Professional Documents
Culture Documents
Technical Specifications
66
Technical Specifications
LOT 1 (JFPR-01-s2014)
Conductors
(44,000 Meters Conductor, Bare, ACSR #4/0, AWG 6/1)
(44,000 Meters Conductor, Bare, ACSR #2/0, AWG 6/1)
Bidders must state under the Column Statement of Compliance either Comply or Not
Comply against each of the individual parameters of each Specification stating the
corresponding performance parameter of the equipment offered. Statements of Comply or
Not Comply must be supported by evidence in a Bidders Bid and cross-referenced to that
evidence. Evidence shall be in the form of manufacturers un-amended sales literature,
unconditional statements of specification and compliance issued by the manufacturer,
samples, independent test data etc., as appropriate. A statement that is not supported by
evidence or is subsequently found to be contradicted by the evidence presented will render
the Bid under evaluation liable for rejection. A statement either in the Bidders statement of
compliance or the supporting evidence that is found to be false either during Bid evaluation,
post-qualification or the execution of the Contract may be regarded as fraudulent and render
the Bidder or supplier liable for prosecution subject to the provisions of ITB Clause 3.1(a)(ii)
and/or GCC Clause 2.1(a)(ii) .
2. Aluminum wire
STEEL CORE:
67
Section 3 of ASTM B498 as follows:
ALUMINUM WIRES:
68
CONDUCTOR STRENGTH: The
rated strength shall be the aggregate
strength of the steel and aluminum wires
determined by the methods described in
Section 9.1 of ASTM B232.
CHARACTERICTICS: ACSR
conductors shall have the following
characteristic:
SPECIFICATIONS STATEMENT OF
COMPLIANCE
69
PACKAGING AND SHIPPING: Conductor shall be
shipped on non-returnable reels manufactured from
aluminum steel or export quality preservative treated
wood lagging. Wood reels and all lagging shall be
constructed from new lumber which shall be square
sawn, be of smooth surface, with not splits, warps,
crooks, loose fibers, decay or insect infestation. The
lumber used for wood reels and all lagging shall be
preservative treated in accordance with American
Wood Preserves Associates Standards.
70
(47,000 Meters Conductor, Insulated, ACSR #2/0, AWG 6/1)
Bidders must state under the Column Statement of Compliance either Comply or Not
Comply against each of the individual parameters of each Specification stating the
corresponding performance parameter of the equipment offered. Statements of Comply or
Not Comply must be supported by evidence in a Bidders Bid and cross-referenced to that
evidence. Evidence shall be in the form of manufacturers un-amended sales literature,
unconditional statements of specification and compliance issued by the manufacturer,
samples, independent test data etc., as appropriate. A statement that is not supported by
evidence or is subsequently found to be contradicted by the evidence presented will render
the Bid under evaluation liable for rejection. A statement either in the Bidders statement of
compliance or the supporting evidence that is found to be false either during Bid evaluation,
post-qualification or the execution of the Contract may be regarded as fraudulent and render
the Bidder or supplier liable for prosecution subject to the provisions of ITB Clause 3.1(a)(ii)
and/or GCC Clause 2.1(a)(ii).
GENERAL: ACSR
conductors shall conform in
all respects to the
dimensional and
performance requirements of
this documents, which
covers:
2. Aluminum wire:
The ACSR conductors shall
be classified as Class A as
71
designated in ASTM B232
72
aluminum and steel wires
and the stranding shall
conform to the requirements
of Table 1, 2 and 3 of ASTM
B232. [1]
(f) Conductor
Strength: The rated strength
shall be the aggregate
strength of the steel and
aluminum wires determined
by the methods described in
Section 9.1 of ASTM [1].
(g) Weight and
Electrical Resistance
Insulation Jacket
Thickness of cables are:
73
SPECIFICATIONS
Performance Requirement: The cable shall
be tested to demonstrate compliance with the
requirements of Section 6 of ICEA S-66-524
(NEMA WC7, [14], in so far as applicable.
