Section VII.

Technical Specifications

66
Technical Specifications
LOT 1 (JFPR-01-s2014)

Conductors
(44,000 Meters Conductor, Bare, ACSR #4/0, AWG 6/1)
(44,000 Meters Conductor, Bare, ACSR #2/0, AWG 6/1)

Bidders must state under the Column Statement of Compliance either Comply or Not
Comply against each of the individual parameters of each Specification stating the
corresponding performance parameter of the equipment offered. Statements of Comply or
Not Comply must be supported by evidence in a Bidders Bid and cross-referenced to that
evidence. Evidence shall be in the form of manufacturers un-amended sales literature,
unconditional statements of specification and compliance issued by the manufacturer,
samples, independent test data etc., as appropriate. A statement that is not supported by
evidence or is subsequently found to be contradicted by the evidence presented will render
the Bid under evaluation liable for rejection. A statement either in the Bidders statement of
compliance or the supporting evidence that is found to be false either during Bid evaluation,
post-qualification or the execution of the Contract may be regarded as fraudulent and render
the Bidder or supplier liable for prosecution subject to the provisions of ITB Clause 3.1(a)(ii)
and/or GCC Clause 2.1(a)(ii) .

SPECIFICATIONS STATEMENT BIDDERS BID /


OF
COMPLIANCE FORM OF EVIDENCE

GENERAL: ACSR conductors shall


conform in all respects to the
dimensional and performance
requirements of this document, which
covers:

1. Steel core wire

2. Aluminum wire

The ACSR conductors shall be classified


as Class A as designated in American
Society for testing and materials B232.

STEEL CORE:

Material: The steel wire shall be


fabricated from steel obtained by the
open-hearth, electric furnace, of basic
oxygen process and conforms to the
chemical composition specified in

67
Section 3 of ASTM B498 as follows:

Testing: The steel wire shall be tested in


accordance with Section 5, 6 and 10 of
ASTM B498.

Corrosion Protection: The steel wire


shall be coated with zinc to Class A
requirement with coating weight
described in Table 4 of ASTM B498.

Additional protection for ACSR


conductor against corrosion of the steel
core shall be provided by use of a
suitable corrosion inhibition, grease or
oil.

ALUMINUM WIRES:

Materials: The round aluminum sire


shall be drawn from rods that conform to
the chemical requirement of Tab le 2,
ASTM B230.

Testing: The aluminum wire shall have


tensile strengths depending on temper as
shown in Table 1 of ASTM B233.

Resistivity: The electrical resistivity


limits and values of the aluminum rods
are presented in Table 4 of ASTM B230.

LAY FACTOR: The lay factor of the


aluminum wire shall be not less than 12
nor more than 14.5 times the outside
diameter of the conductor. The preferred
lay factor is 13 times the diameter, with
the lay in a right hand direction.

CONSTRUCTION: The number and


diameter of aluminum and steel wires
and the stranding shall conform to the
requirements of Table 1, 2 and 3 of
ASTM B232.

68
CONDUCTOR STRENGTH: The
rated strength shall be the aggregate
strength of the steel and aluminum wires
determined by the methods described in
Section 9.1 of ASTM B232.

WEIGHT AND ELECTRICAL


RESISTANCE: The weight and
electrical resistance of the stranded
conductor shall be determined by the
methods described in Section 11 of
ASTM B233.

CHARACTERICTICS: ACSR
conductors shall have the following
characteristic:

FINISH: The conductor shall be free of


imperfections, sharp protrusions and
blemishes not consistent with good
commercial practice.

SPECIFICATIONS STATEMENT OF
COMPLIANCE

TESTS & INSPECTION: The manufacturer shall


conduct conductor tests and inspections in accordance
with Section 16 of ASTM B232 or IEC 888, in so far as
applicable. NEA reserves the right to witness factory
tests and inspections and shall request test reports. The
manufacturer shall also conduct conductor reel tests and
inspections and submit test reports before shipment to
verify that the reel and lagging comply with the
requirements of this Standard. NEA shall also have the
prerogative to inspect conductor reels at any time to
ensure compliance of this standard. Non- conforming
reels and lagging are unacceptable.

69
PACKAGING AND SHIPPING: Conductor shall be
shipped on non-returnable reels manufactured from
aluminum steel or export quality preservative treated
wood lagging. Wood reels and all lagging shall be
constructed from new lumber which shall be square
sawn, be of smooth surface, with not splits, warps,
crooks, loose fibers, decay or insect infestation. The
lumber used for wood reels and all lagging shall be
preservative treated in accordance with American
Wood Preserves Associates Standards.

REEL READY FOR SHIPPING

70
(47,000 Meters Conductor, Insulated, ACSR #2/0, AWG 6/1)

Bidders must state under the Column Statement of Compliance either Comply or Not
Comply against each of the individual parameters of each Specification stating the
corresponding performance parameter of the equipment offered. Statements of Comply or
Not Comply must be supported by evidence in a Bidders Bid and cross-referenced to that
evidence. Evidence shall be in the form of manufacturers un-amended sales literature,
unconditional statements of specification and compliance issued by the manufacturer,
samples, independent test data etc., as appropriate. A statement that is not supported by
evidence or is subsequently found to be contradicted by the evidence presented will render
the Bid under evaluation liable for rejection. A statement either in the Bidders statement of
compliance or the supporting evidence that is found to be false either during Bid evaluation,
post-qualification or the execution of the Contract may be regarded as fraudulent and render
the Bidder or supplier liable for prosecution subject to the provisions of ITB Clause 3.1(a)(ii)
and/or GCC Clause 2.1(a)(ii).

SPECIFICATIONS STATEMENT OF BIDDERS BID /


COMPLIANCE FORM OF EVIDENCE
SCOPE: This standard
establishes the dimensional
and performance
requirements of bare coated
steel-reinforced concentric-
lay-stranded aluminum
conductors (ACSR),
Crosslinked polyethylene
insulated (black colored),
600V to be used on Coop
distribution lines. This
conductor is made of round
aluminum wires wrapped
around a central zinc-coated
round steel-wire core.

GENERAL: ACSR
conductors shall conform in
all respects to the
dimensional and
performance requirements of
this documents, which
covers:

1. Steel core wire.

2. Aluminum wire:
The ACSR conductors shall
be classified as Class A as

71
designated in ASTM B232

3. Steel Core: The steel


core shall consist of wires
which meet the following
requirements:

(a) Material: The steel


wire shall be fabricated from
steel obtained by the open-
hearth, electric furnace.
(b) Testing: The steel
wire shall be tested in
accordance with Section 5, 6
and 10 of ASTM B498.
(c) Corrosion Protection:
The steel wire shall be coated
with zinc to Class A
requirements with coating
weight described in Table 4
of ASTM B498 [2].
Additional protection for
ACSR conductor against
corrosion of the steel core
shall be provided by use of a
suitable corrosion
inhabitation, grease or oil.
(d) Aluminum Wires:
1. Materials: The round
aluminum wire shall be
drawn from rods that
conform to the chemical
requirements of table 2,
ASTM B230 [3]
2. Testing : The
aluminum wire shall have
tensile strengths depending
on temper as shown in Table
1 of ASTM B233 [4]
3. Resistivity: The
electrical resistivity limits
and values of the aluminum
rods are presented in Table 4
of ASTM B230 [3].
4. General : Aluminum
wires used shall meet the
requirements of ASTM B230
[3].
(e) Construction: The
number and diameter of

72
aluminum and steel wires
and the stranding shall
conform to the requirements
of Table 1, 2 and 3 of ASTM
B232. [1]
(f) Conductor
Strength: The rated strength
shall be the aggregate
strength of the steel and
aluminum wires determined
by the methods described in
Section 9.1 of ASTM [1].
(g) Weight and
Electrical Resistance

The weight and electrical


resistance of the stranded
conductor shall be
determined by the methods
described in Section 11 of
ASTM B232 [1].

