SUB: Revised final offer for EDTA Cleaning Boiler, Detergent flushing of feed
& Condensate system and Pickling and passivation of main Steam & Re-heater
pipelines at 1 x 150 MW Unit-Reg.

REF: MOM dated 05.09.2012.

**********
With reference to the telecom had with Mr. Hanumantha Rao today on the above
subject, we are pleased to submit the revised offer for chemical cleaning of
boiler with EDTA method, detergent flushing of feed & condensate system and
pickling and passivation of main Steam & Re-heater pipelines at 1 x 150 MW units
at polancha.

ANNEXURE I: TECHNICAL SPECIFICATION


ANNEXURE I: SCOPE OF WORKS OF ARUCHEM & NBEIL
ANNEXURE II: PRICE SCHEDULE WITH TERMS & CONDITIONS

We hope our offer is in line with your requirement and look forward to hearing
from you. If you have any clarifications please feel free to contact us.

Thanking you and assuring you of our best services at all times.

Yours faithfully,

For ARUCHEM,

S. THIRUMALAI
Sr. Manager- Projects.
Mob.098401 74989
ARUCHEM
79 VALMIKI STREET, THIRUVANMIYUR, CHENNAI 600 041.
PHONE: 91- 44 24453425,24901623, 24430697 FAX:91- 44 - 24424755
E-mail: arudra@eth.net
-------------------------------------------------------------------------------------------------------------
ANNEXXURE-I
TECHNICAL SPECIFICATION FOR EDTA CHEMICAL CLEANING

1. OBJECTIVE

The objective of this procedure is to chemically clean and passivate the


internal surfaces of the steam generating portion (water touched surfaces)
and heating surfaces (Economizer) using specified chemicals employing a
single step process. This will render the above mentioned surfaces free of mill
scale, and other deposits and form uniform & smooth protective layer of
magnetite. With this protective layer, the generating surfaces are rendered
passive to generate adequate negative potential under the operating pH to
resist corrosion.

2. PROPOSAL

The objectives are achieved by carrying out the following proposals, by carrying
out two Hot water flushing, generally loose rust, debris, deposits and
other materials left in the Boiler are removed.

Then, it is subjected to acid cleaning for the removal of inconsistent mill


scale and adherent rust. The acid pickled surface is passivated for the
formation of uniform and adherent magnetite layer. Both chemical cleaning
and passivation process are completed in a single step.

3. EQUIPMENT AND SERVICE REQUIRED

Prior to the commencement of chemical cleaning, all the demineralised water


storage tanks should be kept full and the demineralising units kept in
regenerated condition. Approximately, 1000 m3 of demineralised water will be
consumed for the entire process. At any time of acid cleaning, a minimum of
two boiler volumes (app. 300 Cu.m.) of demineralised water should be available
in ready stock to facilitate rapid flushing of the system in the event of
chemistry upset.

All the required quantities of chemicals as given should be made available


prior to the commencement of the process.
Temporary drum water level gauge glass and (Tel-tale lamp indication)
at control room and low point drain area
Power Supply to be available
ARUCHEM
79 VALMIKI STREET, THIRUVANMIYUR, CHENNAI 600 041.
PHONE: 91- 44 24453425,24901623, 24430697 FAX:91- 44 - 24424755
E-mail: arudra@eth.net
-------------------------------------------------------------------------------------------------------------
220 AC/DC, 110V AC control supply to be available.
Instrument/Service air to be made available.
Chemist/Express lab to be made available for testing during the process.
Flood lights / telephones / walkie-talkie are available.
For effluent treatment, compressed air facility and suitable perforated
Carbon Steel / polythene tubing arrangement shall be made available

4. CHEMICALS;
SR. CHEMICALS SPECIFICATION
NO
01 Trisodium Phosphate 98%
02 Di sodium Phosphate 99%
03 Tetra Ammonium EDTA (40 %Liquid-Straw Yellow 40 %
Active /pH 9.0~ 9.8/ Specific gravity 1.6 ~ 1.19)
04 EDTA Inhibitor Coronil- MAX & Coronil- SOL As required
05 Hydrazine Hydrate 80 %
06 Ammonia 25%

5. PROCESS METHOD:

Note: REFRACTORY DRYOUT & ALKALI FLUSHING:

During refractory dry out alkali flushing process shall be carried out using with
Tri sodium phosphate 2000 ppm & Di sodium phosphate 1000 ppm at the
elevated temperature as per dry out process. The periodical sample will be
collected and check alkalinity, phosphate at regular intervals.

After completion of dry out process the entire system will be flushed with cold
DM water till drain water pH neutral.

5.1 HOT WATER RINSE:


Start filling the boiler with demineralised water.
Light up the boiler as per O&M instructions and gradually raise the boiler
water temp. to 130-140 oc. Trip the boiler and keep the fans running
for cooling. In case if is combined with refractory dry out the process
control to be made accordingly.
ARUCHEM
79 VALMIKI STREET, THIRUVANMIYUR, CHENNAI 600 041.
PHONE: 91- 44 24453425,24901623, 24430697 FAX:91- 44 - 24424755
E-mail: arudra@eth.net
-------------------------------------------------------------------------------------------------------------
When the boiler water temperature comes down to 95 deg.C, drain
the boiler in the hot condition to the plants water disposal system, by
keeping open the drain valves fully(without throttling)
Flush all sampling and blow down lines. Check all temperature /
pressure measurements relevant to the process for monitoring at Unit
Control board (UCB) and ensure their reliability.

5.2 LIGHTING UP
Drum air vents SH air vents & start up Vents is to be opened before
lighting up the boiler.
Initiate boiler light up as per O & M instructions.
Drum level is to be monitored closely and controlled below normal
level by operating down comer blow down from UCB or draining and
filling the boiler at drain header. Drum level Temporary indication
shall be displayed at UCB and near drain header.

5.3 ACID CLEANING & PASSIVATION.


In this process the mixture of chemical solutions containing EDTA,
inhibitor, ammonia and hydrazine in DM water is filled in the boiler.
Boiler is fired and the temperature raised to 140 deg C and
subsequently cooled. The removal of deposit constituents and
subsequent passivation of the metal surfaces will occur during this single
step.
Keep ready the required quantity of ammoniated EDTA (40 % wt/wt)
solution in the EDTA storage tank.
Keep ready the inhibitor and the required quantity of hydrazine
hydrate for making addition into the chemical dilution tank.
Keep all the boiler blow down valves shut and drum vent valves & start
up vent open during boiler filling.
Prepare the EDTA solution in mixing tank batch by batch by filling
DM water, EDTA, Inhibitors, Ammonia and hydrazine and ensure the
concentration of solution for EDTA 3 %, Hydrazine 1000 ppm &
ammonia PH 9.0 to 9.5
Fill the boiler up to +50 mm from the normal working level in the drum.
Light up the boiler as per normal operating procedure with minimum
Firing rate.
ARUCHEM
79 VALMIKI STREET, THIRUVANMIYUR, CHENNAI 600 041.
PHONE: 91- 44 24453425,24901623, 24430697 FAX:91- 44 - 24424755
E-mail: arudra@eth.net
-------------------------------------------------------------------------------------------------------------
The drum and super heater vents are to be closed when steaming Starts,
say at 3.7 kg / sq.cm in the drum and keep open the SH start up Vent.
Keep main steam pipe drain valve in opened condition.
Note the time at which the temperature of boiler water reaches110 deg.
C
Continue raising the temperature of boiler water to a saturation
temperature of 140 deg C.
once the temperature of boiler water reaches 140 deg.C, control the
firing rate in such a way that the boiler water temperature is
maintained at 135 to 140 deg.C, for a period of 4 ~ 6 hours (max).Then
trip the boiler.
Check every hourly the water samples EDTA, total Iron and pH.
After completion of pickling process, the system shall be allowed to cool
with the ID & FD fans in operation. Open the drum air vents when the
pressure reaches to 1 kg / sq.cm.
When the temperature comes down to 95 deg C, the system shall be
drained completely in hot condition to the effluent pit by opening all
drain valves.

5.4. SAMPLING & TESTING.


Samples have to be taken every 30 minutes from the sampling points at
locations given as per 2.7. From the time when the temperature in the
system has reached 110 0C and analyzed for pH, EDTA concentration and
Iron content. Boiler water temperature & Water Wall Metal temperature
at the locations indicated as per 2.3. are to be measured and logged.

5.5. PROCESS COMPLETION:


Cleaning process is to be continued till iron concentration in three
consecutive samples show equilibrium status. When the iron concentration in
the cleaning solution is constant, it indicates that all the oxides have been
dissolved. However, a minimum EDTA contact period of 4 hours from the
time of attaining temperature 140 deg C is required. Pickling process is
completed when the EDTA strength and iron concentration level out and
reach equilibrium.If the iron concentration values do not level out and
attain equilibrium status, the EDTA contact period with temperature
exceeding 1100C shall not be allowed for more than 8 hours, regardless of
analytical results.
ARUCHEM
79 VALMIKI STREET, THIRUVANMIYUR, CHENNAI 600 041.
PHONE: 91- 44 24453425,24901623, 24430697 FAX:91- 44 - 24424755
E-mail: arudra@eth.net
-------------------------------------------------------------------------------------------------------------
5.6. TREATED DM WATER RINSING:
Prepare a blended solution of ammonia & Hydrazine with
calculated quantities in the dissolving tank in order to achieve a
solution pH 9.0 to 9 and hydrazine content 50 ppm in the DM water being
filled in the boiler.
Fill the boiler with the above treated DM water through low point
drains and economizer as practiced earlier, up to just above the
temporary centre gauge glass.
Light up the boiler as per O&M Instruction
Raise boiler water temperature up to 110 deg .C and then shutdown the
boiler. Allow the boiler to cool down naturally. When the boiler water
temperature comes down to 95 deg C. drain the boiler in hot condition to
plant drains and allows the system for natural aeration
Open the drum for inspection. Manually clean the drums if required.
Restore the boiler and prepare it for regular operation for steam
blowing, safety valve floating etc.

5.7. COMPLETION CRITERIA:


The test coupons placed at identified locations will be taken out. All
coupons shall be free of deposits and have uniform coating of the
protective layer. The drum surface shall be visually inspected for uniform
smooth coating of protective layer.
The water wall drain headers will be inspected and loose debris if any,
will be removed.
5.8 CHEMICAL CLEANING WASTE TREATMENT & DISPOSAL
Cold & Hot DM water flushing and treated DM water rinsing shall be drained
into plant normal drain. The organic spent EDTA chemical solution after the
cleaning process is drained into a drain Pit. Perforated headers will be laid
in the floor of the pit to enable well distributed air bubbling. The pH of the
effluent at the time of dumping will be between 9.5 to 10.0. Air bubbling
will be started immediately after the completion of draining and will be
continued for a week. The pH of the effluent will stabilize in the range of
8.5 to 9.0 and hence no further treatment for pH adjustment is required
as it would meet the pH requirement for disposal.EDTA storage tank,
pipelines and inhibitor carboys shall be cleaned with water and the rinsing
shall be put into the pit.
ARUCHEM
79 VALMIKI STREET, THIRUVANMIYUR, CHENNAI 600 041.
PHONE: 91- 44 24453425,24901623, 24430697 FAX:91- 44 - 24424755
E-mail: arudra@eth.net
-------------------------------------------------------------------------------------------------------------
*************************
2. FEED & CONDENSATE SYSTEM CLEANING:
1. PURPOSE:

The object of chemical cleaning of carbon steel piping is to remove the loose
rust, dislodging the burs, loose welding slag and loose mucks adhering to the
internal surface of the pipeline. This procedure specifies the method of
cleaning of internal surface of carbon steel piping based on using of alkaline
based chemicals. This cleaning will enable removal of:-
Paint or varnish if used for protective purposes.
Grease or Oil
Loose mill Scales.
Loose rust.

2. DM WATER FLUSHING:
The temporary circuit consisting of blending tank, circulating pumps, valves and
piping is fabricated as per the drawing. The complete circuit is tested for any
leakage. DM Water is filled up and the system is flushed till the water is clear by
visual observation. If the water is clear and quality is good the same can be used
for Alkali flushing with out draining.

3. DETERGENT FLUSHING:
Fill up the system, establish circulation. The process chemicals may be added in
the following concentration in the mixing tank.

Coronil 100 (Degreasing Chemicals) - 1000 PPM

Chemicals must be mixed little by little observing the foaming in the mixing
tank. The samples are taken out from inlet and outlet at regular intervals. The
same samples are analyzed for alkalinity, Phosphate & pH value. After getting
the steady values at inlet and outlet, then drain the complete system.

4. DM WATER RINSING:
Fill up the system with DM water and establish circulation in the system. Rinse
the system by continuous filling and draining method. The rinsing is continued
till the pH shall be checked I/L & O/L shall be same. The flushing is terminated
once the water is clear and free from alkaline solution for visual appearance.
*******************
ARUCHEM
79 VALMIKI STREET, THIRUVANMIYUR, CHENNAI 600 041.
PHONE: 91- 44 24453425,24901623, 24430697 FAX:91- 44 - 24424755
E-mail: arudra@eth.net
-------------------------------------------------------------------------------------------------------------

3. CHEMICAL CLEANING OF MAIN STEAM /HRH & CRH PIPELINES;

1. PURPOSE:

The object of chemical cleaning of carbon steel/ alloy steel piping is to remove
the loose rust, dislodging the burs, welding slag and mill scales adhering to the
internal surface of the pipeline. This procedure specifies the method of
cleaning and passivation of internal surface of carbon steel piping based on use
of inhibited hydroflouric acid mixture followed by passivation with hydrogen
peroxide/nitrite based chemicals. This cleaning will enable removal of:-

Paint or varnish if used for protective purposes.


Grease or Oil
Mill Scales.
Loose rust.
Welding Slag.

2. PREPARATION WORKS:

The cleaning may be carried out by circulating the specified solutions in the
specified sequence and conditions. Temporary piping and a pump of appropriate
capacity suitable for chemical cleaning may be used for this purpose as part of
the circuit. All necessary temporary piping, fittings, flanges, pumps, tanks,
gaskets, valves, spares, lab facilities with all accessories required for conducting
test during cleaning operation, chemicals and safety accessories for operation
personnel etc shall be made available at site prior to chemical cleaning.

3. SEQUENCE OF PROCESS:

The sequence of cleaning process shall be as follows:-

Leak Test
Cold water flushing
Detergent flushing/Degreasing
Inhibited acid cleaning.
Rinse and Passivation.
ARUCHEM
79 VALMIKI STREET, THIRUVANMIYUR, CHENNAI 600 041.
PHONE: 91- 44 24453425,24901623, 24430697 FAX:91- 44 - 24424755
E-mail: arudra@eth.net
-------------------------------------------------------------------------------------------------------------
3.1. LEAK TEST:
The temporary circuit consisting of blending tank, circulating pumps, valves and
piping is fabricated as per the drawing after forming the cleaning circuit, the
system is filled with DM water and circulates for 1 hour. Check the leak at all
points. If so, arrest it properly.
3.2. COLD WATER FLUSHING:

Fill the system with DM Water and flush till clarity is achieved. Check the
turbidity at regular intervals..

3.3. DETERGENT FLUSHING /DEGREASING:

This step is important as we would be rendering the inner surface from


hydrophobic to hydrophilic, which is an important requirement to render the
acid cleaning operation more effective and less time consuming. Fill the system
with DM water and recalculation established. Add alkaline solutions Trisodium
phosphate 0.50%, NaOH 0.3% & Wetting agent 0.05% (or) Coronil 100 .1% of the
total volume of the system. Monitor the alkalinity and pH. After achieving the
steady values drain the system

3.4. DM WATER RINSE:

The system is filled up with DM water and circulated for one hour. During this
rinsing time, samples are checked for pH. This rinsing operation is continued till
the value pH nearer to that of DM water.

3.5. INHIBITED ACID PICKLING:


After DM water rinse, the system is filled up with DM water and recirculation
established. Once the steady conditions are achieved throughout the system,
add Inhibitor Coronil 240 (0.2%) followed by gradual addition of 1% of
hydrofluoric acid mixture. During process monitor total iron, strength of Acid in
the inlet and outlet sampling points at regular intervals. Circulation is continued
for maximum period of 2 hours and till getting steady values of Iron & acid.
Drain the whole solution from the system. The drained acid solution is
neutralized using lime and then discharged to the drains.

3.6.DM WATER RINSE:

The System is filled up with DM water and circulated for one hour. During this
rinsing time, samples are checked for pH and iron. This rinsing operation is
continued till the iron value drops below 50 ppm and pH nearer to that of DM
water.
ARUCHEM
79 VALMIKI STREET, THIRUVANMIYUR, CHENNAI 600 041.
PHONE: 91- 44 24453425,24901623, 24430697 FAX:91- 44 - 24424755
E-mail: arudra@eth.net
-------------------------------------------------------------------------------------------------------------

3.7. CITRIC ACID RINSE & PASSIVATION:

The Pickled surface can be easily passivated using passivating agent either
hydrogen peroxide or nitrite based chemicals. The aim is to form a coherent,
adhesive, non porous, thin layer of gamaferric oxide. The layer is formed under
expansion and hence is passive and protective.

Now fill the system with DM water and establish circulation. Add ammoniated
citric acid to have 0.5% and circulate 1 2 hours with pH of about 3.5 4.0.
Then increase the pH to 9 9.5 by addition of Ammonia further to add o.5% of
passivating chemicals. This solution will be circulated for 4-6 hrs, then drain the
solution under atmospheric condition.

UTILITY REQUIREMENT

DM Water: 2000 2250 M3 (for all system cleaning)

Electrical Power 200 KW

Fuel for EDTA Cleaning: Approx 50 KL (Based on our experience in other projects)

Neutralization Pit: 500 M3

Area Requirement: 10 M X 10 M

++++++++++++++++++++++++++++++
ARUCHEM
79 VALMIKI STREET, THIRUVANMIYUR, CHENNAI 600 041.
PHONE: 91- 44 24453425,24901623, 24430697 FAX:91- 44 - 24424755
E-mail: arudra@eth.net
-------------------------------------------------------------------------------------------------------------
LIST OF EOUIPMENTS

Sr.No DESCRIPTION OF ITEM QTY


01 Chemical Mixing Tank (20 M3) 1 No
02 Motor Pump Technical Spec- 150 HP /2900 RPM/150 M3 2 Set
/hr at 8 Kg/CM2 )
03 MCC Panel 2 Set
04 C.S. Valves 150 Class With Flange

8 Inch As required
6 Inch As required
4 Inch As required
3 Inch As required
2 Inch As required
1 Inch As required
8 Inch NRV As required
4 Inch NRV As required
05 M.S. ERW PIPES

8 Inch As required
6 Inch As required
4 Inch As required
3 Inch As required
2 Inch As required
1 Inch As required
06 Nitrogen Manifold 1 Set