PACKAGING AND SHIPPING: Conductor
shall be shipped on non-returnable reels
manufactured from aluminum steel or export
quality preservative treated wood lagging.
Wood reels and all lagging shall be constructed
from new lumber which shall be square sawn,
be of smooth surface, with not splits, warps,
crooks, loose fibers, decay or insect infestation.
The lumber used for wood reels and all lagging
shall be preservative treated in accordance with
American Wood Preserves Associates
Standards.
REEL
READY
FOR
SHIPPING
74
Hardware
Bidders must state under the Column Statement of Compliance either Comply or Not
Comply against each of the individual parameters of each Specification stating the
corresponding performance parameter of the equipment offered. Statements of Comply or
Not Comply must be supported by evidence in a Bidders Bid and cross-referenced to that
evidence. Evidence shall be in the form of manufacturers un-amended sales literature,
unconditional statements of specification and compliance issued by the manufacturer,
samples, independent test data etc., as appropriate. A statement that is not supported by
evidence or is subsequently found to be contradicted by the evidence presented will render
the Bid under evaluation liable for rejection. A statement either in the Bidders statement of
compliance or the supporting evidence that is found to be false either during Bid evaluation,
post-qualification or the execution of the Contract may be regarded as fraudulent and render
the Bidder or supplier liable for prosecution subject to the provisions of ITB Clause 3.1(a)(ii)
and/or GCC Clause 2.1(a)(ii).
All line hardwares / materials shall meet the performance requirements application criteria
and manufacturing tolerances passed on the following standards and other applicable
standards.
STATEMENT OF
SPECIFICATIONS
COMPLIANCE
75
Attachment, Guy, Malleable Type With 11/16" Hole 758 pcs.
Diameter
Bolt, Carriage 3/8" X 4-1/2" 334 pcs.
Bolt, Double Arming, 5/8" X 22" 164 pcs.
Bolt, Double Upset, 5/8" X 10" 403 pcs.
Bolt, Oval Eye, 5/8" X 9" 538 pcs.
Bolt, Oval Eye, 5/8" X 10" 1,130 pcs.
Bolt, Oval Eye, 5/8" X 12" 90 pcs.
Bolt, Oval Eye, 5/8" X 18" 60 pcs. These
Bolt, Machine, 1/2" X 6" 10 pcs. items
must be
Bolt, Machine, 1/2" X 12" 5 pcs.
Forged
Bolt, Machine, 5/8" X 8" 1,039 pcs. Type
Bolt, Machine, 5/8" X 9" 103 pcs.
Bolt, Machine, 5/8" X 10" 504 pcs.
Bolt, Machine, 5/8" X 12" 161 pcs.
Bolt, Machine, 5/8" X 14" 64 pcs.
Bolt, Single Upset, 5/8" X 8" 140 pcs.
Bolt, Single Upset, 5/8" X 10" 298 pcs.
Brace, Crossarm, 28", Steel 334 each
Brace, Sidearm, Vertical, 50 inches 5 pcs.
Brace, Sidearm, Diagonal, 7 Feet 5 pcs.
Bracket, Clevis Deadend Without Spool 190 pcs.
Clamp, Hot Line, #2 - #4/0 ACSR Main to #2 - #4/0 229 pcs.
Clamp, Anchor Rod Bonding, Single Eye 758 pcs.
Clamp, Loop Deadend, #2/0 ACSR 2,902 pcs.
Clamp, Deadend Strain, #2/0 ACSR, Socket Eye 448 pcs.
Fitting included
Clamp, Guy Straight, 3 Bolt, Heavy Duty Steel 1,560 pcs.
Clamp, Suspension, Aluminum Alloy Clevis, 2 13 pcs.
Bolts, #2/0 ACSR Max, Socket Eye Fitting included
Clevis, Secondary Swinging Without Spool 1,469 pcs.
Shackle, Anchor, Forged Steel, Galvanized, see 73 pcs.
drawing in Annex B
Clip, Groundwire 748 pcs.
Connector, Compression, #2 - #4/0 ACSR Run To #6 2,744 pcs.
