HVAC Building

HVAC Load Analysis


for

ILC
Zamboanga City

Prepared By:

Omar D. Miguel, RME


ILC

Thursday, May 12, 2016


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Zamil Air Conditioners HVAC Building
Dhahran Airport, 31932 Page 2

General Project Data Input


General Project Information
Project file name: C:\Program Files (x86)\Elite\Chvacw\Projects\HVAC
Zamboanga.CHV
Project title: HVAC Building
Designed by: Omar D. Miguel, RME
Project date: Thursday, May 12, 2016
Project location: ZAMBOANGA, PHILIPPINES
Client name: ILC
Client address: Zamboanga City
Company name: ILC
Company representative: Omar D. Miguel, RME
Barometric pressure: 1009.669 mbar
Altitude: 6 meters
Latitude: 7 Degrees
Mean daily temperature range: 6.8889 Degrees
Starting & ending time for HVAC load calculations: 7am - 8pm
Number of unique zones in this project: 2

Building Default Values


Calculations performed: Cooling loads only
Lighting requirements: 20.00 Watts per square meter
Equipment requirements: 10.00 Watts per square meter
People sensible load multiplier: 70 Watts per person
People latent load multiplier: 45 Watts per person
Zone sensible safety factor: 10 %
Zone latent safety factor: 10 %
Zone heating safety factor: 0 %
People diversity factor: 100 %
Lighting profile number: 1
Equipment profile number: 1
People profile number: 1
Building default ceiling height: 4.50 meters
Building default wall height: 5.50 meters

Internal Operating Load Profiles (C = 100)


hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 0 0 0 0 0 0 10 C C C C 50 C C C C C 50 50 10 0 0 0 0
2 C C C C C C C C C C C C C C C C C C C C C C C C
3 C C C C C C C C C C C C C C C C C C C C C C C C
4 C C C C C C C C C C C C C C C C C C C C C C C C
5 C C C C C C C C C C C C C C C C C C C C C C C C
6 C C C C C C C C C C C C C C C C C C C C C C C C
7 C C C C C C C C C C C C C C C C C C C C C C C C
8 C C C C C C C C C C C C C C C C C C C C C C C C
9 C C C C C C C C C C C C C C C C C C C C C C C C
10 C C C C C C C C C C C C C C C C C C C C C C C C

C:\Program Files (x86)\Elite\Chvacw\Projects\HVAC Zamboanga.CHV Thursday, May 12, 2016, 3:36 PM


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Zamil Air Conditioners HVAC Building
Dhahran Airport, 31932 Page 3

General Project Data Input (cont'd)


Building-Level Design Conditions
Design Outdoor Outdoor Indoor Indoor Grams In/Outdoor
Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
March 34 27 50% 24 11.11 3
Winter 23 24

Master Roofs
Roof ASHRAE Roof Dark Susp.
No. Roof# U-Fac Color Ceil
1 6 0.419 No Yes

Master Walls
Wall ASHRAE Wall Wall
No. Group U-Fac Color
1 B 0.370 M
2 G 3.500 M

Master Partitions
Partition Partition Cool Heat
No. U-Factor T-D T-D
1 1.650 6 0

Master Glass
Glass Summer Winter Glass Interior Interior
No. U-Factor U-Factor Shd.Coef. Shading Shd.Coef
1 2.410 2.410 0.170 2 0.000

C:\Program Files (x86)\Elite\Chvacw\Projects\HVAC Zamboanga.CHV Thursday, May 12, 2016, 3:36 PM


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Zamil Air Conditioners HVAC Building
Dhahran Airport, 31932 Page 4

