.00 0 0 LAMB_SUR_10 30.71 30.71
-0.00 -0.00
-0.00 -0.00 -0.00 10.08
50.74 50.74 0 51.89 1.01 OCCI23 OCCI10
-0.00 143.48
0.00 3.65 1.74 0.00 0.00 22.70 9.91
15.84 0.00 0.74 0.55 -1.12 0.00
tr3 chi_2671 tr3 chi_2672 tr3 chi_2672(1) 49.08 0.99 0.99
25.52 25.52 52.39 8.61 -71.58 138.43
0.39 0.39 10.25 1.08 0.00 1.14
4.13 4.13 7.16
50.74 SECHO1A 1.03 1.03 SECHO1B 50.74 1.03 SECHO1C 51.89 -94.58 1 -1.96 0.16
-63.04 -63.04 -34.59
224.15 1
1.02
-61.67 -0.00 SVCCHI
0.00 zz lamsur zz lam
18.90 -34.74
CHICLAYO_OESTE_220
Load Flow Balanced
1
Nodes Branches SVS ESTUDIO DE OPERAT IVIDAD Project:
Line-Line Voltage, Magnitude [kV]
Active Power [MW]
SE CHICLAYO OEST E Y SE CHICLAYO NORTE Graphic: SECHO
Voltage, Magnitude [p.u.] Reactive Power [Mvar] Estudio de Flujo de Potencia Date:
Voltage, Angle [deg] Maximum Loading [%] PowerFactory 14.1.3 AV14MED - Caso Proyectado Annex:

DLF SAC Pgina 77 de 132 Revisin: 0


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA EN CHICLAYO OESTE Y CHICLAYO
NORTE

DIgSILENT
CAYAL60 TUMAN60
61.06 10.13 23.20 58.45
60.95 1.01 1.01 0.97
1.02 1.02
-53.29
POMAL10 155.75 POMAL23 -54.16 MOTUP60 -55.97
-53.50
1.21 -1.21 1.21 1.86 -3.07
0.38 -0.38 0.09 0.66 -0.75
18.00 2.20 2.20 29.35 5.48
-0.00 tr3 pom_8001 -1.57 1.57 -6.69 3.85 2.84
lne TUM_C.. 0.00 -0.52 0.52 -1.31 1.21 0.09
23.28 23.28 33.66 63.10 14.09
1 1 Lne 60KV-ILLIMO-LA VIA

lne POM_TUM_81 0
0
1.21 -1.21 -0.00 1.30 -1.30 -0.56 0.56 -5.31 -5.04 6.80
0.36 -0.36 -0.00 0.43 -0.43 -0.18 0.18 -1.42 -1.14 1.21
18.00 tr3 cay_8001 18.00 29.35 tr3 tum_8001 29.35 26.66 25.01 33.66 59.57
3.07 1.57
0.65 0.55 0.99
5.48 23.28 -54.99 Tr3 Motup..
-1.15 -2.70
22.93 10.01 22.90 9.97 -0.38 -0.64
1.00 CAYAL23 1.00 CAYAL10 TUMAN23 1.00 1.00 TUMAN10 LA_VIA60 63.10 63.10
-54.32 155.61 -54.59 154.99
61.17 3.55
POMAL60 1.02 1.35 MOTUP10 MOTUP23
-53.11 76.59
-4.64 9.58 22.03
-1.20

tr2 La Via
lne CHIC_POM_81 0.96 0.96
10.06 8.30 5.10 5.38 150.87 -58.45
1.15 2.70
1.01
155.94
CHICN10 0.95 1.17 0
0.38 0.64
25.01 26.66
ILLIMO60

L-6051
1
13.52 0.00 -3.61 -3.58 -6.33 60.45 -3.54
1.77 0.00 -0.48 -0.52 -0.77 1.01 -1.16
20.69 25.66 21.13 -54.27 76.59
-6.45 -6.45 2.42
Lod motup23
-1.54 -1.54 0.95 LA_VIA10
31.66 31.66 51.70
1 9.77
1 1 0.98
152.49 -2.82
3.54
ZZ chicln T1 T2 T3 1.16
-0.27
14.09
3.65 3.58 6.33 4.65 58.10
0.60 0.60 0.90 1.13 OLMOS60 0.97
-56.36
20.69 25.66 21.13 8.30
0
61.32
1.02 -1.52 -0.91 1.08 1.74
-52.88 -0.50 -0.35 -0.07 0.34
51.70 51.70 5.42 30.46
-4.67 -4.67 0
-0.39 -0.39 ILLIMO23 ILLIMO10
12.97 12.97
22.77 9.92
0.99 0.99
lod chicl23 lod chicl10n Chicl G1 Chicl G2 Chicl G3 Chicl G4 Chicl G5 -56.28 -26.68

L-6032

L-6033
1.52 0.91
0.50 0.35
~ ~ ~ ~ ~

Lne ChiclayoOeste-ChiclayoNorte_L1

Lne ChiclayoOeste-ChiclayoNorte_L2
Breaker/S.. G G G G G -0.87
-0.14
-0.87
-0.14
1 30.46 30.46
3.00 2.50
0.43 0.36 OLMOS10 OLMOS22.9

L-6012

L-6022
CHICL23 CHIL10N 9.61
0.96
22.06
0.96
151.69 -57.69
23.16 10.08 10.08 0.87 0.87
1.01 1.01 1.01 0.14 0.14
-52.95 155.43 155.43
-3.00 -7.38 14.95 0.00 -4.91 -5.16
-0.43 -0.80 1.48 0.00 -0.50 -0.53 L-6037
36.84 36.84 CHICL10 27.98 29.40
tr3 Chiclayo T3
-6.61 3.81 -3.81
-0.88 -0.07 0.03
11.15 6.37 6.37
-1.08
ZZ Chicl 1 1
LAMB_SUR_60 LAMBA60 -0.17
1
5.42
61.33 57.94
T3 T1 T2 1.02
-52.99
61.31
1.02
OCCI60 0.97
-56.56
10.40 4.93 5.18 4.68 4.68 6.52 6.52 6.62
CHICL-O6 1.53 0.73 0.76 0.33 0.33 1.31 1.31 0.81
2.80 3.81 -53.07
0.94 -0.03
36.84 27.98 29.40 12.97 12.97 31.66 31.66 11.15 14.34 54.09
61.50
1.02 1.08

tr2 lam_801
-52.64 0.17
0 16.10
2

-13.97 -13.97 -30.60 0.12


-1
2.25 2.25 -36.64 22.77

14.34
-0.00
-0.00
27.61 27.61 48.39 74.06 2.78 -2.78 -3.78
0.88 -0.88 0.22
tr2 chi_674

14.34 54.09 10.00


1.00 -1.08 -0.00
LAMBA10 154.34 -0.15 0.00
0
0 -0.00 0 0 LAMB_SUR_10 16.10 16.10
-0.00 -0.00
0.00 0.00 -0.00 10.19
27.61 27.61 0 48.39 1.02 OCCI23 OCCI10
-0.00 156.52
0.00 2.80 0.98 0.00 0.00 22.29 9.73
-20.96 0.00 0.57 0.31 -1.10 0.00
tr3 chi_2671 tr3 chi_2672 tr3 chi_2672(1) 74.06 0.97 0.97
13.97 13.97 30.65 7.58 -57.33 152.67
0.39 0.39 10.23 0.95 1.08
-1.87 -1.87 38.75
27.61 SECHO1A 1.02 1.02 SECHO1B 27.61 1.02 SECHO1C 48.39 -82.40 1 0.15
-51.88 -51.88 -22.76
224.62 1
1.02
-51.12 0.00 SVCCHI
-0.00 zz lamsur zz lam
47.88 -26.92
CHICLAYO_OESTE_220
Load Flow Balanced
1
Nodes Branches SVS ESTUDIO DE OPERAT IVIDAD Project:
Line-Line Voltage, Magnitude [kV]
Active Power [MW]
SE CHICLAYO OEST E Y SE CHICLAYO NORTE Graphic: SECHO
Voltage, Magnitude [p.u.] Reactive Power [Mvar] Estudio de Flujo de Potencia Date:
Voltage, Angle [deg] Maximum Loading [%] PowerFactory 14.1.3 AV14MIN - Caso Proyectado Annex:

DLF SAC Pgina 78 de 132 Revisin: 0


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA EN CHICLAYO OESTE Y CHICLAYO
NORTE

DIgSILENT
CAYAL60 TUMAN60
60.33 10.65 24.41 57.89
60.13 1.06 1.06 0.96
1.00 1.01
-59.17
POMAL10 148.07 POMAL23 -61.68 MOTUP60 -63.18
-59.50
1.95 -1.95 1.95 3.08 -5.04
0.62 -0.62 0.35 1.14 -1.49
29.17 3.61 3.61 46.70 9.22
-0.00 tr3 pom_8001 -4.74 4.74 -9.88 5.67 4.21
lne TUM_C.. -0.00 -1.56 1.56 -0.01 1.46 -1.45
71.83 71.83 49.25 86.67 22.20
-1 -5 Lne 60KV-ILLIMO-LA VIA

lne POM_TUM_81 -7
0
1.95 -1.95 -0.00 2.41 -2.41 -0.67 0.67 -7.53 -7.11 10.11
0.58 -0.58 -0.00 0.79 -0.79 -0.22 0.22 -1.10 -0.76 0.08
29.17 tr3 cay_8001 29.17 46.70 tr3 tum_8001 46.70 37.10 34.84 49.25 59.25
5.05 4.74
1.41 1.82 0.99
9.22 71.83 -61.47 Tr3 Motup..
-1.32 -4.35
23.02 10.04 23.95 10.43 -0.03 -1.03
1.00 CAYAL23 1.00 CAYAL10 TUMAN23 1.04 1.04 TUMAN10 LA_VIA60 86.67 86.67
-60.81 149.07 -61.12 148.38
60.54 4.54
POMAL60 1.01 1.79 MOTUP10 MOTUP23
-58.87 98.79
-9.78 9.50 21.78
-3.23

tr2 La Via
lne CHIC_POM_81 0.95 0.95
10.11 18.03 7.23 7.65 142.24 -66.88
1.32 0.00 4.35
1.01
148.20
CHICN10 0.66 0.94 0
0.43 -0.41 1.03
34.84 37.10
ILLIMO60

L-6051
1
40.10 0.00 -10.72 -10.59 -18.79 60.35 -4.53
11.67 0.00 -2.67 -2.68 -4.28 1.01 -1.49
63.54 78.17 64.36 -60.34 98.79
-9.59 -9.59 4.29
Lod motup23
-0.66 -0.66 -0.28 LA_VIA10
45.97 45.97 85.58
-1 9.67
-1 -1 0.97
145.27 -4.17
4.53
ZZ chicln T1 T2 T3 1.49
1.31
22.20
10.76 10.59 18.82 9.81 57.61
3.41 3.37 5.49 3.25 OLMOS60 0.96
-63.96
63.54 78.17 64.36 18.03
0
60.91
1.02 -2.91 -1.38 1.27 2.90
-58.38 1.09 -0.53 -1.92 0.61
85.58 85.58 11.54 51.37
-12.97 -12.97 0
-2.77 -2.77 ILLIMO23 ILLIMO10
36.97 36.97
23.16 10.08
1.01 1.01
lod chicl23 lod chicl10n Chicl G1 Chicl G2 Chicl G3 Chicl G4 Chicl G5 -63.83 -34.45

L-6032

L-6033
-0.00 2.91 1.38
-2.05 0.96 0.53
~ ~ ~ ~ ~

Lne ChiclayoOeste-ChiclayoNorte_L1

Lne ChiclayoOeste-ChiclayoNorte_L2
Breaker/S.. G G G G G -1.44
-0.23
-1.44
-0.23
1 51.37 51.37
6.00 5.00 2.04 2.04 2.04 2.04 2.04
1.50 1.25 0.59
29.84
0.59
29.84
0.59
33.91
0.59
33.91
0.59
33.99
OLMOS10 OLMOS22.9

L-6012

L-6022
CHICL23 CHIL10N 9.48
0.95
21.79
0.95
142.73 -66.20
23.11 10.00 10.00 1.44 1.44
1.01 1.00 1.00 0.23 0.23
-58.50 149.22 149.22
-6.00 -11.60 32.43 0.00 -7.62 -8.01
-1.50 -2.35 7.18 0.00 -1.52 -1.60 L-6037
59.23 59.23 CHICL10 44.40 46.65
tr3 Chiclayo T3
-8.81 2.32 -2.32
-1.80 -0.42 0.39
15.05 3.96 3.96
-1.26
ZZ Chicl 1 1
LAMB_SUR_60 LAMBA60 1.70
1
11.54
61.24 57.78
T3 T1 T2 1.02
-58.23
61.23
1.02
OCCI60 0.96
-64.46
17.62 7.64 8.03 13.06 13.06 9.74 9.74 8.83
CHICL-O6 4.62 1.99 2.10 2.85 2.85 0.67 0.67 1.77
6.48 2.32 -58.28
2.23 -0.39
59.23 44.40 46.65 36.97 36.97 45.97 45.97 15.05 33.46 32.98
61.50
1.02 1.26

tr2 lam_801
-57.77 -1.70
0 31.38
-2

-27.53 -27.53 -56.98 0.14


0
-13.49 -13.49 -26.20 25.58

33.46
-0.00
0.00
62.16 62.16 63.57 83.18 6.46 -6.46 -2.30
2.05 -2.05 0.47
tr2 chi_674

33.46 32.98 10.44


1.04 -1.26 -0.00
LAMBA10 150.25 1.76 -0.00
-3
0 -0.00 0 0 LAMB_SUR_10 31.38 31.38
-0.00 -0.00
0.00 0.00 0.00 10.13
62.16 62.16 0 63.57 1.01 OCCI23 OCCI10
-0.00 150.62
0.00 0.00 2.30 -0.00 0.00 22.54 9.84
-23.32 0.00 0.00 0.73 -1.20 0.00
tr3 chi_2671 tr3 chi_2672 tr3 chi_2672(1) 83.18 0.98 0.98
27.53 27.53 57.07 7.50 -65.36 144.64
0.39 0.39 10.24 0.94 0.00 1.26
15.27 15.27 29.84
62.16 SECHO1A 1.04 1.04 SECHO1B 62.16 1.02 SECHO1C 63.57 -87.50 1 -1.94 0.18
-56.30 -56.30 -27.98
222.87 1
1.01
-54.87 -0.00 SVCCHI
-0.00 zz lamsur zz lam
49.70 -26.38
CHICLAYO_OESTE_220
Load Flow Balanced
1
Nodes Branches SVS ESTUDIO DE OPERAT IVIDAD Project:
Line-Line Voltage, Magnitude [kV]
Active Power [MW]
SE CHICLAYO OEST E Y SE CHICLAYO NORTE Graphic: SECHO
Voltage, Magnitude [p.u.] Reactive Power [Mvar] Estudio de Flujo de Potencia Date:
Voltage, Angle [deg] Maximum Loading [%] PowerFactory 14.1.3 ES14MAX - Caso Proyectado Annex:

DLF SAC Pgina 79 de 132 Revisin: 0


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA EN CHICLAYO OESTE Y CHICLAYO
NORTE

DIgSILENT
CAYAL60 TUMAN60
61.44 10.22 23.42 59.10
61.27 1.02 1.02 0.98
1.02 1.02
-61.92
POMAL10 145.88 POMAL23 -63.92 MOTUP60 -65.88
-62.19
1.62 -1.62 1.62 2.46 -4.08
0.51 -0.51 0.22 0.90 -1.12
23.74 2.93 2.93 36.51 7.29
-0.00 tr3 pom_8001 -3.45 3.45 -9.57 5.65 3.93
lne TUM_C.. -0.00 -1.14 1.14 0.18 1.45 -1.63
51.31 51.31 46.79 84.58 20.76
0 0 Lne 60KV-ILLIMO-LA VIA

lne POM_TUM_81 -1
0
1.62 -1.62 -0.00 1.77 -1.77 -0.69 0.69 -7.36 -6.94 9.78
0.48 -0.48 -0.00 0.58 -0.58 -0.23 0.23 -0.97 -0.64 -0.15
23.74 tr3 cay_8001 23.74 36.51 tr3 tum_8001 36.51 35.50 33.33 46.79 60.35
4.09 3.45
1.03 1.29 1.01
7.29 51.31 -64.25 Tr3 Motup..
-1.56 -4.09
23.25 10.15 23.21 10.11 -0.09 -0.97
1.01 CAYAL23 1.01 CAYAL10 TUMAN23 1.01 1.01 TUMAN10 LA_VIA60 84.58 84.58
-63.26 146.65 -63.59 145.90
61.59 4.51
POMAL60 1.03 1.77 MOTUP10 MOTUP23
-61.68 96.41
-7.54 9.70 22.25
-2.32

tr2 La Via
lne CHIC_POM_81 0.97 0.97
10.05 13.57 7.05 7.47 139.64 -69.43
1.56 0.00 4.09
1.01
146.00
CHICN10 0.52 0.78 0
0.51 -0.42 0.97
33.33 35.50
ILLIMO60

L-6051
1
30.97 0.00 -8.28 -8.18 -14.51 61.39 -4.50
9.19 0.00 -1.98 -2.00 -3.19 1.02 -1.48
48.39 59.82 49.25 -63.17 96.41
-8.79 -8.79 3.06
Lod motup23
-0.19 -0.19 -0.92 LA_VIA10
41.32 41.32 62.38
1 9.86
1 1 0.99
142.62 -3.89
4.50
ZZ chicln T1 T2 T3 1.48
1.47
20.76
8.32 8.18 14.53 7.56 58.89
2.44 2.41 3.91 2.28 OLMOS60 0.98
-66.60
48.39 59.82 49.25 13.57
0
61.86
1.03 -1.69 -1.37 1.15 2.74
-61.32 1.59 -0.52 -2.04 0.57
62.38 62.38 11.48 47.51
-9.99 -9.99 0
-1.90 -1.90 ILLIMO23 ILLIMO10
27.91 27.91
23.74 10.34
1.03 1.03
lod chicl23 lod chicl10n Chicl G1 Chicl G2 Chicl G3 Chicl G4 Chicl G5 -65.57 -36.11

L-6032

L-6033
-0.00 1.69 1.37
-2.15 0.56 0.52
~ ~ ~ ~ ~

Lne ChiclayoOeste-ChiclayoNorte_L1

Lne ChiclayoOeste-ChiclayoNorte_L2
Breaker/S.. G G G G G -1.37
-0.21
-1.37
-0.21
1 47.51 47.51
4.80 4.00
0.97 0.81 OLMOS10 OLMOS22.9

L-6012

L-6022
CHICL23 CHIL10N 9.70
0.97
22.29
0.97
140.41 -68.63
23.45 10.13 10.13 1.37 1.37
1.02 1.01 1.01 0.21 0.21
-61.34 146.07 146.07
-4.80 -11.98 24.35 0.00 -7.98 -8.39
-0.97 -2.41 4.87 0.00 -1.60 -1.68 L-6037
60.34 60.34 CHICL10 45.93 48.27
tr3 Chiclayo T3
-13.40 5.43 -5.43
-3.24 0.47 -0.50
22.85 9.04 9.04
-1.14
ZZ Chicl 1 1
LAMB_SUR_60 LAMBA60 1.81
1
11.48
61.87 59.09
T3 T1 T2 1.03
-61.53
61.82
1.03
OCCI60 0.98
-67.07
16.80 8.01 8.41 10.04 10.04 8.91 8.91 13.46
CHICL-O6 4.14 2.10 2.21 1.91 1.91 0.10 0.10 3.31
7.97 5.43 -61.64
2.77 0.50
60.34 45.93 48.27 27.91 27.91 41.32 41.32 22.85 40.80 75.57
62.30
1.04 1.14

tr2 lam_801
-60.86 -1.81
0 30.99
0

-25.41 -25.41 -52.62 0.18


0
-13.26 -13.26 -25.83 29.36

40.80
-0.00
0.00
57.36 57.36 58.66 94.25 7.94 -7.94 -5.39
2.53 -2.53 -0.15
tr2 chi_674

40.80 75.57 10.22


1.02 -1.14 -0.00
LAMBA10 144.88 1.87 0.00
-3
0 -0.00 0 0 LAMB_SUR_10 30.99 30.99
-0.00 -0.00
-0.00 -0.00 0.00 10.22
57.36 57.36 0 58.66 1.02 OCCI23 OCCI10
-0.00 147.09
0.00 3.65 1.74 0.00 0.00 23.06 10.07
-26.48 0.00 0.74 0.55 -1.15 0.00
tr3 chi_2671 tr3 chi_2672 tr3 chi_2672(1) 94.25 1.01 1.01
25.41 25.41 52.70 7.52 -67.85 142.15
0.40 0.40 10.37 0.94 0.00 1.14
14.77 14.77 28.92
57.36 SECHO1A 1.05 1.05 SECHO1B 57.36 1.04 SECHO1C 58.66 -90.55 1 -2.03 0.16
-59.53 -59.53 -31.04
225.46 1
1.02
-58.24 0.00 SVCCHI
0.00 zz lamsur zz lam
52.95 -26.48
CHICLAYO_OESTE_220
Load Flow Balanced
1
Nodes Branches SVS ESTUDIO DE OPERAT IVIDAD Project:
Line-Line Voltage, Magnitude [kV]
Active Power [MW]
SE CHICLAYO OEST E Y SE CHICLAYO NORTE Graphic: SECHO
Voltage, Magnitude [p.u.] Reactive Power [Mvar] Estudio de Flujo de Potencia Date:
Voltage, Angle [deg] Maximum Loading [%] PowerFactory 14.1.3 ES14MED - Caso Proyectado Annex:

DLF SAC Pgina 80 de 132 Revisin: 0


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA EN CHICLAYO OESTE Y CHICLAYO
NORTE

DIgSILENT
CAYAL60 TUMAN60
61.15 10.14 23.24 58.54
61.03 1.01 1.01 0.98
1.02 1.02
-57.13
POMAL10 151.92 POMAL23 -57.99 MOTUP60 -59.80
-57.33
1.21 -1.21 1.21 1.86 -3.07
0.38 -0.38 0.08 0.66 -0.75
17.98 2.20 2.20 29.31 5.47
-0.00 tr3 pom_8001 -1.57 1.57 -6.69 3.85 2.84
lne TUM_C.. 0.00 -0.52 0.52 -1.31 1.21 0.09
23.25 23.25 33.61 62.99 14.07
1 1 Lne 60KV-ILLIMO-LA VIA

lne POM_TUM_81 0
0
1.21 -1.21 -0.00 1.30 -1.30 -0.56 0.56 -5.31 -5.03 6.79
0.36 -0.36 0.00 0.43 -0.43 -0.18 0.18 -1.42 -1.13 1.21
17.98 tr3 cay_8001 17.98 29.31 tr3 tum_8001 29.31 26.62 24.97 33.61 59.66
3.07 1.57
0.65 0.55 0.99
5.47 23.25 -58.82 Tr3 Motup..
-1.15 -2.70
22.96 10.02 22.93 9.99 -0.38 -0.64
1.00 CAYAL23 1.00 CAYAL10 TUMAN23 1.00 1.00 TUMAN10 LA_VIA60 62.99 62.99
-58.15 151.77 -58.42 151.16
61.26 3.55
POMAL60 1.02 1.35 MOTUP10 MOTUP23
-56.95 76.47
-4.64 9.60 22.06
-1.20

tr2 La Via
lne CHIC_POM_81 0.96 0.96
10.08 8.29 5.10 5.38 147.05 -62.27
1.15 2.70
1.01
152.11
CHICN10 0.95 1.17 0
0.38 0.64
24.97 26.62
ILLIMO60

L-6051
1
13.52 0.00 -3.61 -3.58 -6.33 60.54 -3.54
1.77 0.00 -0.48 -0.52 -0.77 1.01 -1.16
20.66 25.63 21.10 -58.10 76.47
-6.45 -6.45 2.42
Lod motup23
-1.53 -1.53 0.95 LA_VIA10
31.61 31.61 51.62
1 9.79
1 1 0.98
148.67 -2.82
3.54
ZZ chicln T1 T2 T3 1.16
-0.27
14.07
3.65 3.58 6.33 4.65 58.19
0.60 0.60 0.90 1.13 OLMOS60 0.97
-60.19
20.66 25.63 21.10 8.29
0
61.41
1.02 -1.52 -0.91 1.08 1.74
-56.71 -0.50 -0.35 -0.07 0.34
51.62 51.62 5.41 30.41
-4.67 -4.67 0
-0.39 -0.39 ILLIMO23 ILLIMO10
12.95 12.95
22.81 9.93
0.99 0.99
lod chicl23 lod chicl10n Chicl G1 Chicl G2 Chicl G3 Chicl G4 Chicl G5 -60.10 -30.51

L-6032

L-6033
1.52 0.91
0.50 0.35
~ ~ ~ ~ ~

Lne ChiclayoOeste-ChiclayoNorte_L1

Lne ChiclayoOeste-ChiclayoNorte_L2
Breaker/S.. G G G G G -0.87
-0.14
-0.87
-0.14
1 30.41 30.41
3.00 2.50
0.43 0.36 OLMOS10 OLMOS22.9

L-6012

L-6022
CHICL23 CHIL10N 9.63
0.96
22.10
0.96
147.87 -61.51
23.20 10.09 10.09 0.87 0.87
1.01 1.01 1.01 0.14 0.14
-56.79 151.60 151.60
-3.00 -7.38 14.95 0.00 -4.91 -5.16
-0.43 -0.80 1.48 0.00 -0.50 -0.53 L-6037
36.79 36.79 CHICL10 27.94 29.36
tr3 Chiclayo T3
-6.61 3.81 -3.81
-0.87 -0.07 0.03
11.13 6.36 6.36
-1.08
ZZ Chicl 1 1
LAMB_SUR_60 LAMBA60 -0.17
1
5.41
61.42 58.03
T3 T1 T2 1.02
-56.83
61.39
1.02
OCCI60 0.97
-60.38
10.40 4.93 5.18 4.68 4.68 6.52 6.52 6.62
CHICL-O6 1.53 0.73 0.76 0.33 0.33 1.30 1.30 0.81
2.80 3.81 -56.91
0.94 -0.03
36.79 27.94 29.36 12.95 12.95 31.61 31.61 11.13 14.31 54.01
61.59
1.03 1.08

tr2 lam_801
-56.48 0.17
0 16.08
2

-14.37 -14.37 -29.86 0.18


-1
-9.59 -9.59 -18.87 28.69

14.31
-0.00
0.00
33.65 33.65 34.42 93.17 2.78 -2.78 -3.78
0.88 -0.88 0.22
tr2 chi_674

14.31 54.01 10.01


1.00 -1.08 -0.00
LAMBA10 150.51 -0.15 0.00
0
0 -0.00 0 0 LAMB_SUR_10 16.08 16.08
-0.00 -0.00
-0.00 -0.00 -0.00 10.20
33.65 33.65 0 34.42 1.02 OCCI23 OCCI10
-0.00 152.68
0.00 2.80 0.98 -0.00 0.00 22.33 9.75
-25.87 0.00 0.57 0.31 -1.10 0.00
tr3 chi_2671 tr3 chi_2672 tr3 chi_2672(1) 93.17 0.97 0.98
14.37 14.37 29.89 7.43 -61.16 148.85
0.39 0.39 10.26 0.93 1.08
10.15 10.15 20.02
33.65 SECHO1A 1.04 1.04 SECHO1B 33.65 1.03 SECHO1C 34.42 -86.18 1 0.15
-55.71 -55.71 -26.59
229.97 1
1.05
-54.96 0.00 SVCCHI
-0.00 zz lamsur zz lam
51.75 -25.87
CHICLAYO_OESTE_220
Load Flow Balanced
1
Nodes Branches SVS ESTUDIO DE OPERAT IVIDAD Project:
Line-Line Voltage, Magnitude [kV]
Active Power [MW]
SE CHICLAYO OEST E Y SE CHICLAYO NORTE Graphic: SECHO
Voltage, Magnitude [p.u.] Reactive Power [Mvar] Estudio de Flujo de Potencia Date:
Voltage, Angle [deg] Maximum Loading [%] PowerFactory 14.1.3 ES14MIN - Caso Proyectado Annex:

DLF SAC Pgina 81 de 132 Revisin: 0


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE
POTENCIA EN CHICLAYO OESTE Y CHICLAYO NORTE

ANEXO IV:

RESULTADOS DE CORTOCIRCUITO.