- #2
Connector, Compression, #2/0 - #4/0 ACSR Run To 601 pcs.
#2/0 - #4/0
Connector, Ground Rod (Clamp) For 5/8" Steel Rod 404 pcs.
Connector, Split Bolt 886 pcs.
Pin, Crossarm, Steel, 5/8" X 10-3/4" 146 pcs.
Hook, Guy 43 pcs.
Insulator, Pin Type, Polymer, ANSI, Class 55 - 3 250 pcs.
Insulator, Pin Type, Polymer, ANSI, Class 55 - 5 146 pcs.
76
Insulator, Spool, 1-3/4", ANSI, Class 53 - 2 1,189 pcs.
Insulator, Spool, 3", ANSI, Class 53 - 4 1,310 pcs.
Insulator, Suspension, 6", Clevis Type Polymer 922 pcs.
Nut, Eye, 5/8", Conventional 275 pcs.
Nut, Lock, Mf Type, 3/8" 334 pcs.
Nut, Lock, Mf Type, 1/2" 14 pcs.
Nut, Lock, Mf Type, 5/8" 4,714 pcs.
Pin, Pole Top, Channel, 1" Thread, 20" Long, Nylon 250 pcs.
Thread
Plate, Grounding, Pole Butt 349 pcs.
Plate, Guy 43 pcs.
Rod, Anchor, Threaded, Single Eye, 5/8" X 7' 764 pcs.
Rod, Armor, Preformed, #2/0 ACSR, Single Support 1,357 sets
Rod, Armor, Preformed, #2/0 ACSR, Double Support 50 sets
Rod, Tapping, Preformed, #2/0 ACSR 229 sets
Rod, Ground Steel, Galvanized, 5/8" X 10' 404 pcs.
Lag, Screw, 1/2" X 4" 172 pcs.
Spacer, Pipe, 3/4" X 1-1/2" 58 pcs.
Staple, Groundwire, 1/2" X 2" 703 pcs.
Washer, Square, Flat, 2-1/4" X 2-1/4" X 3/16", 13/16" 4,946 pcs.
Diameter Hole
Washer, Square, Flat, 4" X 4" X 1/2" With 7/8" 272 pcs.
Diameter Hole
Washer, Round, 1-3/8" Diameter With 9/16" Diameter 14 pcs.
Hole
Wire, Tie, Aluminum Alloy, Soft, #4 AWG 8,299 ft.
Wire, Tape, Armor, Aluminum Alloy, 0.5 " X 0.3" 1,512 ft.
Wire, Grounding, Aluminum Alloy, 3 Strand, #4 9,017 ft.
AWG
Wire, Grounding, Galvanized, 3 Strand, 5/16" 3,492 ft.
Diameter
Wire, Guy, Steel, 3/8", 7 Strand 39,432 ft.
Rectangular Crossarm, Steel, 8 ft. x 3 x 4 , gauge 176 pcs.
3.2mm, Bare Metal Thickness, Hot Dip Galvanized,
86 Microns
77
LOT 2 (JFPR-02-s2014)
Steel Poles
Bidders must state under the Column Statement of Compliance either Comply or Not
Comply against each of the individual parameters of each Specification stating the
corresponding performance parameter of the equipment offered. Statements of Comply or
Not Comply must be supported by evidence in a Bidders Bid and cross-referenced to that
evidence. Evidence shall be in the form of manufacturers un-amended sales literature,
unconditional statements of specification and compliance issued by the manufacturer,
samples, independent test data etc., as appropriate. A statement that is not supported by
evidence or is subsequently found to be contradicted by the evidence presented will render
the Bid under evaluation liable for rejection. A statement either in the Bidders statement of
compliance or the supporting evidence that is found to be false either during Bid evaluation,
post-qualification or the execution of the Contract may be regarded as fraudulent and render
the Bidder or supplier liable for prosecution subject to the provisions of ITB Clause 3.1(a)(ii)
and/or GCC Clause 2.1(a)(ii).
