Professional Documents
Culture Documents
NCC-SES
Gas Insulated Substation
Grounding Analysis
Toolbox Edition
2012 Release
REVISION RECORD
August 1995 1 0
October 1997 1 1
October 1997 2 0
January 1999 7 0
January 2000 8 0
November 2002 10 0
June 2004 11 0
December 2006 13 0
January 2012 14 0
January 2012 14 1
May 2012 14 2
Page iv
SPECIAL NOTE
Due to the continuous evolution of the CDEGS software, you may find that some of the
screens obtained using the present version of the CDEGS package are slightly
different from those appearing in this manual. Furthermore, small differences in the
reported and plotted numerical values may exist due to continuous enhancements of
the computation algorithms.
Copyright 1995-2012 Safe Engineering Services & technologies ltd. All rights reserved.
This page is intentionally left blank
TABLE OF CONTENTS
Page
C
CHHA
APPTTE
ERR 11
INTRODUCTION ................................................................................................................. 1-1
1.1 OBJECTIVE ............................................................................................................................................... 1-1
1.2 COMPUTER MODELING TOOLS ............................................................................................................. 1-2
1.3 METHODOLOGY OF THE GROUNDING DESIGN .................................................................................. 1-2
1.4 ORGANIZATION OF THE MANUAL ......................................................................................................... 1-3
1.5 SOFTWARE NOTE .................................................................................................................................... 1-3
1.6 FILE NAMING CONVENTIONS ................................................................................................................ 1-3
1.7 WORKING DIRECTORY ........................................................................................................................... 1-5
1.8 INPUT AND OUTPUT FILES USED IN TUTORIAL .................................................................................. 1-5
C
CHHA
APPTTE
ERR 22
SOIL RESISTIVITY MEASUREMENTS & INTERPRETATION .......................................... 2-1
2.1 SOIL RESISTIVITY MEASUREMENTS .................................................................................................... 2-1
2.2 INTERPRETATION OF SOIL RESISTIVITY MEASUREMENTS ............................................................. 2-4
2.2.1 PREPARATION OF THE RESISTIVITY INPUT FILE IN CDEGS INPUT MODE ........................ 2-5
2.2.1.1 WINDOWS TOOLBOX INPUT MODE ........................................................................... 2-5
2.2.1.2 START UP PROCEDURES ........................................................................................... 2-5
2.2.1.3 DATA ENTRY ............................................................................................................... 2-10
2.2.1.4 HOW TO PRODUCE THE RESAP INPUT FILE .......................................................... 2-12
2.2.2 SUBMISSION OF THE RESAP RUN ......................................................................................... 2-12
2.2.3 EXTRACTION OF THE RESULTS FROM RESAP COMPUTATION RESULTS FILES............ 2-13
2.2.3.1 CDEGS - EXAMINE MODE OUTPUT PROCESSOR ................................................. 2-13
2.3 SOIL MODELS FROM WENNER MEASUREMENT .............................................................................. 2-14
2.3.1 FIRST RESAP RUN: INITIAL FOUR-LAYER SOIL MODEL IN TABLE 23 .............................. 2-14
2.3.1.1 PREPARATION OF RESAP INPUT FILE .................................................................... 2-14
2.3.1.2 SUBMISSION OF RESAP RUN AND EXTRACTION OF RESULTS USING
TOOLBOX .................................................................................................................... 2-15
2.3.2 SECOND RESAP RUN: FIVE-LAYER SOIL MODEL................................................................. 2-16
2.3.2.1 PREPARATION OF RESAP INPUT FILE .................................................................... 2-16
2.3.2.2 SUBMISSION OF RESAP RUN AND EXTRACTION OF RESULTS USING
TOOLBOX .................................................................................................................... 2-17
2.3.3 THIRD RESAP RUN: FINAL FOUR-LAYER SOIL MODEL IN TABLE 23 ............................... 2-18
2.3.3.1 PREPARATION OF RESAP INPUT FILE .................................................................... 2-18
2.3.3.2 SUBMISSION OF RESAP RUN AND EXTRACTION OF RESULTS USING
TOOLBOX .................................................................................................................... 2-18
2.3.4 FOURTH RESAP RUN: FINAL THREE-LAYER SOIL MODEL IN TABLE 23 ......................... 2-19
2.3.4.1 PREPARATION OF RESAP INPUT FILE .................................................................... 2-19
Page vii
TABLE OF CONTENTS (CONTD)
Page
Page viii
TABLE OF CONTENTS (CONTD)
Page
Page ix
This page is intentionally left blank
Chapter 1. Introduction
CHAPTER 1
INTRODUCTION
1.1 OBJECTIVE
This How To Engineering Guide shows you how to carry out a typical Gas Insulated Substation
(GIS) grounding design using the MultiFields, MultiFields+, MultiFieldsPro, or CDEGS software
packages. A step-by-step approach is used to illustrate how to use the Windows interfaces to input
your data, run the pertinent engineering modules and explore the computation results.
The grounding analysis problem is illustrated in Figure 1.1. A new 154 kV NCC-SES Gas Insulated
Substation is planned, and presently under construction. It will be interconnected to the rest of the
network via four transmission lines terminating at GENNW-SES Power Plant (Terminal GENNW-
SES), GENNE-SES Power Plant (Terminal GENNE-SES), GENSW-SES Substation (Terminal
GENSW-SES) and GENSE-SES Substation (Terminal GENSE-SES), respectively. The objective of
the analysis is to provide a new grid design for NCC-SES GIS. The final design is to limit touch and
step voltages to safe levels for personnel within the substation area, based on up-to-date system data,
appropriate measurement techniques and instrumentation, and state-of-the-art computer modeling
methods.
Terminal
GENNE-SES
Terminal
GENNW-SES
NCC-SES Gas
Insulated Substation
Terminal Terminal
GENSW-SES GENSE-SES
Figure 1.1 Illustration of the Grounding Analysis Problem
Page 1-1
Chapter 1. Introduction
Step 1 The first step of the study is aimed at determining an equivalent soil model to the real earth
structure using the RESAP soil resistivity interpretation engineering module. Several soil
type models can be selected by the designer as an approximation to the real soil (uniform,
two-layer, multilayer, etc.).
Step 2 Based on experience and on the substation ground bonding requirements, a preliminary
economical grounding system configuration is developed and analyzed using the MALT
grounding analysis engineering module based on the equivalent soil model developed in Step
1 (initial design).
Step 3 Using MALT, calculate the grounding resistance of terminal grids and the initial designof the
GIS substation grid with the equivalent soil models. Using HIFREQ, calculate the grounding
resistance of tower footing with the equivalent soil models. Based on these results, the
transmission line or distribution line configuration, conductor data and the fault current from
each terminal, build a HIFREQ system model to calculate the actual fault current to the GIS
substation from each line.
Step 4 With the equivalent soil model, and the fault current from each line to the GIS substation,
build a GIS substation model including the GIS structure and above ground bus bars, etc. The
calculated results are analyzed using one of the output processors and various computation
plots. Printout reports are examined to determine if all design requirements are met. In
particular, the safe touch and step voltage thresholds are determined based on the applicable
standards and regulations and compared to the computed values.
Step 5 If all design requirements are not met, or alternately if all these requirements are met by too
considerable a margin suggesting possible significant savings, design modifications to the
grounding system or to the transmission line network are made and the design analysis is
restarted at Step 2.
Page 1-2
Chapter 1. Introduction
Following the design methodology illustrated above, the manual is organized as follows:
Chapter 2 shows how to use the RESAP engineering module to analyze the soil resistivity data based
on the measurements taken at NCC-SES GIS (Step 1).
Chapter 3 presents the initial design of the grounding system. It describes the detailed computer
model of the NCC-SES GIS grounding grid and shows how to use the MALT engineering module to
determine the grounding grid resistance which will be used for computing the fault current
distribution in Chapter 4 (Step 2).
Chapter 4 describes how to use the HIFREQ module to determine the fault current distribution
during a phase-to-ground fault at NCC-SES GIS. The current injected into the NCC-SES GIS is
obtained (Step 3).
Chapter 5 describes how to build the HIFREQ model including the GIS bus bars using cables, the
connections between cables and phase wires and earthing grid, and defining energizations (Step 4).
Chapter 6 presents the ANSI/IEEE safety criteria applicable to the substation grounding. The fault
simulation results are presented in graphical and tabular form. The touch voltage, step voltage and
grid conductor longitudinal current are provided in detail. Step-by-step instructions about how to
obtain these results will be illustrated (Step 5).
Chapter 7 presents the design of the reinforced grounding system. It describes how to repeat the
computations from Chapter 3 to 6 to meet the safety criteria (Step 6).
In 5.2.2.3, the conclusions of the study are summarized. All the input files used in the study are
identified in Appendix A.
XY_JobID.Fnn
where XY is a two-letter abbreviation corresponding to the name of the program which created the
file or which will read the file as input. The JobID consists of string of characters and numbers that
is used to label all the files produced during a given CDEGS run. This helps identify the
Page 1-3
Chapter 1. Introduction
corresponding input, computation, results and plot files. The nn are two digits used in the extension
to indicate the type of file.
The abbreviations used for the various CDEGS modules are as follows:
* The SICL module is used internally by the Input Toolbox data entry interface. The CSIRPS
module is used internally by the Output Toolbox and GRServer graphics and report
generating interface.
The following four types of files are often used and discussed when a user requests technical support
for the software:
.F05 Command input file (for engineering applications programs). This is a text file that can
be opened by any text editor (WordPad or Notepad) and can be modified manually by
experienced users.
.F09 Computation results file (for engineering applications programs). This is a text file that
can be opened by any text editor (WordPad or Notepad).
.F21 Computation database file (for engineering applications programs). This is a binary file
that can only be loaded by the CDEGS software for reports and graphics display.
.F33 Computation database file (for engineering applications programs MALZ and HIFREQ
only). This is a binary file that stores the current distribution to recover.
For further details on CDEGS file naming conventions and JobID, please consult CDEGS Help
under Help | Contents | File Naming Conventions.
Page 1-4
Chapter 1. Introduction
You may prefer to use a different working directory. Either way, you should take note of the full
path of your working directory before running CDEGS, as you will need this information to follow
this tutorial.
Page 1-5
Chapter 1. Introduction
For those who prefer to load the input files into the software and simply follow the tutorial, you can
copy all of the files from the install\Howto\CDEGS\GisGrnd directory to your working directory.
After the tutorial has been completed, you may wish to explore the other How ToEngineering
Manuals which are available as PDF files on the SES Software DVD in the folder \PDF\Howto.
If the files required for this tutorial are missing or have been modified, you will need to manually
copy the originals from the SES Software DVD. Both original input and output files can be found in
the following directories on the SES Software DVD:
Note that the files found in both the Inputs and the Outputs directories should be copied directly
into the working directory, not into subdirectories of the working directory.
Page 1-6
Chapter 2. Soil Resistivity Measurements & Interpretation
CHAPTER 2
SOIL RESISTIVITY MEASUREMENTS &
INTERPRETATION
2.1 SOIL RESISTIVITY MEASUREMENTS
Soil resistivity measurements at the substation site were carried out using the Wenner
andSchlumberger techniques. Figure 2.1 shows the traverses along which the measurements were
taken. Table 21 gives the measured apparent resistance values along Traverse #1 using the Wenner
method (i.e., the distances between adjacent electrodes are equal). Three different equipments
(STING R1, SAS 300C and YEW-3244) have been used to record the data. Table 22 lists the
measured apparent resistance values along Traverse #1 using the Schlumberger method.
Traverse #3
Traverse #2
Page 2-1
Chapter 2. Soil Resistivity Measurements & Interpretation
Spacing
Measure- Between Depth of Probes Apparent Resistance (V/I)
ments Probes (ft) ()
(ft)
Cpin Ppin STING R1 SAS 300C YEW-3244
R1 1.64 0.492 0.492 554.600 557.000 -----
R2 3.28 0.492 0.492 385.400 386.000 150.000
R3 6.56 0.492 0.492 178.300 179.600 174.000
R4 9.84 0.492 0.492 105.300 106.300 102.500
R5 13.12 0.492 0.492 74.460 75.100 70.000
R6 16.4 0.984 0.984 59.500 59.700 56.000
R7 19.68 0.984 0.984 48.170 48.400 29.000
R8 22.96 0.984 0.984 42.080 42.100 28.000
R9 32.8 1.312 1.312 28.400 27.900 27.500
R10 49.2 1.312 1.312 19.020 18.820 18.500
R11 65.6 1.312 1.312 14.480 14.930 13.900
R12 98.4 1.64 1.64 10.330 10.370 10.000
R13 164 1.64 1.64 6.880 6.610 6.700
R14 229.6 1.64 1.64 5.905 6.090 5.600
R15 328 1.64 1.64 4.523 4.710 4.500
Table 21 Measured Apparent Resistances of Substation Site Using the Wenner Method
Page 2-2
Chapter 2. Soil Resistivity Measurements & Interpretation
Spacing Between
Measure- Depth of Probes Apparent Resistance (V/I)
Probes
ments (ft) ()
(ft)
P1-P2 C1-P1 Cpin Ppin STING R1 SAS 300C YEW-3244
R1 6.56 6.56 0.492 0.492 182.600 172.600 166.000
R2 6.56 11.48 0.492 0.492 64.890 62.000 59.000
R3 6.56 16.4 0.492 0.492 31.870 31.800 31.000
R4 6.56 21.32 0.492 0.492 18.870 18.890 18.450
R5 6.56 26.24 0.492 0.492 11.980 11.940 11.800
R6 6.56 36.08 0.492 0.492 6.777 6.430 6.550
R7 6.56 45.92 0.492 0.492 4.228 4.000 4.100
R8 6.56 55.76 0.492 0.492 3.091 3.840 2.940
R9 6.56 65.6 0.984 0.492 2.417 2.490 2.260
R10 6.56 75.44 0.984 0.492 1.973 1.920 1.890
R11 6.56 85.28 0.984 0.492 1.539 2.210 1.270
R12 6.56 95.12 0.984 0.492 1.287 1.713 1.120
R13 6.56 114.8 0.984 0.492 1.472 1.080 0.960
R14 32.8 101.68 0.984 0.492 6.984 5.510 5.400
R15 6.56 134.48 0.984 0.492 1.335 0.929 0.695
R16 32.8 121.36 0.984 0.492 4.720 4.290 4.000
R17 32.8 141.04 0.984 0.492 3.949 3.600 3.450
R18 32.8 160.72 0.984 0.492 3.178 2.850 2.865
R19 32.8 180.4 1.64 0.492 2.400 2.260 2.355
R20 32.8 213.2 1.64 0.492 1.875 1.868 1.745
R21 32.8 246 1.64 0.492 1.491 1.543 1.325
R22 32.8 278.8 1.64 0.492 1.272 1.213 1.100
R23 32.8 311.6 1.64 0.492 1.016 1.100 0.900
R24 32.8 344.4 1.64 0.492 0.8295 1.041 0.770
R25 32.8 377.2 1.64 0.492 0.6470 0.988 0.580
R26 32.8 410 1.64 0.492 0.6392 0.723 0.595
R27 32.8 475.6 1.64 0.492 0.5419 0.581 0.545
Table 22 Measured Apparent Resistances of Substation Site Using the Schlumberger Method
Page 2-3
Chapter 2. Soil Resistivity Measurements & Interpretation
The RMS Error in Column 5 of Table 23 and Table 24 (computed by RESAP as described in
this section) provides a quantitative indication of the agreement between the measurements and the
proposed soil models. Note that the tables show several equivalent soil structures for each
measurement site, namely multilayer structures and a two-layer structure. Although the fit of
Page 2-4
Chapter 2. Soil Resistivity Measurements & Interpretation
computed to measured soil resistivities is considerably better when multilayered soil models are
used, the computed grid resistances corresponding to the two-layer and multilayered soil models are
similar.
