Air System Sizing Summary for 0002 LIFT LOBBY MF

Project Name: PETRONAS 20150309 03/18/2016


Prepared by: TEKNIS KONSULT 08:44AM

Air System Information


Air System Name ...................... 0002 LIFT LOBBY MF Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 407.0 ft
Air System Type ................................................ SZCAV Location ................................... Kota Kinabalu, Malaysia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ...................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load ............................................................ 1.7 Tons Load occurs at .................................................... Apr 1400
Total coil load .......................................................... 20.9 MBH OA DB / WB ...................................................... 93.1 / 82.9 F
Sensible coil load ................................................... 15.1 MBH Entering DB / WB ............................................. 74.6 / 64.3 F
Coil CFM at Apr 1400 .............................................. 737 CFM Leaving DB / WB .............................................. 55.6 / 54.7 F
Max block CFM ....................................................... 737 CFM Coil ADP ..................................................................... 53.5 F
Sum of peak zone CFM .......................................... 737 CFM Bypass Factor .......................................................... 0.100
Sensible heat ratio ............................................... 0.725 Resulting RH ................................................................. 53 %
ft/Ton ................................................................... 234.1 Design supply temp. ................................................... 55.0 F
BTU/(hr-ft) ............................................................. 51.3 Zone T-stat Check .................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... 4.18 gpm Max zone temperature deviation .................................. 0.0 F

Supply Fan Sizing Data

Actual max CFM ...................................................... 737 CFM Fan motor BHP ........................................................... 0.11 BHP
Standard CFM ......................................................... 737 CFM Fan motor kW ............................................................. 0.08 kW
Actual max CFM/ft ................................................ 1.81 CFM/ft Fan static .................................................................... 0.50 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................... 65 CFM CFM/person ................................................................ 8.00 CFM/person
CFM/ft ................................................................... 0.16 CFM/ft

Hourly Analysis Program v4.50 Page 1 of 1