SECTION A: LT PANELS
1
Supply, receiving, unloading, shifting to indoor Electrical rooms, inspection,
handling, assembly, installing in correct aligned position, making proper
connections, testing and commissioning of the following LT Panels including
alignment leveling, grouting with anchor fasteners, GI nuts and bolts and
making of all incoming and outgoing feeders with approved aluminum
engraved name plates complete as required by Project Managers/Consultant.
All materials and workmanship shall conform to latest Indian standards /
Consultants technical specifications /tender drawings and shall comply with
statutory requirements.
1.1 LT SWITCH BOARDS (As per enclosed technical specifications Ref No.-
100 & SLD Ref No.- WW - ELEC-100)
3 phase, 4wire, floor mounting free standing / Wall mounted, cubicle type, LT
switchboards.
a.
16A TP + NL,10kA, C Curve MCB in IP-52 Powder coated MS enclosure. Nos. 8
b.
25A TP + NL, 10kA, C Curve MCB in IP-52 Powder coated MS enclosure. Nos. 6
c.
20A TP + NL, 10kA, C Curve MCB in IP-52 Powder coated MS enclosure. Nos. 1
d.
32A TP + NL, 10kA, C Curve MCB in IP-52 Powder coated MS enclosure. Nos. 2
e.
40A TP + NL, 10kA, C Curve MCB in IP-52 Powder coated MS enclosure. Nos. 11
f.
63A TP + NL, 10kA, D Curve MCB in IP-52 Powder coated MS enclosure. Nos. 6
g. 125A, 415V, 3P+2NL, TM based, adjustable O/L and Fixed SC, 25kA MCCB
Nos. R0
in IP-52 Powder coated MS enclosure.
h. 63A TP + 2NL, TM based, adjustable O/L and Fixed SC, 16kA, MCCB in IP-
Nos. R0
52 Powder coated MS enclosure.
I 400A isolator in IP-52 Powder coated MS enclosure with indication( UPS input
Nos. 1
side).
SUB TOTAL
a. 3.5C x 185 Sq.mm Al. conductor, XLPE insulated, Armoured, PVC sheathed
Mtrs. 80
Cable. (A2XFY)
b. 3.5C x 150 Sq.mm Al. conductor, XLPE insulated, Armoured, PVC sheathed
Mtrs. R0
Cable. (A2XFY)
c. 3.5C x 120 Sq.mm Al. conductor, XLPE insulated, Armoured, PVC sheathed
Mtrs. R0
Cable. (A2XFY)
d.
3.5C x 95 Sq.mm Al. conductor, XLPE insulated, Armoured, PVC sheathed
Mtrs. 80
Cable. (A2XFY)
e.
3.5C x 70 Sq.mm Al. conductor, XLPE insulated, Armoured, PVC sheathed
Mtrs. 420
Cable. (A2XFY)
2.1.3
4C, 3C & 1C XLPE insulated, Cu conductor, PVC Outer sheathing Cables
j. 4 sq. MM FRLS grade MSCC wires for SRG Earthing including end
Mtrs. R0
termination.
b. 3.5C x 185 Sq.mm Al. conductor, XLPE insulated, Armoured, PVC sheathed
Set 4
Cable. (A2XFY)
c. 3.5C x 150 Sq.mm Al. conductor, XLPE insulated, Armoured, PVC sheathed
Set R0
Cable. (A2XFY)
d. 3.5C x 120 Sq.mm Al. conductor, XLPE insulated, Armoured, PVC sheathed
Set R0
Cable. (A2XFY)
e 3.5C x 95 Sq.mm Al. conductor, XLPE insulated, Armoured, PVC sheathed
Set 4
Cable. (A2XFY)
f 3.5C x 70 Sq.mm Al. conductor, XLPE insulated, Armoured, PVC sheathed
Set 10
Cable. (A2XFY)
2.2.3
4C, 3C & 1C XLPE insulated, Cu conductor, PVC Outer sheathing Cables
SUB TOTAL
Factory fabricated, cable trays made out of 2/ 1.6mm thick Pre- galvanized
sheet steel using proper jigs and fixtures, including all necessary accessories
such as bends, tees, reducers, coupler plates, fasteners etc. Cable tray
sections shall be joined by fish plates. The tray shall be supported at regular
intervals of not more than 1.5/ 2 metre using engineered punched angle
supports / high - tech threaded rods (for 300mm width trays and lesser tray
width) as per enclosed technical specification (Profab Make or equivalent).The
GI tray supports shall be suitable for metal roof with necessary clamps and
fixing accessories.