OPERACION NORMAL BASE

Fallas Monofsicas
Estiaje 2014 Mximo Demanda
Estiaje 2014 Mnimo Demanda

Fallas Bifsicas
Estiaje 2014 Mximo Demanda
Estiaje 2014 Mnimo Demanda

Fallas Trifsicas
Estiaje 2014 Mximo Demanda
Estiaje 2014 Mnimo Demanda

OPERACION NORMAL CON PROYECTO

Estiaje 2014 Mxima Demanda


Fallas Monofsicas
Fallas Bifsicas
Fallas trifsicas

OPERACION NORMAL CON PROYECTO (Acoplamiento Cerrado)

Estiaje 2014 Mxima Demanda


Fallas Monofsicas
Fallas Bifsicas
Fallas trifsicas

DLF SAC Pgina 82 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA EN CHICLAYO OESTE Y CHICLAYO NORTE

DIgSILENT
0.000 32.994
SE. CHICLAYO NORTE POMAL10 0.000
0.000 POMAL23 2.485
6.577
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00 88.792
0.00 tr3 pom_8001 32.99 0.00
0.00 0.00 0.00 0.00 2.48 0.00 TUMAN60 2.563
5.232 CAYAL60
0.00 6.58 0.00

Breaker/S..

Breaker/S..

Breaker/S..
CHICN10B 0.00 2.48 0.00 46.070
1.330
2.159
CHICN10C 0.374 78.89 5.88 4.16
2.686
40.05 6.12
0.910 CHICN10 L-6051 -7 2.28 0.17 0.12 1.16 0.18
2.159 4.65 0.35 0.25 2.33 0.36
2.159 1.71 0.51 0.36 0.81 0.53
0.374 lne POM_TUM_81 lne TUM_CAY_81
0.910
0.374 lne CHIC_POM_81 121.43 5.52 7.54
0.910 3.51 0.16 0.22
0.91 IN1032 0.50 IN1030 0.53 0.74
7.23 0.33 0.45 -5 -1
0.16 0.09 0.09 0.13
2.77 0.48 0.65
0.38 0.21 0.22 0.31
0.00 0.26 0.00 0.38
-1 POMAL60 30.48 0.00 25.13 0.00
2.30 0.00 1.89 0.00
25.62
0.74
T3 -1
T2 -1
14.89
0.43
T1 6.41
0.19
134.274
3.876
5.92
2.30 tr3 tum_8001
0.00
0.00
4.63
1.89 tr3 cay_8001
0.00
0.00
ZZ chicln 7.996
1.56
2.22
0.91
1.29
0.39
0.56
TUMAN23 TUMAN10 CAYAL23 CAYAL10
268.013
7.737 30.485 0.000 25.130 0.000
16.328 2.296 0.000 1.892 0.000
5.923 0.000 4.633 0.000
0.00 0.00
0.00 0.00
0.00 0.00
111.25 111.25 0.00 0.00
3.21 3.21
ZZ CT Chicl 6.78 6.78
Chicl G1 Chicl G2 Chicl G3 Chicl G4 Chicl G5
1.94 1.94
~ ~ ~ ~ ~
G G G G G
SE. CHICLAYO OESTE 0.45 0.23 0.23 0.27
Lne 60KV-ILLIMO-LA VIA
0.08 0.04 0.04 0.05
0.21 0.11 0.11 0.12
0.24 0.04 0.04 0.04 40.00 40.00 5.48 5.15 29.63 28.40 5.13 36.81
1.15 1.15 0.16 0.15 0.86 0.82 0.15 1.06
CT CHICL10

Lne ChiclayoOeste-ChiclayoNorte_L2
Lne ChiclayoOeste-ChiclayoNorte_L1
2.39 2.39 0.33 0.31 1.59 1.52 0.27 1.83
3.318 0.67 0.67 0.47 0.45 0.38 0.40 0.44 0.51
0.575
1.543 ILLIMO60 LA_VIA60 MOTUP60
lod chicl23 lod chicl10n 96.716 73.538
0.00 0.00 2.792 2.123 46.331
0.00 0.00 5.771 3.937 1.337

IN1007
2.299

L-6012

L-6022

L-6032

L-6033
0.00 0.00 6.16 10.48 4.46 5.11
0.00 0.00 0.18 0.30 0.13 0.15
0.37 0.56 0.22 0.25
Breaker/S..

Breaker/S..

tr2 La Via
0.53 0 0.91 0.39 0.44
0
CHICL23 CHIL10N CHICL10B 0
28.06 0.00 0.00
3.318 2.11 0.00 0.00
0.575 5.55 0.00 0.00
1.543 CHICL10A 2.11 0.00 0.00
Breaker/S.. 0.45 0.83 IN - 1008 0.85
0.08 0.14 0.15 3.318 ILLIMO10 LA_VIA10 Tr3 Motup..
0.21 0.39 0.40 0.575 ILLIMO23 0.34
0.06
26.37
1.99
tr3 Chiclayo T3 0.24 0.00 0.00 1.543 28.059 0.000 0.000 0.14 4.26
2.113 0.000 0.000 0.00 1.99
5.553 0.000 0.000
0.00 0.00 0.00 0.00
0 0 0.00 0.00 0.00 0.00 MOTUP10 MOTUP23
0.00 0.00 0.00 0.00
0 T3 ZZ Chicl
17.33
0.50
T1 17.68
0.51
T2 5.13
0.15
5.13
0.15
1.05
0.03
1.05
0.03
0.00
1
0.00 0.00 0.00 0.507
0.088
0.203
26.372
1.995
4.255
0.00 0.17 0.00
1.26 1.28 0.37 0.37 0.08 0.08 0.00 0.03 0.00
28.79
CHICL-O6 0.55 0.56 0.44 0.44 0.09 0.09
0.83 0.00 0.07 0.00
1.39 0.00 0.09 0.00
472.911 1
0.43
13.652
34.362 OLMOS60
124.24 124.24 171.40 0.00 6.00 35.758
Lod motup23
3.59 3.59 4.95 0.00 0.17 LAMB_SUR_60 LAMBA60 1.032 22.39
9.03 9.03 12.45 0.00 0.44 1.732 0.65
4.43 4.43 2.13 0.00 0.52 194.053 3.73 3.27
0 151.338 0.11 0.09 1.07
-3 -3 5.602
4.369 0.18 0.16 0.35
12.464
156.52 29.28 8.45 140.04 11.39 9.549 0.32 0.28
OCCI60
tr2 chi_674

OLMOS22.9
0.00 0.00 0.00 4.52 0.85 0.24 4.04 0.33
0.00 0.00 0.00 10.05 1.88 0.54 8.84 0.72 0
0.00 0.00 0.00 2.37 2.54 0.73 3.39 0.99 27.560

tr2 lam_801

21.009
tr3 chi_2671 tr3 chi_2672 0.00 tr3 chi_2672(1) 0.00 0.796

1.589
3.171
0.00 0.00
0.00 5.20 1.316
-2 0.00
36.78 36.78 69.62 0.15
0 0.00
0.29 0.29 0.55 0.25
0.000 0.000 0.000
0.69
SECHO1A 0.000 0.000 SECHO1B 0.69
0.000 SECHO1C
1.31
0.25
L-6037 0.24 OLMOS10
0.45 0

21.01
0.76 0.76 1.43

1.59
3.17
1.59

0.00
0.00
0.00
0.00
0.000 0.000 0.000 0.05 0.04
0.14 0.10 0.000
0.05 0.00 19.32 0.00

0.00
0.00
0.00
0.00
0.000 1.46 0.00
0.000 0.00
669.612
0.99
LAMBA10 0.00
2.86
1.46
0.00
0.00
5.272 0.254 0.00
12.643 CHICLAYO_OESTE_220 0.055
0.17
0.42
0.364 0.00
0.142 0.00
0.063 OCCI23 OCCI10
0.156
0.00 0.00 0.00 0.00 0.00 0.12
SVCCHI 0.00 0.00 LAMB_SUR_10 0.00 0.00 0.00 0.02
19.322
1.461
0.000
0.000
0.00 0.00 0.00 0.00 0.00 0.05 2.859 0.000
0.00 0.00 1.489 0.00 0.00 0.00 0.06 0.00 0.00
1 0.258 1 0.00 0.00
Max. Single Phase to Ground acc. to IEC60909 SVS 0.636
0.00 0.50
0.00 0.00
0.00 0.00
0.00 0.09 1
Short Circuit Nodes Nodes 0.00 0.21
0.00 0.26 zz lam
Initial Short-Circuit Power A [MVA]Line-Ground Voltage, Magnitude A
Initial Short-Circuit Current A [kA] Line-Ground Voltage, Magnitude B
ESTUDIO DE OPERAT IVIDAD Project:
zz lamsur
Peak Short-Circuit Current A [kA] Line-Ground Voltage, Magnitude C
SE CHICLAYO OEST E Y SE CHICLAYO NORTE Graphic: EOP SECHO
Estudio de Cortocircuito Monofsico Date: 2/12/2014
PowerFactory 14.1.3 ES14MAX - Base Annex:

DLF SAC Pgina 83 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA EN CHICLAYO OESTE Y CHICLAYO NORTE

DIgSILENT
0.000 32.101
SE. CHICLAYO NORTE POMAL10 0.000
0.000 POMAL23 2.417
6.380
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00 82.588
0.00 tr3 pom_8001 32.10 0.00
0.00 0.00 0.00 0.00 2.42 0.00 TUMAN60 2.384
4.951 CAYAL60
0.00 6.38 0.00

Breaker/S..

Breaker/S..

Breaker/S..
CHICN10B 0.00 2.42 0.00 44.342
1.280
1.487
CHICN10C 0.258 73.38 5.47 3.87
2.611
38.54 5.89
0.627 CHICN10 L-6051 0 2.12 0.16 0.11 1.11 0.17
1.487 4.40 0.33 0.23 2.27 0.35
1.487 1.59 0.47 0.34 0.78 0.51
0.258 lne POM_TUM_81 lne TUM_CAY_81
0.627
0.258 lne CHIC_POM_81 109.04 4.96 6.77
0.627 3.15 0.14 0.20
0.63 IN1032 0.50 IN1030 0.36 0.37
6.64 0.30 0.41 1 1
0.11 0.09 0.06 0.06
2.49 0.43 0.59
0.26 0.21 0.15 0.15
0.00 0.26 0.00 0.19
1 POMAL60 29.72 0.00 24.61 0.00
2.24 0.00 1.85 0.00
20.90
0.60
T3 1
T2 1
12.14
0.35
T1 5.23
0.15
120.578
3.481
5.76
2.24 tr3 tum_8001
0.00
0.00
4.54
1.85 tr3 cay_8001
0.00
0.00
ZZ chicln 7.345
1.31
1.81
0.76
1.05
0.33
0.45
TUMAN23 TUMAN10 CAYAL23 CAYAL10
218.401
6.305 29.720 0.000 24.607 0.000
13.713 2.238 0.000 1.853 0.000
5.764 0.000 4.536 0.000
0.00 0.00
0.00 0.00
0.00 0.00
90.64 90.64 0.00 0.00
2.62 2.62
ZZ CT Chicl 5.69 5.69
Chicl G1 Chicl G2 Chicl G3 Chicl G4 Chicl G5
1.58 1.58
~ ~ ~ ~ ~
G G G G G
SE. CHICLAYO OESTE 0.43
Lne 60KV-ILLIMO-LA VIA
0.07
0.20
0.22 36.97 36.97 5.07 4.76 27.91 26.75 4.84 35.46
1.07 1.07 0.15 0.14 0.81 0.77 0.14 1.02
CT CHICL10

Lne ChiclayoOeste-ChiclayoNorte_L2
Lne ChiclayoOeste-ChiclayoNorte_L1
2.24 2.24 0.31 0.29 1.52 1.46 0.26 1.78
2.581 0.62 0.62 0.44 0.41 0.36 0.38 0.42 0.50
0.447
1.205 ILLIMO60 LA_VIA60 MOTUP60
lod chicl23 lod chicl10n 89.381 69.273
0.00 0.00 2.580 2.000 44.639
0.00 0.00 5.424 3.774 1.289

IN1007
2.242

L-6012

L-6022

L-6032

L-6033
0.00 0.00 5.69 9.87 4.30 4.92
0.00 0.00 0.16 0.28 0.12 0.14
0.35 0.54 0.22 0.25
Breaker/S..

Breaker/S..

tr2 La Via
0.49 0 0.85 0.37 0.43
0
CHICL23 CHIL10N CHICL10B 0
27.41 0.00 0.00
2.581 2.06 0.00 0.00
0.447 5.41 0.00 0.00
1.205 CHICL10A 2.06 0.00 0.00
Breaker/S.. 0.43 0.85 IN - 1008 0.87
0.07 0.15 0.15 2.581 ILLIMO10 LA_VIA10 Tr3 Motup..
0.20 0.40 0.41 0.447 ILLIMO23 0.00
0.00
25.79
1.95
tr3 Chiclayo T3 0.22 0.00 0.00 1.205 27.410 0.000 0.000 0.00 4.17
2.064 0.000 0.000 0.00 1.95
5.412 0.000 0.000
0.00 0.00 0.00
1 1 0.00 0.00 0.00 MOTUP10 MOTUP23
0.00 0.00 0.00
0 T3 ZZ Chicl
4.57
0.13
T1 4.66
0.13
T2 3.71
0.11
3.71
0.11
0.76
0.02
0.76
0.02
1
0.00 0.00 0.00 0.000
0.000
0.000
25.795
1.951
4.174
0.00 0.00
0.33 0.33 0.27 0.27 0.05 0.05 0.00 0.00
27.98
CHICL-O6 0.40 0.40 0.32 0.32 0.07 0.07
0.81 0.00 0.00
1.37 0.00 0.00
336.703 1
0.42
9.720
24.183 OLMOS60
92.50 92.50 129.45 0.00 4.33 34.753
Lod motup23
2.67 2.67 3.74 0.00 0.13 LAMB_SUR_60 LAMBA60 1.003 21.90
6.64 6.64 9.30 0.00 0.31 1.699 0.63
3.16 3.16 1.47 0.00 0.38 166.520 3.62 3.18
0 134.069 0.10 0.09 1.05
0 0 4.807
3.870 0.18 0.16 0.34
10.862
134.30 25.14 7.25 124.06 10.09 8.594 0.31 0.28
OCCI60
tr2 chi_674

OLMOS22.9
0.00 0.00 0.00 3.88 0.73 0.21 3.58 0.29
0.00 0.00 0.00 8.76 1.64 0.47 7.95 0.65 0
0.00 0.00 0.00 2.03 2.18 0.63 3.00 0.87 26.963

tr2 lam_801

20.644
tr3 chi_2671 tr3 chi_2672 0.00 tr3 chi_2672(1) 0.00 0.778

1.561
3.126
0.00 0.00
0.00 5.09 1.296
2 0.00
22.95 22.95 43.07 0.15
0 0.00
0.18 0.18 0.34 0.24
0.000 0.000 0.000
0.43
SECHO1A 0.000 0.000 SECHO1B 0.43
0.000 SECHO1C
0.82
0.25
L-6037 0.24 OLMOS10
0.44 -1

20.64
0.54 0.54 1.02

1.56
3.13
1.56

0.00
0.00
0.00
0.00
0.000 0.000 0.000 0.05 0.04
0.14 0.10 0.000
0.05 0.00 19.01 0.00

0.00
0.00
0.00
0.00
0.000 1.44 0.00
0.000 0.00
438.730
0.99
LAMBA10 0.00
2.82
1.44
0.00
0.00
3.454 0.254 0.00
8.303 CHICLAYO_OESTE_220 0.055
0.17
0.42
0.364 0.00
0.142 0.00
0.063 OCCI23 OCCI10
0.156
0.00 0.00 0.00 0.00 0.00 0.12
SVCCHI 0.00 0.00 LAMB_SUR_10 0.00 0.00 0.00 0.02
19.014
1.438
0.000
0.000
0.00 0.00 0.00 0.00 0.00 0.05 2.822 0.000
0.00 0.00 1.488 0.00 0.00 0.00 0.06 0.00
1 0.258 1 0.00
Max. Single Phase to Ground acc. to IEC60909 SVS 0.635
0.00 0.50
0.00
0.00
0.00 0.09 1
Short Circuit Nodes Nodes 0.00 0.21
0.00 0.26 zz lam
Initial Short-Circuit Power A [MVA]Line-Ground Voltage, Magnitude A
Initial Short-Circuit Current A [kA] Line-Ground Voltage, Magnitude B
ESTUDIO DE OPERAT IVIDAD Project:
zz lamsur
Peak Short-Circuit Current A [kA] Line-Ground Voltage, Magnitude C
SE CHICLAYO OEST E Y SE CHICLAYO NORTE Graphic: EOP SECHO
Estudio de Cortocircuito Monofsico Date: 2/12/2014
PowerFactory 14.1.3 ES14MIN - Base Annex:

DLF SAC Pgina 84 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA EN CHICLAYO OESTE Y CHICLAYO NORTE

DIgSILENT
11.974 22.138
SE. CHICLAYO NORTE POMAL10 2.074
5.654 POMAL23 1.667
4.413
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00 83.216
11.97 tr3 pom_8001 22.14 0.00
2.07 1.67 0.00 TUMAN60 2.402
4.904 CAYAL60
2.07 1.67 0.00

Breaker/S..

Breaker/S..

Breaker/S..
CHICN10B 0.00 44.203
0.00 1.276
87.094
CHICN10C 15.085 0.00 83.22 0.00 0.00
2.577
44.20 0.00
36.722 0.00 CHICN10 L-6051 -7 2.40 0.00 0.00 1.28 0.00
87.094 2.40 0.00 0.00 1.28 0.00
87.094
15.085 lne POM_TUM_81 lne TUM_CAY_81
36.722
15.085 lne CHIC_POM_81 121.29 0.00 0.00
36.722 3.50 0.00 0.00
55.09 IN1032 0.00 IN1030 32.01 0.00
3.50 0.00 0.00 -5 -1
9.54 0.00 5.55 0.00
9.54 0.00 5.55 0.00

-1 POMAL60 20.49 11.47 16.92 10.26


1.54 1.99 1.27 1.78
0.00
0.00
T3 -1
T2 -1
0.00
0.00
T1 0.00
0.00
121.292
3.501
1.54
tr3 tum_8001
1.99 1.27
tr3 cay_8001
1.78

ZZ chicln 7.223
0.00 0.00 0.00 TUMAN23 TUMAN10 CAYAL23 CAYAL10
201.180
5.808 20.490 11.473 16.923 10.262
12.256 1.543 1.987 1.274 1.777
3.981 5.331 3.120 4.590
0.00 0.00
0.00 0.00
0.00 0.00
100.59 100.59
2.90 2.90
ZZ CT Chicl 2.90 2.90
Chicl G1 Chicl G2 Chicl G3 Chicl G4 Chicl G5
~ ~ ~ ~ ~
G G G G G
SE. CHICLAYO OESTE 0.00 8.72 8.72 10.47
Lne 60KV-ILLIMO-LA VIA
0.00 1.45 1.45 1.71
0.00 1.51 1.51 1.81
43.93 43.93 0.00 0.00 30.68 28.84 0.00 35.82
1.27 1.27 0.00 0.00 0.89 0.83 0.00 1.03
CT CHICL10

Lne ChiclayoOeste-ChiclayoNorte_L2
Lne ChiclayoOeste-ChiclayoNorte_L1
1.27 1.27 0.00 0.00 0.89 0.83 0.00 1.03
114.044
19.753
53.030 ILLIMO60 LA_VIA60 MOTUP60
lod chicl23 lod chicl10n 87.853 59.514
0.00 0.00 2.536 1.718 35.820
0.00 0.00 5.242 3.186 1.034

IN1007
1.778

L-6012

L-6022

L-6032

L-6033
0.00 0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00
Breaker/S..

Breaker/S..

tr2 La Via
0.00 0
0.00 0
CHICL23 CHIL10N CHICL10B 0.00
0.00 0
17.99 12.55 18.50
114.044 1.35 2.17 3.20
19.753 1.35 2.17 3.20
53.030 CHICL10A
Breaker/S.. 0.00 42.69 IN - 1008 43.54
0.00 7.50 7.64 114.044 ILLIMO10 LA_VIA10 Tr3 Motup..
0.00 7.39 7.54 19.753 ILLIMO23 11.68
2.02
17.12
1.29
tr3 Chiclayo T3 53.030 17.988 12.553 18.497 2.02 1.29
1.355 2.174 3.204
3.560 5.836 7.745
0.00 0.00 0.00 0.00
0 0 0.00 0.00 0.00 0.00 MOTUP10 MOTUP23
0.00 0.00 0.00 0.00
0 T3 ZZ Chicl
10.76
0.30
T1 10.98
0.30
T2 0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
1
11.676
2.022
4.672
17.116
1.295
2.762
0.00 0.00 0.00
0.31 0.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00
26.75
CHICL-O6 0.77 0.00 0.00 0.00
0.77
301.390 1
8.700
21.899 OLMOS60
69.78 69.78 140.10 0.00 0.00 26.749
Lod motup23
2.02 2.02 4.06 0.00 0.00 LAMB_SUR_60 LAMBA60 0.772 20.28
2.01 2.01 4.04 0.00 0.00 1.295 0.59
151.360 0.00 0.00
0 127.172 0.00 0.00 0.59
-3 -3 4.369
9.722 3.671 0.00 0.00
151.36 0.00 0.00 127.17 0.00 8.024
OCCI60
tr2 chi_674

OLMOS22.9
178.78 178.78 81.68 4.37 0.00 0.00 3.67 0.00
30.97 30.97 14.15 4.37 0.00 0.00 3.67 0.00 0
30.97 30.97 14.15 20.280

tr2 lam_801

13.758
tr3 chi_2671 tr3 chi_2672 tr3 chi_2672(1) 9.09 0.585

1.041
2.077
1.57 0.00 0.968
-2 1.57
5.25 5.25 10.54 0.00
0.04 0.04 0.08 0 0.00
178.783 178.783 81.680
0.04
SECHO1A 30.966 30.966 SECHO1B 0.04
14.147 SECHO1C
0.08
70.65
L-6037 22.15 OLMOS10 0

13.76
1.04
1.04

0.00
0.00
0.00
82.917 82.917 36.936 15.30 3.84
15.30 3.84 9.090 11.99 10.26

0.00
0.00
0.00
1.574 0.91 1.78
3.425 0.00
505.823
59.37
LAMBA10 0.00
0.91 1.78
3.982 70.653 0.00
9.550 CHICLAYO_OESTE_220 15.297
10.28
10.28
22.145
39.635 3.836 OCCI23 OCCI10
9.463
0.00 0.00 0.00 0.00 0.00 0.00
SVCCHI 0.00 0.00 LAMB_SUR_10 0.00 0.00 0.00 0.00
11.993
0.907
10.259
1.777
0.00 0.00 0.00 0.00 0.00 0.00 1.774 3.630
59.369 0.00 0.00
1 10.283 1 0.00 0.00
Max. 2-Phase Short-Circuit acc. to IEC60909 SVS 25.346
0.00 0.00
0.00 0.00
0.00 0.00 1
Short Circuit Nodes Nodes 0.00 0.00
zz lam
Initial Short-Circuit Power B [MVA]Line-Ground Voltage, Magnitude A
Initial Short-Circuit Current B [kA] Line-Ground Voltage, Magnitude B
ESTUDIO DE OPERAT IVIDAD Project:
zz lamsur
Peak Short-Circuit Current B [kA] Line-Ground Voltage, Magnitude C
SE CHICLAYO OEST E Y SE CHICLAYO NORTE Graphic: EOP SECHO
Estudio de Cortocircuito Bifsico Date: 2/12/2014
PowerFactory 14.1.3 ES14MAX - Base Annex:

DLF SAC Pgina 85 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA EN CHICLAYO OESTE Y CHICLAYO NORTE

DIgSILENT
0.00 0.00
SE. CHICLAYO NORTE POMAL10 0.000
0.000 POMAL23 0.000
0.000

0.00 0.00 0.00


0.000 0.000 0.000 0.00
0.00 tr3 pom_8001 0.55 0.55
0.000 0.000 0.000 0.000 0.041 0.041 TUMAN60 0.000
0.000 CAYAL60
0.000 0.109 0.109

Breaker/S..

Breaker/S..

Breaker/S..
CHICN10B 0.00
0.000
0.00
CHICN10C 0.000 1.04 0.65 0.40
0.000
0.42 0.42
0.000 CHICN10 L-6051 0 0.030 0.019 0.012 0.012 0.012
0.00 0.062 0.039 0.024 0.025 0.025
0.00
0.000 lne POM_TUM_81 lne TUM_CAY_81
0.000
0.000 lne CHIC_POM_81
0.000 1.57 0.55 1.03
3.10 IN1032 0.00 IN1030 1.78 0.33
0.045 0.016 0.030 1 1
0.537 0.000 0.309 0.057
0.096 0.033 0.063
1.312 0.000 0.755 0.140

1 POMAL60
0.46 0.20 0.42 0.00

3.06
T3 1
T2 1

1.76
T1 1.57
0.00
0.000
0.035 0.034
0.089 tr3 tum_8001 0.091
0.032 0.000
0.078 tr3 cay_8001 0.000
ZZ chicln 0.000
0.088
0.193
0.051
0.111
0.045
0.099
TUMAN23 TUMAN10 CAYAL23 CAYAL10
0.00
0.000 0.00 0.00 0.00 0.00
0.000 0.000 0.000 0.000 0.000
0.000 0.000 0.000 0.000
0.46 0.42
0.035 0.032
0.089 0.078
3.20 3.20
0.092 0.092
ZZ CT Chicl 0.201 0.201
Chicl G1 Chicl G2 Chicl G3 Chicl G4 Chicl G5
~ ~ ~ ~ ~
G G G G G
SE. CHICLAYO OESTE Lne 60KV-ILLIMO-LA VIA
0.00
0.000
0.000
2.19 2.19 1.71 1.82 1.85 1.73 2.32 2.33
CT CHICL10

Lne ChiclayoOeste-ChiclayoNorte_L2
Lne ChiclayoOeste-ChiclayoNorte_L1
0.063 0.063 0.049 0.053 0.053 0.050 0.067 0.067
0.00 0.133 0.133 0.104 0.111 0.101 0.094 0.126 0.117
0.000
0.000 ILLIMO60 LA_VIA60 MOTUP60
lod chicl23 lod chicl10n 0.00 0.00
0.000 0.000 0.00
0.00 0.00 0.000 0.000 0.000

IN1007
0.000

L-6012

L-6022

L-6032

L-6033
0.000 0.000 0.86 1.28 0.97 1.38
0.000 0.000 0.025 0.037 0.028 0.040
0.052 0.070 0.049 0.069
Breaker/S..