BIDDERS BID
STATEMENT OF
/ FORM OF
SPECIFICATION COMPLIANCE
EVIDENCE
78
shall then be bathed in a diluted acid (sulfuric or
hydrochloric) bath for at least five minutes. Just
prior to galvanizing, the acid cleaned steel shalt be
immersed in a flux solution of 30% zinc ammonium
chloride with wetting agents and maintained at 65
deg. C until galvanizing is completed. Steel poles
shall be hot dip galvanized in accordance with
ANSVASTM A153-82, Standard Specification for
Zinc Coating (Hot Dip) on Iron and Steel Hardware.
This standard requires a minimum zinc coating of
610 grams / sq. m. The coating shall be
continuous, smooth, reasonably uniform in
thickness and free of blemishes and other
imperfections which are inconsistent with
commercial practice. Galvanized articles shall be
free from coated areas, blisters, flux deposits, acid
and black spots, and dross inclusions. Lumps,
projections, globules, or heavy deposits of zinc
which will interfere with the intended use of the
material will not be permitted. All holes shall be
clean and reasonably free from excess zinc.
DIMENSION: The poles are specified in
accordance with the ANSI Standard for
classification of wood poles; that is by length
andstrength class. The first number is the overall
length in feet and the second numberis the
designation of the strength class. A 35 foot pole
with a strength classification of 5 is abbreviated
35/5.The diameter of the pole at ground line shall
be similar to an equivalent wood pole of that height
and class to assure that the earth surrounding the
pole will provide the necessary resistance to
develop the strength of the pole.
S T R E N G T H : The strength of the pole is
specified as force acting at 90 degrees to the center
line of the pole at a point two feet from the top of the
pole. The amount of force in pounds that each
classification must be able to withstand without
damage is shown on the table below;
79
Pole strength designated as a force in pounds
acting at right angles to the centerline of the pole at a point
two feet below the top of the pole, and is applicable to both
axes of the pole cross section.
Supplier's name
Month and year of manufacture
Length of pole
Class of pole
Type of coating
Pole production or serial number
80
carried to destruction.
PROCEDURE
81
breaking load up to 80% and thereafter increase by 5%
of the minimum breaking load until failure occur, hold
each load for two (2) minutes.
REPORT
Tip Desig
Butt Yield Zinc
Height Thicknes Diamet n
Diameter Stress Coating
(ft.) s (mm) er Load
(mm) (MPA) (microns)
(mm) (kg)
82
Logo:
The bidder shall provide a 50cm30cm
high quality sticker with reflective face
painted with JFPR and ODA logo for each
pole
83
84
85
86
87
88
89
90
91
92
93
94
772 Expanding Anchor
Bidders must state under the Column Statement of Compliance either Comply or Not
Comply against each of the individual parameters of each Specification stating the
corresponding performance parameter of the equipment offered. Statements of Comply or
Not Comply must be supported by evidence in a Bidders Bid and cross-referenced to that
evidence. Evidence shall be in the form of manufacturers un-amended sales literature,
unconditional statements of specification and compliance issued by the manufacturer,
samples, independent test data etc., as appropriate. A statement that is not supported by
evidence or is subsequently found to be contradicted by the evidence presented will render
the Bid under evaluation liable for rejection. A statement either in the Bidders statement of
compliance or the supporting evidence that is found to be false either during Bid evaluation,
post-qualification or the execution of the Contract may be regarded as fraudulent and render
the Bidder or supplier liable for prosecution subject to the provisions of ITB Clause 3.1(a)(ii)
and/or GCC Clause 2.1(a)(ii).
95
LOT 3 (JFPR-03-s2014)
Kwh Meters
(76 pieces Single Phase Socket Type)
Bidders must state under the Column Statement of Compliance either Comply or Not
Comply against each of the individual parameters of each Specification stating the
corresponding performance parameter of the equipment offered. Statements of Comply or
Not Comply must be supported by evidence in a Bidders Bid and cross-referenced to that
evidence. Evidence shall be in the form of manufacturers un-amended sales literature,
unconditional statements of specification and compliance issued by the manufacturer,
samples, independent test data etc., as appropriate. A statement that is not supported by
evidence or is subsequently found to be contradicted by the evidence presented will render
the Bid under evaluation liable for rejection. A statement either in the Bidders statement of
compliance or the supporting evidence that is found to be false either during Bid evaluation,
post-qualification or the execution of the Contract may be regarded as fraudulent and render
the Bidder or supplier liable for prosecution subject to the provisions of ITB Clause 3.1(a)(ii)
and/or GCC Clause 2.1(a)(ii).
