You are on page 1of 5

ECG Project Name

Job Ref.
Engineering Consultants Group CHECKING AND PACKING HALL

Bldg. 2, Block 10, El Sefarat District Calc. By Date Checked By Date Rev.

P.O.Box No. 1167, Cairo 11511, Egypt. M.Nour Sheet No.

PURLINS ID ( P-1 )

Span = 2.40 m
Spacing = 0.60 m
= 10.00
No Tie Rod
1)- APPLIED FORCES :-
DEAD LOAD
C.sheets = 310.00 Kg/m2
WDL = 195.00 Kg/m\
WXDL = 0.1930 t/m\ WYDL = 0.0339 t/m\
MXDL = 0.1400 m.t MYDL = 0.0250 m.t
QXDL = 0.2400 t

LIVE LOAD
a)Uniform load
Roof is accessible
L.L. = 148.00 Kg/m2
WLL = 89.00 Kg/m\
WXLL = 0.0880 t/m\ WYLL = 0.0160 t/m\
MXLL = 0.0700 m.t MYLL = 0.0120 m.t
QXLL = 0.1100 t
b)100 Kg concentrated load
PX = 99.00 Kg PY = 18.00 Kg
MXLL = 0.0600 m.t MYLL = 0.0110 m.t
QXLL = 0.0500 t
MAX LIVE LOAD :-
MXLL = 0.0700 m.t MYLL = 0.0120 m.t
QXLL = 0.1100 t

WIND LOAD
Ce = -0.60
K = 1.10
q = 70.00 Kg/m2
WXWL = -0.1572 t/m\
MXWL = -0.1132 m.t Neglect wind load
QXWL = 0.00 t
ECG Project Name
Job Ref.
Engineering Consultants Group CHECKING AND PACKING HALL

Bldg. 2, Block 10, El Sefarat District Calc. By Date Checked By Date Rev.

P.O.Box No. 1167, Cairo 11511, Egypt. M.Nour Sheet No.


ECG Project Name
Job Ref.
Engineering Consultants Group CHECKING AND PACKING HALL

Bldg. 2, Block 10, El Sefarat District Calc. By Date Checked By Date Rev.

P.O.Box No. 1167, Cairo 11511, Egypt. M.Nour Sheet No.

FINAL DESIGN LOADS :-


MX = 0.2500 m.t Case a
MY = 0.0400 m.t
QX = 0.4000 t

2)- CHOICE OF SECTION :


C 100X50X4 Single
h = 100 mm b = 50 mm Wt. = 5.76 kg/m
d = mm t = 4 mm r = 8.00 mm
Sx = 21.88 cm 3
Sy = 5.00 cm 3

A = 7.34 cm 2
ey = 1.46 cm
rx = 3.86 cm ry = 1.56 cm

3)- CODE LIMITS FOR SLENDER SECTIONS. ECP P183-189 :


For Web h/t = 19.00 <200 OK
For Falange b/t = 9.50 <40 OK
For Lip d/t = 0.00 <40 OK

4)- CALCULATION OF EFFECTIVE PARTS :


FOR WEB
Web is Stiff subjected to Moment
K = 23.90
= -1
p = 0.1368
= 1.9674 >1
The hole web is fully effective
FOR LIP
Lip is Unstiff. Subjected to Moment.
K = 0.43
= 1
p = 0.00
= 0.00
There is no Lip
FOR FLANGE
Flange is Unstiff subjected to Comp.
K = 0.43
= 1
p = 0.5101
ECG Project Name
Job Ref.
Engineering Consultants Group CHECKING AND PACKING HALL

Bldg. 2, Block 10, El Sefarat District Calc. By Date Checked By Date Rev.

P.O.Box No. 1167, Cairo 11511, Egypt. M.Nour Sheet No.


= 1.1918
ECG Project Name
Job Ref.
Engineering Consultants Group CHECKING AND PACKING HALL

Bldg. 2, Block 10, El Sefarat District Calc. By Date Checked By Date Rev.

P.O.Box No. 1167, Cairo 11511, Egypt. M.Nour Sheet No.

The hole Flange is fully effective


Sx = 21.88 cm3 Sy = 4.99 cm3
A = 7.34 cm2 rx = 3.86 cm
ry = 1.55 cm

5)- CHECK LATERAL TORSIONAL BUCKLING :


Luact = 0.00 cm Cb = 1.13
20bf/(Fy)^0.5 = 64.55 cm
Lumax Lumax = 0.65 m
1380Af.Cb/d.Fy = 129.950 cm
Luact < Lumax
FLTB1 = 1.392 t/cm2
FLTB2 = 1.392 t/cm2 There is no LTB
FLTB = 1.392 t/cm 2

fbc = 1.94 t/cm2 Unsafe

6)- CHECK SHEAR STRESS :


qall = 0.84 t/cm2
qw = 0.11 t/cm2 < qall Safe

h
7)- CHECK DEFLECTION :-
W
L.L = 0.17 cm < span/300 Safe
E