Insulation Jacket
Thickness of cables are:

Conductor Size AWG


2/0

Insulation Thickness (mils)


60

73
SPECIFICATIONS
Performance Requirement: The cable shall
be tested to demonstrate compliance with the
requirements of Section 6 of ICEA S-66-524
(NEMA WC7, [14], in so far as applicable.
PACKAGING AND SHIPPING: Conductor
shall be shipped on non-returnable reels
manufactured from aluminum steel or export
quality preservative treated wood lagging.
Wood reels and all lagging shall be constructed
from new lumber which shall be square sawn,
be of smooth surface, with not splits, warps,
crooks, loose fibers, decay or insect infestation.
The lumber used for wood reels and all lagging
shall be preservative treated in accordance with
American Wood Preserves Associates
Standards.

REEL
READY
FOR
SHIPPING

74
Hardware
Bidders must state under the Column Statement of Compliance either Comply or Not
Comply against each of the individual parameters of each Specification stating the
corresponding performance parameter of the equipment offered. Statements of Comply or
Not Comply must be supported by evidence in a Bidders Bid and cross-referenced to that
evidence. Evidence shall be in the form of manufacturers un-amended sales literature,
unconditional statements of specification and compliance issued by the manufacturer,
samples, independent test data etc., as appropriate. A statement that is not supported by
evidence or is subsequently found to be contradicted by the evidence presented will render
the Bid under evaluation liable for rejection. A statement either in the Bidders statement of
compliance or the supporting evidence that is found to be false either during Bid evaluation,
post-qualification or the execution of the Contract may be regarded as fraudulent and render
the Bidder or supplier liable for prosecution subject to the provisions of ITB Clause 3.1(a)(ii)
and/or GCC Clause 2.1(a)(ii).

All line hardwares / materials shall meet the performance requirements application criteria
and manufacturing tolerances passed on the following standards and other applicable
standards.
STATEMENT OF
SPECIFICATIONS
COMPLIANCE

ANSI C B5. 1-1979


American National Standard for Galvanized Steel bolts and nuts for
overhead line construction.

ANSI C135. 31-1980


American National Standard for Galvanized ferrous Single and
Double Upset Spool Insulator bolts for Overhead line Construction.
ANSI C29.3-1986
American National Standard for Wet-process porcelain insulator
(Spool type)
ASTM A663-82
Standard Specification for steel bars, carbon, merchant quality,
mechanical properties.
ASTM A675-82
Standard Specification for steel bars, carbon, hot wrought, special
quality, mechanical properties.
ASTM A675-82
Standard Specification for steel bars, carbon, hot wrought, special
quality, mechanical properties.
ASTM A570-79
Standard Specification for hot-rolled, carbon, steel sheet and strip,
structural quality.

MATERIALS QTY UNIT STATEMENT


OF
COMPLIANCE

75
Attachment, Guy, Malleable Type With 11/16" Hole 758 pcs.
Diameter
Bolt, Carriage 3/8" X 4-1/2" 334 pcs.
Bolt, Double Arming, 5/8" X 22" 164 pcs.
Bolt, Double Upset, 5/8" X 10" 403 pcs.
Bolt, Oval Eye, 5/8" X 9" 538 pcs.
Bolt, Oval Eye, 5/8" X 10" 1,130 pcs.
Bolt, Oval Eye, 5/8" X 12" 90 pcs.
Bolt, Oval Eye, 5/8" X 18" 60 pcs. These
Bolt, Machine, 1/2" X 6" 10 pcs. items
must be
Bolt, Machine, 1/2" X 12" 5 pcs.
Forged
Bolt, Machine, 5/8" X 8" 1,039 pcs. Type
Bolt, Machine, 5/8" X 9" 103 pcs.
Bolt, Machine, 5/8" X 10" 504 pcs.
Bolt, Machine, 5/8" X 12" 161 pcs.
Bolt, Machine, 5/8" X 14" 64 pcs.
Bolt, Single Upset, 5/8" X 8" 140 pcs.
Bolt, Single Upset, 5/8" X 10" 298 pcs.
Brace, Crossarm, 28", Steel 334 each
Brace, Sidearm, Vertical, 50 inches 5 pcs.
Brace, Sidearm, Diagonal, 7 Feet 5 pcs.
Bracket, Clevis Deadend Without Spool 190 pcs.
Clamp, Hot Line, #2 - #4/0 ACSR Main to #2 - #4/0 229 pcs.
Clamp, Anchor Rod Bonding, Single Eye 758 pcs.
Clamp, Loop Deadend, #2/0 ACSR 2,902 pcs.
Clamp, Deadend Strain, #2/0 ACSR, Socket Eye 448 pcs.
Fitting included
Clamp, Guy Straight, 3 Bolt, Heavy Duty Steel 1,560 pcs.
Clamp, Suspension, Aluminum Alloy Clevis, 2 13 pcs.
Bolts, #2/0 ACSR Max, Socket Eye Fitting included
Clevis, Secondary Swinging Without Spool 1,469 pcs.
Shackle, Anchor, Forged Steel, Galvanized, see 73 pcs.
drawing in Annex B
Clip, Groundwire 748 pcs.
Connector, Compression, #2 - #4/0 ACSR Run To #6 2,744 pcs.
- #2
Connector, Compression, #2/0 - #4/0 ACSR Run To 601 pcs.
#2/0 - #4/0
Connector, Ground Rod (Clamp) For 5/8" Steel Rod 404 pcs.
Connector, Split Bolt 886 pcs.
Pin, Crossarm, Steel, 5/8" X 10-3/4" 146 pcs.
Hook, Guy 43 pcs.
Insulator, Pin Type, Polymer, ANSI, Class 55 - 3 250 pcs.
Insulator, Pin Type, Polymer, ANSI, Class 55 - 5 146 pcs.

76
Insulator, Spool, 1-3/4", ANSI, Class 53 - 2 1,189 pcs.
Insulator, Spool, 3", ANSI, Class 53 - 4 1,310 pcs.
Insulator, Suspension, 6", Clevis Type Polymer 922 pcs.
Nut, Eye, 5/8", Conventional 275 pcs.
Nut, Lock, Mf Type, 3/8" 334 pcs.
Nut, Lock, Mf Type, 1/2" 14 pcs.
Nut, Lock, Mf Type, 5/8" 4,714 pcs.
Pin, Pole Top, Channel, 1" Thread, 20" Long, Nylon 250 pcs.
Thread
Plate, Grounding, Pole Butt 349 pcs.
Plate, Guy 43 pcs.
Rod, Anchor, Threaded, Single Eye, 5/8" X 7' 764 pcs.
Rod, Armor, Preformed, #2/0 ACSR, Single Support 1,357 sets
Rod, Armor, Preformed, #2/0 ACSR, Double Support 50 sets
Rod, Tapping, Preformed, #2/0 ACSR 229 sets
Rod, Ground Steel, Galvanized, 5/8" X 10' 404 pcs.
Lag, Screw, 1/2" X 4" 172 pcs.
Spacer, Pipe, 3/4" X 1-1/2" 58 pcs.
Staple, Groundwire, 1/2" X 2" 703 pcs.
Washer, Square, Flat, 2-1/4" X 2-1/4" X 3/16", 13/16" 4,946 pcs.
Diameter Hole
Washer, Square, Flat, 4" X 4" X 1/2" With 7/8" 272 pcs.
Diameter Hole
Washer, Round, 1-3/8" Diameter With 9/16" Diameter 14 pcs.
Hole
Wire, Tie, Aluminum Alloy, Soft, #4 AWG 8,299 ft.
Wire, Tape, Armor, Aluminum Alloy, 0.5 " X 0.3" 1,512 ft.
Wire, Grounding, Aluminum Alloy, 3 Strand, #4 9,017 ft.
AWG
Wire, Grounding, Galvanized, 3 Strand, 5/16" 3,492 ft.
Diameter
Wire, Guy, Steel, 3/8", 7 Strand 39,432 ft.
Rectangular Crossarm, Steel, 8 ft. x 3 x 4 , gauge 176 pcs.
3.2mm, Bare Metal Thickness, Hot Dip Galvanized,
86 Microns

