LSIS protection and measurement products specializes in the protection and
monitoring of electricity distribution networks, making your power distribution
easier and more reliable. You can either integrate these products into your
intelligent switchgear or use them as stand-alone multifunction units. In addition,
all of these products provide versatile communications as well as sophisticated
functionality for event, alarm and fault analysis.
The whole GIPAM, GIMAC product family for line, motor, generator protection
and monitoring offers you an integrated solution which starts with extensive
protection, measurement and control functionality.
Contents
GIPAM-2200 M1
GIPAM-115 M2
DPR-1000 N1
DPR N2
IMC-III O
GIMAC-PQ P
GIMAC-IV Q1
GIMAC-II plus Q2
GIMAC-i R1
GIMAC-DC R2
Digital Protection device
GIPAM- GIPAM- GIPAM- GIPAM- GIPAM-
DEVICE DPR-1000 DPR-011 DPR-111
2200F 2200T 2200M 2200G 115FI
Phase time overcurrent 51
Ground time overcurrent 51N/G
Phase instantaneous overcurrent 50
Ground instantaneous overcurrent 50N/G
Number of phases protected 3+N 3+N 3+N 3+N 3+N 3+N 3+N 3+N
Hiset & lowset 50H/50L
instantaneous overcurrent 51H/51L
Negative sequence time overcurrent 46
Negative sequence overvoltage 47 (POR)
Thermal overload 49
Directional ground 67N
Sensitive ground 67G
Overvoltage ground 59N, 64
Undervoltage 27
PROTECTION
Overvoltage 59
Stall 48
Locked rotor 51LR
Undercurrent 37
Underfrequency 81U
Overfrequency 81O
Motor differential 87M
Transformer phase differential 87T-P
Transformer ground differential 87T-G
Sync check 25
Forward/reverse active power 32P
Reverse reactive power 32Q
Underpower 37P
Breaker failure 50BF
Trip circuit supervision 74TC
Supervision of startingtime/Notching 66
Lock-out 86
Temperature 38
Power outputs 2 2 2 2 2 2 2 2
Digital outputs 10 10 10 10 8 (Fixed) 5 5 5
I/O
Digital inputs 6 6 6 6 3 3
Analog outputs
Analog inputs 4 4 4 4 2
Ia, Ib, Ic, In
Io, I1, I2 Io, I2 Io, I2 Io, I2 Io, I2 Io, I2
Va, Vb, Vc, Vab, Vbc, Vca
Vo, V1, V2 Vo, V2 Vo, V2 Vo, V2 Vo, V2 Vo Vo
Watts
Vars
MONITORING & METERING
kWh
kVarh
Frequency
Power factor
Trip circuit supervision
Trip relay supervision
VT fuse failure
Full load current %FLC
Motor starting current Is
Motor starting time Ts
Motor starting capacity %Q
Temperature
CB operation
CB operating time
I, V 0.5% 0.5% 0.5% 0.5% 0.5% 0.5%
Accuracy
W, Wh 1.0% 1.0% 1.0% 1.0% 1.0%
Event recording 800 800 800 800 128 128 20 20
ADDITIONAL
RS-485(422)
Ethernet
Fiber optic
I-NET (Custom LS)
Modbus
DNP3.0
Digital Measurement device
DPR-211 DPR-311 DPR-411 DPR-511 IMC-III DEVICE GIMAC-PQ GIMAC-415 GIMAC-115 GIMAC- i EX GIMAC- i NO
Digital inputs 10 10 10
1 2 2 1 Analog inputs 2 2
2 4 4 2 9 Power quality
8 Sag
1 Swell
ADDITIONAL
Interruption
Undervoltage
Io Overvoltage
Auto power factor controller Option
Vo Vo Demand controller Option
Event recording 256 300 256
Fault wave recording Max. 60cycle
COMMUNICATION
RS-485(422)
I-NET (Custom LS)
Modbus
Dual
20 20 20 20
1 1 1 1 1
GIPAM-2200
Contents Features
Functional Block Diagram
Technical Specifications
M1-8
M1-11
M1-12
Communications M1-14
External & Structure M1-15
Man Machine Interface M1-16
Characteristics M1-19
Time Characteristic Curves M1-22
Network Systems M1-26
Wirings M1-28
Contact Usage M1-33
Dimension M1-36
Ordering M1-37
GIPAM-2200 series are multifunction microprocessor-
based protection equipments suitable for all types of
application such as distribution feeders. It can be also be
used for management backup protection of incomings,
feeders, transformers and high tension motors.
Over current protection function includes protection elements such GIPAM-2200 can arrange easily as demand of usersneed as
as over current, over current ground fault, selective ground fault well as apply to various sequences because the logic design
current, directive ground fault current, negative sequence over through a simple logic program is available regarding
current in each phase with regard to time delay or instantaneous input/output contacts.
elements. Moreover, it supports under voltage, over voltage, GIPAM-2200 series provides various monitoring, measuring
ground fault over voltage, phase reversal over voltage, etc. functions and it does easy accident analysis by storing data
regarding voltage protection and thermal overload, rocked rotor, fires such as 800 events, 200 faults and maximum 64 cycle s
differential, ground fault differential regarding various kinds of fault waveform. Furthermore, when accidents happens, alarm
protection functions. As it has differential, ground fault differential signal can put out during the operation in terms of self testing.
to protect a transformer, and the protection of secondary wires GIPAM-2200 series provide IrDA Serial Ports for connecting
transformer is available too. PC which is performing the operation program, and they are
M1-4
M1
GIPAM-2200
M1-5
The optimum protection which leads protective
diagnosis and reliability improvement of own
protection relay, quick accident analysis and
maintenance & repair, preventive control,
minimizing accident spread.
52T
PT(VT) Failure
Select Before Operating (SBO) & Trip Circuit Supervision (TCS) &
Circuit Breaker Failure (CBF)
Check Before Operating (CBO) Trip Relay Supervision (TRS)
The improvement of reliability and Supervise circuit breaker trip circuit Upper breakers trip in case of Circuit
security of the circuit breaker
s control Supervise circuit breaker trip relay breaker Failure (CBF)
contact Prevention of accident spread
(the coordination of protection )
M1-6
Circuit Breaker Failure
M1
GIPAM-2200
Select Before Operating &
Check Before Operating
M1-7
Digital Integrated Protection & Monitoring Device
Features
M1-8
EVENT & FAULT RECORDING Sequence of Event(SOE) Function
M1
GIPAM-2200 is able to store up to 800 events that are related to GIPAM-2200 supports the SOE function that makes easy for
Protection & Measuring function, Breaker operation, Contact trip, reviewing fault analysis and operation information by recording
GIPAM-2200
operation information, and selfdiagnosis outcome.Moreover, in events in sequence at 1ms intervals regarding internal protection
case of line and load fault incidents, GIPAM-2200 can store up relay, breaker operation, or self-diagnosis abnormalities such as
to 200 detailed information regarding fault analysis, current fault, alarm contact output and others.These events including the latest
and voltage fault registered one can be stored as many as 800. Each event can be
verified in detail under the EVENT LIST section from the initial
screen of EVENT/FAULT REC Menu. In addition, it is possible to
save as files with GIPAMManager (capable to manage more than
800).
Vector Diagram
GIPAM-2200 can display a vector diagram regarding the
systems voltage, current, and phase through PC interface
operating program. It is easy to comprehend its electric systems
condition because of visualization from the diagram that verifies
the amount of electricity.
It can record front and rear 64 cycles of fault waveforms for each
phase. And it is also possible to increase number of recording
times by cycle partitions.
M1-9
Digital Integrated Protection & Monitoring Device
Features
Select Before Operating(SBO) and Check Before TRIP CIRCUIT SUPERVISION (TCS) & TRIP RELAY
Operating(CBO) Function SUPERVISION (TRS)
By choosing controlling Points first before sending out orders to To check circuits condition, GIPAM-2200 internally make
where it is desired to control, control orders are executed only micro-current to flow on a trip circuit that is composed of
along with normal responses. This function enhances to control breakers trip coil and control voltage, and trip relay; and
reliability and security.GIPAM-2200 applies SBO/CBO functions tests it every hour. By composing trip relay with 2 pole series,
at CB controls power contact points. For selected control point, not 1 pole by itself, it will execute contact operation at regular
it will wait for control orders for 5 seconds after its response. If cycle or requested time checking trip relay automatically
the control order wont be delivered within 5 seconds, it will be without operation of a circuit breaker. After the automatic
reset. The control functions will be executed only on the normal check-up, the result will be recorded as event and if fault
condition when orders were delivered within 5 seconds, happens, contact output will be printed to prevent accidents
in advance.