Breaker/S..

tr2 La Via
0
0
CHICL23 CHIL10N CHICL10B 0
0.00 0.54 0.33 1.27
0.000 0.040 0.057 0.220
0.000 CHICL10A 0.106 0.152 0.532
Breaker/S.. 0.00 2.27 IN - 1008 2.32
0.000 0.393 0.401 0.00 ILLIMO10 LA_VIA10 Tr3 Motup..
0.000 1.061 1.084 0.000 ILLIMO23 0.42 0.96
tr3 Chiclayo T3 0.000 0.00 0.00 0.00 0.073 0.073
0.000 0.000 0.000 0.168 0.156
0.000 0.000 0.000
0.54 0.33 1.27
1 1 0.040 0.057 0.220 MOTUP10 MOTUP23
0.106 0.152 0.532
0 T3 ZZ Chicl
2.25
T1 2.30
T2 3.19 3.19 2.16 2.16
1
0.00
0.000
0.000
0.00
0.000
0.000
0.42 0.96
0.065 0.066 0.092 0.092 0.062 0.062 0.073 0.073
CHICL-O6 0.162 0.166 0.230 0.230 0.156 0.156
0.98 0.168 0.156
0.028
0.00 1
0.048
0.000
0.000 OLMOS60
5.34 5.34 10.70 9.29 2.16 0.00
Lod motup23
0.154 0.154 0.309 0.268 0.062 LAMB_SUR_60 LAMBA60 0.000
0.385 0.385 0.772 0.670 0.156 0.000 0.38
0.00 0.61 0.37
0 0.00 0.018 0.011 0.011
0 0 0.000
0.000 0.030 0.018 0.018
0.000
2.17 0.96 1.24 1.24 1.24 0.000
OCCI60
tr2 chi_674

OLMOS22.9
0.063 0.028 0.036 0.036 0.036
0.00 0.00 0.00 0.142 0.063 0.081 0.080 0.080 0
0.000 0.000 0.000 0.00

tr2 lam_801
tr3 chi_2671 0.000 0.000 tr3 chi_2672 0.000 tr3 chi_2672(1) 0.000

0.000
0.000
0.00
0.30 0.38 0.000
2 0.053
0.011
0 0.115
5.34 5.34 10.77 0.018
0.00 0.00 0.00
0.042
SECHO1A 0.000 0.000 SECHO1B 0.042
0.000 SECHO1C
0.085 L-6037 OLMOS10 -1

0.023
0.046

0.023
0.046
0.102 0.102 0.205

0.30

0.30
0.000 0.000 0.000 9.27 1.26
2.007 0.218 0.00

0.000
0.000
5.175 0.539

0.00
0.000 0.37 0.00
0.000 0.30
0.00 LAMBA10 0.053
0.028
0.055
0.000
0.000
0.000 0.00 0.115
0.000 CHICLAYO_OESTE_220 0.000
0.95
0.165
0.00
0.000 0.407
0.000 OCCI23 OCCI10
0.000
18.54 9.27 0.95 0.34 0.37 0.00
SVCCHI 4.015 2.007 LAMB_SUR_10 0.165 0.059 0.063 0.000
0.00
0.000
0.00
0.000
10.350 5.175 0.407 0.146 0.157 0.000 0.000 0.000
0.00 0.37
1 0.000 1 0.028
2-Phase Short-Circuit complete SVS 0.000
0.95 0.00
0.055
0.165 0.000 1
Short Circuit Nodes Nodes 0.407 0.000
zz lam
Initial Short-Circuit Power A [MVA]Line-Ground Voltage, Magnitude A
Initial Short-Circuit Current A [kA] Line-Ground Voltage, Magnitude B
ESTUDIO DE OPERAT IVIDAD Project:
zz lamsur
Peak Short-Circuit Current A [kA] Line-Ground Voltage, Magnitude C
SE CHICLAYO OEST E Y SE CHICLAYO NORTE Graphic: EOP SECHO
Estudio de Cortocircuito Bifsico Date: 2/12/2014
PowerFactory 14.1.3 ES14MIN - Base Annex:

DLF SAC Pgina 86 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA EN CHICLAYO OESTE Y CHICLAYO NORTE

DIgSILENT
41.49 76.73
SE. CHICLAYO NORTE POMAL10 2.395
6.531 POMAL23 1.926
5.098

289.01
41.49 tr3 pom_8001 76.73
2.395 1.926 TUMAN60 2.781
5.677 CAYAL60
6.531 5.098

Breaker/S..

Breaker/S..

Breaker/S..
CHICN10B 153.33
1.475
302.42
CHICN10C 17.460 289.01 0.00 0.00
2.980
153.33 0.00
42.504 CHICN10 L-6051 -7 2.781 0.000 0.000 1.475 0.000
302.42 5.677 0.000 0.000 2.980 0.000
302.42
17.460 lne POM_TUM_81 lne TUM_CAY_81
42.504
17.460 lne CHIC_POM_81
42.504 421.73 0.00 0.00
191.27 IN1032 0.00 IN1030 111.16 0.00
4.058 0.000 0.000 -5 -1
11.043 0.000 6.418 0.000
8.371 0.000 0.000
26.883 0.000 15.624 0.000

-1 POMAL60
71.02 39.76 58.65 35.56

0.00
T3 -1
T2 -1

0.00
T1 0.00
421.73
4.058
1.783 2.295
4.599 tr3 tum_8001 6.157
1.472 2.053
3.604 tr3 cay_8001 5.301
ZZ chicln 8.371
0.000
0.000
0.000
0.000
0.000
0.000
TUMAN23 TUMAN10 CAYAL23 CAYAL10
701.15
6.747 71.02 39.76 58.65 35.56
14.239 1.783 2.295 1.472 2.053
4.599 6.157 3.604 5.301

350.58 350.58
3.373 3.373
ZZ CT Chicl 7.119 7.119
Chicl G1 Chicl G2 Chicl G3 Chicl G4 Chicl G5
~ ~ ~ ~ ~
G G G G G
SE. CHICLAYO OESTE Lne 60KV-ILLIMO-LA VIA
0.00 31.39 31.39 37.76
0.000 1.812 1.812 2.180
0.000 4.865 4.865 5.852
152.57 152.57 0.00 0.00 106.48 100.11 0.00 124.23
CT CHICL10

Lne ChiclayoOeste-ChiclayoNorte_L2
Lne ChiclayoOeste-ChiclayoNorte_L1
1.468 1.468 0.000 0.000 1.025 0.963 0.000 1.195
401.69 3.035 3.035 0.000 0.000 1.900 1.786 0.000 2.055
23.192
62.263 ILLIMO60 LA_VIA60 MOTUP60
lod chicl23 lod chicl10n 305.15 206.56
2.936 1.988 124.23
6.070 3.686 1.195

IN1007
2.055

L-6012

L-6022

L-6032

L-6033
0.00 0.00 0.00 0.00
0.000 0.000 0.000 0.000
0.000 0.000 0.000 0.000
Breaker/S..

Breaker/S..

tr2 La Via
0
0
CHICL23 CHIL10N CHICL10B 0
401.69 62.34 43.50 64.11
23.192 1.565 2.511 3.701
62.263 CHICL10A 4.112 6.741 8.948
Breaker/S.. 0.00 149.10 IN - 1008 152.07
0.000 8.608 8.780 401.69 ILLIMO10 LA_VIA10 Tr3 Motup..
0.000 23.111 23.571 23.192 ILLIMO23 40.46 59.32
tr3 Chiclayo T3 62.263 62.34 43.50 64.11 2.336 1.496
1.565 2.511 3.701 5.396 3.191
4.112 6.741 8.948
0.00
0 0 0.000 MOTUP10 MOTUP23
0.000
0 T3 ZZ Chicl
38.36
T1 39.12
T2 0.00 0.00 0.00 0.00
1
40.46
2.336
5.396
59.32
1.496
3.191
0.00
0.369 0.376 0.000 0.000 0.000 0.000 0.000
CHICL-O6 0.929 0.948 0.000 0.000 0.000 0.000
92.75 0.000
0.892
1052.64 1
1.497
10.129
25.495 OLMOS60
243.35 243.35 488.60 0.00 0.00 92.75
Lod motup23
2.342 2.342 4.702 0.000 0.000 LAMB_SUR_60 LAMBA60 0.892
5.894 5.894 11.834 0.000 0.000 1.497 70.30
526.65 0.00 0.00
0 442.20 0.000 0.000 0.676
-3 -3 5.068
4.255 0.000 0.000 1.119
11.276
526.65 0.00 0.00 442.20 0.00 9.300
OCCI60
tr2 chi_674

OLMOS22.9
5.068 0.000 0.000 4.255 0.000
622.14 622.14 283.55 11.276 0.000 0.000 9.300 0.000 0
35.919 35.919 16.371 70.30

tr2 lam_801
tr3 chi_2671 96.180 96.180 tr3 chi_2672 42.742tr3 chi_2672(1) 0.676

47.68
1.202
2.399
31.50 0.00 1.119
-2 1.818
0.000
0 3.956
18.70 18.70 37.55 0.000
622.14 622.14 283.55
0.049
SECHO1A 35.919 35.919 SECHO1B 0.049
16.371 SECHO1C
0.099 L-6037 OLMOS10 0

47.68
1.202
2.399
0.118 0.118 0.236
96.180 96.180 42.742 245.22 76.76
17.697 4.432 31.50

0.000
0.000
45.854 10.933

0.00
1.818 41.56 35.55
3.956
1770.69 LAMBA10 1.048
2.050
2.052
4.193
4.647 245.22
11.144 CHICLAYO_OESTE_220 17.697
205.99
11.893
76.76
45.854 29.314
4.432 OCCI23 OCCI10
10.933
0.00 0.00 0.00 0.00
SVCCHI 0.000 0.000 LAMB_SUR_10 0.000 0.000
41.56
1.048
35.55
2.052
0.000 0.000 0.000 0.000 2.050 4.193
205.99 0.00
1 11.893 1 0.000
Max. 3-Phase Short-Circuit acc. to IEC60909 SVS 29.314
0.00
0.000
0.000 1
Short Circuit Nodes Nodes Branch 0.000
zz lam
Initial Short-Circuit Power [MVA]Line-Line Voltage, Magnitude [kV]
Initia
Initial Short-Circuit Current [kA] Voltage, Magnitude [p.u.] Initia
ESTUDIO DE OPERAT IVIDAD Project:
zz lamsur
Peak Short-Circuit Current [kA] Voltage, Angle [deg] Peak S
SE CHICLAYO OEST E Y SE CHICLAYO NORTE Graphic: EOP SECHO
Estudio de Cortocircuito Trifsico Date: 2/12/2014
PowerFactory 14.1.3 ES14MAX - BASE Annex:

DLF SAC Pgina 87 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA EN CHICLAYO OESTE Y CHICLAYO NORTE

DIgSILENT
40.76 74.30
SE. CHICLAYO NORTE POMAL10 2.354
6.402 POMAL23 1.865
4.922

257.26
40.76 tr3 pom_8001 74.30
2.354 1.865 TUMAN60 2.476
5.140 CAYAL60
6.402 4.922

Breaker/S..

Breaker/S..

Breaker/S..
CHICN10B 143.93
1.385
267.51
CHICN10C 15.445 257.26 0.00 0.00
2.825
143.93 0.00
37.585 CHICN10 L-6051 0 2.476 0.000 0.000 1.385 0.000
267.51 5.140 0.000 0.000 2.825 0.000
267.51
15.445 lne POM_TUM_81 lne TUM_CAY_81
37.585
15.445 lne CHIC_POM_81
37.585 357.27 0.00 0.00
169.20 IN1032 0.00 IN1030 98.33 0.00
3.438 0.000 0.000 1 1
9.769 0.000 5.677 0.000
7.254 0.000 0.000
23.772 0.000 13.816 0.000

1 POMAL60
68.93 39.09 57.22 35.02

0.00
T3 1
T2 1

0.00
T1 0.00
357.27
3.438
1.730 2.257
4.456 tr3 tum_8001 6.043
1.436 2.022
3.515 tr3 cay_8001 5.216
ZZ chicln 7.254
0.000
0.000
0.000
0.000
0.000
0.000
TUMAN23 TUMAN10 CAYAL23 CAYAL10
538.97
5.186 68.93 39.09 57.22 35.02
11.280 1.730 2.257 1.436 2.022
4.456 6.043 3.515 5.216

269.49 269.49
2.593 2.593
ZZ CT Chicl 5.640 5.640
Chicl G1 Chicl G2 Chicl G3 Chicl G4 Chicl G5
~ ~ ~ ~ ~
G G G G G
SE. CHICLAYO OESTE Lne 60KV-ILLIMO-LA VIA
0.00
0.000
0.000
134.96 134.96 0.00 0.00 98.02 92.17 0.00 118.31
CT CHICL10

Lne ChiclayoOeste-ChiclayoNorte_L2
Lne ChiclayoOeste-ChiclayoNorte_L1
1.299 1.299 0.000 0.000 0.943 0.887 0.000 1.138
260.34 2.730 2.730 0.000 0.000 1.780 1.674 0.000 1.981
15.031
40.507 ILLIMO60 LA_VIA60 MOTUP60
lod chicl23 lod chicl10n 269.92 190.16
2.597 1.830 118.31
5.460 3.453 1.138

IN1007
1.981

L-6012

L-6022

L-6032

L-6033
0.00 0.00 0.00 0.00
0.000 0.000 0.000 0.000
0.000 0.000 0.000 0.000
Breaker/S..

Breaker/S..

tr2 La Via
0
0
CHICL23 CHIL10N CHICL10B 0
260.34 60.73 42.70 62.38
15.031 1.524 2.465 3.602
40.507 CHICL10A 3.997 6.604 8.708
Breaker/S.. 0.00 128.89 IN - 1008 131.45
0.000 7.441 7.590 260.34 ILLIMO10 LA_VIA10 Tr3 Motup..
0.000 20.054 20.453 15.031 ILLIMO23 39.77 57.85
tr3 Chiclayo T3 40.507 60.73 42.70 62.38 2.296 1.459
1.524 2.465 3.602 5.308 3.121
3.997 6.604 8.708
1 1 MOTUP10 MOTUP23
0 T3 ZZ Chicl
0.00
T1 0.00
T2 0.00 0.00 0.00 0.00
1
39.77
2.296
5.308
57.85
1.459
3.121
0.000 0.000 0.000 0.000 0.000 0.000
CHICL-O6 0.000 0.000 0.000 0.000 0.000 0.000
89.46
0.861
724.00 1
1.457
6.967
17.334 OLMOS60
180.65 180.65 362.72 0.00 0.00 89.46
Lod motup23
1.738 1.738 3.490 0.000 0.000 LAMB_SUR_60 LAMBA60 0.861
4.325 4.325 8.684 0.000 0.000 1.457 68.42
429.29 0.00 0.00
0 371.53 0.000 0.000 0.658
0 0 4.131
3.575 0.000 0.000 1.096
9.334
429.29 0.00 0.00 371.53 0.00 7.939
OCCI60
tr2 chi_674

OLMOS22.9
4.131 0.000 0.000 3.575 0.000
491.34 491.34 252.60 9.334 0.000 0.000 7.939 0.000 0
28.368 28.368 14.584 68.42

tr2 lam_801
tr3 chi_2671 74.379 74.379 tr3 chi_2672 37.771tr3 chi_2672(1) 0.658

46.73
1.178
2.359
31.08 0.00 1.096
2 1.794
0.000
0 3.908
0.00 0.00 0.00 0.000
491.34 491.34 252.60
0.000
SECHO1A 28.368 28.368 SECHO1B 0.000
14.584 SECHO1C
0.000 L-6037 OLMOS10 -1

46.73
1.178
2.359
0.000 0.000 0.000
74.379 74.379 37.771 221.79 74.30
16.006 4.290 31.08

0.000
0.000
41.203 10.577

0.00
1.794 40.84 35.02
3.908
1057.53 LAMBA10 1.030
2.021
2.022
4.139
2.775 221.79
6.671 CHICLAYO_OESTE_220 16.006
189.18
10.922
74.30
41.203 26.888
4.290 OCCI23 OCCI10
10.577
0.00 0.00 0.00 0.00
SVCCHI 0.000 0.000 LAMB_SUR_10 0.000 0.000
40.84
1.030
35.02
2.022
0.000 0.000 0.000 0.000 2.021 4.139
189.18
1 10.922 1
Max. 3-Phase Short-Circuit acc. to IEC60909 SVS 26.888
0.00
0.000 1
Short Circuit Nodes Nodes Branch 0.000
zz lam
Initial Short-Circuit Power [MVA]Line-Line Voltage, Magnitude [kV]
Initia
Initial Short-Circuit Current [kA] Voltage, Magnitude [p.u.] Initia
ESTUDIO DE OPERAT IVIDAD Project:
zz lamsur
Peak Short-Circuit Current [kA] Voltage, Angle [deg] Peak S
SE CHICLAYO OEST E Y SE CHICLAYO NORTE Graphic: EOP SECHO
Estudio de Cortocircuito Trifsico Date: 2/12/2014
PowerFactory 14.1.3 ES14MIN - Base Annex:

DLF SAC Pgina 88 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA EN CHICLAYO OESTE Y CHICLAYO NORTE

DIgSILENT
0.000 33.013
SE. CHICLAYO NORTE POMAL10 0.000
0.000 POMAL23 2.486
6.580
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00 89.160
0.00 tr3 pom_8001 33.01 0.00
0.00 0.00 0.00 0.00 2.49 0.00 TUMAN60 2.574
5.254 CAYAL60
0.00 6.58 0.00

Breaker/S..

Breaker/S..

Breaker/S..
CHICN10B 0.00 2.49 0.00 46.119
1.331
2.155
CHICN10C 0.373 79.33 5.84 4.13
2.689
40.10 6.11
0.892 CHICN10 L-6051 -7 2.29 0.17 0.12 1.16 0.18
2.155 4.67 0.34 0.24 2.34 0.36
2.155 1.73 0.51 0.36 0.81 0.53
0.373 lne POM_TUM_81 lne TUM_CAY_81
0.892
0.373 lne CHIC_POM_81 122.97 5.43 7.40
0.892 3.55 0.16 0.21
0.67 IN1032 0.50 0.38 IN1030 0.39 0.74
7.32 0.32 0.44 -5 -1
0.12 0.09 0.07 0.07 0.13
2.82 0.47 0.64
0.28 0.21 0.16 0.16 0.31
0.00 0.26 0.00 0.00 0.38
-1 POMAL60 30.50 0.00 25.13 0.00
2.30 0.00 1.89 0.00
22.78
0.66
T3 -1
12.90
0.37
T2 -1
13.24
0.38
T1 5.70
0.16
135.595
3.914
5.93
2.30 tr3 tum_8001
0.00
0.00
4.63
1.89 tr3 cay_8001
0.00
0.00
ZZ chicln 8.075
1.39
1.97
0.79
1.12
0.81
1.15
0.35
0.49
TUMAN23 TUMAN10 CAYAL23 CAYAL10
276.985
7.996 30.495 0.000 25.133 0.000
16.875 2.296 0.000 1.893 0.000
5.925 0.000 4.634 0.000
0.00 0.00
0.00 0.00
0.00 0.00
111.84 111.84 0.00 0.00
3.23 3.23
ZZ CT Chicl 6.81 6.81
Chicl G1 Chicl G2 Chicl G3 Chicl G4 Chicl G5
1.74 1.74
~ ~ ~ ~ ~
G G G G G
SE. CHICLAYO OESTE 0.45 0.23 0.23 0.27
Lne 60KV-ILLIMO-LA VIA
0.08 0.04 0.04 0.05
0.21 0.11 0.11 0.12
0.24 0.04 0.04 0.04 40.03 40.03 5.48 5.15 29.64 28.40 5.13 36.81
1.16 1.16 0.16 0.15 0.86 0.82 0.15 1.06
CT CHICL10

Lne ChiclayoOeste-ChiclayoNorte_L2
Lne ChiclayoOeste-ChiclayoNorte_L1
2.39 2.39 0.33 0.31 1.59 1.52 0.27 1.83
3.318 0.67 0.67 0.47 0.45 0.38 0.40 0.44 0.51
0.575
1.543 ILLIMO60 LA_VIA60 MOTUP60
lod chicl23 lod chicl10n 96.753 73.544
0.00 0.00 2.793 2.123 46.332
0.00 0.00 5.774 3.937 1.337

IN1007
2.299

L-6012

L-6022

L-6032

L-6033
0.00 0.00 6.15 10.47 4.46 5.11
0.00 0.00 0.18 0.30 0.13 0.15
0.00 0.00
0.37 0.56 0.22 0.25
Breaker/S..

Breaker/S..
0.00 0.00

tr2 La Via
0.00 0.00 0.53 0 0.91 0.39 0.44
0.00 0.00 0
CHICL23 CHIL10N CHICL10B 0
28.06 0.00 0.00
3.318 2.11 0.00 0.00
91.284 0.000 5.55 0.00 0.00
0.575
6.904
19.059
0.000
0.000 1.543 CHICL10A 2.11 0.00 0.00
91.28 0.00 Breaker/S.. 0.45 0.83 IN - 1008 0.85
6.90 0.00 0.08 0.14 0.15 3.318 ILLIMO10 LA_VIA10 Tr3 Motup..
19.06 0.00 0.21 0.39 0.40 0.575 ILLIMO23 0.34
0.06
26.37
1.99
6.90 tr3 Chiclayo T3 0.00 0.24 0.00 0.00 1.543 28.059 0.000 0.000 0.14 4.26
2.113 0.000 0.000 0.00 1.99
5.553 0.000 0.000
0.00 0.00 0.00 0.00
0 0 0.00 0.00 0.00 0.00 MOTUP10 MOTUP23
0.00 0.00 0.00 0.00
0 12.56
0.36
T3 ZZ Chicl
16.92
0.49
T1 17.26
0.50
T2 5.38
0.16
5.38
0.16
0.97
0.03
0.97
0.03
0.00
1
0.00 0.00 0.00 0.507
0.088
0.203
26.372
1.995
4.255
0.00 0.17 0.00
0.91 1.23 1.25 0.39 0.39 0.07 0.07 0.00 0.03 0.00
28.79
CHICL-O6 1.09 0.50 0.51 0.47 0.47 0.08 0.08
0.83 0.00 0.07 0.00
1.39 0.00 0.09 0.00
476.797 1
0.43
13.764
34.644 OLMOS60
120.80 120.80 170.67 0.00 5.52 35.758
Lod motup23
3.49 3.49 4.93 0.00 0.16 LAMB_SUR_60 LAMBA60 1.032 22.39
8.78 8.78 12.40 0.00 0.40 1.732 0.65
4.08 4.08 1.96 0.00 0.48 194.169 3.73 3.27
0 151.393 0.11 0.09 1.07
-3 -3 5.605
4.370 0.18 0.16 0.35
12.471
156.70 29.23 8.44 140.11 11.38 9.552 0.32 0.28
OCCI60
tr2 chi_674

OLMOS22.9
0.00 0.00 0.00 4.52 0.84 0.24 4.04 0.33
0.00 0.00 0.00 10.06 1.88 0.54 8.84 0.72 0
0.00 0.00 0.00 2.38 2.53 0.73 3.39 0.99 27.560

tr2 lam_801

21.009
tr3 chi_2671 tr3 chi_2672 0.00 tr3 chi_2672(1) 0.00 0.796

1.589
3.171
0.00 0.00
0.00 5.20 1.316
-2 0.00
37.35 37.35 70.53 0.15
0 0.00
0.29 0.29 0.56 0.25
0.000 0.000 0.000
0.71
SECHO1A 0.000 0.000 SECHO1B 0.71
0.000 SECHO1C
1.33
0.25
L-6037 0.24 OLMOS10
0.45 0

21.01
0.77 0.77 1.45

1.59
3.17
1.59

0.00
0.00
0.00
0.00
0.000 0.000 0.000 0.05 0.04
0.14 0.10 0.000
0.05 0.00 19.32 0.00

0.00
0.00
0.00
0.00
0.000 1.46 0.00
0.000 0.00
672.037
0.99
LAMBA10 0.00
2.86
1.46
0.00
0.00
5.291 0.254 0.00
12.688 CHICLAYO_OESTE_220 0.055
0.17
0.42
0.364 0.00
0.142 0.00
0.063 OCCI23 OCCI10
0.156
0.00 0.00 0.00 0.00 0.00 0.12
SVCCHI 0.00 0.00 LAMB_SUR_10 0.00 0.00 0.00 0.02
19.322
1.461
0.000
0.000
0.00 0.00 0.00 0.00 0.00 0.05 2.859 0.000
0.00 0.00 1.489 0.00 0.00 0.00 0.06 0.00 0.00
1 0.258 1 0.00 0.00
Max. Single Phase to Ground acc. to IEC60909 SVS 0.636
0.00 0.50
0.00 0.00
0.00 0.00
0.00 0.09 1
Short Circuit Nodes Branches 0.00 0.21
0.00 0.26 zz lam
Initial Short-Circuit Power A [MVA]Initial Short-Circuit Power A [MVA]
Initial Short-Circuit Current A [kA] Initial Short-Circuit Current A [kA]
ESTUDIO DE OPERAT IVIDAD Project:
zz lamsur
Peak Short-Circuit Current A [kA] Peak Short-Circuit Current A [kA]
SE CHICLAYO OEST E Y SE CHICLAYO NORTE Graphic: EOP SECHO
3*I0 [kA]
Estudio de Cortocircuito Monofsico Date: 2/12/2014
PowerFactory 14.1.3 ES14MAX - CON PROYECTO Annex:

DLF SAC Pgina 89 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA EN CHICLAYO OESTE Y CHICLAYO NORTE

DIgSILENT
11.974 22.138
SE. CHICLAYO NORTE POMAL10 2.074
5.654 POMAL23 1.667
4.413

0.00 0.00 0.00


0.00 0.00 0.00 83.216
11.97 tr3 pom_8001 22.14 0.00
0.00 0.00 0.00 2.07 1.67 0.00 TUMAN60 2.402
4.904 CAYAL60
5.65 4.41 0.00

Breaker/S..

