You are on page 1of 22

SE Reference Manual Chapter 16

CHAPTER 16

Design Requirements

Chapter 16 of the IBC/CBC prescribes general design requirements for structures


regulated by the code. Relevant information from Chapter 16 is presented below:

1604.5 Occupancy Category

Per Table 1604.5 (IBC/CBC) or Table 1-1 (ASCE 7),

Occupancy Description of Hazard Represented by Building Collapse


Category
I Low
II All buildings except those in I, III and IV
III Substantial
Public Assembly > 300 people
Schools, daycares > 250 people
College, adult education > 500 people
Healthcare (no emergency or surgery) > 50 people
Jails, detention centers
Any building with more than 5000 people
Public utility buildings (not in IV)
Buildings containing hazardous materials (not in IV)
IV Essential facilities
Hospitals with emergency and surgery
Fire, rescue, police
Emergency shelters for earthquakes
Power stations, public utility buildings designated for
earthquake backup
Aviation towers, control centers
Critical nation defense related building
Buildings containing hazardous materials quantities greater
than in Table 307.1.(2).

1605 Load Combinations

Strength Design

IBC/CBC 1605.2.1

1. 1.4(D + F)
2. 1.2(D + F + T) + 1.6(L + H) + 0.5(Lr or S or R)
3. 1.2D + 1.6(Lr or S or R) + (f1L + 0.8W)
4. 1.2D + 1.6W + f1L + 0.5(Lr or S or R)

Chapter 16 CH16-1
SE Reference Manual Chapter 16

Roof Loads (1607.11)

Roof live loads may be reduced per 1607.11.2.1 based on the roof slope and
tributary area, except for landscaped roofs (20psf minimum). Special purpose
roofs (1607.11.2.2) shall be treated similar to floors.

1609 Wind Loads

Wind loads are per Section 6 of ASCE 7. See section Wind Loads.

1617 Earthquake Loads

The IBC references ASCE 7 for the majority of the earthquake load provisions. IBC (and
ASCE 7) assigns a Seismic Design Category to each structure. Seismic design
categories are used to determine permissible lateral systems, height limitations, type of
lateral analysis and seismic detailing requirements. Earthquake loads are described in the
section titled Earthquake Loads. Other relevant items are discussed here. The code
references are to ASCE 7.

The general layout of the seismic provisions of ASCE 7 is as follows:

Chapter Description
11 Seismic design criteria
- Importance Factor & Seismic Design Category (SDC)
- Mapped accelerations etc.
12 Seismic design requirements for buildings
- Design basis
- Provisions for structural system selection, horizontal and vertical
combinations of lateral systems etc.
- Seismic load combinations
- Equivalent lateral force calculations
- Response spectrum analysis
- Drift limits
- Detailing requirements for different SDC etc.
13 Seismic design requirements for non-structural components, including
architectural and MEP components.
14 Seismic design and detailing for different materials Not used by
IBC/CBC
15 Seismic design requirements for non-building structures, including those
similar to buildings (pipe racks, towers etc.) and those not similar to
buildings (tanks, stacks, chimneys etc.).
16 Seismic response history procedures (time history analysis procedures)
17 Design requirements for base isolated structures
18 Design requirements for structures with damping systems.
19 Soil-structure interaction for seismic design
20 Site classification for seismic design

Chapter 16 CH16-5
SE Reference Manual Chapter 16

21 Site-specific ground motion procedures for seismic design


22 Seismic ground motions and long-period transition maps

Relevant Provisions of ASCE 7 Earthquake Design:

12.2.5.1 Dual Systems

Dual systems are defined as a combination, in any given direction of loading, of


moment frames (special or intermediate) and shear walls, braced frames (SCBF,
EBF, BRBF etc.)see Table 12.2-1 for a complete listing of allowed dual
systems.

The moment frames shall be designed to resist a minimum of 25% of the design
base shear. The actual seismic force distribution shall be based on the appropriate
rigidities of the systems.

12.2.2 Combinations in Different Directions

Different seismic systems can be used in each of the orthogonal directions of the
structure. The appropriate values of R, Cd, and o should be used for each system.