Various Communication Compatibilities
GIPAM-2200 is possible to select its communication from RS-
485/422, Optic, and I- NET. Its application to diverse systems
is convenient in the industrial sites, because it supports
various protocols such as DNP 3.0, IEC 60870, MODBUS
and exclusive I-NET protocol as well. Not only it is able to
support the Ethernet communication mode through a protocol
transformer enabling high speed data communications, but
also it is possible to make up differentiated systems using
H.A.(High Availability) communication supports. Moreover, the
products front side is equipped with an IrDA(infrared rays)
port to provide easy access to upload/download with PC
M1
GIPAM-2200
64
67G/N
GIPAM 2200 F
87T-G 87T-P
50N 51N
64
67G/N
GIPAM 2200 T
50 51 46 49
51G 87M
GIPAM 2200 M
50N 51N 67G/N 67G/N
48/
50N 51N 51LR
M1-11
Digital Integrated Protection & Monitoring Device
Technical Specifications
Rating
Type Specification
Frequency 60Hz/50Hz
PT 110V
Voltage
GPT 190V, 190/ 3V
CT 5A
Current
ZCT 200/1.5mA
Input
Control Voltage AC/DC 110V/125V
PT Max. 0.5VA
Burden
CT Max. 1.0VA
3 In for 3 hours
Current circuit
Overload Withstand 20 In for 2 seconds
Air 8kV
ESD (Electrostatic Discharge)
Contact 6kV
Non-impact place
Others
Non-air pollution place
H
Dimension (W D) 237285223mm
M1-12
Protection function M1
GIPAM-2200
Usage type Protection
OCR (50/51) OCGR (50/51N) DGR (67N)
GIPAM-2200 FN UVR (27) OVR (59) OVGR (64)
Incoming NSOVR/POR (47) NSOCR (46) THR (49)
48/51LR UCR (37) NCH (66)
Feeder
OCR (50/51) SGR (67G) OVGR (64G)
Motor
UVR (27) OVR (59) THR (49)
GIPAM-2200 FZ
NSOVR/POR (47) NSOCR (46) NCH (66)
48/51LR UCR (37)
DFR (87M) OCR (50/51) OCGR (50/51N)
DGR (67N) SGR (67G) OVGR (64)
Motor (87M) GIPAM-2200 M
NSOCR (46) THR (49) 48/51LR
NCH (66)
DFR (87T-P) DFR (87T-G) OCR-1 (50/51)
GIPAM-2200 T1 OCR-2 (50/51) OCGR-1 (50/51N) OCGR-2 (50/51N)
OVGR (64) DGR-1 (67N) DGR-2 (67N)
DFR (87T-P) DFR (87T-G) OCR-1 (50/51)
Transformer GIPAM-2200 T2 OCR-2 (50/51) OCGR-1 (50/51N) DGR-1 (67N)
OVGR (64) SGR-2 (67G)
DFR (87T-P) DFR (87T-G) OCR-1 (50/51)
GIPAM-2200 T3 OCR-2 (50/51) OCGR-2 (50/51N) DGR-2 (67N)
OVGR (64) SGR-1 (67G)
Measurement function
M1-13
Digital Integrated Protection & Monitoring Device
Communications
GIPAM-2200 series can be set various kinds of relay functions by handling the Text LCD & Control keys on the front. In the menu, there
are measuring value displays, Fault & Event Data Logging, DI/DO Monitoring, SYSTEM Configuration & System information
for setting the rate of PT/CT, wiring method, setting communication and verifying information.
M1-14
External & Structure
M1
GIPAM-2200
Status LED
Power
Comm(Tx) 4 Text LCD
20
Diag/Err
Pick-up/Trip
Draw-out Handle
Direction Key
Function Key
FUNC
Trip Assign RESET
LED 11EA ESC
ENTER
CB CLOSE/OPEN
CC CLOSE/OPEN
Operating Key
IrDA Port
Remote/Local
Front View
FUNCTION
FUNC Using with ESC key when clearing Data,
No use of it during normal operation
ESC
ESC The cancel of selected item &
change of setting values
ENTER
ENTER The selection of item
The confirmation of setting
Remote / Local
R/L The switching of
Remote/Locai <Draw-out Type>
M1-15
Digital Integrated Protection & Monitoring Device
Man Machine Interface
GIPAM-2200 F
GIPAM-2200 T
M1-16
GIPAM-2200 M
M1-17
GIPAM-2200
M1
Digital Integrated Protection & Monitoring Device
Man Machine Interface
GIPAM-2200 series can be set various kinds of relay functions by handling the Text LCD & Control keys on the front. In the menu,
there are measuring value displays, Fault & Event Data Logging, DI/DO Monitoring, SYSTEM Configuration & System information
for setting the rate of PT/CT, wiring method, setting communication and verifying information.
M1-18
Characteristics
GIPAM-2200 F M1
Operating time
GIPAM-2200
Protection Operating part Setting range Note
Setting Curves
isolated 0.9~6mA/0.1mA
system (Ion=1.5mA)
Zero-phase
current grounded 0.02~2.00Ion/0.01Ion Vo > Vos
system (Ion=5A)
SGR (67G) Time Io > Ios
0.05~10.00s/0.01s Definite
DGR (67N) delay Zero-phase 11~80V/1V (Vo) -(Io) RCA + 87
voltage (Von=190V, 190/ 3V) (Vo) -(Io) RCA - 87
Relay
characteristic 0~90/5
angle
2 2
t : operating time
Hot h : 2.0~60.0min/0.5min
t = hln 2
- IP
[ I -I(kI B)
] 2
k : multiple factor
THR (49) 0.2~1.2In/0.01In 2
Cold c : 2.0~60.0min/0.5min
t = cln 2 [ I
I - (kIB)
2 ] (0.8~1.2/0.05)
: thermal constant
Stall OFF, 0.2~10.0In/0.01In 0.05~300.00s/0.01s Definite
Stall/Lock Time Start time range
0.05~1.00/0.01 Inverse (VI, EI)
(48/51LR) delay Lock OFF, 0.2~10.0In/0.01In 1.0~300.0s/0.1s
0.05~300.00s/0.01s Definite
M1-19
Digital Integrated Protection & Monitoring Device
Characteristics
GIPAM-2200 T
Operating time
Protection Operating part Setting range Note
Setting Curves
Instanta Low set Low: 0.05~300.00s/0.01s Definite
OFF, 1.0~32.0In/0.1In
OCR-1 neous High set High: 40ms and below
(50/51) 0.05~1.20/0.01 Inverse
Time delay OFF, 0.10~10.00In/0.01In DT, SI, VI, EI, LI
0.05~300.00s/0.01s Definite
Instanta Low set Low: 0.05~300.00s/0.01s
OFF, 1.0~32.0In/0.1In Definite
OCR-2 neous High set High: 40ms and below
(50/51) 0.05~1.20/0.01 Inverse
Time delay OFF, 0.10~10.00In/0.01In DT, SI, VI, EI, LI
0.05~300.00s/0.01s Definite
Instanta Low set Low: 0.05~300.00s/0.01s
OFF, 0.1~8.0In/0.02In Definite
OCGR-1 neous High set High: 40ms and below
(50/51N) 0.05~1.20/0.01 Inverse
Time delay OFF, 0.02~2.00In/0.01In DT, SI, VI, EI, LI
0.05~300.00s/0.01s Definite
Instanta Low set Low: 0.05~300.00s/0.01s
OFF, 0.1~8.0In/0.02In Definite
OCGR-2 neous High set High: 40ms and below
(50/51N) 0.05~1.20/0.01 Inverse
Time delay OFF, 0.02~2.00In/0.01In DT, SI, VI, EI, LI
0.05~300.00s/0.01s Definite
M1-20
GIPAM-2200 M M1
Operating time
GIPAM-2200
Protection Operating part Setting range Note
Setting Curves
Instanta Low set Low: 0.05~300.00s/0.01s
OFF, 1.0~32.0In/0.1In Definite
neous High set High: 40ms and below
OCR (50/51)
0.05~1.20/0.01 Inverse
Time delay OFF, 0.10~10.00In/0.01In DT, SI, VI, EI, LI
0.05~300.00s/0.01s Definite
Instanta Low set Low: 0.05~300.00s/0.01s
OFF, 0.1~8.0In/0.02In Definite
OCGR neous High set High: 40ms and below
(50/51N) 0.05~1.20/0.01 Inverse
Time delay OFF, 0.02~2.00In/0.01In DT, SI, VI, EI, LI
0.05~300.00s/0.01s Definite
DT, SI
Instantaneous OFF, 11~80V/1V Inst, 50~250ms/5ms Definite
Von=190V or 190/ 3V
OVGR (64)
0.05~1.00/0.01 Inverse
Time delay OFF, 11~80V/1V Inst : 40ms and below
0.05~300.00s/0.01s Definite
Hot h : 2.0~60.0min/0.5min
t = hln [ I -I(kIB)
2
- IP
] 2
t : operating time
k : multiple factor
THR (49) 0.2~1.2In/0.01In 2
I (0.8~1.2/0.05)
Cold c : 2.0~60.0min/0.5min
t = cln [ I - (kIB) ]
2 2
: thermal constant
Stall OFF, 0.2~10.0In/0.01In 0.05~300.00s/0.01s Definite
Stall/Lock Time Start time range
0.05~1.00/0.01 Inverse (VI, EI)
(48/51LR) delay Lock OFF, 0.2~10.0In/0.01In 1.0~300.0s/0.1s
0.05~300.00s/0.01s Definite
DFR-M (87M) Instantaneous 0.02~2.00In/0.01In Inst, 0.05~300.0s/0.01s Definite Inst : 40ms and below
M1-21
Digital Integrated Protection & Monitoring Device
Time Characteristic Curves
0.14
t= TL + C
(I/IS)0.02-1
Time lever (TL) : 0.05~1.2
OVGR
TL: 0.05~1.0
NSOCR
Relay constant C: 0
13.5
t= TL + C
(I/IS)-1
Relay constant C: 0
M1-22
Extremely Inverse Time-EI M1
GIPAM-2200
Application : OCR (50/51)
OCGR (50/51N)
OVGR (64)
NSOCR (46)
Locked Rotor (51LR)
80
t= TL + C
(I/IS)2-1
Time lever (TL) : 0.05~1.2
OVGR
NSOCR TL: 0.05~1.0
Locked Rotor
Relay constant C: 0
120
t= TL + C
(I/IS)-1
Relay constant C: 0
M1-23
Digital Integrated Protection & Monitoring Device
Time Characteristic Curves
Thermal Curve
(a) Pick-up
323~ 127
(b) Pick-up ~ Drop-out
137~ 313
Vo > Vos
Io > Ios
RCA - 87(Vo) -(Io) RCA + 87
M1-24
Ratio Differential Curve M1
GIPAM-2200
Application : DFR (87T-P)
M1-25
Digital Integrated Protection & Monitoring Device
Network Systems
GIPAM-2200 series perform 64kbps data transmission as maximum speed, and also 250kbps express
serial communication is available by I-NET, which is an exclusive communication system by LSIS.