The three-layer soil model in Table 23 will be used for the grid design. There are two reasons why
we choose this soil model. First of all, this soil model is more conservative (higher resistivity for the
top layer where the grid will be buried) compared to the two-layer and three-layer soil models from
the Schlumberger method. Secondly, since the grid resistances are about the same for the three-layer
and four-layer soil models (see Table 23), the use of the three-layer soil model will reduce the
computation time in the MALT module.
The following describes the steps to achieve the soil models in Table 23. We choose the Wenner
method as an example to illustrate how to use RESAP to obtain the soil models in Table 23.
The following section describes the Windows compatible input session, which, once completed,
generates the Command mode compatible input file, (.INP and .F05 file extension) described in
Printout A.1 both of which can be reloaded during subsequent sessions.
Click here
Page 2-5
Chapter 2. Soil Resistivity Measurements & Interpretation
In the SES Software <Version> group folder, where <Version> is the version number of the
software, you should see the icons representing Autogrid Pro, AutoGroundDesign, CDEGS,
Right-of-Way, SESEnviroPlus, SESShield-3D and SESTLC software packages, as well as four
folders. The Documentation folder contains help documents for various utilities and software
packages. The Program Folders provides shortcuts to programs, installation and projects folders.
The System folder allows you to conveniently set up security keys. Various utilities can be found in
the Tools folder. The main function of each software package and utility is described hereafter.
SOFTWARE PACKAGES
Autogrid Pro provides a simple, integrated environment for carrying out detailed grounding
studies. This package combines the computational powers of the engineering programs RESAP,
MALT and FCDIST with a simple, largely automated interface.
AutoGroundDesign offers powerful and intelligent functions that help electrical engineers
design safe grounding installations quickly and efficiently. The time devoted to design a safe and
also cost-effective grounding grid is minimized by the use of automation techniques and
appropriate databases. This module can help reduce considerably the time needed to complete a
grounding design.
SESShield-3D is a powerful graphical program for the design and analysis of protective
measures against lightning for substations and electrical networks. Its 3D graphical environment
can be used to model accurately systems with complex geometries.
SESTLC is a simplified analysis tool useful to quickly estimate the inductive and conductive
electromagnetic interference levels on metallic utility paths such as pipelines and railways
located close to electric lines (and not necessary parallel to them), as well as the magnetic and
Page 2-6
Chapter 2. Soil Resistivity Measurements & Interpretation
electric fields of arbitrary configurations of parallel transmission and distribution lines. It can
also compute line parameters.
CDEGS is a powerful set of integrated engineering software tools designed to accurately analyze
problems involving grounding, electromagnetic fields, electromagnetic interference including
AC/DC interference mitigation studies and various aspects of cathodic protection and anode bed
analysis with a global perspective, starting literally from the ground up. It consists of eight
engineering modules: RESAP, MALT, MALZ, SPLITS, TRALIN, HIFREQ, FCDIST and
FFTSES. This is the primary interface used to enter data, run computations, and examine results
for all software packages other than Right-of-Way, Autogrid Pro, AutoGroundDesign, SESTLC,
SESShield-3D and SESEnviroPlus. This interface also provides access to the utilities listed
below.
TOOLS
AutoTransient automates the process required to carry out a transient analysis with the HIFREQ
and FFTSES modules
CETU simplifies the transfer of Right-of-Way and SPLITS output data to MALZ. A typical
application is the calculation of conductive interference levels in an AC interference study.
FFT21Data extracts data directly from FFTSES output database files (File21) in a spreadsheet-
compatible format or in a format recognized by the SESPLOT utility.
GraRep is a program that displays and prints graphics or text files. For more information on
GraRep see Chapter 6 of the Utilities Manual or invoke the Windows Help item from the menu
bar.
GRServer is an advanced output processor which displays, plots, prints, and modifies
configuration and computation results obtained during previous and current CDEGS sessions.
GRSplits plots the circuit models entered in SPLITS or FCDIST input files. This program
greatly simplifies the task of manipulating, visualizing and checking the components of a
SPLITS or FCDIST circuit.
GRSplits-3D is a powerful interactive 3D graphical environment that allows you to view and
edit the circuit data contained in SPLITS input files and to simultaneously visualize the
computation results.
ROWCAD is a graphical user interface for the visualization and specification of the geometrical
data of Right-of-Way projects. Its 3D graphical environment can be used to visualize, specify
and edit the path data of Right-of-Way, and to define the electrical properties of those paths.
SESAmpacity computes the ampacity, the temperature rise or the minimum size of a bare buried
conductor during a fault. It also computes the temperature of bare overhead conductors for a
given current or the current corresponding to a given temperature, accounting for environmental
conditions.
Page 2-7
Chapter 2. Soil Resistivity Measurements & Interpretation
SESBat is a utility that allows you to submit several CDEGS engineering program runs at once.
The programs can be run with different JobIDs and from different Working Directories.
SESCad is a CAD program which allows you to create, modify, and view complex grounding
networks and aboveground metallic structures, in these dimensions. It is a graphical utility for the
development of conductor networks in MALT, MALZ and HIFREQ.
SESConductorDatabase gives access to the SES Conductor Database. It allows you to view the
electrical properties of conductors in the database, and to add new conductors to the database or
modify their properties.
SESGSE rapidly computes the ground resistances of simple grounding systems, such as ground
rods, horizontal wires, plates, rings, etc, in uniform soils. SESGSE also estimates the required
size of such grounding systems to achieve a given ground resistance.
SESPlot provides simple plots from data read from a text file.
SESScript is a simple programming language that automatically generates input files for
parametric analyses.
SESShield provides optimum solutions for the protection of transmission lines and substations
against direct lightning strikes and optimizes the location and configuration of shield wires and
masts in order to prevent the exposure of energized conductors, busses and equipment. It can also
perform risk assessment calculations associated with lightning strikes on various structures.
SESSystemViewer is a powerful 3D graphics rendition software that allows you to visualize the
complete system including the entire network and surrounding soil structure. Furthermore,
computation results are displayed right on the system components.
SoilModelManager is a software tool that automates the selection of soil model structures that
apply during various seasons.
SoilTransfer utility allows you to transfer the soil model found in several SES files into several
MALT, MALZ or HIFREQ input (F05) files.
TransposIT is a tool for the analysis of line transpositions on coupled electric power line
circuits. To ensure that voltage unbalance is kept within predefined limits, it allows the user to
determine the optimal number of power line transpositions and their required locations.
WMFPrint displays and prints WMF files (Windows Metafiles) generated by CDEGS or any
other software.
Page 2-8
Chapter 2. Soil Resistivity Measurements & Interpretation
We will be using mostly the CDEGS icon to carry out most of the input/output tasks. We will refer
to the other utility modules when appropriate. In the SES Software group folder, double-click the
CDEGS icon to start the CDEGS program interface (if not already started). You will be prompted
for a Current Job ID. Any character string could be entered here, although NCC1T is
recommended. Enter the complete path of your working directory in the Working Directory box.
Select Specify in the Session Mode list and click the RESAP button located in the toolbar. The
CDEGS-Specify-RESAP screen will appear (without the text) and you are now ready to input data.
In the following section, it will be assumed that the reader is entering the data as indicated in the
instructions. Note that it is advisable to save your work regularly by clicking on the Save button in
the toolbar and following the instructions in the dialog box. The data entered up to that point will be
saved in two files called RS_NCC1T.F05 and RS_NCC1T.INP. Each file can be retrieved at any
time by clicking on the Import / Load button and following the instructions in the dialog box.
The same considerations apply if a data entry session has to be interrupted. (Click in the toolbar
to go back to the Start-Up window after saving your data.)
If you intend to enter the data manually, proceed directly to Section 2.2.1.3. If you do not wish to do
so, you can import all the data by proceeding as follows.
Importing DATA
Click the Import / Load button. Change the File Name in the dialog box to RS_07T.F05 then
click on the Load button in the dialog box. Click OK in the resulting Message Box. The data
described in the next section will be loaded and you will not have to enter it.
Page 2-9
Chapter 2. Soil Resistivity Measurements & Interpretation
The data entry field in the Module Description tab under the Case Description block allows you to
type comment lines that are used to describe the case to be analyzed in the RESAP module. They are
echoed in the RESAP output. If you place your mouse cursor on any comment line and click on it
(i.e., focus on the comment line) then hitting the F1 (Help Key) will bring a help text describing the
Case Description lines. A Run-ID NCC1T is entered in the Run-Identification box and the
British System of Units is chosen. The Run-ID is useful in identifying all the plots which will be
made later in Section 2.2.3. Focusing on the Run-Identification field and then hitting the F1 key
will bring a help text related to the focused field. This applies to all CDEGS Input and Output text
fields.
Page 2-10
Chapter 2. Soil Resistivity Measurements & Interpretation
required fields, otherwise the program will make its own assumptions. Click OK to return to the
RESAP main screen.
The Computations screen allows you to Lock and/or Unlock the resistivity and depth of each layer
and define the extent of the Computed Resistivity Traverse. It also allows you to choose or
generate different filters. By default, RESAP chooses Standard Filter, which is sufficient for most
practical cases. The High Precision Filter is sometimes needed when extreme soil conditions (very
large soil resistivity contrast ratio) are encountered; it increases the computation time considerably.
Generating new filters is seldom needed unless RESAP encounters a missing or corrupted filter
database file. The Computed Resistivity Traverse option specifies a traverse along which apparent
earth resistivities are to be computed based on the equivalent earth model determined by RESAP.
Two values are entered:
Please note that the calculations start with a very short electrode spacing. The ratio of the outer-inner
electrode spacing to the inner-inner electrode spacing will be based on the average ratio as
determined from the field measurement data.
Step Size: This parameter specifies the minimum change of RMS error below which the
optimization process will stop. The program will conduct a convergence test by computing the
average RMS error change over the past 25 iterations. The minimization will stop if the averaged
Page 2-11
Chapter 2. Soil Resistivity Measurements & Interpretation
RMS error change is less than the value specified by Step Size command. Decreasing the Step
Size usually improves the fit of the computed soil model to the measured data, but increases the
computation time. The default value of Step Size is 0.0001 (0.01%).
RESAP will terminate the iterative minimization process whenever the desired Accuracy is reached,
or the minimization Step Size is smaller than the threshold value, or the total number of Iterations is
reached.
If you are a licensee of the CDEGS software you are now able to proceed to Section 2.2.2. Users of
the demo software are not able to process the input file, but are able to peruse all output files that are
already available. Therefore read Section 2.2.2 for reference only. Any attempt to start the
engineering modules will result in a message stating that the Engineering module is not active.
Click the Compute/Submit button to submit and run the model. This does two things:
1. It saves two files under the names RS_NCC1T.F05 and RS_NCC1T.INP. These two files can
be reread from the Toolbox using the Import/Load button. Furthermore, the *.F05 and
*.INP files are ASCII files you can edit and view at any time. (The *.F05 file is typically
identical to the *.INP file.)
The RESAP program will start and will carry out all requested
computations. The run should take very little time. At completion,
the program will produce three important files: an OUTPUT file
(RS_NCC1T.F09), a DATABASE file (RS_NCC1T.F21) and the
SHARE file (SF_NCC1T.F11).
The next section examines the computation results using the Examine (Output) Mode of CDEGS.
Depending on your settings, the program may automatically start the output session the moment the
engineering program terminates. This is controlled by the option View the output session after
Page 2-12
Chapter 2. Soil Resistivity Measurements & Interpretation
engineering computations in the System Settings window (accessible from the Settings | System
menu item).
The DATABASE file is normally used by CDEGS (Examine Mode) and the SES Interactive
Report & Plot Software processors (such as GraRep) to display the computation results. In the
following, we will give an example demonstrating how to use the Examine mode of the CDEGS
program (Section 2.2.3.1) to produce the corresponding graphs.
Figure 2.2 Result of Trial RESAP Run Using All of Data Points: AUTOMATIC-LAYER Soil
Model.
Page 2-13
Chapter 2. Soil Resistivity Measurements & Interpretation
You can also send the plot and report to a file for
processing.
