Smart-MEC

Digital Protection &


Measurement Device

Electric Equipment
LSIS protection and measurement products specializes in the protection and
monitoring of electricity distribution networks, making your power distribution
easier and more reliable. You can either integrate these products into your
intelligent switchgear or use them as stand-alone multifunction units. In addition,
all of these products provide versatile communications as well as sophisticated
functionality for event, alarm and fault analysis.

The whole GIPAM, GIMAC product family for line, motor, generator protection
and monitoring offers you an integrated solution which starts with extensive
protection, measurement and control functionality.
Contents
GIPAM-2200 M1
GIPAM-115 M2
DPR-1000 N1
DPR N2
IMC-III O
GIMAC-PQ P
GIMAC-IV Q1
GIMAC-II plus Q2
GIMAC-i R1
GIMAC-DC R2
Digital Protection device
GIPAM- GIPAM- GIPAM- GIPAM- GIPAM-
DEVICE DPR-1000 DPR-011 DPR-111
2200F 2200T 2200M 2200G 115FI
Phase time overcurrent 51
Ground time overcurrent 51N/G
Phase instantaneous overcurrent 50
Ground instantaneous overcurrent 50N/G
Number of phases protected 3+N 3+N 3+N 3+N 3+N 3+N 3+N 3+N
Hiset & lowset 50H/50L
instantaneous overcurrent 51H/51L
Negative sequence time overcurrent 46
Negative sequence overvoltage 47 (POR)
Thermal overload 49
Directional ground 67N
Sensitive ground 67G
Overvoltage ground 59N, 64
Undervoltage 27
PROTECTION

Overvoltage 59
Stall 48
Locked rotor 51LR
Undercurrent 37
Underfrequency 81U
Overfrequency 81O
Motor differential 87M
Transformer phase differential 87T-P
Transformer ground differential 87T-G
Sync check 25
Forward/reverse active power 32P
Reverse reactive power 32Q
Underpower 37P
Breaker failure 50BF
Trip circuit supervision 74TC
Supervision of startingtime/Notching 66
Lock-out 86
Temperature 38
Power outputs 2 2 2 2 2 2 2 2
Digital outputs 10 10 10 10 8 (Fixed) 5 5 5
I/O

Digital inputs 6 6 6 6 3 3
Analog outputs
Analog inputs 4 4 4 4 2
Ia, Ib, Ic, In
Io, I1, I2 Io, I2 Io, I2 Io, I2 Io, I2 Io, I2
Va, Vb, Vc, Vab, Vbc, Vca
Vo, V1, V2 Vo, V2 Vo, V2 Vo, V2 Vo, V2 Vo Vo
Watts
Vars
MONITORING & METERING


kWh
kVarh
Frequency
Power factor
Trip circuit supervision
Trip relay supervision
VT fuse failure
Full load current %FLC
Motor starting current Is
Motor starting time Ts
Motor starting capacity %Q
Temperature
CB operation
CB operating time
I, V 0.5% 0.5% 0.5% 0.5% 0.5% 0.5%
Accuracy
W, Wh 1.0% 1.0% 1.0% 1.0% 1.0%
Event recording 800 800 800 800 128 128 20 20
ADDITIONAL

Fault recording 200 200 200 200 32 32 1 1


Fault wave recording Max. 64 cycle Max. 64 cycle Max. 64 cycle Max. 64 cycle Max. 32 cycle
Auto restart
Sequence logic
Programmable logic
PC Interface IrDA port
COMMUNICATION

RS-485(422)
Ethernet
Fiber optic
I-NET (Custom LS)
Modbus
DNP3.0
Digital Measurement device
DPR-211 DPR-311 DPR-411 DPR-511 IMC-III DEVICE GIMAC-PQ GIMAC-415 GIMAC-115 GIMAC- i EX GIMAC- i NO

Ia, Ib, Ic, In


Io, I1, I2
Va, Vb, Vc, Vab, Vbc, Vca
Vo, V1, V2
3+N 3+N 3+N 3+N 3+N Watts
Vars
VA
kWh
(POR) kVarh
VAh

MONITORING & METERING


Reverse Watts
Reverse Vars
Reverse VA
Reverse kWh
() Reverse kVarh
Frequency
Power factor
Phase
Unbalanced factor
Harmonics (V, I) (15th) (63th) (15th) (15th)
THD (V, I)
TDD (I)
k-factor
Demand I
Demand W
CB operation
CB operating time
I, V 0.2% 0.2% 0.3% 0.3% 0.3%
Accuracy
W, Wh 0.5% 0.5% 0.5% 0.5% 0.5%
Power outputs 2 2 2
Digital outputs 8 8 8
I/O

Digital inputs 10 10 10
1 2 2 1 Analog inputs 2 2
2 4 4 2 9 Power quality
8 Sag
1 Swell
ADDITIONAL

Interruption
Undervoltage
Io Overvoltage
Auto power factor controller Option
Vo Vo Demand controller Option
Event recording 256 300 256
Fault wave recording Max. 60cycle
COMMUNICATION

RS-485(422)
I-NET (Custom LS)
Modbus
Dual

20 20 20 20
1 1 1 1 1



GIPAM-2200

Digital Integrated Protection &


Monitoring Device

The optimum protection which leads protective


diagnosis and reliability improvement of
own protection relay, quick
accident analysis and
maintenance & repair,
preventive control,
minimizing accident spread.
M1

Contents Features
Functional Block Diagram
Technical Specifications
M1-8
M1-11
M1-12
Communications M1-14
External & Structure M1-15
Man Machine Interface M1-16
Characteristics M1-19
Time Characteristic Curves M1-22
Network Systems M1-26
Wirings M1-28
Contact Usage M1-33
Dimension M1-36
Ordering M1-37
GIPAM-2200 series are multifunction microprocessor-
based protection equipments suitable for all types of
application such as distribution feeders. It can be also be
used for management backup protection of incomings,
feeders, transformers and high tension motors.

Over current protection function includes protection elements such GIPAM-2200 can arrange easily as demand of usersneed as
as over current, over current ground fault, selective ground fault well as apply to various sequences because the logic design
current, directive ground fault current, negative sequence over through a simple logic program is available regarding
current in each phase with regard to time delay or instantaneous input/output contacts.
elements. Moreover, it supports under voltage, over voltage, GIPAM-2200 series provides various monitoring, measuring
ground fault over voltage, phase reversal over voltage, etc. functions and it does easy accident analysis by storing data
regarding voltage protection and thermal overload, rocked rotor, fires such as 800 events, 200 faults and maximum 64 cycle s
differential, ground fault differential regarding various kinds of fault waveform. Furthermore, when accidents happens, alarm
protection functions. As it has differential, ground fault differential signal can put out during the operation in terms of self testing.
to protect a transformer, and the protection of secondary wires GIPAM-2200 series provide IrDA Serial Ports for connecting
transformer is available too. PC which is performing the operation program, and they are

M1-4
M1

GIPAM-2200

equipped with RS-485, optic communication ports to


communicate with the upper systems. In addition, they support
DNS 3.0, MODBUS protocol widely spread in the industrial
electric section and I-NET which is the exclusive express
communication system by LSIS.
Setting all protection function and monitoring as well as
checking many kinds of functions are available through the
operation program based on PC interface.

M1-5
The optimum protection which leads protective
diagnosis and reliability improvement of own
protection relay, quick accident analysis and
maintenance & repair, preventive control,
minimizing accident spread.

