Fecha: 30/11/16 INFORME ESTUDIO DE COORDINACIN DE PROTECCIONES
Pgina 1 de 43
Rev. 6
CONTENIDO
1. OBJETO Y ALCANCE ..................................................................................................................... 5
7. CONCLUSIONES ......................................................................................................................... 27
LISTA DE FIGURAS.
Figura 3.1-1 Zona de Influencia SE El Carmen 66 kV ........................................................................... 9
Figura 4-1 Cortocircuito Falla Trifsica, Dem. MAX, Ao 2016, Zona Bolivar 66 kV ......................... 12
Figura 4-2 Cortocircuito Falla Monofsica, Dem. MAX, Ao 2016, Zona Bolivar 66 kV .................... 13
Figura 4-3 Cortocircuito Falla Trifsica, Dem. MIN, Ao 2016, Zona Bolivar 66 kV .......................... 13
Figura 4-4 Cortocircuito Falla Monofsica, Dem. MIN, Ao 2016, Zona Bolivar 66 kV..................... 14
Figura 4-5 Cortocircuito Falla Trifsica, Dem. MAX, Ao 2016, Zona Bolivar 66 kV. Escenario Lnea
Gambote-El Carmen Abierta ............................................................................................................. 14
Figura 4-6 Cortocircuito Falla Monofsica, Dem. MAX, Ao 2016, Zona Bolivar 66 kV. Escenario
Lnea Gambote-El Carmen Abierta.................................................................................................... 15
Figura 4-7 Cortocircuito Falla Trifsica, Dem. MIN, Ao 2016, Zona Bolivar 66 kV. Escenario Lnea
Gambote-El Carmen Abierta ............................................................................................................. 15
Figura 4-8 Cortocircuito Falla Monofsica, Dem. MIN, Ao 2016, Zona Bolvar 66 kV. Escenario
Lnea Gambote-El Carmen Abierta.................................................................................................... 16
Figura 4-9 Cortocircuito Falla Trifsica, Dem. MAX, Ao 2016, Zona Bolivar 66 kV. Escenario Lnea
Gambote-El Carmen Cerrada. Falla Posterior a Reactor de Sincronizacin...................................... 16
Figura 4-10 Cortocircuito Falla Trifsica, Dem. MAX, Ao 2016, Zona Bolivar 66 kV. Escenario Lnea
Gambote-El Carmen Abierta. Falla posterior a Reactor de Sincronizacin ...................................... 17
Figura 4-11 Cortocircuito Falla Monofsica, Dem. MAX, Ao 2016, Zona Bolivar 66 kV. Escenario
Lnea Gambote-El Carmen Cerrada. Falla Posterior a Reactor de Sincronizacin ............................ 17
Figura 4-12 Cortocircuito Falla Monofsica, Dem. MAX, Ao 2016, Zona Bolivar 66 kV. Escenario
Lnea Gambote-El Carmen Abierto. Falla posterior a Reactor de Sincronizacin ............................. 18
Figura 4-13 Cortocircuito Falla Trifsica, Dem. MIN, Ao 2016, Zona Bolivar 66 kV. Escenario Lnea
Gambote-El Carmen Cerrada. Falla posterior a Reactor de Sincronizacin...................................... 18
Figura 4-14 Cortocircuito Falla Trifsica, Dem. MIN, Ao 2016, Zona Bolivar 66 kV. Escenario Lnea
Gambote-El Carmen Abierta. Falla Posterior a Reactor de Sincronizacin ...................................... 19
Figura 4-15 Cortocircuito Falla Monofsica, Dem. MIN, Ao 2016, Zona Bolivar 66 kV. Escenario
Lnea Gambote-El Carmen Cerrada. Falla posterior a Reactor de Sincronizacin ............................ 19
Figura 4-16 Cortocircuito Falla Monofsica, Dem. MIN, Ao 2016, Zona Bolivar 66 kV. Escenario
Lnea Gambote-El Carmen Abierto. Falla posterior a Reactor de Sincronizacin ............................. 20
Figura A 1 Falla Trifsica. Sub El Carmen R OC Gambote-El Carmen & R OC COMP El Carmen ....... 29
Figura A 2Falla Trifsica. Sub El Carmen R OC BAHTRANS El Carmen & R OC COMP El Carmen ...... 30
Figura A 3Falla Monofsica Ubicacin despus del rel de sobrecorriente compensacin capacitiva.
Sub Gambote R OC Gambote-El Carmen & R OC COMP El Carmen Ph-E ......................................... 31
Figura A 4Falla Monofsica Ubicacin despus del rel de sobrecorriente compensacin capacitiva.
Sub El Carmen R OC BAHTRANS El Carmen & R OC COMP El Carmen Ph-E...................................... 32
Compensacin Capacitiva Proyecto UPME STR 04-2015
S/E El Carmen 66 KV
Fecha: 30/11/16 INFORME ESTUDIO DE COORDINACIN DE PROTECCIONES
Pgina 4 de 43
Rev. 6
LISTA DE TABLAS
Tabla 3-1 Parmetros de las lneas adyacentes a la Subestacin EL Carmen ..................................... 6
Tabla 3-2. Parmetros transformador - Baha de transformacin El Carmen ................................... 6
Tabla 3.1-1. Parmetros Compensacin Capacitiva El Carmen .......................................................... 6
Tabla 3.1-2. Caracterstica de Soportabilidad Banco Capacitivo El Carmen 66 kV ............................. 7
Tabla 3.1-3 Parmetro de las protecciones y equipos de medicin ................................................... 8
Tabla 4-1 Niveles de Cortocircuito - Demanda Mxima 2016 .......................................................... 10
Tabla 4-2 Niveles de Cortocircuito - Demanda Mnima 2016 ........................................................... 10
Tabla 4-3 Niveles de Cortocircuito - Demanda Maxima 2016. Escenario Linea Gambtote El Carmen
Abierta ............................................................................................................................................... 11
Tabla 4-4 Niveles de Cortocircuito - Demanda Mnima 2016. Escenario Lnea Gambote El Carmen
Abierta ............................................................................................................................................... 11
Tabla 4-5 Niveles de Cortocircuito - Demanda Mnima y Mxima 2016. Falla Posterior a Reactor de
Sincronizacin ................................................................................................................................... 12
Tabla 6-1 Ajuste propuestos para la proteccin de sobrecorriente 50/51 y 50N/51N .................... 23
Tabla 6-2 Ajustes proteccin de sobrevoltaje 59 .............................................................................. 24
Tabla 6-3. Tiempo de operacin de la proteccin 59........................................................................ 25
Tabla 6-4 Ajustes de la proteccin de Subtension 27 ....................................................................... 25
Tabla 6-5 Ajustes para la proteccin de desbalance de neutro 60 N. .............................................. 26
Compensacin Capacitiva Proyecto UPME STR 04-2015
S/E El Carmen 66 KV
Fecha: 30/11/16 INFORME ESTUDIO DE COORDINACIN DE PROTECCIONES
Pgina 5 de 43
Rev. 6
1. OBJETO Y ALCANCE
CONELCA S.A.S. E.S.P. se encuentra desarrollando el proyecto del sistema de transmisin regional
STR 04 2015 de la UPME, el cual incluye el diseo, adquisicin de los suministros, construccin,
operacin y mantenimiento de las compensaciones capacitivas en las subestaciones el Carmen 66
kV, el Banco 110 kV y Montera 110 kV.
Este documento presenta los resultados del estudio de ajuste y coordinacin de protecciones del
banco capacitivo instalado en la subestacin Carmen 66 kV.
2. METODOLOGIA Y SOFTWARE
Para el desarrollo del estudio se emple el software Digsilent versin 14.1., el cual es una
herramienta especializada para el modelamiento de sistemas elctricos, simulacin de fallas y
coordinacin de protecciones, entre otras de sus muchas funcionalidades.