12.2.3 Combinations in the Same Direction

For non-dual systems used in combination in the same direction, use the least
value of R for any of the systems. The Cd and o values shall correspond to the R
factor being used in a given direction and shall not be less than the largest
respective values for that R factor.

Exception:

Different systems in each independent line of lateral system are permitted to be


designed for the least value of the R factor in that line if the following conditions
are met:

1. Occupancy Category I or II.


2. Height is two stories or less.
3. Light frame construction or flexible diaphragms.

12.2.3.1 Vertical Combinations of Lateral Systems

R used in any story shall not exceed the lowest R value used in any story above.
Cd and o shall not be less than the largest value of each factor used in any story
above.

Exceptions:

Chapter 16 CH16-6
SE Reference Manual Chapter 16

Table 1

Structural Design Requirements

Description SDC A SDC B SDC C SDC D SDC E & F

Building height limits Table 12.2-1 Table 12.2-1 Table 12.2-1 Table 12.2-1 & Table 12.2-1 &
12.2.5.4 12.2.5.4
Redundancy/Reliability = 1.0 = 1.0 = 1.0 = 1.3
factor Same as SDC D
(12.3.4) =1.00 permitted if
conditions in 12.3.4.2
& Table 12.3-3 are met.

Analysis Procedures1,2 1 OC I, II & 3 stories Same as SDC B Same as SDC B Same as SDC D
(12.6 & Table 12.6-1) (11.7.2) with building frame or
bearing wall system & For SDC F, the
OC Occupany Category 2,3,4,5 simplified design
All other light framed procedure (type 2) is
(See Note 2 for a All other structures structures 3,4,5 not permitted.
description of analytical 3,4,5
procedures 1 through 5) Regular with T<3.5Ts
Any structure with site 3,4,5,
class E or F 3,4,5
Irregular with T<3.5Ts
and irregularities listed
in Note 3 - 3,4,5

Any structure with


torsional irregularity
(Table 12.3-1, Type 1a
or 1b) - 4,5

Chapter 16 CH16-8
SE Reference Manual Chapter 16

Description SDC A SDC B SDC C SDC D SDC E & F

Design & Detailing


Load Path Connections Provide continuous Connections between a Same as SDC B Same as SDC B Same as SDC B
(12.1.3 & 11.7.3) path to the lateral smaller portion & the
system within the main structure shall be
structure. capable of carrying the
greater of:
Connection between Fp=0.133SDSwp
a smaller portion & or
main structure shall Fp=0.05wp
be for Fp=0.05wp
Anchorage of Concrete Horizontal force shall Horizontal force to be Minimum
or Masonry Walls be greater of: greater of: requirements as per Same as SDC C Same as SDC C
(12.11 & 11.7.5) Fp=0.05Wp Fp=0.10Wp SDC B
& &
Fp 280plf Fp=0.40SDSIWp For flexible
(11.7.5) & diaphragms,
Fp=400SDSI Fp=0.8SDSIWp
& (12.11.2.1)
Fp 280plf
Maximum
Wall Design to be based length/width ratio for
on greater of: sub-diaphragms shall
Fp=0.10Wp be 2.5 to 1.0
& (12.11.2.2.1)
Fp=0.40SDSIWp

If anchor spacing > 4ft,


design wall to span
between anchors

Chapter 16 CH16-10
SE Reference Manual Chapter 16

collectors and
connections between
diaphragms and
collectors to vertical
elements.

Force increase not


required if load
combinations with
over-strength are used.

See also Collectors


above in this table.

Notes: 1. OC Occupancy Group, ASCE 7 Table 1-1, CBC Table 1604.5 and 1604A.5.
2. Analysis Procedures: 1 Minimum Lateral Force (11.7), 2 Simplified Design Procedure, 3 Equivalent Lateral Force, 4
Response Spectrum, 5 Time History. See Section Earthquake Loads.
3. Irregular structures with T < 3.5Ts and having only Horizontal Irregularities (Table 12.3-1) type 2, 3, 4, or 5 or Vertical
Irregularities (Table 12.3-2) type 4, 5a or 5b.

