You are on page 1of 38

Consilium Marine AB

Salwico CS4000
Fire Detection System
Consilium Marine AB

Salwico CS4000
Analogue Addressable
Fire Detection System

Fire detection from the


worlds leading supplier
Consilium Marine AB

Salwico CS4000
Designed in accordance with
EN-54 och marine requirements

User friendly self instructing


system operation
Analogue, fully addressable

Extended redundancy

Small dimensions for flexible


installation onboard
Consilium Marine AB

CS4000 available in:


Analogue addressable versions
basic configuration of 3 loops (762
units or 512 detectors).
Prepared to be extended to any size
system distributed or centralized.
Conventional versions
with a basic configuration of 16
zones. Can be extended to any
multiple of 16 fire detection zones.
Mixed analogue/conventional
version
CS4000 is backwards compatible
with existing installations
Consilium Marine AB

Operator Panel
Certified to comply with EN-54
Graphical display window
Back lighted push buttons
Logical self instructing system operation,
service and log lists
Suggested measures at failure alarms
Intelligent MMI (Man Machine Interface)
Small dimensions for flexible installation
onboard
Redundant two-way communication
allows remote installation from central
cabinet
Consilium Marine AB

System features
The operator panel can be separated from
the central unit to further facilitate
installation.
Main cabinet size 430x500x158 mm
separate control/repeater panel
288x144x66 mm
Linux based state-of-the-art technology
Extensive interface capability (network,
VDR, paging, telephone, field bus)
Off-the-shelf solution
Start up mode one person can start up
the system
Consilium Marine AB

Interface
Alarm monitoring system
Fire doors, dampers and
sprinklers
Telephone / Paging systems
PLC systems
Ventilation and fans
VDR
Consilium Marine AB

Standard Inputs
- Outputs
9 programmable relay outputs
4 programmable inputs
Opto isolated serial interface
output, RS 232/485 NMEA or
MODBUS
Printer output
Additional inputs on several
PCBs
Consilium Marine AB

Configuration

Free configuration of
fire detection zones regardless of loop

Time saving USB or Salwico Memory


Stick connection
Consilium Marine AB

Configuration
Salwico Memory Stick

To facilitate configuration and


upgrading, the central is equipped
with an USB-port and Salwico
Memory Stick with a
configuration tool.
With these tools the customer has
the possibility to upload or
download the definition data from
the central using the USB stick as
well as changing the same with the
configuration software.
Consilium Marine AB

Loop communication

FSK - Frequency Shift Keying


modulated signal

Well proven technology

High resistance against interference

Galvanically isolated loops with


possibility to detect earth faults
on the individual loop
Consilium Marine AB

Loop features
(analogue addressable)
254 addresses per loop
Automatic detection of double addressing,
cable breaks and earth faults at loop level
Easy addressing of detectors
No special cable requirements
Up to 2.000 m loop cable
Addressable loop sounders capabilities
Backwards compatible with all existing installations
Possible to group zones independently of the physical loops

Statistics about contamination in the smoke detectors


Consilium Marine AB

Loop configuration using zones

4 12 15
2 9
ZONE 16 7
ZONE 23
ZONE 14
10 ZONE 27
5
1
13
ZONE 18 8 11 ZONE 25
3 14 16
6
ZONE 22

Loop 1 Loop 2

Loop Board LB
Consilium Marine AB

Adaptive detectors

Smoke

FIRE

PRE ALARM

FAULT

Time
Consilium Marine AB

Adaptive detectors
Alarm evaluation
Measure amount of smoke over time

Alarm level

Time

Start Alarm accepted


Consilium Marine AB

Adaptive detectors
The Cuban cigar
Smoke

No alarm from Salwico detector

100%

Clean air

Time

Standard detector
Consilium Marine AB

Adaptive detectors
Flaming plastics fire
Smoke

100%

Clean air

Time

Standard detector End of test


Salwico detector
Consilium Marine AB

Adaptive detectors
The midnight poker game
Smoke

No alarm from Salwico detector

100%

Clean air

Time

Standard detector
Consilium Marine AB

Adaptive detectors
Detector testing

Smoke

100%

Smoke gas applied

Clean air

Salwico detector, normal operation Time

Standard detector
Salwico detector, in test mode
Consilium Marine AB

Adaptive detectors
Detector contamination compensation
Calculate average clean air' value and
keep a constant gap to the alarm level.