52T

PT(VT) Failure

Trip Circuit Supervision &


Trip Relay Supervision

Select Before Operating (SBO) & Trip Circuit Supervision (TCS) &
Circuit Breaker Failure (CBF)
Check Before Operating (CBO) Trip Relay Supervision (TRS)
The improvement of reliability and Supervise circuit breaker trip circuit Upper breakers trip in case of Circuit
security of the circuit breaker
s control Supervise circuit breaker trip relay breaker Failure (CBF)
contact Prevention of accident spread
(the coordination of protection )

M1-6
Circuit Breaker Failure

M1

GIPAM-2200
Select Before Operating &
Check Before Operating

PT(VT) Failure (PTF)

Prevention of unnecessary interception of


the systems in terms of detecting fuse
opening of second PT
(distinction with voltage dip on the system)

M1-7
Digital Integrated Protection & Monitoring Device
Features

3 types of model for various protection functions


GIPAM-2200 comprises of 3 types of model for protection Incoming/Feeder/Motor and
for transformer and it has various kinds of protection functions such as followings.

Overcurrent relay : 50/51 Thermal overload relay : 49


Ground overcurrent relay : 50/51N Stall/Locked rotor relay : 48/51LR
Negative sequence overcurrent relay : 46 Under current relay : 37
Undervoltage relay : 27 Notching or jogging relay : 66
Overvoltage relay : 59 Ratio differential relay : 87T-P
Ground overvoltage relay : 64 Ground ratio differential relay : 87T-G
Negative sequence overvoltage relay : 47 Breaker Failure : 50BF
Sensitive directional ground relay : 67G
Directional ground relay : 67N

Easy GIPAM-2200 Setting


GIPAM-2200 series is simple to set all relay functions and verify all supported functions through the offered operation program
(GIPAMManager) which is based on PC interface. After setting the each parameter, downloading data from the communication port on the
front of GIPAM-2200 series leads completion of setting. It is very easy to maintain and repair due to the availability of download & upload.

M1-8
EVENT & FAULT RECORDING Sequence of Event(SOE) Function
M1
GIPAM-2200 is able to store up to 800 events that are related to GIPAM-2200 supports the SOE function that makes easy for
Protection & Measuring function, Breaker operation, Contact trip, reviewing fault analysis and operation information by recording

GIPAM-2200
operation information, and selfdiagnosis outcome.Moreover, in events in sequence at 1ms intervals regarding internal protection
case of line and load fault incidents, GIPAM-2200 can store up relay, breaker operation, or self-diagnosis abnormalities such as
to 200 detailed information regarding fault analysis, current fault, alarm contact output and others.These events including the latest
and voltage fault registered one can be stored as many as 800. Each event can be
verified in detail under the EVENT LIST section from the initial
screen of EVENT/FAULT REC Menu. In addition, it is possible to
save as files with GIPAMManager (capable to manage more than
800).

Vector Diagram
GIPAM-2200 can display a vector diagram regarding the
systems voltage, current, and phase through PC interface
operating program. It is easy to comprehend its electric systems
condition because of visualization from the diagram that verifies
the amount of electricity.

It can record front and rear 64 cycles of fault waveforms for each
phase. And it is also possible to increase number of recording
times by cycle partitions.

Time Characteristic Curve


By operating PC interface operating program, it is possible to
verify time characteristic curves to check with arranged values
after setting each protection relay. Therefore, it is very
Fault waveforms are saved as a Comtrade (IEEE) file format to convenient to program protection relay. Besides, it is simple to
be analyzed its waveforms or used for fault simulations. make protection coordination among electric systems as well.

M1-9
Digital Integrated Protection & Monitoring Device
Features

Select Before Operating(SBO) and Check Before TRIP CIRCUIT SUPERVISION (TCS) & TRIP RELAY
Operating(CBO) Function SUPERVISION (TRS)
By choosing controlling Points first before sending out orders to To check circuits condition, GIPAM-2200 internally make
where it is desired to control, control orders are executed only micro-current to flow on a trip circuit that is composed of
along with normal responses. This function enhances to control breakers trip coil and control voltage, and trip relay; and
reliability and security.GIPAM-2200 applies SBO/CBO functions tests it every hour. By composing trip relay with 2 pole series,
at CB controls power contact points. For selected control point, not 1 pole by itself, it will execute contact operation at regular
it will wait for control orders for 5 seconds after its response. If cycle or requested time checking trip relay automatically
the control order wont be delivered within 5 seconds, it will be without operation of a circuit breaker. After the automatic
reset. The control functions will be executed only on the normal check-up, the result will be recorded as event and if fault
condition when orders were delivered within 5 seconds, happens, contact output will be printed to prevent accidents
in advance.
Various Communication Compatibilities
GIPAM-2200 is possible to select its communication from RS-
485/422, Optic, and I- NET. Its application to diverse systems
is convenient in the industrial sites, because it supports
various protocols such as DNP 3.0, IEC 60870, MODBUS
and exclusive I-NET protocol as well. Not only it is able to
support the Ethernet communication mode through a protocol
transformer enabling high speed data communications, but
also it is possible to make up differentiated systems using
H.A.(High Availability) communication supports. Moreover, the
products front side is equipped with an IrDA(infrared rays)
port to provide easy access to upload/download with PC

TRIP LOGIC and SEQUENCE


Including a trip relay, GIPAM-2200 series all I/O contact CIRCUIT BREAKER FAILURE (CBF)
points and protection relays operation signals can be GGIPAM-2200 supports breaker failure function that can
managed by the logic that is directly designed by users. The prevent further extension of accident by controlling upper
logic can be easily arranged by using provided PC operating circuit breaker to trip, when lower circuit breaker failed to act
program, and applied to a variety of sequences. despite protection relay was activated and sent trip signal for
problems in the circuit. This function is not limited only on
trip signal, but also includes CB Close/Open control failure; it
will produce alarm output as well.

ANALOG INPUT (OPTION)


PT(VT) FAILURE
GIPAM-2200 is able to measure various analog data such as
distribution panels internal temperatures, transformer By detecting PT 2nd fuse melt-down in advance, its possible to
temperature, motors internal stator and bearing temperatures, collect alarm message and logic prints which can be used to
and rectifiers AC/DC voltage and current through its analog prevent unnecessary system cutoffs by protection relay
contacts(4point) without using additional TD. operation of UVR and NSOVR. It does not activate under under-
AI input variation : DC 4~20mA voltage or blackout situation, it compares with voltage current
Number of Contact Point : 4point and on breaker conditions to decide PT fuse opening. By
Display method : User Define utilizing DO output, it can generate alarm signal and it can also
Accuracy rate : 0.2% at Full scale make Trip Block to disable trip function. Replacing PT fuse will
reset it immediately.
M1-10
Functional Block Diagram

M1

GIPAM-2200
64

67G/N

GIPAM 2200 F

87T-G 87T-P

50N 51N

64

67G/N

GIPAM 2200 T

50 51 46 49

51G 87M
GIPAM 2200 M
50N 51N 67G/N 67G/N

48/
50N 51N 51LR

GIPAM 2200 F GIPAM 2200 F

M1-11
Digital Integrated Protection & Monitoring Device
Technical Specifications

Rating

Type Specification

Wiring 1P3W, 3P3W, 3P4W

Frequency 60Hz/50Hz

PT 110V
Voltage
GPT 190V, 190/ 3V
CT 5A
Current
ZCT 200/1.5mA
Input
Control Voltage AC/DC 110V/125V