Wire 2 wire
Volt 240 V
Frequency 60 Hz
Cover Plastic
Base Plastic
Phase 1 phase
Voltage Power
Consumption < 2.5 VA, 1w
Current Power
Consumption < 0.25 VA
96
KWH,KW, Current,
LCD Display Voltage
97
SPECIFICATIONS STATEMENT OF
COMPLIANCE
PACKAGING:
The purchaser reserves the right to check, and test the meters
after they arrive in the cooperative, ESAMELCO, if they are
found not to conform to the standard in all respects, they are
automatically rejected.
98
d. Current flow display
e. With provisions for sealing using wire and security
seals.
f. Temperature
- Can withstand temperature of -20c to +70c
- Humidity of up to 95% non-condensing
g. Voltage- can withstand to 180 volts uo to 290 volts.
h. Multiple level password permission of meter
i. With back light display
j. With built-in battery for LCD display and back-up
battery
k. Large digit LCD display, 16 x 7.1 mm (with
backlight-optional)
l. TOU programmable ready
m. Watt lost= 0.5 watt or better
Starting watts= less than 5 watts
- Measured/display:
- True RMS voltage
- True RMS current
- Calendar
- Time
n. 5 to 7 Digits display
ACCESSORIES
Bidders must state under the Column Statement of Compliance either Comply or Not
Comply against each of the individual parameters of each Specification stating the
corresponding performance parameter of the equipment offered. Statements of Comply or
Not Comply must be supported by evidence in a Bidders Bid and cross-referenced to that
evidence. Evidence shall be in the form of manufacturers un-amended sales literature,
unconditional statements of specification and compliance issued by the manufacturer,
samples, independent test data etc., as appropriate. A statement that is not supported by
evidence or is subsequently found to be contradicted by the evidence presented will render
the Bid under evaluation liable for rejection. A statement either in the Bidders statement of
compliance or the supporting evidence that is found to be false either during Bid evaluation,
post-qualification or the execution of the Contract may be regarded as fraudulent and render
the Bidder or supplier liable for prosecution subject to the provisions of ITB Clause 3.1(a)(ii)
and/or GCC Clause 2.1(a)(ii).
99
RF 2.0
Primary Bushing Double Single
BIDDERS BID/
STATEMENT OF
SPECIFICATIONS QTY FORM OF
COMPLIANCE
EVIDENCE
L Softswitch 76 pcs.
kWh Meter Seal, Twist Seal 158 pcs.
kWh Meter Box, Stainless Steel 12 pcs.
Standard Meter Box for Form 48A,
Hub 1" (upper position)
Socket Meter Base, Rectangular, 4 75 pcs.
Jaws, 200 Amperes Continuous, 600
Volts
Socket Meter Base, Rectangular, 7 8 pcs.
Jaws, 200 Amperes Continuous, 600
Volts
Test Block, 30 Amperes, 600 Volts, 10 12 pcs.
color
Weather Head Cap, 1" 19 pcs.
Weather Head Cap, 2"x8 inches 76 pcs.
diameter, G.I.
Wire, Stranded, Single, #10 AWG, 19 boxe
THHN or THWN 600 volts s
Miscellaneous Accessories (male 19 pcs.
adaptor, solvent, t-connector)
Bushing Reducer, G.I., 2" x 1" 7 pcs.
Nipple, G.I., 2" Dia. X 8" L 76 pcs.