Alarm level

Detectors
analogue value

Time
Contamination
(Fault alarm)
Consilium Marine AB

Detectors & Loop units


Complete range of analogue addressable
heat, smoke, flame, call points and accessories.
For IS areas completely addressable optical smoke,
combined heat/smoke and manual call point.
Analogue addressable flame detector (UV)
Interchangable detector heads
Both IDA and NOSE protocol detectors can be used on
the same system or even on the same loop
Back compatible with all previous Salwico analouge
addressable loop units
Consilium Marine AB

Smoke detectors

NS-AOS
Analogue addressable optical smoke detector
IP 22 or IP 55

NS-AOHS
Analogue addressable combined optical
smoke/heat detector
IP 22 or IP 55
Consilium Marine AB

Smoke
Smoke alarm

Dual alarm detector 100%

Standard detector 80%


Two alarms! Heat alarm

Prealarm
Heat

54C

Smoke Increased smoke sensitivity


Smoke/heat alarm
Combi detector
(Multi criteria) 100%
Salwico NS-AOHS 80%
/ NS-AOHS-IS
Smoke/heat alarm
ONE ALARM!

Prealarm
Heat

40C 54C 84C


Consilium Marine AB

Heat detectors
NS-AH/AIS
Analogue addressable heat detector 54 degrees
IP 22 or IP 55
Rate of rise function (10 deg C / min)

NS-AH/CS
Analogue addressable heat detector 84 degrees
IP 22 or IP 55
Rate of rise function (10 deg C / min)

SWM-1KL/C
Conventional heat detector, 57 degrees for cold stores
IP 65
Consilium Marine AB

Flame detector
NS-AUV

Analouge addressable UV flame detector

IP 22 or IP 55

Wavelength: 185-260 um
Consilium Marine AB

Manual call points


NS-ACP
Addressable manual call point
IP 22

NS-ACP-IP55
Addressable manual call point
IP 55
Available in white colour, for sprinkler release

NS-ACPWP
Addressable manual call point
IP 67
Consilium Marine AB

IS equipments, Eex ia
NS-AOS-IS
Analogue addressable optical smoke detector

NS-AOHS-IS
Analogue addressable combined heat/smoke
detector
Dual function

ACP-IS
Addressable manual call point

ISOLATOR A
Max 20 addressable IS units on each isolator
Max 5 isolators on each loop
Does not require separate 24 VDC
Consilium Marine AB

Some accessories
NS-AIN1/2 address unit
Address units with 1 or 2 inputs
Installed on the loop without separate 24
VDC supply

NS-AIO21 control units


Multipurpose control units
Installed on the loop with separate 24 VDC
supply

NS-Timer
Timer unit for temporary disconnections
Installed on the loop without separate 24
VDC supply
Consilium Marine AB

Standard base plates

UB-2
Base plate for dry space
IP 22

NS-2IP55
Base plate with 2 cable glands for wet space
IP 55

SPB-1
Adapter for wet space
IP 55
Consilium Marine AB

Adaptive detectors

Continuous monitoring and measuring


Intelligent, adaptive alarm algorithm
Suppression of unwanted alarms
Contamination supervision and compensation
Interference immunity
Three detector sensitivity levels (low, normal, high)
Consilium Marine AB

Normal condition

Salwico CS4000 06:53

Press MENU to operate


Consilium Marine AB

Fire

FIRE
FIRE ALARM 1(1) 06:53
1 FIRE ZONE 61 MCP 612,
Analogue Zone 61, text 1
LB3 address 6l

MUTE=Silence bells (and local buzzer).


RESET=Reset fire alarm, OK=Details
Consilium Marine AB

Fault

FAULT

FAULT 1(1) 06:53


LOOP 2
CABLE BREAK
Between address 47 and 48

To MUTE or RESET press buttons


Consilium Marine AB

Disconnection

DISC.

Salwico CS4000 06:53


DISCONNECTION 1(2)
ZONE 5 SMOKE DETECTOR 6
MFZ 4 DK:3

Press MENU to access panel


Consilium Marine AB

Coming products and


features....
Evolution detector ranges, Analogue
addressable optical SMOKE/HEAT

Maintenance features:
TCP/IP for remote service and configuration assistance
Predictive maintenance
Remote maintenance
Remote diagnostics
Remote repair guidance
Support for spare part management
Consilium Marine AB

Central unit (with/without operator


panel)
3 loops (512 detectors).
Internal power supply with
redundancy

RS485

Control or Repeater Panel


Control or Repeater Panel
Consilium Marine AB

Summary
Backwards compatible with all existing
installations
Unique tools for remote service and
configuration assistance
Extended redundancy function including
power supply
254 addresses per loop
Time saving USB or Salwico Memory
Stick connection
The system can be supplied as a mixed
conventional and analouge addressable
system
All type approved
And many more features to come
Consilium Marine AB

You might also like