I-E96-500B G-1
INSTALLATION DRAWINGS
38.1
1.50
FLOOR
OPENING
NOTES:
1. FOR OPTIONAL W ELD MOUNTING, W ELD BOTTOM OF CABINET BASE
TO EMBEDDED STEEL 5 PLACES FRONT AND BACK, STARTING AT EACH
CORNER AND EQUALLY SPACED. W ELDS SHALL BE MADE BY SHIELDED
METAL ARC PROCESS USING E6010 ELECTRODE.
2. THIS CABINET MUST BE INSTALLED PER STANDARD FLOOR MOUNTING
OR OPTIONAL SHELF MOUNTING.
3. STANDARD ENVIRONMENTAL SPECIFICATIONS FOR THE SYSTEM ARE
APPLICABLE.
4. IF THIS CABINET W ILL BE EXPOSED TO HIGH VIBRATION OR SHOCK
609.6 FORCES, CONSULT ELSAG BAILEY FOR SPECIAL DESIGN.
24.00
5. UNUSED OPENINGS IN TOP AND BOTTOM COVERS, WALLS AND
1136.8 ONE DOOR DOORS OTHER THAN PROVIDED FOR VENTILATION MUST BE
44.76 OPEN EFFECTIVELY CLOSED BY PLUGS OR PLATES TO PROVIDE PROTECTION
SUBSTANTIALLY EQUIVALENT TO THE WALL OF THE CABINET.
INTRODUCTION
G-2 I-E96-500B
INSTALLATION DRAWINGS
OPTIONAL TOP
ENTRY COVER CABLE
IECAP0 OPENING
56.8 228.6
2.12 9.00
COOLING AIR
EXHAUST
COOLING AIR
ENTRANCE
FLOOR
LINE
B 762.0 B
30.00
17.5 DIA. 4 MOUNTING HOLES
A 0.69
INTRODUCTION
I-E96-500B G-3
INSTALLATION DRAWINGS
0.190-32
SCREW SIZE
AC IN
TB1
1153.80
45.425
120 VAC L N
CUSTOMER'S
AC SUPPLY
ENLARGED VIEW A-A
DIMENSIONS
MILLIMETERS
INCHES
WALL MOUNTING DIMENSIONS
NOTES:
1. REVIEW ALL RELATED INSTALLATION AND MAINTENANCE MANUALS BEFORE BEGINNING INSTALLATION OF UNIT.
2. SYSTEM SAFETY GROUND CONNECTION (VIEW A-A).
3. 120 VAC POW ER SOURCE MUST BE W IRED CORRECTLY. INCORRECT W IRING CAN CAUSE SERIOUS EQUIPMENT DAMAGE.
4. APPROXIMATE TOTAL W EIGHT = 93 KG (205 LB) FOR IECFE11/12.
5. MOUNTING BOLT SPECIFICATIONS:
FLOOR MOUNT: 4, 7 /16 -14, GR-5 BOLTS, TORQUE TO 43.4 NM (32 FT-LBS).
D3053760
TP25441A
INTRODUCTION
G-4 I-E96-500B
INSTALLATION DRAWINGS
333.25
13.120
306.26
12.058 WALL MOUNT UNIT ONLY
FRONT DOOR 278.77
DOORS OPEN
HEAT SINK OPEN IECFE12/62 10.975
BOTH ENDS
FAN
MMU
MMU
1243.58
48.960
1122.17
44.180 MMU
SEE ENLARGED
VIEW A-A
PEP (NOTE 3)
115.19
4.535
381.00
15.000 BOTTOM
CABLE ENTRY
355.60 57.15
14.000 2.250
DIMENSIONS
MILLIMETERS
INSULATED GROUND INCHES
BAR FOR DC SYSTEM
469.90
18.500
69.85
2.750
INTRODUCTION
I-E96-500B G-5
G-6
INTRODUCTION
INSTALLATION DRAWINGS
CABINET LIFTING
EYEBOLT (REMOVABLE)
65.1 936.7
2.56 36.88
65.1
2.56 763.6
30.06
1988.3
78.28
BOTTOM VIEW
NOTES:
1. THE CABINET INSTALLATION IS TO PROVIDE FOR FLOOR MOUNTING
USING FOUR -13 GR5 BOLTS, FLAT WASHERS AND SPLIT RING
LOCKWASHERS INTO FLOOR ANCHORS.