Chapter 16 CH16-14
SE Reference Manual Loads & Analysis

LOADS & ANALYSIS

EARTHQUAKE LOADS

Per IBC 1613, the earthquake loads shall be per ASCE 7. The relevant provisions are
presented below. All references are to ASCE 7, unless otherwise noted.

Per IBC and ASCE 7, the earthquake forces and the associated detailing is based on the
Seismic Design Category (SDC) assigned to the building.

Seismic Design Category (SDC), IBC 1613.5.6, ASCE 7 11.6:

The SDC is a function of the Occupancy Category (IBC/CBC Table 1604.5 and ASCE
7 Table 1-1) and the mapped accelerations at the site. See IBC/CBC Tables 1613.5.6(1)
and 1613.5.6(2) (ASCE 7 Tables 11.6-1 and 11.6-2, respectively) for SDC classification.

SDC A and B indicate low seismic risk; SDC C indicates moderate seismic risk; while
SDC D, E and F apply to high seismic risk. The detailing requirements as well as
construction quality assurance requirements for SDC D, E, and F are much more
stringent than for the lower categories.

Earthquake Loads

The code permits a variety of analytical procedures see Table 1 in Chapter Design
Requirements. The Equivalent Lateral Force Procedure per ASCE 7 12.8 is presented
below.

Equivalent Lateral (Static) Force Procedure (ASCE 7 12.8 & 11.4)

Step 1 Obtain Mapped Spectral Accelerations: ASCE 7 11.4.1

From the maps (IBC Figure 1613.5(1) through 1613.5(14) or ASCE 7 Chapter 22,
obtain the following:

Ss = Short period earthquake spectral response acceleration, &


S1 = 1-second period earthquake spectral response acceleration

Step 2 - Determine Site Coefficients Fa and Fv: ASCE 7 11.4.3

Determine Site Coefficients Fa and Fv from Tables 11.4-1 & 11.4-2.

If site class is not known, assume D.

IBC Earthquake Loads IBCSL1


SE Reference Manual Loads & Analysis

Note: OSHPD requires that if a structure is not assigned to SDC E of F, it shall


be assigned to SDC D (1613A.5.6)

Step 6 Compute Base Shear: ASCE 7 12.8

V = CsW (Eqn 12.8-1)

W = Dead load + 25% live load for storage areas + Actual partition load
(or 10psf minimum) + weight of permanent equipment + snow load
(12.7.2)

Step 6a Approximate Period Calculation: ASCE 7 12.8.2.1

T = Ta = CT hn
x
(Eqn 12.8-7)

12.8.2 If the period is computed from analysis, T CuTa.

where, CT & x are given below (Table 12.8-2)


hn = Height of building in feet
Cu is given below (Table 12.8-1)

Structure Type Cu x SD1 Cu


Steel MRF 0.028 0.8 0.4 1.4
Concrete MRF 0.016 0.9 0.3 1.4
Steel EBF 0.03 0.75 0.2 1.5
All others 0.02 0.75 0.15 1.6
0.1 1.7

Alternative methods for periods for moment frames and shear wall
buildings are presented in 12.8.2.1.

Step 6b Cs calculation: ASCE 7 12.8.1.1

S DS
Cs =
( )
R
I
(Eqn 12.8-2)

where, R = Response reduction factor, Table 12.2-1


I = Importance factor, IBC Table 1604.5A, ASCE & Table 1-1.
I = 1, 1.25 & 1.5 for Occupancy Category I/II, III & IV,
respectively.

IBC Earthquake Loads IBCSL3


SE Reference Manual Loads & Analysis

The value of Cs need not exceed:

S D1
Cs = for T TL
( )
R T
I
(Eqn 12.8-3)

S D1TL
Cs =
( )
R T2
I
for T > TL (Eqn 12.8-4)

Cs shall not be less than:

C s = 0.01 (OSHPD/DSA, C s = 0.03 ) (Eqn 12.8-5)

Where S1 0.6g, Cs shall not be less than:

0.5S1
Cs = (Eqn 12.8-6)
R
I

Step 7 Vertical Distribution of Base Shear: ASCE 7 12.8.3

At each level the seismic force is given as:

Fx = C vxV (Eqn 12.8-11)

wx hxk
C vx = n
(Eqn 12.8-12)
w h
i =1
i i
k

If T 0.5 k = 1.0
If T 2.5 k = 2.0
Use k = 2 or linear interpolation between the period limits.