By examining the shape of the curve, i.e., by following the number of inflection points, we realize
that a four-layer soil model should provide an appropriate fit for all data points. A three-layer soil
model could also provide an appropriate fit provided that the first data point is removed. A two-layer
soil model can be obtained by simply forcing the number of the user-defined layers to 2. The
following describes how to obtain the three soil models in Table 23.
Page 2-14
Chapter 2. Soil Resistivity Measurements & Interpretation
simply modifying the soil type in RS_NCC1T.F05. It can also be created by loading a pre-prepared
file RS_07A.F05, as described in Section 2.2.1.2. The following describes how to create
RS_NCC1A.F05 using RS_NCC1T.F05.
Click the Import/Load button. Change the File Name in the dialog box to RS_NCC1T.F05,
then click on the Load button in the dialog box. Click OK in the resulting Message Box. You are
ready to modify RS_NCC1T.F05 by proceeding as follows.
First, change the comments and Run-Identification according to the following screen.
Click the Soil Type button. Click the User-Defined option button under Number of Soil Layers
and enter 4 in the adjoining box.
You have completed the modification of the data and can now return to the RESAP main screen by
clicking OK.
Click the Compute/Submit button to exit the RESAP screen and start the RESAP engineering
module. A RESAP input file RS_NCC1A.F05 is generated. Printout A.2 shows this file.
Page 2-15
Chapter 2. Soil Resistivity Measurements & Interpretation
After completion of the RESAP run, the results can be extracted by repeating the instructions
described in Section 2.2.3. The following shows the best fit of soil resistivity data using the four-
layer soil model.
As shown in Figure 2.3 below, the computed curve now fits the measured data well. However, the fit
to the first data point can still be improved. The RMS error is now reduced from 6.4% (see Figure
2.2) to 3.4%.
Figure 2.3 Computed Versus Measured Resistivities for Wenner Method: Four-Layer Soil
Model.
Options (a) and (b) can also be combined into an effective two-step procedure which will work most
of the time. The procedure is described as follows:
Page 2-16
Chapter 2. Soil Resistivity Measurements & Interpretation
Step 1: Obtain the best-fit layer parameters by simply increasing the number of layers (Option (a))
Step 2: Based on the best-fit layer parameters and the correct number of layers, obtain good initial
guesses for the layer parameters. These values are then used in Option (b).
Steps 1 and 2 are applied in this section and the next section to obtain the best fit four-layer soil
model.
In this section, a five-layer soil model is used. NCC1B is chosen as the Job ID. The steps to generate
RS_NCC1B.F05 files from RS_NCC1A.F05 are very similar to those used to create the
RS_NCC1A.F05 file from RS_NCC1T.F05. These steps are described in the preceding section.
RS_NCC1B.F05 can also be obtained by loading a pre-prepared input file RS_07B.F05. Printout A.3
shows the input file RS_NCC1B.F05.
Start the RESAP engineering module by clicking the Compute/Submit button in the CDEGS-
Specify-RESAP screen. After completion of the RESAP run, the results can be extracted by
repeating the instructions described in Section 2.2.3. Figure 2.4 shows that the computed curve now
fits the measured data very well. The RMS error decreased further from 3.4 % to 2.5%.
Figure 2.4 Computed Versus Measured Resistivities for Wenner Method: Five-Layer Soil
Model.
Page 2-17
Chapter 2. Soil Resistivity Measurements & Interpretation
Start the RESAP engineering module by clicking the Compute/Submit button in the CDEGS-
Specify-RESAP screen. After completion of the RESAP run, the results can be extracted by
repeating the instructions described in Section 2.2.3. Figure 2.5 indicates that the computed curve
still fits the measured data very well. The RMS error is increased slightly from 2.5 % to 2.6%.
Figure 2.5 Computed Versus Measured Resistivities for Wenner Method: Final Four-Layer Soil
Model.
Page 2-18
Chapter 2. Soil Resistivity Measurements & Interpretation
By examining the resistivity measurement curve, we expect that a three-layer soil model will fit the
measurement curve very well provided that the first data point is removed. This assumption is
justified since the measurement was taken on a rainy day. By following the steps described in
Section 2.2.1.2, we can create RS_NCCR1.F05 from RS_NCC1A.F05. RS_NCCR1.F05 can also be
obtained by loading a pre-prepared input file RS_07D.F05. Note that the lines of data corresponding
to 1.64 ft (Measurement R1 and R16) are deleted in the Measurements module.
Start the RESAP engineering module by clicking the Compute/Submit button in the CDEGS-
Specify-RESAP screen. After completion of the RESAP run, the results can be extracted by
repeating the instruction described in Section 2.2.3. Figure 2.6 compares the measured resistivities
with those computed from a three-layer soil structure. The REPORT file screen lists the attributes of
each layer.
Figure 2.6 Computed Versus Measured Resistivities for Wenner Method: Final Three-Layer Soil
Model (the first data points are removed).
Page 2-19
Chapter 2. Soil Resistivity Measurements & Interpretation
By following the similar steps described in Section 2.2.1.2, we can create RS_NCC1E.F05 from
RS_NCCR1.F05. RS_NCC1E.F05 can also be obtained by loading a pre-prepared input file
RS_07E.F05. NCC1E is chosen as the JobID.
Start the RESAP engineering module by clicking the Compute/Submit button in the CDEGS-
Specify-RESAP screen. After completion of the RESAP run, the results can be extracted by
repeating the instruction described in Section 2.2.3. Figure 2.7 compares the measured resistivities
with those computed from a two-layer soil structure. The REPORT file screen lists the attributes of
each layer.
Figure 2.7 Computed Versus Measured Resistivities for Wenner Method: Final Two-Layer Soil
Model (the first data points are removed).
Page 2-20
Chapter 2. Soil Resistivity Measurements & Interpretation
data points are discarded. For this part of the tutorial, we will use the SAS 300C data (R1 to R27)
from Table 22.
The results are shown in Figure 2.8 and Figure 2.9. The input files for Figure 2.8 and Figure 2.9 are
RS_NCC2T.F05 and RS_NCC2A.F05, respectively. These input files can be created by loading two
pre-prepared input files RS_072T.F05 and RS_072A.F05. Printout A.5 shows the input file
RS_NCCR1.F05 and Printout A.6 shows the input file RS_NCC1E.F05.
Figure 2.8 Computed vs. Measured Resistivities for Schlumberger Method: Four-Layer Soil
Model.
Figure 2.9 Computed Versus Measured Resistivities for Schlumberger Method: Three-Layer Soil
Model.
Page 2-21
This page is intentionally left blank
Chapter 3. Initial Design of Grounding System and Computation of Grid Impedance
CHAPTER 3
INITIAL DESIGN OF GROUNDING SYSTEM
AND COMPUTATION OF GRID RESISTANCE
In this chapter, the detailed computer model of the initial design of the NCC-SES grounding system
will be presented. We will show how to use the MALT engineering module to determine the
grounding grid resistance that will be used for computing fault current distribution in the next
chapter.
The rebar in the concrete floor of GIS building has dimensions of 40.4 ft by 204.7 ft with conductor
radius of 0.125 buried at a depth of 0.5 ft. The rebars are connected to the main ground grid at 14
locations, every 15 ft.
The initial ground resistance of the NCC-SES GIS substation is 13.47 as will be determined in this
chapter with the soil resistivity calculated from RS_NCCR1.F05.
Page 3-1
Chapter 3. Initial Design of Grounding System and Computation of Grid Impedance
43.5 ft
255 ft
(-136, -135) ft
(a) The Grounding System at the NCC-SES GIS Substation without Rebar
Rebar
43.5 ft
40.4 ft
255 ft
(b) The Grounding System at the NCC-SES GIS Substation with Rebar
Figure 3.1 Initial Design of the Grounding System at the NCC-SES GIS Substation
Page 3-2
Chapter 3. Initial Design of Grounding System and Computation of Grid Impedance
Click here
This step is identical to the one already described in Section 2.2.1.2. In the SES Software group
folder, double-click the CDEGS icon to start the CDEGS program interface (if not already started).
You will be prompted for a Working Directory and a
"Current Job ID". Make sure that the proposed working
directory is the same as the one used in the preceding
chapter. In the Current Job ID box enter NCCR1 (while
any character string could be entered here, note that if
you enter a Job ID other than NCCR1, the data transfer Click here to
between RESAP and MALT will not be available). start SESCAD
Page 3-3
Chapter 3. Initial Design of Grounding System and Computation of Grid Impedance
In the following section, it will be assumed that the reader is entering the data as indicated in the
instructions. Note that it is advisable to save your work regularly by clicking on the Save button in
the toolbar and following the instructions in the dialog box. The data entered up to that point will be
saved in a file called MT_NCCR1.F05. This file can be retrieved at any time by selecting the File |
Open Document menu item in SESCAD and following the instructions in the dialog box. The same
considerations apply if a data entry session has to be interrupted (close all active windows to exit the
program after saving your data).
If you intend to enter the data manually, proceed directly to Section 3.2.2. If you do not wish to do
so, you can import all the data by proceeding as follows.
Importing DATA
First be sure to close the MT_NCCR1.F05 which was just created. Select the Open
Documentunder the File menu. Browse to the file MT_07R1.F05 in the working directory
\CDEGS Howto\Gisgrnd, then click on the OK button to open the file. Click on Save Document
As and select the file MT_NCCR1.F05 in working directory to overwrite this file. The data
described in the next section will be loaded and you will not have to enter it.
Page 3-4
Chapter 3. Initial Design of Grounding System and Computation of Grid Impedance
British Systems of Units are chosen. The Run-ID is useful in identifying all the plots which
will be made later in Section 3.4. Click the OK button to save and exit this screen.
Page 3-5
Chapter 3. Initial Design of Grounding System and Computation of Grid Impedance
Click here to
change to XY,
XZ, YZ, 3D or
Plan Views
a. First create a loop along the GIS building boundary at the depth of 1 ft. The size of the
loop is 43.5 ft 204.7 ft. The loop is created by selecting the Insert | Conductor Grid
menu item. The following provides the input data.
Page 3-6
Chapter 3. Initial Design of Grounding System and Computation of Grid Impedance
b. Select all conductors by selecting the Edit | Select All menu item. Select the Tools |
Break Conductors at Every Conductor Intersection. This will break all conductors at
intersections so that we can move only the GIS grounding conductors to the depth of 2 ft
(see the next step).
c. Under the Edit menu, uncheck the Use Group Information in order to access all
conductors without ungrouping them.
d. Select only the grounding conductors for the GIS building. Right-click and select the
Characteristics. Set the radius of all these conductors to 0.4065.
Page 3-7
Chapter 3. Initial Design of Grounding System and Computation of Grid Impedance
a. Still with the GIS grounding conductors selected, change the view to XZ, 3D view.
b. Under the Tools menu, select the Shift Object function. Enter 1 ft under the Quick
Distance. Click on the arrow downwards. This will move the GIS conductors by 1 ft, to
the depth of 2 ft.
Change view to
XZ, 3D
Click here to
move
conductors
downwards
a. Select the Edit | User Group Information to turn on the group information. This
enables you to access the grouped conductors again.
b. Change the view back to XY, 3D view and click on the loop conductor for the GIS
building (the 4 perimeter conductors).
c. Select the Tools | Create Rods menu item. In the Create Rods window, select only
Create rods at origin and end of conductors. Enter -1 ft under the Rod Height
(Feet). The -1 ft instructs the program to create rods in the opposite direction, i.e.,
upwards, to connect the GIS grid to the main grid. See Figure 3.2 and Figure 3.3.
d. With the loop still selected, delete the loop conductor for the GIS building.
e. Click on the connection conductors just created. Right-click and select the
Characteristics to set the radius to 0.264.
f. Select the Edit | User Group Information to turn off the group information, delete the
four connection conductors at the corners of the GIS building. See Figure 3.4.
g. Select the Edit | User Group Information to turn on the group information and select
the grid.
Page 3-8
Chapter 3. Initial Design of Grounding System and Computation of Grid Impedance
Figure 3.2 Create Rods (Connections) to Connect Two Grids: Select GIS Loop Conductor
Figure 3.3 Create Rods (Connections) to Connect Two Grids: Create Rods
Page 3-9
Chapter 3. Initial Design of Grounding System and Computation of Grid Impedance
a. We will now create 10 ft ground rods which are connected to the GIS building
conductors. Make sure you are still in the XY view and also select the Advanced | Set As
Active Object (or press the Function Key F9) to access conductors inside grouped
conductors. From the Power Tool, select Create Rods. Keep the default rod length to
10 ft. Click on the Point at X = -16, Y = 105. This creates the first ground rod. The
second rod (X = -1, Y = 90) and the third rod (X = 14, Y = 105) are created the same
way.
b. Right-click on those three rods and set the radius in the Characteristic window to 0.375.
The rest of rods are created by using the Tools | Shift Objects. The spacing between rods
is 30 ft. First select the three rods just created and select the Edit | Group menu item to
group them. Select the grouped rods and shift them by using the Shift Objects. The
figure below shows their final locations.
Page 3-10
Chapter 3. Initial Design of Grounding System and Computation of Grid Impedance
Step 7. Create Rebar for GIS Building: The rebars are created similarly by selecting the
Insert | Conductor Grid menu item. The following are the input screens. The radius of the
rebar is 0.125.
Page 3-11
Chapter 3. Initial Design of Grounding System and Computation of Grid Impedance
Step 8. Connect GIS Rebar to Main Grid: The last step is to connect the GIS rebar to the
main grounding grid. Make sure that you are in the XY, 3D view.
a. We will first create a connection by selecting the Insert | Single Conductor menu item.
The following are the input screens. The radius of the connection conductor is 0.4065.
b. We will then shift the connection conductor along the Y direction, downwards, by 15 ft
and duplicate it 13 times.
Page 3-12
Chapter 3. Initial Design of Grounding System and Computation of Grid Impedance
At this point, you have completed the preparation of the data. The energization of the grid is kept at
1000 A (a default setting) since the grounding resistance is independent of the injection current.
Under the File menu, select Save Document and then click Close Document to close this file in
SESCAD. The *.F05 is an ASCII file you can edit and view at any time.