Power Consumption Normal : Max. 30W, Operating : Max. 70W

PT Max. 0.5VA
Burden
CT Max. 1.0VA

Input Contact 6EA Digital Input : AC/DC 110V/125V

AC 250V 16A / DC 30V 16A, Resistive Load


2EA for Power
4000VA, 480W
Output Contact
AC 250V 5A / DC 30V 5A, Resistive Load
10EA for Alarm
1250VA, 150W

Insulation Resistance Over DC 500V 100

Insulation Voltage AC 2kV (1kV) / for 1 min

Impulse Voltage AC 5kV (3kV) Over 1.2 50

3 In for 3 hours
Current circuit
Overload Withstand 20 In for 2 seconds

Voltage circuit 1.15 Vn for 3 hours

Power Input 4kV


Fast Transient Disturbance
Other Input 2kV (Analog input 1kV)

Air 8kV
ESD (Electrostatic Discharge)
Contact 6kV

Operation temperature -10 ~ 55

Storage Temperature -25 ~ 70

Humidity Average 30% ~ 80%

Altitude 1000m and below

Non-impact place
Others
Non-air pollution place

Standard IEC 60255, IEC 61000-4, KEMC 1120

H
Dimension (W D) 237285223mm

Weight Max. 7.8kg

M1-12
Protection function M1

GIPAM-2200
Usage type Protection
OCR (50/51) OCGR (50/51N) DGR (67N)
GIPAM-2200 FN UVR (27) OVR (59) OVGR (64)
Incoming NSOVR/POR (47) NSOCR (46) THR (49)
48/51LR UCR (37) NCH (66)
Feeder
OCR (50/51) SGR (67G) OVGR (64G)
Motor
UVR (27) OVR (59) THR (49)
GIPAM-2200 FZ
NSOVR/POR (47) NSOCR (46) NCH (66)
48/51LR UCR (37)
DFR (87M) OCR (50/51) OCGR (50/51N)
DGR (67N) SGR (67G) OVGR (64)
Motor (87M) GIPAM-2200 M
NSOCR (46) THR (49) 48/51LR
NCH (66)
DFR (87T-P) DFR (87T-G) OCR-1 (50/51)
GIPAM-2200 T1 OCR-2 (50/51) OCGR-1 (50/51N) OCGR-2 (50/51N)
OVGR (64) DGR-1 (67N) DGR-2 (67N)
DFR (87T-P) DFR (87T-G) OCR-1 (50/51)
Transformer GIPAM-2200 T2 OCR-2 (50/51) OCGR-1 (50/51N) DGR-1 (67N)
OVGR (64) SGR-2 (67G)
DFR (87T-P) DFR (87T-G) OCR-1 (50/51)
GIPAM-2200 T3 OCR-2 (50/51) OCGR-2 (50/51N) DGR-2 (67N)
OVGR (64) SGR-1 (67G)

Measurement function

Type Measurement Display range Accuracy (%) Note


A 0.0A ~ 999.99kA 0.5% Phase current
V 0.0V ~ 999.99kV 0.5% Line voltage, Phase voltage
W 0.00W ~ 999.99MW 1.0%
Var 0.00Var ~ 999.99MVar 1.0% Forward, Reverse
Wh 0.00Wh ~ 9999.999MWh 1.0% Forward, Reverse
GIPAM-2200 F Varh 0.00Varh ~ 9999.999MVarh 1.0%
F 45 ~ 65Hz 0.5%
PF -1.000 ~ 1.000 1.0% cos, LEAD (-) / LAG (+)
Io 0.0A ~ 999.9A Io(In), Io(In)_max
I2 0.0A ~ 999.99kA
Vo 0.0V ~ 999.99V Vo, Vo_max
V2 0.0V ~ 999.99kV
A 0.0A ~ 999.99kA 0.5% Phase current
Io 0.0A ~ 999.9A Io(In), Io(In)_max
I2 0.0A ~ 999.99kA
Vo 0.0V ~ 999.99V Vo, Vo_max
GIPAM-2200 T
Id
Ir
Iod
Ior
A 0.0A ~ 999.99kA 0.5% la, lb, lc
Io 0.0A ~ 999.9A Io(n), Io(n)_max
I2 0.0A ~ 999.99kA
GIPAM-2200 M
Vo 0.0V ~ 999.99V Vo, Vo_max (Peak)
Id lda, ldb, ldc
5 lalb, lalc

M1-13
Digital Integrated Protection & Monitoring Device
Communications

GIPAM-2200 series can be set various kinds of relay functions by handling the Text LCD & Control keys on the front. In the menu, there
are measuring value displays, Fault & Event Data Logging, DI/DO Monitoring, SYSTEM Configuration & System information
for setting the rate of PT/CT, wiring method, setting communication and verifying information.

1 Protocol 5 Extra Communication Equipments.


I-NET, DNP3.0, MODBUS Protocol Converter (GMPC-V)
I-NET only
2 I-NET communication standards Converting into RS-232/485/422 common use, Ethernet
I-NET is an express and high reliable communication Supporting DNP3.0, MODBUS Protocol
which is designed with Custom LSI(GCV14605) ASIC Communication as Max.80 terminals are connected per 1
Chip developed by LSIS. GMPC-V at last.
Baud rate: 250kbps
Communication Line:
Low capacitance LAN Interface cable
Communication range: Maximum 1 km
Specification:
LIREV-AMEBSB 22AWG 2-pair (7/0.254TA)
Isolation Method: Pulse Transformer
Characteristic Impedance: 10MHz, 120 <GMPC-V>

Connection Method: 4-Wire Multi-drop


Termination: 2 Vertical 120 resistances are needed
in the both sides of the line ends.
Signal Modulation: Bipolar

3 DNS3.0, MODBUS / RS-485 Communication


standards
Operation mode: Differential Communication Reset Switch, Communication (RX) LED Terminal Block 1
Communication Range: Maximum 1.2km
Communication Line: RS-485 shield twist 2-Pair cable
Communication speed: Normally 19.2kbps~38.4bps
Transmission Method: Half-Duplex
Terminal Block 2
Maximum Input/Output Voltage: -7V~+12V

4 DNS3.0, MODBUS/Optic Communication


Communication Terminal
Standards (Optic Transceiver Specification)
Wave Length: 820nm
Fiber Size: 50/125. 62.5/125, 100/140
Optical Connector Type: ST Type
Optic Link Distance: Optical Port

Depends on Data rate, Maximum 4km


(GIPAM-2200s Data bit rate: 9600bps ~ 230.4kbps)
I/O Terminal
- Transceiver specification:
500m (175Mbps) ~ 2.7km (20Mbps)
Fiber: Multi Mode Cable
<Rear View>

Annotation1): For further information about communication protocol, Please address


inquiries to us separately.