Seismic Load Effect: ASCE 7 12.4.2

E = Eh Ev (Eqn 12.4-1)

E = QE + 0.2SDSD
E = QE - 0.2SDSD

Where, QE = Effect of horizontal seismic forces


0.2 SDSD = Vertical acceleration effect (Eqn 12.4-4)

IBC Earthquake Loads IBCSL4


SE Reference Manual Loads & Analysis

Where seismic over strength factor needs to be included in the design, 12.4.3,

Em = Emh Ev

Em = QE 0.2SDSD

The load combinations with over strength are given in 12.4.3.2.

Redundancy Factor : ASCE 7 12.3.4.2

For SDC A, B, or C, = 1.0

For SDC D, E, or F = 1.3 For all structures, or


= 1.0 if one of the following two
conditions are met.

a. Each story resisting more than 35% of the base shear (typically the lower
stories in a building) shall comply with the following:

1. Loss of one of the following does not result in more than 33%
reduction in story strength:
i. An individual brace or connection thereto
ii. Moment connections at both ends of one beam
iii. A shear wall or wall pier with height-to-length ratio > 1.0
iv. Moment resistance at the base of a single cantilever column.

2. Loss of one of the above does not result in an extreme torsional


irregularity (Type 1b, Table 12.3-1).

b. For structures regular in plan at all levels with at least two perimeter bays of
the seismic force-resisting in each direction at each level resisting more than
35% of the base shear.

For shear walls: Number of bays = (n*Wall length)/story height

Where, n = 2, For shear walls in light framing.


n = 1, for all other shear wall building.

In addition to the above, = 1.0 is permitted for the following:

1. Drift & P- calculations


2. Design of non-structural components & non-building structures that are not
similar to buildings.
3. Design of collectors, splices, their connections etc., for which the load
combinations with over-strength as used.

IBC Earthquake Loads IBCSL5


SE Reference Manual Loads & Analysis

4. For design of any member or connection for which the load combinations with
over-strength are used.

Displacement amplification: ASCE 7 9.5.5.7

For allowable stress design, displacement is computed for earthquake loads


without dividing by 1.4 and using = 1.0.

The design deflection at the center of mass at any level is calculated as,

C d xe
x = (Eqn 12.8-15)
I

where, x = Maximum inelastic displacement at level x.


Cd = Displacement amplification factor, Table 12.2-1
xe = deflection from an elastic lateral analysis of the building.

The deflections/drifts can be determined for the seismic forces at the actual period
calculated for the building, without applying the CuTa limit in Step 6a.

Exceptions to Static Force Procedure:

Where applicable, the equivalent lateral force procedure may be substituted by one of the
procedures below. See Table-1 of Chapter 16 Design Requirements for more
information.

Minimum Lateral Force: IBC 11.7.1

Applies to SDC A only. At each floor the minimum base shear shall be:

Fx = 0.01Wx
where, Fx = Design seismic force @ story x
Wx = Seismic weight @ story x

Simplified Procedure: 12.14

Note: Not permitted by OSHPD & DSA (1613A.5.6.2).

This procedure can be used in lieu of the other analytical procedures for the
analysis/design of simple buildings with bearing walls or building frame systems,
if the building meets certain limitations. See 12.14.1.1 for a complete list and
below for the major limitations:

1. The building shall be in Occupancy Category I or II and shall not


exceed 3 stories in height.

IBC Earthquake Loads IBCSL6


SE Reference Manual Loads & Analysis

SELECTION OF LATERAL SYSTEMS FOR SEISMIC DESIGN

CHAPTERS 19 & 22

As with seismic loads and detailing requirements, the IBC/CBC places limits on the type
of structural systems that can be used for lateral design based on Seismic Design
Category (SDC)--see section Chapter 16 and Earthquake Loads for more information.