The file MT_NCCR1.F05 is ready to be submitted to the MALT engineering module in the next
section.
If you are a licensee of the CDEGS software you will now be able to proceed to Section 3.3. Users
of the demo software are not able to process the input file, but are able to peruse all output files,
which are already available. Therefore read Section 3.3 for reference only. Any attempt to start the
engineering modules will result in a message stating that the Engineering module is not active.
Page 3-13
Chapter 3. Initial Design of Grounding System and Computation of Grid Impedance
Once the run is complete, a window will pop up to inform you that a log file has been generated.
Click the OK button to close the message window. SESBatch allows you to conveniently access
some of the important files that it generates. For example, from the Tools | View Run Log File
menu item you can view the log file generated during the computations. From the Tools | View
Output File menu item you can view the output file, which may contain ERROR or WARNING
messages requiring your attention. Finally, you can launch Output Toolbox directly from the Tools |
View Results with Output Toolbox menu item.
The MALT program will start and carry out all requested computations. Upon completion, the
program will produce three important files: an OUTPUT file (MT_NCCR1.F09), a DATABASE file
(MT_ NCCR1.F21) and the SHARE file (SF_ NCCR1.F11).
The OUTPUT file is an ASCII file, while the DATABASE file is a binary file. Any ERROR or
WARNING messages generated during the MALT run will appear in the OUTPUT file. The
SHARE file SF_NCCR1.F11 now contains the soil model and the grid resistance computed by
MALT. You can view the OUTPUT file by clicking the File Viewer ( ) button in the Output
section of the toolbar. (If prompted, select the Low Frequency Grounding option, and click OK.)
Page 3-14
Chapter 3. Initial Design of Grounding System and Computation of Grid Impedance
In the CDEGS main screen, select Examine from the Session Mode drop-down list. Click on the
MALT button to load this screen. You are now ready to make Computations and Configuration
plots.
In the CDEGS-Examine-MALT screen, click on the Report button and this generates a report. The
Resistance of Electrode is 13.47 . This value will be used in HIFREQ model to calculate the fault
current distribution in the next chapter.
Page 3-15
This page is intentionally left blank
Chapter 4. Fault Current Distribution Analysis Using HIFREQ
CHAPTER 4
FAULT CURRENT DISTRIBUTION ANALYSIS
USING HIFREQ
4.1 INTRODUCTION
The touch and step voltages associated with the grounding network are directly proportional to the
magnitude of the fault current component discharged directly into the soil by the grounding network.
It is therefore important to determine how much of the fault current returns to remote sources via the
shield wires of the transmission lines connected to NCC-SES GIS. In other words, the current
discharged into the NCC-SES GIS grounding system is smaller than the maximum available fault
current, because a portion of the fault current returns via the shield wires connected to NCC-SES
GIS. In order to determine the actual fault current split, a HIFREQ model of the overhead
transmission line network is built to compute the fault current distribution. Note that the calculation
can also be carried out by using the TRALIN and SPLITS which use a circuit model approach.
GENNE-SES
Distance = 90,052 ft
No. of Spans = 94
Span Length = 958 ft
Distance = 79,184 ft
135 No. of Spans = 101
Span Length = 784 ft
NCC-SES GIS 30
X
55
160
Distance = 115,918 ft
Distance = 87,024 ft
No. of Spans = 121
No. of Spans = 111
Span Length = 958 ft
Span Length = 784 ft
GENSW-SES
GENSE-SES
Page 4-1
Chapter 4. Fault Current Distribution Analysis Using HIFREQ
GENNW-SES GENNE-SES
GENSW-SES GENSE-SES
Height of Tower 151'-6" 172'
Length of Insulator 10' 8'
Height of Faulted Phase 90' 117'
Sag of Phase 37'-10" 40'
Height of Faulted Phase Considering Sag 64.78' 90.33'
Offset of Phase from Tower Center 18'-3" 17'-6"
Height of Sky Wire 151'-6" 172'
Sag of Sky Wire 32'-10" 35'
Offset of Sky Wire from Tower Center 12'-3" 10'-6"
Height of Sky Wire Considering Sag 129.61' 148.67'
Average Span Length (ft) 958 784
1590 MCM 2167 MCM
Phase Conductor
ACSR Lapwing ACSR Kiwi
Sky Wire 7#8 Alumoweld 7#8 Alumoweld
Table 41 Detail Data of Line Cross Section and Conductor Types for 154 kV Lines
GENNW-SES and GENSW-SES GENNE-SES and GENSE-SES
S1 S2 S1 S2
20'
18'
18'-3 '' 16'
A1 A2 A1 A2
20'
22'
17'
18'-3 '' 17'-6 ''
C1 C2 C1 C2
90'
117'
Figure 4.2 Transmission Line Cross Sections. Conductors Heights Are at Structures
Page 4-2
Chapter 4. Fault Current Distribution Analysis Using HIFREQ
The short-circuit calculations carried out by the power utility provide the following fault current
contributions from each terminal substation (Bus No. 1-8 in Table 44). The total fault current (sum
of Bus 1-8) is 10.557 76.31 kA. This information is based on a bolted fault at the GIS site
(internal fault) assuming a 0 equivalent ground resistance at the NCC-SES GIS (worst-case
scenario).
Energization
Bus No. Identification Magnitude (A) Angle (Deg) Terminal
Type
1 GENNE-C1 LEAD 688.18 -79.92 T1
2 GENNE-C2 LEAD 921.25 -71.84 T1
3 GENSE-C1 LEAD 1985.00 -75.00 T2
4 GENSE-C2 LEAD 1929.00 -77.00 T2
5 GENSW-C1 LEAD 646.00 -72.00 T3
6 GENSW-C2 LEAD 611.00 -75.00 T3
7 GENNW-C1 LEAD 562.00 -84.00 T4
8 GENNW-C2 LEAD 3227.00 -77.00 T4
9 Zero GPR GPR-Potential 0 0
Table 44 Energizations of Transmission Lines
The currents flowing on the overhead shield wires as well as the currents injected into the NCC-SES
GIS grounding system from each terminal can be obtained from the following HIFREQ circuit
model. In the HIFREQ computer model, only the faulted phase and shield wires are represented.
The faulted phase is assumed to be the bottom phase which has the least mutual coupling with the
Page 4-3
Chapter 4. Fault Current Distribution Analysis Using HIFREQ
shield wires and therefore leads to the largest fault current flowing into the GIS grounding grid. The
steps required to build the HIFREQ input file are described in the next section.
Click here
Page 4-4
Chapter 4. Fault Current Distribution Analysis Using HIFREQ
In the following section, it will be assumed that the reader is entering the data as indicated in the
instructions. Note that it is advisable to save your work regularly by clicking on the Save button in
the toolbar and following the instructions in the dialog box. The data entered up to that point will be
saved in two files called HI_NCCR1.F05. Each file can be retrieved at any time by selecting the File
| Open Document menu item in SESCAD and following the instructions in the dialog box. The
same considerations apply if a data entry session has to be interrupted (close all active windows to
exit the program after saving your data).
If you intend to enter the data manually, proceed directly to Section 4.4.2. If you do not wish to do
so, you can import all the data by proceeding as follows.
Importing DATA
First be sure to close the HI_NCCR1.F05 which was just created. Select the Open
Documentunder the File menu. Browse to the file HI_07R1.F05 in the working directory
\CDEGS Howto\Gisgrnd, then click on the OK button to open the file. Click on Save Document
As and select the file HI_NCCR1.F05 in working directory to overwrite this file. The data
described in the next section will be loaded and you will not have to enter it.
Page 4-5
Chapter 4. Fault Current Distribution Analysis Using HIFREQ
Step 3. Define Conductor Types: Four types of conductors are defined in the HIFREQ
model. As shown in the following screen, Conductor Type No. 1 is defined as 7No.8
Alumoweld for the overhead shield wires. Conductor Type No. 2 defines the 13.47 ohms
ground resistance at the NCC-SES GIS Grid. Conductor Type No. 3 defines the 40 ohms
tower ground resistance. Conductor Type No. 4 defines the 0.5 ohms terminal ground
resistance. These four conductor types are specified by selecting the Define | Conductor
Types menu item and by entering the data as shown in the following screen.
Note that the characteristics of a stranded conductor, such as 7 No.8 Alumoweld, are defined by first
selecting the User-Defined under Impedance Specification and then by entering its internal
impedance. The Internal Resistance and Internal Reactance of the 7 No.8 Alumoweld are
obtained from the SESConductorDatabase Tool. Appendix B provides details on how to obtain
these values.
To reduce the amount of work in the input data, the phase wires are simply modeled as a solid 4/0
copper wire (0.264 radius, default in SESCAD) since we will be using current sources to energize
the phase conductors. However, if one wishes to use voltage sources to carry out a study, it is
important to model the phase conductors accurately. In this case, the ACSR conductors can also be
defined by their internal resistances and reactances from the SESConductorDatabase Tool.
Step 4. Define Energization Types: The energizations of the phase conductors are defined
by selecting the Define | Energization Types menu item. You can copy and paste the data
from Table 44 into the following screen. Note that Bus No. 9 defines a 0 Volts GPR-
Page 4-6
Chapter 4. Fault Current Distribution Analysis Using HIFREQ
Potential energization which is used to remotely ground the 40 ohm towers. Step 6 will show
how to use the zero GPR energization.
Step 5. Define Overhead Network for GENNE-SES: We are now ready to define the
overhead shield wires and the phase conductors for Terminal GENNE-SES. From the Insert
menu, select the Right-of-Way Model. In the following screen, enter the Length, Angle
and Number of Structures according to Figure 4.1 and Table 43.
Select the Cross-Section tab and enter the cross section according to Figure 4.2. Leave No under
the Connected? Column as we will manually connect the shield wires in the next step. Click on the
Characteristics button, for each conductor, to define the characteristics of these conductors. Define
the phase wires (NE-C1 and NE-C2) to be 0.264 solid copper and the shield wires (NE-S1 and NE-
S2) to be 0.1925 7No.8 Alumoweld.
Page 4-7
Chapter 4. Fault Current Distribution Analysis Using HIFREQ
No data will be entered in the Structures and Terminations tab as we will define them manually in
the next steps to minimize the number of conductor segments. Click on the OK button. This creates
the overhead shield wires and phase conductors.
a. In the SESCAD screen, make sure that you are in the X-Y Plan View, zoom into near
(X = 0, Y = 0) as shown below.
b. Click on the Draw conductor button to draw a connection between the two shield wires.
By default, a 0.264 copper conductor is used for the connection.
Click here to
Click here to draw change to X-Y,
a conductor X-Z, Y-Z, 3D or
Plan Views
Page 4-8
Chapter 4. Fault Current Distribution Analysis Using HIFREQ
a. Change the view to the X-Y 3D View. Click on the Power Tool and select Create Rod.
Enter 100 ft and click at the corner of the shield wire and the connection conductor1. This
will generate a 100 ft rod.
b. Right-click on the 100 ft rod and select the Characteristics. Select Tower 40 ohms from
the Conductor Type drop-down list and click OK. This assigns the 40 ohms to the rod.
The radius of the rod is chosen to be 0.375 (default).
Note that the length of 100 ft is chosen so that the ground rod is completely in the air. This
ignores the conductive interactions among the towers which is a good approximation in the
fault current distribution calculation. This will allow us to conveniently use a fixed 40 ohms
tower resistance provided by the utilities. Note also that if one wishes to carry out the fault
current distribution calculation by modeling actual towers (such as a single ground rod
driven into the soil), the length of rods must be determined accounting for the conductive
couplings between towers.
Click here to
select Power Tool
| Create Rods
a. With the 100 ft rod selected, select the Edit | Duplicate menu item to make a copy of the
100 ft rod.
1
Note that this will create the 40 ohms tower at the one end of the connection conductor to avoid subdividing the
connection conductor. This will reduce the total number of conductor segments significantly.
Page 4-9
Chapter 4. Fault Current Distribution Analysis Using HIFREQ
b. Select the Edit | Edit Object (or press the Ctrl+E key). Modify the Z coordinates of the
rod in the following screen. This has created a 1 ft ground rod.
c. Click on the Characteristics button. Set Conductor Type = 0 and Energization Type =
9- Zero GPR. Note that you must set Z Starts At = -47.67 ft so that this node (called
pseudo node in HIFREQ) is energized with a zero GPR.
a. First select the connection conductor, select the Display | Align View menu item, choose
Y-Axis and click OK. This rotates the overhead shield wires along the X-Axis.
b. Select the connection conductor, the 40 ohms tower and the 1 ft rod with zero GPR all
together. Select the Edit | Group to group them. Under the Tools menu, select Shift
Objects.
c. Click on the Apply To Duplicate. Set Number Of Duplicates = 101; Quick Distance =
784 ft according to Table 43.
d. Click on the black arrow to move to the right. This creates the remaining towers and the
connections.
Click here to
move in + X-Axis
Page 4-10
Chapter 4. Fault Current Distribution Analysis Using HIFREQ
a. Still in the XY Align View, zoom-in to the last tower at Terminal GENNE-SES.
b. Select the last grouped tower and the connection. Under the Advanced menu, select Set
As Active Object (or press the function key F9). This allows you to edit objects inside a
grouped object.
c. Turn off Apply To Duplicate. Enter 10.5 ft under the Quick Distance. Select only the
tower and the zero GPR rod. Click on the black arrow to move them down by 10.5 ft.
d. Right-click on the 100 ft rod. Select the Characteristics and choose Terminal 0.5 ohms
under the Conductor Types.
e. Select the Advanced | Set Parent As Active Object (or press the function key Shift+F9)
menu item to exit the grouped tower and the connection.
a. Still in the XY Align View, zoom-in to the last tower at Terminal GENNE-SES. Select
the View | Labeling | Show Conductor Numbers and View | Orientation | Show
Orientation of Conductors.
b. Click on the Draw conductor button to draw a conductor from Conductor #1 (Shield
Wire S1, see Figure 4.2) to Conductor #3 (Phase Wire C1); and a conductor from
Conductor #2 (Shield Wire S2) to Conductor #4 (Phase Wire C2). This creates
Conductors #311 and #312.
c. Right-click on Conductor #311 and select the Characteristics. From the drop-down
menu of the Energization, select 1-GENNE-C1. Conductor #311 is now energized.
