Connection Example

VLT HVAC Drive Software: 3.4

Closed loop operation from 0 - 10bar pressure transmitter with 4-20mA output. The motor needs to speed up
when the pressure drops below 7bar. The PID startup frequency is 10Hz and when the drive is running at min
frequency 10Hz, it will goto sleep.
Relevant Parameters
Par. Function Settings
FC
FC102
202 0-02 Motor Speed Unit [1] Hz
+24 V 12 0-21 Display 1.2 small [1652] Feedback
+24 V 13 1-00 Configuration mode [3] Closed loop
D IN 18 Start / Stop 3-41 Ramp up time 20s
D IN 19 3-42 Ramp down time 20s
COM 20 4-12 Motor Speed Low 10 Hz
D IN 27 Coast Inverse 20-12 Unit [71] Bar
D IN 29 3-02 Min reference 0
D IN 32 3-03 Max reference 10
D IN 33 315 Reference Source 1 [0] No function
D IN (S.Stopp)**37 Safety Stop 6-24 Min feedback 0
6-25 Max Feedback 10
+10 V 50 Pressure transducer 20-13 Min reference 0
A IN (S201 U-I) 53 4-20mA 20-14 Max refeerence 10
A IN (S202 U-I) 54 20-21 Setpoint 7
COM 55 20-73 Min feedback 0
A OUT 42 20-74 Max Feedback 10
A OUT 39 20-81 Normal / Inverse [0] Normal
20-83 PID start frequency 10
01 20-93 Proportional gain 2
Relay 1

02 20-94 Integral time 10


03 22-22 Low speed detect [1] Enabled
22-23 No flow function [1] Sleep mode
*04
Relay 2

*05
*06

NOTE: Erstellt von: Schulung


All settings are based on factory settings.
It is recommended to set all the motor parameters in Par. 1-20 to 1-26 and then perform Automatic Motor
Adaption (AMA) in Par. 1-29.