Building Summary Loads


Building peaks in March at 5pm.
Bldg Load Area Sen %Tot Lat Sen Net %Net
Descriptions Quan Loss Loss Gain Gain Gain Gain
Roof 121 0 0.00 0 910 910 6.51
Wall 73 0 0.00 0 249 249 1.78
Glass 40 0 0.00 0 3,285 3,285 23.50
Floor Slab 0 0 0.00 0 0 0 0.00
Skin Loads 0 0.00 0 4,444 4,444 31.79
Lighting 2,428 0 0.00 0 2,671 2,671 19.11
Equipment 1,662 0 0.00 0 1,828 1,828 13.08
People 7 0 0.00 347 539 886 6.33
Partition 35 0 0.00 0 380 380 2.72
Cool. Pret. 0 0 0.00 0 0 0 0.00
Heat. Pret. 0 0 0.00 0 0 0 0.00
Cool. Vent. 60 0 0.00 1,905 658 2,563 18.34
Heat. Vent. 0 0 0.00 0 0 0 0.00
Cool. Infil. 0 0 0.00 0 0 0 0.00
Heat. Infil. 0 0 0.00 0 0 0 0.00
Draw-Thru Fan 0 0 0.00 0 652 652 4.66
Blow-Thru Fan 0 0 0.00 0 0 0 0.00
Reserve Cap. 0 0 0.00 0 0 0 0.00
Reheat Cap. 0 0 0.00 0 0 0 0.00
Supply Duct 0 0 0.00 0 553 553 3.96
Return Duct 0 0 0.00 0 0 0 0.00
Misc. Supply 0 0 0.00 0 0 0 0.00
Misc. Return 0 0 0.00 0 0 0 0.00
Building Totals 0 0.00 2,252 11,726 13,978 100.00

Building Sen %Tot Lat Sen Net %Net


Summary Loss Loss Gain Gain Gain Gain
Ventilation 0 0.00 1,905 658 2,563 18.34
Infiltration 0 0.00 0 0 0 0.00
Pretreated Air 0 0.00 0 0 0 0.00
Zone Loads 0 0.00 347 9,863 10,209 73.04
Plenum Loads 0 0.00 0 0 0 0.00
Fan & Duct Loads 0 0.00 0 1,205 1,205 8.62
Building Totals 0 0.00 2,252 11,726 13,978 100.00

Check Figures
Total Building Supply Air (based on a 11 TD): 819 L/s
Total Building Vent. Air (7.27% of Supply): 60 L/s
Total Conditioned Air Space: 121 Sq.m
Supply Air Per Unit Area: 6.7425 L/s/Sq.m
Area Per Cooling Capacity: 8.6858 Sq.m/kW 30.5465 Sq.m/Ton
Cooling Capacity Per Area: 0.1151 kW/Sq.m 0.0327 Tons/Sq.m
Heating Capacity Per Area: 0.00 Watts/Sq.m
Total Heating Required With Outside Air: 0.00 kW
Total Cooling With Outside Air: 13.98 kW 3.97 Tons

C:\Program Files (x86)\Elite\Chvacw\Projects\HVAC Zamboanga.CHV Thursday, May 12, 2016, 3:36 PM


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Zamil Air Conditioners HVAC Building
Dhahran Airport, 31932 Page 5

Air Handler #1 - Unit-1 - Summary Loads


Zn Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Peak Time People Htg.L/s Clg.L/s S.Exh Req.L/s Req.L/s
Volume L/s/Sqm L/s/Sqm W.Exh Act.L/s Act.L/s
1 Office-1 116 0 8,807 297 None 8.5/P
5pm March 6 0 731 0 0 51
523 0.00 6.29 0 0 53

2 Kitchen-1 5 0 1,056 50 None 8.5/P


5pm March 1 0 88 41 0 9
23 0.00 16.85 0 0 6
Zone Peak Totals: 121 0 9,863 347
Total Zones: 2 7 0 819 41 0 60
Unique Zones: 2 546 0.00 6.74 0 0 60

C:\Program Files (x86)\Elite\Chvacw\Projects\HVAC Zamboanga.CHV Thursday, May 12, 2016, 3:36 PM


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Zamil Air Conditioners HVAC Building
Dhahran Airport, 31932 Page 6