100
LOT 4 (JFPR-04-s2014)
Distribution Transformer,
Accessories and Protection
Bidders must state under the Column Statement of Compliance either Comply or Not
Comply against each of the individual parameters of each Specification stating the
corresponding performance parameter of the equipment offered. Statements of Comply or
Not Comply must be supported by evidence in a Bidders Bid and cross-referenced to that
evidence. Evidence shall be in the form of manufacturers un-amended sales literature,
unconditional statements of specification and compliance issued by the manufacturer,
samples, independent test data etc., as appropriate. A statement that is not supported by
evidence or is subsequently found to be contradicted by the evidence presented will render
the Bid under evaluation liable for rejection. A statement either in the Bidders statement of
compliance or the supporting evidence that is found to be false either during Bid evaluation,
post-qualification or the execution of the Contract may be regarded as fraudulent and render
the Bidder or supplier liable for prosecution subject to the provisions of ITB Clause 3.1(a)(ii)
and/or GCC Clause 2.1(a)(ii).
SPECIFICATIONS:
ELECTRICAL
CHARACTERISTICS
Quantity 20 18 35 51
101
No load-losses (watts) 120 195 290 360
Audible Sound Level
(decibels)
48 db 48 db 48 db 48 db
Cooling Class OA OA OA OA
No. of bushings 1 2 2 2
Polarity Additive Additive Additive Additive
SPECIFICATIONS:
ELECTRICAL
CHARACTERISTICS
Statement of Statement of Statement of
KVA RATING 50 Compliance 75 Compliance 100 Compliance
Quantity 15 2 1
BIL (KV) HV 95 95 95
LV 30 30 30
2 2 2
% Impedance 10% 10% 10%
tolerance tolerance tolerance
Cooling Class OA OA OA
No. of bushings 2 2 2
102
IEC standards:
Frequency: The transformer shall be designed to operate at 60 Hz.
103
a.) Serial Number
b.) Class
d.) Frequency
h.) Polarity
j.) BIL
104
correct oil level at 25 C shall be marked inside the tank.
The tank shall be painted with two (2) coats of outdoor type, light
gray paint conforming to Munsell Notation 5BG7.0/0.4, ANSI70
Gray, over a suitable prime coat.
b) Ratio Test
105
of meeting the requirement in the following design tests:
a) Temperature Rise
b) Lightning Impulse
d) Insulation Resistance
e) Short-Circuit Capability
106
BIDDERS BID
/
STATEMENT OF
SPECIFICATIONS FORM
COMPLIANCE
OF
EVIDENCE
The low-voltage bushings shall be made from high-grade, wet-
process porcelain with the entire exposed surface to be glazed. The
color of the bushings shall be Light Gray ANSI 70, Munsell
Notation 5BG 7.0/0.4.
The low-voltage bushings shall be designated as X1, X2, X3, and
X4, depending on the transformer secondary voltage rating, shall be
arranged in accordance with the latest revision of IEEE Std
C57.12.20.
The low-voltage bushings of transformers rated 167 kVA and above
shall be designed to withstand without damage or leakage a
minimum cantilever force of 40 kg.
Bushing Terminals: The high-voltage bushing and high-voltage
neutral bushing shall be equipped with eye-bolt-type connectors
made from tinned copper-alloy material and provided with stainless
steel spring washers. The terminal connectors shall accommodate
(AWG No.8) solid to 30 mm2 (AWG No. 2) stranded copper
conductor. Terminal detail shall be in accordance with the latest
revision of IEEE Std C57.12.20.
The low-voltage bushings shall be equipped with the tinned copper
alloy, eyebolt-type connectors or tinned spade terminal pads,
arranged for vertical takeoff of cables. Size of terminal openings and
cables, and type of spade terminal pads are shown in Table 9.
Terminal details shall be in accordance with IEEE Std C57.12.20,
latest revision.
Size of
Size of Conductor
Terminal
that the Terminal Will Accommodate
Openingmm
mm2 (AWG/kcmil)
(in)
Transformer Polarity
107
13 200GrdY/ 7620 V
The tank shall be painted with two (2) coats of outdoor type, light
gray paint conforming to Munsell Notation 5BG7.0/0.4, ANSI170
Gray, over a suitable prime coat.