Con base en la informacin, base de datos y parmetros del sistema, suministrados por CONELCA,
se modelaron la subestacin, equipos y lneas bajo estudio en Digsilent, y se llev a cabo el
proceso de ajuste y coordinacin de las protecciones respectivas, con base en los criterios
descritos en el numeral 5 de este documento y analizando escenarios de demanda mxima y
mnima en el ao 2016 de entrada del proyecto.
La subestacin El Carmen posee a nivel de tensin de 66kV las siguientes dos bahas de lnea, una
compensacin capacitiva y una baha de transformacin 110/66 kV:
Los parmetros principales de estas lneas y el transformado, as como los elementos de medicin
y proteccin asociados a estos equipos, se presentan en las siguientes tablas:
Compensacin Capacitiva Proyecto UPME STR 04-2015
S/E El Carmen 66 KV
Fecha: 30/11/16 INFORME ESTUDIO DE COORDINACIN DE PROTECCIONES
Pgina 6 de 43
Rev. 6
Nota: Los valores de impedancia de corto circuito estn referidos a la mayor potencia entre devanados.
Los bancos de compensacin reactiva incluyendo la sintonizacin del reactor al 5to armnico
permite mantener los niveles armnicos en tensin dentro de los lmites admisibles
establecidos por la norma IEEE 519, a excepcin de los niveles del armnico 11 en tensin el
cual se encuentra por encima de los niveles permitidos, a raz de la resonancia que ocurre por
la conexin en paralelo de los bancos.
La corriente de Energizacin (Inrush), considerando la energizacin individual de la unidad
capacitiva es de 426 [A]. De acuerdo al estudio de transitorios, el tiempo de duracin del pico
de corriente mximo se encuentra por debajo de los 10 ms. Para tiempos por encima de 60
ms, la corriente se encuentra de nuevo por debajo de 100 [A] y cercano a sus valores
nominales de operacin.
La corriente de Energizacin (Inrush), considerando la energizacin de la unidad capacitiva
habiendo conectada otra unidad previamente (Energizacin Back to Back) es de 487[A]. De
acuerdo al estudio de transitorios, el tiempo de duracin del pico de corriente mximo se
encuentra por debajo de los 10 ms de duracin.
Compensacin Capacitiva Proyecto UPME STR 04-2015
S/E El Carmen 66 KV
Fecha: 30/11/16 INFORME ESTUDIO DE COORDINACIN DE PROTECCIONES
Pgina 8 de 43
Rev. 6
Lnea:
600/5 Proteccin PL1_ABB-RXIDF-
Zambrano -El 66 N.A
5P20 Principal 2H
Camen
Rel Schneider-
Proteccin
Lnea: Electric
200/5 66/ - Principal
Gambote El 66 PL1_MICOM P445
5P20 0.110/
Carmen Proteccin de Rel PL2_ZIV-
lnea 8IRV-A2N
Schneider-Electric
Proteccin
Linea: Rel PL1_MICOM
400/5 66/ - Principal
Gambote 66 P445
5P20 0.110/
Ternera Proteccin de Rel PL2_ZIV-
lnea 8IRV-A2N
Compensacin Capacitiva Proyecto UPME STR 04-2015
S/E El Carmen 66 KV
Fecha: 30/11/16 INFORME ESTUDIO DE COORDINACIN DE PROTECCIONES
Pgina 9 de 43
Rev. 6
El Anexo C Presenta los ajustes de las protecciones presentes en la zona de influencia El Carmen
66 kV. La Figura 3.1-1 presenta el diagrama simplificado del sistema modelado en DigSilent (SE El
Carmen 66 kV, lneas y SE adyacentes).
lod CALAMAR6
62.04
0.94
-45.81
Gambote 66
44.36
44.36
44.83
-7.78
-5.40
5.53
7.65
9.31
2.89
9.16
3.00
-29.45
lod SNJACIN6
-0.08
95.03
22.54
-4.69
-2.05
4.69
2.05
-42.14
62.12
23.92 0.94
7.86
0.00
31.34 -8.10
2.80 70.13
95.03 1.06
TSan Jacinto 66 -0.00
-43.76
8.10
114.45 63.54
1.04
-32.22
Series Re..
6.09
0.60 70.13
Shunt/Filter
10.30 1.06
-43.76
-8.10
0.00
0.00
-7.75 -0.00
63.54 8.10
63.54
Ternera 110
-0.00
Series Re..
7.75
63.54
lod ELCARMN6
Line
12.70 -7.75 -7.75
67.37 63.54 63.54
10.04
3.17
67.02
1.02
-43.76
El Carmen 66 Zambrano 66
18.60 63.41
9.42 0.96
90.78 -46.89
El Carmen - Zambrano 1 66
-18.08
90.78
18.08
-8.42
8.42
37.47
14.23 lod ZAMBRAN6
69.20
El Carmen 110
106.19
0.97 28.84
-38.00 11.40
-37.47
-14.23
36.32
45.42
13.17
45.65
38.44
10.30
-6.04
-5.28
15.62 -45.20
36.32 -12.63
45.65
SE Toluviejo 110
25.19
6.72
12.44
3.39
13.42
Coveas 110
113.19
1.03
-32.80
4. ANALISIS DE CORTOCIRCUITO
Para el anlisis de cortocircuito se calcularon las corrientes mximas de falla en las barras que
conforman la zona de influencia de la subestacin El CARMEN 66 kV para escenarios de demanda
mxima y mnima en el ao 2016 de entrada del proyecto.
En la Tabla 4-1 y Tabla 4-2, se presentan las corrientes de falla inicial para escenarios de
demanda mxima y mnima. La Tabla 4-3 y Tabla 4-4 presenta presentan las corrientes de falla
inicial para escenarios de demanda mxima y mnima tomando en cuenta el estado de
operacin del sistema con la lnea Gambote El Carmen abierta.