They offer RS-485/I-NET Multi-port & Fiber Optic Port, and supports DNP3.0, IEC 60870, MODBUS,
and exclusive I-NET Protocol. When the protocol converter (GMPC-V) is used , I-NET only
can be converted into RS- 232/485, Ethernet and Protocol conversion
also can be converted into DNS3.0, MODBUS is available.
DCS, BAS
Event Logging
DNP3.0
MODBUS
Fiber Optic
RS-485
GMPC-V MODBUS
DNP3.0
RS-485
MODBUS
RS-232/485
Ethernet
GIPAM-115FI
DPR-1000
GIPAM-2000 GIPAM-2200
M1-26
M1
GIPAM-2200
Web-Server
(Web-based S/W)
MODBUS
RS-232
MODBUS
Ethernet Internet /
Intranet
MODBUS
RS-232/485
MODBUS
RS-232/485
MODBUS
RS-485
M1-27
Digital Integrated Protection & Monitoring Device
Wirings
3P3W
2CT
2PT
(Open delta wiring)
M1-28
3P4W M1
GIPAM-2200
1P3W
* NCT application
M1-29
Digital Integrated Protection & Monitoring Device
Wirings
GIPAM-2200 T1
M1-30
GIPAM-2200 T2 M1
GIPAM-2200
GIPAM-2200 T3
M1-31
Digital Integrated Protection & Monitoring Device
Wirings
GIPAM-2200 M
M1-32
Contact Usage
GIPAM-2200 F M1
GIPAM-2200
Input / Output
Terminal No. Usage Default Note
60 DI_01 CB_52a
Fixed
59 DI_02 CB_52b
57 DI_03 General DI General DI
56 DI_04 General DI General DI
55 DI_05 General DI General DI
54 DI_06 General DI General DI
50 CB_OFF0
CB_OPEN output
49 CB_OFF1
Fixed
48 CB_ON0
CB_CLOSE output
47 CB_ON1
46 DO_01 50/51 (OCR) General DO (Normal/Pulse)
45 DO_02 50/51N, 67G/N (OCGR/SGR/DGR) General DO (Normal/Pulse)
44 DO_03 27 (UVR) General DO (Normal/Pulse)
43 DO_04 59 (OVR) General DO (Normal/Pulse)
40 DO_05 64 (OVGR) General DO (Normal/Pulse)
39 DO_06 47 (NSOVR) General DO (Normal/Pulse)
38 DO_07 49 (THR) General DO (Normal/Pulse)
36 DO_08 48/51LR (Stall/Lock) General DO (Normal/Pulse)
35 DO_09 Pick-up
Fixed
34 DO_10 Power_Fail/Diag_Err
M1-33
Digital Integrated Protection & Monitoring Device
Contact Usage
GIPAM-2200 T
Comm. Reset switch, LED
output
input
Input / Output
Terminal No. Usage Default Note
60 DI_01 CB_52a
Fixed
59 DI_02 CB_52b
57 DI_03 General DI General DI
56 DI_04 General DI General DI
55 DI_05 General DI General DI
54 DI_06 General DI General DI
50 CB_OFF0
CB_OPEN output
49 CB_OFF1
Fixed
48 CB_ON0
CB_CLOSE output
47 CB_ON1
46 DO_01 87T-P (DFR) General DO (Normal/Pulse)
45 DO_02 87T-G (DFR) General DO (Normal/Pulse)
44 DO_03 50/51 (OCR 1) General DO (Normal/Pulse)
43 DO_04 50/51 (OCR 2) General DO (Normal/Pulse)
40 DO_05 50/51N, 67G/N (OCGR/SGR/DGR 1) General DO (Normal/Pulse)
39 DO_06 50/51N, 67G/N (OCGR/SGR/DGR 2) General DO (Normal/Pulse)
38 DO_07 64 (OVGR) General DO (Normal/Pulse)
36 DO_08 General DO (Normal) General DO (Normal/Pulse)
35 DO_09 Pick-up
Fixed
34 DO_10 Power_Fail/Diag_Err
M1-34
GIPAM-2200 M M1
GIPAM-2200
Input / Output
Terminal No. Usage Default Note
60 DI_01 CB_52a
Fixed
59 DI_02 CB_52b
57 DI_03 General DI General DI
56 DI_04 General DI General DI
55 DI_05 General DI General DI
54 DI_06 General DI General DI
50 CB_OFF0
CB_OPEN output
49 CB_OFF1
Fixed
48 CB_ON0
CB_CLOSE output
47 CB_ON1
46 DO_01 50/51 (OCR) General DO (Normal/Pulse)
45 DO_02 50/51N, 67G/N (OCGR/SGR/DGR) General DO (Normal/Pulse)
44 DO_03 64 (OVGR) General DO (Normal/Pulse)
43 DO_04 46 (NSOCR) General DO (Normal/Pulse)
40 DO_05 49 (THR) General DO (Normal/Pulse)
39 DO_06 48/5LR (Stall/Lock) General DO (Normal/Pulse)
38 DO_07 37 (UCR) General DO (Normal/Pulse)
36 DO_08 DFR-M (87M) General DO (Normal/Pulse)
35 DO_09 Pick-up
Fixed
34 DO_10 Power_Fail/Diag_Err
M1-35
Digital Integrated Protection & Monitoring Device
Dimension
M1-36
Ordering
GIPAM-2200 FN RS D AI 60Hz M1
GIPAM-2200
Protection Usage Communication Protocol Analog Input Frequency
FN Feeder, Incoming, Motor / NCT RS RS-485 D DNP3.0 AI 4~20mA 60Hz
FZ Feeder, Incoming, Motor / ZCT OP Fiber-Optic/RS-485 E IEC60870 - Non 50Hz
M Motor (87M) / NCT, ZCT IN I-NET M MODBUS
T1 Transformer / Pri_NCT, Sec_NCT - Non I I-NET
T2 Transformer / Pri_NCT, Sec_ZCT
T3 Transformer / Pri_ZCT, Sec_NCT
M1-37
GIPAM-115
GIPAM-115
Digital Integrated Protection & Monitoring Equipment
Contents Features
Technical specifications
Communications
M2-4
M2-6
M2-8
External & MMI M2-9
Operation curves M2-10
Wirings M2-12
Ordering & Dimension M2-15
Digital Integrated Protection & Monitoring Device
Features
GIPAM
Digital Integrated Protection & Monitoring Equipment
GIPAM is a multifunction, microprocessor-based protection equipment suitable
for all types of applications such as distribution feeders.
It can be also be used for management and backup protection of buses,
transformers, and power lines.