108
Logo: The bidder shall provide a 12cm18cm high quality sticker
with reflective face painted with JFPR and ODA logos for each
transformer.
109
Accessories and Protection
SPECIFICATION OF 15 KV VACUUM RECLOSER 12 STATEMENT BIDDERS
OF BID / FORM
Outdoor Vacuum 15 kV Reclosers COMPLIANCE OF
EVIDENCE
Manufacturer: Subject to Eligibility Requirements under Bid Data
Sheet Clauses 5.1, 5.2 and 7
Nominal operating voltage : 2.4-14.4 KV
Rated Power frequency : 60 HZ
Rated Continuous current : 630 Amps
Control voltage : 90-265 VAC / 125 VDC
Rated symmetrical
interrupting current : 8 / 10 / 12.5 / 16 A
Rated lightning
impulse withstand(BIL) 110/125
Dry withstand 60 Hz 1 Min. : 50
Wet withstand 60 Hz 10 Sec. : 45
Phase spacing : 15.50 ( 394 )
External creep distance, H2-ground : 38.00 ( 960 )
External creep distance, H1-H2 : 45.00 ( 1160 )
Min. External strike distance : 9.50 ( 240 )
Max. interrupting time : 0.030 s
Max. closing time : 0.055 s
Accessories
o Vacuum interrupter
o Epoxy bushing
o Earthing point
o Stainless steel tank
o Magnetic actuator
o Memory card
o Control cable(User Measured Length)
o Manual trip ring
o Buzzer alarm when tripped
o One (1) Unit Brand New Laptop in every three (3) units of
15KV Vacuum Recloser, for programming and event downloading
o Tripped counter
o Copper terminal lugs
Recloser functions :
Battery
o 2 sets 48 VDC, 12 AH battery bank (Std. Cabinet) or 48 VDC, 7.2
AH battery bank
110
o Sealed led acid rechargeable battery pack
o Monitor locally and remotely
o Easily accessible in low voltage control cabinet
o Allows up to 48 hours (15-27 kV) / 24 hours carryover and multiple
operations upon loss of power
o Includes capacitor backup in case of discharge or disconnected
battery
111
Special Tools SF6 Handling Equipment:
o SF6 Filing Equipment
o SF6 leakage detector
o 2 Cylinder with 10 kg. SF6 Gas
Accessories:
o Closing Coil
o Tripping Coil Cylinder with 10 kg. SF6 Gas
o Auxiliary Switch/Relays
o Contactor
Surface Protection:
o Aluminum alloy parts will not be painted
o Ferrous parts are hot-dip galvanized
o flanges of insulators are anodized aluminum sheets and operating
mechanisms get two protective coats of paint (RAL 7044)
112
Potential Transformers:
3
Voltage Transformers according to the following specifications:
113
RATINGS: Voltage and current ratings of the fuse links shall be based
on the service condition defined in ANSI C37.40 and as specified in
ANSI C37.42.
1. Quantity
2. Manufacturers identification
3. Manufacturers Catalog number and type identification.
4. Rated continuous current.
114
conductors.
Lightning Arrester:
Rated Voltage : 10 KVMCOV
: 8.4 KVBIL
: 110 KVType
: Outdoor High Current Operating
Duty
: 110 KV
RATINGS:
115
1. Rated Voltage
a. Nominal System Voltage-13.2/7.62 KV grd Y
b. Rated Maximum Voltage-15,000 volts
c. Low Frequency Withstand KV, RMS
-dry, 60 sec. -35
-wet, 10 sec. -30
DESIGN:
b. Markings
Manufacturers identification
Product type
Rated continuous current
Rated maximum voltage
Rated interrupting current
Basic impulse level
c. Contacts - silver
a) Fuse tube bone fiber lining with exterior painted gray, non-
expendable cap.
116
4. Lock Washer : All mounting bolts and conductor connectors
require lock washers. Lock washers shall be fabricated from material
that comply with the requirements of ANSI B18.21.1-1983, [4].
117