77
LOT 2 (JFPR-02-s2014)

Steel Poles
Bidders must state under the Column Statement of Compliance either Comply or Not
Comply against each of the individual parameters of each Specification stating the
corresponding performance parameter of the equipment offered. Statements of Comply or
Not Comply must be supported by evidence in a Bidders Bid and cross-referenced to that
evidence. Evidence shall be in the form of manufacturers un-amended sales literature,
unconditional statements of specification and compliance issued by the manufacturer,
samples, independent test data etc., as appropriate. A statement that is not supported by
evidence or is subsequently found to be contradicted by the evidence presented will render
the Bid under evaluation liable for rejection. A statement either in the Bidders statement of
compliance or the supporting evidence that is found to be false either during Bid evaluation,
post-qualification or the execution of the Contract may be regarded as fraudulent and render
the Bidder or supplier liable for prosecution subject to the provisions of ITB Clause 3.1(a)(ii)
and/or GCC Clause 2.1(a)(ii).

BIDDERS BID
STATEMENT OF
/ FORM OF
SPECIFICATION COMPLIANCE
EVIDENCE

S C O P E : This specification establishes the


physical characteristics and performance
requirements of steel poles for use on Eastern
Samar Electric Cooperatives, Inc. electric
distribution system. Poles furnished to NEA
specifications shall conform in all respects to the
performance of this standard. The text, figures and
references of other standards supplement each
other and shall be considered part of this standard.
The poles are to be of the embedded type and not
to require a special foundation.

MATERIAL: Steel poles shall be fabricated from


structural quality hot rolled steel which conforms to
ASTM A570-79, 'Standard Specification for Hot-
Rolled Carbon Steel Sheet and Strip, Structural
Quality.'

FINISHING: The pole shall be cleaned of scale,


rust, oil, paint and other surface contaminants and
then rinsed in an alkaline cleaning bath. The steel

78
shall then be bathed in a diluted acid (sulfuric or
hydrochloric) bath for at least five minutes. Just
prior to galvanizing, the acid cleaned steel shalt be
immersed in a flux solution of 30% zinc ammonium
chloride with wetting agents and maintained at 65
deg. C until galvanizing is completed. Steel poles
shall be hot dip galvanized in accordance with
ANSVASTM A153-82, Standard Specification for
Zinc Coating (Hot Dip) on Iron and Steel Hardware.
This standard requires a minimum zinc coating of
610 grams / sq. m. The coating shall be
continuous, smooth, reasonably uniform in
thickness and free of blemishes and other
imperfections which are inconsistent with
commercial practice. Galvanized articles shall be
free from coated areas, blisters, flux deposits, acid
and black spots, and dross inclusions. Lumps,
projections, globules, or heavy deposits of zinc
which will interfere with the intended use of the
material will not be permitted. All holes shall be
clean and reasonably free from excess zinc.
DIMENSION: The poles are specified in
accordance with the ANSI Standard for
classification of wood poles; that is by length
andstrength class. The first number is the overall
length in feet and the second numberis the
designation of the strength class. A 35 foot pole
with a strength classification of 5 is abbreviated
35/5.The diameter of the pole at ground line shall
be similar to an equivalent wood pole of that height
and class to assure that the earth surrounding the
pole will provide the necessary resistance to
develop the strength of the pole.
S T R E N G T H : The strength of the pole is
specified as force acting at 90 degrees to the center
line of the pole at a point two feet from the top of the
pole. The amount of force in pounds that each
classification must be able to withstand without
damage is shown on the table below;

POLE STRENGTH AND GROUND LINE


DIMENSION
POLE
STRENGTH PIECES
LENGTH
30/2 3700 588
35/2 3700 362
40/2 3700 40
Pole length in feet and strength classification.

79
Pole strength designated as a force in pounds
acting at right angles to the centerline of the pole at a point
two feet below the top of the pole, and is applicable to both
axes of the pole cross section.

SPECIFICATIONS STATEMENT OF COMPLIANCE

MARKINGS: Each steel pole shall be identified by


the supplier by stamping into the pole, prior to
coating, with letters not less than 1/2" high squarely
on the face of the pole at ten (10) feet from the butt
of the pole. The following information shall be
stamped into the pole:

Supplier's name
Month and year of manufacture
Length of pole
Class of pole
Type of coating
Pole production or serial number

The marks shall be legible after application of


the protective coating.

INSPECTION AND TESTING:


The manufacturer shall conduct factory tests to
verify that the poles comply with the requirements
of this standard. NEA reserves the right to witness
ANY OR ALL factory tests and the Supplier shall
notify NEA fifteen (15) days before each test is to be
conducted. The Supplier is required to furnish NEA
a copy of all test reports. NEA expects to
commission an internationally recognized third
party, independent inspection and/or testing agency
for independent inspection and/or testing at the
factory, prior to shipping or after receipt of the poles
in the Philippines. The galvanizing shall be tested in
accordance with ASTM Standard A 123-89. Any
pole that fails an inspection is automatically rejected
and additional poles from that lot must be tested in
accordance with the following testing schedule:

TESTING SCHEDULE: One pole out of


every lot of 25 poles shall be tested to 50 percent of
its rated strength and a record kept of the deflection
after a two (2) minute hold at each multiple of 10
percent. This is a non-destructive test unless it
shows some weakness indicating the pole could not
meet the strength requirements and then it is to be

80
carried to destruction.

One pole out of every lot of 100 poles shall be


tested to destruction. If it fails at less than rated
strength, then four additional poles from the same
lot shall be tested to rated load. If they all pass, the
lot is considered to have passed that test. If two or
more of the additional test poles fail, the entire lot
will be rejected. If only one of them fails, ten more
from the same lot may be tested to rated load. If
there are no failures, the remaining poles of that lot
are considered to have passed that test, however, if
there are any failures in these ten, and then the lot
is automatically rejected.

PROCEDURE

Proof Load Test:

Initially set the dynamometer to a load of 40% of


the minimum breaking load. Apply load steadily
until it reaches 40%. Hold for two (2) minutes.
Note for the development of weld cracks or
splitting. If any appear at the 40 % load, the pole is
considered to have FAILED the test and the batch
represented shall be rejected.

Break Load Test: Initially set the dynamometer to a


load of 40% of the minimum breaking load. Apply
load steadily until it reaches 40%. Hold for one (1)
minute. Note for the development of weld splits or
cracks. If cracks appear at 40% load, the pole is
considered to have failed the test. The batch
represented shall be rejected.

If no cracks or splits appear after the application of


40% load, set the dynamometer to a load of 50% of
the minimum breaking load. Apply load steadily until
it reaches 50%. Hold for one (1) minute. Note for the
development of cracks or splits. If found the pole is
considered to have failed the test. Release load to zero.

Upon removal of the load, immediately increase


the load gradually to 70% of the minimum
breaking load and hold for two (2) minutes. Note
for the development of additional cracks or splits.

Again remove the load and sussessivety increase the


load by an amount equal to 10% of the minimum

81
breaking load up to 80% and thereafter increase by 5%
of the minimum breaking load until failure occur, hold
each load for two (2) minutes.