Drawout structure for panel mounting
User-friendly front panel to monitor, program, and test the GIPAM
Data communication with a host computer
M2-4
Protection
Multi-functions offering a wide choice of protective options
OCR, 50/51
OCGR, 50/51N
OVR, 59
UVR, 27
OVGR, 64G
SGR, 67G
POR, 47 M2
Broad setting ranges
GIPAM-115
All types of curves provided
SI, Standard inverse time delay
VI, Very inverse time delay
EI, Extremely inverse time delay
LI, Long inverse time delay
DI, Definite time delay
Displaying status via digital LCD and analog Bar graph for better visualization
Communication
Modbus/RS-485
I-NET / LS customized protocol
M2-5
Digital Integrated Protection & Monitoring Device
Technical specifications
Rating
Type Specification
Frequency 60Hz/50Hz
PT 110V
Voltage
GPT 190V
CT 5A
Current
ZCT 200/1.5mA
Input
Control Voltage AC/DC 110V or DC 125V
PT Max. 0.5VA
Burden
CT Max. 1.0VA
2 In for 3 hours
Current circuit
Overload Withstand 20 In for 2 seconds
Air 8kV
ESD (Electrostatic Discharge)
Contact 6kV
Non-impact place
Others
Non-air pollution place
H
Dimension (W D) 437210165 mm
Weight 10.5kg
M2-6
Protection functions
GIPAM-115
[59] Time-delay(Low) OFF, 0.80~1.60Vn / 0.02Vn 0.1~60.0s / 0.01s Definite time
UVR Time-delay(high) OFF, 0.20~0.90Vn / 0.02Vn 0.1~60.0s / 0.01s Definite time Outage lock :
[27] Time-delay(Low) OFF, 0.20~0.90Vn / 0.02Vn 0.1~60.0s / 0.01s Definite time (below 15V)
OFF, 0.10~0.40Von / 0.02Von
Time-delay(high) 0.1~60.0s / 0.01s Definite time
OVGR (Von=190V)
[64G] OFF, 0.10~0.40Von / 0.02Von
Time-delay(Low) 0.1~60.0s / 0.01s Definite time
(Von=190V)
Zero-phase current(Io) OFF, 0.6~3.6Ion / 0.2Ion (Ion=1.5mA)
SGR
Zero-phase voltage(Vo) 0.10~0.40Von / 0.02Von (Von=190V) 0.1~60.0s / 0.01s Definite time
[67G]
RCA 45fixed
POR Time-delay(high) OFF, 5~100% / 1% 0.1~60.0s / 0.01s Definite time
[47] Time-delay(Low) OFF, 5~100% / 1% 0.1~60.0s / 0.01s Definite time
Measurement functions
0~190(V)
Zero-phase voltage, Vo - Vo, Vo_max(peak)
Bar graph 0~120%
0~9,999MW
Active power, Watts 1.0%
Bar graph 0~120%
0~999,999MWh
Active energy, Wh 1.0%
Bar graph 0~120%
0~999,999MVarh
Reactive energy, Varh 1.0%
Bar graph 0~120%
M2-7
Digital Integrated Protection & Monitoring Device
Communications
Modbus/RS-485
Operation mode: Differential
Distance: Max. 1.2km
Cable : SCADA system
General RS-485 shielded twist
2-pair cable
Modbus/RS-485
Baud rate :
9600bps, 19200bps, 38400bps
Transmission method: Half-Duplex
Termination: 150
M2-8
External & MMI
M2
GIPAM-115
Control keys
M2-9
Digital Integrated Protection & Monitoring Device
Operation curves
0.14
SI, Standard Inverse T= D2, Definite Time T=2
(I / IS)0.02 - 1
13.5
VI, Very Inverse T= D4, Definite Time T=4
(I / IS) - 1
80
EI, Extremely Inverse T= D8, Definite Time T=8
(I / IS)2 - 1
120
LI, Long Inverse T=
(I / IS) - 1
100
10
1.2 10
Operation time, sec
Operation time, sec
0.6
1 0.4
0.3
0.2
1
1.2
0.1
0.6
0.4
0.05 0.3
0.1
0.2
0.1
0.1
0.05
0.01 0.01
1 10 20 1 10 20
M2-10
EI curves for OCR and OCGR LI curves for OCR and OCGR
1000 10000
100
1000
10
GIPAM-115
10
1.2
1.2
0.6
0.1 0.4 0.6
0.3 0.4
0.2 0.3
0.1 0.2
1
0.01 0.05 0.1
0.05
0.001 0.1
1 10 20 1 10 20
Definite Time curves for UVR and OVR Operation phase characterictic of SGR
135
UVR Setting OVR Setting
60
Operation time, sec
10
0.1
315
0.2 0.8 0.9 1 1.6
M2-11
Digital Integrated Protection & Monitoring Device
Wirings
Input Output
Comm
terminals
Note) 1. Avoid connectting GIPAM parallel with the other devices that generate noises.
2. Press the clear switch to initialize all data after installation.
M2-12
1P 2W
M2
1P 3W
GIPAM-115
3P 3W(with 2CT, 2PT)
M2-13
Digital Integrated Protection & Monitoring Device
Wirings
3P 3W
3P 4W
(NCT is available)
ZCT GPT
M2-14
Dimension & Ordering
Dimensions
M2
Cutout
GIPAM-115
Ordering
GIPAM-115 FI RS M 60Hz
M2-15
DPR-1000
Function
Protection & Control
Overcurrent (50/51P), Overcurrent ground (50/51N)
Thermal (49), Negative sequence overcurrent (46)
Selective ground (67G), Directional ground (67N)
Under current (37), Stall & locked rotor (48/51LR)
Starts per hour (66)
Lock-out (86)
2 analog inputs (Thermistor)
5 digital outputs
3 digital inputs
User Interface
204 Character LCD
DNP3.0, Modbus/RS-485
PC interface software (GIPAM manager)
Block diagram
N1-4
Technical Specifications
Rating
Type Specification
Frequency 60Hz
Voltage GPT
190, 190 / 3
CT 5A
Current
ZCT 1.5mA
Burden PT 0.5VA
CT 1.0VA
N1
Digital Input Digital Input: AC/DC 110V
DPR-1000
For trip
AC 2500VA, DC 300W
Output
AC 250V 5A/DC 30V 5A Resistive Load
For alarm
AC 750VA, DC 90W
3 In for 3 hours
Current circuit
Overload Withstand 20 In for 2 seconds
Air 8kV
ESD (Electrostatic Discharge)
Contact 6kV
Non-impact place
Others
Non-air pollution palce
H
Dimension (W D) 120245185 (mm)
Weight 3.4kg
N1-5
Digital Protective Relays
Technical Specifications
Protection functions
Protective
Operating part Setting & Operating time Remark
function
Instantaneous
Setting: OFF, 0.5~20.0/0.1In Below 40ms
high set
OCR Instantaneous Setting: OFF, 0.5~20.0/0.1In
Definite
(50/51) low set Operating time: 0.05~60.0/0.01s
Setting: OFF, 0.1~4.0/0.02In Curves
Time delay
Operating time: 0.05~1.20/0.01 (Inverse) SI, VI, EI, LI
Setting: OFF, 0.1~8.0/0.02In
Instantaneous Definite
Operating time: 0.05~300.0/0.01s
OCGR
Setting: OFF, 0.02~2.0/0.01In
(50/51N) Curves
Time delay Operating time: 0.05~1.20/0.01 (Inverse)
DT, SI, VI, EI, LI
0.05~60.0/0.01s (Definite)
Time delay Setting: OFF, 0.1~1.0/0.02In
Definite
high set Operating time: 0.08~60.0/0.01s
NSOCR
Time delay Setting: OFF, 0.1~1.0/0.01In
(46) Curves
low set Operating time: 0.05~1.00/0.01(Inverse)
DT, SI, VI, EI, LI
0.08~60.0/0.01s(Definite)
Io Setting: 0.02~2.0/0.01Ion
DGR Vo Setting: 11~80/1V Grounded system
Time delay
(67N) RCA Setting: 0~90/1 Definite
Operating time: 0.05~10.00/0.01s
Io Setting: 0.9~6.0/0.01mA
SGR Vo Setting: 11~80/1V Isolated system
Time delay
(67G) RCA Setting: 0~90/1 Definite
Operating time: 0.05~10.00/0.01s
THERMAL
Time delay Setting: OFF, 50~100/1% (h, c) Motor Config.
(49)
Time delay Setting: 0.50~10.00/0.01
STALL/ Motor Config.
(Stall) (FLCSVC.O/L)
LOCK
Time delay Operating time: 0.05~300.0/0.01s(Definite)
(48/51LR) Motor Config.
(Lock) 0.05~1.20/0.01(Inverse)
UCR Setting: 0.1~0.9/0.02In
Time delay Definite
(37) Operating time: 0.05~300.0/0.01s
Starts number: OFF, 1~5 times/1
NCH Base time: 10~60min/1min
- Notching
(66) Time between starts block: 1~60min/1min
Operating time: 10~80%/1%
RTD Setting: OFF, 20~180/1C
Time delay Definite
(38) Operating time: below 50ms
N1-6
Motor protection
N1
Measurement
DPR-1000
Item Display range Remark
Line / Load current 0.000A ~ 999.99kA (CTpri) Start current (CTsec) : 0.050A
Starting current
0.000A ~ 999.99kA (CTpri) Start current (CTsec) : 0.050A
(Is_avg, Is_peak)
Starting time
0.000sec ~ 4294967.296sec -
(Ts_avg, Ts_peak)
%FLC, %FLCavg,
0.000% ~ 999.99% Start %FLC: 5.000%
%FLCpeak
0.000A ~ 999.99kA (CTpri) Start current (CTsec/ZCTsec)
Io, Io max
0.000A ~ 200.00mA (ZCTpri) : 0.050A/0.15mA
N1-7
Digital Protective Relays
Dimension
110.4
221.4
230
230
112.4
20 165
120 142 23
142.4
219.4
245
N1-8
Ordering
DPR-1000 FN RS D AI 60Hz
N1
DPR-1000
N1-9
DPR
Compact design
easy to operate and set
Back-lit LCD display
Contents Features
Environmental characteristics
Constitution
N2-4
N2-5
N2-6
Additional functions N2-7
Overcurrent relay for phase and ground faults N2-8
(OCR & OCGR)
Selective Ground Relay (SGR) N2-10
Under and Overvoltage Relay (UVR & OVR) N2-12
Over Voltage Ground Relay (OVGR) N2-14
Characteristics curve N2-16
Dimensions and ordering N2-17
LSs advanced technology realized the digitalization of the measuring,
monitoring and protecting equipment in the power transmission and
distribution system.
GIMAC
GIMAC-i DPR
Desktop PC
RS232C
RS485
Protocol
Converter
GMPC -
I-NET
C- Plus communication
network
N2
DPR
-RTU
DPR
N2-5
Digital Protection Relay (DPR)
Features
Compact design
124mm(Width) 177mm(Height) 243mm(Depth)
Easy to operate and set
Set and check all the values by operating the ket button in the front.
Back-lit LCD display
Back-lit LCD diaplay provide increased visibility
Easy to check the cause of a fault and setting status by the abundant indication functions
LCD flickers when all trips happens
Adjustable current and operation time
Minute setting steps for the current and time are appropriate for network protection.