The brief list below specifies the minimum concrete and steel system requirements for a
given SDC. It is always permitted to provide a better lateral system and take advantage of
the lower seismic design forces (ACI 318, R21.2.1)

For a detailed listing of lateral systems and associated limitations, see ASCE 7 Table
12.2-1. All reference in the following are to IBC/CBC, unless noted otherwise.

Concrete (Chapter 19 & ACI 318)

Seismic Design Categories A & B (Low Seismic Risk) 1910.2 & 1910.3

Ordinary Shear Walls

Designed using Chapters 1 through 18 of ACI 318.

Note: For SDC A, shear walls can be ordinary plan concrete walls per Chapter
22 of ACI 318 or detailed plain concrete walls per IBC 1908.1.14.

Ordinary Precast Concrete Shear Walls

Designed using Chapters 1 through 18 of ACI 318.

Ordinary Moment Frames

Designed using Chapters 1 through 18 of ACI 318.

108.1.1 Provide at least two reinforcing bars continuously at top and bottom in
beams and develop at (or continuous through) the columns.

1908.1.2 Columns with clear height to maximum dimension ratio of five or


less shall also be designed for shear.

Seismic Design Category C (Intermediate or Moderate Seismic Risk) 1908.1.4

Ordinary Shear Walls:

Designed using Chapters 1 through 18 of ACI 318.

IBC Lateral System Selection LSS1


SE Reference Manual Loads & Analysis

Note: Plain concrete shear walls not permitted except as basement (retaining)
walls for one or two family dwellings with stud framing above.

Intermediate Precast Concrete Shear Walls:

Designed using Section 21.13 in addition to Chapters 1 through 18 of ACI 318.

Intermediate Moment Frames:

Designed using Section 21.12 in addition to Chapters 1 through 18 of ACI 318.

Discontinuous Members (1908.1.12): Columns supporting discontinuous lateral


systems above (such as shear walls) shall be designed for the special seismic load
combinations (i.e. using o) with appropriate transverse reinforcement, per
21.12.5.2 of ACI 318, over the full height as well as above and below as required.

Seismic Design Categories D, E, F (High Seismic Risk) 1908.1.4

Special Shear Walls:

Cast-in-place walls designed using Sections 21.2 and 21.7 in addition to Chapters
1 through 18 of ACI 318.

Precast walls shall also satisfy 21.8 of ACI 318 in addition to the above.

Special Moment Frames:

Cast-in-place frames designed using Sections 21.2, 21.3, 21.4 and 21.5 in addition
to Chapters 1 through 18 of ACI 318.

Precast frames designed per Sections 21.2, 21.3, 21.4 and 21.6 of ACI 318,
including all requirements for ordinary moment frames.

Diaphragms and Foundations:

Designed using Sections 21.2 and 21.9 for diaphragms and 21.2 and 21.10 for
foundations, in addition to Chapters 1 through 18 of ACI 318.

Frame members not part of the lateral system:

Designed/checked per section 21.11 to ensure that they can continue to carry the
gravity loads at the maximum lateral displacements corresponding to the design
level seismic forces.

IBC Lateral System Selection LSS2


SE Reference Manual Loads & Analysis

Steel (Chapter 22, AISC Steel Specifications (ASD/LRFD AISC 360) & AISC
Seismic Provisions, AISC 341)

Seismic Design Categories A, B & C (Low or Moderate Seismic Risk) 2205.2.1

Steel structures may be designed using the following two options:

1. Use R = 3 per ASCE 7, Table 12.2-1, Item H for Structural Steel Systems Not
Specifically Detailed for Seismic Resistance in conjunction with the typical AISC
LRFD or ASD Specifications.