SUB TOTAL
Supply and installation of Race ways of following sizes made of 1.6 mm thick
pre galvanized sheet steel (Perforated wherever specified) with 1.2 mm thick
screwed / Push to fit type cover. The race ways shall be similar to Profab
make UT range & shall be suitable for installation in floor screed / above false
ceiling / open ceiling areas. The joining accessories shall be of same material
supplied along with race ways. Approval shall be obtained from consultants on
product sample before procurement.
5.3 CONDUITS .
a. 32Mmm dia conduit ( Ceiling ) Mtrs 1660
b. 32Mmm dia conduit ( Floor ) Mtrs 590
SUB TOTAL
1 DISTRIBUTION BOARDS
Surface mounting double door type MCB DBs conforming to the specification
and fabricated out of CRCA sheet with powder coated to RAL 7032 lockable
hinged glazed front door, cable gland plate, conduit knockouts. The DBs shall
comprise of 63A Neutral terminal block for incomer, insulated fork type phase
bus bars, independent neutral terminal bar for each phase where required,
common insulated earth terminal bar and complete with interconnecting wiring.
The IP class shall be 31 or better. The rate shall include costs of MCB /
RCCB / RCBO.
3 Nos. of din rail mounting type SPD, 1.5kV, 15kA, DP Surge protection device
for each phase incomer.
b.
6Way TPN Phase segregated DB with cable ties for cable management and
Top & Bottom removable gland plates with knockouts, suitable for TP MCB as
main incomer, DP `D' Type MCBs as phase incomer and `D' Type DP MCBs
Nos. R0
as outgoings with separate neutral bus for each phase. Common earth bus
and insulated bus bars and interconnecting wiring and incoming neutral bus
shall be rated 100A Copper.
1.2
Raw Power Distribution Board: (As per enclosed technical specification)
SUB TOTAL
Frame with wire ways shall be made out of 16SWG CRCA sheet steel and
powder coating colour shall match the colour of MCB DB's. 200mm x 200mm
wire ways / Raceway with 2mm thick screwed / press to fit cover for making
Frame for MCB DB's. Complete required including installation accessories.
SUB TOTAL
a 32A, 1 Phase 3pin IP44 Indoor type industrial interlocked plug & socket with
32A DP MCB in a single unit Similar to Mennekes make : 7213 or Approved Nos. R0
equivalent. with all fixing accessories.
c
1 no., 32A, 3 phase 5 pin,TP+NE weather proof Industrial plug and socket
with interlock switch in single unit similar to Nos. R0
Mennekes make : 5608, Legrand, Schneider or approved equivalent.(IP67)
b. Floor POPUP box for fixing the power and data points ( 2nos 6/16A UPS
socket controlled by individual 16A switches and 1no. Data outlet ). Legrand Nos. 36
Make.
SUB TOTAL
Supply, installation, testing and commissioning Power wiring from Raw power
& UPS power DBs to power sockets with 660V FRLS insulated multi strand
copper wires in conduits / Raceways including termination in sockets/ MCBs.
iv) Insulation sleeves for flexible wires as required in the workstation partitions.
6.1 GI Conduits:
a. 25mm dia GI conduit Mtrs. R0
6.2 MS Conduit:
a. 25mm dia MS conduit Mtrs. R0
SUB TOTAL
1
Lighting Distribution Board: (As per enclosed technical specification)
SUB TOTAL
a 1 tier / row 14 module MCB DB with 1 pole 14 module insulated fork bus bar,
Neutral, earth terminal block with supports (1-Phase SP outgoing Circuits).For Nos. 5
Emergency Lighting.
b 2 tier / row 28 module MCB DB with 1 pole 28 module insulated fork bus bar,
Neutral, earth terminal block with supports (1-Phase DP outgoing Circuits) for Nos. R0
Main Emergency lighting DB.
SUB TOTAL
Supply and installation of circuit wiring with 660V FRLS insulated multi
strand copper wires in already laid conduits including terminations.
a 3 Run of 1.5 Sq.mm copper FRLS wires in already laid conduits with ferrules
and pin type lugs for both the ends. Mtrs. R0
b 2 Run of 2.5 Sq.mm+ 1Run of 1.5sq.mm copper FRLS wires in already laid
Mtrs. 26250
conduits with ferrules and pin type lugs for both the ends.
SUB TOTAL
5 POINT WIRING
Supply and installation of Point Wiring for light points with 660V grade multi
strand flexible copper wires 3 run 2.5 sq. mm, 25mm dia 2mm thick FRLS
PVC conduits, PVC reinforced flexible conduits with end couplers and conduit
accessories and decorative modular type switches in zinc passivated switch
box, switches and front cover etc., complete in all respect.
k. One exhaust fan point controlled by one 6A switch and one socket near the
Set R0
exhaust fan.
l. One Wall mounted fan point controlled by one 6A switch and one socket near
Set R0
the exhaust fan.
SUB TOTAL
Supply and installation of PVC FRLS conduit having 2mm wall thickness,
Block enameled MS conduit having 1.6mm wall thickness and GI conduit
having 360gms/ sq. mt. Zinc coating (As per IS standards) with complete
conduit accessories and fixing accessories etc.
6.1 GI Conduits:
a. 25mm dia GI conduit Mtrs. R0
6.2 MS Conduit:
a. 25mm dia MS conduit Mtrs. 100
SUB TOTAL
SUB TOTAL
a
3-Phase input & 3 Phase output 10kVA Line interactive type inverter with 90
Minutes Battery Backup and Protections for Incoming and outgoing Circuits.
The batteries shall be placed in cabinet. The batteries shall be
VRLA+AGM+GEL type SMF batteries. Technical specifications approval shall
be obtained from Consultants along with offer submittals. The battery shall be
provided in 2mm thick MS powder coated rack. The inverter /batteries shall Nos. 1
comply to relevant standards/codes. The inverter design Output PF shall not
be less than 0.95PF. Inverter efficiency shall be 93% or more. The complete
equipment shall be supplied as per enclosed SLD. Make of batteries shall be
Global Yuhasa (Rocket)/ Panasonic / Exide. Minimum 2 years warranty from
date of commissioning of batteries & Inverters
SUB TOTAL
a
Supply, installation testing & commissioning of Cu Bonded electrode Earth
station as per latest IS 3043 & technical specifications complete with 3000 mm
long, 25mm outer dia Molecular Copper bonded low carbon Steel rod earth
electrode, 150mm dia bore with wire mesh, earth flat clamp & test link. The Nos.
rate shall include excavation of earth, filling with 2 bags of back fill compound
per pit. 450mm x 450mm brick masonry chamber with vehicle heavy duty
chamber covers etc.
2 GI EARTHING CONDUCTOR
Supply, laying and termination of the following sizes of earth flats and wires
laid underground at 600mm deep / on Cable trays/ drawn through pipe sleeves
along with column/ walls for safety earthing As per enclosed technical
specifications. All joints in the runs of the conductor shall be welded. All weld
joints shall be protected with bitumin paint. The equipment tape connections
shall be bolted using galvanized hardware.
j.
25x6mm GI 300mm Long Bus bar with FRP Supporting insulator with suitable
Nos. 1
size of Brass coated Bolts and Nuts and suitable size of Grip Bolts
f
25x6mm Copper 300mm Long Bus bar with FRP Supporting insulator with
Nos. 2
suitable size of Brass coated Bolts and Nuts and suitable size of Grip Bolts
SUB TOTAL
2 MISCELLANEOUS ITEMS
2.1 MS Fabrication work carried out of M.S angle, plates and flats for fixing
of cable tray/pipe sleeves, DBs, etc., duly painted complete with
necessary hardware.
a 12mm dia Anchor fasteners Nos.
b 10mm dia Anchor fasteners Nos. 147
c 8mm dia Anchor fasteners Nos. 1400
d Galvanized M8 rod Hi-tech supports Mtrs. 1120
e Galvanized M10 rod Hi-tech supports Mtrs. 117
f Galvanized M12 rod Hi-tech supports Mtrs.
g ISMC channels / angles supporting structure for raceways, cable trays &
suspended lighting etc.The cost shall be including cutting, welding, painting Kgs R0
and necessary items to complete the work. .
h
5mm Thick, 25mm W G.I slotted channel supports for ceiling raceways. The
cost including making of 'L' or 'C' type supports for ceiling suspended trays
Mtrs. 200
installations .The cost shall be including cutting, welding, painting, installation
and necessary items to complete the work.
i 2mm Thick, 40mm W G.I slotted channel for ceiling raceways. The cost
including making of 'L' or 'C' type supports for raceway installation .The cost
Mtrs. 200
shall be including cutting, welding, painting installation, and necessary items to
complete the work.
e
10mm thick, SYNTEX make Hot pressed SMC moulded Chequered Plates.
Sq. M R0
Plate to be cut to size as required and installed after removing all sharp edges.
g
Fire barriers at wall / Floor crossing with Intuemescent sealant for sealing
small & medium size penetrations with 2 hour fire rated sealant as per the site
condition - Only HILTI / 3M make intuemescent sealant shall be used. Sq. M 4
The same shall be installed by authorized agency & the installation shall have
the manufacturers Certificate.
SUB TOTAL
GENERAL CONDITIONS
Clients reserves to supply any listed items, the contractor shall install the
A
same at quoted installation price.
Clients reserves to change specification and makes of materials prior to
B
procurement by contractor.
All the execution shop drawings shall be prepared by vendor and approval
C shall be taken from Consultants/Architects/Clients before execution.
The quantities indicated cover the probable quantities of work involved. The quantities are indicated for the guidance of the bidder.
The order arising out of this enquiry will be an unit rate contract & not a lump sum one. The Owner, however, does not in any way
B guarantee that the actual work involved would correspond to the quantities indicated in the tender.
C No change in unit rate will be allowed for any change in quantity, or for any other reason whatsoever.
D The rates quoted for the "Supply" items shall be include all taxes, packing, forwarding, freight, insurance & unloading charges.
The installation charges shall be inclusive of the cost of shifting materials to the installation spot, unpacking, installation on
E foundations as specified elsewhere, supply of hardware, consumables and any minor civil works involved.
The installation rate of all LT switchboards shall include the cost of fixing bolts & nuts, painting of cable sizes, fixing of nameplates,
F danger boards, testing & commissioning.
The rate for installation of earthing grid conductors shall include the cost of welding/ riveting & brazing of the joints, protecting the
G same against corrosion at joints, drilling holes for equipment terminations, cost of lugs for earthing wires and supply of hardware.
H All testing charges for the Equipment shall be included n the installation rate of the respective equipment.
The installation rate for cables shall include shifting of cable drums, unwinding & laying as per engineering standards all labor
supervision, routine testing, supply of consumables and installation materials such as identification tags, clamps etc. However,
the cost shall exclude steel supports, installation of trays and cable termination as also the excavation, backfilling, supply of
I protective covers, sand, bricks etc. which be quoted separately under the appropriate item.
The cost of excavation, supply of sand, bricks, back filling and supply of cable markers etc shall not be included in the cost of cable laying and
J same shall be covered under appropriate headings in the BOQ
The supply rate quoted for cable termination shall include heavy duty single compression brass cable gland, crimping type heavy
duty tinned copper lugs & earth tag for gland earthing. The installation rate shall include all consumables and Labor for preparation
K of cable, glanding & crimping.
The supply price of power wiring shall include the cost of FRLS grade wires, crimping type lugs for termination, Conduit, all conduit
L accessories such as bends, junction boxes, draw boxes etc., as per the specification.
The installation rates for concealed conduits shall include the cost of chasing the walls to appropriate depth to provide 20mm cover.
Installing the conduits with clamps in the wall recess and rough plastering the surface using cement mortar of specified mix to bring
M the wall surface to the original level. The final finishing shell however be carried out by other agencies.
The installation price of wiring shall include the cost of all necessary consumable required for fixing drawing, the wires and
N terminating the same with ferrules, sleeves etc.
The installation rate of cable trays shall exclude tray supports but shall include necessary clamp/ hardware required for fixing it
O on tray supports.
The installation rate for recess mounted luminaire shall include all the above and the cost of the GI suspension chain and alignment
P of luminaries.
The cost of steel frame work & supporting structure, required for the Switchboards / bus duct/ cable tray etc., shall be quoted under
Q the heatd Supply and Installation' of supporting steel.
The point wiring rate for luminaires shall include supply of all materials starting from passivated metal switchbox, junction boxes,
switch plate, switches, conduits & accessories, wires, tags, earthing the switchbox, earthing of luminaires etc. and no extra claim will
be allowed under any circumstances. The cost of suspension conduits, flexible PVC conduits, wires as required shall be included.
The point wiring rates of *ceiling fans shall include the supply of fan hook boxes in the case of recessed wiring and hooks in the case
R of surface wiring.
Page 10
preamble
The installation price of industrial power socket outlets shall include all necessary hardware & consumables required for mounting
S it on the surface of the wall/ column or concealing the same in walls.
Installation rate for pipe sleeves/ conduits shall cover necessary chasing in the floor/ walls etc., excavation if any and backfilling
T and rough plastering if required.
U The installation cost of surface mounted luminaires shall include the following
I Assembling the luminaire and checking the same.
ii Supply & installation of anchor fastners as required for the supports.
iii Installation of luminaire using appropriate hardware.
iv Wiring connection and installation of lamps.
V Testing & commissioning.
Any item not specifically mentioned in this specification & BOQ but considered essential for satisfactory operation of the system
shall be included by the tenderer in his offer. NO EXTRA AMOUNT WHATSOEVER WILL BE PAID FOR ANY CONTINGENT
V SUPPLY OR INSTALLATION WORK.
Page 11