The use of the output contacts are programmable
Various settings for output contacts(Trip or Alarm) are available
For details, refer to the table in page N2-15, 19
Fault recording function
When there is a fault in the power line, it records the fault wave forms for 10 cycles
to the EEPROM.
Sequence of event function(S.O.E/Optional)
It provides the sequence of the event (relay operation and cause of the fault and
data adjustment, etc) to the higher system by the mili second intervals and it helps to
analyze the cause of the fault easily.
Various communication network configurations
-NET exclusive communication and Modbus communication(optional)
EMC/EMI test certified
N2-6
Environmental characteristics
IEC 60255-5 2kV rms. for 1 minute between all case terminals connected together
and the case earth.
Dielectric withstand KEMC 1120 2kV rms. for 1 between all terminals of independent circuits
with terminals and each independent circuit connected together
1kV rms. for I minute between each all terminals of open contact circuits
IEC 60255-5 5kV peak, 1.250, between all terminals connected together and case earth
KEMC 1120 5kV peak, 1.250, between mutual PT/CT circuits
5kV peak, 1.250, between PT/CT circuits and control circuits
High voltage impulse
3kV peak, 1.250, between mutual control circuits
3kV peak, 1.250, between all terminals of PT/CT circuits
3kV peak, 1.250, between all terminals of control power supply circuits
IEC 60255-5 DC 500V 10 and over between all case terminals connected together
and the case earth.
Insulation resistance KEMC 1120 DC 500V 5 and over between all terminals of independent circuits
with terminals and each independent circuits connected together
DC 500V 5 and over between each terminals of open contact circuits
KEMC 1120 Current circuit : In2 for 3 hours(2 times by 1 minute interval)
In20 for 2 seconds
Overload capacity
JEC-2500 In40 for 1 second
KEMC 1120 Voltage circuit : Vn1.15 for 3 hours (1 time)
IEC 60255-22-1 2.5kv peak between independent circuits and case
High frequency disturbance
Class 1.0kv peak across terminals of the same circuit
IEC 60255-22-4 4kv applied directly to power input
Fast transient disturbance
Class 2kv applied to other inputs
IEC 60255-22-2 8kv discharge in air with cover in place
N2
Electrostatic discharge (ESD)
Class 6kv point contact discharge with cover removed
KEMC 1120 Making a wave by accessing to the edge of relay
RFI
DPR
with 5W transceiver(150MHz, 400MHz)
EN 50081-2 AC power:0.15~0.50MHz, standard 79dB, average 66dB
EMI
Class 0.50~30MHz, standard 73dB, average 60dB
Operating temperature IEC 60068-2-1 -10~55
Storage temperature IEC 60068-2-2 -20~70
Humidity IEC 60068-2-3 56 days at 93% RH and +40
IEC 60255-21-2 30g, 3times/dir.
Shock Class
KEMC 1120
Vibration KEMC 1120 30Hz, 0.4mm vibration applied for 600 seconds
Enclosure protection IEC 529 IP 50(dust protected)
N2-7
Digital Protection Relay (DPR)
Constitution
Indicators
Alarm: Alarm status LED
Run: Normal operation
status LED
DISPLAY Comm: Communication
2 linesback-lit LCD for status LED
FUNC key
Shifting to each menu
ENT/RESET key M4 screw
System constitution
RS232C
RS485
Protocol
converter
GMPC-
I-NET I-NET
DPR1 DPR1
DPR2 DPR2
DPR3 GIMAC3
GIMAC4
DPR4
DPR20 GIMAC20
N2-8
Additional functions
Fault records
1. The fault curves are recorded into EEPROM when line fault happens, which will provide fast and correct grasping for the cause of a fault.
2. Storage the sample value of each phase for 10 cycles before and after the fault
5 cycles before the fault
5 cycles after the fault
8 samples for a cycle
3. A fault recording information is available for ascertaining them via communications.
DPR
2. Twenty events are stored in a buffer (maximum)
Communication specification
1. I-NET communication
High speed, high reliability of serial communication by use of the custom LSI(GC829016) developed by LSIS
1) Data rate : 250kbps
2) Cable length : 1000m(max.)
3) Insulation : Pulse Transformer
4) Connection : 4 Wires multi-drop
5) Signal modulation : Bipolar modulation
6) Connectable quantity : max. 20units per a GMPC(a protocol converter)
7) Address : Parameter setting from 1 to 255
8) Communication cable : Low capacitance LAN interface cable
Spec : LIREV AMESB 22AWG 2-pair (1/0.643)
Impedance : 10MHz, 120()
Termination : Please use it by connecting 2 resistors with each end of cable
2. MODBUS communication (Optional)
FIELD BUS open protocol applied
Please contact us before applying this communication method
N2-9
Digital Protection Relay (DPR)
Overcurrent relay for phase and ground faults (OCR & OCGR)
Features
Self-diagnostics High speed serial data communication
Fault recording International standard applied
Sequence of event(S.O.E) - IEC 60255, IEC 61000-4, KEMC 1120
N2-10
Connection methods
3phase 3wires
3phase 4wires
Terminal block
OCR/OCGR-A OCR/OCGR-B
1 F.G 2 TX0 1 Rk 2 Rl
3 DC+ 4 TX1 3 Sk 4 Sl
DC- 6 RX0 6
5
7 8 RX1
5
7
Tk
8
Tl
N2
Nk Nl
9 10 ALARM2 9 10
11 12 ALARM2 11 12
13 TRIP 1 14 ALARM3 13 14
DPR
15 TRIP 1 16 ALARM3 15 16
17 TRIP 2 18 ALARM4 17 18
19 TRIP 2 20 ALARM4 19 20
21 ALARM1 22 ALARM5 21 22
23 ALARM1 24 ALARM5 23 24
DPR-111
N2-11
Digital Protection Relay (DPR)
Selective Ground Relay (SGR)
Features
Self-diagnostics High speed serial data communication
Fault recording International standard applied
Sequence of event(S.O.E) - IEC 60255, IEC 61000-4, KEMC 1120
N2-12
Connection methods
Terminal block
SGR
1 F.G 2 TX0
3 DC+ 4 TX1
5 DC_ 6 RX0
7 8 RX1
9 GPTk 10 GPTl
11 12
13 ZCTk 14 ZCTl N2
15 16
17 18 ALARM1
19 20 ALARM1
DPR
21 TRIP 22 ALARM2 DPR-211
23 TRIP 24 ALARM2
N2-13
Digital Protection Relay (DPR)
Under and Overvoltage Relay (UVR & OVR)
Features
Self-diagnostics High speed serial data communication
Fault recording International standard applied
Sequence of event(S.O.E) - IEC 60255, IEC 61000-4, KEMC 1120
DPR-411
Operating time Time delayed definite element 0.05, 0.1~10seconds in a 0.1 step
Additional function Self-diagnostics
Fault records
Sequence of event(S.O.E)
Communication mode I-NET
Display Back-lit LCD (Dot matrix)
Output contacts Switching capacity Make 10A/250Vac, 0.5sec, resistive
Break 1A/250Vac 0.1PF
Constitution(6EA) Note2) Trip relay 2a, 1250VA and over
Alarm relay 3a
System fail relay 1a
Type At Trip operation Trip relay+Trip LED+Alarm relay
Self-diagnostics error System fail relay+Alarm relay
At Normal RUN LED
Insulation resistance DC 500V 100 and over
Dielectric withstand 2kV(1kV) rms, and over for 1minute
High voltage impulse 5kv(3kV) peak and over applied for 1.250
Overload capacity Voltage circuit Vn1.15 for 2 hours
Temperature Operating -10~55
Storage -20~70
Humidity 80% RH (Non- condensing)
Applied standard IEC 60255, IEC 61000-4, KEMC 1120
Weight 3.1kg
Dimension 124(W)177(H)243(D) mm
Note 1) No-voltage lock : The lock function can be selected not to be tripped when no input voltage appeared (20% and under of rated voltage)
Note 2) The output contacts are programmable.
N2-14
Connection methods
Terminal block
OVR/UVR
Definite Time 1 F.G 2 TX0
3 DC+ 4 TX1
5 DC_ 6 RX0
7 8 RX1
9 Rk 10 Rl
11 Sk 12 Sl
13 Tk 14 Tl
15 16 ALARM1
17 TRIP1 18 ALARM2
19 TRIP1 20 ALARM3 N2
21 TRIP2 22 ALARM4
23 TRIP2 24 ALARM COM
DPR
DPR-411
Trip 1
Note 3)
for Trip
Trip 2
OVR
Alarm 1
/
Alarm 2
UVR
for Alarm
Alarm 3
Alarm 4
1phase and
Self-
over R,S,T all 1phase and 3phase RphaseSphaseTphase Overload
Purpose of contacts diagnostics No use
fault among phase fault over trip Trip Trip Trip Trip Pre alarm
Error
of R,S,T
Note 1) Alarm relay can not be used for Trip(CB control) contacts.
Note 2) DPR-311 is available for selectable use as OVR or UVR, and it will be set on UVR when shipment.
Note 3) DPR-411 is used as OVR, UVR multiple relay. The Trip 1 is OVR and Trip 2 is for UVR as Trip contacts and it can be selected by Trip or Trip- 3phase.