Compensacin Capacitiva Proyecto UPME STR 04-2015
S/E El Carmen 66 KV
Fecha: 30/11/16 INFORME ESTUDIO DE COORDINACIN DE PROTECCIONES
Pgina 10 de 43
Rev. 6
Zona: Bolvar 66 kV
Niveles mximos de Cortocircuito - Demanda Mxima
2016
Barra Trifsico Monofsico
I_kss[kA] I_kss[kA]
Ternera 110 3.736 5.644
Gambote 66 2.884 1.782
El Carmen 110 2.019 1.943
El Carmen 66 2.300 3.040
Zambrano 66 1.220 0.991
Coveas 110 4.485 2.988
TSan Jacinto 66 2.114 2.024
TCalamar 66 2.072 1.537
Toluviejo 110 5.354 3.938
Zona: Bolivar 66 kV
Niveles mximos de Cortocircuito - Demanda Minima
2016
Barra Trifsico Monofsico
I_kss[kA] I_kss[kA]
Ternera 110 3.463 5.230
Gambote 66 2.788 1.756
El Carmen 110 1.964 1.908
El Carmen 66 2.252 2.984
Zambrano 66 1.206 0.985
Coveas 110 4.257 2.918
TSan Jacinto 66 2.072 1.998
TCalamar 66 2.028 1.521
Toluviejo 110 5.014 3.810
Compensacin Capacitiva Proyecto UPME STR 04-2015
S/E El Carmen 66 KV
Fecha: 30/11/16 INFORME ESTUDIO DE COORDINACIN DE PROTECCIONES
Pgina 11 de 43
Rev. 6
Tabla 4-3 Niveles de Cortocircuito - Demanda Maxima 2016. Escenario Linea Gambtote El Carmen Abierta
Tabla 4-4 Niveles de Cortocircuito - Demanda Mnima 2016. Escenario Lnea Gambote El Carmen Abierta
Tabla 4-5 Niveles de Cortocircuito - Demanda Mnima y Mxima 2016. Falla Posterior a Reactor de Sincronizacin
lod CALAMAR6
0.000
130.34
0.000
1.140
2.280
0.000
0.000
255.37
0.00
2.234
4.094
Atlantico 110
329.63
13
711.85
0.000 0.00 3.736 San Jacinto 66
lod SNJACIN6
0.000 0.000 9.737
0.000 0.000 TSan Jacinto 66
0.000
0.000
185.65
0.00
0.974
0.000 2.539
0.000
Cap Ternera 43 MVAR
0.00 0.00 0.00 0.00 0.00 0.00 0.000 0.00 0.00 Inactive
0.000 0.000 0.000 0.000 0.00 0.000 0.000 0.000 0.000
0.000 Out of Calculation
25
El Carmen - Zambrano 1 66
139.45
0.000
0.000
0.000
1.220
2.537
14
0.00
0.000
0.000 0.00
0.000 0.000
0.000 0.000 Trafo1 0.00 71.89
0.000 0.377 lod ZAMBRAN6
66/13.8
0.000
0.000
0.00
0.000 0.805
lod ARGOS__1 El Carmen 110
0.000 0.00 0.00
384.74
Trafo2 Mamonal 66 0.000 0.000 0.000
0.000
0.000
0.000 2.019
0.00
0.000
0.000
0.000
0.00
0.00
0.000
0.00
0.000 0.000
0.000
0.000
0.000
0.000
0.00
0.00
0.00
0.000 SE Sierra Flor 110
0.000
0.000
0.00
0.000
160.10
58.31
0.840
1.950
391.09
~ ~ 2.053 Ikss Ik" [kA] u u, Magnitude [p.u.] Ikss I
4.781
Proelectrica 1
Proelectrica 2
Candelaria 1
Candelaria 2
ena 2
ena 3
La Marina 66
Figura 4-1 Cortocircuito Falla Trifsica, Dem. MAX, Ao 2016, Zona Bolivar 66 kV
Compensacin Capacitiva Proyecto UPME STR 04-2015
S/E El Carmen 66 KV
Fecha: 30/11/16 INFORME ESTUDIO DE COORDINACIN DE PROTECCIONES
Pgina 13 de 43
Rev. 6
lod CALAMAR6
0.000
0.000
28.05
0.736
1.472
0.001
0.002
0.000
0.000
49.97
0.05
0.00
1.311
2.403
Atlantico 110
lod TUBOCAR1 Calamar 66
67.90
1.782
3.266
0.00
0.000
0.000
0.00 0.00 Ternera 1 220/66 (150MVA) 0.00 0.00 0.00 0.00
0.000 0.000 0.000 0.000 0.000 0.000
0.00 0.000 0.000 0.000 0.000 0.000 0.000
0.000
0.000 SE Ternera 66 Ternera 1 220/110
25
13
358.45
0.000 0.00 5.644 San Jacinto 66
lod SNJACIN6
0.000 0.000 14.709
0.000 0.000 TSan Jacinto 66
0.000
0.000
0.000
0.000
62.13
0.00
0.00
0.978
0.000 2.550
0.000
Cap Ternera 43 MVAR
0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.000 0.00 0.00 Inactive
0.000 0.000 0.000 0.000 0.000 0.000 0.00 0.000 0.000 0.000 0.000
0.000 Out of Calculation
25
0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Contecar 66 0.000
Ternera 2 220/66 (150MVA) Ternera 110 De-energized
0.000
0.000
0.000
0.000 0.000 El Carmen - Zambrano 1 66
0.000
0.000
37.76
0.991
2.061
0.000
0.000
14
0.00
0.00
0.000 0.000
0.000 0.00 0.00
0.000 0.000 0.000
0.000
0.000
Trafo1
0.00
0.000 0.000 0.000 0.00 0.00 44.37
0.000 0.000 0.699 lod ZAMBRAN6
66/13.8
0.000
0.000
0.00
0.000 0.000 1.490
lod ARGOS__1 El Carmen 110
0.000 0.00 0.00
123.37
Trafo2 Mamonal 66 0.000 0.000 0.000
0.000
0.000
0.000 1.943
0.00
0.000
0.000
0.000
0.00
0.00
0.000
0.000
0.00
0.000 0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.00
0.00
0.00
0.00
0.000 SE Sierra Flor 110
0.000
0.000
0.00
0.000 24.24
39.15
0.616
1.431
0.000 0.382 124.19
88.67
~ ~ 1.396 Ikss:A Ik" A [kA] U:B U, Magnitude B [kV] Ik
3.252
Proelectrica 1
Proelectrica 2
Candelaria 1
Candelaria 2
ena 2
ena 3
La Marina 66
Figura 4-2 Cortocircuito Falla Monofsica, Dem. MAX, Ao 2016, Zona Bolivar 66 kV
Gambote 66 TCalamar 66
lod CALAMAR6
0.000
0.000
0.000
127.07
1.112
2.234
0.000
0.000
246.14
0.00
2.153
3.983
Atlantico 110
Calamar 66
318.66
lod TUBOCAR1
2.788
5.157
13
659.88
0.00 3.463 San Jacinto 66
lod SNJACIN6
0.000 9.007
0.000 176.32 TSan Jacinto 66
0.000
0.000
0.00
0.925
0.000 2.407
Cap Ternera 43 MVAR
0.000
0.00 0.00 0.00 0.00 0.00 0.00 0.000 0.00 0.00 Inactive
0.000 0.000 0.000 0.000 0.00 0.000 0.000 0.000 0.000
0.000 Out of Calculation
15
137.92
0.000 5
0.000
0.000
1.206
2.515
0.00
0.000
0.00
0.000
0.000 Trafo1 0.00 69.30
0.000 0.364 lod ZAMBRAN6
66/13.8
0.000
0.000
0.00
0.000 0.779
lod ARGOS__1 El Carmen 110
0.000 0.00 0.00
374.27
Trafo2 Mamonal 66 0.000
0.000
0.000
0.000
0.000
0.000 0.000 1.964
0.000 4.209
66/13.8 0.00
0.000 Candelaria 110 0.000
Chambacu 66 0.000 305.26
0.000
1.602
0.000 Mem brillal 66 0.000
0.000
0.000
0.00
0.000 3.433
0.000 0.000
El Carmen - Toluviejo 1 110
0.000
0.00
0.000 0.000
0.000
0.000
0.00
0.00
0.000 SE Sierra Flor 110
0.000
0.000
0.00
0.000
145.72
53.09
0.765
1.787
G G 369.64
~ ~ 1.940 Iks s Ik" [kA] u u, Magnitude [p.u.] Iks s I
Proelectrica 1
Proelectrica 2
4.542
Candelaria 1
Candelaria 2
na 2
na 3
La Marina 66
Figura 4-3 Cortocircuito Falla Trifsica, Dem. MIN, Ao 2016, Zona Bolivar 66 kV