2. Use an R factor per ASCE 7, Table 12.2-1 and design per AISC Seismic
Provisions (ASIC 341), Part I.

Seismic Design Categories D, E & F (High Seismic Risk) 2205.2.2

3. Steel structures shall be designed using AISC Seismic Provisions (ASIC 341-02),
Part I.

IBC Lateral System Selection LSS3


(4) 13.2d Columns
(1) 13.2 Bracing Members (2) 13.3 Bracing Connections
WF: b 0.30 E
t Fy Same limits as braces, Table I-8-1.
13.3a Tensile strength of connections (including beam-column
13.2a Braces: KL 4 E
r Fy Rectangular HSS: b or h 0.64 E connection) shall be the lesser of:
t tw Fy
See 13.2a for KL/r greater than above limit. 1. Pst = RyFyAg (LRFD) or Pst = RyFyAg/1.5 (ASD)
Column strength and splice design shall be per 13.5 => See sheet SLRS-Col1&2 for details. 2. Maximum load effect that can be transferred to brace
13.2d Compactness (8.2b, Table I-8-1): by the system
WF & Channels: b 0.30 E 13.3b Flexural strength of the connection shall be based on
t Fy
1.1RyMp (LRFD) or (1.1/1.5)RyMp (ASD) of the brace
For h/tw under flexure and axial load, see Table I-8-1.
about the critical buckling axis (typically out of plane).
Rectangular HSS: b or h 0.64 E
t tw Fy
This strength requirement does not apply if the
Circular HSS: OD 0.044 E connection can accommodate the inelastic rotations due
t Fy to the brace post-buckling deformations. This can be
Angles: b 0.30 E accomplished by using single plate gussets with a 2t
t Fy setback from the yield line for out-of-plane rotation to
OSHPD/DSA do not permit the use of rectangular HSS the brace end. The gusset plate shall be designed to
sections unless filled with concrete. resist the compressive strength of the brace without
buckling.
13.2c Lateral Force Distribution
For a line of bracing:
0.3VTotal Vh tension 0.7Vtotal

Vh tension = Horizontal component of axial force for braces


in tension.
VTotal = Total horizontal force in line of bracing. (3) 13.4.a Beam Design for V-Type & Inverted V-Type Bracing

Note: Exception if all braces are designed to resist the 1. Beam shall be continuous between columns and designed to carry all applicable gravity load
load combinations including o in compression. combinations without braces.
2. For load combinations that include earthquake effects, use the following:
a. (1.2 + 0.2SDS)D + Pb + f1L + f2S
13.2e Built-up Members: b. (0.9 - 0.2SDS)D Pb
where, Pb = unbalanced post-buckling force based on Pst = RyFyAg & Psc = 0.3Pn, where Pn
For each individual element between stitches, l/r 0.4l t/r, is the nominal compressive capacity of the brace.
where lt/r is for whole member. 3. Both flanges of the beam shall be braced as follows: Net Area: Typical connections use slotted HSS members
a. At the point of brace intersection. welded to the gusset. The net area in tension shall be
Shear strength of stitches tensile strength of each E r
calculated as the gross area minus the slot width
element. b. At a maximum spacing of Lb = L pd = 0.12 + 0.076 M 1 F y (A-1-7) times the thickness of the HSS. This area needs to be
M 2 y
replaced via a plate welded to the two non-slotted
where, M1 & M2 (k-in) are the smaller and larger moments at the ends of the unbraced faces of the HSS (curved plates for round HSS). The
Stitches to be placed uniformly along length. No less than
length. The ratio is positive for reverse curvature and negative for single curvature. side plates need to be adequately extended either side
2 stitches. No bolted stitches within the middle of the
Note: For TS beams, see Appendix 1 A.1.7. of AISC Specification. of the slot via a shear lag analysis (see D3 of the
brace clear length.
AISC Specification).
Lateral braces shall be per Eqns. A-6-7 & A-6-8 of Appendix 6 of the AISC Spec. with Mr
being either RyZFy (LRFD) or RyZFy/1.5(ASD) and Cd = 1.0.

STEEL SPECIAL CONCENTRIC BRACED FRAMES (AISC 341, 13, ASCE 7, Table 12.2-1)
R = 6, = 2, Cd=5
SLRS-SCBF
SE Reference Manual Concrete Design

REINFORCED CONCRETE

SHEAR WALL DESIGN

Referencec: ACI-318 & IBC 2006/CBC 2007.

