Professional Documents
Culture Documents
Distance protection settings (ZM, PHS and SOTF) are according to exercise5. SOTF
function should be set to Automatically detect the CB closing action.
NOTHING should be artificially set OFF.
2. Configure the carrier receive signal to a proper Binary Input by using SMT (if not
done previously):
In this exercise the carrier receive signal is supposed to be received by the IED via a
binary input. Open SMT and connect a suitable binary input to the virtual input ZM CR
representing the carrier receive signal1:
1
If you want you can also turn one LED on the HMI when the signal is received, as it is done in the picture
with LED N. 7 (the first of the yellow ones).
Substation Automation & Protection Training
SA.T. Training SEP-602A 2007-09-13 Page 2 of 17
ABB AB
Training Course SEP-602A EXERCISE 6
Power Automation & Substation
Lima - Per
3. Enter correct settings for ZCOM and ZCAL and download them in the IED
Correct settings for ZCOM to perform PTT scheme are the followings:
ZCAL is set ON and set to send echo carrier and trip local CB.
2
Coordination Time is used in blocking schemes. In permissive schemes like PUTT or POTT, there is no
need to wait. As soon as the carrier is received and the local fault detection is achieved (ZM02-START) the
trip command can be issued.
Substation Automation & Protection Training
SA.T. Training SEP-602A 2007-09-13 Page 3 of 17
ABB AB
Training Course SEP-602A EXERCISE 6
Power Automation & Substation
Lima - Per
3
Consider that the IED can store up to 100 disturbances, so it may be difficult to find (or recognize) exactly
the last disturbances and it can happen that you upload the wrong disturbance. To save time it is better to
avoid confusion and delete the disturbances at the beginning.
Substation Automation & Protection Training
SA.T. Training SEP-602A 2007-09-13 Page 4 of 17
ABB AB
Training Course SEP-602A EXERCISE 6
Power Automation & Substation
Lima - Per
Inject the sequence and verify in the disturbance recorder that the relay tripped by
ZCOM function!
Remove the carrier receive signal from the IED. Inject the same sequence, verify time
delayed trip by ZM02 timer:
Manually and steadily activate the binary input corresponding to Carrier Receive
signal. Do not inject any fault. Verify that the relay will not trip.
5. Inject a fault in ZM01 (or ZM02) and verify that the IED sends the carrier signal.
1) Inject a fault in forward direction, inside the protected line, but with fault current level
below the minimum operating current of the IED. The easiest way is to just drop one
voltage, after the correct pre-fault quantities, and zero fault current.
2) After the fault, the relay on the other line-end, sees the fault (ZM01 or ZM02) and
sends the carrier, which reaches our IED. So after lets say 15 ms the carrier receive
signal reaches our IED. This is simulated by a binary output activation of the test set.
3) It is expected that the tested IED will send the echo carrier and will also issue local
trip signal from ZCAL function.
Unfortunately the A32 configuration does not have the Carrier Send signal connected to
disturbance recorder, but if you have solved the previous exercises, you have probably
connected the Carrier Send Signal to a suitable LED, so you can verify that the Echo
Carrier has been sent by monitoring that LED.
Interesting to notice that Automatic Fuse Failure can be activated during Weak Infeed
situations, but this does not cause any problem, as impedance protection is not involved
in this logic (it cannot be involved! It is a weak infeed!).
It is of common to believe that Weak Infeed does not work for three-phase faults. This is
why the test is here.
File is:
Same procedure as before, but all the voltages are dropped for the weak infeed fault:
Substation Automation & Protection Training
SA.T. Training SEP-602A 2007-09-13 Page 10 of 17
ABB AB
Training Course SEP-602A EXERCISE 6
Power Automation & Substation
Lima - Per
and verify as well that the echo carrier has been sent (HMI LED for instance).
The weak infeed logic should be carefully tested for reverse faults4 (external faults).
In case of fault in the reverse zone, ZM02 from the other line-end will send the carrier.
THIS IS NOT a weak infeed situation with an internal fault, and we have to make sure
that the relay does not trip instantaneously for this fault.
An instantaneous trip can be caused by wrong settings or also wrong configuration.
Sequence is here:
The fault is a quite strong fault (5A secondary fault current in reverse direction).
Think about A32 configuration, and try to understand why Weak Infeed logic is not
blocked for this external fault!
OPEN the disturbance file for this test. Did the relay measure in reverse direction?
4
All communication schemes should be tested by injecting faults in the protected line INSTANTANEOUS
TRIP and faults outside the protected line NO INSTANTANEOUS TRIP or NO TRIP AT ALL.
Substation Automation & Protection Training
SA.T. Training SEP-602A 2007-09-13 Page 13 of 17
ABB AB
Training Course SEP-602A EXERCISE 6
Power Automation & Substation
Lima - Per
The distance protection zone in A32, dedicated to communication schemes, and set in
reverse direction, is ZM05.
ZM04 has NOTHING to do with the communication scheme. It is just a reverse-backup
zone.
ZM05 is also connected to PHS-STCNDZ, to have the same measuring algorithm of
forward zones ZM01 and ZM02.
We have always considered ZM05 OFF. Now it is time to set it on and make use of it.
It is not wrong to assume that ZM02 from the remote end is similar to our ZM02. So, we
set ZM05 to be 30% larger (or even more) of forward ZM02:
This means that we need to check PHS settings: is PHS also covering reverse ZM05?
Answer is no. So, PHS settings (not related to load encroachment) must be increased
to cover both ZM02 in forward and ZM05 in reverse:
trip is coming after 1s from reverse back-up ZM04. We dont care about it.
Of course, all the tests that we have done previously, should be repeated now, as
we have drastically changed the relay set-up.
Verify in the disturbance recorder the correct behaviour of the internal signals: