MATERIALS USED
Concrete - M 35
Steel - Fe 415
INPUT DATA
Dimensions - 15 m x 5.8 m
Effective Span - 5.8 m
Wearing Coat - 100 mm
Permissible Stresses - m= 10 j= 0.9 cb= 8.3
- Q= 1.1 st= 200
Total Depth - 0.4833 m Assumption : d = L/12
- So lets take 0.5 m OR
- 500 mm
Assume diameter of main bar - 20 mm
Assume clear cover - 40 mm
Then, Effective Depth - 450 mm
Then, Width of Bearing - 500 mm
Unit Weight of Concrete - 25 kN/m2
Unit Weight of Wearing Coat - 22 kN/m2
-
LOAD CALCULATION -
Load Combination - VII IRC 6:2014, Clause 202.3, Table 1
Dead Load - Most extreme Load Case in the list
Slab - 12.5 kN/m2
Wearing Coat - 2.2 kN/m2
Total - 14.7 kN/m2
-
Live Load - Class 70R Tracked vehicle IRC 6:2014, Clause 207.4, Table 2
-
Load - 70 tonne
L of Dispersion - 5.57
B(eff) - 4.436 bef = kx (1-(x/L))+bw
W of Dispersion - 6.496
Distribution Area - 36.1827 m2 IS 456, Clause 24.3.2
Therefore, Load Intensity - 1.93463 t/m2 OR
- 19.3463 kN/m2
Impact Load - 22 % of LL By Iteration IF for 5m - 25%
- 4.25618 kN/m2 IF for 9m - 10%
Impact Load of Floating Bodies - N.A No Water Body present
Wind Load - Negligible
Water Current - N.A No Water Body present
Tractive Force - 20 % of LL
This force is longitudinal and hence used only
- 3.86925 kN/m2 in footing design. ( Check for oveturning
- moment)
Centrifugal Force - N.A Only for Curved roads/bridges
Buoyancy - N.A
Earth Pressure - N.A Only Applicable for supports
Temperature - N.A
Deformation Effects - N.A Will be taken care by Distibution Steel
Secondary Effects - N.A
Seismic Effect - N.A Refer IRC:6- 2000,Clause 222.1
Wave Pressure - N.A Only for structures in Sea/Ocean
Grade Effect - Negligible
Permissible Stresses - 133 %
The RCC Slab culvert will be designed as per the guidance provided in the civil technical specification. Vehihicular traffic
load as per the IRC specification of Class "70R" shall be taken into account. Manual load calculations are made and
analysed using the software STAAD pro for the loadings, bending moments and shear forces and design/detail shall be
made as per the manual calculation.
= kx (1-(x/L))+bw
IF for 5m - 25%
IF for 9m - 10%
o Water Body present
by Distibution Steel
000,Clause 222.1
ures in Sea/Ocean
mm c/c spacing
ke 180 mm c/c
Design of Strip Footing
Thickness of Footing
Design of Stem
For Central Supports
Hori. Force due to Traction = 19.239 kN
Moment due to Traction = 48.0975 kNm
Factored Moment, Mu = 72.15 kNm
Eff. depth required to resist Mu = 256.10 mm
Therefore thickness req. = 306.10 mm
Thickness provided = 500 mm Higher depth helps in avoiding
Mu/bd2 = 0.36 mm shear reinforcement
Ast req = 0.113 %
But for footing min. Rein. = 0.2 %
Hence Ast req = 1000 mm2
Therefore provide 16 mm bars = 201.061 mm Hence take spacing 200 mm c/c
Distri. Take .12 % = 600 mm2
Take 12 mm bars @ spacing = 188.495 Hence take spacing 180 mm c/c
Assumption
Assumption
afe in shear
fe