2. FOR MULTIPLE CABINETS, THE INSTALLATION MUST PROVIDE FOR A
38.1 MM (1.5 IN.) MINIMUM SPACING BETW EEN ADJACENT CABINETS TO DIMENSIONS
PERMIT CLEARANCE FOR DOOR SW ING. MILLIMETERS
3. NEMA 4 RATING IS PENDING CONFIRMATION. RATING MAY BE INCHES
AFFECTED BY THE ADDITION OF CABLE ENTRY OPENINGS UNLESS
PROVISIONS ARE MADE TO ADEQUATELY SEAL SUCH OPENINGS AFTER
CABLES HAVE BEEN INSTALLED.
4. W HEN LIFTING CABINET USE ALL 4 EYEBOLTS.
611.2
24.06 D3053764
ACCESS PLATE TP25442A
I-E96-500B
482.73
19.005
TOP
390.55
15.376
589.81
23.221
IIOIC404
ONLY BOTH SIDES OF
127.00
PANEL AND EACH
COVER 5.000
SIDE OF MONITOR
HOLDDOW N
149.4
SCREW S (2)
5.88 REF
BEZEL
41.46
ADJUST
INSTALLATION DRAWINGS
256.5
10.10 REF SCREW S
1.632
DIMENSIONS
495.30 MILLIMETERS
19.500 INCHES
VAX MOUNTING BRACKET 550.67
21.680
INTRODUCTION
OMITTED ON IIOIC204/304
614.10
24.177 D3053790
TP25451A
Figure G-4. Panel Mount Operator Interface Console (IIOIC204/404) Installation Drawing
G-7
INSTALLATION DRAWINGS
1090.1 762.0
42.92 30.00
RECOMMENDED
CLEARANCE
FROM WALL FOR
SERVICING AND
AISLEWAY (SEE
NOTE 3)
711.2
28.00
108.7
4.28
149.4
5.88
40.1
1.58
493.8
19.44
A A
BOTTOM CABLE 203.2 63.5
8.00 2.50
SEE NOTE 4 ENTRY AREA
BOTTOM
0.312-18UNC-2A MOUNTING
FASTENERS (4)
CUSTOMER SUPPLIED
CONSOLE
LEVELING
ADJUSTMENT
57.1
2.25
INTRODUCTION
G-8 I-E96-500B
INSTALLATION DRAWINGS
465.1
18.31
REMOVABLE FRONT AND REAR STANDARD RACK
DOORS LIFT OFF FOR EASY ACCESS MOUNTING
63.5
2.50
REAR CABLE ENTRY
711.2
28.00
(REAR) (FRONT)
SEE NOTE 4
1523.9
60.00
433.7
17.08
SEE NOTE 4
738.3
29.07
687.5
27.07
TO REMOVE
INTRODUCTION
I-E96-500B G-9
INSTALLATION DRAWINGS
495.3
19.50
1568.3
61.74
1085.7
42.75
711.2
28.00 63.5
2.50
REAR CABLE ENTRY
FRONT REAR
1090.1 762.0
42.92 30.00
90 ROTATION OF
.
TOP MONITOR
711.2
.
28.00
TOP
NOTES:
1. THE 120/240 VAC POW ER SOURCE MUST BE W IRED CORRECTLY. DIMENSIONS
INCORRECT WIRING CAN CAUSE SERIOUS EQUIPMENT DAMAGE.
MILLIMETERS
2. STABILIZER (PROVIDED) MUST BE USED W HEN CONSOLE IS NOT INCHES
SECURED TO FLOOR.