Compensacin Capacitiva Proyecto UPME STR 04-2015
S/E El Carmen 66 KV
Fecha: 30/11/16 INFORME ESTUDIO DE COORDINACIN DE PROTECCIONES
Pgina 14 de 43
Rev. 6
Gambote 66 TCalamar 66
lod CALAMAR6
0.000
0.000
0.000
27.67
0.726
1.460
0.001
0.002
0.000
0.000
49.15
0.05
0.00
1.290
2.386
Atlantico 110
lod TUBOCAR1 Calamar 66
66.93
1.756
3.250
0.00
0.000
0.000
0.00 0.00 Ternera 1 220/66 (150MVA) 0.00 0.00 0.00 0.00
0.000 0.000 0.000 0.000 0.000 0.000
0.00 0.000 0.000 0.000 0.000 0.000 0.000
0.000
0.000 SE Ternera 66 Ternera 1 220/110
15
13
332.14
0.00 5.230 San Jacinto 66
lod SNJACIN6
0.000 13.601
0.000 58.97 TSan Jacinto 66
0.000
0.000
0.000
0.000
0.00
0.00
0.929
0.000 2.415
Cap Ternera 43 MVAR
0.000
0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.000 0.00 0.00 Inactive
0.000 0.000 0.000 0.000 0.000 0.000 0.00 0.000 0.000 0.000 0.000
0.000 Out of Calculation
15
0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
0.000
Ternera 2 220/66 (150MVA) Ternera 110 De-energized
0.000
0.000
0.000
0.000 0.000 5
0.000
0.000
37.53
0.985
2.053
0.000
0.000
0.00
0.00
0.000 0.000
0.00 0.00
0.000 0.000 0.000
Trafo1 0.000
0.00
0.000
0.000
0.00
0.000 0.000 1.466
lod ARGOS__1 El Carmen 110
0.000 0.00 0.00
121.16
Trafo2 Mamonal 66 0.000
0.000
0.000
0.000
0.000
0.000 0.000 1.908 0.00
0.000 4.088 0.000
66/13.8 0.00
0.000 Candelaria 110 0.000 0.000
Chambacu 66 0.000 77.73
0.000
1.224
0.000 Mem brillal 66 0.000
0.000
0.000
0.00
0.000 2.623
0.000 0.000
0.000
0.000
0.000
0.00
0.00
0.000 0.000
0.000
0.000
0.000
0.000
0.00
0.00
0.00
0.000 SE Sierra Flor 110
0.000
0.000
0.00
0.000 23.21
37.18
0.585
1.368
0.000 0.365 120.80
G G 86.37
~ ~ 1.360 Iks s :A Ik" A [kA] U:B U, Magnitude B [kV] Ik
Proelectrica 1
Proelectrica 2
3.184
Candelaria 1
Candelaria 2
na 2
na 3
La Marina 66
Figura 4-4 Cortocircuito Falla Monofsica, Dem. MIN, Ao 2016, Zona Bolivar 66 kV
lod VILLAES6
TCalamar 66
lod CALAMAR6
Gambote 66 0.000
0.000
257.11 0.000
0.000
0.000
0.000
0.000
0.00
0.00
2.249
3.897
Atlantico 110
lod T UBOCAR1 Calamar 66
257.11
2.249
3.897
13
711.28
3.733 San Jacinto 66
lod SNJACIN6
0.00
0.000 9.734
0.000 184.25 TSan Jacinto 66
0.000
0.000
0.00
0.967
0.000 2.522
Cap Ternera 43 MVAR
0.000
.00 0.00 0.00 0.00 0.00 0.00 0.000 0.00 0.00 Inactive
000 0.000 0.000 0.000 0.00 0.000 0.000 0.000 0.000
000 0.000 0.000 0.000 0.000 0.000 0.000 Out of Calculation
25
0.000 0.000
0.000
T ernera 2 220/66 (150MVA) Ternera 110 De-energized
0.000 14
111.98
0.000
0.000
0.980
2.146
0.00
0.000
0.00
0.000
0.000 Trafo1 0.00 0.00
0.000 0.000 lod ZAMBRAN6
66/13.8 0.000 0.000
0.000
0.000
0.00
0.000
0.00
0.000 0.000
El Carmen - Toluviejo 1 110
0.000 0.000
0.000
0.000
0.00
0.00
0.000 SE Sierra Flor 110
0.000
0.000
0.00
0.000 0.00
162.61
0.853
1.994
0.00 0.00
0.000 0.000 2.800
6.541 Cordoba-Sucre 110
0.000
0.000
0.000
0.000
SE Toluviejo 110
0.00 0.00
Proelectrica.. Proelectrica.. 0.000 0.000 967.45
0.000 0.000 0.000 5.078
Bgrande 66 0.000
0.000 6030
0.000
0.000
11.865
0.000
0.00 0.00
0.000 0.000
0.000 0.000
G G 372.99
~ ~ 1.958 Ikss Ik" [kA] u u, Magnitude [p.u.] Ikss I
Proelectrica 1
Proelectrica 2
4.580
Candelaria 1
Candelaria 2
Figura 4-5 Cortocircuito Falla Trifsica, Dem. MAX, Ao 2016, Zona Bolivar 66 kV. Escenario Lnea Gambote-El Carmen
Abierta
Compensacin Capacitiva Proyecto UPME STR 04-2015
S/E El Carmen 66 KV
Fecha: 30/11/16 INFORME ESTUDIO DE COORDINACIN DE PROTECCIONES
Pgina 15 de 43
Rev. 6
lod VILLAES6
TCalamar 66
lod CALAMAR6
Gambote 66 0.000
0.000
47.92 0.000
0.002
0.003
0.001
0.002
0.000
0.000
0.06
0.04
0.00
1.258
2.179
Atlantico 110
lod T UBOCAR1 Calamar 66
47.92
1.258
2.179
0.00
0.000
0.000
0.00 0.00 T ernera 1 220/66 (150MVA) 0.00 0.00 0.00 0.00
0.000 0.000 0.000 0.000 0.000 0.000
0.00 0.000 0.000 0.000 0.000 0.000 0.000
0.000
0.000 SE Ternera 66 T ernera 1 220/110
25
13
358.16
5.640 San Jacinto 66
lod SNJACIN6
0.00
0.000 14.705
0.000 61.66 TSan Jacinto 66
0.000
0.000
0.000
0.000
0.00
0.00
0.971
0.000 2.532
Cap Ternera 43 MVAR
0.000
0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.000 0.00 0.00 Inactive
0.000 0.000 0.000 0.000 0.000 0.00 0.000 0.000 0.000 0.000
0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 Out of Calculation
25
0.000 0.000
0.000
T ernera 2 220/66 (150MVA) Ternera 110 De-energized
0.000
0.000
33.36
0.875
1.918
0.000
0.000
0.00
0.00
0.000 0.000
0.00 0.00
0.000 0.000
Trafo1
0.000
0.000
0.00
0.000
0.00
0.000 0.000
0.000
0.000
0.00
0.00
0.000 0.000
0.000
0.000
0.000
0.000
0.00
0.00
0.00
0.000 SE Sierra Flor 110
0.000
0.000
0.00
0.000 14.41
40.03
0.630
1.473
0.000 0.227 125.88
0.00 0.00
0.000 0.530 1.982
4.632 Cordoba-Sucre 110
0.000
0.000
0.000
0.000
SE Toluviejo 110
0.00 0.00
Proelectrica.. Proelectrica.. 0.000 0.000 243.64
0.000 0.000 0.000 3.836
grande 66 0.000
0.000 6030
0.000
0.000
8.964
0.000
0.00 0.00
0.000 0.000
0.000 0.000
0.00
0.000
0.000
Short Circuit Nodes Nodes Br
Skss:A Sk" A [MVA] U:A U, Magnitude A [kV] Sk
lod LAMARIN6
G G 86.41
~ ~ 1.361 Ikss:A Ik" A [kA] U:B U, Magnitude B [kV] Ik
Proelectrica 1
Proelectrica 2
3.183
Candelaria 1
Candelaria 2
Figura 4-6 Cortocircuito Falla Monofsica, Dem. MAX, Ao 2016, Zona Bolivar 66 kV. Escenario Lnea Gambote-El Carmen
Abierta
lod VILLAES6
Gambote 66 TCalamar 66
lod CALAMAR6
0.000
0.000
249.42 0.000
0.000
0.000
0.000
0.000
0.00
0.00
2.182
3.815
Atlantico 110
lod TUBOCAR1 Calamar 66
249.42
2.182
3.815
13
659.63
3.462 San Jacinto 66
lod SNJACIN6
0.00
0.000 9.006
0.000
175.38 TSan Jacinto 66
0.000
0.000
0.00
0.921
0.000 2.395
Cap Ternera 43 MVAR
0.000
0.00 0.00 0.00
0.00