Measure load at the point of failure to the nearest 5


kilograms.

The pole is considered to have failed the break


load test if it yielded at less than the minimum
breaking load.

REPORT

For tests conducted at source, the test shall be


prepared by the manufacturer in coordination with
the witnessing inspection engineer or test engineer.

The following test data shall be collected and


recorded in accordance with the attached format:

Manufacturer's serial numbers of the test


pole sample.
Pole Class
Date Manufactured
Date Tested
Pole dimensions
Load, including point of failure
Deflection
Recovery

Galvanizing thickness measured at ground line,


pole butt and pole top

Tip Desig
Butt Yield Zinc
Height Thicknes Diamet n
Diameter Stress Coating
(ft.) s (mm) er Load
(mm) (MPA) (microns)
(mm) (kg)

30 3.5 226 127 750 345 86

35 3.5 248 127 750 345 86

40 3.5 317 127 750 345 86

82
Logo:
The bidder shall provide a 50cm30cm
high quality sticker with reflective face
painted with JFPR and ODA logo for each
pole

83
84
85
86
87
88
89
90
91
92
93
94
772 Expanding Anchor
Bidders must state under the Column Statement of Compliance either Comply or Not
Comply against each of the individual parameters of each Specification stating the
corresponding performance parameter of the equipment offered. Statements of Comply or
Not Comply must be supported by evidence in a Bidders Bid and cross-referenced to that
evidence. Evidence shall be in the form of manufacturers un-amended sales literature,
unconditional statements of specification and compliance issued by the manufacturer,
samples, independent test data etc., as appropriate. A statement that is not supported by
evidence or is subsequently found to be contradicted by the evidence presented will render
the Bid under evaluation liable for rejection. A statement either in the Bidders statement of
compliance or the supporting evidence that is found to be false either during Bid evaluation,
post-qualification or the execution of the Contract may be regarded as fraudulent and render
the Bidder or supplier liable for prosecution subject to the provisions of ITB Clause 3.1(a)(ii)
and/or GCC Clause 2.1(a)(ii).

MATERIALS QTY UNIT STATEMENT BIDDERS BID /


OF FORM OF
COMPLIANCE EVIDENCE
Anchor, Expanding, 8,000 Pounds, 772 pcs.
8 Way, Hot Dip Galvanized Steel,
8mm Galv. Steel, Base Plate
Inches, 8", top plate sq. inch 135

95
LOT 3 (JFPR-03-s2014)

Kwh Meters
(76 pieces Single Phase Socket Type)
Bidders must state under the Column Statement of Compliance either Comply or Not
Comply against each of the individual parameters of each Specification stating the
corresponding performance parameter of the equipment offered. Statements of Comply or
Not Comply must be supported by evidence in a Bidders Bid and cross-referenced to that
evidence. Evidence shall be in the form of manufacturers un-amended sales literature,
unconditional statements of specification and compliance issued by the manufacturer,
samples, independent test data etc., as appropriate. A statement that is not supported by
evidence or is subsequently found to be contradicted by the evidence presented will render
the Bid under evaluation liable for rejection. A statement either in the Bidders statement of
compliance or the supporting evidence that is found to be false either during Bid evaluation,
post-qualification or the execution of the Contract may be regarded as fraudulent and render
the Bidder or supplier liable for prosecution subject to the provisions of ITB Clause 3.1(a)(ii)
and/or GCC Clause 2.1(a)(ii).

SINGLE PHASE KWH BIDDERS BID /


STATEMENT OF
PARAMETERS METER FORM OF
COMPLIANCE
SPECIFICATIONS EVIDENCE

Accuracy class Class 0.5 or better

Wire 2 wire

Volt 240 V

Current Range 0.1 A to 200 A

Frequency 60 Hz

Register Type LCD

Cover Plastic

Base Plastic

Phase 1 phase
Voltage Power
Consumption < 2.5 VA, 1w
Current Power
Consumption < 0.25 VA

96
KWH,KW, Current,
LCD Display Voltage

(7 pieces Three Phase Socket Type)


3 PHASE KWH
STATEMENT OF BIDDERS BID /
PARAMETERS METER
COMPLIANCE FORM OF EVIDENCE
SPECIFICATIONS
Accuracy CA 0.2 or better
Class 200
Wire 4 wire
Volt 120-480V
Test Amper 30A
Frequency 60 Hz
Register Type LCD
Meter Constant (Kh) 21.6
Cover Plastic
Vbase Plastic
Form FM16S
Phase 3 Phase
TOU Ready
Soft Switch A, K, N, P
LCD Display Programmable

(12 pieces Three Phase Bottom Type)


3 PHASE KWH
STATEMENT OF BIDDERS BID /
PARAMETERS METER
COMPLIANCE FORM OF EVIDENCE
SPECIFICATIONS
Accuracy CA 0.5 or better
Class 20
Wire 4 wire
Volt 120-480V
Test Amper 2.5A
Frequency 60 Hz
Register Type LCD
Meter Constant (Kh) 1.8
Cover Plastic
Vbase Plastic
Form FM48A
Phase 3 Phase
TOU Ready
Soft Switch A, K, N, P
LCD Display Programmable

97
SPECIFICATIONS STATEMENT OF
COMPLIANCE

Transparent glass cover (good plastic) for durability and easy


reading. Glass cover shall effectively seal the meter to
prevent the entry of rain and dust into its internal parts.

It shall be designed to operate continuously for the normal


life of the meter in an unsheltered outdoor tropical location
exposed to the elements without rust, corrosion, or other
damage which might adversely affect the meters accuracy or
reliability.

The kwh meter shall have ESAMELCO printed in English


with black letters at least 3/8, to be checked (3.2 cm) high on
the face plate.

Bidder shall submit dimensional drawings, pictures, catalog


information, data on starting watts and losses, characteristic
performance curves and instruction bulletins for adjustment,
installation and storage meters.

INSPECTION: The manufacturer shall perform the


necessary inspection and test to determine if the watt-hour
meters comply with the specifications and supply certified
test reports that give proof of conformance to the
performance standards in all respects. All information, test
reports, instruction look, etc., shall be written in English.
NEA reserves the right to witness factory tests.

PACKAGING:

The kWh meters shall be individually packaged in a suitable


container for a tropical climate. Each container (box) shall be
clearly labeled with manufacturer name and catalog no.

The purchaser reserves the right to check, and test the meters
after they arrive in the cooperative, ESAMELCO, if they are
found not to conform to the standard in all respects, they are
automatically rejected.

The kWh meter shall have the following features:

a. Anti-pilferage capability (pilferage proof)


b. Tamper proof-can measure reverse current
c. Wrong wiring alarm

98
d. Current flow display
e. With provisions for sealing using wire and security
seals.
f. Temperature
- Can withstand temperature of -20c to +70c
- Humidity of up to 95% non-condensing
g. Voltage- can withstand to 180 volts uo to 290 volts.
h. Multiple level password permission of meter
i. With back light display
j. With built-in battery for LCD display and back-up
battery
k. Large digit LCD display, 16 x 7.1 mm (with
backlight-optional)
l. TOU programmable ready
m. Watt lost= 0.5 watt or better
Starting watts= less than 5 watts
- Measured/display:
- True RMS voltage
- True RMS current
- Calendar
- Time
n. 5 to 7 Digits display

ACCESSORIES
Bidders must state under the Column Statement of Compliance either Comply or Not
Comply against each of the individual parameters of each Specification stating the
corresponding performance parameter of the equipment offered. Statements of Comply or
Not Comply must be supported by evidence in a Bidders Bid and cross-referenced to that
evidence. Evidence shall be in the form of manufacturers un-amended sales literature,
unconditional statements of specification and compliance issued by the manufacturer,
samples, independent test data etc., as appropriate. A statement that is not supported by
evidence or is subsequently found to be contradicted by the evidence presented will render
the Bid under evaluation liable for rejection. A statement either in the Bidders statement of
compliance or the supporting evidence that is found to be false either during Bid evaluation,
post-qualification or the execution of the Contract may be regarded as fraudulent and render
the Bidder or supplier liable for prosecution subject to the provisions of ITB Clause 3.1(a)(ii)
and/or GCC Clause 2.1(a)(ii).