Breaker/S..

Breaker/S..
CHICN10B 44.203
1.276
102.535
CHICN10C 17.760 83.22 0.00 0.00
2.577
44.20 0.00
42.443 CHICN10 L-6051 -7 2.40 0.00 0.00 1.28 0.00
102.535 4.90 0.00 0.00 2.58 0.00
102.535
17.760 lne POM_TUM_81 lne TUM_CAY_81
42.443
17.760 lne CHIC_POM_81
42.443 121.29 0.00 0.00
47.75 IN1032 0.00 27.05 IN1030 27.75 0.00
3.50 0.00 0.00 -5 -1
8.27 0.00 4.68 4.81 0.00
7.22 0.00 0.00
19.76 0.00 11.20 11.49 0.00

-1 POMAL60
20.49 11.47 16.92 10.26

0.00
T3 -1

0.00
T2 -1

0.00
T1 0.00
121.292
3.501
1.54 1.99
3.98 tr3 tum_8001 5.33
1.27 1.78
3.12 tr3 cay_8001 4.59
ZZ chicln 7.223
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
TUMAN23 TUMAN10 CAYAL23 CAYAL10
201.180
5.808 20.490 11.473 16.923 10.262
12.256 1.543 1.987 1.274 1.777
3.981 5.331 3.120 4.590
0.00 0.00
0.00 0.00
0.00 0.00
100.59 100.59
2.90 2.90
ZZ CT Chicl 6.13 6.13
Chicl G1 Chicl G2 Chicl G3 Chicl G4 Chicl G5
~ ~ ~ ~ ~
G G G G G
SE. CHICLAYO OESTE Lne 60KV-ILLIMO-LA VIA
0.00 8.40 8.40 9.85
0.00 1.45 1.45 1.71
0.00 3.90 3.90 4.58
43.93 43.93 0.00 0.00 30.68 28.84 0.00 35.82
CT CHICL10

Lne ChiclayoOeste-ChiclayoNorte_L2
Lne ChiclayoOeste-ChiclayoNorte_L1
1.27 1.27 0.00 0.00 0.89 0.83 0.00 1.03
114.044 2.62 2.62 0.00 0.00 1.64 1.54 0.00 1.78
19.753
53.030 ILLIMO60 LA_VIA60 MOTUP60
lod chicl23 lod chicl10n 87.853 59.514
2.536 1.718 35.820
0.00 0.00 5.242 3.186 1.034

IN1007
1.778

L-6012

L-6022

L-6032

L-6033
0.00 0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00
Breaker/S..

Breaker/S..
0.00 0.00

tr2 La Via
0.00 0.00 0
0.00 0.00 0
CHICL23 CHIL10N CHICL10B 0
114.044 17.99 12.55 18.50
59.987 88.525 1.35 2.17 3.20
19.753
4.537
12.525
15.333
41.848 53.030 CHICL10A 3.56 5.84 7.74
59.99 88.52 Breaker/S.. 0.00 43.28 IN - 1008 44.14
4.54 15.33 0.00 7.50 7.64 114.044 ILLIMO10 LA_VIA10 Tr3 Motup..
12.52 41.85 0.00 20.12 20.52 19.753 ILLIMO23 11.68 17.12
tr3 Chiclayo T3 53.030 17.988 12.553 18.497 2.02 1.29
1.355 2.174 3.204 4.67 2.76
3.560 5.836 7.745
0.00 0.00 0.00 0.00
0 0 0.00 0.00 0.00 0.00 MOTUP10 MOTUP23
0.00 0.00 0.00 0.00
0
0.00
T3 ZZ Chicl
10.30
T1 10.51
T2 0.00 0.00 0.00 0.00
1
11.676
2.022
4.672
17.116
1.295
2.762
0.00 0.00 0.00
0.00 0.30 0.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CHICL-O6 0.00 0.75 0.76 0.00 0.00 0.00 0.00
26.75 0.00 0.00 0.00
0.77
301.390 1
1.30
8.700
21.899 OLMOS60
70.01 70.01 140.58 0.00 0.00 26.749
Lod motup23
2.02 2.02 4.06 0.00 0.00 LAMB_SUR_60 LAMBA60 0.772
5.09 5.09 10.21 0.00 0.00 1.295 20.28
151.360 0.00 0.00
0 127.172 0.00 0.00 0.59
-3 -3 4.369
3.671 0.00 0.00 0.97
9.722
151.36 0.00 0.00 127.17 0.00 8.024
OCCI60
tr2 chi_674

OLMOS22.9
4.37 0.00 0.00 3.67 0.00
178.78 178.78 81.68 9.72 0.00 0.00 8.02 0.00 0
30.97 30.97 14.15 20.280

tr2 lam_801

13.758
tr3 chi_2671 82.92 82.92 tr3 chi_2672 36.94 tr3 chi_2672(1) 0.585

1.041
2.077
9.09 0.00 0.968
-2 1.57
0.00
0 3.42
5.03 5.03 10.11 0.00
178.783 178.783 81.680
0.04
SECHO1A 30.966 30.966 SECHO1B 0.04
14.147 SECHO1C
0.08 L-6037 OLMOS10 0

13.76
0.10 0.10 0.19

1.04
2.08

0.00
0.00
0.00
82.917 82.917 36.936 70.65 22.15
15.30 3.84 9.090
39.64 9.46

0.00
0.00
0.00
1.574 11.99 10.26
3.425 0.00
505.823 LAMBA10 0.00
0.91
1.77
1.78
3.63
3.982 70.653 0.00
9.550 CHICLAYO_OESTE_220 15.297
59.37
10.28
22.145
39.635 25.35
3.836 OCCI23 OCCI10
9.463
0.00 0.00 0.00 0.00 0.00 0.00
SVCCHI 0.00 0.00 LAMB_SUR_10 0.00 0.00 0.00 0.00
11.993
0.907
10.259
1.777
0.00 0.00 0.00 0.00 0.00 0.00 1.774 3.630
59.369 0.00 0.00
1 10.283 1 0.00 0.00
Max. 2-Phase Short-Circuit acc. to IEC60909 SVS 25.346
0.00 0.00
0.00 0.00
0.00 0.00 1
Short Circuit Nodes Branches 0.00 0.00
zz lam
Initial Short-Circuit Power B [MVA]Initial Short-Circuit Power B [MVA]
Initial Short-Circuit Current B [kA] Initial Short-Circuit Current B [kA]
ESTUDIO DE OPERAT IVIDAD Project:
zz lamsur
Peak Short-Circuit Current B [kA] Peak Short-Circuit Current B [kA]
SE CHICLAYO OEST E Y SE CHICLAYO NORTE Graphic: EOP SECHO
Estudio de Cortocircuito Bifsico Date: 2/12/2014
PowerFactory 14.1.3 ES14MAX - CON PROYECTO Annex:

DLF SAC Pgina 90 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA EN CHICLAYO OESTE Y CHICLAYO NORTE

DIgSILENT
41.49 76.73
SE. CHICLAYO NORTE POMAL10 2.395
6.531 POMAL23 1.926
5.098

289.01
41.49 tr3 pom_8001 76.73
2.395 1.926 TUMAN60 2.781
5.677 CAYAL60
6.531 5.098

Breaker/S..

Breaker/S..

Breaker/S..
CHICN10B 153.33
1.475
356.19
CHICN10C 20.565 289.01 0.00 0.00
2.980
153.33 0.00
49.147 CHICN10 L-6051 -7 2.781 0.000 0.000 1.475 0.000
356.19 5.677 0.000 0.000 2.980 0.000
356.19
20.565 lne POM_TUM_81 lne TUM_CAY_81
49.147
20.565 lne CHIC_POM_81
49.147 421.73 0.00 0.00
165.86 IN1032 0.00 93.96 IN1030 96.39 0.00
4.058 0.000 0.000 -5 -1
9.576 0.000 5.425 5.565 0.000
8.371 0.000 0.000
22.885 0.000 12.965 13.300 0.000

-1 POMAL60
71.02 39.76 58.65 35.56

0.00
T3 -1

0.00
T2 -1

0.00
T1 0.00
421.73
4.058
1.783 2.295
4.599 tr3 tum_8001 6.157
1.472 2.053
3.604 tr3 cay_8001 5.301
ZZ chicln 8.371
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
TUMAN23 TUMAN10 CAYAL23 CAYAL10
701.15
6.747 71.02 39.76 58.65 35.56
14.239 1.783 2.295 1.472 2.053
4.599 6.157 3.604 5.301

350.58 350.58
3.373 3.373
ZZ CT Chicl 7.119 7.119
Chicl G1 Chicl G2 Chicl G3 Chicl G4 Chicl G5
~ ~ ~ ~ ~
G G G G G
SE. CHICLAYO OESTE Lne 60KV-ILLIMO-LA VIA
0.00 31.39 31.39 37.76
0.000 1.812 1.812 2.180
0.000 4.865 4.865 5.852
152.57 152.57 0.00 0.00 106.48 100.11 0.00 124.23
CT CHICL10

Lne ChiclayoOeste-ChiclayoNorte_L2
Lne ChiclayoOeste-ChiclayoNorte_L1
1.468 1.468 0.000 0.000 1.025 0.963 0.000 1.195
401.69 3.035 3.035 0.000 0.000 1.900 1.786 0.000 2.055
23.192
62.263 ILLIMO60 LA_VIA60 MOTUP60
lod chicl23 lod chicl10n 305.15 206.56
2.936 1.988 124.23
6.070 3.686 1.195

IN1007
2.055

L-6012

L-6022

L-6032

L-6033
0.00 0.00 0.00 0.00
0.000 0.000 0.000 0.000
0.000 0.000 0.000 0.000
Breaker/S..

Breaker/S..

tr2 La Via
0
0
CHICL23 CHIL10N CHICL10B 0
401.69 62.34 43.50 64.11
208.12 307.34 1.565 2.511 3.701
23.192
5.247
14.485
17.744
48.430 62.263 CHICL10A 4.112 6.741 8.948
208.12 307.34 Breaker/S.. 0.00 149.10 IN - 1008 152.07
5.247 17.744 0.000 8.608 8.780 401.69 ILLIMO10 LA_VIA10 Tr3 Motup..
14.485 48.430 0.000 23.111 23.571 23.192 ILLIMO23 40.46 59.32
tr3 Chiclayo T3 62.263 62.34 43.50 64.11 2.336 1.496
1.565 2.511 3.701 5.396 3.191
4.112 6.741 8.948
0.00
0 0 0.000 MOTUP10 MOTUP23
0.000
0
0.00
T3 ZZ Chicl
38.36
T1 39.12
T2 0.00 0.00 0.00 0.00
1
40.46
2.336
5.396
59.32
1.496
3.191
0.00
0.000 0.369 0.376 0.000 0.000 0.000 0.000 0.000
CHICL-O6 0.000 0.929 0.948 0.000 0.000 0.000 0.000
92.75 0.000
0.892
1052.64 1
1.497
10.129
25.495 OLMOS60
243.35 243.35 488.60 0.00 0.00 92.75
Lod motup23
2.342 2.342 4.702 0.000 0.000 LAMB_SUR_60 LAMBA60 0.892
5.894 5.894 11.834 0.000 0.000 1.497 70.30
526.65 0.00 0.00
0 442.20 0.000 0.000 0.676
-3 -3 5.068
4.255 0.000 0.000 1.119
11.276
526.65 0.00 0.00 442.20 0.00 9.300
OCCI60
tr2 chi_674

OLMOS22.9
5.068 0.000 0.000 4.255 0.000
622.14 622.14 283.55 11.276 0.000 0.000 9.300 0.000 0
35.919 35.919 16.371 70.30

tr2 lam_801
tr3 chi_2671 96.180 96.180 tr3 chi_2672 42.742tr3 chi_2672(1) 0.676

47.68
1.202
2.399
31.50 0.00 1.119
-2 1.818
0.000
0 3.956
18.70 18.70 37.55 0.000
622.14 622.14 283.55
0.049
SECHO1A 35.919 35.919 SECHO1B 0.049
16.371 SECHO1C
0.099 L-6037 OLMOS10 0

47.68
1.202
2.399
0.118 0.118 0.236
96.180 96.180 42.742 245.22 76.76
17.697 4.432 31.50

0.000
0.000
45.854 10.933

0.00
1.818 41.56 35.55
3.956
1770.69 LAMBA10 1.048
2.050
2.052
4.193
4.647 245.22
11.144 CHICLAYO_OESTE_220 17.697
205.99
11.893
76.76
45.854 29.314
4.432 OCCI23 OCCI10
10.933
0.00 0.00 0.00 0.00
SVCCHI 0.000 0.000 LAMB_SUR_10 0.000 0.000
41.56
1.048
35.55
2.052
0.000 0.000 0.000 0.000 2.050 4.193
205.99 0.00
1 11.893 1 0.000
Max. 3-Phase Short-Circuit acc. to IEC60909 SVS 29.314
0.00
0.000
0.000 1
Short Circuit Nodes Branches 0.000
zz lam
Initial Short-Circuit Power [MVA]Initial Short-Circuit Power [MVA]
Initial Short-Circuit Current [kA] Initial Short-Circuit Current [kA]
ESTUDIO DE OPERAT IVIDAD Project:
zz lamsur
Peak Short-Circuit Current [kA] Peak Short-Circuit Current [kA]
SE CHICLAYO OEST E Y SE CHICLAYO NORTE Graphic: EOP SECHO
Estudio de Cortocircuito Trifsico Date: 2/12/2014
PowerFactory 14.1.3 ES14MAX - CON PROYECTO Annex:

DLF SAC Pgina 91 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA EN CHICLAYO OESTE Y CHICLAYO NORTE

DIgSILENT
0.000 32.733
SE. CHICLAYO NORTE POMAL10 0.000
0.000 POMAL23 2.465
6.517

0.00 0.00 0.00


0.00 0.00 0.00 87.142
0.00 tr3 pom_8001 32.73 0.00
0.00 0.00 0.00 0.00 2.47 0.00 TUMAN60 2.516
5.160 CAYAL60
0.00 6.52 0.00

Breaker/S..

Breaker/S..

Breaker/S..
CHICN10B 45.573
1.316
3.106
CHICN10C 0.538 77.53 5.71 4.04
2.665
39.63 6.03
1.285 CHICN10 L-6051 -2 2.24 0.16 0.12 1.14 0.17
3.106 4.59 0.34 0.24 2.32 0.35
3.106
0.538 lne POM_TUM_81 lne TUM_CAY_81
1.285
0.538 lne CHIC_POM_81
1.285 118.78 5.24 7.15
0.96 IN1032 0.51 0.55 IN1030 0.56 1.12
3.43 0.15 0.21 -5 -1
0.17 0.09 0.09 0.10 0.19
7.12 0.31 0.43
0.40 0.21 0.23 0.23 0.46

-2 POMAL60
30.26 0.00 24.97 0.00

21.25
T3 -2

12.04
T2 -2

12.35
T1 5.32
130.981
3.781
2.28
5.87 tr3 tum_8001
0.00
0.00
1.88
4.60 tr3 cay_8001
0.00
0.00
ZZ chicln 7.852
0.61
1.31
0.35
0.74
0.36
0.76
0.15
0.33
TUMAN23 TUMAN10 CAYAL23 CAYAL10
258.352
7.458 30.256 0.000 24.971 0.000
15.884 2.278 0.000 1.880 0.000
5.874 0.000 4.602 0.000
0.00 0.00
0.00 0.00
0.00 0.00
104.31 104.31
3.01 3.01
ZZ CT Chicl 6.41 6.41
Chicl G1 Chicl G2 Chicl G3 Chicl G4 Chicl G5
~ ~ ~ ~ ~
G G G G G
SE. CHICLAYO OESTE Lne 60KV-ILLIMO-LA VIA
0.43
0.07
0.20
39.04 39.04 5.34 5.02 29.08 27.88 5.04 36.39
CT CHICL10

Lne ChiclayoOeste-ChiclayoNorte_L2
Lne ChiclayoOeste-ChiclayoNorte_L1
1.13 1.13 0.15 0.14 0.84 0.80 0.15 1.05
2.588 2.34 2.34 0.32 0.30 1.57 1.50 0.27 1.81
0.448
1.193 ILLIMO60 LA_VIA60 MOTUP60
lod chicl23 lod chicl10n 94.372 72.178
2.724 2.084 45.798
0.00 0.00 5.659 3.884 1.322

IN1007
2.281

L-6012

L-6022

L-6032

L-6033
0.00 0.00 6.00 10.28 4.41 5.05
0.00 0.00 0.17 0.30 0.13 0.15
0.36 0.55 0.22 0.25
Breaker/S..

Breaker/S..
0.00 0.00

tr2 La Via
0.00 0.00 0
0.00 0.00 0
CHICL23 CHIL10N CHICL10B -6
2.588 27.86 0.00 0.00
113.995 2.588 2.10 0.00 0.00
0.448
8.622
23.476
0.448
1.193 1.193 CHICL10A 5.51 0.00 0.00
114.00 0.89 Breaker/S.. 0.43 0.41 IN - 1008 0.42
8.62 0.15 0.07 0.07 0.07 2.588 ILLIMO10 LA_VIA10 Tr3 Motup..
23.48 0.41 0.20 0.19 0.19 0.448 ILLIMO23 0.34 26.19
tr3 Chiclayo T3 1.193 27.857 0.000 0.000 0.06 1.98
2.098 0.000 0.000 0.14 4.23
5.508 0.000 0.000
0.00 0.00 0.00 0.00
0 0 0.00 0.00 0.00 0.00 MOTUP10 MOTUP23
0.00 0.00 0.00 0.00
0
11.27
T3 ZZ Chicl
5.22
T1 5.33
T2 4.83 4.83 0.87 0.87
1
0.507
0.088
0.203
26.192
1.981
4.229
0.00 0.17 0.00
0.33 0.15 0.15 0.14 0.14 0.03 0.03 0.00 0.03 0.00
CHICL-O6 0.81 0.38 0.38 0.35 0.35 0.06 0.06
28.54 0.00 0.07 0.00
0.82
423.617 1
1.39
12.229
30.545 OLMOS60
112.33 112.33 161.17 0.00 4.95 35.443
Lod motup23
3.24 3.24 4.65 0.00 0.14 LAMB_SUR_60 LAMBA60 1.023
8.10 8.10 11.62 0.00 0.36 1.721 22.24
184.779 3.69 3.24
0 145.629 0.11 0.09 0.64
-5 -5 5.334
4.204 0.18 0.16 1.06
11.915
149.12 27.82 8.03 134.77 10.95 9.228
OCCI60
tr2 chi_674

OLMOS22.9
4.30 0.80 0.23 3.89 0.32
0.00 0.00 0.00 9.62 1.79 0.52 8.54 0.69 -2
0.00 0.00 0.00 27.374

tr2 lam_801

20.896
tr3 chi_2671 tr3 chi_2672 0.00 tr3 chi_2672(1) 0.790

1.580
3.157
0.00 0.00
0.00 5.17 1.310
-2 0.00
0.15
0 0.00
30.91 30.91 57.86 0.25
0.000 0.000 0.000
0.24
SECHO1A 0.000 0.000 SECHO1B 0.24
0.000 SECHO1C
0.46 L-6037 OLMOS10 0

20.90
0.58 0.58 1.08

1.58
3.16

0.00
0.00
0.00
0.000 0.000 0.000 0.25 0.24
0.05 0.04 0.000
0.14 0.10

0.00
0.00
0.00
0.000 19.23 0.00
0.000 0.00
597.603 LAMBA10 0.00
1.45
2.85
0.00
0.00
4.705 0.254 0.00
11.204 CHICLAYO_OESTE_220 0.055
0.99
0.17
0.364
0.142 0.42
0.063 OCCI23 OCCI10
0.156
0.00 0.00 0.00 0.00 0.00 0.12
SVCCHI 0.00 0.00 LAMB_SUR_10 0.00 0.00 0.00 0.02
19.227
1.454
0.000
0.000
0.00 0.00 0.00 0.00 0.00 0.05 2.847 0.000
1.489 0.00 0.00
1 0.258 1 0.00 0.00
Max. Single Phase to Ground acc. to IEC60909 SVS 0.635
0.00 0.50
0.00 0.00
0.00 0.09 1
Short Circuit Nodes Branches 0.00 0.21
zz lam
Initial Short-Circuit Power A [MVA]Initial Short-Circuit Power A [MVA]
Initial Short-Circuit Current A [kA] Initial Short-Circuit Current A [kA]
ESTUDIO DE OPERAT IVIDAD Project:
zz lamsur
Peak Short-Circuit Current A [kA] Peak Short-Circuit Current A [kA]
SE CHICLAYO OEST E Y SE CHICLAYO NORTE Graphic: EOP SECHO
Estudio de Cortocircuito Monofsico Date: 2/12/2014
PowerFactory 14.1.3 ES14MAX - CON PROYECTO Annex:

DLF SAC Pgina 92 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA EN CHICLAYO OESTE Y CHICLAYO NORTE

DIgSILENT
11.909 21.920
SE. CHICLAYO NORTE POMAL10 2.063
5.619 POMAL23 1.651
4.364

0.00 0.00 0.00


0.00 0.00 0.00 80.223
11.91 tr3 pom_8001 21.92 0.00
0.00 0.00 0.00 2.06 1.65 0.00 TUMAN60 2.316
4.751 CAYAL60
5.62 4.36 0.00

Breaker/S..

Breaker/S..

Breaker/S..
CHICN10B 43.346
1.251
97.982
CHICN10C 16.971 80.22 0.00 0.00
2.534
43.35 0.00
40.543 CHICN10 L-6051 -2 2.32 0.00 0.00 1.25 0.00
97.982 4.75 0.00 0.00 2.53 0.00
97.982
16.971 lne POM_TUM_81 lne TUM_CAY_81
40.543
16.971 lne CHIC_POM_81
40.543 115.03 0.00 0.00
45.63 IN1032 0.00 25.85 IN1030 26.52 0.00
3.32 0.00 0.00 -5 -1
7.90 0.00 4.48 4.59 0.00
6.90 0.00 0.00
18.88 0.00 10.70 10.97 0.00

-2 POMAL60
20.30 11.41 16.80 10.21

0.00
T3 -2

0.00
T2 -2

0.00
T1 0.00
115.027
3.321
1.53 1.98
3.94 tr3 tum_8001 5.30
1.26 1.77
3.10 tr3 cay_8001 4.57
ZZ chicln 6.895
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
TUMAN23 TUMAN10 CAYAL23 CAYAL10
184.464
5.325 20.303 11.414 16.795 10.214
11.341 1.529 1.977 1.265 1.769
3.941 5.299 3.096 4.567
0.00 0.00
0.00 0.00
0.00 0.00
92.23 92.23
2.66 2.66
ZZ CT Chicl 5.67 5.67
Chicl G1 Chicl G2 Chicl G3 Chicl G4 Chicl G5
~ ~ ~ ~ ~
G G G G G
SE. CHICLAYO OESTE Lne 60KV-ILLIMO-LA VIA
0.00
0.00
0.00
42.26 42.26 0.00 0.00 29.90 28.11 0.00 35.29
CT CHICL10

Lne ChiclayoOeste-ChiclayoNorte_L2
Lne ChiclayoOeste-ChiclayoNorte_L1
1.22 1.22 0.00 0.00 0.86 0.81 0.00 1.02
126.771 2.53 2.53 0.00 0.00 1.61 1.51 0.00 1.76
21.957
58.403 ILLIMO60 LA_VIA60 MOTUP60
lod chicl23 lod chicl10n 84.518 58.002
2.440 1.674 35.286
0.00 0.00 5.068 3.121 1.019

IN1007
1.757

L-6012

L-6022

L-6032

L-6033
0.00 0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00
Breaker/S..

Breaker/S..
0.00 0.00

tr2 La Via
0.00 0.00 0
0.00 0.00 0
CHICL23 CHIL10N CHICL10B -6
126.771 17.84 12.48 18.34
77.577 126.771 1.34 2.16 3.18
21.957
5.868
15.976
21.957
58.403 58.403 CHICL10A 3.53 5.80 7.68
77.58 65.48 Breaker/S.. 0.00 30.34 IN - 1008 30.95
5.87 11.34 0.00 5.26 5.36 126.771 ILLIMO10 LA_VIA10 Tr3 Motup..
15.98 30.17 0.00 13.98 14.26 21.957 ILLIMO23 11.61 16.99
tr3 Chiclayo T3 58.403 17.844 12.483 18.343 2.01 1.28
1.344 2.162 3.177 4.65 2.74
3.528 5.799 7.679
0.00 0.00 0.00 0.00
0 0 0.00 0.00 0.00 0.00 MOTUP10 MOTUP23
0.00 0.00 0.00 0.00
0
0.00
T3 ZZ Chicl
0.00
T1 0.00
T2 0.00 0.00 0.00 0.00
1
11.614
2.012
4.648
16.985
1.285
2.743
0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CHICL-O6 0.00 0.00 0.00 0.00 0.00 0.00 0.00
26.46 0.00 0.00 0.00
0.76
265.170 1
1.28
7.655
19.120 OLMOS60
66.16 66.16 132.85 0.00 0.00 26.455
Lod motup23
1.91 1.91 3.84 0.00 0.00 LAMB_SUR_60 LAMBA60 0.764
4.77 4.77 9.58 0.00 0.00 1.285 20.11
141.660 0.00 0.00
0 120.261 0.00 0.00 0.58
-5 -5 4.089
3.472 0.00 0.00 0.96
9.135
141.66 0.00 0.00 120.26 0.00 7.620
OCCI60
tr2 chi_674

OLMOS22.9
4.09 0.00 0.00 3.47 0.00
165.64 165.64 78.74 9.13 0.00 0.00 7.62 0.00 -2
28.69 28.69 13.64 20.113

tr2 lam_801

13.674
tr3 chi_2671 76.14 76.14 tr3 chi_2672 35.48 tr3 chi_2672(1) 0.581

1.034
2.066
9.05 0.00 0.962
-2 1.57
0.00
0 3.41
0.00 0.00 0.01 0.00
165.642 165.642 78.740
0.00
SECHO1A 28.690 28.690 SECHO1B 0.00
13.638 SECHO1C
0.00 L-6037 OLMOS10 0

13.67
0.00 0.00 0.00

1.03
2.07

0.00
0.00
0.00
76.136 76.136 35.485 68.46 21.93
14.82 3.80 9.053
38.29 9.36

0.00
0.00
0.00
1.568 11.93 10.21
3.412 0.00
442.003 LAMBA10 0.00
0.90
1.77
1.77
3.62
3.480 68.463 0.00
8.287 CHICLAYO_OESTE_220 14.823
57.81
10.01
21.925
38.292 24.66
3.798 OCCI23 OCCI10
9.365
0.00 0.00 0.00 0.00 0.00 0.00
SVCCHI 0.00 0.00 LAMB_SUR_10 0.00 0.00 0.00 0.00
11.930
0.902
10.212
1.769
0.00 0.00 0.00 0.00 0.00 0.00 1.767 3.615
57.813 0.00 0.00
1 10.014 1 0.00 0.00
Max. 2-Phase Short-Circuit acc. to IEC60909 SVS 24.656
0.00 0.00
0.00 0.00
0.00 0.00 1
Short Circuit Nodes Branches 0.00 0.00
zz lam
Initial Short-Circuit Power B [MVA]Initial Short-Circuit Power B [MVA]
Initial Short-Circuit Current B [kA] Initial Short-Circuit Current B [kA]
ESTUDIO DE OPERAT IVIDAD Project:
zz lamsur
Peak Short-Circuit Current B [kA] Peak Short-Circuit Current B [kA]
SE CHICLAYO OEST E Y SE CHICLAYO NORTE Graphic: EOP SECHO
Estudio de Cortocircuito Bifsico Date: 2/12/2014
PowerFactory 14.1.3 ES14MAX - CON PROYECTO Annex:

DLF SAC Pgina 93 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE POTENCIA EN CHICLAYO OESTE Y CHICLAYO NORTE

DIgSILENT
41.50 76.78
SE. CHICLAYO NORTE POMAL10 2.396
6.533 POMAL23 1.927
5.101

289.63
41.50 tr3 pom_8001 76.78
2.396 1.927 TUMAN60 2.787
5.686 CAYAL60
6.533 5.101

Breaker/S..