N2-15
Digital Protection Relay (DPR)
Over Voltage Ground Relay (OVGR)
Features
Self-diagnostics High speed serial data communication
Fault recording International standard applied
sequence of event(S.O.E) -IEC 60255, IEC 61000-4, KEMC 1120
N2-16
Connection methods
Terminal block
OVGR
1 F.G 2 TX0
3 DC+ 4 TX1
5 DC_ 6 RX0
7 8 RX1
9 GPTk 10 GPTl
11 12 N2
13 14
15 16
17 18 ALARM1
DPR
19 20 ALARM1
21 TRIP 22 ALARM2
DPR-511
23 TRIP 24 ALARM2
OVGR Alarm1
for Alarm
Alarm2
Self-diagnostics
Purpose of contacts Trip Trip alarm
error
Note) Alarm relay can not be used for Trip(CB control) contacts.
N2-17
Digital Protection Relay (DPR)
Characteristics curve
Standard inverse - (OCR, OCGR, OVGR) Very inverse - (OCR, OCGR, OVGR)
Standard inverse time (SI) Very inverse time (VI)
100 100
10
10
Operating(sec)
Operating(sec)
1
1.0 1.0
0.4
1 0.4 0.3
0.3 0.2
0.1
0.2 0.1
0.05
0.1
Extremely inverse - (OCR, OCGR, OVGR) Long inverse - (OCR, OCGR, OVGR)
Extremely inverse time (EI) Long inverse time (LI)
1000 1000
100
100
10
Operating(sec)
Operating(sec)
10
1.0
1
0.4
0.3
0.2
1.0
1
0.1 0.4
0.1
0.3
0.2 0.05
0.1
0.01 0.05 0.1
1 10 100 1 10 20
Current(Multiples of setting, I/Is) Current(Multiples of setting, I/Is)
N2-18
Dimensions and ordering
Dimensions
Cut-out dimension
N2
DPR
Ordering
DPR - 0 1 1
4 OVR/UVR
5 OVGR
Note) DPR-311 is available for selectable use for OVR or UVR and DPR-411 is multi-relay with OVR and UVR
N2-19
IMC-III
Direct start
Y- start
Reactor start
For/Rev
start
Inverter start
Overcurrent
Under current
Unbalance
Stall/Locked
Phase rotor
Earth Phase loss
fault reverse
Various protection function
Safely protection for over current, Under current,
Phase loss, Unbalance, (Stall, Lock)
Earth fault, Alarm function.
O-4
Emergency
Stop
SCADA
Water Level
O-5
Intelligent Motor Controller
Main characteristic
TIMER CT
Internal
Front
Minimizing wiring
work
Reduce labor cost
Compact size panel
Easy maintenance
Good design
Various function
O-6
The moment stopping of power supply compensation and Restart
The moment stopping of power supply compensation Ex) Incase of restarting delayed time 30S
- Line current reduces under 65% of rated voltage.
- When the moment stopping of power supply within 10S,
IMC-III makes it restart same as before condition.
Restart delayed time(0~300S)
- When the line voltage recovers over 75% rated voltage, Information
it can be restarted.
It can be changed operation mode (ON, OFF) and
- when it restarted, IMC-III makes it sequence restart 0~300s for count time during countdown
prohibition overload. Changed operation mode can be applied after
- Indication of Restart delayed time countdown. finishing count.
Operating condition and maintain operation mode When the short stopping power supply generates
under 100ms, IMC-III dose not detect, so the motor
- It can be maintained before the moment stopping power will maintain normal condition
supply condition(Local, MCC, Auto, W/L, Remote)
Digital ampere-meter
Bar LED
It can be monitored indication of R, S, T current, and load ratings(%) by Bar LED. Indication of load ratings
O
Self-supervision and contactor failure function
IMC-III
IMC-III can be checked self-supervision like a memory fault. When the motor starts/stops,
that indicates Error.No and turn on Sys.Fail LED by supervising Input/output condition.
Communication function
Its possible to communicate with other system and organize various communication Network by
MODBUS/RS-485. And its also possible to communicate with system by Analog current signal(4~20mA).
So that makes it possible to interchange by using TD(Transducer).
O-7
Intelligent Motor Controller
Ratings and function
Rating
Model IMC-III
Operating time Characteristic Inv/Def time
Current range(A) 0.125~60A(Within 1 model)
Time setting (s) Inverse time 1~60sec/1sec(Class)
Definite time D-Time * 1~200sec/1sec
O-Time * 1~60sec/1sec
Auto re-closing time 1~20min/1min, OFF
Control power Voltage AC 110V or AC 220V(15%)
Frequency 50/60Hz
Power consumption Under 6W
Output contact Capacity 5A/250VAC impedance load
(9EA) Composition Operating contact 3a Forward/Reverse, Y-, Reactor, Inverter start
Condition contact 3a Local, Auto, W/L condition indication
Timer contact 2a ON delay, OFF delay
Trip contact 1a Fault output contact
Input contact Operating input 5a Local, Auto, Water, Level, Flow, switch operating inout
(9EA) MC condition input 1a Sequence condition monitoring(LED)
External trip 2a Emergency stop, Sequence
ZCT Ratings 200mA/0.1mA(ZCT)
Specification 25, 40, 80
Indication 7-Segment 3-Phase current, Trip cause, Settings
LED Operating condition, Trip, System fail settings
Self-Diagnostic System fail LED and err indication
Communication(Option) Modbus/RS-485 or 4~20mA
Installation Inside the panel
Separate cable MCT cable 2m base(4m cable option)
Insulation voltage AC 2kV(1.5kV) / 1 min
Impulse voltage Over AC 5kV(3kV), 1.2x50s
Insulation resistance Over DC500V 10M
Power frequency magnetic field 100A/m, 50Hz
Burst disturbance Common 2.5kV
Differential 1.0kV
Fast transients disturbance Input 2kV, Other Input 1kV
Electrostatic discharge Air 8kV, Contact 6kV
RFI 30cm near electric wave by
5W transceiver(230MHz)
EMI AC power : 0.15~0.50MHz, Standard : 79dB, Average : 66dB
0.50~30MHz, Standard : 73dB Average : 60dB
Operating temperature -10 ~ 55
Storage temperature -20 ~ 70
Relative humidity 93% @40 for 56days
Standard IEC 60255, IEC 61000-4, IEC 60068-2, EN 50081-2
Weight 0.6kg(MCT 0.35kg)
Dimension Main unit 148(W) 100(H) 74(D) mm
MCT 151(W) 55(H) 33(D) mm
* D-Time(Delay time) : It is delay time for IMC-III start during motor start time
* O-time (Operating delay time) : When over current generates more then setting current, that makes it delayed until IMC-III operated.
O-8
Motor protection
Operating condition Time Remark
Over Inverse Over 110% setting current 1~60s/1s 600% standard operating time
current Definite time Over 105% setting current 1~60s/1s Delay time 1~200s
Phase fault Over 70% current phase unbalance Within 1.5s
Phase unbalance Current phase unbalance 30~50% Within 5s
Reverse phase Reverse the current phase Within 0.1s Over 110% minimum ratings
Under current Rating current 30~70% Within 3s
Holding Stall Rating current 150~300% Within 5s
Detection after over current setting time
Locked rotor Rating current 200~700% Within 0.5s
Ground fault The current rating 0.1~2.5A setting 0.05~1.0s Ground fault delay operation
Pre-alarm Over 120% setting value Bar-LED blinking
Sequence function
Contents Remark
Operating type Direct operation Non-reversible direct operation
operation
Y- Y operation time 1~120s/1s
switching time
Y- 0.05, 0.1, 0.2s
Forward / Reverse operating Reversible direct operation
Reactor Reactor time 1~120s/1s
Inverter Inverter delayed time ON 1sec/0.1sec
Instantaneous Compensation time OFF 1~10s /1s
under voltage Re-operation delay time 0~300s /1s
compensation Under voltage detection (Rating control voltage 65%) 10%
Recovering voltage detection (Rating control voltage 75%) 10%
User contact Normal Normal mode
point mode Time delay ON delay
0~300s/1s
OFF delay
Flow switch ON delay
Comparing
OFF delay 0~300s/1s
Timer ON delay timer
Comparing timer
Remote control Local LOP(Local Operation Panel) O
MCC Motor Control Center
Auto PLC, DDC, DCS auto operation
W/L Water Level
IMC-III
Communication function
Type Contents Specification Remark
Protocol Modbus_RTU
Communication RS-485
Modbus Operation Differential
/ Baud rate 9600, 19200, 38400bps
RS-485 Length Max 1.2km Different from local situation
Cable RS-485 Shielded twist 2-pair cable
Transmission Half-duplex
Max in/Output voltage -7V ~ +12V
O-9
Intelligent Motor Controller
Main function description
Protection function
Overload protection(49)
Overload protection function senses current which is flowing on
the motor, and tracing the heat, and then protects. When the
heat capacity approaches, it generates overload trip, and this
heat capacity is calculated by characteristic curve and It.
Class1 ~Class60 overload characteristic curve is determined by
sec
sec
setting motors rated current, considering motor operating time,
setting operating time 1s~60s by according to 600% of setting
current.
When you choose the definite time characteristic, it starts over
current after Delayed time and if over current keeps applying
over Operation-time, it generates trip.
current current
<Inverse time> <Definite time>
Stall/Locked rotor protection (48/51LR)
When the fault generates like locked rotor, the mechanical units
like pump, fan can be damaged easily. IMC-III prohibits stall, locked rotor, start failure, over
current and open the circuit when the current increases rapidly, load torque exceeds the motor
torque. But IMC-III has delayed time, it can not be tripped by operating current.