Parameters Current Statement Potential Statement of


Transformer of Transformer Compliance
Compliance
Primary Voltage 15KV 15Kv
BIL 110KV 110Kv
Frequency 60Hz 60Hz
Ratio 15/10:5 70:1
Acc. Class 0.3 0.3

99
RF 2.0
Primary Bushing Double Single

BIDDERS BID/
STATEMENT OF
SPECIFICATIONS QTY FORM OF
COMPLIANCE
EVIDENCE
L Softswitch 76 pcs.
kWh Meter Seal, Twist Seal 158 pcs.
kWh Meter Box, Stainless Steel 12 pcs.
Standard Meter Box for Form 48A,
Hub 1" (upper position)
Socket Meter Base, Rectangular, 4 75 pcs.
Jaws, 200 Amperes Continuous, 600
Volts
Socket Meter Base, Rectangular, 7 8 pcs.
Jaws, 200 Amperes Continuous, 600
Volts
Test Block, 30 Amperes, 600 Volts, 10 12 pcs.
color
Weather Head Cap, 1" 19 pcs.
Weather Head Cap, 2"x8 inches 76 pcs.
diameter, G.I.
Wire, Stranded, Single, #10 AWG, 19 boxe
THHN or THWN 600 volts s
Miscellaneous Accessories (male 19 pcs.
adaptor, solvent, t-connector)
Bushing Reducer, G.I., 2" x 1" 7 pcs.
Nipple, G.I., 2" Dia. X 8" L 76 pcs.

100
LOT 4 (JFPR-04-s2014)

Distribution Transformer,
Accessories and Protection
Bidders must state under the Column Statement of Compliance either Comply or Not
Comply against each of the individual parameters of each Specification stating the
corresponding performance parameter of the equipment offered. Statements of Comply or
Not Comply must be supported by evidence in a Bidders Bid and cross-referenced to that
evidence. Evidence shall be in the form of manufacturers un-amended sales literature,
unconditional statements of specification and compliance issued by the manufacturer,
samples, independent test data etc., as appropriate. A statement that is not supported by
evidence or is subsequently found to be contradicted by the evidence presented will render
the Bid under evaluation liable for rejection. A statement either in the Bidders statement of
compliance or the supporting evidence that is found to be false either during Bid evaluation,
post-qualification or the execution of the Contract may be regarded as fraudulent and render
the Bidder or supplier liable for prosecution subject to the provisions of ITB Clause 3.1(a)(ii)
and/or GCC Clause 2.1(a)(ii).

SPECIFICATIONS:

ELECTRICAL
CHARACTERISTICS

Statement of Statement of Statement Statement of


KVA RATING 10 Compliance 15 Compliance 25 of Compliance 37.5 Compliance

Quantity 20 18 35 51

Voltage Primary 7620 v/ 7620v/ 7620 v/


7620 v
13200Y v 13200Y v 13200Y v
Secondary (v) 240 240 240 240
Frequency (H2) 60 Hz 60 Hz 60 Hz 60 Hz
95
T of compliaBIL (KV) HV 95 95 95
LV 30 30 30 30
2 2 2 2
% Impedance 10% 10% 10% 10%
tolerance tolerance tolerance tolerance
Load losses (watts)
36 50 80 105

101
No load-losses (watts) 120 195 290 360
Audible Sound Level
(decibels)
48 db 48 db 48 db 48 db
Cooling Class OA OA OA OA
No. of bushings 1 2 2 2
Polarity Additive Additive Additive Additive

SPECIFICATIONS:
ELECTRICAL
CHARACTERISTICS
Statement of Statement of Statement of
KVA RATING 50 Compliance 75 Compliance 100 Compliance
Quantity 15 2 1

Voltage Primary 7620 v/ 7620v/


7620 v
13200Y v 13200Y v
Secondary (v) 240 240 240
Frequency (H2) 60 Hz 60 Hz 60 Hz

BIL (KV) HV 95 95 95
LV 30 30 30
2 2 2
% Impedance 10% 10% 10%
tolerance tolerance tolerance

Load losses (watts) 135 190 210

No load-losses (watts) 500 650 850

Audible Sound Level (decibels)48 db 48 db 48 db

Cooling Class OA OA OA

No. of bushings 2 2 2

Polarity Additive Additive Additive

SPECIFICATIONS STATEMENT BIDDERS


OF BID/
COMPLIANCE FORM OF
EVIDENCE
Applicable Standards: All transformers furnished under this
specification shall be designed, manufactured and tested to meet or
exceed the requirements of the latest revision of the following
IEEE, ANSI IEEE. NEMA and ASTM Standards or equivalent

102
IEC standards:
Frequency: The transformer shall be designed to operate at 60 Hz.

KVA Ratings: The kVA rating shall be continuous and based on


not exceeding either a 65 C average winding temperature rise or
an 80 C hottest-spot temperature rise above an ambient of 30 C.
The temperature rise of the insulating oil shall not exceed 65 C
when measured near the top of the tank (IEEE Std C57.12.20).
Short-Circuit Characteristics: The transformer shall withstand
the mechanical and thermal stresses produced by external short-
circuit currents specified in IEEE Std 057.12.00, latest revision.
Loading Capability: The transformer shall be guaranteed to have
the loading capability in accordance with ANSI IEEE Std C 57.92,
latest revision
Audible Sound Level: Transformers shall he designed so that the
average sound level does not exceed the values specified.
Cooling Class: The cooling method employed for transformers
supplied under this specification shall be self-cooled (OA or
ONAN).

Core-Coil Assembly: Transformer core shall be manufactured


using either low-loss high-permeability grain-oriented silicon steel
or amorphous metal.
Transformer windings shall be made of high-conductivity copper,
The core and coil assembly shall be mounted rigidly in the tank.
The assembly shall not shift in direction during shipping, handling,
installation, or during normal operation due to vibrations.
The core and coil assembly shall he vacuum processed to ensure
maximum penetration of the insulating liquid to the coil insulation
system.

Insulating Liquid: The transformer shall be filled with unused


mineral oil meeting the requirements of the latest revision of
ASTM D3487 (Specification of Mineral Insulating Oil Used in
Electrical Apparatus). Insulating Liquid must not contain more
than 2 PPM of Polychlorinated Biphenyl (PCB), classified as
PCB Free.
Hardware: All energized hardware, i.e., bolts, nuts and washers
shall be made of tinned copper alloy material such as silicon
bronze or equivalent. All other hardware shall be hot-dip
galvanized.

Nameplate: The transformer shall be provided with a nameplate in


accordance with the latest revision of IEEE Std C57.12.00. The
nameplate shall be made of stainless steel with the technical
information etched on the surface and coated with black enamel.