Breaker/S..

Breaker/S..
CHICN10B 153.51
1.477
357.16
CHICN10C 20.620 289.63 0.00 0.00
2.983
153.51 0.00
49.268 CHICN10 L-6051 -7 2.787 0.000 0.000 1.477 0.000
357.16 5.686 0.000 0.000 2.983 0.000
357.16
20.620 lne POM_TUM_81 lne TUM_CAY_81
49.268
20.620 lne CHIC_POM_81
49.268 423.06 0.00 0.00
166.31 IN1032 0.00 94.22 IN1030 96.66 0.00
4.071 0.000 0.000 -5 -1
9.602 0.000 5.440 5.580 0.000
8.392 0.000 0.000
22.942 0.000 12.997 13.333 0.000

-1 POMAL60
71.05 39.77 58.68 35.57

0.00
T3 -1

0.00
T2 -1

0.00
T1 0.00
423.06
4.071
1.784 2.296
4.602 tr3 tum_8001 6.159
1.473 2.053
3.606 tr3 cay_8001 5.303
ZZ chicln 8.392
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
TUMAN23 TUMAN10 CAYAL23 CAYAL10
704.87
6.783 71.05 39.77 58.68 35.57
14.299 1.784 2.296 1.473 2.053
4.602 6.159 3.606 5.303

352.43 352.43
3.391 3.391
ZZ CT Chicl 7.150 7.150
Chicl G1 Chicl G2 Chicl G3 Chicl G4 Chicl G5
~ ~ ~ ~ ~
G G G G G
SE. CHICLAYO OESTE Lne 60KV-ILLIMO-LA VIA
0.00 31.39 31.39 37.76
0.000 1.812 1.812 2.180
0.000 4.806 4.806 5.781
152.92 152.92 0.00 0.00 106.64 100.26 0.00 124.34
CT CHICL10

Lne ChiclayoOeste-ChiclayoNorte_L2
Lne ChiclayoOeste-ChiclayoNorte_L1
1.472 1.472 0.000 0.000 1.026 0.965 0.000 1.196
574.68 3.040 3.040 0.000 0.000 1.902 1.788 0.000 2.056
33.179
87.989 ILLIMO60 LA_VIA60 MOTUP60
lod chicl23 lod chicl10n 305.85 206.87
2.943 1.991 124.34
6.081 3.690 1.196

IN1007
2.056

L-6012

L-6022

L-6032

L-6033
0.00 0.00 0.00 0.00
0.000 0.000 0.000 0.000
0.000 0.000 0.000 0.000
Breaker/S..

Breaker/S..

tr2 La Via
0
0
CHICL23 CHIL10N CHICL10B 0
574.68 62.37 43.51 64.14
307.56 547.31 1.566 2.512 3.703
33.179
7.754
21.136
31.599
83.799 87.989 CHICL10A 4.114 6.743 8.952
307.56 233.25 Breaker/S.. 0.00 113.49 IN - 1008 115.75
7.754 13.467 0.000 6.552 6.683 574.68 ILLIMO10 LA_VIA10 Tr3 Motup..
21.136 35.713 0.000 17.376 17.722 33.179 ILLIMO23 40.47 59.35
tr3 Chiclayo T3 87.989 62.37 43.51 64.14 2.337 1.496
1.566 2.512 3.703 5.398 3.192
4.114 6.743 8.952
0.00
0 0 0.000 MOTUP10 MOTUP23
0.000
0
44.40
T3 ZZ Chicl
20.57
T1 20.98
T2 0.00 0.00 0.00 0.00
1
40.47
2.337
5.398
59.35
1.496
3.192
0.00
0.427 0.198 0.202 0.000 0.000 0.000 0.000 0.000
CHICL-O6 1.075 0.498 0.508 0.000 0.000 0.000 0.000
92.81 0.000
0.893
1061.11 1
1.498
10.211
25.691 OLMOS60
243.35 243.35 488.60 0.00 0.00 92.81
Lod motup23
2.342 2.342 4.702 0.000 0.000 LAMB_SUR_60 LAMBA60 0.893
5.892 5.892 11.830 0.000 0.000 1.498 70.33
528.76 0.00 0.00
0 443.67 0.000 0.000 0.677
-3 -3 5.088
4.269 0.000 0.000 1.119
11.314
528.76 0.00 0.00 443.67 0.00 9.326
OCCI60
tr2 chi_674

OLMOS22.9
5.088 0.000 0.000 4.269 0.000
624.99 624.99 284.18 11.314 0.000 0.000 9.326 0.000 0
36.084 36.084 16.407 70.33

tr2 lam_801
tr3 chi_2671 96.618 96.618 tr3 chi_2672 42.833tr3 chi_2672(1) 0.677

47.70
1.203
2.399
31.50 0.00 1.119
-2 1.819
0.000
0 3.957
20.67 20.67 41.50 0.000
624.99 624.99 284.18
0.054
SECHO1A 36.084 36.084 SECHO1B 0.054
16.407 SECHO1C
0.109 L-6037 OLMOS10 0

47.70
1.203
2.399
0.130 0.130 0.261
96.618 96.618 42.833 245.67 76.80
17.730 4.434 31.50

0.000
0.000
45.938 10.939

0.00
1.819 41.57 35.56
3.957
1778.58 LAMBA10 1.048
2.050
2.053
4.193
4.668 245.67
11.194 CHICLAYO_OESTE_220 17.730
206.31
11.911
76.80
45.938 29.357
4.434 OCCI23 OCCI10
10.939
0.00 0.00 0.00 0.00
SVCCHI 0.000 0.000 LAMB_SUR_10 0.000 0.000
41.57
1.048
35.56
2.053
0.000 0.000 0.000 0.000 2.050 4.193
206.31 0.00
1 11.911 1 0.000
Max. 3-Phase Short-Circuit acc. to IEC60909 SVS 29.357
0.00
0.000
0.000 1
Short Circuit Nodes Branches 0.000
zz lam
Initial Short-Circuit Power [MVA]Initial Short-Circuit Power [MVA]
Initial Short-Circuit Current [kA] Initial Short-Circuit Current [kA]
ESTUDIO DE OPERAT IVIDAD Project:
zz lamsur
Peak Short-Circuit Current [kA] Peak Short-Circuit Current [kA]
SE CHICLAYO OEST E Y SE CHICLAYO NORTE Graphic: EOP SECHO
Estudio de Cortocircuito Trifsico Date: 2/12/2014
PowerFactory 14.1.3 ES14MAX - CON PROYECTO Annex:

DLF SAC Pgina 94 de 132 Revisin: 1


ESTUDIO DE OPERATIVIDAD
PUESTA EN OPERACION DEL TERCER TRANSFORMADOR DE
POTENCIA EN CHICLAYO OESTE Y CHICLAYO NORTE

ANEXO V:

PLANILLAS DE AJUSTES

DLF SAC Pgina 95 de 132 Revisin: 1


BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: DIFERENCIAL Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: ABB Cd.Transf.: TR3 Depto: LAMBAYEQUE
Modelo: RET670 Potencia: 30 / 16 / 20 MVA Empresa: ELECTRONORTE
Versin: Tensin 60 8x1.25%/22.9/10 kV Diag.Unif.N:
Tecnologa: NUMRICA Uprim[kV]: 60 Man.Serv.N:
Ao instal.: Fases: RST-N Fecha: 11-feb-14
Cdigo: Ucc [V]: Respons.:
N Serie: Uca [V]: 100 Revisin: 0
Ubic.Tabl: Ica [A]: 1
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES (AS BUILT) ECP 2010 OBSERVACIONES
GRUPO 1 GRUPO 1
ANSI COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

DATOS GENERALES
DATOS DEL TANSFORMADOR TRANSFORMADORES DE CORRIENTE

VALORES DE AJUSTE
51 SOBRE/SUBCORRIENTE 51 SOBRE/SUBCORRIENTE DE TIEMPO DEFINIDO
50 SOBRECORRIRNTE INSTANTANEO 51 SOBRECORRIRNTE INVERSO

DATOS GENERALES
DATOS DEL TANSFORMADOR
Generales
Tipo (Transformador-Autotransformador) - Transformador
Arrollamiento primario
Tensin nominal primaria entre fases kV 60
Tensin mxima de servicio entre fases kV
Potencia aparente nominal MVA 30
Sobrecarga permanente %
Corriente nominal A 288.68
Corriente de inrush primaria Acr
Arrollamiento secundario
Tensin nominal primaria entre fases kV 22.9
Tensin mxima de servicio entre fases kV
Potencia aparente nominal MVA 16
Corriente nominal A 403.39
Arrollamiento terciario
Tensin nominal primaria entre fases kV 10
Tensin mxima de servicio entre fases kV
Potencia aparente nominal MVA 20
Corriente nominal A 1154.70
Grupos de conexin
Grupo de conexin primario-secundario - YNyn0
Grupo de conexin primario-terciario - YNd5
Grupo de conexin secundario-terciario - ynd5
Regulador bajo carga
Ubicado en arrollamiento: - Primario
Rango de regulacin % 8x1.25
Relaciones de cortocircuito
Potencia base MVA
Primario-Secundario secuencia positiva % 6.76
Primario-Terciario secuencia positiva % 5
Secundario-Terciario secuencia positiva % 2.28

SE_ChiclOest_TR3_RET670_2014 1 de 14 11/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: DIFERENCIAL Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: ABB Cd.Transf.: TR3 Depto: LAMBAYEQUE
Modelo: RET670 Potencia: 30 / 16 / 20 MVA Empresa: ELECTRONORTE
Versin: Tensin 60 8x1.25%/22.9/10 kV Diag.Unif.N:
Tecnologa: NUMRICA Uprim[kV]: 60 Man.Serv.N:
Ao instal.: Fases: RST-N Fecha: 11-feb-14
Cdigo: Ucc [V]: Respons.:
N Serie: Uca [V]: 100 Revisin: 0
Ubic.Tabl: Ica [A]: 1
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES (AS BUILT) ECP 2010 OBSERVACIONES
GRUPO 1 GRUPO 1
ANSI COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

Primario-Secundario secuencia cero % 6.76


Primario-Terciario secuencia cero % 5
Secundario-Terciario secuencia cero % 2.28
TRANSFORMADORES DE CORRIENTE PRIMARIO (HV)
Marca - -
Tipo - -
Modelo - -
Cantidad de ncleos - -
Corriente nominal A - 5 400
Relacin de transformacin - - 80.00
Clase - -
Prestacin VA -
TRANSFORMADORES DE CORRIENTE SECUNDARIO (MV)
Marca - -
Tipo - -
Modelo - -
Cantidad de ncleos - -
Corriente nominal A - 5 500
Relacin de transformacin - - 100.00
Clase - -
Prestacin VA -
TRANSFORMADORES DE CORRIENTE TERCIARIO (LV)
Marca - -
Tipo - -
Modelo - -
Cantidad de ncleos - -
Corriente nominal A - 5 1200
Relacin de transformacin - - 240.00
Clase - -
Prestacin VA -
VALORES DE AJUSTE
@ GENERAL SETTINGS Disp.s/interr.:
@ Power System
Frequency Frecuencia - 50 60 10 - 60
87 Differential protection
TransformerDiff3Wind(PDIF,87T)
RatedVoltageW1 Rated voltage of transformer winding 1 (HV winding) in kV kV 0.05 2000.00 0.05 - 60
RatedVoltageW2 Rated voltage of transformer winding 2 in kV kV 0.05 2000.00 0.05 - 22.9
RatedVoltageW3 Rated voltage of transformer winding 3 in kV kV 0.05 2000.00 0.05 - 10
RatedCurrentW1 Rated current of transformer winding 1 (HV winding) in A A 1 99999 1 3.61 289.0
RatedCurrentW2 Rated current of transformer winding 2 in A A 1 99999 1 4.03 403

SE_ChiclOest_TR3_RET670_2014 2 de 14 11/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: DIFERENCIAL Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: ABB Cd.Transf.: TR3 Depto: LAMBAYEQUE
Modelo: RET670 Potencia: 30 / 16 / 20 MVA Empresa: ELECTRONORTE
Versin: Tensin 60 8x1.25%/22.9/10 kV Diag.Unif.N:
Tecnologa: NUMRICA Uprim[kV]: 60 Man.Serv.N:
Ao instal.: Fases: RST-N Fecha: 11-feb-14
Cdigo: Ucc [V]: Respons.:
N Serie: Uca [V]: 100 Revisin: 0
Ubic.Tabl: Ica [A]: 1
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES (AS BUILT) ECP 2010 OBSERVACIONES
GRUPO 1 GRUPO 1
ANSI COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

RatedCurrentW3 Rated current of transformer winding 3 in A A 1 99999 1 4.81 1155


ConnectTypeW1 Connection type of winding 1: Y-wye (1) or D-delta (2) - WYE (Y) - WYE(Y)
Delta (D)
ConnectTypeW2 Connection type of winding 2: Y-wye (1) or D-delta (2) - WYE (Y) - WYE(Y)
Delta (D)
ConnectTypeW3 Connection type of winding 3: Y-wye (1) or D-delta (2) - WYE (Y) - Delta (D)
Delta (D)
ClockNumberW2 Phase displacement between W2 & W1=HV winding - 0 [0 deg ] a 11 [30 deg lead] - 0 [0 deg]
ClockNumberW3 Phase displacement between W3 & W1=HV winding - 0 [0 deg ] a 11 [30 deg lead] - 5[150 deg
ZSCurrSubtrW1 Enable zer. seq. current subtraction for W1 side - ON - OFF - l ON ]
ZSCurrSubtrW2 Enable zer. seq. current subtraction for W2 side - ON - OFF - ON
ZSCurrSubtrW3 Enable zer. seq. current subtraction for W3 side - ON - OFF - OFF
TconfigForW1 Two CT inputs (T-config.) for winding 1 - YES - NO - NO
CT1RatingW1 CT primary rating in A, T-branch 1, on transf. W1 side A 1 99999 1 5.00 400
CT2RatingW1 CT primary rating in A, T-branch 2, on transf. W1 side A 1 99999 1 - -
TconfigForW2 Two CT inputs (T-config.) for winding 2 - YES - NO - NO
CT1RatingW2 CT primary rating in A, T-branch 1, on transf. W2 side A 1 99999 1 5.00 500
CT2RatingW2 CT primary rating in A, T-branch 2, on transf. W2 side A 1 99999 1 - -
TconfigForW3 Two CT inputs (T-config.) for winding 3 - YES - NO - NO
CT1RatingW3 CT primary rating in A, T-branch 1, on transf. W3 side A 1 99999 1 5.00 1200
CT2RatingW3 CT primary rating in A, T-branch 2, on transf. W3 side A 1 99999 1 - -
51 Current protection
PhaseOverCurrent4Step(PTOC, 51/67)
MeasType TOC1 - DFT - RMS - RMS
MeasType TOC2 - DFT - RMS - RMS
MeasType TOC3 - DFT - RMS - RMS
59/27 Voltage Protection -
OverVoltage2Step(PTOV,59) -
ConnType TOV1 - PhN DFT, PhPh DFT, - -
PhN RMS, PhPh RMS
ConnType TOV2 - PhN DFT, PhPh DFT, - -
PhN RMS, PhPh RMS
UnderVoltage2Step(PTUV,27) -
ConnType TUV1 - PhN DFT, PhPh DFT, - -
PhN RMS, PhPh RMS
ConnType TUV2 - PhN DFT, PhPh DFT, - -
PhN RMS, PhPh RMS
ConnType TUV3 - PhN DFT, PhPh DFT, - -
PhN RMS, PhPh RMS
@ Setting Group N1
87 DIFFERENTIAL PROTECTION

SE_ChiclOest_TR3_RET670_2014 3 de 14 11/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: DIFERENCIAL Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: ABB Cd.Transf.: TR3 Depto: LAMBAYEQUE
Modelo: RET670 Potencia: 30 / 16 / 20 MVA Empresa: ELECTRONORTE
Versin: Tensin 60 8x1.25%/22.9/10 kV Diag.Unif.N:
Tecnologa: NUMRICA Uprim[kV]: 60 Man.Serv.N:
Ao instal.: Fases: RST-N Fecha: 11-feb-14
Cdigo: Ucc [V]: Respons.:
N Serie: Uca [V]: 100 Revisin: 0
Ubic.Tabl: Ica [A]: 1
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES (AS BUILT) ECP 2010 OBSERVACIONES
GRUPO 1 GRUPO 1
ANSI COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

87T TransformerDiff3Wind(PDIF,87T)
Operation Operation - ON - OFF - ON
SOTFMode SOTF mode - ON - OFF - ON
IDiffAlarm IDiffAlarm %IB 5.00 100.00 1.00 - 50.00
tAlarmDelay tAlarmDelay seg 0.000 60.000 0.001 - 10.000
IdMin Section 1 sensitivity,multiple of Winding 1 rated current IB 0.10 0.60 0.01 - 0.30
EndSection1 End of section 1, multiple of Winding 1 rated current IB 0.20 1.50 0.01 - 1.25
EndSection2 End of section 2, multiple of Winding 1 rated current IB 1.00 10.00 0.01 - 3.00
SlopeSection2 Slope in section 2 of operate-restrain characteristic, in % % 10.0 50.0 0.1 - 25.00
SlopeSection3 Slope in section 3 of operate-restrain characteristic, in % % 30.0 100.0 0.1 - 50.00
IdUnre Unrestr. prot. limit, multiple of Winding 1 rated current IB 1.00 50.00 0.01 - 10.00
I2/I1Ratio Max. ratio of 2nd harm. to fundamental harm dif. curr. in % % 5.0 100.0 0.1 - 15.00
I5/I1Ratio Max. ratio of 5th harm. to fundamental harm dif. curr. in % % 5.0 100.0 0.1 - 25.00
OpCrossBlock Operation On / Off for cross-block logic between phases - ON - OFF - ON
OpNegSeqDiff Operation On / Off for neg. seq. differential protections - ON - OFF - ON
IMinNegSeq Neg. seq. curr. must be higher than this level to be used IB 0.02 0.20 0.01 - 0.10
NegSeqROA Operate Angle for int. /ext. neg. seq. fault discriminator Deg 30.0 120.0 0.1 - 60.00
OpenCTEnable Open CT Enable - ON - OFF - ON
tOCTAlarmDelay tOCTAlarmDelay seg 0.100 10.000 0.001 - 3.00
tOCTResetDelay tOCTResetDelay seg 0.100 10.000 0.001 - 0.250
tOCTUnrstDelay tOCTUnrstDelay seg 0.10 6000.00 0.01 - 10.00
51 CURRENT PROTECTION
51/67 Phase OverCurrent 4 Step
TOC 1
General TOC1
Operation Operation - ON - OFF - ON
IBase Base setting for currentv values A 1 99999 1 - 400
UBase Base setting for voltage levels in kV kV 0.05 2000.00 0.05 - -
AngleRCA Relay characteristic angle (RCA) Deg 40 65 1 - -
AngleROA Relay characteristic angle (ROA) Deg 40 89 1 - -
StartPhSel Number of phases required for operation - Not Used, 1 out of 3, - 1 out of 3
2 out of 3, 3 out of 3

IMinOpPhSel Minimum current for phase selection in % of Ibase %IB 1 100 1 - -


2ndHarmStab Operate level of 2nd harm restrain op in % of %IB 5 100 1 - -
Step 1 TOC1 -
Off
Non-directional Non-
DirMode1 Directional mode of step 1 - -
Forward directional
Reverse

SE_ChiclOest_TR3_RET670_2014 4 de 14 11/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: DIFERENCIAL Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: ABB Cd.Transf.: TR3 Depto: LAMBAYEQUE
Modelo: RET670 Potencia: 30 / 16 / 20 MVA Empresa: ELECTRONORTE
Versin: Tensin 60 8x1.25%/22.9/10 kV Diag.Unif.N:
Tecnologa: NUMRICA Uprim[kV]: 60 Man.Serv.N:
Ao instal.: Fases: RST-N Fecha: 11-feb-14
Cdigo: Ucc [V]: Respons.:
N Serie: Uca [V]: 100 Revisin: 0
Ubic.Tabl: Ica [A]: 1
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES (AS BUILT) ECP 2010 OBSERVACIONES
GRUPO 1 GRUPO 1
ANSI COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

ANSI EI, VI, NI, MI, DT


L.T.E. inv
L.T.V. inv
L.T. inv
Characteristic 1 Selection of time delay curve type for step 1 - IEC NI, VI, EI, S.T.I, L.T.I, DT - IEC NI
Reserved
Programmable
RI type
RD type
I1> Operate phase current level for step 1 in % of IBase %IB 1 2500 1 376.00 94
t1 Independent (definitive) time delay of step 1 s 0.000 60.000 0.001 - 0.00
k1 Time multiplier for the dependent time delay for step 1 - 0.05 999.00 0.01 - 0.15
t1Min Minimum operate time for IEC IDMT curves for step 1 s 0.000 60.000 0.001 - 0.00
I1Mult Multiplier for operate current level for step 1 - 1.0 10.0 0.1 - 1.00
Instantaneous
ResetTypeCrv1 Selection of reste curve type for step 1 - IEC Reset - -
ANSI Reset
tReset1 Reset time delay used in IEC Definite Time curve step 1 s 0.000 60.000 0.001 - -
tPCrv1 Param. P for customer programmable curve for step 1 - 0.005 3.000 0.001 - -
tACrv1 Param. A for customer programmable curve for step 1 - 0.005 200.000 0.001 - -
tBCrv1 Param. B for customer programmable curve for step 1 - 0.00 20.00 0.01 - -
tCCrv1 Param. C for customer programmable curve for step 1 - 0.1 10.0 0.1 - -
tPRCrv1 Param. PR for customer programmable curve for step 1 - 0.005 3.000 0.001 - -
tTRCrv1 Param. TR for customer programmable curve for step 1 - 0.005 100.000 0.001 - -
tCRCrv1 Param. CR for customer programmable curve for step 1 - 0.1 10.0 0.1 - -
HarmRestrain1 Enabled block of step 1 from harmonic restrain - ON - OFF - -
Step 2 TOC1
Off
Non-directional Non-
DirMode2 Directional mode of step 2 - -
Forward directional
Reverse
ANSI EI, VI, NI, MI, DT
L.T.E. inv
L.T.V. inv
L.T. inv
Characteristic 2 Selection of time delay curve type for step 2 - IEC NI, VI, EI, S.T.I, L.T.I, DT - DT
Reserved
Programmable
RI type
RD type
I2> Operate phase current level for step 2 in % of IBase %IB 1 2500 1 3640.00 910

SE_ChiclOest_TR3_RET670_2014 5 de 14 11/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: DIFERENCIAL Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: ABB Cd.Transf.: TR3 Depto: LAMBAYEQUE
Modelo: RET670 Potencia: 30 / 16 / 20 MVA Empresa: ELECTRONORTE
Versin: Tensin 60 8x1.25%/22.9/10 kV Diag.Unif.N:
Tecnologa: NUMRICA Uprim[kV]: 60 Man.Serv.N:
Ao instal.: Fases: RST-N Fecha: 11-feb-14
Cdigo: Ucc [V]: Respons.:
N Serie: Uca [V]: 100 Revisin: 0
Ubic.Tabl: Ica [A]: 1
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES (AS BUILT) ECP 2010 OBSERVACIONES
GRUPO 1 GRUPO 1
ANSI COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

t2 Independent (definitive) time delay of step 2 s 0.000 60.000 0.001 - 0.10


k2 Time multiplier for the dependent time delay for step 2 - 0.05 999.00 0.01 - 0.00
t2Min Minimum operate time for IEC IDMT curves for step 2 s 0.000 60.000 0.001 - 0.00
I2Mult Multiplier for operate current level for step 2 - 1.0 10.0 0.1 - 1.00
Instantaneous
ResetTypeCrv2 Selection of reste curve type for step 2 - IEC Reset - -
ANSI Reset
tReset2 Reset time delay used in IEC Definite Time curve step 2 s 0.000 60.000 0.001 - -
tPCrv2 Param. P for customer programmable curve for step 2 - 0.005 3.000 0.001 - -
tACrv2 Param. A for customer programmable curve for step 2 - 0.005 200.000 0.001 - -
tBCrv2 Param. B for customer programmable curve for step 2 - 0.00 20.00 0.01 - -
tCCrv2 Param. C for customer programmable curve for step 2 - 0.1 10.0 0.1 - -
tPRCrv2 Param. PR for customer programmable curve for step 2 - 0.005 3.000 0.001 - -
tTRCrv2 Param. TR for customer programmable curve for step 2 - 0.005 100.000 0.001 - -
tCRCrv2 Param. CR for customer programmable curve for step 2 - 0.1 10.0 0.1 - -
HarmRestrain2 Enabled block of step 2 from harmonic restrain - ON - OFF - -
TOC 2
General TOC2
Operation Operation - ON - OFF - ON
IBase Base setting for currentv values A 1 99999 1 - 500
UBase Base setting for voltage levels in kV kV 0.05 2000.00 0.05 - -
AngleRCA Relay characteristic angle (RCA) Deg 40 65 1 - -
AngleROA Relay characteristic angle (ROA) Deg 40 89 1 - -
StartPhSel Number of phases required for operation - Not Used, 1 out of 3, - 1 out of 3
2 out of 3, 3 out of 3
IMinOpPhSel Minimum current for phase selection in % of Ibase %IB 1 100 1 - -
2ndHarmStab Operate level of 2nd harm restrain op in % of %IB 5 100 1 - -
Step 1 TOC2
Off
Non-directional Non-
DirMode1 Directional mode of step 1 - -
Forward directional
Reverse
ANSI EI, VI, NI, MI, DT
L.T.E. inv
L.T.V. inv
L.T. inv
Characteristic 1 Selection of time delay curve type for step 1 - IEC NI, VI, EI, S.T.I, L.T.I, DT - IEC NI
Reserved
Programmable
RI type
RD type