M1-14
External & Structure

M1

GIPAM-2200
Status LED
Power
Comm(Tx) 4 Text LCD
20
Diag/Err
Pick-up/Trip
Draw-out Handle
Direction Key

Function Key
FUNC
Trip Assign RESET
LED 11EA ESC
ENTER

CB CLOSE/OPEN
CC CLOSE/OPEN
Operating Key
IrDA Port

Remote/Local

Front View

FUNCTION
FUNC Using with ESC key when clearing Data,
No use of it during normal operation

The Restoration of trip


RESET The indication of LED after faults,
The restoration of LCD

ESC
ESC The cancel of selected item &
change of setting values

ENTER
ENTER The selection of item
The confirmation of setting

Remote / Local
R/L The switching of
Remote/Locai <Draw-out Type>

M1-15
Digital Integrated Protection & Monitoring Device
Man Machine Interface
GIPAM-2200 F

GIPAM-2200 T

M1-16
GIPAM-2200 M

M1-17
GIPAM-2200
M1
Digital Integrated Protection & Monitoring Device
Man Machine Interface

GIPAM-2200 series can be set various kinds of relay functions by handling the Text LCD & Control keys on the front. In the menu,
there are measuring value displays, Fault & Event Data Logging, DI/DO Monitoring, SYSTEM Configuration & System information
for setting the rate of PT/CT, wiring method, setting communication and verifying information.

M1-18
Characteristics

GIPAM-2200 F M1
Operating time

GIPAM-2200
Protection Operating part Setting range Note
Setting Curves

Instanta Low set Low: 0.05~300.00s/0.01s


OFF, 1.0~32.0In/0.1In Definite
neous High set High: 40ms and below
OCR (50/51
0.05~1.20/0.01 Inverse
Time delay OFF, 0.10~10.00In/0.01In DT, SI, VI, EI, LI
0.05~300.00s/0.01s Definite
Instanta Low set Low: 0.05~300.00s/0.01s
OFF, 0.1~8.0In/0.02In Definite
OCGR neous High set High: 40ms and below
(50/51N) 0.05~1.20/0.01 Inverse
Time delay OFF, 0.02~2.00In/0.01In DT, SI, VI, EI, LI
0.05~300.00s/0.01s Definite
NSOVR Time Low set V2=1/3 (VR + a2VS + aVT)
(47) OFF, 0.1~1.0Vn/0.1Vn 0.05~10.00s/0.01s Definite
POR delay High set a=1120, a2=1 240

UVR (27) Time delay 0.20~1.00Vn/0.01Vn 0, 0.05~10.00s/0.01s Definite

Time Low set


OVR (59) OFF, 0.8~1.6Vn/0.01Vn 0.05~10.00s/0.01s Definite
delay High set

Instantaneous OFF, 11~80V/1V Inst, 50~250ms/5ms Definite DT, SI


OVGR (64) Von=190V or 190/ 3V
0.05~1.00/0.01 Inverse
Time delay OFF, 11~80V/1V Inst : 40ms and below
0.05~300.00s/0.01s Definite

Instantaneous OFF, 0.1~1.0In/0.02In Inst, 50~250ms/5ms Definite


DT, SI, VI, EI, LI
NSOCR (46)
0.05~1.00/0.01 Inverse
Time delay OFF, 0.1~1.0In/0.01In Inst : 40ms and below
0.05~10.00s/0.01s Definite

isolated 0.9~6mA/0.1mA
system (Ion=1.5mA)
Zero-phase
current grounded 0.02~2.00Ion/0.01Ion Vo > Vos
system (Ion=5A)
SGR (67G) Time Io > Ios
0.05~10.00s/0.01s Definite
DGR (67N) delay Zero-phase 11~80V/1V (Vo) -(Io) RCA + 87
voltage (Von=190V, 190/ 3V) (Vo) -(Io) RCA - 87
Relay
characteristic 0~90/5
angle
2 2
t : operating time
Hot h : 2.0~60.0min/0.5min
t = hln 2
- IP
[ I -I(kI B)
] 2
k : multiple factor
THR (49) 0.2~1.2In/0.01In 2

Cold c : 2.0~60.0min/0.5min
t = cln 2 [ I
I - (kIB)
2 ] (0.8~1.2/0.05)
: thermal constant
Stall OFF, 0.2~10.0In/0.01In 0.05~300.00s/0.01s Definite
Stall/Lock Time Start time range
0.05~1.00/0.01 Inverse (VI, EI)
(48/51LR) delay Lock OFF, 0.2~10.0In/0.01In 1.0~300.0s/0.1s
0.05~300.00s/0.01s Definite

UCR (37) Time delay 0.1~0.9In/0.02In 0.1~10.0s/0.01s Definite

Starts Number 1~5 times/1


Base Time 10~60min/1min
NCH (66) Time between starts Block 0~60min/1min
Restart Block 0~60min/1min
Residual Thermal 10~80%/1%

M1-19
Digital Integrated Protection & Monitoring Device
Characteristics

GIPAM-2200 T

Protection Setting range Operating time Note

Id (Pick up): 0.2~1.0In/0.1In Normal mode


Slope 1: 15~100%/1% Inst : 40ms and below
Time delay Inst, 0.05~10.00s/0.01s
Slope 2: 15~100%/1% Inrush mode
differential current
Knee Point: 1.0~20.0In/0.1 In Inst : 50ms and below
(Low set)
DFR
Inrush Inhibit: ON (10~50%/1%) OFF 2Harmonic/Basic
(87T-P)
Instantaneous
differential current Id (Pick up): 2.0~32.0 In/0.1In 40ms and below Inrush Inhibit
(High set)

Io Elimination: ON, OFF

DFR Zero-phase Iod (Pick up): 0.05~1.00In/0.01In


Inst, 0.05~10.00s/0.01s Inst : 40ms and below
(87T-G) differential current Slope: 15~100%/1%

Operating time
Protection Operating part Setting range Note
Setting Curves
Instanta Low set Low: 0.05~300.00s/0.01s Definite
OFF, 1.0~32.0In/0.1In
OCR-1 neous High set High: 40ms and below
(50/51) 0.05~1.20/0.01 Inverse
Time delay OFF, 0.10~10.00In/0.01In DT, SI, VI, EI, LI
0.05~300.00s/0.01s Definite
Instanta Low set Low: 0.05~300.00s/0.01s
OFF, 1.0~32.0In/0.1In Definite
OCR-2 neous High set High: 40ms and below
(50/51) 0.05~1.20/0.01 Inverse
Time delay OFF, 0.10~10.00In/0.01In DT, SI, VI, EI, LI
0.05~300.00s/0.01s Definite
Instanta Low set Low: 0.05~300.00s/0.01s
OFF, 0.1~8.0In/0.02In Definite
OCGR-1 neous High set High: 40ms and below
(50/51N) 0.05~1.20/0.01 Inverse
Time delay OFF, 0.02~2.00In/0.01In DT, SI, VI, EI, LI
0.05~300.00s/0.01s Definite
Instanta Low set Low: 0.05~300.00s/0.01s
OFF, 0.1~8.0In/0.02In Definite
OCGR-2 neous High set High: 40ms and below
(50/51N) 0.05~1.20/0.01 Inverse
Time delay OFF, 0.02~2.00In/0.01In DT, SI, VI, EI, LI
0.05~300.00s/0.01s Definite

Instantaneous OFF, 11~80V/1V Inst, 50~250ms/5ms Definite DT, SI


OVGR (64)
Time delay OFF, 11~80V/1V
0.05~1.00/0.01 Inverse Von=190V or 190/ 3V
0.05~300.00s/0.01s Definite Inst : 40ms and below
isolated OFF, 0.9~6mA/0.1mA
Zero-phase system (Ion=1.5mA)
current grounded OFF, 0.02~2.0Ion/0.01Ion Vo > Vos
SGR (67G) Time system (Ion=5A) Io > Ios
0.05~10.00s/0.01s Definite
DGR (67N) delay Zero-phase 11~80V/1V (Vo) -(Io) RCA + 87
voltage (Von=190V, 190/ 3V) (Vo) -(Io) RCA - 87
Relay
characteristic 0~90/5
angle