The following minimum information shall appear on the


nameplate:

103
a.) Serial Number

b.) Class

c.) Number of phases

d.) Frequency

e.) Voltage rating

f.) kVA rating

g.) Temperature rise, C

h.) Polarity

i.) Percent impedance

j.) BIL

k.) Total weight, kg

l.) Connection diagram

m.) Name of manufacturer

n.) Installation and operating instructions reference

o.) The word Transformer

p.) Type of insulating liquid (generic name

q.) Conductor material for each winding)

r.) Equipment identification number

Standard support lugs shall be he provided on the tank wall for


securely mounting the transformer on the pole. The type of support
lug to be provided corresponding to the transformer size shall he as
shown in IEEE Std C57.12.20, latest revision. Lifting facilities for
the core-coil assembly shall be provided. The tank shall surge
arrester mounting provision adjacent to the high-voltage bushing
per IEEE Std C57.12.20. It shall consist of two steel pads with a
inch-13 NC tapped holes 11 mm (0.44 in) deep and located on the
side of the tank in line vertically with the high voltage bushing.
The arrester mounting provisions shall have centerline-to
centerline spacing as shown in IEEE Std 057.12.20, latest revision.
Corrosion-resistant flanged cup shall be installed to protect the
threaded opening of the unused arrester mounting pads. The

104
correct oil level at 25 C shall be marked inside the tank.

The tank shall be painted with two (2) coats of outdoor type, light
gray paint conforming to Munsell Notation 5BG7.0/0.4, ANSI70
Gray, over a suitable prime coat.

Tank Markings: Transformer kVA rating shall be painted in


black using 3-inch block letters and numerals. The location of the
kVA marking shall be below the low-voltage bushings. The JFPR
Logo shall be embossed on the tank wall using 3-inch block
letters. The location of the name shall be below the kVA marking.
Tap Changer: The transformer shall be provided with a tap
changer designed for de-energized operation only. The tap changer
shall be provided with an external operating handle mounted on
the tank wall that can be rotated in a clockwise direction from a
high tap voltage to low tap voltage. It shall be provided with stops
when rotating from the highest to the lowest tap positions and shall
be designed to prevent accidental operation by requiring a
preliminary step before the tap setting can be changed. A caution:
DO NOT OPERATE WHEN ENERGIZED shall be marked near
the tap changer-operating handle, clearly visible to the operator.
Tap positions and caution markings shall be marked with reflector,
non-weathering decals at least 25 mm (1.0 inch) high. 1 shall be
assigned to the highest tap.

Tests: Each transformer shall be subjected to the following routine


production tests in accordance with procedures specified in IEEE
StdC57.12.60 and IEEE Std C57.12.90, latest revisions:

a) Winding resisting measurement tests

b) Ratio Test

c) Polarity Test and Phase Relation

d) No-Load Losses and Excitation Current at rated voltage and


frequency

e) Impedance Voltage and Load Loss Measurement

f) Induced Potential Test (Low-frequency Dielectric Test)

g) Dielectric Test of Insulating Oil

h) Mechanical (Leak Test)

Design Tests: Copies of certified test reports from a reputable,


internationally-accepted testing facility shall be submitted as proof

105
of meeting the requirement in the following design tests:

a) Temperature Rise

b) Lightning Impulse

c) Insulation Power Factor

d) Insulation Resistance

e) Short-Circuit Capability

Primary Bushings: The transformer shall be furnished at the


primary side with cover-mounted high-voltage bushing.
The high-voltage bushings shall be made from high-grade, wet
process porcelain with the entire exposed surface to be glazed. The
color of the bushings shall be Light Gray ANSI 70, Munsell
Notation 5BG 7.0/0.4.

The high-voltage bushing/s shall be designated as H1 (for single


bushings transformer) of H1 & H2 (for double bushing
transformer) and shall be arranged in accordance with the latest
revision of IEEE Std C57.12.20.

For single-bushing transformers, the H2 end of the primary


winding shall be brought out through a high-voltage neutral
bushing, which shall be designated as H2. The high-voltage neutral
bushing shall be sidewall-mounted, 1.2 kV class, 30 kV BIL, made
from high-grade, wet, process porcelain, colored Light Gray ANSI
70. It shall be externally grounded to the tank wall using a
removable copper ground strap.

Secondary Bushings: The transformer shall be furnished at the


secondary side with sidewall-mounted, low-voltage bushings. The
number and characteristics of the low-voltage bushings are shown
in Table 8.

Transformer Secondary Bushings Number and Characteristics


Low-Voltage Bushing Transformer Secondary Voltage Rating
Number and Characteristics 240 V
Number 2
Voltage Class (kV) 1.2
BIL Withstand(kV,min) 30
60 Hz Withstand, 1-min dry (kV,
min) 10
60 Hz Withstand, 10-s dry
(kv,min) 6

106
BIDDERS BID
/
STATEMENT OF
SPECIFICATIONS FORM
COMPLIANCE
OF
EVIDENCE
The low-voltage bushings shall be made from high-grade, wet-
process porcelain with the entire exposed surface to be glazed. The
color of the bushings shall be Light Gray ANSI 70, Munsell
Notation 5BG 7.0/0.4.
The low-voltage bushings shall be designated as X1, X2, X3, and
X4, depending on the transformer secondary voltage rating, shall be
arranged in accordance with the latest revision of IEEE Std
C57.12.20.
The low-voltage bushings of transformers rated 167 kVA and above
shall be designed to withstand without damage or leakage a
minimum cantilever force of 40 kg.
Bushing Terminals: The high-voltage bushing and high-voltage
neutral bushing shall be equipped with eye-bolt-type connectors
made from tinned copper-alloy material and provided with stainless
steel spring washers. The terminal connectors shall accommodate
(AWG No.8) solid to 30 mm2 (AWG No. 2) stranded copper
conductor. Terminal detail shall be in accordance with the latest
revision of IEEE Std C57.12.20.
The low-voltage bushings shall be equipped with the tinned copper
alloy, eyebolt-type connectors or tinned spade terminal pads,
arranged for vertical takeoff of cables. Size of terminal openings and
cables, and type of spade terminal pads are shown in Table 9.
Terminal details shall be in accordance with IEEE Std C57.12.20,
latest revision.

Terminal markings shall be in accordance with IEEE Std


C57.12.70, latest revision.
Size of Low-Voltage Terminals and Conductor Range

Size of
Size of Conductor
Terminal
that the Terminal Will Accommodate
Openingmm
mm2 (AWG/kcmil)
(in)

30 mm2 (AWG No. 2) solid to AWG


(5/8) No. 4/0

Polarity: Transformers supplied under this specification shall have


the polarity specified below.

Transformer Polarity

kVA Range Transformer Primary Voltage Rating

107
13 200GrdY/ 7620 V

167 kVA and


below Additive

Tank: The transformer tank shall be made of steel. It shall be of


sealed-type construction with a steel cover. The tank cover shall be
provided with a reusable gasket. The tank cover shall be grounded to
the tank body using a copper strap adequately sized for the short-
circuit of the transformer.
The tank shall be provided with a tank grounding connector located
near the base of the tank. The connector shall be eyebolt-type, made
from tinned copper alloy material, and designed to accommodate 8
mm2 (AWG No. 8) to 30 mm2 (AWG No. 2) stranded copper
conductors.
Standard support lugs shall be provided on the tank wall for
securely mounting the transformer on the pole. The type support lug
to be provided corresponding to the transformer size shall be as
shown in IEEE Std C57.12.20, latest revision.
Lifting lugs shall be permanently attached near the top of the
transformer tank to allow for balanced vertical lift. The design of
the lifting lugs shall incorporate a safety factor of 5.
Lifting facilities for the core-oil assembly shall be provided.

The tank shall have surge arrester mounting provision adjacent to


the high-voltage bushing. It shall consist of two steel pads with a
inch-13 NC tapped holes 11 mm (0.44 in) deep and located on the
side of the tank in line vertically with the high voltage bushing. The
arrester mounting provisions shall have centerline-to-centerline
spacing as shown in IEEE Std C57.12.20, latest revision. Corrosion-
resistant flanged cup shall be installed to protect the threaded
opening of unused arrester mounting pads.
The correct oil level at 25 C shall be marked inside the tank.