3. REMOVABLE COUNTER HAS INDEPENDENT LEVELING ADJUSTMENTS.
REFER TO OIS HARDWARE INSTRUCTION. D3053781
TP25444A
INTRODUCTION
G - 10 I-E96-500B
INSTALLATION DRAWINGS
1732.5
68.21
30 TOTAL
TILT
MOUNTING HOLES
FOR ARRAY W EDGES COOLING AIR
EXHAUST
REMOVABLE COUNTER
SEE NOTE 3
COOLING AIR
EXHAUST
COOLING AIR
ENTRANCE
687.5
27.07
IIOIS403 AND
IIOIS4023 ONLY
TO REMOVE
SIDE 113.6
CUSTOMER POW ER 4.47
476.2
CONNECTIONS 18.75 CONSOLE LEVELERS
SEE CROSS-SECTION A-A
108.7
4.28
149.4
5.88
493.8
19.44
0.312-18UNC-2A MOUNTING
FASTENERS (4)
CUSTOMER SUPPLIED
A A
197.1 129.5
CONSOLE 7.76 5.10
LEVELING BOTTOM CABLE
ADJUSTMENT ENTRY AREA
57.1
2.25
DIMENSIONS
MILLIMETERS
INCHES
12.7 DIA. (4) MOUNTING HOLDS
0.50 FOR FLOOR MOUNTING
INTRODUCTION
I-E96-500B G - 11
INSTALLATION DRAWINGS
529.1 439.8
20.83 19.44
69.2 335.4
2.73 13.20
15
482.6
19.00 52.8
2.08
50.8
2.00
404.2
15.91 IICPI01
956.7 493.8
37.66 19.44
885.1
34.85 791.4
31.16
395.8
15.58 482.6
45 19.00
1089.7
42.90
254.5
10.02
50.8
482.6 2.00
19.00
615.4
24.23 DIMENSIONS
IICPI02 MILLIMETERS
INCHES
D3053787
TP25448A
INTRODUCTION
G - 12 I-E96-500B
I-E96-500B
15
482.6
19.00 52.8 STABILIZER
2.08 SEE NOTE 2
INTERUNIT
CABLE RUN
NOTES:
50.8 1. CABLES MAY BE BROUGHT UP
2.00 THROUGH FLOOR UNDER ONE
404.2 UNIT AND ROUTED TO THE
15.91 OTHERS IN AN ARRAY VIA 395.48
711.20 MM (15.57 28.00 IN.) CABLE
RUN.
RECOMMENDED CLEARANCE 2. STABILIZERS (PROVIDED) MUST
15 762.0 FROM WALL FOR SERVICING
REF 30.00 BE USED W HEN CONSOLE IS NOT
AND AISLEWAY (SEE NOTE 5) 711.2 SECURED TO FLOOR.
28.00 3. FLOOR MOUNTING: ALL FULL
W IDTH UNITS MUST BE SECURED
TO FLOOR. W EDGES ARE TIED TO
ADJACENT FULL W IDTH UNITS.
1089.4 4. THE W EDGE UNIT IS DESIGNED
INSTALLATION DRAWINGS
42.89 TO BE USED ONLY BETW EEN FULL
W IDTH UNITS.
215.7
8.49 5. APPLICABLE CODES AND
STANDARDS MAY REQUIRE
ADDITIONAL CLEARANCE.
1270.0 DIMENSIONS
1054.1 50.00
MILLIMETERS
INTRODUCTION
41.50
INCHES
D3053782
TP25445A
G - 13
INSTALLATION DRAWINGS
1732.5
68.21
MOUNTING
HOLES FOR COOLING AIR
ARRAY W EDGES EXHAUST
REMOVABLE COUNTER
1085.7 (SEE NOTE 2) COOLING AIR
42.75
EXHAUST
COOLING AIR
ENTRANCE
687.5
27.07
63.5 711.2
2.50 REAR CABLE ENTRY 28.00
TO REMOVE
REAR FRONT SEE NOTE 1
1090.1 762.0
CUSTOMER POW ER SIDE
42.92 30.00 476.2
CONSOLE LEVELERS. SEE
CONNECTIONS CROSS-SECTION A-A.
18.75
108.7
711.2
149.4 4.28
28.00
5.88
CONSOLE
493.8 LEVELING
19.44 ADJUSTMENT
57.1
TOP 2.25
NOTES:
1. STABILIZER (PROVIDED) MUST BE USED W HEN CONSOLE DIMENSIONS A A
IS NOT SECURED TO FLOOR. 197.1 129.5
MILLIMETERS 12.7 DIA. (4) MOUNTING HOLES
2. REMOVABLE COUNTER HAS INDEPENDENT LEVELING BOTTOM CABLE 7.76 5.10 0.50 FOR FLOOR MOUNTING
INCHES
ADJUSTMENTS. REFER TO OIS HARDW ARE INSTRUCTION. ENTRY AREA
D3053785
BOTTOM SECTION A-A TP25446A
COOLING AIR
EXHAUST
30 TOTAL
TILT
558.8
22.00
COOLING AIR
ENTRANCE
495.3
19.50 90 ROTATION
OF MONITOR
609.6
24.00
NOTES:
1. UNIT IS SUPPLIED W ITH A 3-M LONG AC POW ER CORD TO PLUG
INTO TYPICAL U.S.A. 125 VAC, 15 A, 3-W IRE GROUNDED RECEPTACLES.