M1-20
GIPAM-2200 M M1
Operating time

GIPAM-2200
Protection Operating part Setting range Note
Setting Curves
Instanta Low set Low: 0.05~300.00s/0.01s
OFF, 1.0~32.0In/0.1In Definite
neous High set High: 40ms and below
OCR (50/51)
0.05~1.20/0.01 Inverse
Time delay OFF, 0.10~10.00In/0.01In DT, SI, VI, EI, LI
0.05~300.00s/0.01s Definite
Instanta Low set Low: 0.05~300.00s/0.01s
OFF, 0.1~8.0In/0.02In Definite
OCGR neous High set High: 40ms and below
(50/51N) 0.05~1.20/0.01 Inverse
Time delay OFF, 0.02~2.00In/0.01In DT, SI, VI, EI, LI
0.05~300.00s/0.01s Definite
DT, SI
Instantaneous OFF, 11~80V/1V Inst, 50~250ms/5ms Definite
Von=190V or 190/ 3V
OVGR (64)
0.05~1.00/0.01 Inverse
Time delay OFF, 11~80V/1V Inst : 40ms and below
0.05~300.00s/0.01s Definite

Instantaneous OFF, 0.1~1.0In/0.02In Inst, 50~250ms/5ms Definite


DT, SI, VI, EI, LI
NSOCR (46)
0.05~1.00/0.01 Inverse Inst : 40ms and below
Time delay OFF, (0.10~1.00)In/0.01In
0.05~10.00s/0.01s Definite
isolated 0.9~6mA/0.1mA
Zero-phase system (Ion=1.5mA)
current grounded 0.02~2.00Ion/0.01Ion Vo > Vos
SGR (67G) Time system (Ion=5A) Io > Ios
0.05~10.00s/0.01s Definite
DGR (67N) delay Zero-phase 11~80V/1V (Vo) -(Io) RCA + 87
voltage (Von=190V, 190/ 3V) (Vo) -(Io) RCA - 87
Relay
characteristic 0~90/5
angle
2 2

Hot h : 2.0~60.0min/0.5min
t = hln [ I -I(kIB)
2
- IP
] 2
t : operating time
k : multiple factor
THR (49) 0.2~1.2In/0.01In 2
I (0.8~1.2/0.05)
Cold c : 2.0~60.0min/0.5min
t = cln [ I - (kIB) ]
2 2
: thermal constant
Stall OFF, 0.2~10.0In/0.01In 0.05~300.00s/0.01s Definite
Stall/Lock Time Start time range
0.05~1.00/0.01 Inverse (VI, EI)
(48/51LR) delay Lock OFF, 0.2~10.0In/0.01In 1.0~300.0s/0.1s
0.05~300.00s/0.01s Definite

UCR (37) Time delay 0.1~0.9In/0.02In 0.1~10.0s/0.01s Definite

Starts Number 1~5 times/1


Base Time 10~60min/1min
NCH (66) Time between starts Block 0~60min/1min
Restart Block 0~60min/1min
Residual Thermal) 10~80%/1%

DFR-M (87M) Instantaneous 0.02~2.00In/0.01In Inst, 0.05~300.0s/0.01s Definite Inst : 40ms and below

M1-21
Digital Integrated Protection & Monitoring Device
Time Characteristic Curves

Standard Inverse Time-SI

Application : OCR (50/51)


OCGR (50/51N)
OVGR (64)
NSOCR (46)

0.14
t= TL + C
(I/IS)0.02-1
Time lever (TL) : 0.05~1.2
OVGR
TL: 0.05~1.0
NSOCR

Relay constant C: 0

Operation Delay Time: 0.00~10.00s/0.01s


(OCR, OCGR, NSOCR)

Very Inverse Time-VI

Application : OCR (50/51)


OCGR (50/51N)
OVGR (64)
NSOCR (46)
Locked Rotor (51LR)

13.5
t= TL + C
(I/IS)-1

Time lever (TL) : 0.05~1.2


OVGR
NSOCR TL: 0.05~1.0
Locked Rotor

Relay constant C: 0

Operation Delay Time: 0.00~10.00s/0.01s


(OCR, OCGR, NSOCR)

M1-22
Extremely Inverse Time-EI M1

GIPAM-2200
Application : OCR (50/51)
OCGR (50/51N)
OVGR (64)
NSOCR (46)
Locked Rotor (51LR)

80
t= TL + C
(I/IS)2-1
Time lever (TL) : 0.05~1.2
OVGR
NSOCR TL: 0.05~1.0
Locked Rotor

Relay constant C: 0

Operation Delay Time: 0.00~10.00s/0.01s


(OCR, OCGR, NSOCR)

Long Inverse Time-LI

Application : OCR (50/51)


OCGR (50/51N)
NSOCR (46)

120
t= TL + C
(I/IS)-1

Time lever TL: 0.05~1.2


(NSOCR (TL): 0.05~1.0)

Relay constant C: 0

Operation Delay Time: 0.00~10.00s/0.01s


(NSOCR)

M1-23
Digital Integrated Protection & Monitoring Device
Time Characteristic Curves

Thermal Curve

Application : THR (49)


I2-IP2
HOT t=hIn
I 2-
(kIB)2
h = 2.0 ~ 60.0min
I2
COLD t=
cIn
I2- (kIB)2
c = 2.0 ~ 60.0min
IP = 0.5
k= 1
IB = 1
IP
: Fault full load current
: Rating load current
IB
k: Overload constant
I: Fault current
h (heating)
c (cooling)

Application : SGR (67G)


DGR(67N)

(a) Pick-up
323~ 127
(b) Pick-up ~ Drop-out
137~ 313

Vo > Vos
Io > Ios
RCA - 87(Vo) -(Io) RCA + 87

RCA (Relay Characteristic Angle)

M1-24
Ratio Differential Curve M1

GIPAM-2200
Application : DFR (87T-P)

Id = Idifferential = I1I2 (Vector sum.)


Ir = Irestraint = I1 + I2 (Scalar sum.)
Id
SLOPE =
Ir

Fault Characteristic : ( I1st = If , I2nd = 0 )

Id: Differential current


Ir: Restraint current
Id>: Time delay differential current
(Low set: 0.2~1.0)
Id>>: Instantaneous differential current
(High set: 2.0~32.0)
KNEE POINT
SLOPE 1
SLOPE 2

Ground Ratio Differential Curve

Application : DFR (87T-G)

Iod = 3IoIg (Vector sum.)


Ior = 3Io + Ig (Scalar sum.)
Iod
SLOPE =
Ior

Fault Characteristic ( I1st = If , I2nd = 0)

Iod: Zero-phase differential current


Ior: Zero-phase restraint current
Iod>: Time delay zero-phase differential
current (0.05 ~ 1.00)
SLOPE

M1-25
Digital Integrated Protection & Monitoring Device
Network Systems

GIPAM-2200 series perform 64kbps data transmission as maximum speed, and also 250kbps express
serial communication is available by I-NET, which is an exclusive communication system by LSIS.
They offer RS-485/I-NET Multi-port & Fiber Optic Port, and supports DNP3.0, IEC 60870, MODBUS,
and exclusive I-NET Protocol. When the protocol converter (GMPC-V) is used , I-NET only
can be converted into RS- 232/485, Ethernet and Protocol conversion
also can be converted into DNS3.0, MODBUS is available.

