For MRIL job, we were running our CAT at 1800 rpm to run alternator in manual mode. Now we can run
MRIL by setting CAT at rpm 1375-1400.
Now run CAT at 1375-1400 RPM and start the alternator. It should make frequency around 60Hz. We
can also adjust the fluid displacement value to get frequency=60Hz in manual mode.
Regards
Harish Chugh
Dear BBT
Thanks for confirming
Dear Harish
Please circulate the findings.
Kind regards
Pravesh
Sir,
We have confirmed that running with two ACs and Checked RDT, found voltage remained about 112V
and frequency 60-62hz which is good.
Dear Harish
Pls confirm voltage of 112.6V is with load applied ie AC and tools powered on..
Kind regards
Pravesh
Dear Sir,
After checking frequency by changing this value, we found the following parameters
We also checked by giving load on alternator, the voltage remain same 112.6v.
So, now we can run MRIL with CAT rpm-1375 in manual mode.
Regards
Harish Chugh
Kind regards
Pravesh
Dear Sir,
We did MRIL jobs in manual mode with CAT RPM-1825 in SKD007OH. With this RPM, alternator is
making 48-49 HZ frequency and 89V. So we increased the voltage by setting Basler at maximum limit
and voltage reached upto 110-115v (max) but still frequency was 48-49Hz and we did job which is not
good.
But in SKD008OHNER and SKD009OHNER units, Alternator is making 115V and Frequency 57-59 Hz with
Rexroth in manual mode having CAT rpm 1700-1800. So, No need to disturb our Basler.
A. Doubt is either Rexroth is not giving exact voltage to pump solenoid in manual mode.
B. Or pump is not giving full displacement according to Rexroth voltage.
C. Or CAT rpm meter showing 1800 rpm is not correct.
Now, we found Rexroth (Frequency controller) gives 4.5V to pump solenoid in manual mode and 6.5v in
automatic. Then we checked same with another Rexroth in Lab. It was also giving same voltage. We will
confirm the same from Barmer also.
For other option, there is a fluid displacement value of 50 in manual mode of Rexroth parameters, if we
increase this value to 55 (it will increase pump solenoid voltage to 4.8v in manual mode), then our unit
will make frequency near about 56 Hz and voltage 113V without disturbing Basler having 1800 rpm of
CAT.
Please suggest.
Regards
Harish Chugh