IEC320 RECEPTACLE ON REAR OF UNIT PROVIDES INTERNATIONAL
POW ER CORD OPTIONS. . .
INTRODUCTION
I-E96-500B G - 15
INSTALLATION DRAWINGS
EYEBOLT
REMOVABLE
1778.0
70.00
FRONT
762.0
30.00
96.9
762.0 96.9 3.82
30.00 3.82
472.5
18.60
777.9
30.63
15.9
0.62
76.2
IIOIC203/253 3.00 DIMENSIONS
MILLIMETERS
TOP INCHES
INTRODUCTION
G - 16 I-E96-500B
INSTALLATION DRAWINGS
762.0
30.00
762.0
30.00
762.0
30.00
406.4
16.00
IIOIC403/13
TOP
EYEBOLT
REMOVABLE
AIR
177.80 FILTER
70.00
CONDUIT AND
CABLE ENTRY 12.7 DIA. MOUNTING BOLTS
AREA 0.50 4 REQUIRED
INTRODUCTION
I-E96-500B G - 17
INSTALLATION DRAWINGS
609.6
24.00
63.5
2.50
REAR CABLE ENTRY
1347.9
53.07 REAR
0.312-18UNC-2A MOUNTING
FASTENERS (4) CUSTOMER
SUPPLIED
CONSOLE
LEVELING
ADJUSTMENT
711.2 57.1
28.00 2.25
FRONT
NOTES:
1. TOTAL WEIGHT IS APPROXIMATELY 114 KG (250 LB).
2. STABILIZERS (PROVIDED) MUST BE USED W HEN
CONSOLES ARE NOT SECURED TO FLOOR. 12.7 DIA. (4) MOUNTING HOLES
0.50 FOR FLOOR MOUNTING
3. APPLICABLE CODES AND STANDARDS MAY REQUIRE
ADDITIONAL CLEARANCE.
SECTION A-A FOR
4. THE 2 W ORK SURFACE ALIGNMENT PINS IN PLASTIC BAG
LOCATED INSIDE UNIT ARE REQUIRED ONLY W HEN CONSOLE FLOOR MOUNTING
IS USED IN AN ARRAY.
5. UNIT IS SUPPLIED WITH A 3-M LONG AC POW ER CORD TO
PLUG INTO TYPICAL U.S.A. 125 VAC, 15A, 3-W IRE GROUNDED
RECEPTACLES. IEC320 RECEPTACLE ON REAR OF UNIT DIMENSIONS
PROVIDES INTERNATIONAL POW ER CORD OPTIONS.
MILLIMETERS
6. UNIT POW ER SUPPLY IS 120/240 VAC, 47-63 HZ INCHES
AUTOSENSING. USER MUST CORRECTLY BRING POW ER TO
UNIT'S IEC320 RECEPTACLE OR SERIOUS EQUIPMENT
D3053789
DAMAGE MAY OCCUR. TP25450A
INTRODUCTION
G - 18 I-E96-500B
INSTALLATION DRAWINGS
RECOMMENDED
CLEARANCE FROM WALL
FOR SERVICING AND
AISLEWAY (SEE NOTE 3)
1090.1 762.0
42.92 30.00
.
711.2 90 ROTATION
.