DCS, BAS

Event Logging

DNP3.0
MODBUS
Fiber Optic
RS-485

GMPC-V MODBUS
DNP3.0
RS-485
MODBUS
RS-232/485
Ethernet

GIPAM-115FI

DPR-1000

GIPAM-2000 GIPAM-2200

M1-26
M1

GIPAM-2200
Web-Server
(Web-based S/W)

MODBUS
RS-232

MODBUS
Ethernet Internet /
Intranet
MODBUS
RS-232/485

MODBUS
RS-232/485

PLC or DDC GMPC-III GMPC-MASTER


MODBUS MODBUS
RS-232/485 RS-232
* GIPAM 2000/2200, GIMAC-IV except Ethernet

MODBUS
RS-485

GIMAC- i GIMAC- DC IMC-III


DPR micro-RTU
GIMAC-PQ
GIMAC-II Plus
GIMAC-IV

M1-27
Digital Integrated Protection & Monitoring Device
Wirings

3P3W

* 3P3W 3-Winding CT application

* 3P3W Ground CT application

2CT

2PT
(Open delta wiring)

M1-28
3P4W M1

GIPAM-2200
1P3W

* NCT application

M1-29
Digital Integrated Protection & Monitoring Device
Wirings

GIPAM-2200 T1

M1-30
GIPAM-2200 T2 M1

GIPAM-2200
GIPAM-2200 T3

M1-31
Digital Integrated Protection & Monitoring Device
Wirings

GIPAM-2200 M

M1-32
Contact Usage

GIPAM-2200 F M1

GIPAM-2200
Input / Output
Terminal No. Usage Default Note
60 DI_01 CB_52a
Fixed
59 DI_02 CB_52b
57 DI_03 General DI General DI
56 DI_04 General DI General DI
55 DI_05 General DI General DI
54 DI_06 General DI General DI
50 CB_OFF0
CB_OPEN output
49 CB_OFF1
Fixed
48 CB_ON0
CB_CLOSE output
47 CB_ON1
46 DO_01 50/51 (OCR) General DO (Normal/Pulse)
45 DO_02 50/51N, 67G/N (OCGR/SGR/DGR) General DO (Normal/Pulse)
44 DO_03 27 (UVR) General DO (Normal/Pulse)
43 DO_04 59 (OVR) General DO (Normal/Pulse)
40 DO_05 64 (OVGR) General DO (Normal/Pulse)
39 DO_06 47 (NSOVR) General DO (Normal/Pulse)
38 DO_07 49 (THR) General DO (Normal/Pulse)
36 DO_08 48/51LR (Stall/Lock) General DO (Normal/Pulse)
35 DO_09 Pick-up
Fixed
34 DO_10 Power_Fail/Diag_Err

M1-33
Digital Integrated Protection & Monitoring Device
Contact Usage

GIPAM-2200 T
Comm. Reset switch, LED

output

input

Input / Output
Terminal No. Usage Default Note
60 DI_01 CB_52a
Fixed
59 DI_02 CB_52b
57 DI_03 General DI General DI
56 DI_04 General DI General DI
55 DI_05 General DI General DI
54 DI_06 General DI General DI
50 CB_OFF0
CB_OPEN output
49 CB_OFF1
Fixed
48 CB_ON0
CB_CLOSE output
47 CB_ON1
46 DO_01 87T-P (DFR) General DO (Normal/Pulse)
45 DO_02 87T-G (DFR) General DO (Normal/Pulse)
44 DO_03 50/51 (OCR 1) General DO (Normal/Pulse)
43 DO_04 50/51 (OCR 2) General DO (Normal/Pulse)
40 DO_05 50/51N, 67G/N (OCGR/SGR/DGR 1) General DO (Normal/Pulse)
39 DO_06 50/51N, 67G/N (OCGR/SGR/DGR 2) General DO (Normal/Pulse)
38 DO_07 64 (OVGR) General DO (Normal/Pulse)
36 DO_08 General DO (Normal) General DO (Normal/Pulse)
35 DO_09 Pick-up
Fixed
34 DO_10 Power_Fail/Diag_Err

M1-34
GIPAM-2200 M M1

GIPAM-2200
Input / Output
Terminal No. Usage Default Note
60 DI_01 CB_52a
Fixed
59 DI_02 CB_52b
57 DI_03 General DI General DI
56 DI_04 General DI General DI
55 DI_05 General DI General DI
54 DI_06 General DI General DI
50 CB_OFF0
CB_OPEN output
49 CB_OFF1
Fixed
48 CB_ON0
CB_CLOSE output
47 CB_ON1
46 DO_01 50/51 (OCR) General DO (Normal/Pulse)
45 DO_02 50/51N, 67G/N (OCGR/SGR/DGR) General DO (Normal/Pulse)
44 DO_03 64 (OVGR) General DO (Normal/Pulse)
43 DO_04 46 (NSOCR) General DO (Normal/Pulse)
40 DO_05 49 (THR) General DO (Normal/Pulse)
39 DO_06 48/5LR (Stall/Lock) General DO (Normal/Pulse)
38 DO_07 37 (UCR) General DO (Normal/Pulse)
36 DO_08 DFR-M (87M) General DO (Normal/Pulse)
35 DO_09 Pick-up
Fixed
34 DO_10 Power_Fail/Diag_Err

M1-35
Digital Integrated Protection & Monitoring Device
Dimension

M1-36
Ordering

GIPAM-2200 FN RS D AI 60Hz M1

GIPAM-2200
Protection Usage Communication Protocol Analog Input Frequency
FN Feeder, Incoming, Motor / NCT RS RS-485 D DNP3.0 AI 4~20mA 60Hz
FZ Feeder, Incoming, Motor / ZCT OP Fiber-Optic/RS-485 E IEC60870 - Non 50Hz
M Motor (87M) / NCT, ZCT IN I-NET M MODBUS
T1 Transformer / Pri_NCT, Sec_NCT - Non I I-NET
T2 Transformer / Pri_NCT, Sec_ZCT
T3 Transformer / Pri_ZCT, Sec_NCT

GIPAM-OPTOMASTER IrDA Serial Port(Option)

M1-37
GIPAM-115

Digital Integrated Protection &


Monitoring Device

GIPAM-115
Digital Integrated Protection & Monitoring Equipment

GIPAM is a multifunction, microprocessor-based protection equipment suitable


for all types of applications such as distribution feeders.
It can be also be used for management and backup protection of buses,
transformers, and power lines.
Drawout structure for panel-flush mounting
User-friendly front panel to monitor, program, and test the GIPAM
Data communication with a host computer
M2

Contents Features
Technical specifications
Communications
M2-4
M2-6
M2-8
External & MMI M2-9
Operation curves M2-10
Wirings M2-12
Ordering & Dimension M2-15
Digital Integrated Protection & Monitoring Device
Features

GIPAM
Digital Integrated Protection & Monitoring Equipment
GIPAM is a multifunction, microprocessor-based protection equipment suitable
for all types of applications such as distribution feeders.
It can be also be used for management and backup protection of buses,
transformers, and power lines.
Drawout structure for panel mounting
User-friendly front panel to monitor, program, and test the GIPAM
Data communication with a host computer

M2-4
Protection
Multi-functions offering a wide choice of protective options
OCR, 50/51
OCGR, 50/51N
OVR, 59
UVR, 27
OVGR, 64G
SGR, 67G
POR, 47 M2
Broad setting ranges