Air Handler #1 - Unit-1 - Total Load Summary


Air Handler Description: Unit-1 Constant Volume - Proportion
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.65 kW
Fan Input: 75% motor and fan efficiency with 0.6 kPa across the fan
Sensible Heat Ratio: 0.97 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 5pm in March.
Outdoor Conditions: 33 DB, 27 WB, 20.71 grains
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Zone Space sensible loss: 0 Watts
Infiltration sensible loss: 0 Watts 0 L/s
Outside Air sensible loss: 0 Watts 0 L/s
Supply Duct sensible loss: 0 Watts
Return Duct sensible loss: 0 Watts
Return Plenum sensible loss: 0 Watts
Total System sensible loss: 0 Watts
Heating Supply Air: 0 / (.999 X 1.21 X 0) = 0 L/s
Winter Vent Outside Air (0.0% of supply) = 0 L/s
Zone space sensible gain: 9,863 Watts
Infiltration sensible gain: 0 Watts
Draw-thru fan sensible gain: 652 Watts
Supply duct sensible gain: 553 Watts
Reserve sensible gain: 0 Watts
Total sensible gain on supply side of coil: 11,068 Watts
Cooling Supply Air: 11,068 / (.999 X 1.23 X 11) = 819 L/s
Summer Vent Outside Air (7.3% of supply) = 60 L/s
Return duct sensible gain: 0 Watts
Return plenum sensible gain: 0 Watts
Outside air sensible gain: 658 Watts 60 L/s
Blow-thru fan sensible gain: 0 Watts
Total sensible gain on return side of coil: 658 Watts
Total sensible gain on air handling system: 11,726 Watts
Zone space latent gain: 347 Watts
Infiltration latent gain: 0 Watts
Outside air latent gain: 1,905 Watts
Total latent gain on air handling system: 2,252 Watts
Total system sensible and latent gain: 13,978 Watts

Check Figures
Total Air Handler Supply Air (based on a 11 TD): 819 L/s
Total Air Handler Vent. Air (7.27% of Supply): 60 L/s
Total Conditioned Air Space: 121 Sq.m
Supply Air Per Unit Area: 6.7425 L/s/Sq.m
Area Per Cooling Capacity: 8.6858 Sq.m/kW 30.5465 Sq.m/Ton
Cooling Capacity Per Area: 0.1151 kW/Sq.m 0.0327 Tons/Sq.m
Heating Capacity Per Area: 0.00 Watts/Sq.m
Total Heating Required With Outside Air: 0.00 kW
Total Cooling With Outside Air: 13.98 kW 3.97 Tons

C:\Program Files (x86)\Elite\Chvacw\Projects\HVAC Zamboanga.CHV Thursday, May 12, 2016, 3:36 PM


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Zamil Air Conditioners HVAC Building
Dhahran Airport, 31932 Page 7

Zone Detailed Loads (At Zone Peak Times)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Zone 1-Office-1 peaks (sensible) in March at 5pm, Air Handler 1 (Unit-1), Group 0, 116.2 x 1.0,
Construction Type: 12 (Medium)
Roof-1-6-Susp.C-L 116 0.50 16.3 0.419 792 0.233 27
Wall-1-N-B-M 32 0.83 6.1 0.370 72 0.206 7
Wall-2-W-B-M 41 0.83 10.2 0.370 154 0.206 8
Partition-3-1 9.625 6/0 1.650 95 0.000 0
Gls-N-1-90-Tran 16.9 1.000 10 2.410 398 1.340 23
0%S-0-NS-Solar 16.9 0.170 170 0.750 367
Gls-W-1-90-Tran 16.9 1.000 10 2.410 398 1.340 23
0%S-0-NS-Solar 16.9 0.170 785 0.560 1,264
Gls-W-1-90-Tran 5.7 1.000 10 2.410 134 1.340 8
0%S-0-NS-Solar 5.7 0.170 785 0.560 425
Lights-Prof=1 2,324 1.000 2,324
Equipment-Prof=1 1,162 1.000 1,162 0
People-Prof=1 6.0 1.000 420 270
Sub-total 8,006 270 0
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 8,807 297 0

Zone 2-Kitchen-1 peaks (sensible) in March at 5pm, Air Handler 1 (Unit-1), Group 0, 2.6 x 2.0,
Construction Type: 22 (Medium)
Roof-1-6-Susp.C-L 5 0.50 16.3 0.419 35 0.233 1
Partition-1-1 11 6/0 1.650 109 0.000 0
Partition-2-1 14.3 6/0 1.650 142 0.000 0
Lights-Prof=1 104 1.000 104
Equipment-Prof=1 500 1.000 500 0
People-Prof=1 1.0 1.000 70 45
Sub-total 960 45 0
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 1,056 50 0

C:\Program Files (x86)\Elite\Chvacw\Projects\HVAC Zamboanga.CHV Thursday, May 12, 2016, 3:36 PM


