12-8 PSYCHROMETRY, EVAPORATIVE COOLING, AND SOLIDS DRYING

In the past, psychrometric charts have been used to perform quite qa = heat added to system, Btu/lb dry air
precise calculations. To do this, additive corrections are often required qr = heat removed from system, Btu/lb dry air
for enthalpy of added water or ice, and for variations in barometric pres-
sure from the standard level (101,325 Pa, 14.696 lbf/in2, 760 mmHg, Subscripts 1, 2, 3, etc., indicate entering and subsequent states.
29.921 inHg). It is preferable to use formulas, which give an accurate fig-
ure at any set of conditions. Psychrometric charts and tables can be used Example 1: Determination of Moist Air Properties Find the prop-
erties of moist air when the dry-bulb temperature is 80F and the wet-bulb tem-
as a rough cross-check that the result has been calculated correctly. Table perature is 67F.
12-4 gives values of saturation humidity, specific volume, enthalpy, and Solution: Read directly from Fig. 12-2a (Fig. 12-6a shows the solution dia-
entropy of saturated moist air at selected conditions. Below the freezing grammatically).
point, these become virtually identical to the values for dry air, as satura-
tion humidity is very low. For pressure corrections, an altitude increase of Moisture content H = 78 gr/lb dry air
approximately 900 ft gives a pressure decrease of 1 inHg (0.034 bar). For = 0.011 lb water/lb dry air
a recorded wet-bulb temperature of 50F (10C), this gives an increase Enthalpy at saturation h = 31.6 Btu/lb dry air
in humidity of 1.9 gr/lb (0.00027 kg/kg) and the enthalpy increases by Enthalpy deviation D = 0.1 Btu/lb dry air
0.29 Btu/lb (0.68 kJ/kg). This correction increases roughly proportion-
True enthalpy h = 31.5 Btu/lb dry air
ately for further changes in pressure, but climbs sharply as wet-bulb tem-
perature is increased; when Twb reaches 100F (38C), Y = 11.2 gr/lb Specific volume v = 13.8 ft3/lb dry air
(0.0016 kg/kg) and H = 1.77 Btu/lb (4.12 kJ/kg). Equivalent, more Relative humidity = 51 percent
detailed tables in SI units can be found in the ASHRAE Handbook. Dew point td = 60.3F
Examples Illustrating Use of Psychrometric Charts In these
examples the following nomenclature is used: Example 2: Air Heating Air is heated by a steam coil from 30F dry-bulb
temperature and 80 percent relative humidity to 75F dry-bulb temperature. Find
t = dry-bulb temperatures, F the relative humidity, wet-bulb temperature, and dew point of the heated air.
tw = wet-bulb temperature, F Determine the quantity of heat added per pound of dry air.
td = dewpoint temperature, F Solution: Reading directly from the psychrometric chart (Fig. 12-2a),
H = moisture content, lb water/lb dry air Relative humidity = 15 percent
H = moisture added to or rejected from the airstream, Wet-bulb temperature = 51.5F
lb water/lb dry air Dew point = 25.2F
h = enthalpy at saturation, Btu/lb dry air
D = enthalpy deviation, Btu/lb dry air The enthalpy of the inlet air is obtained from Fig. 12-2a as h1 = h1 + D1 =
h = h + D = true enthalpy, Btu/lb dry air 10.1 + 0.06 = 10.16 Btu/lb dry air; at the exit, h2 = h2 + D2 = 21.1 0.1 = 21 Btu/lb
hw = enthalpy of water added to or rejected from system, Btu/lb dry air. The heat added equals the enthalpy difference, or
dry air qa = h = h2 h1 = 21 10.16 = 10.84 Btu/lb dry air

FIG. 12-2a Grosvenor psychrometric chart (medium temperature) for the air-water system at standard atmospheric pressure, 29.92 inHg,
U.S. Customary units. (Courtesy Carrier Corporation.)