The tank shall be painted with two (2) coats of outdoor type, light
gray paint conforming to Munsell Notation 5BG7.0/0.4, ANSI170
Gray, over a suitable prime coat.

108
Logo: The bidder shall provide a 12cm18cm high quality sticker
with reflective face painted with JFPR and ODA logos for each
transformer.

109
Accessories and Protection
SPECIFICATION OF 15 KV VACUUM RECLOSER 12 STATEMENT BIDDERS
OF BID / FORM
Outdoor Vacuum 15 kV Reclosers COMPLIANCE OF
EVIDENCE
Manufacturer: Subject to Eligibility Requirements under Bid Data
Sheet Clauses 5.1, 5.2 and 7
Nominal operating voltage : 2.4-14.4 KV
Rated Power frequency : 60 HZ
Rated Continuous current : 630 Amps
Control voltage : 90-265 VAC / 125 VDC
Rated symmetrical
interrupting current : 8 / 10 / 12.5 / 16 A
Rated lightning
impulse withstand(BIL) 110/125
Dry withstand 60 Hz 1 Min. : 50
Wet withstand 60 Hz 10 Sec. : 45
Phase spacing : 15.50 ( 394 )
External creep distance, H2-ground : 38.00 ( 960 )
External creep distance, H1-H2 : 45.00 ( 1160 )
Min. External strike distance : 9.50 ( 240 )
Max. interrupting time : 0.030 s
Max. closing time : 0.055 s

Accessories
o Vacuum interrupter
o Epoxy bushing
o Earthing point
o Stainless steel tank
o Magnetic actuator
o Memory card
o Control cable(User Measured Length)
o Manual trip ring
o Buzzer alarm when tripped
o One (1) Unit Brand New Laptop in every three (3) units of
15KV Vacuum Recloser, for programming and event downloading
o Tripped counter
o Copper terminal lugs

Recloser functions :

o Remote control ON/OFF


o Local control ON/OFF
o Sensitive Earth Fault ON/OFF
o Earth Fault ON/OFF
o Auto reclose mode ON/OFF
o Close/Trip ISOLATE

Alarms status such as:


o Auxiliary supply fail
o Battery supply fail
o Lockout

Battery
o 2 sets 48 VDC, 12 AH battery bank (Std. Cabinet) or 48 VDC, 7.2
AH battery bank

110
o Sealed led acid rechargeable battery pack
o Monitor locally and remotely
o Easily accessible in low voltage control cabinet
o Allows up to 48 hours (15-27 kV) / 24 hours carryover and multiple
operations upon loss of power
o Includes capacitor backup in case of discharge or disconnected
battery

Features of 15 kV Vacuum Circuit Breaker:


o Protection setting and fault history
o Line measurement and historical data
o Metering data such as:
o Kw, Kvar, Pf, Kva, etc
o Distribution System Automation (DSA) or SCADA System.
Information on recloser status and fault current values transmitted to
system control allows fast location of the faulted line section.
o Substation mount or pole mount

-Cable requirement upon user needs.


AUTOMATIC CIRCUIT RECLOSER, 1-Phase, Brand New, 15 kV
max. rated voltage, 100 amperes or higher continuous current, 110 kV 7
rated lightning impulse, 50 kV power frequency insulation level test
voltage, 12.5/16 kA rated symmetrical interrupting current, 20/25 kA
rated asymmetrical interrupting current, 32.5/41 rated peak making
current, 10,000 OPS mechanical life, up to 250 OPS permissible short-
circuit operations, -40 to +55 ambient temp. range, 265 mm flashover
dist. phase/ground, 810 mm creepage dist. phase/ground, 1,170 mm
between line-side and load side terminal, Min. Trip Current: 40 A
phase faults, 4 A ground faults, Operation Time: <60 ms Closing Time,
<35 ms Opening Time, <15 ms Arcing Time, <50 ms Interrupting
Time, Dead Time: 0.2 to 14,400 s dead time after first open, 2 to
14,400 s dead time after second and third open, 30 to 14,400 s dead
time after fourth open.

69 KV POWER CIRCUIT BREAKER


1
Standards for outdoor installation with spring operated
mechanism

Manufacturer: Subject to Eligibility Requirements under Bid Data


Sheet Clauses 5.1, 5.2 and 7
Rated Voltage : 75 kV
Rated Nominal Voltage : 69 kV
Rated Maximum Voltage : 75 kV
Rated Frequency : 60 Hz
Test Voltage 60 Hz 1 min : 140 kV rms
BIL (peak) : 350 kV
Rated Current : 1250 A
Maximum Interrupting Current: 31.5 kA
Rated Duration of short circuit: 3 sec.
Momentary Current : 64 kA (ANSI)
Opening Time : 35 ms max.
Closing Time : 60 ms max.
Close Open Time : 40 ms. Max.
Resistance across breaking unit: 50 micro ohms
Rated Tripping Voltage : 125 Vdc
Ambient air temp. Range : 30 deg. C to +40 deg. C

111
Special Tools SF6 Handling Equipment:
o SF6 Filing Equipment
o SF6 leakage detector
o 2 Cylinder with 10 kg. SF6 Gas

Accessories:
o Closing Coil
o Tripping Coil Cylinder with 10 kg. SF6 Gas
o Auxiliary Switch/Relays
o Contactor

Features of 69 kV Power Circuit Breaker:


o suitable for three phase auto reclosing
o creepage distance : 1,810 mm
o color porcelain : brown (RAL 8016)
o protection class IP 54
o Differential relay
o 50 / 51
o phase center distance : 1,050 mm
o six A high voltage terminal pads, drilled according to NEMA
o circuit breaker poles will be delivered with 0.02-05 Mpa SF6
pressure
o SF6 density monitor with color and graduated scale (Mpa/bar)
o Nameplate in English

Features of Spring Operating Mechanism:


o - operating voltage of auxiliary circuits : DC 125 V
o - 1 universal motor per operating mechanism : DC 125
V
o alternate current circuit (heating, lighting) : Ac 230 V
o operating range of coil: Trip 70% / close 85% (IEC)
o anti-condensation heater, permanently
o red/green position indicator lamps included
o A.C. supply protected with M.C.B.
o SF6 density control included
o Two independent trip coils, one closing coil
o mechanically coupled auxiliary switch with 13 NC, 11 NO and 1
wiping contact free
o local mechanical and local electrical C/O operation with /Off remote
selector switch
o without motor protection
o wiring 1.5 sq. mm, stranded wire with ferrules
o terminal strip UK5 with 16 sq. mm earthing wire with ferrules
o no numbering ferrules
o lighting of operating mechanism housing included
o with socket (outlet)
o door of housing lockable
o mechanical interlock Ronis included
o I/Q position indicator red-green included

Surface Protection:
o Aluminum alloy parts will not be painted
o Ferrous parts are hot-dip galvanized
o flanges of insulators are anodized aluminum sheets and operating
mechanisms get two protective coats of paint (RAL 7044)

112
Potential Transformers:
3
Voltage Transformers according to the following specifications:

Brand: Subject to Eligibility Requirements under Bid Data Sheet


Clauses 5.1, 5.2 and 7
Installation : Outdoor
System Voltage : up to 75 kV
Rated Voltage : 69 kV
Ratio : (69000 V / 40250
V:115V)
BIL : 350 kV @ <
1,000 m
Thermal Rating : 25-kA/1 sec. (IEC)
Momentary Current : 40 kA (ANSI)
Flag type 4 Hole
Terminal Lugs : Tap to 336.4 acsr thru
ampact

69 kV Current Transformers for SF6 Power Circuit Breaker:


Current Transformers are three (3) single phase units in live tank 3
design. The coil respective core data are properly designed with
protection and metering system. Current Transformer designed as per
IEC/ANSI standard.