0.00 0.00 0.000 0.00 0.00 Inactive
0.000 0.000 0.000 0.000 0.000 0.000 0.000
0.000 Out of Calculation
15
0.000
111.19
5
0.000
0.000
0.973
2.133
0.00
0.000
0.00
0.000
0.000 Trafo1 0.00 0.00
0.000 0.000 lod ZAMBRAN6
66/13.8
0.000
0.000
0.000 0.000
0.00
3.522
0.00
0.000 0.000
0.000
0.000
0.00
0.00
0.000 SE Sierra Flor 110
0.000
0.000
0.00
0.000
149.02
0.00
0.782
1.837
0.00 0.00
0.000 0.000 2.651
6.228 Cordoba-Sucre 110
0.000
0.000
0.000
0.000
SE Toluviejo 110
0.00 0.00
Proelectrica.. Proelectrica.. 0.000 0.000 911.18
0.000 0.000 0.000 4.782
0.000
ande 66 0.000 6030
0.000
0.000
11.235
0.000
0.00 0.00
0.000 0.000
0.000 0.000
G G 353.78
~ ~ 1.857 Ikss Ik" [kA] u u, Magnitude [p.u.] Ikss I
Proelectrica 1
Proelectrica 2
4.364
Candelaria 1
Candelaria 2
agena 2
agena 3
La Marina 66
Figura 4-7 Cortocircuito Falla Trifsica, Dem. MIN, Ao 2016, Zona Bolivar 66 kV. Escenario Lnea Gambote-El Carmen
Abierta
Compensacin Capacitiva Proyecto UPME STR 04-2015
S/E El Carmen 66 KV
Fecha: 30/11/16 INFORME ESTUDIO DE COORDINACIN DE PROTECCIONES
Pgina 16 de 43
Rev. 6
lod VILLAES6
Gambote 66 TCalamar 66
lod CALAMAR6
0.000
0.000
47.35 0.000
0.002
0.003
0.001
0.002
0.000
0.000
0.06
0.04
0.00
1.243
2.173
Atlantico 110
lod TUBOCAR1 Calamar 66
47.35
1.243
2.173
0.00
0.000
0.000
0.00 0.00 Ternera 1 220/66 (150MVA) 0.00 0.00 0.00 0.00
0.000 0.000 0.000 0.000 0.000 0.000
0.00 0.000 0.000 0.000 0.000 0.000 0.000
0.000
0.000 SE Ternera 66 Ternera 1 220/110
15
13
332.01
5.228 San Jacinto 66
lod SNJACIN6
0.00
0.000 13.599
0.000
58.65 TSan Jacinto 66
0.000
0.000
0.000
0.000
0.00
0.00
0.924
0.000 2.403
Cap Ternera 43 MVAR
0.000
0.00 0.00 0.00 0.00 0.00
0.00
0.00 0.00 0.000 0.00 0.00 Inactive
0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
0.000 Out of Calculation
15
0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
0.000
Ternera 2 220/66 (150MVA) Ternera 110 De-energized
33.22
0.872
1.912
0.000
0.000
0.00
0.00
0.000 0.000
0.00 0.00
0.000 0.000
0.000
0.000
Trafo1
0.00
2.782
0.00
0.000
0.000
0.00
0.00
0.000 0.000
0.000
0.000
0.000
0.000
0.00
0.00
0.00
0.000 SE Sierra Flor 110
0.000
0.000
0.00
0.000 13.98
38.11
0.600
1.410
0.000 0.220 122.53
0.00 0.00
0.000 0.517 1.929
4.533 Cordoba-Sucre 110
0.000
0.000
0.000
0.000
SE Toluviejo 110
0.00 0.00
Proelectrica.. Proelectrica.. 0.000 0.000 236.26
0.000 0.000 0.000 3.720
0.000
e 66 0.000 6030
0.000
0.000
8.739
0.000
0.00 0.00
0.000 0.000
0.000 0.000
0.00
0.000
0.000
Short Circuit Nodes Nodes Br
Skss:A Sk" A [MVA] U:A U, Magnitude A [kV] Sk
lod LAMARIN6
G G 84.29
~ ~ 1.327 Ikss:A Ik" A [kA] U:B U, Magnitude B [kV] Ik
Proelectrica 1
Proelectrica 2
3.119
Candelaria 1
Candelaria 2
agena 2
agena 3
La Marina 66
Figura 4-8 Cortocircuito Falla Monofsica, Dem. MIN, Ao 2016, Zona Bolvar 66 kV. Escenario Lnea Gambote-El Carmen
Abierta
TCalamar 66
52.776 lod CALAMAR6
0.800
3.180
35.62
0.312
0.000
0.000
0.000
0.00
Atlantico 110
lod TUBOCAR1 Calamar 66
9.00 2.73
0.024 0.007
lod SNJACIN6
0.000 0.000
Ternera 1 220/110
0.000
0.000
0.00
13
116.968
11.11 1.063
0.029 -0.054
0.000 11.11
TSan Jacinto 66 0.00
San Jacinto 66
0.058 43.500
Shunt/Filter
0.000 0.659
238.218 0.000 0.000 4.785
0.000
0.000
0.00
1.083
-0.066 8.62 8.62 106.75 Inactive
0.023 0.023 0.934 0.00
0.000 0.000 2.380 0.000 Out of Calculation
0.000 De-energized
Ternera 110 106.75
0.934
2.380
Series Re..
Series Reactor
0.00
lod ELCARMN6 0.000
0.000
35.62 106.75 0.00
Nv Cospique 110 0.312
0.000
0.934
0.000
0.000
0.000
43.500
0.659
0.00 0.00 4.785
0.000 0.000 El Carmen 66 Zambrano 66
0.000 0.000
0.00 43.500
0.000 0.659
0.000 4.785
14 El Carmen - Zambrano 1 66
0.000
0.000
0.00
72.00
0.378 lod ZAMBRAN6
0.000
Figura 4-9 Cortocircuito Falla Trifsica, Dem. MAX, Ao 2016, Zona Bolivar 66 kV. Escenario Lnea Gambote-El Carmen
Cerrada. Falla Posterior a Reactor de Sincronizacin
Compensacin Capacitiva Proyecto UPME STR 04-2015
S/E El Carmen 66 KV
Fecha: 30/11/16 INFORME ESTUDIO DE COORDINACIN DE PROTECCIONES
Pgina 17 de 43
Rev. 6
TCalamar 66
lod CALAMAR6
36.418
0.552
3.448
0.000
0.000
0.000
0.000
0.00
0.00
Atlantico 110
TUBOCAR1 Calamar 66
1.94 2.48
0.005 0.007
lod SNJACIN6
0.000 0.000
Ternera 1 220/110
0.000
0.000
0.00
13
117.108
15.02 1.065
0.039 -0.118
0.000 15.02
TSan Jacinto 66 0.00
San Jacinto 66
0.079 36.418
Shunt/Filter
0.000
239.983 0.000 0.000 0.552
0.000
0.000
3.448
0.00
1.091
-0.004 5.06 5.06 89.37 Inactive
0.013 0.013 0.782 0.00
0.000 0.000 2.032 0.000 Out of Calculation
0.000 De-energized
Ternera 110 89.37
0.782
2.032
Series Re..
Series Reactor
0.00
lod ELCARMN6 0.000
0.000
0.00 89.37 0.00
Nv Cospique 110 0.000
0.000
0.782
0.000
0.000
0.000
36.418
0.552
0 0.00 3.448
0 0.000 El Carmen 66 Zambrano 66
0 0.000
0.00 36.418
0.000 0.552
0.000 3.448
14 El Carmen - Zambrano 1 66
0.000
0.000
0.00
89.37
Figura 4-10 Cortocircuito Falla Trifsica, Dem. MAX, Ao 2016, Zona Bolivar 66 kV. Escenario Lnea Gambote-El Carmen
Abierta. Falla posterior a Reactor de Sincronizacin
TCalamar 66
lod CALAMAR6
32.308
41.153
39.803
9.13
0.24
0.00
0.03
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
Atlantico 110
od TUBOCAR1 Calamar 66
0.00 2.20 0.65
0.00 0.02 0.01
0.00 0.00 0.00
lod SNJACIN6
0.00
0.00
0.00
0.00
13
68.131
2.87 69.436
0.02 69.440
0.00
0.00
2.99 TSan Jacinto 66 0.00
0.00
San Jacinto 66
0.05 27.818
Shunt/Filter
0.00 0.00
138.078 0.00 40.727
0.01 38.990
0.00
0.00
0.00
0.00
139.299
139.361 2.19 2.19 39.41 Inactive
0.02 0.02 1.034 0.00
0.00 0.00 2.636 0.00 Out of Calculation
0.00 0.00 0.00 De-energized
Ternera 110 39.41
0.00
1.03
2.64
Series Re..