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Zamil Air Conditioners HVAC Building
Dhahran Airport, 31932 Page 8

Air System #1 (Unit-1) Psychrometric Analysis


System Load Analysis Latent Grams Sensible Temp L/s
Leaving Coil Condition 9.170 13.000
Draw-Thru Fan 652 0.648 48
Misc Load on Supply Side 0 0.000 0
Supply Air Duct 553 0.550 41
Zone Loads 347 0.143 9,863 9.802 729
Sensible Reserve 0 0.000 0
Zone Condition 347 9.313 11,068 24.000 819
Return Air Duct 0 0.000
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000
Vent Air 60 L/s 1,905 0.788 658 0.654
Blow-Thru Fan 0 0.000
Entering Coil Condition 2,252 10.101 11,726 24.654 819

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 1010.387)
TSH = PR x 1.23 x L/s x (DB entering - DB leaving)
TLH = PR x 2.96 x L/s x (g/kg entering - g/kg leaving)
GTH = PR x 1.20 x L/s x (Enthalpy entering - Enthalpy leaving)

TSH = 0.999 x 1.23 x 819 x( 24.654 - 13.000 )= 11,726 Watts


TLH = 0.999 x 2.96 x 819 x( 10.101 - 9.170 )= 2,255 Watts
----------
SUM = 13,981 Watts
GTH = 0.999 x 1.20 x 819 x( 50.589 - 36.308 )= 14,019 Watts
Total System Load = 13,978 Watts

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling L/s = 14,019 / ( 0.00 x 4,179 ) = 0.0 L/s
Heating L/s = 0 /( 0.00 x 4,179 ) = 0.0 L/s
Steam Req. = 0 / 970 = 0.00 kg./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 24.65 Dry bulb temperature: 24.00
Wet bulb temperature: 17.94
Relative humidity: 52.17
Enthalpy: 50.59 kJ/kg

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 13.00 Dry bulb temperature: 24.00
Wet bulb temperature: 12.84
Relative humidity: 98.23
Enthalpy: 36.31 kJ/kg

C:\Program Files (x86)\Elite\Chvacw\Projects\HVAC Zamboanga.CHV Thursday, May 12, 2016, 3:36 PM


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Zamil Air Conditioners HVAC Building
Dhahran Airport, 31932 Page 9

Air System #1 (Unit-1) Psychrometric Chart


ZC Zone Condition OC Outdoor Condition
LC Leaving Coil Condition EC Entering Coil Condition
SD Supply Duct Temperature Rise RD Return Duct Temperature Rise
DTF Draw Through Fan Sensible Gain BTF Blow Through Fan Sensible Gain
RE Reserve or Reheat Sensible Gain PL Return Air Plenum Sensible Gain
SM Supply Side Miscellaneous Sensible Gain RM Return Side Miscellaneous Gain
PRE Pretreated Air Condition

C:\Program Files (x86)\Elite\Chvacw\Projects\HVAC Zamboanga.CHV Thursday, May 12, 2016, 3:36 PM


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Zamil Air Conditioners HVAC Building
Dhahran Airport, 31932 Page 10

Building Pie Charts


Building peaks in March at 5pm.

Roof - 6.51% Supply Duct - 3.96%


Wall - 1.78% Draw-Thru Fan - 4.66%

Cool. Vent. - 18.34%


Glass - 23.50%
Building
Net
Gain
13,978
Partition - 2.72%
Watts
People - 6.33%

Lighting - 19.11% Equipment - 13.08%

C:\Program Files (x86)\Elite\Chvacw\Projects\HVAC Zamboanga.CHV Thursday, May 12, 2016, 3:36 PM


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
Zamil Air Conditioners HVAC Building
Dhahran Airport, 31932 Page 11

Air Handler #1 Pie Charts


Air Handler #1 peaks in March at 5pm.

Roof - 6.51% Supply Duct - 3.96%


Wall - 1.78% Draw-Thru Fan - 4.66%

Cool. Vent. - 18.34%


Air Glass - 23.50%
Handler
#1
Net
Gain
Partition - 2.72%
13,978
Watts
People - 6.33%

Lighting - 19.11% Equipment - 13.08%

C:\Program Files (x86)\Elite\Chvacw\Projects\HVAC Zamboanga.CHV Thursday, May 12, 2016, 3:36 PM