Professional Documents
Culture Documents
VECTOR
Feeedwater Valves
1
I
t is critical within power plant
operations in drum boilers (or flow 3500
in once-through boilers); the level of
feedwater is within required limits. Feedwater pump pressure
3000
Considering drum type boilers, if the
High Cv
drum level is too high or too low, the required to
plant may be forced to trop. Drum or boiler 2500 minimize system
level control is crucial at plant start-up, resistance and
maximize
when the pressure differential between the
Pressure (psi)
2000 plant efficiency
boiler feed pump (BFP) and boiler is very Low Cv required to handle
large pressure difference !
high and control id difficult. Boiler feedwater
1500
control valves much achieve a smooth start-
up and maintain required drum level for
safe, reliable and efficient plant operation. 1000
During load change This VECTOR feedwater valve is one of 20 severe service control
(assuming fixed speed boiler feed pump) valves supplied to Maire Tecnimont S.p.A., based in Rome, Italy for
Load changes are often experienced the Colbun coal-fired power plant in Chile.
and this will result in a lower steam
pressure and drum pressure, but
feedwater pressure will remain similar,
resulting in a higher pressure differential.
Figure 2 shows that the P, and do Cv
requirements, at full load on a 2x2x1
combined cycle power plant (CCPP)
are significantly different depending on
whether one GT (gas turbine) or two
GTs are in operation and so the control
valve used must be able to meet a wide
range of Cv requirements to provide full
flexibility to the plant.
With once-through boilers there can be
similar issues, particularly at start-up
when boiler regulator valve is used before
the main variable speed pumps (usually
steam turbine driven) go into operation.
2
Warning signs of feedwater control valve Solution: This service requires:
problems Customized Cv versus stroke characterization that matches the flow
Cavitation/flashing: insufficient pressure reducing stages will characteristics of the feedwater valve as seen in Figure 1.
cause high velocity flows, leading to valve/trim damage Pneumatically stiff actuator for good resolution in positioning. A
conventional diaphragm is not adequate double-acting pneumatic
Down-time: poor control at low flows can lead to plant trips and/or piston actuator is required.
an extended start-up process
Long stroke is required for fine control of feedwater flow.
Increased maintenance: frequent replacement and repair of valve
Velocity control in the trim (less than 75 ft. per second at the trim
components exit) to ensure that the performance of the I/P, positioner etc. is not
Symptoms of feedwater control valve problems degraded by high vibration.
Erosion damage caused by: Conclusion:
Insufficient number of trim stages, creating excessive trim velocities
Fluid velocity control was vitally important to solving the problems
Poor seat design and insufficient seat force experienced by the existing valve.
Plug or stem breakage: typically caused by high trim velocities The solution proposed by Koso met all the solution requirements
that lead to trim vibration and fatigue failure identified above and will provide long-term reliable service at
Springerville Generating Station.
Vibration and noise: caused by cavitation and rampant internal velocities
velocities at the trim exit. High vibrations can cause the failure of control ~
accessories mounted on the valve as well as stem breakage. In this case Boiler feedpump
recirculation
Economizer valve
the vibration was further aggravated by cavitation. area of boiler DA level
control valve
Feedwater
regulator
Boiler Deaerator
Solution: This service required VECTOR trim with a minimum of 12 valve
feedpump Condensate Hot well
pump
stages of pressure reduction at low flow rates to eliminate high vibrations
and provide 75 ft. per second of feedwater velocity at the trim exit.
2 valve solution Combined
2) Observation: The control of feedwater flow by the low load solution
feedwater regulator was poor and was also causing transients that were
not good for the boiler feed-pump.
Combined feedwater
control valve
Diagnosis: Poor control by the low load feedwater regulator can be Start-up feedwater
traced primarily to poor characterization and insufficient actuator Diagram 3. Combined control valve
resolution. Also, the high vibration affected the control performance of feedwater control valve
Figure 2: Combined feedwater control valve
confiuration instead of two
the valve.
3
KOSO estimates for a feedwater control system on a 500MW
2x2x1 combined cycle power plant, the hardware savings
could amount to at least $20,000 per unit with two units per
plant. Heres what KOSO have identified savings sources; fill in
the table (Table 1) to see what yours would be.
One of 12 four inch min-flow feedwater recirc valves supplied to CFE - Comision Federal de
Electricidad in Mexico.
4
VECTOR technology
provides superior fluid
velocity control
KOSO has designed VECTOR
to operate within the ISA Guide,
Control Valves, Practical Guides for
Measurements and Control, to provide
sufficient velocity control.
Fluid
velocity vs.
Recommended Recommended
P stages of
velocity stages
pressure
drop
4 stages Multi-stage Stages
Bar psi m/s ft/s m/s ft/s
100 1450 48 157 30 98 10
Diagram 6. VECTOR multi-stage trim can be characterized to permit excellent low flow
control and high-flow capacity protection.
5
Staging stops erosion and cavitation
VECTOR solution
Kosos VECTOR trim forces the flow to travel through a tortuous
path of right angle turns (Figure 8). Each turn causes a pressure P1
loss to the fluid (Figure 9) so velocity is reduced gradually based Inlet
pressure
on the number of turns. The series of multiple pressure drops
allows the pressure to reduce without falling below the vapor
pressure (Figure 10) thus avoiding cavitation (Figure 11). Cavitation
Outlet
can be a devastating destructive force to valve components and V1 V2 Velocity
custom solutions 80
70
Linear
6
Actuator sized to
provide optimum
seat ring loading
Characterized
Stem packing
VECTORTM
disk stack Balance seal
Multi-stage VECTORTM
disk stack technology
Class V shut-off
100 100
90 90
80 80
70 70
60 60
% Cv
% Cv
50 50
40 40
30 30
20 20
10 10
0 0
0 10 20 30 40 50 60 70 80 90 100 0 10 20 30 40 50 60 70 80 90 100
% stroke % stroke
7
Diagram 11. Specifications shown are for the standard
VECTOR feedwater product offering. Other custom
sizes are available.
50.8 mm (2.0) Use 2500 ANSI Use 2500 ANSI 3300 mm (13.00) 1270 (50) 180 kg (400 lbs) 3, 4 578 mm (22.75) 300 mm (13.00) 2030 mm (50) 200 kg (450 lbs)
127 mm (5.0) 8, 10 1980 mm (42.50) 1370 mm (54) 1150 (kg) 2500 lbs 8, 10 1080 mm (42.50) 1370 mm (54) 1150 kg (2500 lbs
152.4 mm (6.0) 10, 12, 14 1270 mm (50) 1880 mm (74) 2300 kg (5000 lbs) 10, 12, 14 1270 mm (50) 1880 mm (74) 2300 kg (5000 lbs)
Contact KOSO for Contact KOSO for
these options these options
177.8 mm (7.0) 10, 12, 14 1270 mm (50) 1880 mm (74) 2300 kg (5000 lbs) 10, 12, 14 1270 mm (50) 1880 mm (74) 2300 kg (5000 lbs)
228.6 mm (9.0) 12, 14, 16 1610 mm (63.40) 1920 mm (76) 3400 kg (7500 lbs) 12, 14, 16 1610 mm (63.40) 1920 mm (76) 3400 kg (7500 lbs)