GIPAM-115
All types of curves provided
SI, Standard inverse time delay
VI, Very inverse time delay
EI, Extremely inverse time delay
LI, Long inverse time delay
DI, Definite time delay

Logging of fault current and voltage for each phase

Metering and Monitoring


Acquisistion, visualization and storage of electrical data
Volt, Amepre, Watt, Zero phase volt, VAR, Watthour
VARH, Power factor, Frequency, Cumulative operating time
Number of operations closing and opening status
Digital displaying of each fault information

Broad setting ranges

Displaying status via digital LCD and analog Bar graph for better visualization

Offering operation reliability


Continuous monitoring and autodiagnostics systems
through microprocessor technology

Communication
Modbus/RS-485
I-NET / LS customized protocol

M2-5
Digital Integrated Protection & Monitoring Device
Technical specifications

Rating

Type Specification

Wiring 1P2W, 1P3W, 3P3W, 3P4W

Frequency 60Hz/50Hz

PT 110V
Voltage
GPT 190V

CT 5A
Current
ZCT 200/1.5mA
Input
Control Voltage AC/DC 110V or DC 125V

Power Consumption Max. 30W

PT Max. 0.5VA
Burden
CT Max. 1.0VA

Input Contact 3EA Digital Input : AC/DC 110V

AC 250V 16A / DC 30V 16A, Resistive Load


2EA for Power
4000VA, 480W
Output Contact
AC 250V 5A / DC 30V 5A, Resistive Load
8EA for Alarm (7a 1c)
1250VA, 150W

Insulation Resistance Over DC 500V 100

Insulation Voltage AC 2kV (1kV) / for 1 min

Impulse Voltage AC 5kV (3kV) Over 1.2 50

2 In for 3 hours
Current circuit
Overload Withstand 20 In for 2 seconds

Voltage circuit 1.15 Vn for 3 hours

Power Input 4kV


Fast Transient Disturbance
Other Input 2kV (Analog input 1kV)

Air 8kV
ESD (Electrostatic Discharge)
Contact 6kV

Operation temperature -10 ~ 55

Storage Temperature -25 ~ 70

Humidity Average 30% ~ 80%

Altitude 1000m and below

Non-impact place
Others
Non-air pollution place

Standard IEC 60255, IEC 61000-4, KEMC 1120

H
Dimension (W D) 437210165 mm

Weight 10.5kg

M2-6
Protection functions

Operating time characteristics


Functions Operation element Setting range Remarks
Setting range Characteristics
Instantaneous OFF, 2~24In / 1In 0.04~60.0s / 0.01s Definite time
OCR
Definite time 3 types D2, D4, D8
[50/51] Time-delay OFF, 0.2~10.0In / 0.1In 0.05~1.20 / 0.01
Inverse time 4 types SI, VI, EI, LI
Instantaneous OFF, 0.5~8.0In / 0.5In 0.04~60.0s / 0.01s Definite time
OCGR Block time :
Definite time 3 types
[50/51N] Time-delay OFF, 0.1~0.5In / 0.02In 0.05~1.20 / 0.01
Inverse time 4 types
0.1~60.0s/0.1s M2
OVR Time-delay(high) OFF, 0.80~1.60Vn / 0.02Vn 0.1~60.0s / 0.01s Definite time

GIPAM-115
[59] Time-delay(Low) OFF, 0.80~1.60Vn / 0.02Vn 0.1~60.0s / 0.01s Definite time
UVR Time-delay(high) OFF, 0.20~0.90Vn / 0.02Vn 0.1~60.0s / 0.01s Definite time Outage lock :
[27] Time-delay(Low) OFF, 0.20~0.90Vn / 0.02Vn 0.1~60.0s / 0.01s Definite time (below 15V)
OFF, 0.10~0.40Von / 0.02Von
Time-delay(high) 0.1~60.0s / 0.01s Definite time
OVGR (Von=190V)
[64G] OFF, 0.10~0.40Von / 0.02Von
Time-delay(Low) 0.1~60.0s / 0.01s Definite time
(Von=190V)
Zero-phase current(Io) OFF, 0.6~3.6Ion / 0.2Ion (Ion=1.5mA)
SGR
Zero-phase voltage(Vo) 0.10~0.40Von / 0.02Von (Von=190V) 0.1~60.0s / 0.01s Definite time
[67G]
RCA 45fixed
POR Time-delay(high) OFF, 5~100% / 1% 0.1~60.0s / 0.01s Definite time
[47] Time-delay(Low) OFF, 5~100% / 1% 0.1~60.0s / 0.01s Definite time

Measurement functions

Parameters Display Accuracy Remarks

AC 0.5~414,000V Va, Vb, Vc


Voltage, V 0.5%
Bar graph 0~120% Vab, Vbc, Vca

Current, A AC 0.05~7,200A 0.5% Ia, Ib, Ic

0~190(V)
Zero-phase voltage, Vo - Vo, Vo_max(peak)
Bar graph 0~120%
0~9,999MW
Active power, Watts 1.0%
Bar graph 0~120%

Reactive power, Vars 0~9,999MVar 1.0%

0~999,999MWh
Active energy, Wh 1.0%
Bar graph 0~120%
0~999,999MVarh
Reactive energy, Varh 1.0%
Bar graph 0~120%

Power factor, PF Lead/Lag 0~100% 1.0%

Frequency, F 45~65Hz 0.5%

M2-7
Digital Integrated Protection & Monitoring Device
Communications

Modbus/RS-485
Operation mode: Differential
Distance: Max. 1.2km
Cable : SCADA system
General RS-485 shielded twist
2-pair cable
Modbus/RS-485
Baud rate :
9600bps, 19200bps, 38400bps
Transmission method: Half-Duplex
Termination: 150

I-NET communication standards Extra Communication Equipments.


I-NET is an express and high reliable communication which is Protocol Converter (GMPC-V)
designed with Custom LSI(GCV14605) ASIC Chip developed I-NET only
by LSIS. Converting into RS-232/485/422 common use, Ethernet
Communication Speed: 250kbps Supporting DNP3.0, MODBUS Protocol
Communication Line: Communication as Max.80 terminals are connected per 1
Low capacitance LAN Interface cable GMPC-V at last.
Communication range: Maximum 1 km
Specification:
LIREV-AMEBSB 22AWG 2-pair (7/0.254TA)
Isolation Method: Pulse Transformer
Characteristic Impedance: 10MHz, 120
Connection Method: 4-Wire Multi-drop
Termination: 2 Vertical 120 resistances are needed in the
both sides of the line ends. <GMPC-V>
Signal Modulation: Bipolar

M2-8
External & MMI

Protection function keys an displays Easurement keys and displays


M2

GIPAM-115
Control keys

Key No. Description Key No. Description


1 Reset key to reset fault indications 11 Function key, red LED
2 162 Text LCD 12 Communication LED, blinking on communicating
3 Fault indication LEDs 13 Power LED, red LED
4 Set/Run key 14 CB ON key, red LED
5 ESC key 15 CB OFF key, green LED
6 Enter key 16 Selection key for CB local operation, yellow LED
7 Decrement key 17 Selection key for CB remote operation, yellow LED
8 Increment key 18 Clear key
9 LCD display 19 CPU reset key
10 Display selection key 20 Control key protection cover

M2-9
Digital Integrated Protection & Monitoring Device
Operation curves

Operation time, t(sec) = T x tap, tap = 0.05 to 1.00

Type of curve T Type of curve T

0.14
SI, Standard Inverse T= D2, Definite Time T=2
(I / IS)0.02 - 1

13.5
VI, Very Inverse T= D4, Definite Time T=4
(I / IS) - 1

80
EI, Extremely Inverse T= D8, Definite Time T=8
(I / IS)2 - 1

120
LI, Long Inverse T=
(I / IS) - 1

Note) I = operation current, Is = set current


In case of OVGR substitute ( V / Vs ) for ( I / Is ).