SE_ChiclOest_TR3_RET670_2014 6 de 14 11/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: DIFERENCIAL Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: ABB Cd.Transf.: TR3 Depto: LAMBAYEQUE
Modelo: RET670 Potencia: 30 / 16 / 20 MVA Empresa: ELECTRONORTE
Versin: Tensin 60 8x1.25%/22.9/10 kV Diag.Unif.N:
Tecnologa: NUMRICA Uprim[kV]: 60 Man.Serv.N:
Ao instal.: Fases: RST-N Fecha: 11-feb-14
Cdigo: Ucc [V]: Respons.:
N Serie: Uca [V]: 100 Revisin: 0
Ubic.Tabl: Ica [A]: 1
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES (AS BUILT) ECP 2010 OBSERVACIONES
GRUPO 1 GRUPO 1
ANSI COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

I1> Operate phase current level for step 1 in % of IBase %IB 1 2500 1 525.00 105
t1 Independent (definitive) time delay of step 1 s 0.000 60.000 0.001 - 0.00
k1 Time multiplier for the dependent time delay for step 1 - 0.05 999.00 0.01 - 0.14
t1Min Minimum operate time for IEC IDMT curves for step 1 s 0.000 60.000 0.001 - 0.00
I1Mult Multiplier for operate current level for step 1 - 1.0 10.0 0.1 - 1.00
Instantaneous
ResetTypeCrv1 Selection of reste curve type for step 1 - IEC Reset - -
ANSI Reset
tReset1 Reset time delay used in IEC Definite Time curve step 1 s 0.000 60.000 0.001 - --
tPCrv1 Param. P for customer programmable curve for step 1 - 0.005 3.000 0.001 - -
tACrv1 Param. A for customer programmable curve for step 1 - 0.005 200.000 0.001 - -
tBCrv1 Param. B for customer programmable curve for step 1 - 0.00 20.00 0.01 - -
tCCrv1 Param. C for customer programmable curve for step 1 - 0.1 10.0 0.1 - -
tPRCrv1 Param. PR for customer programmable curve for step 1 - 0.005 3.000 0.001 - -
tTRCrv1 Param. TR for customer programmable curve for step 1 - 0.005 100.000 0.001 - -
tCRCrv1 Param. CR for customer programmable curve for step 1 - 0.1 10.0 0.1 - -
HarmRestrain1 Enabled block of step 1 from harmonic restrain - ON - OFF - -
TOC 3
General TOC3
Operation Operation - ON - OFF - ON
IBase Base setting for currentv values A 1 99999 1 - 1200
UBase Base setting for voltage levels in kV kV 0.05 2000.00 0.05 - -
AngleRCA Relay characteristic angle (RCA) Deg 40 65 1 - -
AngleROA Relay characteristic angle (ROA) Deg 40 89 1 - -
StartPhSel Number of phases required for operation - Not Used, 1 out of 3, - 1 out of 3
2 out of 3, 3 out of 3
IMinOpPhSel Minimum current for phase selection in % of Ibase %IB 1 100 1 - -
2ndHarmStab Operate level of 2nd harm restrain op in % of %IB 5 100 1 - -
Step 1 TOC3
Off
Non-directional Non-
DirMode1 Directional mode of step 1 - -
Forward directional
Reverse

SE_ChiclOest_TR3_RET670_2014 7 de 14 11/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: DIFERENCIAL Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: ABB Cd.Transf.: TR3 Depto: LAMBAYEQUE
Modelo: RET670 Potencia: 30 / 16 / 20 MVA Empresa: ELECTRONORTE
Versin: Tensin 60 8x1.25%/22.9/10 kV Diag.Unif.N:
Tecnologa: NUMRICA Uprim[kV]: 60 Man.Serv.N:
Ao instal.: Fases: RST-N Fecha: 11-feb-14
Cdigo: Ucc [V]: Respons.:
N Serie: Uca [V]: 100 Revisin: 0
Ubic.Tabl: Ica [A]: 1
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES (AS BUILT) ECP 2010 OBSERVACIONES
GRUPO 1 GRUPO 1
ANSI COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

ANSI EI, VI, NI, MI, DT


L.T.E. inv
L.T.V. inv
L.T. inv
Characteristic 1 Selection of time delay curve type for step 1 - IEC NI, VI, EI, S.T.I, L.T.I, DT - IEC NI
Reserved
Programmable
RI type
RD type
I1> Operate phase current level for step 1 in % of IBase %IB 1 2500 1 1500.00 125
t1 Independent (definitive) time delay of step 1 s 0.000 60.000 0.001 - 0.00
k1 Time multiplier for the dependent time delay for step 1 - 0.05 999.00 0.01 - 0.11
t1Min Minimum operate time for IEC IDMT curves for step 1 s 0.000 60.000 0.001 - 0.00
I1Mult Multiplier for operate current level for step 1 - 1.0 10.0 0.1 - 1.00
Instantaneous
ResetTypeCrv1 Selection of reste curve type for step 1 - IEC Reset - -
ANSI Reset
tReset1 Reset time delay used in IEC Definite Time curve step 1 s 0.000 60.000 0.001 - -
tPCrv1 Param. P for customer programmable curve for step 1 - 0.005 3.000 0.001 - -
tACrv1 Param. A for customer programmable curve for step 1 - 0.005 200.000 0.001 - -
tBCrv1 Param. B for customer programmable curve for step 1 - 0.00 20.00 0.01 - -
tCCrv1 Param. C for customer programmable curve for step 1 - 0.1 10.0 0.1 - -
tPRCrv1 Param. PR for customer programmable curve for step 1 - 0.005 3.000 0.001 - -
tTRCrv1 Param. TR for customer programmable curve for step 1 - 0.005 100.000 0.001 - -
tCRCrv1 Param. CR for customer programmable curve for step 1 - 0.1 10.0 0.1 - -
HarmRestrain1 Enabled block of step 1 from harmonic restrain - ON - OFF - -
52PD Pole Discordance
Pole discordance protection (RPLD, 52PD)
Operat Operation - On - Off Off -
51N/67N Residual Overcurrent4 Step
TEF 1
General TEF1
Operation Operation on/off - ON - OFF - ON
IBase Base setting for current values A 1 99999 1 - 400
UBase Base setting for voltage levels in kV kV 0.05 2000.00 0.01 - -
AngleRCA Relay Characteristic angle (RCA) Deg -180 180 1 - --
polMethod PolMethod - Voltage, Current, Dual - -
UPolMin UPolMin %UB 1 100 1 - -
IPolMin IPolMin %IB 2 100 1 - --
RNPol RNPol ohm 0.50 1000.00 0.01 - -
XNPol XNPol ohm 0.50 3000.00 0.01 - -

SE_ChiclOest_TR3_RET670_2014 8 de 14 11/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: DIFERENCIAL Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: ABB Cd.Transf.: TR3 Depto: LAMBAYEQUE
Modelo: RET670 Potencia: 30 / 16 / 20 MVA Empresa: ELECTRONORTE
Versin: Tensin 60 8x1.25%/22.9/10 kV Diag.Unif.N:
Tecnologa: NUMRICA Uprim[kV]: 60 Man.Serv.N:
Ao instal.: Fases: RST-N Fecha: 11-feb-14
Cdigo: Ucc [V]: Respons.:
N Serie: Uca [V]: 100 Revisin: 0
Ubic.Tabl: Ica [A]: 1
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES (AS BUILT) ECP 2010 OBSERVACIONES
GRUPO 1 GRUPO 1
ANSI COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

IN>Dir IN>Dir %IB 1 100 1 - -


2ndHarmStab 2nd harmonic restrain operation in % of INAMPL % 5 100 1 - -
BlkParTransf Enable blocking at parallel transformers - ON - OFF - -
UseStartValue Current level blk at parallel transf (Step1,2,3 or 4) - IN1>, IN2>, IN3>, IN4> - -
Off
SOTF
SOTF SOTF operation mode - - -
UnderTime
SOTF+UnderTime
Open
Act. SOTF Select signal that shall activate SOTF - Closed - -
CloseCommand
Step2
StepForSOTF StepForSOTF - - -
Step3
HarmResSOTF Enalbed harmonic restrain function SOTF - ON - OFF - -
tSOTF Time delay for SOTF s 0.000 60.000 0.001 - -
t4U Switch-onto-fault active time s 0.000 60.000 0.001 - -
CB position
ActUnderTime Select signal to active under time - - -
CB command
tUnderTime Time delay for under time s 0.000 60.000 0.001 - -
Step 1 TEF1
Off
Non-directional Non-
DirMode1 Directional mode of step 1 - -
Forward directional
Reverse
ANSI EI, VI, NI, MI, DT
L.T.E. inv
L.T.V. inv
L.T. inv
Characteristic 1 Selection of time delay curve type for step 1 - IEC NI, VI, EI, S.T.I, L.T.I, DT - IEC NI
Reserved
Programmable
RI type
RD type
IN1> Operate residual current level for step 1 in % of IBase %IB 1 2500 1 116.00 29
t1 Independent (definitive) time delay of step 1 s 0.000 60.000 0.001 - 0.00
k1 Time multiplier for the dependent time delay for step 1 - 0.05 999.00 0.01 - 0.16
IN1Mult Multiplier for operate current level for step 1 - 1.0 10.0 0.1 - 1.00
t1Min Minimum operate time for IEC IDMT curves for step 1 s 0.000 60.000 0.001 - 0.00
Instantaneous
ResetTypeCrv1 Selection of reste curve type for step 1 - IEC Reset - -
ANSI Reset

SE_ChiclOest_TR3_RET670_2014 9 de 14 11/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: DIFERENCIAL Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: ABB Cd.Transf.: TR3 Depto: LAMBAYEQUE
Modelo: RET670 Potencia: 30 / 16 / 20 MVA Empresa: ELECTRONORTE
Versin: Tensin 60 8x1.25%/22.9/10 kV Diag.Unif.N:
Tecnologa: NUMRICA Uprim[kV]: 60 Man.Serv.N:
Ao instal.: Fases: RST-N Fecha: 11-feb-14
Cdigo: Ucc [V]: Respons.:
N Serie: Uca [V]: 100 Revisin: 0
Ubic.Tabl: Ica [A]: 1
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES (AS BUILT) ECP 2010 OBSERVACIONES
GRUPO 1 GRUPO 1
ANSI COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

tReset1 Reset time delay used in IEC Definite Time curve step 1 s 0.000 60.000 0.001 - -
HarmRestrain1 Enabled block of step 1 from harmonic restrain - ON - OFF - ON
tPCrv1 Param. P for customer programmable curve for step 1 - 0.005 3.000 0.001 - -
tACrv1 Param. A for customer programmable curve for step 1 - 0.005 200.000 0.001 - -
tBCrv1 Param. B for customer programmable curve for step 1 - 0.00 20.00 0.01 - -
tCCrv1 Param. C for customer programmable curve for step 1 - 0.1 10.0 0.1 - -
tPRCrv1 Param. PR for customer programmable curve for step 1 - 0.005 3.000 0.001 - -
tTRCrv1 Param. TR for customer programmable curve for step 1 - 0.005 100.000 0.001 - -
tCRCrv1 Param. CR for customer programmable curve for step 1 - 0.1 10.0 0.1 - -
Step 2 TEF1
Off
Non-directional Non-
DirMode2 Directional mode of step 2 - -
Forward directional
Reverse
ANSI EI, VI, NI, MI, DT
L.T.E. inv
L.T.V. inv
L.T. inv
Characteristic 2 Selection of time delay curve type for step 2 - IEC NI, VI, EI, S.T.I, L.T.I, DT - DT
Reserved
Programmable
RI type
RD type
IN2> Operate residual current level for step 2 in % of IBase %IB 1 2500 1 2312.00 578
t2 Independent (definitive) time delay of step 2 s 0.000 60.000 0.001 - 0.10
k2 Time multiplier for the dependent time delay for step 2 - 0.05 999.00 0.01 - 0.00
IN2Mult Multiplier for operate current level for step 2 - 1.0 10.0 0.1 - 1.00
t2Min Minimum operate time for IEC IDMT curves for step 2 s 0.000 60.000 0.001 - 0.00
Instantaneous
ResetTypeCrv2 Selection of reste curve type for step 2 - IEC Reset - -
ANSI Reset
tReset2 Reset time delay used in IEC Definite Time curve step 2 s 0.000 60.000 0.001 - -
HarmRestrain2 Enabled block of step 2 from harmonic restrain - On - Off - -
tPCrv2 Param. P for customer programmable curve for step 2 - 0.005 3.000 0.001 - -
tACrv2 Param. A for customer programmable curve for step 2 - 0.005 200.000 0.001 - -
tBCrv2 Param. B for customer programmable curve for step 2 - 0.00 20.00 0.01 - -
tCCrv2 Param. C for customer programmable curve for step 2 - 0.1 10.0 0.1 - -
tPRCrv2 Param. PR for customer programmable curve for step 2 - 0.005 3.000 0.001 - -
tTRCrv2 Param. TR for customer programmable curve for step 2 - 0.005 100.000 0.001 - -
tCRCrv2 Param. CR for customer programmable curve for step 2 - 0.1 10.0 0.1 - -
TEF 2

SE_ChiclOest_TR3_RET670_2014 10 de 14 11/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: DIFERENCIAL Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: ABB Cd.Transf.: TR3 Depto: LAMBAYEQUE
Modelo: RET670 Potencia: 30 / 16 / 20 MVA Empresa: ELECTRONORTE
Versin: Tensin 60 8x1.25%/22.9/10 kV Diag.Unif.N:
Tecnologa: NUMRICA Uprim[kV]: 60 Man.Serv.N:
Ao instal.: Fases: RST-N Fecha: 11-feb-14
Cdigo: Ucc [V]: Respons.:
N Serie: Uca [V]: 100 Revisin: 0
Ubic.Tabl: Ica [A]: 1
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES (AS BUILT) ECP 2010 OBSERVACIONES
GRUPO 1 GRUPO 1
ANSI COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

General TEF2
Operation Operation on/off - ON - OFF - ON
IBase Base setting for current values A 1 99999 1 - 500
UBase Base setting for voltage levels in kV kV 0.05 2000.00 0.01 - -
AngleRCA Relay Characteristic angle (RCA) Deg -180 180 1 - -
polMethod PolMethod - Voltage, Current, Dual - -
UPolMin UPolMin %UB 1 100 1 - -
IPolMin IPolMin %IB 2 100 1 - -
RNPol RNPol ohm 0.50 1000.00 0.01 - -
XNPol XNPol ohm 0.50 3000.00 0.01 - -
IN>Dir IN>Dir %IB 1 100 1 - -
2ndHarmStab 2nd harmonic restrain operation in % of INAMPL % 5 100 1 - -
BlkParTransf Enable blocking at parallel transformers - ON - OFF - -
UseStartValue Current level blk at parallel transf (Step1,2,3 or 4) - IN1>, IN2>, IN3>, IN4> - -
Off
SOTF
SOTF SOTF operation mode - - -
UnderTime
SOTF+UnderTime
Open
Act. SOTF Select signal that shall activate SOTF - Closed - -
CloseCommand
Step2
StepForSOTF StepForSOTF - - -
Step3
HarmResSOTF Enalbed harmonic restrain function SOTF - ON - OFF - -
tSOTF Time delay for SOTF s 0.000 60.000 0.001 - -
t4U Switch-onto-fault active time s 0.000 60.000 0.001 - -
CB position
ActUnderTime Select signal to active under time - - -
CB command
tUnderTime Time delay for under time s 0.000 60.000 0.001 - -
Step 1 TEF2
Off
Non-directional Non-
DirMode1 Directional mode of step 1 - -
Forward directiona
Reverse

SE_ChiclOest_TR3_RET670_2014 11 de 14 11/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: DIFERENCIAL Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: ABB Cd.Transf.: TR3 Depto: LAMBAYEQUE
Modelo: RET670 Potencia: 30 / 16 / 20 MVA Empresa: ELECTRONORTE
Versin: Tensin 60 8x1.25%/22.9/10 kV Diag.Unif.N:
Tecnologa: NUMRICA Uprim[kV]: 60 Man.Serv.N:
Ao instal.: Fases: RST-N Fecha: 11-feb-14
Cdigo: Ucc [V]: Respons.:
N Serie: Uca [V]: 100 Revisin: 0
Ubic.Tabl: Ica [A]: 1
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES (AS BUILT) ECP 2010 OBSERVACIONES
GRUPO 1 GRUPO 1
ANSI COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

ANSI EI, VI, NI, MI, DT


L.T.E. inv
L.T.V. inv
L.T. inv
Characteristic 1 Selection of time delay curve type for step 1 - IEC NI, VI, EI, S.T.I, L.T.I, DT - IEC NI
Reserved
Programmable
RI type
RD type
IN1> Operate residual current level for step 1 in % of IBase %IB 1 2500 1 160.00 32
t1 Independent (definitive) time delay of step 1 s 0.000 60.000 0.001 - 0.00
k1 Time multiplier for the dependent time delay for step 1 - 0.05 999.00 0.01 - 0.15
IN1Mult Multiplier for operate current level for step 1 - 1.0 10.0 0.1 - 1.00
t1Min Minimum operate time for IEC IDMT curves for step 1 s 0.000 60.000 0.001 - 0.00
Instantaneous
ResetTypeCrv1 Selection of reste curve type for step 1 - IEC Reset - -
ANSI Reset
tReset1 Reset time delay used in IEC Definite Time curve step 1 s 0.000 60.000 0.001 - -
HarmRestrain1 Enabled block of step 1 from harmonic restrain - ON - OFF - ON
tPCrv1 Param. P for customer programmable curve for step 1 - 0.005 3.000 0.001 - -
tACrv1 Param. A for customer programmable curve for step 1 - 0.005 200.000 0.001 - -
tBCrv1 Param. B for customer programmable curve for step 1 - 0.00 20.00 0.01 - -
tCCrv1 Param. C for customer programmable curve for step 1 - 0.1 10.0 0.1 - -
tPRCrv1 Param. PR for customer programmable curve for step 1 - 0.005 3.000 0.001 - -
tTRCrv1 Param. TR for customer programmable curve for step 1 - 0.005 100.000 0.001 - -
tCRCrv1 Param. CR for customer programmable curve for step 1 - 0.1 10.0 0.1 - -
TEF 3
General TEF3
Operation Operation on/off - ON - OFF - OFF
IBase Base setting for current values A 1 99999 1 - -
UBase Base setting for voltage levels in kV kV 0.05 2000.00 0.01 - -
AngleRCA Relay Characteristic angle (RCA) Deg -180 180 1 - -
polMethod PolMethod - Voltage, Current, Dual - -
UPolMin UPolMin %UB 1 100 1 - -
IPolMin IPolMin %IB 2 100 1 - -
RNPol RNPol ohm 0.50 1000.00 0.01 - -
XNPol XNPol ohm 0.50 3000.00 0.01 - -
IN>Dir IN>Dir %IB 1 100 1 - -
2ndHarmStab 2nd harmonic restrain operation in % of INAMPL % 5 100 1 - -
BlkParTransf Enable blocking at parallel transformers - ON - OFF - -
UseStartValue Current level blk at parallel transf (Step1,2,3 or 4) - IN1>, IN2>, IN3>, IN4> - -

SE_ChiclOest_TR3_RET670_2014 12 de 14 11/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: DIFERENCIAL Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: ABB Cd.Transf.: TR3 Depto: LAMBAYEQUE
Modelo: RET670 Potencia: 30 / 16 / 20 MVA Empresa: ELECTRONORTE
Versin: Tensin 60 8x1.25%/22.9/10 kV Diag.Unif.N:
Tecnologa: NUMRICA Uprim[kV]: 60 Man.Serv.N:
Ao instal.: Fases: RST-N Fecha: 11-feb-14
Cdigo: Ucc [V]: Respons.:
N Serie: Uca [V]: 100 Revisin: 0
Ubic.Tabl: Ica [A]: 1
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES (AS BUILT) ECP 2010 OBSERVACIONES
GRUPO 1 GRUPO 1
ANSI COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

Off
SOTF
SOTF SOTF operation mode - - -
UnderTime
SOTF+UnderTime
Open
Act. SOTF Select signal that shall activate SOTF - Closed - -
CloseCommand
Step2
StepForSOTF StepForSOTF - - -
Step3
HarmResSOTF Enalbed harmonic restrain function SOTF - ON - OFF - -
tSOTF Time delay for SOTF s 0.000 60.000 0.001 - -
t4U Switch-onto-fault active time s 0.000 60.000 0.001 - -
CB position
ActUnderTime Select signal to active under time - - -
CB command
tUnderTime Time delay for under time s 0.000 60.000 0.001 - -
49 Thermal Overload 2 Time Constant
ThermalOverload2TimeConst(PTTR,49) TTR1
Operation Operation Off/On - ON - OFF - OFF
ThermalOverload2TimeConst(PTTR,49) TTR2
Operation Operation Off/On - ON - OFF - OFF
59/27 VOLTAGE PROTECTION
59 Overvoltage 2 Step (PTOV, 59)
Operation Operation - On - Off - OFF
59N Two step residual overvoltage protection (POVM, 59)
TOV 1
General TOV1
Operation Operation - On - Off - OFF
TOV 2
General TOV2
Operation Operation - On - Off - OFF
59N Residual OverVoltage 2 Step (PTOV, 59N)
TRV1
General TRV1
Operation Operation - On - Off - OFF
TRV2
General TRV2
Operation Operation - On - Off - OFF
TRV3
General TRV3
Operation Operation - On - Off - OFF
27 Undervoltage 2 Step (PTUV, 27)

SE_ChiclOest_TR3_RET670_2014 13 de 14 11/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: DIFERENCIAL Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: ABB Cd.Transf.: TR3 Depto: LAMBAYEQUE
Modelo: RET670 Potencia: 30 / 16 / 20 MVA Empresa: ELECTRONORTE
Versin: Tensin 60 8x1.25%/22.9/10 kV Diag.Unif.N:
Tecnologa: NUMRICA Uprim[kV]: 60 Man.Serv.N:
Ao instal.: Fases: RST-N Fecha: 11-feb-14
Cdigo: Ucc [V]: Respons.:
N Serie: Uca [V]: 100 Revisin: 0
Ubic.Tabl: Ica [A]: 1
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES (AS BUILT) ECP 2010 OBSERVACIONES
GRUPO 1 GRUPO 1
ANSI COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

TUV1
General TUV1
Operat Operation - On - Off - OFF
TUV2
General TUV2
Operat Operation - On - Off - OFF
UBase Base voltage, phase-phase in kV kV 0.05 2000.00 0.01 - -
TUV3
General TUV3
Operat Operation - On - Off - OFF
@ SECONDARY SYSTEM SUPERVISION
RFUF Fuse failure supervision (RFUF)
FSD1
Operation Operation - On - Off - OFF
@ CONTROL
25 Synchronizing (RSYN, 25)
Operation Operation - On - Off - OFF

SE_ChiclOest_TR3_RET670_2014 14 de 14 11/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: SOBRECORRIENTE Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: ABB Cd.Transf.: TR3 Depto: LAMBAYEQUE
Modelo: REC670 Potencia: 30 / 16 / 20 MVA Empresa: ELECTRONORTE
Versin: Tensin Nom.: 60 8x1.25%/22.9/10 kV Diag.Unif.N:
Tecnologa: NUMRICA Uprim[kV]: 60 Man.Serv.N:
Ao instal.: Fases: RST-N Fecha: 11-feb-14
Cdigo: Ucc [V]: Respons.:
N Serie: Uca [V]: 100 Revisin: 0
Ubic.Tabl: Ica [A]: 1
Sistema: SECUNDARIO Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES GRUPO 1 GRUPO 1 OBSERVACIONES
(AS BUILT) ECP 2010
3 COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

DATOS GENERALES
DATOS DEL TRANSFORMADOR TRANSFORMADORES DE CORRIENTE

VALORES DE AJUSTE
50/51 CURRENT PROTECCION 1 SECONDARY SYSTEM SUPERVISION

DATOS GENERALES
DATOS DEL TRANSFORMADOR
Generales
Tipo (Transformador-Autotransformador) - Transformador
Arrollamiento primario
Tensin nominal primaria entre fases kV 60
Tensin mxima de servicio entre fases kV
Potencia aparente nominal MVA 30
Sobrecarga permanente %
Corriente nominal A 288.68
Corriente de inrush primaria Acr
Arrollamiento secundario
Tensin nominal primaria entre fases kV 22.9
Tensin mxima de servicio entre fases kV
Potencia aparente nominal MVA 16
Corriente nominal A 403.39
Arrollamiento terciario
Tensin nominal primaria entre fases kV 10
Tensin mxima de servicio entre fases kV
Potencia aparente nominal MVA 20
Corriente nominal A 1154.70
Grupos de conexin
Grupo de conexin primario-secundario - YNyn0
Grupo de conexin primario-terciario - YNd5
Grupo de conexin secundario-terciario - ynd5
Regulador bajo carga
Ubicado en arrollamiento: - Primario
Rango de regulacin % 8x1.25
Relaciones de cortocircuito
Potencia base MVA 30
Primario-Secundario secuencia positiva % 6.76
Primario-Terciario secuencia positiva % 5
Secundario-Terciario secuencia positiva % 2.28
Primario-Secundario secuencia cero % 6.76
Primario-Terciario secuencia cero % 5

SE_ChiclOest_TR3_REC670_2014 1 de 7 12/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: SOBRECORRIENTE Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: ABB Cd.Transf.: TR3 Depto: LAMBAYEQUE
Modelo: REC670 Potencia: 30 / 16 / 20 MVA Empresa: ELECTRONORTE
Versin: Tensin Nom.: 60 8x1.25%/22.9/10 kV Diag.Unif.N:
Tecnologa: NUMRICA Uprim[kV]: 60 Man.Serv.N:
Ao instal.: Fases: RST-N Fecha: 11-feb-14
Cdigo: Ucc [V]: Respons.:
N Serie: Uca [V]: 100 Revisin: 0
Ubic.Tabl: Ica [A]: 1
Sistema: SECUNDARIO Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES GRUPO 1 GRUPO 1 OBSERVACIONES
(AS BUILT) ECP 2010
3 COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

Secundario-Terciario secuencia cero % 2.28


TRANSFORMADORES DE CORRIENTE PRIMARIO
Marca - -
Tipo - -
Modelo - -
Cantidad de ncleos - -
Corriente nominal A - 5 400
Relacin de transformacin - - 80.00
Clase - -
Prestacin VA -
VALORES DE AJUSTE
50/51 CURRENT PROTECCION Disp.s/interr.:
Campo Funcional
DFT
6701 MeasType - DFT -
RMS
Basic param. for the TOC1-
ON
6801 Operation - ON -
OFF
6802 I BASE A 1 99999 1 400 -
6803 UBASE KV 0.05 2000.00 0.05 60 -
6804 AngleRCA 40 65 1 55 -
6805 AngleROA 40 89 1 80 -
Not in use
1out of 3
6806 StartPhSel - 1out of 3 -
2 out of 3
3 out of 3
OFF
Non-Dir
6807 DirMode1 - Non-Dir -
Forward
Reverse
ANSI e IEC(ext;very;norm)inv.
ANSI Normal
6808 Characterist1 - ANSI e IEC(Def.Time) -
Inverse
IEC inv.