07 Pressure Gauges 0-20 kg/cm2 6 Nos

08 Temperature Gauges 0- 100 0C 3 Nos

09 Compound gauges 1 214 1 Set

10 Pipe fittings Elbows/Reducers As required


11 Tools Box with tools As required
12 Express Laboratory 1 Set
ARUCHEM
79 VALMIKI STREET, THIRUVANMIYUR, CHENNAI 600 041.
PHONE: 91- 44 24453425,24901623, 24430697 FAX:91- 44 - 24424755
E-mail: arudra@eth.net
-------------------------------------------------------------------------------------------------------------
ANNEXURE-II- SCOPE OF WORKS
SCOPE OF WORKS OF ARUCHEM & NBEIL
Sr.N DESCRIPTION ARUCHEM NBEIL
o
1. Mobilization of Motor Pumps for Circulation, X
Mixing Tank, Valves, Pipes, Plates, MCC Panels,
Tools & Tackles etc
2. Required No. of Experienced Technical persons, X
Skilled and Semi skilled Workers
3. Supply of all Cleaning Process chemicals required X
for the process except boiler alkali flushing
chemicals.( TSP & DSP)
4. Providing experienced chemist for chemical X
analysis
5. Supervision & Execution of the job with X
experienced Engineers.
6. Conveyance, Boarding & Lodging for our crew. X

7. Setting up Express laboratory. X


8. Transportation of materials (To & Fro) X
9. Loading / Unloading and Shifting of materials X
10. Round the clock operation on shift basis. X
11. Engineering study and submission of X
documentation
12. Test certificate for chemicals with MSDS X

13. Internal electrical cable for Motor pumps X

14. Chemicals Handling and storage X


15. Quality assurance and control, safety, site X
management and coordination.
16 Temporary fabrication and erection of chemical X
cleaning pipelines, valves and spools.
Page Contd-2
ARUCHEM
79 VALMIKI STREET, THIRUVANMIYUR, CHENNAI 600 041.
PHONE: 91- 44 24453425,24901623, 24430697 FAX:91- 44 - 24424755
E-mail: arudra@eth.net
-------------------------------------------------------------------------------------------------------------
-2-

SR. DESCRIPTION ARUCHEM NBEIL


No
17 AC 3 Phase -Electric Power for our cleaning X
equipment
18. DM water & Service water X

19. Instrument/ Compressed Air X

20. Providing of one tank 20 M3 Capacity X

21. Hydra crane Facilities if required X

22. Necessary scaffolding if required. X

23. Storage area for our equipments and chemicals X


24. Road Permit if required for transportation of X
materials.
25. If required any cutting and welding of permanent
lines and removal and re-fixing of permanent
X
instruments, valves boiler/pre boiler piping.

26. Providing of temporary Neutralization pit approx X


500 M3
27. Necessary temporary civil foundation for motor X
pumps if required.
28 If required 10 /12 mm scrap plates, channels and X
angles for temporary erection works.

For ARUCHEM,

S. THIRUMALAI
Sr. Manager- Projects.
Mob.098401 74989
ARUCHEM
79 VALMIKI STREET, THIRUVANMIYUR, CHENNAI 600 041.
PHONE: 91- 44 24453425,24901623, 24430697 FAX:91- 44 - 24424755
E-mail: arudra@eth.net
-------------------------------------------------------------------------------------------------------------
ANNEXXURE-III
PRICE WITH TERMS & CONDITIONS

Chemicals Cost Break-Up:

A.BOILER EDTA CLEANING (200 M3)


Sr. CHEMICALS % to be UNIT QTY RATE/ TOTAL
No used Unit
1 EDTA 3% Kg 15000 122/- 18, 30,000/-
2 Hydrazine Hydrate 1000 ppm Kg 800 325/- 2, 60,000/-
3 Liquor Ammonia Ph 9.5 to Kg 3000 25/- 75,000/-
10.0
4 Inhibitor Coronil MAX 0.2 % Kg 400 750/- 3, 00,000/-
5 Inhibitor Coronil SOL 0.2 % Kg 400 750/- 3, 00,000/-
Sub total Rs. (A) 27, 65,000/-