Brand: Subject to Eligibility Requirements under Bid Data Sheet


Clauses 5.1, 5.2 and 7
Type : Dry Type Cast
Resin
Installation : Outdoor
Rated Voltage : 75 kV
Frequency : 60 Hz
BIL : 350 kV
Ratio : 100/50:5 A,
Multi Ratio
Metering Core : 0.3, B-1
Class Protection Core 1 : C100
Class Protection Core 2 : C100
Thermal Rating : 31.5 kA/1 sec. (IEC)
Momentary Current : 51 kA (ANSI)
1-min Power Freq. Voltage : 140 kV
Dynamic withstand current : 80 kA
Total Creepage Distance : 1810 mm
Arcing Distance : 700 mm
Lightning Impulse : 350 kVp
Straight Paddle 4 Hole Terminal: Lugs Tap to 336.4 acsr
thru ampact

FUSE LINKS: Fuse Links shall conform in all respects to the


requirements of this document. The fuse links covered in this
specification are intended for use in open-type distribution fuse cutouts.
The fuse links shall be of the buttonhead-type to be used in the
overcurrent protection of distribution transformers and circuits. The
fuse links shall meet the electrical and mechanical interchangeability
requirements for fuse links used in open-type cutouts as described in
Sections 3.2 of ANSI C37.42 [1].

113
RATINGS: Voltage and current ratings of the fuse links shall be based
on the service condition defined in ANSI C37.40 and as specified in
ANSI C37.42.

Rated maximum voltage which is determined by the highest voltage


rated cutout with which the fuse link is designed to be used and yet
conform to the interchangeability requirement of Section 3.2.1 of ANSI
C37.42.

MARKINGS: Each fuse link shall bear the manufacturers


identification mark or symbol and rated continuous current followed by
the fuse type identifier.

PACKAGING: Fuse links shall be package in lots of 25 per box with 95


each fuse links in an individual container. All fuse link in a given lot
shall be of the same type and ampere rating. Boxes containing lots of
fuse links of the same type and ampere rating shall be packagedin
shipping cases as required to meet the quantities specified in the tender
documents. Each individual container, lot box and shipping case shall
be clearly marked to show the following minimum information:

1. Quantity
2. Manufacturers identification
3. Manufacturers Catalog number and type identification.
4. Rated continuous current.

The type identification K shall follow the rated current.

LIGHTNING ARRESTER: (POLYMER)


Rated Voltage : 10 KV 138
MCOV : 8.4 KV
BIL : 110 KV
pcs
Type : Outdoor .
High Current Operating Duty : 110 KV
CUTOUT AND ARRESTER COMBINATION, POLYMER 238
GENERAL: Arrester shall protect pole-mounted equipment from
voltage impulses or surges resulting from lightning strokes, system
faults, circuit switching, load rejection or other events. The arresters
shall limit such over voltage levels below equipment BIL ratings.

SERVICE CONDITIONS: Arresters shall meet the following physical


and system conditions:
1. Ambient temperature above 40C
2. Altitude up to 1,800 meter above sea level
3. Nominal system frequency 60 Hertz
4. Arresters shall be rated 9/10 kV MCOV, for phase to ground
connection on a 13.2/7.62 kV grd Y system.
CONSTRUCTION: Arrester shall be gapless type, described briefly as
follows:
Gapless arresters shall have valve elements fabricated from non-linear
resistance metal oxide materials to perform both the surge discharge
and power frequency reseal functions.

CONNECTORS: Both line-lead and isolator terminals shall


accommodate # 6 solid through 2/0 AWG stranded copper or aluminum

114
conductors.

PROTECTIVE CHARACTERISTICS: Arresters shall have protective


characteristic based on standard rms data cycle voltage as summarized
from ANSI C62.11 [1].

NAMEPLATE: Information required for identification must be


embossed on an nameplate firmly fixed to the arrester and shall
include:
a. Arrester classification
b. Manufacturers identification or symbol
c. Arrester model and identification number
d. Arrester voltage rating
e. Date of manufacture

The nameplate must be eligible over the lifetime of the arrester.

MOUNTING: Distribution arrester shall be supplied with a crossarm


mounting bracket that conforms to the requirement of NEMA Pub.
No.1 PH25, [3], or with appropriate bracket when supplied as a cutout-
arrester combination on it.

All mounting bolts and conductor connections require lock washers.


Lock washer shall be fabricated from material that complies with the
requirements of ANSI B18.21.1 [5].

PACKAGING: Arrester shall be securely packaged for shipping. Each


package shall be clearly marked with the manufacturers name and
catalog number.

SPECIFICATIONS FUSE CUT-OUT and ARRESTER


COMBINATION

Fuse Cut-out & Arrester Assembly:


Manufacturer: Subject to Eligibility Requirements under Bid Data
Sheet Clauses 5.1, 5.2 and 7

Rated Voltage : 15 kVAmpere Frame


: 100 AFFuse Link Rating
: 5A

Lightning Arrester:
Rated Voltage : 10 KVMCOV
: 8.4 KVBIL
: 110 KVType
: Outdoor High Current Operating
Duty
: 110 KV

CUTOUT, FUSE, SINGLE-SHOT 138


GENERAL: Fuse cutouts furnished shall conform in all respects to the
requirements of this specification. These fuse cutouts shall be of the
open, expulsion, dropout, type and shall be satisfactory for use in a
tropical climate with high relative humidity.

RATINGS:

115
1. Rated Voltage
a. Nominal System Voltage-13.2/7.62 KV grd Y
b. Rated Maximum Voltage-15,000 volts
c. Low Frequency Withstand KV, RMS
-dry, 60 sec. -35
-wet, 10 sec. -30

2. Rated Impulse withstand voltage - 95 KV


3. Rated Frequency - 60 Hertz
4. Rated Continuous Current - 100 amperes

DESIGN:

1. Fuse Support Assembly

a. Fuse Support Insulator - wet process porcelain

b. Markings

Manufacturers identification
Product type
Rated continuous current
Rated maximum voltage
Rated interrupting current
Basic impulse level

c. Contacts - silver

d. Connectors tin-plated bronze parallel grove type, for #6 to


4/0 AWG copper or aluminum conductors.

e. Loadbuster tool attachment hooks.

2. Fuse Tube Assembly

a) Fuse tube bone fiber lining with exterior painted gray, non-
expendable cap.

b) Contacts silver plated

c) Fuse Link Position The fuse tube shall be designed so the


fuse link is centered in the tube, with provision for mechanical
ejection of the fuse link leader on low current faults.

d) Opening and Lifting Eyes - the fuse holder shall hang


vertically from the fuse support assembly when in the open position,
and shall have opening and lifting eyes suitable for removal and
installation of the assembly, and opening and closing of the cutout
with a switch stick described in ANSI C37 42-1981, [3].

e) Thumb Screw for securing the fuse link to fuse holder


assembly.

3. Mounting Bracket : Each distribution fuse cutout shall be


provided with a mounting bracket meeting the requirements of ANSI
C37 42-1981, Section 2.4 for type A mounting when specified and
ordered as a combination cut-out arrester unit.

116
4. Lock Washer : All mounting bolts and conductor connectors
require lock washers. Lock washers shall be fabricated from material
that comply with the requirements of ANSI B18.21.1-1983, [4].

PACKAGING: Each distribution fuse cutout and arrester if ordered in


combination, together with its mounting bracket shall be securely
packaged in a box clearly labeled to show the manufacturers name,
product, identification and type and voltage and current ratings.