O-10
Fault analysis, fault recording Self-diagnostic function
User can check fault current value by UP/DOWN button and fault
When MC condition input contact point is ON after
recording can be checked by [ESC + ENT].
output contact OFF operating.
Motor start
1) If F/S (FlowSwitch) is applied within setting comparison timer-ON
Delay timer after ON operation. After ON delay timer, motor will
operate.
2) If F/S is not applied, ON will be canceled, t2-F will be
indicated, will maintain OFF condition.
1) After ON operation, it passed ON delay time, 88M will be ON O
and motor will operate. Motor operation
2) After OFF operation, it passed OFF delay time, 88M will be
1) During motor operation, if F/S input is out of state, 88M will be
IMC-III
O-11
Intelligent Motor Controller
Operation and setting
Front view
Current & Operation mode
Information LED
R, S, T Phase
Condition LED
indication
Motor condition
LED
Setting value
Motor start
choice & move to
button
contents
Operation mode
Move to previous
button
button
Indication of trip
IMC-III main unit analysis,
Indication of
setting group.
MCT
RX0
3) When user push the ENT button after selecting group, it
4~20mA pole
pole RX1 move to the detail setting contents.
TX0
TX1
4) After selecting contents by pushing UP/DOWN button, if
user push the ENT button, the setting value will be
stored.
5) When UP/DOWN button is pushed, the setting value
will change, so that after selecting contents, if you push
the ENT button , setting value will be stored.
6) After setting, if user push the ESC button, IMC-III will be
returned normal operating condition.
Note) 1. Pls note that setting value can be changed during motor operation.
2. If user did not operate for 10S , Setting value and group setting contents will
returned to current indication mode automatically.
O-12
Group No. Setting Indication Setting value Default value Remark
1 Characteristic
(Over current protection) Inu/dEF Inu Inverse/Definite time selection
6 Start type selection dir/y-d/F-r/Ind/Iut dir Direct, Y-. Reactor, Inverter start
A. grp
3 Phase-fault
OFF/On On
Protection function
protection enabled
7 Ground fault protection OFF/On OFF OFF setting in case of inverter start
B. grp
8 Ground fault
0.1, 0.2, 0.5, 1.0, 1.5, 2.0, 2.5(A) 0.1
operation current
indicatingOrH
Additional function
6 User contact
nor/t-d/F-S nor Normal/Time delay/Flow switch
point mode
O-13
Intelligent Motor Controller
Operation and setting
Fault recording
IMC-III provides fault recording function even if power is OFF. If user push the ESC + button, user can check the Fault analysis and
fault current value. If user push the RESET button, fault analysis and fault recording will be deleted.
If there is no string data, it will be indicated non And then if user push the ESC + button, it will come back to normal mode.
3-phase current
circulation indication
Maximum phase
current indication
Note) If user push the RESET button for over 10s, IMC-III will come
back first manufacturing status. At this time, user has to know
that setting and storing value is deleted and comes back first
manufacturing status.
O-14
Total operation time
Total operation time check : day Hour minute
ex) If total operation time is 50hours 50 minutes : 2 days 2.50(2 hours 50 minutes)
Operation time Total operation time converse day Extra hour, minutes
ex) If operation time is 50 hours 50minutes : 50 hours 2days 2.50 (2 hours 50 minutes)
O-15
Intelligent Motor Controller
Wiring method
start
Y-
O-16
For/Rev start
Reactor start
O
IMC-III
O-17
Intelligent Motor Controller
Wiring method
Inverter start
Inverter start
ON(INV)
88M
* INPUT (220VAC) * Comm. Port 88I
0~1sec / 0.1sec
1,3,4,5,6-2 (COM1) RS-485 4~20mA
7,8,10,11-9 (COM2) RX0 (-) Bypass(Direct) start
* OUTPUT RX1 (+)
12,13,14,16-15 (VCC1) TX0 REV(BYS)
FO/FC start(Forward)
O-18
S/V valve start(Direct)
If ON S/W applied, S/V(Solenoid Valve) becomes ON, OFF Delay Timer T1 becomesON.
If F/S (Flow Switch) applied within [T2-T3] time, ON Delay timer T3 becomes ON.
If T3 becomes ON, comparison timer T2 becomes OFF after setting time. And then Motor will operate because 88MX becomes ON.
At this time, if F/S does not apply within setting [T2-T3], ON will be canceled and thent2-Fwill be indicated.
Comparison timer T2 has to be set more than ON Delay Timer T3 , user has to consider time margin until F/S application.
If OFF s/w applied for motor stop, S/V and motor will be OFF delay same as T1 time
If F/S input is removed during motor operation, 88MX will be OFF, motor will be stopped. At this time S/V will be OFF.
Terminal number
O
Terminal Terminal
Explanation Explanation
No No
1 LOP selection input 14 Y-start/Reverse rotation/Reactor/Bypass contact point output
IMC-III
* Normal mode
20-21 : Operation alarm(OrH) output
[ 20-22 : not in use
O-19
Intelligent Motor Controller
System configuration
O-20
O IMC-III
O-21
Intelligent Motor Controller
Accessories
Dimension(mm) A B C D E F
LZT-025(I) 81 43 43.5 68 81 25
LZT-040(I) 101 43 53.5 88 101 40
LZT-080(I) 146 43 76 133 146 80
Note) This product is only for IMC, and user has to use this ZCT for protection ground fault.
SCT(3CT)
1CT 3CT(Combination of 1CT 3EA) Ratings
Model 3CT
SCT-100 100:5A
Current SCT-150 150:5A
transformer SCT-200 200:5A
ratio SCT-300 300:5A
SCT-400 400:5A
Class 1.0
Dimension Burden 5VA
Insulated voltage AC 600V
Insulated internal pressure 2kV
Insulation resistance 10M(DC 500V Megger)
65
65
Mounting Panel
64 82
120
27.5
65
32.5
256
82 82
256
Note) 1. This product is only for EMPR, IMC, user must not use for other service
2. Pls order each 3EA with IMC-III, because this product is 1CT type.
O-22
Dimension & Ordering
Dimensions
IMC-III main unit
MCT
O
IMC-III
Ordering
O-23
GIMAC-PQ
MODBUS/RS-485
Dual communication
P
Rating
Model GIMAC-PQ
P-4
Power quality functions
Measurement functions
P-5
Power Quality Meter
External
Status LED
Power
Comm 4 Text LCD
20
Alarm
Sys Err
REMOTE/LOCAL CB ON/OFF
Transfer KEY Control KEY
State LED State LED
Front View
P-6
Initial menu
MMI
Setting menu
P-7
P
GIMAC-PQ
Power Quality Meter
Wirings
2PT application
OPEN DELTA ( )
P-8
3P4W
R S T
Va
Vb
Vc
Vo
Ia
Ib
Ic
1P3W 1P2W
R S R
P
GIMAC-PQ
P-9
Power Quality Meter
Dimension
Cutout size
P-10
Ordering
P
GIMAC-PQ
P-11
GIMAC-IV
GIMAC-IV /
APFC / DC
Digital Integrated Metering & Control Device
Technical Specifications
Rating
Model GIMAC-415
PT 10~230V
Voltage
GPT 2.2~230V
Current CT 0.05~6A
PT Max. 1.0VA
Burden
CT Max. 1.0VA
3680VA, 480W
2EA for power
AC230V 8A / DC30V 8A, Inductive load(cos=0.4, L/R=7ms)
1840VA, 240W
Output contact
AC230V 12A / DC25V 12A, Resistive load
2760VA, 300W
8EA for alarm
AC230V 6A / DC25V 6A, Inductive load(cos=0.4, L/R=7ms)
1880VA, 150W
2 In for 3 hours
Current circuit
Overload withstand 20 In for 2 seconds
Air 8kV
ESD(Electrostatic Discharge)
Contact 6kV
Non-impact place
Others
Non-air pollution place
Weight 3.6 kg
Q1-4
Measurement functions Q1