Wall Type Reinforcement Shear Axial & Flexural Other


SDC Limits Design Design
Ordinary A, B 14.3 14.2, 14.3
Shear Wall 11.10.8, 11.10.9 11.10 (10.2, 10.3. 10.10- -
10.14, 10.17)
Special A, B, C, 21.7.2 21.7.3, 21.7.5 Boundary
Shear Wall D, E, F 21.7.4 (10.2, 10.3. 10.10- Elements
10.14, 10.17) 21.7.6
Notes: 1. Provisions 10.10-10.14, 10.17 address slenderness, moment magnification,
bearing strength etc. and typically do not govern the design.
2. Precast walls follow similarly to above, except Intermediate Precast Walls
(permitted in SDC A, B, C) shall also comply with 21.13.

Reinforcement Limits (11.10.9, 14.3, 21.7.2)

Note: 1. OSHPD/DSA Minimum reinforcement parallel to all edges of the wall and
boundaries of all openings shall be twice the shear reinforcement required per lineal
foot of wall (1908A.1.37).
2. For seismic design reinforcement development lengths (& splices) shall be per 21.5.4
See Reinforcement Development & Lap Splices, pp. RDL3-RDL5.

Shear Wall Design CSWD1


SE Reference Manual Concrete Design

Boundary element requirements for Special Walls (21.7.6):

Boundary element requirements can be evaluated by either one of the two methods
described below:

a) For walls that are effectively continuous from the base to the top with a single
critical section for axial and flexural loads (21.7.6.2):

lw
Provide boundary elements where: c (21-8)
600( u / hw )

where, c = neutral axis depth for (1.2 + 0.2SDS)D + QE + f1L


u = design displacement at top of wall (i.e. Cdx/I)
u/hw 0.007 (21.7.6.2(a))

For u/hw = 0.007, c = 0.24w.

At some height along the wall, the above requirement will not be applicable

Extend the boundary element reinforcing beyond this elevation by a distance not
less than the larger of: w or Mu/4Vu.

b) For walls not designed per above, provide boundary elements at wall boundaries,
and edges of openings where maximum compressive stress exceeds 0.2fc.
Discontinue boundary detailing where the stress is less than 0.15fc (21.7.6.3).
Pu
Factored Loads
Mu

Shear wall Extend up to and


0.15fc
discontinue above
0.2fc Boundary detailing
required.

Axial Stress Use gross section properties


with elastic force distribution
21.7.6.3
Flexural Stress

If res > 0.2fc, provide boundary


Resultant Stress
reinforcing.

Shear Wall Design CSWD6


SE Reference Manual Concrete Design

REINFORCED CONCRETE

BEAM DESIGN

Reference: ACI 318

General Design Provisions for Beams:

Analysis

Reinforcement Limits:

3 f 'c
Check min = bw d
f y

s min 10.5.1
200
min = bw d
fy

6 f 'c
( As min = bw d for T-beams with flanges in tension)
fy
The above limits need not apply if As provided, at each section, exceeds by 1/3rd
the steel area required by analysis (10.5.3).

In ACI 318-05, section strength is governed by available ductility (i.e. amount of


reinforcement at a given section and tensile stress in the reinforcement) and the
strength-reduction factor, , e.g. the higher the ductility, the smaller the strength
reduction and vice-versa.

Each section is classified as either compression-controlled, tension-controlled or


in transition. These categories are based on the net tensile strain (t) in the
extreme tension steel and are defined at a concrete ultimate strain (cu) of 0.003.