28.00
OF MONITOR
TOP
1523.9
60.00
30
TOTAL REMOVE PLUG
TILT FOR CABLE
ROUTING
SEE
NOTE 3
433.7
17.08
SEE NOTE 3
738.3
29.07
687.5
27.07
TO REMOVE
SIDE
SEE NOTE 2 CABLE ACCESS
614.7
24.20
COVER PLATE
108.7
4.28
149.4
5.88
40.1
1.58
493.8
19.44
DIMENSIONS
A A
203.2 63.5 MILLIMETERS
SEE BOTTOM CABLE 8.00 2.50 INCHES
NOTE 4 ENTRY AREA
D3053789
BOTTOM TP25460A
INTRODUCTION
I-E96-500B G - 19
INSTALLATION DRAWINGS
VIBRATION DAMPENERS
SEE NOTE 2
65.0
2.56 VIBRATION
153.0 DAMPENER
6.02
SEE NOTE 7
FILLET W ELD
BY CUSTOMER
CONCRETE
FLOOR
CHANNEL 127.0
5.00 ELEVATION
419.0
16.50
REINFORCING BAR
553.0 64.0
21.77 2.52
DETAIL X
CURB MOUNTED
BOTTOM VIEW
SINGLE CABINET 65.0 VIBRATION
2.56
DAMPENER
SEE NOTE 7
CONCRETE
FILLET W ELD FLOOR
BY CUSTOMER ELEVATION
SEE
NOTE 4
CHANNEL 127.0
5.00 REINFORCING BAR
1899.0 DETAIL X
74.76 FLOOR MOUNTED
65.0
2.56
SEE NOTE 7
CONCRETE
FILLET W ELD FLOOR
BY CUSTOMER ELEVATION
CHANNEL 152.0
597.0 5.98 REINFORCING BAR
23.50
DETAIL X
25.0 660.0
TYP
0.98 25.98 DIMENSIONS
NO VIBRATION DAMPENER
FLOOR MOUNTED
FRONT VIEW MILLIMETERS
INCHES DL780399
SINGLE CABINET TP25454A
INTRODUCTION
G - 20 I-E96-500B
INSTALLATION DRAWINGS
991.0
39.02
CABINET 1 CABINET 2 CABINET 3 CABINET 4
2032.0
80.00
2070.0
81.50
1041.0
40.98
NOTES: TABLE 1
1. ADD 50 MM (1.97 IN.) FOR THE W IDTH OF TW O SIDE PANELS TO THE SUM OF THE
INDIVIDUAL "A" DIMENSIONS FOR AN OVERALL CABINET LENGTH. A MULTIPLE CABINET NO. OF CABINETS "A" DIMENSION
ARRANGEMENT W ILL BE SHIPPED IN ASSEMBLIES AS SHOW N IN TABLE 1, W HICH W ILL BE IN ONE ASSEMBLY (NOTE 1)
BOLTED TOGETHER ON-SITE TO PROVIDE A ___ CABINET ARRANGEMENT. 660
1
2. BOLTING OF INDIVIDUAL VIBRATION DAMPENERS TO CABINET AND ATTACHMENT TO 26
CHANNEL DONE BY CUSTOMER DURING INSTALLATION.
2 1321
3. MINIMUM CLEARANCE FOR MAINTENANCE: 52
FRONT: 1000 MM (39.37 IN.)
3 1981
REAR: 1000 MM (39.37 IN.) 78
4. DOOR HANDLES PROJECT 45 MM (1.77 IN.) FRONT AND REAR. 2642
4
5. THIS CABINET MUST BE INSTALLED PER STANDARD FLOOR MOUNTING AS SHOW N. 104
6. STANDARD ENVIRONMENTAL SPECS FOR THE SYSTEM ARE APPLICABLE (REF. CE96-500).
7. FRONT TRIM PIECE OF FRAME CAN BE REMOVED FOR EASE OF WELDING VIBRATION DIMENSIONS
DAMPENERS. MILLIMETERS
INCHES DL780399
TP25452A
INTRODUCTION
I-E96-500B G - 21
INSTALLATION DRAWINGS
762.00
30.000
32.00 TYP
1.260 TOP VIEW FOR DOOR K 89.00
3.504
330.0
12.99 VIBRATION DAMPENERS
SEE NOTE 2
660.0 660.0 660.0
25.98 25.98 25.98
273.0
10.75
826.0 632.0
32.52 24.88
546.0 114.0
65.0 21.50 4.49
2.56
REMOVABLE BOTTOM COVERS 590 168 MM (23.23 6.61 IN.)
DIMENSIONS CABLE ENTRY W ITH 559 152 MM (22.01 5.98 IN.) OPENINGS
MILLIMETERS
INCHES BOTTOM VIEW DL780399
TP25453A
INTRODUCTION
G - 22 I-E96-500B
INSTALLATION DRAWINGS
TOP VIEW
70.0
27.62
DIMENSIONS
740.0 MILLIMETERS 956.0
29.13 INCHES 37.64
SCREEN CENTER
112.0
1827.0 4.41
71.93
99.0
3.88
STABILIZER
SIDE VIEW
TP25373A .
INTRODUCTION
I-E96-500B G - 23