6809 I1> %IB 1 2500 1 94 376.00

6810 t1 s 0.000 60.000 0.001 0.000 -

6811 K1 - 0.05 999.00 0.01 0.15 -

6812 t1Min - 0.000 60.000 0.001 0.000 -

6813 I1Mult - 1.0 10.0 0.1 1.0 -

SE_ChiclOest_TR3_REC670_2014 2 de 7 12/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: SOBRECORRIENTE Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: ABB Cd.Transf.: TR3 Depto: LAMBAYEQUE
Modelo: REC670 Potencia: 30 / 16 / 20 MVA Empresa: ELECTRONORTE
Versin: Tensin Nom.: 60 8x1.25%/22.9/10 kV Diag.Unif.N:
Tecnologa: NUMRICA Uprim[kV]: 60 Man.Serv.N:
Ao instal.: Fases: RST-N Fecha: 11-feb-14
Cdigo: Ucc [V]: Respons.:
N Serie: Uca [V]: 100 Revisin: 0
Ubic.Tabl: Ica [A]: 1
Sistema: SECUNDARIO Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES GRUPO 1 GRUPO 1 OBSERVACIONES
(AS BUILT) ECP 2010
3 COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

OFF
Non-Dir
6814 DirMode2 - Non-Dir -
Forward
Reverse
ANSI e IEC(ext;very;norm)inv.
6815 Characterist2 - ANSI e IEC(Def.Time) Definite time -
IEC inv.

6816 I2> %IB 1 2500 1 910 3640.00

6817 t2 s 0.000 60.000 0.001 0.100 -

6818 K2 - 0.05 999.00 0.01 0.05 -

6820 I2Mult - 1.0 10.0 0.1 1.0 -

6821 t2Min - 0.000 60.000 0.001 0.000 -


Advan.param.for the TOC1-
6901 IMinOpPhSel %IB 1 100 1 7 -
6902 2ndHarmStab %IB 5 100 1 20 -
Instantaneous
6903 ResetTypeCrv1 IEC Reset Instantaneous -
ANSI reset
6904 tReset1 s 0.000 60.000 0.001 0.020 -
6905 tPCrv1 - 0.005 3.000 0.001 1.000 -
6906 tACrv1 - 0.005 200.000 0.001 13.500 -
6907 tBCrv1 - 0.000 20.000 0.010 0.000 -
6908 tCCrv1 - 0.100 10.000 0.100 1.000 -
6909 tPRCrv1 - 0.005 3.000 0.001 0.500 -
6910 tTRCrv1 - 0.005 100.000 0.001 13.500 -
6911 tCRCrv1 - 0.100 10.000 0.100 1.000 -
6912 HarmRestrain1 - ON - OFF OFF -
Instantaneous
6913 ResetTypeCrv2 - IEC Reset Instantaneous -
ANSI reset
6914 tReset2 s 0.000 60.000 0.001 0.020 -
6915 tPCrv2 - 0.005 3.000 0.001 1.000 -
6916 tACrv2 - 0.005 200.000 0.001 13.500 -

SE_ChiclOest_TR3_REC670_2014 3 de 7 12/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: SOBRECORRIENTE Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: ABB Cd.Transf.: TR3 Depto: LAMBAYEQUE
Modelo: REC670 Potencia: 30 / 16 / 20 MVA Empresa: ELECTRONORTE
Versin: Tensin Nom.: 60 8x1.25%/22.9/10 kV Diag.Unif.N:
Tecnologa: NUMRICA Uprim[kV]: 60 Man.Serv.N:
Ao instal.: Fases: RST-N Fecha: 11-feb-14
Cdigo: Ucc [V]: Respons.:
N Serie: Uca [V]: 100 Revisin: 0
Ubic.Tabl: Ica [A]: 1
Sistema: SECUNDARIO Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES GRUPO 1 GRUPO 1 OBSERVACIONES
(AS BUILT) ECP 2010
3 COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

6917 tBCrv2 - 0.000 20.000 0.010 0.000 -


6918 tCCrv2 - 0.100 10.000 0.100 1.000 -
6919 tPRCrv2 - 0.005 3.000 0.001 0.500 -
6920 tTRCrv2 - 0.005 100.000 0.001 13.500 -
6921 tCRCrv2 - 0.100 10.000 0.100 1.000 -
6922 HarmRestrain2 - ON - OFF OFF -
Instantaneous
6923 ResetTypeCrv3 - IEC Reset - -
ANSI reset
6924 tReset3 s 0.000 60.000 0.001 - -
6932 HarmRestrain3 - ON - OFF OFF -
Instantaneous
6933 ResetTypeCrv4 - IEC Reset - -
ANSI reset
6934 tReset4 s 0.000 60.000 0.001 - -
Basic param.for the TEF1-
ON
7801 Operation - ON -
OFF
7802 I BASE A 1 99999 1 400 -
7803 UBASE KV 0.05 2000.00 0.05 60.00 -
7804 AngleRCA -180 180 1 65 -
Voltage
7805 polMethod - Current Voltage -
Dual
7806 UPolMin %UB 1 100 1 1 -
7807 IPolMin %IB 2 100 1 5 -
7808 RNPol ohm 0.50 1000.00 0.01 5.00 -
7809 XNPol ohm 0.50 3000.00 0.01 40.00 -
7810 IN>Dir %IB 1 100 1 10 -
7811 2ndHarmStab % 5 100 1 20 -
ON
7812 BlkParTransf - OFF -
OFF
7813 UseStartValue - IN1> : IN2> : IN3> : IN4> IN4> -
OFF;SOTF;UnderTime;SOTF+UnderTi
7814 SOTF - OFF -
me
7815 ActivationSOTF - Open; Closed; ClosedCommand OPEN -
7816 StepForSOTF - Step 2; Step 3 Step 2 -

SE_ChiclOest_TR3_REC670_2014 4 de 7 12/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: SOBRECORRIENTE Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: ABB Cd.Transf.: TR3 Depto: LAMBAYEQUE
Modelo: REC670 Potencia: 30 / 16 / 20 MVA Empresa: ELECTRONORTE
Versin: Tensin Nom.: 60 8x1.25%/22.9/10 kV Diag.Unif.N:
Tecnologa: NUMRICA Uprim[kV]: 60 Man.Serv.N:
Ao instal.: Fases: RST-N Fecha: 11-feb-14
Cdigo: Ucc [V]: Respons.:
N Serie: Uca [V]: 100 Revisin: 0
Ubic.Tabl: Ica [A]: 1
Sistema: SECUNDARIO Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES GRUPO 1 GRUPO 1 OBSERVACIONES
(AS BUILT) ECP 2010
3 COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

7817 HarmResSOTF - ON OFF OFF -


7818 Tsotf s 0.000 60.000 0.001 0.2 -
7819 t4U s 0.000 60.000 0.001 1 -
OFF
Non-Dir
7820 DirMode - Non-Dir -
Forward
Reverse
ANSI e IEC(ext;very;norm)inv.
7821 Characterist1 - ANSI e IEC(Def.Time) ANSI Def Time -
IEC inv.

7822 IN1> %IB 1 2500 1 29 116.00

7823 t1 s 0.000 60.000 0.001 0.160 -

7824 K1 - 0.05 999.00 0.01 0.05 -

7825 IN1Mult - 1.0 10.0 0.1 1.0 -

7826 t1Min - 0.000 60.000 0.001 0.000 -


ON
7827 HarmRestrain1 - ON -
OFF
OFF
Non-Dir
7828 DirMode 2 - Non-Dir -
Forward
Reverse
ANSI e IEC(ext;very;norm)inv.
7829 Characterist2 - ANSI e IEC(Def.Time) ANSI Def Time -
IEC inv.

7830 IN2> %IB 1 2500 1 578 2312.00

7831 t2 s 0.000 60.000 0.001 0.100 -

7832 K2 - 0.05 999.00 0.01 0.05 -

7833 IN2Mult - 1.0 10.0 0.1 1.0 -

7834 t2Min - 0.000 60.000 0.001 0.000 -

SE_ChiclOest_TR3_REC670_2014 5 de 7 12/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: SOBRECORRIENTE Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: ABB Cd.Transf.: TR3 Depto: LAMBAYEQUE
Modelo: REC670 Potencia: 30 / 16 / 20 MVA Empresa: ELECTRONORTE
Versin: Tensin Nom.: 60 8x1.25%/22.9/10 kV Diag.Unif.N:
Tecnologa: NUMRICA Uprim[kV]: 60 Man.Serv.N:
Ao instal.: Fases: RST-N Fecha: 11-feb-14
Cdigo: Ucc [V]: Respons.:
N Serie: Uca [V]: 100 Revisin: 0
Ubic.Tabl: Ica [A]: 1
Sistema: SECUNDARIO Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES GRUPO 1 GRUPO 1 OBSERVACIONES
(AS BUILT) ECP 2010
3 COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

ON
7835 HarmRestrain2 - ON -
OFF
OFF
Non-Dir
7836 DirMode 3 - Non-Dir -
Forward
Reverse
Advan param.for the TEF1-
7901 ActUnderTime - CB position ; CB command CB position -
7902 tUnderTime s 0.000 60.000 0.001 0.3 -
Instantaneous
7903 ResetTypeCrv1 IEC Reset Instantaneous -
ANSI reset
7904 tReset1 s 0.000 60.000 0.001 0.020 -
7905 tPCrv1 - 0.005 3.000 0.001 1.000 -
7906 tACrv1 - 0.005 200.000 0.001 13.500 -
7907 tBCrv1 - 0.000 20.000 0.010 0.000 -
7908 tCCrv1 - 0.100 10.000 0.100 1.000 -
7909 tPRCrv1 - 0.005 3.000 0.001 0.500 -
7910 tTRCrv1 - 0.005 100.000 0.001 13.500 -
7911 tCRCrv1 - 0.100 10.000 0.100 1.000 -
Instantaneous
7912 ResetTypeCrv2 - IEC Reset Instantaneous -
ANSI reset
7913 tReset2 s 0.000 60.000 0.001 0.020 -
7914 tPCrv2 - 0.005 3.000 0.001 1.000 -
7915 tACrv2 - 0.005 200.000 0.001 13.500 -
7916 tBCrv2 - 0.000 20.000 0.010 0.000 -
7917 tCCrv2 - 0.100 10.000 0.100 1.000 -
7918 tPRCrv2 - 0.005 3.000 0.001 0.500 -
7919 tTRCrv2 - 0.005 100.000 0.001 13.500 -
7920 tCRCrv2 - 0.100 10.000 0.100 1.000 -
Instantaneous
7921 ResetTypeCrv3 - IEC Reset Instantaneous -
ANSI reset
7922 tReset3 s 0.000 60.000 0.001 0.020 -
7923 tPCrv3 - 0.005 3.000 0.001 1.000 -
7924 tACrv3 - 0.005 200.000 0.001 13.500 -

SE_ChiclOest_TR3_REC670_2014 6 de 7 12/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: SOBRECORRIENTE Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: ABB Cd.Transf.: TR3 Depto: LAMBAYEQUE
Modelo: REC670 Potencia: 30 / 16 / 20 MVA Empresa: ELECTRONORTE
Versin: Tensin Nom.: 60 8x1.25%/22.9/10 kV Diag.Unif.N:
Tecnologa: NUMRICA Uprim[kV]: 60 Man.Serv.N:
Ao instal.: Fases: RST-N Fecha: 11-feb-14
Cdigo: Ucc [V]: Respons.:
N Serie: Uca [V]: 100 Revisin: 0
Ubic.Tabl: Ica [A]: 1
Sistema: SECUNDARIO Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES GRUPO 1 GRUPO 1 OBSERVACIONES
(AS BUILT) ECP 2010
3 COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

7925 tBCrv3 - 0.000 20.000 0.010 0.000 -


7926 tCCrv3 - 0.100 10.000 0.100 1.000 -
7927 tPRCrv3 - 0.005 3.000 0.001 0.500 -
7928 tTRCrv3 - 0.005 100.000 0.001 13.500 -
7929 tCRCrv3 - 0.100 10.000 0.100 1.000 -
59/27 VOLTAGE PROTECTION
27 Undervoltage 2 Step (PTUV, 27)
TUV1
Basic Gen.for the TUV1-
PhG DFT; PhPh RMS; PhG RMS; PhG
ConnType ConnType - PhN DFT -
DFT
Basic param.for the TUV1-
Operat Operation - On - Off OFF -
59 Overvoltage 2 Step (PTOV, 59)
TOV1
Basic Gen.for the TOV1-
PhG DFT; PhPh RMS; PhG RMS; PhG
ConnType ConnType - PhN DFT -
DFT
Basic param.for the TOV1-
Operation Operation - On - Off OFF -
SECONDARY SYSTEM SUPERVISION Disp.s/interr.:
Fuse Failure Supervision
Bas.para.gr.set.for the FSD1-
ON
Operation - OFF -
OFF

SE_ChiclOest_TR3_REC670_2014 7 de 7 12/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: SOBRECORRIENTE Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: SIEMENS Alimentador: A-223 y C-224 Depto: LAMBAYEQUE
Modelo: 7SJ64 Potencia: Empresa: ELECTRONORTE
Versin: Uprim[kV]: 22.9 kV Man.Serv.N:
N Serie: Diag.Unif.N: Fecha:
Tecnologa: NUMRICA Fases: RST-N Respons.: 11-feb-14
Ao instal.: Ucc [V]: Revisin:
Cdigo: Uca [V]: 100 0
Ubic.Tabl: Ica [A]: 1
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES GRUPO 1 GRUPO 1 OBSERVACIONES
COES ECP 2010
3 COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

DATOS GENERALES
DATOS DEL TRANSFORMADOR TRANSFORMADORES DE CORRIENTE

VALORES DE AJUSTE
50/51 DEVICE CONFIGURATION 1 POWER SYSTEM DATA 1
2 POWER SYSTEM DATA 2 50/51 PHASE/GROUND OVERCURRENT
50/51 COLD LOAD PICKUP 46 NEGATIVE SEQUENCE (TIME OVERCURRENT)
49 49 THERMAL OVERLOAD @ MEASUREMENT SUPERVISION
74TC 74TC TRIP CIRCUIT SUPERVISION 64 64, 50Ns, 51Ns, 67Ns
50BF BREAKER FAILURE 50 50 1Ph

DATOS GENERALES
TRANSFORMADORES DE CORRIENTE
Marca - -
Tipo -
Modelo - -
Cantidad de ncleos - - 3
Corriente nominal A - 5 500
Relacin de transformacin - - 100.00
Clase - - 0.2-5P20-5P20
Prestacin VA - 30-30-30
VALORES DE AJUSTE
50/51 DEVICE CONFIGURATION Disp.s/interr.:
Campo Funcional
Disabled
103 Setting Group Change Option - Disabled -
Enabled
Disabled
104 Oscillographic Fault Records - Enabled -
Enabled
Disabled
Definite Time Only
TOC IEC
112 50/51 - TOC IEC -
TOC ANSI
User Defined Pickup Curve
User Defined Pickup & Reset Curve
Disabled
Definite Time Only
TOC IEC
113 50N/51N - TOC IEC -
TOC ANSI
User Defined Pickup Curve
User Defined Pickup & Reset Curve

SE_ChiclOest_Alim22.9_7SJ64 1 de 8 12/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: SOBRECORRIENTE Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: SIEMENS Alimentador: A-223 y C-224 Depto: LAMBAYEQUE
Modelo: 7SJ64 Potencia: Empresa: ELECTRONORTE
Versin: Uprim[kV]: 22.9 kV Man.Serv.N:
N Serie: Diag.Unif.N: Fecha:
Tecnologa: NUMRICA Fases: RST-N Respons.: 11-feb-14
Ao instal.: Ucc [V]: Revisin:
Cdigo: Uca [V]: 100 0
Ubic.Tabl: Ica [A]: 1
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES GRUPO 1 GRUPO 1 OBSERVACIONES
COES ECP 2010
3 COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

Disabled
Definite Time
TOC IEC
115 67 - Disabled -
TOC ANSI
User Defined PU
User Defined Reset
Disabled
Definite Time
TOC IEC
116 67N - Disabled -
TOC ANSI
User Defined PU
User Defined Reset
Disabled
117 Cold Load Pickup - Disabled -
Enabled
Disabled
122 2nd Harmonic Inrush Restraint - Disabled -
Enabled
Disabled
127 50 1Ph - Disabled -
Enabled
cos / sin
130 (sens.) Earth fault dir. characteristic - cos / sin -
V0/I0 mea.
Disabled
Definite Time Only
131 (sensitive) Ground fault - Disabled -
User Defined Pickup Curve
Logarithmic inverse
Disabled
TOC IEC
140 46 Negative Sequence Protection - Disabled -
TOC ANSI
Definite Time
Disabled
142 49 Thermal Overload Protection - Without ambient TC Disabled -
With ambient TC
Disabled
150 Under / Overvoltage Protection - Disabled -
Enabled
Disabled
154 Over / Underfrequency Protection - Disabled -
Enabled
Disabled
161 SYNC Function group 1 - ASYN/SYNCHRON Disabled -
SYNCHROCHECK
Disabled
162 SYNC Function group 2 - ASYN/SYNCHRON Disabled -
SYNCHROCHECK

SE_ChiclOest_Alim22.9_7SJ64 2 de 8 12/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: SOBRECORRIENTE Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: SIEMENS Alimentador: A-223 y C-224 Depto: LAMBAYEQUE
Modelo: 7SJ64 Potencia: Empresa: ELECTRONORTE
Versin: Uprim[kV]: 22.9 kV Man.Serv.N:
N Serie: Diag.Unif.N: Fecha:
Tecnologa: NUMRICA Fases: RST-N Respons.: 11-feb-14
Ao instal.: Ucc [V]: Revisin:
Cdigo: Uca [V]: 100 0
Ubic.Tabl: Ica [A]: 1
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES GRUPO 1 GRUPO 1 OBSERVACIONES
COES ECP 2010
3 COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

Disabled
163 SYNC Function group 3 - ASYN/SYNCHRON Disabled -
SYNCHROCHECK
Disabled
164 SYNC Function group 4 - ASYN/SYNCHRON Disabled -
SYNCHROCHECK
Disabled
170 50BF Breaker Failure Protection - Disabled -
Enabled
Disabled
171 Auto-Reclose Function - - -
Enabled
Disabled
172 52 Breaker Wear Monitoring - Ix-Method Disabled -
2P-Method
Disabled
182 74TC Trip Circuit Supervision - with 2 Binary Inputs Disabled -
with 1 Binary Input
Disabled
190 External Temperature Input - Disabled -
Port C
6 RTD simplex operation
6 RTD simplex
191 Ext. Temperature Input Connection Type - 6 RTD half duplex operation -
operation
12 RTD half duplex operation
1 POWER SYSTEM DATA 1
Power System
214 Rated Frequency Hz 50 - 60 60 -
ABC
209 Phase Sequence - ABC -
ACB
Degree Celsius
276 Unit of temperature measurement - Degree Celsius -
Degree Fahrenheit
Towards Line
201 CT Starpoint - Towards Line -
Towards Busbar
NO
280 Holmgreen-conn. (for fast sum-i-monit.) - NO -
YES
A, B, C, (Gnd)
251A CT Connection - A,G2,C,G; G->B A, B, C, (Gnd) -
A,G2,C,G; G2->B
Van, Vbn, Vcn
Vab, Vbc, VGnd
Vab, Vbc, Vx
213 VT Connect. 3ph - Van, Vbn, Vcn -
Van,Vbn,Vcn,VGn
Van,Vbn,Vcn,VSy
Van,Vbn,Vcn,Vx

SE_ChiclOest_Alim22.9_7SJ64 3 de 8 12/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: SOBRECORRIENTE Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: SIEMENS Alimentador: A-223 y C-224 Depto: LAMBAYEQUE
Modelo: 7SJ64 Potencia: Empresa: ELECTRONORTE
Versin: Uprim[kV]: 22.9 kV Man.Serv.N:
N Serie: Diag.Unif.N: Fecha:
Tecnologa: NUMRICA Fases: RST-N Respons.: 11-feb-14
Ao instal.: Ucc [V]: Revisin:
Cdigo: Uca [V]: 100 0
Ubic.Tabl: Ica [A]: 1
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES GRUPO 1 GRUPO 1 OBSERVACIONES
COES ECP 2010
3 COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

NO, Van, Vbn, Vcn,


240 VT Connect. 1ph - NO -
Vab, Vbc,,Vca
NO
235 A Storage of th. Replicas w/o Power Supply - NO -
YES
OFF
250 A 50, 51 Time Overcurrent with 2ph. prot. - OFF -
ON
Ignd (measured)
613A (I) DMT Earth Overcurrent with - 3I0 (calcul.) -
3I0 (calcul.)
Vphph
Vph-n
614A Operating Quantity for Overvolt. Prot. - Vphph -
V1
V2
V1
615A Operating Quantity for Undervolt. Prot. - Vphph V1 -
Vph-n
CT's
204 CT Rated Primary Current A 10 50000 1 500 -

205 CT Rated Secondary Current A 1-5 5 -

217 Ignd-CT rated primary current - 1 50000 1 1 -

218 Ignd-CT rated secondary current - 1-5 1 -


VT's
202 Rated Primary Voltage KV 0.10 800 0.01 22.9 -

203 Rated Secondary Voltage (L-L) V 100 225 1 100 -

206A Matching ratio Phase-VT To Open-Delta-VT - 0.10 3.00 0.01 1.73 -


Breaker
210 A Minimum TRIP Command Duration s 0.01 32.00 0.01 0.15 -

211 A Maximum Close Command Duration s 0.01 32.00 0.01 1.00 -

212 Closed Breaker Min. Current Threshold A 0.04 1.00 0.01 0.04 4.00

260 Rated Normal Current (52 Breaker) A-prim 10 50000 1 - -

264 Exponent for the Ix-Method - 1.0 3.0 0.1 - -

SE_ChiclOest_Alim22.9_7SJ64 4 de 8 12/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: SOBRECORRIENTE Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: SIEMENS Alimentador: A-223 y C-224 Depto: LAMBAYEQUE
Modelo: 7SJ64 Potencia: Empresa: ELECTRONORTE
Versin: Uprim[kV]: 22.9 kV Man.Serv.N:
N Serie: Diag.Unif.N: Fecha:
Tecnologa: NUMRICA Fases: RST-N Respons.: 11-feb-14
Ao instal.: Ucc [V]: Revisin:
Cdigo: Uca [V]: 100 0
Ubic.Tabl: Ica [A]: 1
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES GRUPO 1 GRUPO 1 OBSERVACIONES
COES ECP 2010
3 COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

<none>
52 Breaker
Disc. Swit.
265 52 B.Wear: Open Cmd. via Control Device - Fan ON/OFF - -
GndSwit
Q2 Op/Cl
Q9 Op/Cl
266 Breaktime (52 Breaker) ms 1 600 1 - -

267 Opening Time (52 Breaker) ms 1 500 1 - -


2 POWER SYSTEM DATA 2
1101 Measurem:FullScaleVoltage (Equipm.rating) KV-prim 0.10 800 0.01 60 -

1102 Measurem:FullScaleCurrent(Equipm.rating) A-prim 10 50000 1 403 -

1107 Motor Start Current (BLK OVL,Start Mon.) A 0.40 10.00 0.01 2.5 -
not reversed
1108 P,Q operational measured values sign not reversed -
reversed
50/51 PHASE/GROUND OVERCURRENT
General
1201 50, 51 Phase Time Overcurrent - ON - OFF ON -
I>> Instantaneously
I> Instantaneously I>>
1213 A Manual Close Mode - -
Ip Instantaneously Instantaneously
Inactive
1215 A 50 Drop-Out Time Delay s 0.00 60.00 0.01 0.00 -
1301 50N, 51N Ground Time Overcurrent - ON - OFF ON -
IE>> Instantaneously
IE> Instantaneously IE>>
1313 A Manual Close Mode - -
IEp Instantaneously Instantaneously
Inactive
1315 A 50N Drop-Out Time Delay s 0.00 60.00 0.01 0 -
2201 Inrush Restraint - ON - OFF - -
50 - PHASE OVERCURRENT
Fundamental
1219A I>>> measurement - True RMS True RMS -
Instantaneous

Always
1216A I>>> active - Always -
with 79 active

SE_ChiclOest_Alim22.9_7SJ64 5 de 8 12/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: SOBRECORRIENTE Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: SIEMENS Alimentador: A-223 y C-224 Depto: LAMBAYEQUE
Modelo: 7SJ64 Potencia: Empresa: ELECTRONORTE
Versin: Uprim[kV]: 22.9 kV Man.Serv.N:
N Serie: Diag.Unif.N: Fecha:
Tecnologa: NUMRICA Fases: RST-N Respons.: 11-feb-14
Ao instal.: Ucc [V]: Revisin:
Cdigo: Uca [V]: 100 0
Ubic.Tabl: Ica [A]: 1
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES GRUPO 1 GRUPO 1 OBSERVACIONES
COES ECP 2010
3 COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

1217 I>>> Pickup A 1 a 35 (paso: 0.01) - infinito infinito -


1218 T I>>> Time Delay s 0 a 60 (paso: 0.01) - infinito 0 -
Fundamental
1220A I>> measurement - True RMS True RMS -

Always
1214 A I>> active - Always -
with 79 active
1202 I>> Pickup A 0.10 35; infinito 0.01 40 4000.00
1203 T I>> Time Delay s 0 a 60 (paso: 0.01) - infinito 0 -
Fundamental
1221A I> measurement - True RMS Fundamental -

1204 I> Pickup A 0.10 35;infinito 0.01 0 0.00


1205 T I> Time Delay s 0 a 60 (paso: 0.01) - infinito 0 -
51- PHASE OVERCURRENT
Fundamental
1222A Ip measurement - True RMS True RMS -

1207 Ip Pickup A 0.10 4.00 0.01 6 600.00


1208 T Ip Time Dial - IEC s 0.05 a 3.20 (paso: 0.01) ; infinito 0.08 -
1209 51 Time Dial - ANSI s 0.5 a 15 (paso: 0.01); infinito - -
1210 Drop-out characteristic Instantaneous / Disk Emulation Disk -