1.03
Series Reactor
0.00
lod ELCARMN6 0.000
0.000
9.12 39.41 0.00
0.24 1.03 0.00
Nv Cospique 110 0.00
0.00
0.03
0.00
1.03
0.00
0.00
0.00
0.00
0.00 27.818
40.727
.00 0.00 0.00 38.990
.00 0.00 0.00 El Carmen 66 Zambrano 66
.00 0.00 0.00
.00 0.00 0.00 0.01 27.815
0.00 40.727
0.00 38.992
0.00 El Carmen - Zambrano 1 66
14
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
19.04
0.30
0.00 lod ZAMBRAN6
0.06
Figura 4-11 Cortocircuito Falla Monofsica, Dem. MAX, Ao 2016, Zona Bolivar 66 kV. Escenario Lnea Gambote-El
Carmen Cerrada. Falla Posterior a Reactor de Sincronizacin
Compensacin Capacitiva Proyecto UPME STR 04-2015
S/E El Carmen 66 KV
Fecha: 30/11/16 INFORME ESTUDIO DE COORDINACIN DE PROTECCIONES
Pgina 18 de 43
Rev. 6
TCalamar 66
lod CALAMAR6
24.277
39.655
38.500
0.01
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
Atlantico 110
BOCAR1 Calamar 66
0.00 0.48 0.64
0.00 0.00 0.01
0.00 0.00 0.00
lod SNJACIN6
0.00 0.00 0.00
Ternera 1 220/110
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
13
68.119
3.98 69.400
0.03 69.468
0.00
0.00
4.09 TSan Jacinto 66 0.00
0.00
San Jacinto 66
0.06 24.295
Shunt/Filter
0.00 0.00
138.801 0.00 39.654
0.01 38.487
0.00
0.00
0.00
0.00
139.513
139.498 1.35 1.35 34.42 Inactive
0.01 0.01 0.903 0.00
0.00 0.00 2.348 0.00 Out of Calculation
0.00 0.00 0.00 De-energized
Ternera 110 34.42
0.00
0.90
2.35
Series Re..
0.90
Series Reactor
0.00
lod ELCARMN6 0.000
0.000
0.01 34.42 0.00
0.00 0.90 0.00
Nv Cospique 110 0.00
0.00
0.00
0.00
0.90
0.00
0.00
0.00
0.00
0.00 24.295
39.654
0.00 0.00 38.487
0.00 0.00 El Carmen 66 Zambrano 66
0.00 0.00
0.00 0.00 0.00 24.292
0.00 39.654
0.00 38.489
0.00 El Carmen - Zambrano 1 66
14
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
24.15
0.38
0.00 lod ZAMBRAN6
0.06
Figura 4-12 Cortocircuito Falla Monofsica, Dem. MAX, Ao 2016, Zona Bolivar 66 kV. Escenario Lnea Gambote-El
Carmen Abierto. Falla posterior a Reactor de Sincronizacin
0.000
0.000
0.00
Atlantico 110
TUBOCAR1 Calamar 66
7.67 3.13
0.020 0.008
lod SNJACIN6
0.000 0.000
Ternera 1 220/110
0.000
0.000
0.00
13
115.786
10.48 1.053
0.028 -0.078
0.000 10.48 TSan Jacinto 66 0.00
San Jacinto 66
43.121
Shunt/Filter
0.055 0.000
235.610 0.000 0.000 0.653
0.000
0.000
1.071 4.746
0.00
lod ELCARMN6
43.121
0.653
0.00 4.746
0.000 El Carmen 66 Zambrano 66
0.000
0.00 43.121
0.000 0.653
0.000 4.746
5 El Carmen - Zambrano 1 66
0.000
0.000
0.00
71.56
0.376 lod ZAMBRAN6
0.000
Figura 4-13 Cortocircuito Falla Trifsica, Dem. MIN, Ao 2016, Zona Bolivar 66 kV. Escenario Lnea Gambote-El Carmen
Cerrada. Falla posterior a Reactor de Sincronizacin
Compensacin Capacitiva Proyecto UPME STR 04-2015
S/E El Carmen 66 KV
Fecha: 30/11/16 INFORME ESTUDIO DE COORDINACIN DE PROTECCIONES
Pgina 19 de 43
Rev. 6
TCalamar 66
lod CALAMAR6
36.211
0.549
3.448
0.000
0.000
0.000
0.000
0.00
0.00
Atlantico 110
lod TUBOCAR1 Calamar 66
lod SNJACIN6
0.000 0.000 0.000
Ternera 1 220/110
0.000
0.000
0.00
13
116.243
14.53 1.057
0.038 -0.116
0.000 14.53 TSan Jacinto 66 0.00
San Jacinto 66
36.211
Shunt/Filter
0.076 0.000
238.067 0.000 0.000 0.549
0.000
0.000
1.082 3.448
0.00
0.26 -0.010 5.35 5.35 88.86 Inactive
0.001 0.014 0.014 0.777 0.00
0.000 0.000 0.000 2.020 0.000 Out of Calculation
A) Ternera 110 88.86 0.000 De-energized
0.777
2.020
Series Re..
Series Re..
lod ELCARMN6
5
0.000
0.000
0.000
0.000
0.00
0.00
88.86
0.466 lod ZAMBRAN6
0.000
0.000
0.000
0.00
El Carmen 110
0.00 0.00
0.000 0.000 86.751
119.053 0.789
Figura 4-14 Cortocircuito Falla Trifsica, Dem. MIN, Ao 2016, Zona Bolivar 66 kV. Escenario Lnea Gambote-El Carmen
Abierta. Falla Posterior a Reactor de Sincronizacin
lod CALAMAR6
32.078
41.093
39.752
9.02
0.24
0.00
0.03
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
Atlantico 110
lod TUBOCAR1 Calamar 66
2.10 0.00 1.89 0.75
0MVA) 0.02 0.00 0.01 0.01
0.00 0.00 0.00 0.00
lod SNJACIN6
0.00
0.00
0.00
0.00
13
67.622
2.72 69.315
0.02 69.312
0.00
0.00
2.84 TSan Jacinto 66 0.00
0.00
San Jacinto 66
0.04 27.638
Shunt/Filter
0.00 0.00
136.960 0.00 40.678
0.01 38.952
139.021
0.00
0.00
0.00
0.00
1.03
Series Re..
lod ELCARMN6
9.01 39.16 0.00
68.496 0.24 1.03 0.00
69.511 Nv Cospique 110 0.00
0.00
0.03
0.00
1.03
0.00
0.00
69.546 0.00
0.00
0.00 27.638
40.678
0.00 0.00 0.00 38.952
0.00 0.00 0.00 El Carmen 66 Zambrano 66
0.00 0.00 0.00
0.00 0.00 0.00 0.01 27.635
Argos 110 0.00 40.678
0.00 38.955
0.00 El Carmen - Zambrano 1 66
68.496
69.511
69.546
5
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
18.96
0.00
0.30
0.00 lod ZAMBRAN6
0.06
0.00
0.00
0.00
0.00
Figura 4-15 Cortocircuito Falla Monofsica, Dem. MIN, Ao 2016, Zona Bolivar 66 kV. Escenario Lnea Gambote-El
Carmen Cerrada. Falla posterior a Reactor de Sincronizacin
Compensacin Capacitiva Proyecto UPME STR 04-2015
S/E El Carmen 66 KV
Fecha: 30/11/16 INFORME ESTUDIO DE COORDINACIN DE PROTECCIONES
Pgina 20 de 43
Rev. 6
TCalamar 66
lod CALAMAR6
24.170
39.634
38.475
0.01
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
Atlantico 110
lod TUBOCAR1 Calamar 66
0.08 0.00 0.18 0.68
VA) 0.00 0.00 0.00 0.01
0.00 0.00 0.00 0.00
lod SNJACIN6
0.00 0.00 0.00 0.00
Ternera 1 220/110
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
13
67.731
3.86 69.317
0.03 69.363
0.00
0.00
3.97 TSan Jacinto 66 0.00
0.00
San Jacinto 66
0.06 24.187
Shunt/Filter
0.00 0.00
137.946 0.00 39.634
0.01 38.463
139.317
0.00
0.00
0.00
0.00
0.08 139.271 1.43 1.43 34.27 Inactive
0.00 0.01 0.01 0.899 0.00
0.00 0.00 0.00 2.337 0.00 Out of Calculation
0.00 0.00 0.00 0.00
VA) Ternera 110 34.27
0.00
De-energized
0.90
2.34
Series Re..