Conductor #312 is energized similarly by select 2-GENNE-C2 in the Characteristics
screen.
Page 4-11
Chapter 4. Fault Current Distribution Analysis Using HIFREQ
a. Still in the XY Align View, but zoom-in to the first tower at NCC-SES GIS.
b. Repeat Step 10 to move the tower to the mid-point between the two shield wires, i.e., X =
0 and Y = 0.
c. As shown in the following screen, Right-click on Conductor #6 and change the
Characteristics. Select 2-NCC-SES GIS from the Conductor Type drop-down menu
to set the ground resistance of the NCC-SES GIS to 13.47 ohms.
Page 4-12
Chapter 4. Fault Current Distribution Analysis Using HIFREQ
Step 13. Define Phase-To-Ground Fault At NCC-SES: At NCC-SES GIS: In order to avoid
conductors crossing each other between different terminals at NCC-SES GIS, we will first
shorten Conductors #1-#4 by 50 ft along the transmission line.
a. Still in the XY Align View, click on Conductor #5. Select the Tools | Shift Objects to
move Conductor #5 to the right by 50 ft. Select the Advanced | Set Parent As Active
Object to exit the grouped conductor. See Figure 4.3.
b. Click on the Power Tool | Extend. First click on the start of Conductor #1 (the mouse
changes to a little black arrow), then click on the start end of Conductor #5. This shortens
Conductor #1 by 50 ft from the center of the substation. Repeat the same for Conductor
#2, but extend the start of Conductor #2 to the end of Conductor #5. See Figure 4.4.
c. Click on the Draw button to connect the two phase conductors (Conductor #3 and #4) at
the substation. This creates a new Conductor #313. Select the Tools | Shift Objects to
move Conductor #313 to the right by 50 ft. See Figure 4.5.
d. Click on the Power Tool | Extend and extend the two phase conductors Conductor #3
and #4 to Conductor #313. See Figure 4.6.
e. Delete Conductor #313.
f. Click on the Draw button, draw one conductor from Start of Conductor #5 to Conductor
#6. Draw two more conductors to connect Start of Conductor #3 to the Start of Conductor
#5, and to connect Start of Conductor #4 to End of Conductor #5. This creates a phase-to-
ground fault for the transmission line to Terminal GENNE-SES at NCC-SES GIS. Figure
4.7.
Page 4-13
Chapter 4. Fault Current Distribution Analysis Using HIFREQ
Figure 4.4 Extend Conductors #1 and #2 to Conductor #5 (Shorten Shield Wires by 50 ft).
Page 4-14
Chapter 4. Fault Current Distribution Analysis Using HIFREQ
Figure 4.6 Extend Conductors #3 and #4 to Conductor #313 (Shorten Phase Wires by 50 ft).
Page 4-15
Chapter 4. Fault Current Distribution Analysis Using HIFREQ
Step 14. Terminal NCCNE-SES is defined completely. The other three terminals can be
defined by the same way by repeating Steps 5 through 13, except Step 12 since there is no
need to re-create the NCC-SES GIS ground resistance. Since the cross section for Terminal
NCCSE-SES is the same as that of NCCNE-SES, you can create this terminal first, followed
by Terminal NCCSW-SES, then followed by Terminal NCCNW-SES. The following list the
Create Right-of-Way input data for these terminals.
Page 4-16
Chapter 4. Fault Current Distribution Analysis Using HIFREQ
Page 4-17
Chapter 4. Fault Current Distribution Analysis Using HIFREQ
An input file HI_07R1.F05 has been prepared for those who wish to simply load the data.
At this point, you have completed the preparation of the data. Under the File menu, select Save
Document and then click Close Document to close this file in SESCAD. The *.F05 is an ASCII file
you can edit and view at any time.
The file HI_NCCR1.F05 is ready to be submitted to the HIFREQ engineering module in the next
section.
If you are a licensee of the CDEGS software you will now be able to proceed to Section 3.3. Users
of the demo software are not able to process the input file, but are able to peruse all output files,
which are already available. Therefore read Section 3.3 for reference only. Any attempt to start the
engineering modules will result in a message stating that the Engineering module is not active.
Page 4-18
Chapter 4. Fault Current Distribution Analysis Using HIFREQ
Once the run is complete, a window will pop up to inform you that a log file has been generated.
Click the OK button to close the message window. SESBatch allows you to conveniently access
some of the important files that it generates. For example, from the Tools | View Run Log File
menu item you can view the log file generated during the computations. From the Tools | View
Output File menu item you can view the output file, which may contain ERROR or WARNING
messages requiring your attention. Finally, you can launch Output Toolbox directly from the Tools |
View Results with Output Toolbox menu item.
The HIFREQ program will start and will carry out all requested computations. The run takes about
20 minutes to complete (on an Intel Core i7-2600 CPU@3.4GHz and 16 GB RAM). At
completion, the program will produce two important files: an OUTPUT file (HI_ NCCR1.F09) and a
DATABASE file (HI_ NCCR1.F21).
The OUTPUT file is an ASCII file, while the DATABASE is a binary file. The OUTPUT file
contains all the input information and computation results from your HIFREQ run. Any ERROR or
WARNING messages generated during the HIFREQ run will appear in the OUTPUT file. You can
view the OUTPUT file by clicking the Output/File Viewer (or button) in the Output section of
the toolbar. You can also use the GraRep utility module (see Sections 2.2.1.2) to view and edit any
ASCII output files.
If you have followed the instructions up to this point, the active Job ID should be "NCCR1". We
will, therefore, extract the results and display the plots on screen. In the CDEGS screen, select
Examine from the Session Mode drop-down list. Click on the HIFREQ button to start the Output
Toolbox (or by click on the button on the toolbar).
The following lists the steps to obtain the fault current distribution at NCC-SES GIS:
Page 4-19
Chapter 4. Fault Current Distribution Analysis Using HIFREQ
Page 4-20
Chapter 4. Fault Current Distribution Analysis Using HIFREQ
Page 4-21
This page is intentionally left blank
Chapter 5. Model Gas Insulated Substation in HIFREQ
CHAPTER 5
MODEL GAS INSULATED SUBSTATION IN
HIFREQ
In this chapter, we will describe how to model the NCC-SES GIS in HIFREQ. The conductor
network of the NCC-SES GIS consists of the grounding system described in Chapter 3 and the above
ground GIS bus works which will be described in this chapter. After the conductor network is built,
we will compute touch and step voltages during a phase-to-ground fault at the NCC-SES GIS. This
chapter describes how to build the HIFREQ model. Chapter 6 and Chapter 7 present the safety
evaluations of the initial grid and the reinforced grounding grid, respectively.
Page 5-1
Chapter 5. Model Gas Insulated Substation in HIFREQ
Figure 5.2 3D View of NCC-SES GIS Bus Works (each line represents a GIS phase and its
enclosure)
Click here
Page 5-2
Chapter 5. Model Gas Insulated Substation in HIFREQ
In the Select a file to open window, select Open the HIFREQ file HI_NCCR1-GIS.F05 <New
Case>. You are now ready to input data.
Because the GIS model shown in Figure 5.2 is very complex, it is not practical as a tutorial to
demonstrate how to create the complete model. In the next section, we will therefore only describe
some key steps on how to create a section of the GIS bus works: how to ground the GIS enclosure to
the grounding grid and how to make a phase-to-ground fault between the core and the sheath of the
GIS cable.
After this, you can simply re-load a HIFREQ file which has been prepared in advance to follow the
rest of the tutorial (see Section 5.2.3).
a. First be sure to close the HI_NCCR1-GIS.F05 which was just created. In SESCAD,
browse to the MALT file MT_NCCR1.F05 and open it.
b. Select File | Save Document As. Under the Files of type drop-down list, select HIFREQ
Input Files (hi_*.f05; hi_*.inp). Change the file name to HI_NCCR1-GIS.F05. Click
OK. Answer Yes to overwrite the HI_NCCR1-GIS.F05.
c. Answer Yes in the Exporting Template Inconsistency message. This converts the
MT_NCCR1.F05 in Chapter 3 as the HI_NCCR1-GIS.F05.
Page 5-3
Chapter 5. Model Gas Insulated Substation in HIFREQ
A-B -9.40311 74.4743 -18.211 -9.40311 100.065 -18.211 0.5 0.875 999999 11 12 10 300 1
B-C -9.40311 100.065 -18.211 -9.40311 100.065 -9.875 0.5 0.458333 999999 6 7 10 300 2
C-D -9.40311 100.065 -9.875 -1.52811 100.065 -9.875 0.5 0.458333 999999 6 7 10 300 2
D-E -1.52811 100.065 -9.875 -1.52811 100.065 -4.102 0.5 0.458333 999999 6 7 10 300 2
E-F -1.52811 100.065 -4.102 6.64389 100.065 -4.102 0.5 0.458333 999999 6 7 10 300 2
F-G 6.64389 100.065 -4.102 6.64389 100.065 -13.222 0.5 0.458333 999999 6 7 10 300 2
G-H 6.64389 100.065 -13.222 8.61289 100.065 -13.222 0.5 0.458333 999999 6 7 10 300 2
H-I 8.61289 100.065 -13.222 8.61289 87.9241 -13.222 0.5 0.458333 999999 6 7 10 300 2
I-J 8.61289 87.9241 -13.222 6.64389 87.9241 -13.222 0.5 0.458333 999999 6 7 10 300 2
J-K 6.64389 87.9241 -13.222 6.64389 87.9241 -15.19 0.5 0.458333 999999 6 7 10 300 2
K-L 6.64389 87.9241 -15.19 34.9394 87.9241 -15.19 0.5 0.458333 999999 6 7 10 300 2
Page 5-4
Chapter 5. Model Gas Insulated Substation in HIFREQ
E F
C D
G H
B
J I
K L
a. Select the Define | Cable Types menu item. The following screen shows up (without any
data initially). Click on the Add button and enter Enclosure 24inch as the cable name.
b. Enter the conductor and insulation properties according to Table 51.
c. Click on the Add button and enter Enclosure 14inch as the cable name.
d. Enter the conductor and insulation properties according to Table 51.
e. Click OK. This defines both cable types.
Page 5-5
Chapter 5. Model Gas Insulated Substation in HIFREQ
a. Select the Insert | Single Conductor menu item. In the following Create Object screen,
enter the coordinates for the Start Point and End Point for Section AB.
b. Click on the Characteristics button. Select Cable Type and select 1 Enclosure 24inch.
This defines the conductor and it physical properties of the cable completely.
Page 5-6
Chapter 5. Model Gas Insulated Substation in HIFREQ
c. We now define Section BC. Repeat the previous two steps and enter the coordinates using
Table 51. Click on the Characteristics. Select Cable Type and select 1 Enclosure
14inch. This defines the conductor and physical properties of the cable Section BC.
d. The rest cables from C-L are defined by the same way by using Table 51 and Figure 5.3.
Page 5-7
Chapter 5. Model Gas Insulated Substation in HIFREQ
Page 5-8
Chapter 5. Model Gas Insulated Substation in HIFREQ
Connect Sheath of
Conductor #824 (End
Extremity) to Conductor
#825 (Start Extremity)
Figure 5.6 Make Connection from Enclosure to Grounding Grid in Connections Layer
Importing DATA
First be sure to close the HI_NCCR1-GIS.F05 which was just been created. Select the Open
Documentunder the File menu. Browse to the file HI_07R1-GIS.F05 in the working directory
\CDEGS Howto\Gisgrnd, then click on the OK button to open the file. Click on Save Document
As and select the file HI_NCCR1-GIS.F05 in working directory to overwrite this file. The data
described in the next section will be loaded and you will not have to enter it.
Figure 5.7 shows the HIFREQ model corresponding to the HI_NCCR1-GIS.F05 file. It contains the
grounding grid prepared in Chapter 3, the GIS bus works in Figure 5.2 and additional conductors
(highlighted in red) which connect the GIS bus works to the grounding grid underneath the rebar.
Page 5-9
Chapter 5. Model Gas Insulated Substation in HIFREQ
There are four above grounding conductors which will be used to inject the currents into the NCC-
SES GIS from each of the four terminals. The currents are provided in Table 45.
a. In SESCAD, under the Edit menu, turn off the User Group Information.
b. In the Edit menu, choose the Select By Index and enter 180. Click OK. Conductor #180 is
selected.
c. Zoom into the beginning of Conductor #180. Turn on the Connection layer. Select the
connection at the beginning of Conductor #180 and choose the Edit | Edit Object (Ctrl+E)
menu item. You will see the following screen. The fault is simply defined as a connection
between the core and sheath.
2
Note that this is a different file. The conductor numbers in this file is not related to the file in Section 5.2.2.
Page 5-10
Chapter 5. Model Gas Insulated Substation in HIFREQ
Connection defined
at the beginning of
Conductor #180
Page 5-11
Chapter 5. Model Gas Insulated Substation in HIFREQ
Page 5-12
Chapter 6. Safety Evaluation of NCC-SES GIS
CHAPTER 6
SAFETY EVALUATION OF NCC-SES GIS
We have now determined the soil structure, fault current distribution, and the predesigned grounding
system. In this chapter, we will demonstrate how to extract the computation results, and we will
evaluate if our proposed design is safe and adequate. The detailed steps are provided to get the touch
voltage, step voltage, and longitudinal currents throughout NCC-SES GIS, in order to determine at
what locations, if any, mitigation measures are required.