B.DETERGENT FLUSHING OF FEED & CONDENSATE LINES (Max 50 M3)


1 Detergent Chemicals 0.1% Kg 60 230/- 13,800/-
Sub total Rs. (B) 13,800/-
C.PICKLING & PASSIVATION OF MAIN STEAM & RE-HEATER PIPELINES (106 M3)
Sr. CHEMICALS % to be UNIT QTY RATE/ TOTAL
No used Unit
1 Non Ionic Detergent 0.05% Kg 60 155/- 9,330/-
2 Hydrofluoric acid 1% Kg 2500 75/- 1, 87,500/-
3 Inhibitor Coronil 240 0.2% Litrs 300 550/- 1, 65,000/-
4 Citric Acid 0.5% Kg 600 77/- 46,200/-
5 Ammonia 0.5% Litrs 2500 25/- 62,500/-
6 Sodium Nitrite 0.5% Kg 600 48/- 28,800/-
7 Lime Neutralizer Kg 5000 10/- 50,000/-
Sub total Rs. (C) 5, 49,330/-
Subtotal Rs 33,28,130/-

All taxes Inclusive

Total Amount Rs. 33,28,130/-

The above price is inclusive of transportation charges F.O.R at Site


ARUCHEM
79 VALMIKI STREET, THIRUVANMIYUR, CHENNAI 600 041.
PHONE: 91- 44 24453425,24901623, 24430697 FAX:91- 44 - 24424755
E-mail: arudra@eth.net
-------------------------------------------------------------------------------------------------------------
A. Price Break-Up:
Item Description of works No Rate Total Amount
No. Of (Rs) (Rs)
Unit
1 Service charges for EDTA
Chemical cleaning of 150 MW
boiler including machinery 1 LS Rs.19,50,000/-
and manpower except
process chemicals.

2 Service Charges for


Detergent flushing of feed 1 LS Rs.3,50,000/-
and condensate system for
150 MW unit except process
chemicals.

3 Service Charges for Pickling


and passivation of Main 1 LS Rs.5,00,000/-
Steam and Re-heater
pipelines for 150 MW unit
except process chemicals.

4 Supply of chemicals for


Boiler EDTA Chemical
Cleaning, Detergent flushing 1 Lot Rs. 33,28,130/-
and Pickling and passivation (Inclusive of all
of Main steam pipe lines taxes)
including effluent
neutralization chemicals as
per list attached.

Sub Total Rs. 61,28,130/-


Service tax 12.36% (for item 1,2&3 except item 4) Extra
Rupees Sixty one lakhs twenty eight thousand one hundred and thirty only
ARUCHEM
79 VALMIKI STREET, THIRUVANMIYUR, CHENNAI 600 041.
PHONE: 91- 44 24453425,24901623, 24430697 FAX:91- 44 - 24424755
E-mail: arudra@eth.net
-------------------------------------------------------------------------------------------------------------
B. TERMS & CONDITIONS

1. Mobilisation: We need 7-10 days time for mobilize all men and materials. And
the job will be completed as per your project schedule.

2. Payment Terms:

a) For Supply of chemicals:


100 % advance along with LOI/Order
b) For cleaning Service:
30% against mobilization of men & materials.
70 % against completion of job with in 30 days.

3. Validity: Our offer is valid for the period of 15 days from the date of
submission.

4. Service tax: 12.36% will be extra to your account for item 1,2 and 3

We hope our offer is in line with your requirement and look forward to receiving
your valued order.

Thanking you and assuring you of our best quality services at all times.

Yours Sincerely,
For ARUCHEM,

S. Thirumalai,

M/s. ARUCHEM,
No 79, Valmiki Street,
Thiruvanmiyur-Chennai 600 041,
Mobile. 09840174989
Phone. 044-2490 1623/2443 0705

You might also like