0.90
Series Re..
lod ELCARMN6
0.01 34.27 0.00
68.983 0.00 0.90 0.00
69.659 Nv Cospique 110 0.00
0.00
0.00
0.00
0.90
0.00
0.00
69.637 0.00
0.00
0.00 24.187
39.634
0.00 0.00 0.00 38.463
0.00 0.00 0.00 El Carmen 66 Zambrano 66
0.00 0.00 0.00
0.00 0.00 0.00 0.00 24.184
rgos 110 0.00 39.634
0.00 38.465
0.00 El Carmen - Zambrano 1 66
69.659
69.637
5
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
24.04
0.38
0.00 lod ZAMBRAN6
0.06
00
00
00
00
Figura 4-16 Cortocircuito Falla Monofsica, Dem. MIN, Ao 2016, Zona Bolivar 66 kV. Escenario Lnea Gambote-El
Carmen Abierto. Falla posterior a Reactor de Sincronizacin
Se recomienda ajustar una etapa de tiempo definido a una corriente de 3 *In y un tiempo de
operacin de 100 ms, para asegurar la no operacin de la proteccin ante corrientes inrush.
Compensacin Capacitiva Proyecto UPME STR 04-2015
S/E El Carmen 66 KV
Fecha: 30/11/16 INFORME ESTUDIO DE COORDINACIN DE PROTECCIONES
Pgina 21 de 43
Rev. 6
Para los sistemas de potencia aterrizados con bancos de condensadores aislados, el rel de
sobreintensidad de neutro 51N debe ajustarse sensitivamente para detectar y proporcionar una
compensacin rpida para fallos de tierra de bajas magnitudes, no detectadas por los rels de
sobre intensidad de fase. Para tal caso se recomienda un valor de corriente de arranque de
0.15*In.
En el ajuste del rel de sobretensin se deber considerar las tensiones mximas operativas bajo
las cuales trabajar la compensacin para evitar que se desconecte en una condicin operativa
normal, en la cual se requiere que el banco est conectado. Se debe ajustar el rel a una tensin
inferior a su curva de soporte y garantizando que opere de manera selectiva con las funciones de
sobretensin de los elementos adyacentes (Lneas de Transmisin y Transformadores)
El ajuste se realizar con dos etapas de tiempo definido, las cuales se ajustarn teniendo en cuenta
las condiciones de soportabilidad mostradas en la Tabla 3.1-2. y el tiempo de operacin con las
protecciones de sobretensin de los elementos adyacentes.
El retardo de rel impide el disparo del banco por fallas del sistema externas a l. Por lo tanto se
deber ajustar de tal manera que para fallas ubicadas en puntos del sistema que provoquen una
tensin inferior al 40% de la tensin nominal este actu con mnimo 200 ms despus del tiempo
de operacin de las protecciones de tiempo inverso y de distancia que protegen las lneas
adyacentes.
Compensacin Capacitiva Proyecto UPME STR 04-2015
S/E El Carmen 66 KV
Fecha: 30/11/16 INFORME ESTUDIO DE COORDINACIN DE PROTECCIONES
Pgina 22 de 43
Rev. 6
Teniendo en cuenta los criterios establecidos en el numeral 5.1 se obtuvieron los siguientes
ajustes registrados en la Tabla 6-1 para la proteccin 50/51 y 50N/51N.
Tabla 6-1 Ajuste propuestos para la proteccin de sobrecorriente 50/51 y 50N/51N
Se ajusta la caracterstica de tiempo definido para asegurar que la proteccin no opere ante
corrientes de energizacin en la zona de tiempo definido
Se verific que no hubiera descoordinacin para fallas trifsicas hechas en el banco capacitivo de
la subestacin el Carmen 66 kV, con la proteccin de distancia de fase de la lnea El Carmen -
Gambote, en el extremo de la subestacin Gambote. Para este caso de coordinacin se garantiz
que la gradacin de tiempo existente entre esta proteccin y la funcin de sobrecorriente de fase
fuese superior a 150 [ms].
Se verific que no hubiera descoordinacin para fallas monofsicas hechas en el banco capacitivo
de la subestacin el Carmen 66 kV, con la proteccin de distancia de tierra de la lnea El Carmen -
Gambote, en el extremo de la subestacin Gambote. Para este caso de coordinacin se garantiz
que la gradacin de tiempo existente entre esta proteccin y la funcin de sobrecorriente de tierra
fuese superior a 200 [ms].
Se verific que los ajustes calculados consideraran las condiciones de energizacin descritas en el
numeral 3.1.1 de este documento.
Teniendo en cuenta los criterios establecidos en el numeral 5.3 y las caractersticas del banco
capacitivo de acuerdo al numeral 3.1, se obtuvieron los siguientes ajustes registrados en la Tabla
6-2 para la proteccin 59.
Parmetro Ajuste
Method of measurement Fundamental comp
Measured Value Phase-to-phase
Pickup mode 3 out of 3
Primera Etapa Tiempo Definido
Definite-T 1:Mode on
Thereshold 1.12* V rated= 1.12*110=123.2 secV
Time Delay 50 s
Compensacin Capacitiva Proyecto UPME STR 04-2015
S/E El Carmen 66 KV
Fecha: 30/11/16 INFORME ESTUDIO DE COORDINACIN DE PROTECCIONES
Pgina 25 de 43
Rev. 6
Teniendo en cuenta los criterios establecidos en el numeral 5.4 se obtuvieron los siguientes
ajustes registrados en la Tabla 6-4 para la proteccin 27.
Tabla 6-4 Ajustes de la proteccin de Subtension 27
Parmetro Ajuste
Method of measurement Fundamental comp
Measured methot Phase to phase
Pickup Thershold 40% Rated Voltage =26.4 pri kV
Pickup mode 1 out 3
Pickup delay yes
Operate delay 2.5 s
Teniendo en cuenta los criterios establecidos en el numeral 5.5 se obtuvieron los siguientes
ajustes registrados en la siguiente tabla para la proteccin 60N. Tomando la configuracin del
banco capacitivo conformada por 4 niveles en serie y dos unidades paralelas por nivel, se calcul el
desbalance producido al sacar de operacin una unidad capacitiva.
Compensacin Capacitiva Proyecto UPME STR 04-2015
S/E El Carmen 66 KV
Fecha: 30/11/16 INFORME ESTUDIO DE COORDINACIN DE PROTECCIONES
Pgina 26 de 43
Rev. 6
Parmetro Ajuste
MP Selection Punto de medicin I unbalanced CT 5:1
Threshold defective C-elem 1.88 secA
General:De-energ.time w/o comp. 1s
El ajuste se determin tomando el desbalance generado por la falla de una unidad capacitiva,
calculada con la capacitancia total suministrada por el fabricante y la disposicin de las unidades
(4S2P)
Compensacin Capacitiva Proyecto UPME STR 04-2015
S/E El Carmen 66 KV
Fecha: 30/11/16 INFORME ESTUDIO DE COORDINACIN DE PROTECCIONES
Pgina 27 de 43
Rev. 6
7. CONCLUSIONES
Todos los ajustes recomendados con base en los criterios establecidos, funcionan de manera
adecuada en cuanto a coordinacin, selectividad, rapidez y estabilidad, permitiendo adems la
operacin de las protecciones principales y luego las de respaldo.