One of the main concerns when designing grounding systems is to ensure that no electrical hazard
exists outside or within the substation during normal and fault conditions. In most cases, there are no
safety concerns during steady-state normal conditions because very little current flows in the neutral
and grounding system. This current, called residual current, rarely exceeds 10% of the nominal load
current in most electrical distribution systems. Therefore, safety is usually a concern only during
phase-to-ground faults.
In practice, most electric substations are fenced and the fence is quite often placed 3.28 feet (1 m)
inside the outer conductor loop of the grounding system. This way, a person contacting the fence
from the outside will be standing above or close to a ground conductor which will normally result in
lower touch voltages than in the case where the fence is not surrounded by such a ground conductor
loop. In this study, the fence at the NCC-SES GIS is located 3.28 ft inside the outer loop of the
grounding system. Furthermore a large portion of the fence is not metallic (concrete or bricks).
Therefore, unless there are concerns for transferred potentials to remote locations via overhead or
metallic paths, such as gas, oil or water pipes, railway tracks, etc., only the area delimited by the
grounding system outer loop conductor needs to be examined with respect to unsafe touch voltages.
However, step voltages must be explored everywhere inside and outside the substation site. In
general though, step voltages are rarely a concern at electric power substations.
ANSI/IEEE Standard 80-2000 provides a methodology for determining maximum acceptable touch
voltages, based on the minimum current required to induce ventricular fibrillation in a human
subject. The touch voltage limit is a function of shock duration (i.e., fault clearing time), system
characteristics (for short fault clearing times), body weight, and foot contact resistance (which
Page 6-1
Chapter 6. Safety Evaluation of NCC-SES GIS
depends on the electrical resistivity of the material, such as crushed rock or soil, on which the person
is standing). Table 61 shows how the touch voltage varies as a function of the resistivity of earth
surface covering material (for a 0.5 s fault clearing time, a system X/R ratio of 20, and a 50 kg body
weight).
Surface Layer
Touch Voltage Limit (V)
Type Resistivity (-m)
Native Soil 2553 778.2
6 Crushed Rock 3000 868.9
Table 61 Touch Voltage Limit as a Function of Surface Layer Resistivity
The crushed rock surface layer installed on the surface of the NCC-SES GIS is 6 thick and has an
estimated resistivity (when wet) of 3000 ohm-m. The maximum clearing time of the backup relays is
assumed to be 0.5 s. The crushed rock surface layer overlies a soil with a resistivity of 2553 -m.
Resistivity varies as a function of the type of rock, the size of the stones, the moisture content and
the degree of contamination (e.g., filling of the voids between stones by finer lower resistivity
material).
Surface Layer
Step Voltage Limit (V)
Type Resistivity ( -m)
Native Soil 2553 2644.8
6 inch Crushed Rock 3000 3007.8
Table 62 Step Voltage Limit as a Function of Surface Layer Resistivity
Within a substation and within 3.28 ft (1 m) outside the perimeter fence, step voltages are lower than
touch voltages; furthermore, the maximum acceptable values are higher than for touch voltages.
Consequently, satisfying the touch voltage safety criteria in this area automatically ensures
satisfaction of the step voltage safety criteria. The step voltages in the substation and in an area
extending 10 ft outside the substation will be examined. Further away from the substation, no
computations were performed. However, it is unlikely for hazardous step voltages to exist at such
remote locations when they are safe closer to the substation.
Page 6-2
Chapter 6. Safety Evaluation of NCC-SES GIS
If you followed the tutorial up to this point, your current JobID should be NCCR1-GIS for the
HI_NCCR1-GIS.F05. Select Examine from the Session Mode list. The HIFREQ button will be
highlighted in the toolbar. Click the HIFREQ button, the CDEGS-Examine-HIFREQ screen will
appear and you are now ready to make a safety analysis by selecting Configuration and clicking the
Safety button to access the Safety screen. Click on the Safety button to start the Safety screen.
The crushed rock surface installed on the surface of the NCC-SES GIS is 6 thick (default value) and
overlying a soil with a resistivity of 2552.9 -m which is taken automatically from the soil model.
The crushed rock has an estimated resistivity (when wet) of 3000 ohm-m. The maximum clearing
time of the backup relays is 0.5 s. Enter all these in the Safety screen as shown below and click the
Generate Safety Threshold Limits and Report button, the following report appears on your
screen.
Page 6-3
Chapter 6. Safety Evaluation of NCC-SES GIS
==============================================
| Fault Clearing Time ( sec)| 0.500 |
+----------------------------+---------------+
| Decrement Factor | 1.052 |
| Fibrillation Current (amps)| 0.164 |
| Body Resistance (ohms)| 1000.00 |
==============================================
======================================
| | FAULT | |
| SURFACE | CLEARING TIME | |
| LAYER |-----------------| |
| RESIST- | 0.500 sec. | FOOT |
| IVITY |-----------------| RESIST-|
| (OHM-M) | STEP | TOUCH | ANCE: |
| | VOLTAGE| VOLTAGE| 1 FOOT |
| | (VOLTS)| (VOLTS)| (OHMS) |
======================================
| 3000.0| 3007.8| 868.9| 9141.6|
|---------+--------+--------+--------+
The table above indicates that the touch voltages of 868.9 Volts or less and step voltages of 3007.8
Volts or less are safe if 6 of crushed rock of 3000 -m is overlying a native soil with a resistivity of
2553 -m. To obtain the limits for the case where no surface covering is present, check No Surface
Layer Is installed and click Generate Safety Threshold Limits and Report. The report shows that
the touch voltages of 778.2 Volts or less and step voltages of 2644.8 Volts or less are safe for a
native soil (no crushed rock) with a resistivity of 2553 -m (more exactly 2552.9 -m).
Page 6-4
Chapter 6. Safety Evaluation of NCC-SES GIS
Page 6-5
Chapter 6. Safety Evaluation of NCC-SES GIS
Page 6-6
Chapter 6. Safety Evaluation of NCC-SES GIS
In the Cable Data Selection screen, enter From 1 To 2 in Range #1. Click on the
Plot/Draw button. This will display the currents flowing along both the core and sheath.
Page 6-7
Chapter 6. Safety Evaluation of NCC-SES GIS
Page 6-8
Chapter 6. Safety Evaluation of NCC-SES GIS
In the CDEGS Examine HIFREQ window, select the Use Safety Limit. Click on the
Plot/Draw button. This will reveal the area where touch voltages at NCC-SES GIS exceed
the safe touch voltage limit of 868.9 V. It shows that the touch voltages at the four corners
are excessive. Mitigation of the grid is therefore needed.
Page 6-9
Chapter 6. Safety Evaluation of NCC-SES GIS
Page 6-10
Chapter 6. Safety Evaluation of NCC-SES GIS
It is important to mention that the computation of step voltages is sensitive to the location of
observation points. When the maximum computed step voltage is close to the safe step voltage limit
(which is not the case here), it is recommended to reduce the spacing between the observation points
to a value smaller than 1 m in order to capture the worst case step voltage (which is usually at the
corners of the substation where earth potentials drop quickly).
We have now examined the computation results. Click in the toolbar to go back to the CDEGS
startup screen.
Page 6-11
This page is intentionally left blank
Chapter 7. Reinforcing the Grounding System
CHAPTER 7
REINFORCING THE GROUNDING SYSTEM
The touch voltages obtained in Chapter 6 indicate that our initial design hasnt reached a safe ground
grid design. The touch voltages in Figure 6.1 exceed the safe value near the corner meshes of the
grounding grid, which suggests that more conductors are needed near the edge and corner of the
grounding system. This observation is consistent with analytical and experimental evidence. The
optimum or most efficient conductor compaction at the periphery of a grounding system depends on
many factors, particularly on earth structure characteristics. Moreover, practical considerations often
introduce additional constraints which must be accounted for. In general, however, the following
crude rule of thumbs can be used as a preliminary set of guidelines:
When the surface (shallow depth) soil resistivity is small compared to the deeper layers
(those which are not in contact with the grounding system), use grids with more conductors
at the edge than at the center area (exponentially-spaced conductors). The degree of
conductor clustering (compactness) at the periphery of the grid should increase with an
increase of the contrast between the surface and deep layers.
When the surface soil resistivity becomes larger than that of the deeper soil layers, the
clustering (compactness) ratio should decrease towards a uniform distribution of conductors
in the case where the contrast ratio is significant (5 or more) and the thickness of surface
layers is small compared to the size of the grounding system (1/5 or less),
Finally, when the surface soil resistivity is quite large compared to the deeper layers and its
thickness is small enough so that use of ground rods penetrating the deeper layer is efficient,
a number of ground rods should be installed wherever possible to reduce the GPR, touch and
step voltages instead of using unequally spaced conductors.
Based on the soil model and the initial design, we will combine the first and the third methods in this
study.
Page 7-1
Chapter 7. Reinforcing the Grounding System
Step 1. In the SESCAD, first browse to the MT_NCCR1.F05. Save this file as MT_NCCR1-
GIS_Mit01.F05.
Step 2. Select the ground grid and select the Advanced | Set As Active Objects to modify
the perimeter ground conductors.
Step 3. Select the perimeter grounding conductor and use the Tools | Shift Objects to
duplicate the four perimeter grounding conductors by 7.5 ft towards the center of the
grid.
Step 4. Select the Power Tools and create the four 10 ft ground rods at the four corners of the
grounding grid. The radius of the ground rods is 0.375.
Step 5. Select the Define | Soil Model and enter the three-layer soil model in Table 23.
Step 6. Select the Run/Reports | Save & Run. This will start the SES Batch Processor.
Step 7. In the CDEGS window, select Examine from the session model and obtain the
grounding grid resistance.
Page 7-2
Chapter 7. Reinforcing the Grounding System
Page 7-3
Chapter 7. Reinforcing the Grounding System
For those who wish to just view the changes, you can load the HI_07R1-GIS_Mit01.F05.
This file is submitted into HIFREQ. Make sure your JobID is NCCR1-GIS_Mit01.
By following the steps provided in Section 6.2.3, the touch voltages are obtained. Figure 7.1 shows
that the maximum touch voltage is well below the safe touch voltage limit of 868.9 V.
3
Note that if the resistance of the reinforced grounding grid has changed significantly, you will need to re-run the fault
current distribution in HIFREQ.
Page 7-4
Chapter 7. Reinforcing the Grounding System
Since touch and step voltages are well below our target safe values of 868.9 V and 2645 V
respectively, the main engineering work is completed.
Further design iterations may be required to remove or reposition some conductors at more practical
locations. Extra ground rods may be added to account for winter soil freezing or summer extreme
drought conditions. In some cases, other soil structure models may need to be analyzed to account
for inherent data uncertainties or known soil characteristics variations. In such cases, the worst-case
scenario should be retained as a reference for the final recommended grounding design
configuration.
You can export the final design of the grounding grid to a DXF file that can be imported in most
CAD packages. This can be done easily by selecting the File | Save Document As in SESCAD.
Under the Files of type, select the DXF Files (*.dxf). Click OK and click OK again to take the
Default Color Number. The file MT_NCCR1-GIS_Mit01.dxf is generated. Additional information
can be obtained by clicking the Help button.
On a final note, it is worthwhile mentioning that when redesigning an existing grounding system
(update, upgrade, etc.), you can import the actual system configuration from a DXF-compatible
CAD file by clicking the File | Import | File Import | DXF (*.files) in the SESCAD and filling in
the fields of the dialog box. It is however important to note here that some drawings may contain
overlapping lines which will ultimately result in invalid overlapping conductors in MALT.
Furthermore, too many details such as short wire connections and bonding conductors have a
minimal impact on the grounding design performance but a significant negative impact on the
computations in terms of run time and run accuracy. One way to remove this kind of problem is to
Page 7-5
Chapter 7. Reinforcing the Grounding System
use the minimum conductor length threshold to ignore such non-significant short conductors. This
strategy, however, can be used in MALT only and may have a negative impact on the node
subdivision process.
Page 7-6
Chapter 8. Conclusions
CHAPTER 8
CONCLUSIONS
The detailed study has presented concise step-by-step instructions on how to prepare, submit and
examine results for the NCC-SES Gas Insulated Substation grounding system using the RESAP,
MALT and HIFREQ engineering modules of the CDEGS software package.
One major result of this study shows that significant fault currents are carried away along the
overhead shield wires and that accurate computations of the fault current distribution are crucial to
determine the safe touch voltages at substations where the soil resistivity is poor.
Only a few of the many features of the software have been used in this tutorial. You should try the
many other options available to familiarize yourself with the CDEGS software package. Your SES
Software DVD also contains a wealth of information stored under the PDF directory. There you will
find the Getting Started with SES Software Packages manual (\PDF\getstart.pdf) which contains
useful information on the CDEGS environment. You will also find other How ToEngineering
Guides, Annual Users Group Meeting Proceedings and much more. All Help documents are also
available online.
Page 8-1
This page is intentionally left blank
Appendix A. Command Input Mode
APPENDIX A
COMMAND INPUT MODE
Any of the interfaces listed below or a text editor can be used to prepare the input data. The
Windows Toolbox input modes convert the results of an input session to a Command Mode
compatible ASCII input file which can be edited at any time. This document describes the Windows
Toolbox mode in detail.
The Windows Toolbox mode.
The Command mode.
Plain text editor mode.
Printout A.1 is the resulting RESAP Command mode compatible input file which analyzes the soil
structure using the soil resistivity measurements from Traverse 1. The data for Traverse 1 can be
found in Table 21. This RESAP file can be edited directly by an experienced user or is
automatically produced when using one of the above-listed input interface modules.
Similar files can be prepared quite easily by following the information contained in the template
shown in Figure A.1. The following section describes the Windows compatible Toolbox input
session which, once completed, generates the input file described in Printout A.1 which can be
reloaded during subsequent sessions.
RESAP
TEXT,MODULE,NCC-SES GIS SOIL RESISTIVITY ANALYSIS FOR
TEXT,MODULE,THE WENNER ELECTODE CONFIGURATION. DATA
TEXT,MODULE,MEASURED BY STING R1 AND SAS 300C ARE COMBINED.