Model Measurement Display range Accuracy Remarks
GIMAC-IV
GIMAC-415 Current, I 0.000A ~ 999.99kA 0.2% Ia, Ib, Ic, In
Voltage, V 0.000V ~ 999.99kV 0.2% Va, Vb, Vc, Vab, Vbc, Vca
Active power, Watts 0.000W ~ 99999.9MW 0.5%
Reactive power, Var 0.000Var ~ 99999.9MVar 0.5% + : Forward
Apparent power, VA 0.000VA ~ 99999.9MVA 0.5% - : Reverse
Active energy, Wh 0.000Wh ~ 99999.9MWh 0.5%
Reactive energy, Varh 0.000Varh ~ 99999.9MVarh 0.5%
Frequency, F 45 ~ 70Hz 0.05Hz
Power factor, PF -1.000 ~ 1.000 0.5% cos (+ : Lag, - : Lead)
Phase 0.000~ 360.00 0.5
Normal current, I1 0.000A ~ 999.99kA
Reverse phase current, I2 0.000A ~ 999.99kA
Zero phase voltage, Vo 0.000V ~ 999.99kV 0.5% Vo, Vo_max
Normal voltage, V1 0.000V ~ 999.99kV
Reverse phase voltage, V2 0.000V ~ 999.99kV
Unbalanced factor 0.000 ~ 100.00%
Harmonics I 0.000A ~ 999.99kA 2nd ~63th
Harmonics V 0.000V ~ 999.99kV 2nd ~63th
THD(V, I)
TDD(I)
k-Factor
Demand I 0.000A ~ 999.99kA Peak demand
Demand W 0.000W ~ 99999.9MW Peak demand
AI (Analog Input) 4.000 ~ 20.00mA 0.5%
Communication
Q1-5
Digital Integrated Metering & Control Device
Technical Specifications
Model GIMAC-415 AP
Demand Controller
Model GIMAC-415 DC
Q1-6
Functional Block Diagram
Q1
GIMAC-IV
50/51 50/51G
A V W Wh
Var Varh F PF
GIMAC-415NO DPR-1000
DC
Demand
Controller
APFC
Automatic Power
Factor Controller
Q1-7
Digital Integrated Metering & Control Device
External
Status LED
Power
Comm 4 Text LCD
20
Alarm
Sys Err
AUTO/MANUAL
Transfer KEY CB ON/OFF
State LED
Control KEY
State LED
REMOTE/LOCAL
Transfer KEY
State LED Front View
Q1-8
Initial menu MMI
Setting menu
Q1-9
GIMAC-IV
Q1
Digital Integrated Metering & Control Device
Wirings
3P3W
2PT application
OPEN DELTA ( )
Q1-10
3P4W Q1
R S T
GIMAC-IV
Va
Vb
Vc
Vo
GIMAC-IV
Ia
Ib
Ic
1P3W 1P2W
R S R
GIMAC-IV GIMAC-IV
Q1-11
Digital Integrated Metering & Control Device
Dimension
Cutout size
Q1-12
Ordering
Q1
GIMAC-415 NO RS M AC/DC 110V 60Hz AI
GIMAC-IV
Model Protocol Frequency
NO Normal M Modbus 60Hz
AP APFC I I-NET 50Hz
DC Demand Control D DNP3.0
PD APFC, D/C
Demand Controller
Q1-13
GIMAC-II plus
MODBUS/RS-485, I-NET
Self-diagnosis
Q2
Rating
Model GIMAC-115
Q2-4
Measurement functions
Model Measurement Display range Accuracy Remarks
GIMAC-115 Current, I 0.000A ~ 999.99kA 0.3% Ia, Ib, Ic, In
Voltage, V 0.000V ~ 999.99kV 0.3% Va, Vb, Vc, Vab, Vbc, Vca
Active power, Watts 0.000W ~ 99999.9MW 0.5%
Reactive power, Var 0.000Var ~ 99999.9MVar 0.5% + : Forward
Apparent power, VA 0.000VA ~ 99999.9MVA 0.5% - : Reverse
Active energy, Wh 0.000Wh ~ 99999.9MWh 0.5%
Reactive energy, Varh 0.000Varh ~ 99999.9MVarh 0.5% Q2
Frequency, F 45 ~ 70Hz 0.05Hz
GIMAC-II Plus
Power factor, PF -1.000 ~ 1.000 0.5% cos(+ : Lag, - : Lead)
Phase 0.000~ 360.00 0.5
Normal current, I1 0.000A ~ 999.99kA
Reverse phase current, I2 0.000A ~ 999.99kA
Zero phase voltage, Vo 0.000V ~ 999.99kV 0.5% Vo, Vo_max
Normal voltage, V1 0.000V ~ 999.99kV
Reverse phase voltage, V2 0.000V ~ 999.99kV
Unbalanced factor 0.000 ~ 100.00%
Harmonics I 0.000A ~ 999.99kA 2nd ~15th
Harmonics V 0.000V ~ 999.99kV 2nd~15th
THD (V, I)
TDD (I)
k-Factor
Demand I 0.000A ~ 999.99kA Peak demand
Demand W 0.000W ~ 99999.9MW Peak demand
AI (Analog Input) 4.000 ~ 20.00mA 0.5%
Communication
Type Item Specifications Remarks
Baud rate 250kbps
Distance Max. 1km
Cable spec Low Capacitance LAN Interface cable
LIREV-AMESB 22AWG 2-Pair(7/0.254TA)
I-NET Insulation Pulse Transformer LS custom protocol
Impedance 10MHz, 120
Wiring 4-Wire Multi-drop
Termination 120(2EA)
Modulation Bipolar
Operation mode Differential
Baud rate 9600, 19200, 38400bps
Distance Max. 1.2km
MODBUS/RS-485
Cable spec Standard RS-485 Shielded Twist 2-Pair cable
Transmission Half-Duplex
Max. input/output -7V ~ +12V
Fault indication
LED indicator
Digital
Troubleshooting after reset Reset after troubleshooting
input Normal Fault input
Troubleshooting Reset Reset Troubleshooting
Fault DI_1~8 Off Blink Blink Off On Off
Q2-5
Digital Integrated Metering & Control Device
External
Status LED
Power
Comm 204 Text LCD
Alarm
Sys Err
REMOTE/LOCAL CB ON/OFF
Transfer KEY Control KEY
State LED State LED
Front View
Q2-6
Wirings
3P3W
Q2
GIMAC-II Plus
GIMAC-II Plus
2PT application
OPEN DELTA ()
Q2-7
Digital Integrated Metering & Control Device
Wirings
3P4W
R S T
Va
Vb
Vc
Vo
GIMAC-II Plus
Ia
Ib
Ic
1P3W 1P2W
R S R
Q2-8
Dimension& Ordering
Dimension
Q2
GIMAC-II Plus
Cutout size
Ordering
Q2-9
GIMAC-
MODBUS/RS-485
Protecting mis-wiring
R1
Rating
Model GIMAC-i
Self-diagnosis
R1-4
Measurement functions
Vavg 0.3% -
Voltage Vab, Vbc, Vca 0.3% -
Va, Vb, Vc 0.3% -
lavg 0.3% -
Current la, lb, lc 0.3% -
Load factor la, lb, lc - -
VabVbc, VabVca - 0.5 3P3W
Vabla, Vablb, Vablc - 0.5 3P3W
Phase
VaVb, VaVc - 0.5 3P4W
Vala, Vblb, Vclc - 0.5 3P4W
P 0.5% IEC 1036
Pa, Pb, Pc - 0.5% IEC 1036
Power
Q 0.5% IEC 1036 R1
Qa, Qb, Qc - 0.5% IEC 1036
S 0.5% IEC 1036
GIMAC-i
Sa, Sb, Sc - 0.5% IEC 1036
Wh 0.5% IEC 1036
Varh 0.5% IEC 1036
Energy rWh - 0.5% IEC 1036
rVarh - 0.5% IEC 1036
VAh 0.5% IEC 1036
Frequency F(Hz) 0.05Hz -
PF
+ : Lag
Power factor PFa, PFb, PFc -
- : Lead
DPFa, DPFb, DPFc -
THD(V) - - Va(ab), Vb(bc), Vc(ca)
THD
THD(I) - - Ia, Ib, Ic
1st ~ 15th Harmonics (V) - - Va(ab), Vb(bc), Vc(ca)
Harmonics
1st ~ 15th Harmonics (I) - - Ia, Ib, Ic
Demand W - -
Demand
Demand la, lb, lc, lavg - - -
max la, max lb, max Ic, max lavg
- - -
max Va(ab) THD, max Vb(bc) THD
max Vc(ca) THD
- - -
max la THD, max lb THD,
max lc THD - - -
MAX
max W - - -
max VAR - - -
max VA - - -
max Demand lavg, la, lb, lc - - -
max Demand W - - -
R1-5
Digital Power Meter
External
PHASE OPTION
(EX TYPE)
B PHASE
UP KEY
OPTION
(EX TYPE)
DOWN KEY
C PHASE
ENTER KEY
Minus (-)
1000 unit
R1-6
Wirings
3P4W
LINE
LINE
R S T N
R S T N
Fuse, 2A
Fuse, 2A
CCT
R1
GIMAC-i
LOAD LOAD
3P3W
LINE
LINE
R S T
R S T
Fuse, 2A
Fuse, 2A
CCT CCT
LOAD LOAD
R1-7
Digital Power Meter
Wirings
LINE
R S T LINE
Fuse, 2A R S N
Fuse, 2A
CCT
CCT
LOAD LOAD
1P 2W
LINE
R N
Power Supply
CCT
LOAD
R1-8
Dimension & Ordering
Dimension
144
23.5 61.5 89 144
85
R1
GIMAC-i
86
92
86 92
Ordering
R1-9
GIMAC-DC
DC Meter
MODBUS/RS-485, 422
R2
Rating
Model GIMAC-DC
Measurement functions
R2-4
External
Comm.
R2
GIMAC-DC
Rectifier
R2-5
Digital Integrated Meter
Wirings
Rectifier
Shunt
Shunt
Fuse, 2A Fuse, 2A
Rectifier
Shunt
Shunt
Fuse, 2A Fuse, 2A
Rectifier
Shunt
Shunt
Fuse, 2A Fuse, 2A
Rectifier
Shunt
Shunt
Fuse, 2A Fuse, 2A
R2-6
Dimension & Ordering
Dimension
VAC
COMM
ACV HZ
M ACV
THD
M DCV
M DCA
DCV VDC
IOUT
DCA
IBAT
R2
Ordering GIMAC-DC
R2-7
For your safety, please read user's manual thoroughly before operating.
Contact the nearest authorized service facility for examination, repair, or adjustment.
Please contact qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!
Safety Instructions Any maintenance and inspection shall be performed by the personnel having expertise concerned.
www.lsis.biz
2009. 01 Digital Protection & Measurement Device (E) 2009. 01/(01) 2009. 01 Printed in Korea STAFF