Para la proteccin de sobrecorriente no direccional de fase y de tierra del banco de
condensadores, se simularon fallas trifsicas y monofsicas para verificar su adecuada
operacin y coordinacin con las funciones de proteccin de la zona de influencia del
proyecto. Los resultados de estos anlisis se presentan en el Anexo A de este documento.
Se deber realizar en campo la medida de la corriente de desbalance para verificar y calcular
nuevamente en caso de ser necesario el ajuste de la funcin de desbalance de neutro (60N).
Se encontr que para una falla hecha en el banco capacitivo de la subestacin el Carmen 66
kV, la proteccin de distancia de fase de la lnea El Carmen - Gambote, en el extremo de la
subestacin Gambote presenta un disparo de la zona 2 de proteccin en un tiempo de 0.2 [s].
Para garantizar la operacin coordinada de la proteccin de sobrecorriente de fase del banco
capacitivo, se redujo al mnimo el tiempo de operacin de la funcin de tiempo definido para
as lograr una gradacin de tiempo de mnimo 150 [ms].
Se encontr que para una falla hecha en el banco capacitivo de la subestacin el Carmen 66
kV, la proteccin de distancia de tierra de la lnea El Carmen - Gambote, en el extremo de la
subestacin Gambote presenta un disparo de la zona 2 de proteccin en un tiempo de 0.2 [s].
Para garantizar la operacin coordinada de la proteccin de sobrecorriente de tierra del banco
capacitivo, se redujo al mnimo el tiempo de operacin de la funcin de tiempo definido para
as lograr una gradacin de tiempo de mnimo 200 [ms].
Todos los ajustes recomendados en este estudio, as como la correcta operacin de la
direccionalidad, deben ser probados y verificados en sitio mediante pruebas de inyeccin
secundaria en todos los rels de las subestaciones del proyecto durante la etapa de puesta en
se vi io y se de e ve ifi a en sitio ue las ela iones de CTs y PTs o esponde a lo a
reportado.
Compensacin Capacitiva Proyecto UPME STR 04-2015
S/E El Carmen 66 KV
Fecha: 30/11/16 INFORME ESTUDIO DE COORDINACIN DE PROTECCIONES
Pgina 28 de 43
Rev. 6
DIgSILENT
I =767.404 pri.A X =2300.000 pri.A
100
[s ]
10
0.729 s
2300.010 pri.A
0.100ss
0.100
0.1
66.00 kV 10 100 1000 [pri.A] 10000
El Carm en 66\Cub_2\R OC COMP El Carm en Ph-Ph Gam bote 66\Cub lin CARM\R OC Gam bote-El Carm en Ph ph
Figura A 1 Falla Trifsica. Sub El Carmen R OC Gambote-El Carmen & R OC COMP El Carmen
Compensacin Capacitiva Proyecto UPME STR 04-2015
S/E El Carmen 66 KV
Fecha: 30/11/16 INFORME ESTUDIO DE COORDINACIN DE PROTECCIONES
Pgina 30 de 43
Rev. 6
DIgSILENT
I =1551.255 pri.A
I =2300.000 pri.A
10
[s ]
R OC COMP El Carmen Ph-Ph
0.470 s
0.372 s
2300.568 pri.A
0.100 s
0.1 0.100 s
66.00 kV 10 100 1000 [pri.A] 10000
El Carm en 66\Cub_2\R OC COMP El Carm en Ph-Ph El Carm en 66\Cub tr3 CARM 13.8\R OC BAHTRAN T1 60 MVA Ph-Ph El Carm en
Figura A 2Falla Trifsica. Sub El Carmen R OC BAHTRANS El Carmen & R OC COMP El Carmen
Compensacin Capacitiva Proyecto UPME STR 04-2015
S/E El Carmen 66 KV
Fecha: 30/11/16 INFORME ESTUDIO DE COORDINACIN DE PROTECCIONES
Pgina 31 de 43
Rev. 6
DIgSILENT
3*I0 = 84.886 pri.A 3*I0 =3040.120 pri.A
100
[s ]
10
0.1
0.020 s
0.01
66.00 kV 10 100 1000 [pri.A] 10000
El Carm en 66\Cub_2\R OC COMP EL Carm en Ph-E Gam bote 66\Cub lin CARM\R OC Gam bote-El Carm en Ph E
Figura A 3Falla Monofsica Ubicacin despus del rel de sobrecorriente compensacin capacitiva. Sub Gambote R OC
Gambote-El Carmen & R OC COMP El Carmen Ph-E
Compensacin Capacitiva Proyecto UPME STR 04-2015
S/E El Carmen 66 KV
Fecha: 30/11/16 INFORME ESTUDIO DE COORDINACIN DE PROTECCIONES
Pgina 32 de 43
Rev. 6
DIgSILENT
3*I0 =3040.120 pri.A
10
0.113 s
0.1
0.020 s
0.01
66.00 kV 10 100 1000 [pri.A] 10000
El Carm en 66\Cub_2\R OC COMP EL Carm en Ph-E El Carm en 66\Cub tr3 CARM 13.8\R OC BAHTRAN T1 60 MVA Ph-E
Figura A 4Falla Monofsica Ubicacin despus del rel de sobrecorriente compensacin capacitiva. Sub El Carmen R OC
BAHTRANS El Carmen & R OC COMP El Carmen Ph-E
Compensacin Capacitiva Proyecto UPME STR 04-2015
S/E El Carmen 66 KV
Fecha: 30/11/16 INFORME ESTUDIO DE COORDINACIN DE PROTECCIONES
Pgina 33 de 43
Rev. 6
Proteccin de Sobrecorriente
Sobreintensidad temporizada Unidad 1
Arranque Temp Fase 0.52
Curva Temp Fase [IEC]Inversa
Indice Temp Fase 0.08
Tiempo fijo de Fase 0.05
Sobreintensidad temporizada Unidad 1 de Neutro Unidad 1
Arranque Temp Neutro 0.15
Compensacin Capacitiva Proyecto UPME STR 04-2015
S/E El Carmen 66 KV
Fecha: 30/11/16 INFORME ESTUDIO DE COORDINACIN DE PROTECCIONES
Pgina 38 de 43
Rev. 6
Proteccin de Sobrecorriente
Sobreintensidad temporizada
Arranque Temp Fase 1.5
Curva Temp Fase [IEC]Inversa
Dial 0.2
Tiempo fijo de Fase
Sobreintensidad temporizada Unidad 1 de Neutro Unidad 1
Arranque Temp Neutro 0.5
Curva Temp Neutro (IEC) Inversa
Dial 0.1 (RELE RX Serie earth)
Tiempo fijo Neutro
Instantneo de Fases
Arranq Inst Fase 10
Tiempo Inst Fase 0
Instantneo de Neutro
Arranq Inst Fase 6
Tiempo Inst Fase 0
Angulo ZP Tierra 59
Alcance Z4F-Tierrra 3.3
Angulo Z4F-Tierra 59
tZ1 Gnd delay 0.05
tZ2 Gnd delay 0.2
tZ3 Gnd delay 0.8
tZp Gnd delay 1
Proteccin de Sobre-corriente
Sobre intensidad temporizada Unidad 1
Arranque Temp Fase 4.68 A
Curva Temp Fase [IEC] Inversa
Indice Temp Fase 0.14
Tiempo fijo de Fase 0.05
Sobreintensidad temporizada Unidad 1 de Neutro Unidad 1
Arranque Temp Neutro 1.5 A
Curva Temp Neutro [IEC] Inversa
Indice Temp Neutro 0.16
Tiempo fijo Neutro 0.05
Instantneo de Fases Unidad 1
Arranq Inst Fase No
Tiempo Inst Fase No
Instantneo de Neutro Unidad 1
Arranq Inst Fase No
Tiempo Inst Fase No
Compensacin Capacitiva Proyecto UPME STR 04-2015
S/E El Carmen 66 KV
Fecha: 30/11/16 INFORME ESTUDIO DE COORDINACIN DE PROTECCIONES
Pgina 42 de 43
Rev. 6