TEXT,MODULE,TRIAL RUN.
OPTIONS
UNITS,BRITISH
RUN-IDENTIFICATION,NCC1T
PRINTOUT,DETAILED
MEASUREMENTS,APPARENT-RES
METHOD,WENNER
RESULTS,1.64,554.6,.492,.492
RESULTS,3.28,385.4,.492,.492
RESULTS,6.56,178.3,.492,.492
RESULTS,9.84,105.3,.492,.492
RESULTS,13.12,74.46,.492,.492
RESULTS,16.4,59.50,.984,.984
RESULTS,19.68,48.17,.984,.984
RESULTS,22.96,42.08,.984,.984
RESULTS,32.8,28.40,1.312,1.312
RESULTS,49.2,19.02,1.312,1.312
RESULTS,65.6,14.48,1.312,1.312
RESULTS,98.4,10.33,1.64,1.64
RESULTS,164,6.88,1.64,1.64
RESULTS,229.6,5.905,1.64,1.64
RESULTS,328,4.523,1.64,1.64
RESULTS,1.64,557.0,.492,.492
RESULTS,3.28,386.0,.492,.492
RESULTS,6.56,179.6,.492,.492
RESULTS,9.84,106.3,.492,.492
RESULTS,13.12,75.11,.492,.492
RESULTS,16.4,59.7,.984,.984
RESULTS,19.68,48.4,.984,.984
RESULTS,22.96,42.1,.984,.984
RESULTS,32.8,27.9,1.312,1.312
RESULTS,49.2,18.82,1.312,1.312
RESULTS,65.6,14.93,1.312,1.312
RESULTS,98.4,10.37,1.64,1.64
RESULTS,164,6.61,1.64,1.64
RESULTS,229.6,6.09,1.64,1.64
RESULTS,328,4.71,1.64,1.64
OPTIMIZATION
ACCURACY,0.025
ITERATIONS,500
METHODOLOGY
MARQUARDT
STEPSIZE,0.0001
ENDPROGRAM
Page A-1
Appendix A. Command Input Mode
Page A-2
Appendix A. Command Input Mode
The input file RS_NCC1A.F05 can be easily created from RS_NCC1T.F05 using your favorite text
editor. Note that the SOIL-TYPE module in RS_NCC1T.F05 is replaced by the following
commands:
SOIL-TYPE, MULTILAYER
HORIZONTAL
LAYER, TOP, 0.0,0.0
LAYER, CENTRAL, 0.0,0.0
LAYER, CENTRAL, 0.0,0.0
LAYER, BOTTOM,0.0
RESAP
OPTIONS
UNITS,BRITISH
RUN-IDENTIFICATION,NCC1A
PRINTOUT,DETAILED
MEASUREMENTS,APPARENT-RES
METHOD,WENNER
RESULTS,1.64,554.6,.492,.492
RESULTS,3.28,385.4,.492,.492
RESULTS,6.56,178.3,.492,.492
RESULTS,9.84,105.3,.492,.492
RESULTS,13.12,74.46,.492,.492
RESULTS,16.4,59.50,.984,.984
RESULTS,19.68,48.17,.984,.984
RESULTS,22.96,42.08,.984,.984
RESULTS,32.8,28.40,1.312,1.312
RESULTS,49.2,19.02,1.312,1.312
RESULTS,65.6,14.48,1.312,1.312
RESULTS,98.4,10.33,1.64,1.64
RESULTS,164,6.88,1.64,1.64
RESULTS,229.6,5.905,1.64,1.64
RESULTS,328,4.523,1.64,1.64
RESULTS,1.64,557.0,.492,.492
RESULTS,3.28,386.0,.492,.492
RESULTS,6.56,179.6,.492,.492
RESULTS,9.84,106.3,.492,.492
RESULTS,13.12,75.11,.492,.492
RESULTS,16.4,59.7,.984,.984
RESULTS,19.68,48.4,.984,.984
RESULTS,22.96,42.1,.984,.984
RESULTS,32.8,27.9,1.312,1.312
RESULTS,49.2,18.82,1.312,1.312
RESULTS,65.6,14.93,1.312,1.312
RESULTS,98.4,10.37,1.64,1.64
RESULTS,164,6.61,1.64,1.64
RESULTS,229.6,6.09,1.64,1.64
RESULTS,328,4.71,1.64,1.64
SOIL-TYPE,MULTILAYER
HORIZONTAL
LAYER,TOP,0.,0.
LAYER,CENTRAL,0.,0.
LAYER,CENTRAL,0.,0.
LAYER,BOTTOM,0.
OPTIMIZATION
ACCURACY,0.025
ITERATIONS,500
METHODOLOGY
MARQUARDT
STEPSIZE,0.0001
ENDPROGRAM
Page A-3
Appendix A. Command Input Mode
Printout A.3 shows the input file RS_NCC1B.F05. The only difference between RS_NCC1B.F05
and RS_NCC1A.F05 is the number of layers in the SOIL-TYPE module.
RESAP
OPTIONS
UNITS,BRITISH
RUN-IDENTIFICATION,NCC1B
PRINTOUT,DETAILED
MEASUREMENTS,APPARENT-RES
METHOD,WENNER
RESULTS,1.64,554.6,.492,.492
RESULTS,3.28,385.4,.492,.492
RESULTS,6.56,178.3,.492,.492
RESULTS,9.84,105.3,.492,.492
RESULTS,13.12,74.46,.492,.492
RESULTS,16.4,59.50,.984,.984
RESULTS,19.68,48.17,.984,.984
RESULTS,22.96,42.08,.984,.984
RESULTS,32.8,28.40,1.312,1.312
RESULTS,49.2,19.02,1.312,1.312
RESULTS,65.6,14.48,1.312,1.312
RESULTS,98.4,10.33,1.64,1.64
RESULTS,164,6.88,1.64,1.64
RESULTS,229.6,5.905,1.64,1.64
RESULTS,328,4.523,1.64,1.64
RESULTS,1.64,557.0,.492,.492
RESULTS,3.28,386.0,.492,.492
RESULTS,6.56,179.6,.492,.492
RESULTS,9.84,106.3,.492,.492
RESULTS,13.12,75.11,.492,.492
RESULTS,16.4,59.7,.984,.984
RESULTS,19.68,48.4,.984,.984
RESULTS,22.96,42.1,.984,.984
RESULTS,32.8,27.9,1.312,1.312
RESULTS,49.2,18.82,1.312,1.312
RESULTS,65.6,14.93,1.312,1.312
RESULTS,98.4,10.37,1.64,1.64
RESULTS,164,6.61,1.64,1.64
RESULTS,229.6,6.09,1.64,1.64
RESULTS,328,4.71,1.64,1.64
SOIL-TYPE,MULTILAYER
HORIZONTAL
LAYER,TOP,0.,0.
LAYER,CENTRAL,0.,0.
LAYER,CENTRAL,0.,0.
LAYER,CENTRAL,0.,0.
LAYER,BOTTOM,0.
OPTIMIZATION
ACCURACY,0.025
ITERATIONS,500
METHODOLOGY
MARQUARDT
STEPSIZE,0.0001
ENDPROGRAM
Page A-4
Appendix A. Command Input Mode
Printout A.4 shows the input file RS_NCC1C.F05. Based on the five-layer soil model, an initial
guess for the four-layer soil model is constructed and defined.
RESAP
OPTIONS
UNITS,BRITISH
RUN-IDENTIFICATION,NCC1C
PRINTOUT,DETAILED
MEASUREMENTS,APPARENT-RES
METHOD,WENNER
RESULTS,1.64,554.6,.492,.492
RESULTS,3.28,385.4,.492,.492
RESULTS,6.56,178.3,.492,.492
RESULTS,9.84,105.3,.492,.492
RESULTS,13.12,74.46,.492,.492
RESULTS,16.4,59.50,.984,.984
RESULTS,19.68,48.17,.984,.984
RESULTS,22.96,42.08,.984,.984
RESULTS,32.8,28.40,1.312,1.312
RESULTS,49.2,19.02,1.312,1.312
RESULTS,65.6,14.48,1.312,1.312
RESULTS,98.4,10.33,1.64,1.64
RESULTS,164,6.88,1.64,1.64
RESULTS,229.6,5.905,1.64,1.64
RESULTS,328,4.523,1.64,1.64
RESULTS,1.64,557.0,.492,.492
RESULTS,3.28,386.0,.492,.492
RESULTS,6.56,179.6,.492,.492
RESULTS,9.84,106.3,.492,.492
RESULTS,13.12,75.11,.492,.492
RESULTS,16.4,59.7,.984,.984
RESULTS,19.68,48.4,.984,.984
RESULTS,22.96,42.1,.984,.984
RESULTS,32.8,27.9,1.312,1.312
RESULTS,49.2,18.82,1.312,1.312
RESULTS,65.6,14.93,1.312,1.312
RESULTS,98.4,10.37,1.64,1.64
RESULTS,164,6.61,1.64,1.64
RESULTS,229.6,6.09,1.64,1.64
RESULTS,328,4.71,1.64,1.64
SOIL-TYPE,MULTILAYER
HORIZONTAL
LAYER,TOP,0.,0.
LAYER,CENTRAL,0.,0.
LAYER,CENTRAL,0.,0.
LAYER,BOTTOM,0.
OPTIMIZATION
ACCURACY,0.025
ITERATIONS,500
METHODOLOGY
MARQUARDT
STEPSIZE,0.0001
ENDPROGRAM
Page A-5
Appendix A. Command Input Mode
Printout A.5 shows the input file RS_NCCR1.F05. By examining the resistivity measurement curve,
we expect that a three-layer soil model will fit the measurement curve very well provided that the
first data point is removed. This assumption is justified since the measurement was made during a
rainy day.
RESAP
OPTIONS
UNITS,BRITISH
RUN-IDENTIFICATION,NCCR1
PRINTOUT,DETAILED
MEASUREMENTS,APPARENT-RES
METHOD,WENNER
RESULTS,3.28,385.4,.492,.492
RESULTS,6.56,178.3,.492,.492
RESULTS,9.84,105.3,.492,.492
RESULTS,13.12,74.46,.492,.492
RESULTS,16.4,59.50,.984,.984
RESULTS,19.68,48.17,.984,.984
RESULTS,22.96,42.08,.984,.984
RESULTS,32.8,28.40,1.312,1.312
RESULTS,49.2,19.02,1.312,1.312
RESULTS,65.6,14.48,1.312,1.312
RESULTS,98.4,10.33,1.64,1.64
RESULTS,164,6.88,1.64,1.64
RESULTS,229.6,5.905,1.64,1.64
RESULTS,328,4.523,1.64,1.64
RESULTS,3.28,386.0,.492,.492
RESULTS,6.56,179.6,.492,.492
RESULTS,9.84,106.3,.492,.492
RESULTS,13.12,75.11,.492,.492
RESULTS,16.4,59.7,.984,.984
RESULTS,19.68,48.4,.984,.984
RESULTS,22.96,42.1,.984,.984
RESULTS,32.8,27.9,1.312,1.312
RESULTS,49.2,18.82,1.312,1.312
RESULTS,65.6,14.93,1.312,1.312
RESULTS,98.4,10.37,1.64,1.64
RESULTS,164,6.61,1.64,1.64
RESULTS,229.6,6.09,1.64,1.64
RESULTS,328,4.71,1.64,1.64
SOIL-TYPE,MULTILAYER
HORIZONTAL
LAYER,TOP,0.,0.
LAYER,CENTRAL,0.,0.
LAYER,BOTTOM,0.
OPTIMIZATION
ACCURACY,0.025
ITERATIONS,500
METHODOLOGY
MARQUARDT
STEPSIZE,0.0001
ENDPROGRAM
Page A-6
Appendix A. Command Input Mode
Printout A.6 shows the input file RS_NCC1E.F05. By examining the resistivity measurement curve,
we expect that a three-layer soil model will fit the measurement curve very well provided that the
first data point is removed. This assumption is justified since the measurement was made during a
rainy day.
RESAP
OPTIONS
UNITS,BRITISH
RUN-IDENTIFICATION,NCCR1
PRINTOUT,DETAILED
MEASUREMENTS,APPARENT-RES
METHOD,WENNER
RESULTS,3.28,385.4,.492,.492
RESULTS,6.56,178.3,.492,.492
RESULTS,9.84,105.3,.492,.492
RESULTS,13.12,74.46,.492,.492
RESULTS,16.4,59.50,.984,.984
RESULTS,19.68,48.17,.984,.984
RESULTS,22.96,42.08,.984,.984
RESULTS,32.8,28.40,1.312,1.312
RESULTS,49.2,19.02,1.312,1.312
RESULTS,65.6,14.48,1.312,1.312
RESULTS,98.4,10.33,1.64,1.64
RESULTS,164,6.88,1.64,1.64
RESULTS,229.6,5.905,1.64,1.64
RESULTS,328,4.523,1.64,1.64
RESULTS,3.28,386.0,.492,.492
RESULTS,6.56,179.6,.492,.492
RESULTS,9.84,106.3,.492,.492
RESULTS,13.12,75.11,.492,.492
RESULTS,16.4,59.7,.984,.984
RESULTS,19.68,48.4,.984,.984
RESULTS,22.96,42.1,.984,.984
RESULTS,32.8,27.9,1.312,1.312
RESULTS,49.2,18.82,1.312,1.312
RESULTS,65.6,14.93,1.312,1.312
RESULTS,98.4,10.37,1.64,1.64
RESULTS,164,6.61,1.64,1.64
RESULTS,229.6,6.09,1.64,1.64
RESULTS,328,4.71,1.64,1.64
SOIL-TYPE,MULTILAYER
HORIZONTAL
LAYER,TOP,0.,0.
LAYER,BOTTOM,0.
OPTIMIZATION
ACCURACY,0.025
ITERATIONS,500
METHODOLOGY
MARQUARDT
STEPSIZE,0.0001
ENDPROGRAM
Page A-7
Appendix A. Command Input Mode
Printout A.7 shows the required MALT input file MT_NCCR1.F05 corresponding to the initial
grounding system of NCC-SES substation. The three-layer soil model from Traverse 1 using the
Wenner method is used.