Balanced strain conditions: @ cu = 0.003, sb = fy/Es 10.3.2

sb = 0.002 for fy = 60ksi 10.3.3

Compression-controlled: @ cu = 0.003, t sb 10.3.3

Tension-controlled: @ cu = 0.003 , t 0.005 10.3.4

Transition-range: @ cu = 0.003 , 0.002 < t 0.005 10.3.4

Concrete Beam Design CBD1


SE Reference Manual Concrete Design

Beam Deflection (9.5.2)

Per Table 9.5(a), deflections need not be computed if the following minimum
depths are provided (for normal weight concrete & 60ksi reinforcement):
Beams Slabs
- Simple span: L/16 L/20
- Cantilever: L/8 L/10
- One end continuous: L/18.5 L/24
- Both ends continuous: L/21 L/28

Deflection Calculation (9.5.2.3):

Deflection is to be based on beam formulas and Ie shown below,

M
3
M
3

I e = cr I g + 1 cr I cr (Eqn 9-8)
Ma M a

fr I g D
M cr = where, f r = 7.5 f ' c & y t = (Eqn 9-9)
yt 2

Ma is the service level moment (if Ma < Mcr=> No cracking =>Ie = Ig)

b(kd ) 3
I cr = + nAs (d kd ) 2
3

b Using transformed section from


2 d + 1 1
nAs working stress design.
kd = PCA Notes on ACI 318-95, pg. 8-3
b

nAs

Long-term deflection factors (9.5.2.5):


= (Eqn 9-11)
1 + 50 '

where, = compressive steel ratio


= 2.0 for 5 years or more, 1.4 for 12 months or more etc.

Notes: 1. See ACI 318, Table 9.5(a) for quick estimates of slab/beam thickness.
2.See ACI 318, Table 9.5(b) or UBC/CBC Table 19-C-2 for permissible
deflections (typically use D+L L/240 & L L/360).

Concrete Beam Design CBD5


SE Reference Manual Concrete Design

Non-Seismic Beam Reinforcement Detailing (12.10, 12.11, & 12.12):

Positive Moment Reinforcement:

Distance to extend reinforcement past where it is no longer required =


MAX(d,12db) except at supports of simple spans and ends of cantilevers.

Extend bars at least d past the critical section.

Minimum reinforcement to be extended at least 6 into support (Bars B):


1
Simple span beams: As +
3 12.11.1
1
Continuous beams: As +
4

At simple supports & points of inflection, bar size shall be limited such that d
satisfies the following:

Mn
Ld + la 12.11.3
Vu
Mn = Nominal flexural capacity of beam
Vu = Factored shear at the section
la = Embedment length beyond center of support or maximum of beam
effective depth & 12db at an inflection point.

Notes: 1. This provision limits the bar size to ensure adequate Ld is available.
2. Use 1.3(Mn/Vn) in above equation if a compressive reaction confines
the end of the bars.

Concrete Beam Design CBD8


SE Reference Manual Concrete Design

Seismic Provisions for Special Moment Frame (SMRF) Beams:

Pu 0.10Agfc 21.3.1.1

ClearSpan
4 21.3.1.2
d

Width
0.3 21.3.1.3
Depth

Width 10 21.3.1.4

3 f 'c 200bw d
As top & As bot bw d & 21.3.2.1
fy fy
As
max = 0.025 , where =
bw d

Provide 2 continuous bars top


and bottom, typical.

At face of joint, As min bot = As top 1921.3.2.2

Anywhere along the beam length, Mn min at top & bottom Mn max.

Lap splices permitted only if confined over full length by hoop or spiral
reinforcement (see figure below). 21.3.2.3

(M + M prB ) wg Lclr
Beam shear demand, Ve = +
prA
21.3.4.1
Lclr 2

Where, MprA & MprB = Moment capacities @ beam ends using 1.25fy & =1.0
Wg = Factored gravity load
Lclr = Clear span

Vu
If Ve & Pu < 0.05 Ag f ' c 21.3.4.2
2
Ve = seismic shear demand from analysis.
Assume Vc = 0 & design stirrups to carry entire shear demand, Ve (shear
from analysis)see CBD4 for Vs.

Concrete Beam Design CBD11


SE Reference Manual Concrete Design

Since Ve approximates the maximum shear that can develop in a member,


use = 0.75 (21.3.4.1 & 9.3.4).

Detailing Requirements for SMRF Beams

Note: For development lengths, splices etc. see Concrete Column Design
section.

Concrete Beam Design CBD12

You might also like