NORMAL INVERSE - VERY INVERSE -


1211 IEC Curve - EXTREMELY INVERSE - LONG INVERSE
NORMAL INVERSE -

INVERSE - SHORT INVERSE - LONG


INVERSE - MODERATELY INVERSE -
1212 ANSI Curve - VERY INVERSE - EXTREMELY INVERSE -
- -
DEFINITE INVERSE

NO
Volt. controll.
1223 Voltage Influence - - -
Volt. restraint

1224 U< Threshold for Release Ip - 10.0 125.0 0.10 - -


50N - GROUND OVERCURRENT
Fundamental
1319A IE>>> measurement - True RMS True RMS -
Instantaneous

Always
1316A IE>>> active - Always -
with 79 active
1317 IE>>> Pickup A 0.25 a 35 (paso: 0.01) - infinito infinito -
1318 T IE>>> Time Delay s 0 a 60 (paso: 0.01) - infinito 0 -

SE_ChiclOest_Alim22.9_7SJ64 6 de 8 12/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: SOBRECORRIENTE Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: SIEMENS Alimentador: A-223 y C-224 Depto: LAMBAYEQUE
Modelo: 7SJ64 Potencia: Empresa: ELECTRONORTE
Versin: Uprim[kV]: 22.9 kV Man.Serv.N:
N Serie: Diag.Unif.N: Fecha:
Tecnologa: NUMRICA Fases: RST-N Respons.: 11-feb-14
Ao instal.: Ucc [V]: Revisin:
Cdigo: Uca [V]: 100 0
Ubic.Tabl: Ica [A]: 1
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES GRUPO 1 GRUPO 1 OBSERVACIONES
COES ECP 2010
3 COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO
Fundamental
1320A IE>> measurement - True RMS True RMS -

Always
1314 A IE>> active - Always -
with 79 active
1302 IE>> Pickup A 0.05 35;infinito 0.01 20 2000.00
1303 T IE>> Time Delay s 0 a 60 (paso: 0.01) - infinito 0 -
Fundamental
1321 A IE> measurement - True RMS True RMS -

1304 IE> Pickup A 0.05 35;infinito 0.01 0 0.00


1305 T IE> Time Delay s 0 a 60 (paso: 0.01) - infinito 0 -
51N - GROUND OVERCURRENT
Fundamental
1322 A IEp> measurement - True RMS True RMS -

1307 51N Pickup A 0.05 4.00 0.01 1.6 160.00


1308 51N Time Dial - IEC s 0.05 a 3.20 (paso: 0.01) ; infinito 0.07 -
1309 51N Time Dial - ANSI s 0.5 a 15 (paso: 0.01); infinito - -
1310 Drop-out characteristic Instantaneous / Disk Emulation Disk -
NORMAL INVERSE - VERY INVERSE -
1311 IEC Curve - EXTREMELY INVERSE - LONG INVERSE
NORMAL INVERSE -

INVERSE - SHORT INVERSE - LONG


INVERSE - MODERATELY INVERSE -
1312 ANSI Curve - VERY INVERSE - EXTREMELY INVERSE -
- -
DEFINITE INVERSE

INRUSH RESTRAINT
2202 2nd harmonic in % of fundamental % 10 45 1 - -
2203 Cross Block - NO - YES - -
2204 Cross Block Time s 0.00 180.00 0.01 - -
2205 Maximum Current for Inrush Restraint A 1.50 125.00 0.01 - #VALOR!
67/67N PHASE/GROUND OVERCURRENT
General
1501 67, 67-TOC Phase Time Overcurrent - ON - OFF OFF -
50/51 COLD LOAD PICKUP
General
1701 Cold-Load-Pickup Function - ON - OFF OFF -
46 NEGATIVE SEQUENCE (TIME OVERCURRENT)
General
4001 46 Negative Sequence Protection - ON - OFF OFF
49 49 THERMAL OVERLOAD
General
4201 49 Thermal Overload Protection - ON - OFF - Only Alarm OFF
59/27 Over / Under Voltage

SE_ChiclOest_Alim22.9_7SJ64 7 de 8 12/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: SOBRECORRIENTE Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: SIEMENS Alimentador: A-223 y C-224 Depto: LAMBAYEQUE
Modelo: 7SJ64 Potencia: Empresa: ELECTRONORTE
Versin: Uprim[kV]: 22.9 kV Man.Serv.N:
N Serie: Diag.Unif.N: Fecha:
Tecnologa: NUMRICA Fases: RST-N Respons.: 11-feb-14
Ao instal.: Ucc [V]: Revisin:
Cdigo: Uca [V]: 100 0
Ubic.Tabl: Ica [A]: 1
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES GRUPO 1 GRUPO 1 OBSERVACIONES
COES ECP 2010
3 COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

General
5101 Undervoltage Protection - OFF - ON - Alarm Only OFF -
5001 Overvoltage Protection - OFF - ON - Alarm Only OFF -
MEASUREMENT SUPERVISION
General
5301 Fuse Fail Monitor - ON - OFF OFF
74TC TRIP CIRCUIT SUPERVISION
8201 74TC Trip Circuit Supervision - ON - OFF OFF
64, 50Ns, 51Ns, 67Ns (Sensitive) GROUND FAULT
General
3101 (sensitive) Ground fault - ON - OFF OFF
50BF BREAKER FAILURE
General
7001 50BF Breaker Failure Protection - OFF - ON OFF -
50 BF
7004 Check Breaker Contacts ON - OFF OFF -
7005 TRIP - Timer s 0.06 a 60 (paso: 0.01) - infinito 0.25 -
7006 Pick-up threshold I> A 0.03 a 20 (paso: 0.01) 0.10 -
7008 TRIP-Timer 2 s 0.06 a 60 (paso: 0.01)-infinito - -
50 1Ph 50 1Ph
General
2701 50 1Ph - OFF - ON OFF -
50 BF
2702 50 1Ph-2 PICKUP A 0.050 35, infinito 0.010 infinito -
2703 50 1Ph-2 Pickup A 0.003 1.5, infinito 0.001 - -
2704 50 1Ph-2 Time Delay s 0.00 60, infinito 0.01 infinito -
2705 50 1Ph-1 PICKUP A 0.050 35, infinito 0.010 infinito -
2706 50 1Ph-1 Pickup A 0.003 1.5, infinito 0.001 - -
2707 50 1Ph-1 Time Delay s 0.0 60, infinito 0.01 infinito -

SE_ChiclOest_Alim22.9_7SJ64 8 de 8 12/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: SOBRECORRIENTE Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: SIEMENS Alimentador: C-213 y C-218 Depto: LAMBAYEQUE
Modelo: 7SJ64 Potencia: Empresa: ELECTRONORTE
Versin: Uprim[kV]: 10 kV Man.Serv.N:
N Serie: Diag.Unif.N: Fecha:
Tecnologa: NUMRICA Fases: RST-N Respons.: 11-feb-14
Ao instal.: Ucc [V]: Revisin:
Cdigo: Uca [V]: 100 0
Ubic.Tabl: Ica [A]: 1
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES GRUPO 1 GRUPO 1 OBSERVACIONES
COES ECP 2010
3 COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

DATOS GENERALES
DATOS DEL TRANSFORMADOR TRANSFORMADORES DE CORRIENTE

VALORES DE AJUSTE
50/51 DEVICE CONFIGURATION 1 POWER SYSTEM DATA 1
2 POWER SYSTEM DATA 2 50/51 PHASE/GROUND OVERCURRENT
50/51 COLD LOAD PICKUP 46 NEGATIVE SEQUENCE (TIME OVERCURRENT)
49 49 THERMAL OVERLOAD @ MEASUREMENT SUPERVISION
74TC 74TC TRIP CIRCUIT SUPERVISION 64 64, 50Ns, 51Ns, 67Ns
50BF BREAKER FAILURE 50 50 1Ph

DATOS GENERALES
TRANSFORMADORES DE CORRIENTE
Marca - -
Tipo -
Modelo - -
Cantidad de ncleos - - 3
Corriente nominal A - 5 500
Relacin de transformacin - - 100.00
Clase - - 0.2-5P20-5P20
Prestacin VA - 30-30-30
VALORES DE AJUSTE
50/51 DEVICE CONFIGURATION Disp.s/interr.:
Campo Funcional
Disabled
103 Setting Group Change Option - Disabled -
Enabled
Disabled
104 Oscillographic Fault Records - Enabled -
Enabled
Disabled
Definite Time Only
TOC IEC
112 50/51 - TOC IEC -
TOC ANSI
User Defined Pickup Curve
User Defined Pickup & Reset Curve
Disabled
Definite Time Only
TOC IEC
113 50N/51N - TOC IEC -
TOC ANSI
User Defined Pickup Curve
User Defined Pickup & Reset Curve

SE_ChiclOest_Alim10_7SJ64 1 de 8 12/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: SOBRECORRIENTE Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: SIEMENS Alimentador: C-213 y C-218 Depto: LAMBAYEQUE
Modelo: 7SJ64 Potencia: Empresa: ELECTRONORTE
Versin: Uprim[kV]: 10 kV Man.Serv.N:
N Serie: Diag.Unif.N: Fecha:
Tecnologa: NUMRICA Fases: RST-N Respons.: 11-feb-14
Ao instal.: Ucc [V]: Revisin:
Cdigo: Uca [V]: 100 0
Ubic.Tabl: Ica [A]: 1
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES GRUPO 1 GRUPO 1 OBSERVACIONES
COES ECP 2010
3 COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

Disabled
Definite Time
TOC IEC
115 67 - Disabled -
TOC ANSI
User Defined PU
User Defined Reset
Disabled
Definite Time
TOC IEC
116 67N - Disabled -
TOC ANSI
User Defined PU
User Defined Reset
Disabled
117 Cold Load Pickup - Disabled -
Enabled
Disabled
122 2nd Harmonic Inrush Restraint - Disabled -
Enabled
Disabled
127 50 1Ph - Disabled -
Enabled
cos / sin
130 (sens.) Earth fault dir. characteristic - cos / sin -
V0/I0 mea.
Disabled
Definite Time Only
131 (sensitive) Ground fault - Enabled -
User Defined Pickup Curve
Logarithmic inverse
Disabled
TOC IEC
140 46 Negative Sequence Protection - Disabled -
TOC ANSI
Definite Time
Disabled
142 49 Thermal Overload Protection - Without ambient TC Disabled -
With ambient TC
Disabled
150 Under / Overvoltage Protection - Disabled -
Enabled
Disabled
154 Over / Underfrequency Protection - Disabled -
Enabled
Disabled
161 SYNC Function group 1 - ASYN/SYNCHRON Disabled -
SYNCHROCHECK
Disabled
162 SYNC Function group 2 - ASYN/SYNCHRON Disabled -
SYNCHROCHECK

SE_ChiclOest_Alim10_7SJ64 2 de 8 12/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: SOBRECORRIENTE Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: SIEMENS Alimentador: C-213 y C-218 Depto: LAMBAYEQUE
Modelo: 7SJ64 Potencia: Empresa: ELECTRONORTE
Versin: Uprim[kV]: 10 kV Man.Serv.N:
N Serie: Diag.Unif.N: Fecha:
Tecnologa: NUMRICA Fases: RST-N Respons.: 11-feb-14
Ao instal.: Ucc [V]: Revisin:
Cdigo: Uca [V]: 100 0
Ubic.Tabl: Ica [A]: 1
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES GRUPO 1 GRUPO 1 OBSERVACIONES
COES ECP 2010
3 COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

Disabled
163 SYNC Function group 3 - ASYN/SYNCHRON Disabled -
SYNCHROCHECK
Disabled
164 SYNC Function group 4 - ASYN/SYNCHRON Disabled -
SYNCHROCHECK
Disabled
170 50BF Breaker Failure Protection - Disabled -
Enabled
Disabled
171 Auto-Reclose Function - - -
Enabled
Disabled
172 52 Breaker Wear Monitoring - Ix-Method Disabled -
2P-Method
Disabled
182 74TC Trip Circuit Supervision - with 2 Binary Inputs Disabled -
with 1 Binary Input
Disabled
190 External Temperature Input - Disabled -
Port C
6 RTD simplex operation
6 RTD simplex
191 Ext. Temperature Input Connection Type - 6 RTD half duplex operation -
operation
12 RTD half duplex operation
1 POWER SYSTEM DATA 1
Power System
214 Rated Frequency Hz 50 - 60 60 -
ABC
209 Phase Sequence - ABC -
ACB
Degree Celsius
276 Unit of temperature measurement - Degree Celsius -
Degree Fahrenheit
Towards Line
201 CT Starpoint - Towards Line -
Towards Busbar
NO
280 Holmgreen-conn. (for fast sum-i-monit.) - NO -
YES
A, B, C, (Gnd)
251A CT Connection - A,G2,C,G; G->B A, B, C, (Gnd) -
A,G2,C,G; G2->B
Van, Vbn, Vcn
Vab, Vbc, VGnd
Vab, Vbc, Vx
213 VT Connect. 3ph - Van, Vbn, Vcn -
Van,Vbn,Vcn,VGn
Van,Vbn,Vcn,VSy
Van,Vbn,Vcn,Vx

SE_ChiclOest_Alim10_7SJ64 3 de 8 12/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: SOBRECORRIENTE Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: SIEMENS Alimentador: C-213 y C-218 Depto: LAMBAYEQUE
Modelo: 7SJ64 Potencia: Empresa: ELECTRONORTE
Versin: Uprim[kV]: 10 kV Man.Serv.N:
N Serie: Diag.Unif.N: Fecha:
Tecnologa: NUMRICA Fases: RST-N Respons.: 11-feb-14
Ao instal.: Ucc [V]: Revisin:
Cdigo: Uca [V]: 100 0
Ubic.Tabl: Ica [A]: 1
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES GRUPO 1 GRUPO 1 OBSERVACIONES
COES ECP 2010
3 COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

NO, Van, Vbn, Vcn,


240 VT Connect. 1ph - NO -
Vab, Vbc,,Vca
NO
235 A Storage of th. Replicas w/o Power Supply - NO -
YES
OFF
250 A 50, 51 Time Overcurrent with 2ph. prot. - OFF -
ON
Ignd (measured)
613A (I) DMT Earth Overcurrent with - 3I0 (calcul.) -
3I0 (calcul.)
Vphph
Vph-n
614A Operating Quantity for Overvolt. Prot. - Vphph -
V1
V2
V1
615A Operating Quantity for Undervolt. Prot. - Vphph V1 -
Vph-n
CT's
204 CT Rated Primary Current A 10 50000 1 500 -

205 CT Rated Secondary Current A 1-5 5 -

217 Ignd-CT rated primary current - 1 50000 1 50 -

218 Ignd-CT rated secondary current - 1-5 1 -


VT's
202 Rated Primary Voltage KV 0.10 800 0.01 22.9 -

203 Rated Secondary Voltage (L-L) V 100 225 1 100 -

206A Matching ratio Phase-VT To Open-Delta-VT - 0.10 3.00 0.01 1.73 -


Breaker
210 A Minimum TRIP Command Duration s 0.01 32.00 0.01 0.15 -

211 A Maximum Close Command Duration s 0.01 32.00 0.01 1.00 -

212 Closed Breaker Min. Current Threshold A 0.04 1.00 0.01 0.04 4.00

260 Rated Normal Current (52 Breaker) A-prim 10 50000 1 - -

264 Exponent for the Ix-Method - 1.0 3.0 0.1 - -

SE_ChiclOest_Alim10_7SJ64 4 de 8 12/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: SOBRECORRIENTE Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: SIEMENS Alimentador: C-213 y C-218 Depto: LAMBAYEQUE
Modelo: 7SJ64 Potencia: Empresa: ELECTRONORTE
Versin: Uprim[kV]: 10 kV Man.Serv.N:
N Serie: Diag.Unif.N: Fecha:
Tecnologa: NUMRICA Fases: RST-N Respons.: 11-feb-14
Ao instal.: Ucc [V]: Revisin:
Cdigo: Uca [V]: 100 0
Ubic.Tabl: Ica [A]: 1
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES GRUPO 1 GRUPO 1 OBSERVACIONES
COES ECP 2010
3 COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

<none>
52 Breaker
Disc. Swit.
265 52 B.Wear: Open Cmd. via Control Device - Fan ON/OFF - -
GndSwit
Q2 Op/Cl
Q9 Op/Cl
266 Breaktime (52 Breaker) ms 1 600 1 - -

267 Opening Time (52 Breaker) ms 1 500 1 - -


2 POWER SYSTEM DATA 2
1101 Measurem:FullScaleVoltage (Equipm.rating) KV-prim 0.10 800 0.01 60 -

1102 Measurem:FullScaleCurrent(Equipm.rating) A-prim 10 50000 1 403 -

1107 Motor Start Current (BLK OVL,Start Mon.) A 0.40 10.00 0.01 2.5 -
not reversed
1108 P,Q operational measured values sign not reversed -
reversed
50/51 PHASE/GROUND OVERCURRENT
General
1201 50, 51 Phase Time Overcurrent - ON - OFF ON -
I>> Instantaneously
I> Instantaneously I>>
1213 A Manual Close Mode - -
Ip Instantaneously Instantaneously
Inactive
1215 A 50 Drop-Out Time Delay s 0.00 60.00 0.01 0.00 -
1301 50N, 51N Ground Time Overcurrent - ON - OFF ON -
IE>> Instantaneously
IE> Instantaneously IE>>
1313 A Manual Close Mode - -
IEp Instantaneously Instantaneously
Inactive
1315 A 50N Drop-Out Time Delay s 0.00 60.00 0.01 0 -
2201 Inrush Restraint - ON - OFF - -
50 - PHASE OVERCURRENT
Fundamental
1219A I>>> measurement - True RMS True RMS -
Instantaneous

Always
1216A I>>> active - Always -
with 79 active

SE_ChiclOest_Alim10_7SJ64 5 de 8 12/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: SOBRECORRIENTE Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: SIEMENS Alimentador: C-213 y C-218 Depto: LAMBAYEQUE
Modelo: 7SJ64 Potencia: Empresa: ELECTRONORTE
Versin: Uprim[kV]: 10 kV Man.Serv.N:
N Serie: Diag.Unif.N: Fecha:
Tecnologa: NUMRICA Fases: RST-N Respons.: 11-feb-14
Ao instal.: Ucc [V]: Revisin:
Cdigo: Uca [V]: 100 0
Ubic.Tabl: Ica [A]: 1
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES GRUPO 1 GRUPO 1 OBSERVACIONES
COES ECP 2010
3 COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

1217 I>>> Pickup A 1 a 35 (paso: 0.01) - infinito infinito -


1218 T I>>> Time Delay s 0 a 60 (paso: 0.01) - infinito 0 -
Fundamental
1220A I>> measurement - True RMS True RMS -

Always
1214 A I>> active - Always -
with 79 active
1202 I>> Pickup A 0.10 35; infinito 0.01 40 4000.00
1203 T I>> Time Delay s 0 a 60 (paso: 0.01) - infinito 0 -
Fundamental
1221A I> measurement - True RMS Fundamental -

1204 I> Pickup A 0.10 35;infinito 0.01 0 0.00


1205 T I> Time Delay s 0 a 60 (paso: 0.01) - infinito 0 -
51- PHASE OVERCURRENT
Fundamental
1222A Ip measurement - True RMS True RMS -

1207 Ip Pickup A 0.10 4.00 0.01 6 600.00


1208 T Ip Time Dial - IEC s 0.05 a 3.20 (paso: 0.01) ; infinito 0.1 -
1209 51 Time Dial - ANSI s 0.5 a 15 (paso: 0.01); infinito - -
1210 Drop-out characteristic Instantaneous / Disk Emulation Disk -

NORMAL INVERSE - VERY INVERSE -


1211 IEC Curve - EXTREMELY INVERSE - LONG INVERSE
NORMAL INVERSE -

INVERSE - SHORT INVERSE - LONG


INVERSE - MODERATELY INVERSE -
1212 ANSI Curve - VERY INVERSE - EXTREMELY INVERSE -
- -
DEFINITE INVERSE

NO
Volt. controll.
1223 Voltage Influence - - -
Volt. restraint

1224 U< Threshold for Release Ip - 10.0 125.0 0.10 - -


50N - GROUND OVERCURRENT
Fundamental
1319A IE>>> measurement - True RMS True RMS -
Instantaneous

Always
1316A IE>>> active - Always -
with 79 active
1317 IE>>> Pickup A 0.25 a 35 (paso: 0.01) - infinito infinito -
1318 T IE>>> Time Delay s 0 a 60 (paso: 0.01) - infinito 0 -

SE_ChiclOest_Alim10_7SJ64 6 de 8 12/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: SOBRECORRIENTE Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: SIEMENS Alimentador: C-213 y C-218 Depto: LAMBAYEQUE
Modelo: 7SJ64 Potencia: Empresa: ELECTRONORTE
Versin: Uprim[kV]: 10 kV Man.Serv.N:
N Serie: Diag.Unif.N: Fecha:
Tecnologa: NUMRICA Fases: RST-N Respons.: 11-feb-14
Ao instal.: Ucc [V]: Revisin:
Cdigo: Uca [V]: 100 0
Ubic.Tabl: Ica [A]: 1
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES GRUPO 1 GRUPO 1 OBSERVACIONES
COES ECP 2010
3 COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO
Fundamental
1320A IE>> measurement - True RMS True RMS -

Always
1314 A IE>> active - Always -
with 79 active
1302 IE>> Pickup A 0.05 35;infinito 0.01 3.6 180.00
1303 T IE>> Time Delay s 0 a 60 (paso: 0.01) - infinito 0.5 -
Fundamental
1321 A IE> measurement - True RMS True RMS -

1304 IE> Pickup A 0.05 35;infinito 0.01 0.15 7.50


1305 T IE> Time Delay s 0 a 60 (paso: 0.01) - infinito 0 -
51N - GROUND OVERCURRENT
Fundamental
1322 A IEp> measurement - True RMS True RMS -

1307 51N Pickup A 0.05 4.00 0.01 0 0.00


1308 51N Time Dial - IEC s 0.05 a 3.20 (paso: 0.01) ; infinito 0 -
1309 51N Time Dial - ANSI s 0.5 a 15 (paso: 0.01); infinito - -
1310 Drop-out characteristic Instantaneous / Disk Emulation Disk -
NORMAL INVERSE - VERY INVERSE -
1311 IEC Curve - EXTREMELY INVERSE - LONG INVERSE
NORMAL INVERSE -

INVERSE - SHORT INVERSE - LONG


INVERSE - MODERATELY INVERSE -
1312 ANSI Curve - VERY INVERSE - EXTREMELY INVERSE -
- -
DEFINITE INVERSE

INRUSH RESTRAINT
2202 2nd harmonic in % of fundamental % 10 45 1 - -
2203 Cross Block - NO - YES - -
2204 Cross Block Time s 0.00 180.00 0.01 - -
2205 Maximum Current for Inrush Restraint A 1.50 125.00 0.01 - #VALOR!
67/67N PHASE/GROUND OVERCURRENT
General
1501 67, 67-TOC Phase Time Overcurrent - ON - OFF OFF -
50/51 COLD LOAD PICKUP
General
1701 Cold-Load-Pickup Function - ON - OFF OFF -
46 NEGATIVE SEQUENCE (TIME OVERCURRENT)
General
4001 46 Negative Sequence Protection - ON - OFF OFF
49 49 THERMAL OVERLOAD
General
4201 49 Thermal Overload Protection - ON - OFF - Only Alarm OFF
59/27 Over / Under Voltage

SE_ChiclOest_Alim10_7SJ64 7 de 8 12/02/2014
BASE DE DATOS DE AJUSTE DE PROTECCIONES
Tipo: SOBRECORRIENTE Subestacin: CHICLAYO OESTE Regin: ZONA COSTA NORTE
Fabricante: SIEMENS Alimentador: C-213 y C-218 Depto: LAMBAYEQUE
Modelo: 7SJ64 Potencia: Empresa: ELECTRONORTE
Versin: Uprim[kV]: 10 kV Man.Serv.N:
N Serie: Diag.Unif.N: Fecha:
Tecnologa: NUMRICA Fases: RST-N Respons.: 11-feb-14
Ao instal.: Ucc [V]: Revisin:
Cdigo: Uca [V]: 100 0
Ubic.Tabl: Ica [A]: 1
Sistema: PRINCIPAL Frec.[Hz]: 60
DESCRIPCION DE LOS AJUSTES GRUPO 1 GRUPO 1 OBSERVACIONES
COES ECP 2010
3 COD DESCRIPCION UNIDAD MIN MAX PASO SECUNDARIO PRIMARIO SECUNDARIO PRIMARIO

General
5101 Undervoltage Protection - OFF - ON - Alarm Only OFF -
5001 Overvoltage Protection - OFF - ON - Alarm Only OFF -
MEASUREMENT SUPERVISION
General
5301 Fuse Fail Monitor - ON - OFF OFF
74TC TRIP CIRCUIT SUPERVISION
8201 74TC Trip Circuit Supervision - ON - OFF OFF
64, 50Ns, 51Ns, 67Ns (Sensitive) GROUND FAULT
General
3101 (sensitive) Ground fault - ON - OFF ON
3121 A 50Ns Drop-Out Time Delay s 0.00 60.00 0.01 0 -
50Ns
3113 50Ns-2 Pickup A 0.005 7.500 0.001 0.02 1.00
3114 50Ns-2 Time Delay s 0.0 320, infinito 0.1 0.5 -
3117 50Ns-1 Pickup A 0.005 7.500 0.001 0.01 0.50
3118 50Ns-1 Time Delay s 0.0 320, infinito 0.1 1 -
CT's
3102 Current I1 for CT Angle Error A 0.005 8.000 0.001 - -
3103 CT Angle Error at I1 Degrees 0.0 5.0 0.1 - -
3104 Current I2 for CT Angle Error A 0.005 8.000 0.001 - -
3105 CT Angle Error at I2 Degrees 0.0 5.0 0.1 - -
50BF BREAKER FAILURE
General
7001 50BF Breaker Failure Protection - OFF - ON OFF -
50 BF
7004 Check Breaker Contacts ON - OFF OFF -
7005 TRIP - Timer s 0.06 a 60 (paso: 0.01) - infinito 0.25 -
7006 Pick-up threshold I> A 0.03 a 20 (paso: 0.01) 0.10 -
7008 TRIP-Timer 2 s 0.06 a 60 (paso: 0.01)-infinito - -
50 1Ph 50 1Ph
General
2701 50 1Ph - OFF - ON OFF -
50 BF
2702 50 1Ph-2 PICKUP A 0.050 35, infinito 0.010 infinito -
2703 50 1Ph-2 Pickup A 0.003 1.5, infinito 0.001 - -
2704 50 1Ph-2 Time Delay s 0.00 60, infinito 0.01 infinito -
2705 50 1Ph-1 PICKUP A 0.050 35, infinito 0.010 infinito -
2706 50 1Ph-1 Pickup A 0.003 1.5, infinito 0.001 - -
2707 50 1Ph-1 Time Delay s 0.0 60, infinito 0.01 infinito -

SE_ChiclOest_Alim10_7SJ64 8 de 8 12/02/2014