Similar files can be prepared quite easily by following the information contained in the template
shown in Figure A.2.
MALT
COMPONENTS
TEMPLATES
GRID, DETAILED, -1, 0, 0, 0, .125, 52, 11
CGRIDCOORD, -17.6423, -96.5519, .5, 22.7577, -96.5519, .5, -17.6423, 108.148, .5
SPACING, LINEAR
GROUP, , 0, 0
GROUP, , 1, 0
GROUP, , 1, 0
GROUP, , 1, 0
GROUP, , 1, 1
GROUP, , 0, 0
OPTIONS
RUN-IDENTIFI, NCCSAFETY(NCCR1)
UNITS, INCH-RADIUS
PRINTOUT, DETAILED
SYSTEM
NETWORK
MAIN-GROUND
ENERGIZATION, CURRENT, 1000
CONDUCTOR,-136,-135,1,-121,-135,1,.264, 1,,1
CONDUCTOR,-121,-135,1,-106,-135,1,.264, 1,,1
CONDUCTOR,-106,-135,1,-91,-135,1,.264, 1,,1
CONDUCTOR,-91,-135,1,-76,-135,1,.264, 1,,1
CONDUCTOR,-76,-135,1,-61,-135,1,.264, 1,,1
CONDUCTOR,-61,-135,1,-46,-135,1,.264, 1,,1
CONDUCTOR,-46,-135,1,-31,-135,1,.264, 1,,1
CONDUCTOR,-31,-135,1,-16,-135,1,.264, 1,,1
CONDUCTOR,14.677678415,105,.5,14,105.000449232,2,.4065, 1,,1
CONDUCTOR,14.677678415,90,.5,14,90.000449232,2,.4065, 1,,1
CONDUCTOR,14.677678415,75,.5,14,75.000449232,2,.4065, 1,,1
CONDUCTOR,14.677678415,60,.5,14,60.000449232,2,.4065, 1,,1
CONDUCTOR,14.677678415,45,.5,14,45.000449232,2,.4065, 1,,1
CONDUCTOR,14.677678415,30,.5,14,30.000449232,2,.4065, 1,,1
CONDUCTOR,14.677678415,15,.5,14,15.000449232,2,.4065, 1,,1
CONDUCTOR,14.677678415,1.1655884773E-14,.5,14,.000449231999992,2,.4065, 1,,1
CONDUCTOR,14.677678415,-15,.5,14,-14.999550768,2,.4065, 1,,1
CONDUCTOR,14.677678415,-30,.5,14,-29.999550768,2,.4065, 1,,1
CONDUCTOR,14.677678415,-45,.5,14,-44.999550768,2,.4065, 1,,1
CONDUCTOR,14.677678415,-60,.5,14,-59.999550768,2,.4065, 1,,1
CONDUCTOR,14.677678415,-75,.5,14,-74.999550768,2,.4065, 1,,1
CONDUCTOR,14.677678415,-90,.5,14,-89.999550768,2,.4065, 1,,1
COMPUTATIONS
DETERMINE, ALL
ENDPROGRAM
Page A-8
Appendix A. Command Input Mode
Page A-9
Appendix A. Command Input Mode
Figure A.2 MALT Command Mode Compatible Input File Template (Contd)
Page A-10
Appendix A. Command Input Mode
Printout A.8 is the resulting HIFREQ Command mode compatible input file that is used in the fault
current distribution analysis. This file is created by using the SESCAD in Chapter 4.
HIFREQ
COMPONENTS
GROUP, , 0, 0
OPTIONS
RUN-IDENTIFI, NCCFAULT40(NCCR1)
UNITS, INCH-RADIUS
PRINTOUT, DETAILED
SYSTEM
ENERGIZATION, LEAD,120.5,-677.55,,,,,,GENNE-C1
ENERGIZATION, LEAD,287.171,-875.349,,,,,,GENNE-C2
ENERGIZATION, LEAD,513.759,-1917.36,,,,,,GENSE-C1
ENERGIZATION, LEAD,433.931,-1879.56,,,,,,GENSE-C2
ENERGIZATION, LEAD,199.619,-614.38,,,,,,GENSW-C1
ENERGIZATION, LEAD,158.14,-590.18,,,,,,GENSW-C2
ENERGIZATION, LEAD,58.7399,-558.92,,,,,,GENNW-C1
ENERGIZATION, LEAD,725.923,-3144.29,,,,,,GENNW-C2
ENERGIZATION, GPR-POTENTIAL,0,0,,,,,,Zero GPR
CHARACTERISTICS
CONDUCTOR-TYPE,DEFAULT,1,1,0,0,0,0,0,0,Default Conductor
CONDUCTOR-TYPE,User-Defined,2.83773,.246407,0,0,0,0,0,0,7No.8 Alumoweld
CONDUCTOR-TYPE,Computed,1,1,0,0,13.47,0,0,0,NCC-SES GIS
CONDUCTOR-TYPE,Computed,1,1,0,0,40,0,0,0,Tower 40 ohms
CONDUCTOR-TYPE,Computed,1,1,0,0,0.5,0,0,0,Terminal 0.5 ohm
NETWORK
MAIN-GROUND
CONDUCTOR,-1, 1, 0, 0,38.0512797534,34.0932560653,-148.67,68570.1500026,39601.0932682,-148.67,.1925, 1,103
CONDUCTOR,-1, 1, 0, 0,48.5512746515,15.9067196403,-148.67,68580.6499974,39582.9067318,-148.67,.1925, 1,103
CONDUCTOR,-1, 0, 0, 0,34.551281454,40.1554348736,-90.33,68566.6500043,39607.155447,-90.33,.264, 1,103
CONDUCTOR,-1, 0, 0, 0,52.0512729509,9.84454083191,-90.33,68584.1499957,39576.844553,-90.33,.264, 1,103 .
Page A-11
Appendix A. Command Input Mode
Printout A.9 is the resulting HIFREQ Command mode compatible input file that describes the initial
NCC-SES GIS grounding system with the complete GIS bus works modeled.
HIFREQ
COMPONENTS
GROUP, , 0, 0
GROUP, , 1, 0
GROUP, , 2, 0
OPTIONS
RUN-IDENTIFI, NCCR1-GIS
UNITS, INCH-RADIUS
PRINTOUT, DETAILED
SYSTEM
TOLERANCE,0.001,1.,0.005,0.00005,0.001,0.,0.,0.,0.5
ENERGIZATION, LEAD,84.9816,808.546,,,,,,GENNE-SES
ENERGIZATION, LEAD,55.3714,-1056.55,,,,,,GENSE-SES
ENERGIZATION, LEAD,110.292,898.254,,,,,,GENSW-SES
ENERGIZATION, LEAD,-40.8324,-1169.29,,,,,,GENNW-SES
CHARACTERISTICS
CONDUCTOR-TYPE,Computed,1,1,0,,0,0,0,0,Cu-500kcmil-0.4065in
CONDUCTOR-TYPE,Computed,1,1,0,,0,0,0,0,Cu-4/0-0.264in
CONDUCTOR-TYPE,Computed,1,1,0,,0,0,0,0,Cu-Rod-10L-3/4R
CONDUCTOR-TYPE,Computed,12.1,250,0,,0,0,0,0,Rebar Wire
CONDUCTOR-TYPE,Computed,2.28489,.927289,0,,0,0,0,0,1590ACSR
CONDUCTOR-TYPE,Computed,2.23759,.957659,0,,0,0,0,0,2167ACSR
CABLE-TYPE, Enclosure24inch
COMPONENT, CORE, .5
METAL,1,1,0,,,,,,
INSULATION, 999999,0.875,,,
COMPONENT, SHEATH, 12
METAL,10,300,11,,,,,,
INSULATION, ,,,,
CABLE-TYPE, Enclosure14inch
COMPONENT, CORE, .5
METAL,1,1,0,,,,,,
INSULATION, 999999,0.458333,,,
COMPONENT, SHEATH, 7
METAL,10,300,6,,,,,,
INSULATION, ,,,,
SUBDIVISION,YES,
NETWORK
MAIN-GROUND
CONDUCTOR,-1, 0, 0, 0,-6.45011044727,98.0600740844,-18.211,-6.45011044727,98.0600740844,-9.875,.375, 1,16, 0, 2
CONDUCTOR,-1, 0, 0, 0,-3.49711044727,96.0548740844,-18.211,-3.49711044727,96.0548740844,-9.875,.375, 1,16, 0, 2
CONDUCTOR,-1, 0, 0, 0,-9.40311044727,100.065274084,-18.211,-9.40311044727,100.065274084,-9.875,.375, 1,16, 0, 2
Page A-12
Appendix A. Command Input Mode
Printout A.10 is the resulting MALT Command mode compatible input file that describes the
reinforced NCC-SES GIS grounding system. This file is created by using the SESCAD in Chapter 7.
MALT
COMPONENTS
TEMPLATES
GRID, DETAILED, -1, 0, 0, 0, .125, 52, 11
CGRIDCOORD, -17.6423, -96.5519, .5, 22.7577, -96.5519, .5, -17.6423, 108.148, .5
SPACING, LINEAR
GROUP, , 0, 0
GROUP, , 1, 0
GROUP, , 1, 0
GROUP, , 1, 0
GROUP, , 1, 1
GROUP, , 0, 0
OPTIONS
RUN-IDENTIFI, NCCSAFETY(NCCR1)
UNITS, INCH-RADIUS
PRINTOUT, DETAILED
SYSTEM
NETWORK
MAIN-GROUND
ENERGIZATION, CURRENT, 1000
CONDUCTOR,-136,-135,1,-121,-135,1,.264, 1,,1
CONDUCTOR,-121,-135,1,-106,-135,1,.264, 1,,1
CONDUCTOR,-136,-135,1,-136,-135,11,.375, 1,,1
CONDUCTOR,119,-135,1,119,-135,11,.375, 1,,1
CONDUCTOR,119,135,1,119,135,11,.375, 1,,1
COMPUTATIONS
DETERMINE, ALL
SOIL-TYPE,MULTILAYER
HORIZONTAL
LAYER,TOP,2552.23,4.36532
LAYER,CENTRAL,1742.39,116.99
LAYER,BOTTOM,4027.2
ENDPROGRAM
Page A-13
Appendix A. Command Input Mode
Printout A.11 is the resulting HIFREQ Command mode compatible input file that describes the
reinforced NCC-SES GIS grounding system with the complete GIS bus works modeled. This file is
created by using the SESCAD in Chapter 7.
HIFREQ
COMPONENTS
GROUP, , 0, 0
GROUP, , 1, 0
GROUP, , 2, 0
OPTIONS
RUN-IDENTIFI, NCCR1-GIS_Mit01
UNITS, INCH-RADIUS
PRINTOUT, DETAILED
SYSTEM
TOLERANCE,0.001,1.,0.005,0.00005,0.001,0.,0.,0.,0.5
ENERGIZATION, LEAD,84.9816,808.546,,,,,,GENNE-SES
ENERGIZATION, LEAD,55.3714,-1056.55,,,,,,GENSE-SES
ENERGIZATION, LEAD,110.292,898.254,,,,,,GENSW-SES
ENERGIZATION, LEAD,-40.8324,-1169.29,,,,,,GENNW-SES
CHARACTERISTICS
CONDUCTOR-TYPE,Computed,1,1,0,,0,0,0,0,Cu-500kcmil-0.4065in
CONDUCTOR-TYPE,Computed,1,1,0,,0,0,0,0,Cu-4/0-0.264in
CONDUCTOR-TYPE,Computed,1,1,0,,0,0,0,0,Cu-Rod-10L-3/4R
CONDUCTOR-TYPE,Computed,12.1,250,0,,0,0,0,0,Rebar Wire
CONDUCTOR-TYPE,Computed,2.28489,.927289,0,,0,0,0,0,1590ACSR
CONDUCTOR-TYPE,Computed,2.23759,.957659,0,,0,0,0,0,2167ACSR
CABLE-TYPE, Enclosure24inch
COMPONENT, CORE, .5
METAL,1,1,0,,,,,,
INSULATION, 999999,0.875,,,
COMPONENT, SHEATH, 12
METAL,10,300,11,,,,,,
INSULATION, ,,,,
CABLE-TYPE, Enclosure14inch
COMPONENT, CORE, .5
METAL,1,1,0,,,,,,
INSULATION, 999999,0.458333,,,
COMPONENT, SHEATH, 7
METAL,10,300,6,,,,,,
INSULATION, ,,,,
SUBDIVISION,YES,
NETWORK
MAIN-GROUND
CONDUCTOR,-1, 0, 0, 0,-6.45011044727,98.0600740844,-18.211,-6.45011044727,98.0600740844,-9.875,.375, 1,16, 0, 2
CONDUCTOR,-1, 0, 0, 0,-3.49711044727,96.0548740844,-18.211,-3.49711044727,96.0548740844,-9.875,.375, 1,16, 0, 2
CONDUCTOR,-1, 0, 0, 0,-9.40311044727,100.065274084,-18.211,-9.40311044727,100.065274084,-9.875,.375, 1,16, 0, 2
Page A-14
Appendix B. Obtain Internal Impedances from SESConductorDatabase Tool
APPENDIX B
USE SESCONDUCTORDATABASE TOOL TO
OBTAIN INTERNAL IMPEDANCES
In HIFREQ, in order to model a stranded conductor, such as 7No.8 Alumoweld, we will need to
obtain its internal impedance first. This value is obtained by using the SESConductorDatabase
Tool.
Start the SESConductorDatabase from the Tools menu in the CDEGS screen.
Page B-1
Appendix B. Obtain Internal Impedances from SESConductorDatabase Tool
Click on the View button, you will see the following screen which lists the Internal Impedance for
7No.8 Alumoweld. Make sure to use the correct units when defining conductor types in HIFREQ.
Page B-2
Notes
NOTES