POR(Phase open relay)


Vmax - Vmin
Voltage unbalance Vunbal = 100% (setting range 5~100% / 1%)
Vavg
Vmax = max ( Va , Vb , Vc )
Vmin = min ( Va , Vb , Vc )
1
Vavg = max ( Va + Vb + Vc )
3

SI curves for OCR, OCGR VI curves for OCR and OCGR


100 1000

100
10

1.2 10
Operation time, sec
Operation time, sec

0.6
1 0.4
0.3
0.2
1
1.2
0.1
0.6
0.4
0.05 0.3
0.1
0.2
0.1
0.1

0.05

0.01 0.01
1 10 20 1 10 20

Current in multiples of set current, I / Is Current in multiples of set current, I / Is

M2-10
EI curves for OCR and OCGR LI curves for OCR and OCGR
1000 10000

100
1000

10

Operation time, sec


100
M2
Operation time, sec

GIPAM-115
10
1.2
1.2
0.6
0.1 0.4 0.6
0.3 0.4
0.2 0.3
0.1 0.2
1
0.01 0.05 0.1

0.05

0.001 0.1
1 10 20 1 10 20

Current in multiples of set current, I / Is Current in multiples of set current, I / Is

Definite Time curves for UVR and OVR Operation phase characterictic of SGR

135
UVR Setting OVR Setting

60
Operation time, sec

10

0.1

315
0.2 0.8 0.9 1 1.6

Voltage in multiples of set voltage, V / Vs

M2-11
Digital Integrated Protection & Monitoring Device
Wirings

[Output terminal block] [Input terminal block]

Input Output

Comm
terminals

Note) 1. Avoid connectting GIPAM parallel with the other devices that generate noises.
2. Press the clear switch to initialize all data after installation.

M2-12
1P 2W

M2
1P 3W

GIPAM-115
3P 3W(with 2CT, 2PT)

3P 3W(with 3CT, 2PT)

M2-13
Digital Integrated Protection & Monitoring Device
Wirings

3P 3W

3P 4W
(NCT is available)

ZCT GPT

M2-14
Dimension & Ordering

Dimensions

M2
Cutout

GIPAM-115

Ordering

GIPAM-115 FI RS M 60Hz

Protection Communication Protocol Frequency

Feeder, RS RS-485 M MODBUS 60Hz


FI
Incoming IN I-NET I I-NET 50Hz

M2-15
DPR-1000

Digital Protection Relay

DPR-1000 is the digital protective relay which is intended for


monitoring and protecting the faults on the feeder of distribution
system, especially for the medium-voltage motors.

11 protective function for the medium-voltage motors


Compact type protective relay with built-in various add
functions
Remote control & Monitoring of circuit breaker
MODBUS, DNP3.0 / RS-485 communication
N1

Contents Feeder/Motor protection relay


Rating
Technical Specifications
N1-4
N1-5
N1-6
Dimension N1-7
Ordering N1-8
Digital Protective Relays
Feeder/Motor protection relay

DPR-1000 is the digital protective relay which is intended


for monitoring and protecting the faults on the feeder of
distribution system, especially for the medium-voltage motors.

11 protective function for the medium-voltage motors


Compact type protective relay with built-in various add functions
Remote control & Monitoring of circuit breaker
MODBUS, DNP3.0 / RS-485 communication

Function
Protection & Control
Overcurrent (50/51P), Overcurrent ground (50/51N)
Thermal (49), Negative sequence overcurrent (46)
Selective ground (67G), Directional ground (67N)
Under current (37), Stall & locked rotor (48/51LR)
Starts per hour (66)
Lock-out (86)
2 analog inputs (Thermistor)
5 digital outputs
3 digital inputs

Monitoring & Metering


I, Io, I2, Vo
Temperature (2 ch.)
Starting current, starting time, full load current, thermal, etc.
Event triggered wave recording: 15 Traces (Ir, Is, It, Io, Vo, AI1, AI2, DI/DO, etc.)

User Interface
204 Character LCD
DNP3.0, Modbus/RS-485
PC interface software (GIPAM manager)

Block diagram

N1-4
Technical Specifications

Rating

Type Specification

Wiring 3P3W, 3P4W

Frequency 60Hz

Voltage GPT
190, 190 / 3

CT 5A
Current
ZCT 1.5mA

Control voltage AC/DC: 110V


Input
Steady: below 30W
Power consumption
Operating: below 70W

Burden PT 0.5VA

CT 1.0VA
N1
Digital Input Digital Input: AC/DC 110V

AC 250V 16A/DC 30V 16A Resistive Load

DPR-1000
For trip
AC 2500VA, DC 300W
Output
AC 250V 5A/DC 30V 5A Resistive Load
For alarm
AC 750VA, DC 90W

Insulation resistance Over DC 500V 100

Insulation voltage AC 2kV (1kV)/for 1 min

Impulse voltage AC 5kV (3kV) Over 1.250

3 In for 3 hours
Current circuit
Overload Withstand 20 In for 2 seconds

Voltage circuit 1.15Vn for 3 hours

Power Input 4kV


Fast transient disturbance
Other Input 2kV (Analog Input 1kV)

Air 8kV
ESD (Electrostatic Discharge)
Contact 6kV

Operation temperature -10C ~ 55C

Storage temperature -25C ~ 70C

Humidity Average 30% ~ 80%

Altitude 1000m and below

Non-impact place
Others
Non-air pollution palce

Standard IEC 60255, IEC 61000-4, KEMC 1120

H
Dimension (W D) 120245185 (mm)

Weight 3.4kg

N1-5
Digital Protective Relays
Technical Specifications

Protection functions

Protective
Operating part Setting & Operating time Remark
function
Instantaneous
Setting: OFF, 0.5~20.0/0.1In Below 40ms
high set
OCR Instantaneous Setting: OFF, 0.5~20.0/0.1In
Definite
(50/51) low set Operating time: 0.05~60.0/0.01s
Setting: OFF, 0.1~4.0/0.02In Curves
Time delay
Operating time: 0.05~1.20/0.01 (Inverse) SI, VI, EI, LI
Setting: OFF, 0.1~8.0/0.02In
Instantaneous Definite
Operating time: 0.05~300.0/0.01s
OCGR
Setting: OFF, 0.02~2.0/0.01In
(50/51N) Curves
Time delay Operating time: 0.05~1.20/0.01 (Inverse)
DT, SI, VI, EI, LI
0.05~60.0/0.01s (Definite)
Time delay Setting: OFF, 0.1~1.0/0.02In
Definite
high set Operating time: 0.08~60.0/0.01s
NSOCR
Time delay Setting: OFF, 0.1~1.0/0.01In
(46) Curves
low set Operating time: 0.05~1.00/0.01(Inverse)
DT, SI, VI, EI, LI
0.08~60.0/0.01s(Definite)
Io Setting: 0.02~2.0/0.01Ion
DGR Vo Setting: 11~80/1V Grounded system
Time delay
(67N) RCA Setting: 0~90/1 Definite
Operating time: 0.05~10.00/0.01s
Io Setting: 0.9~6.0/0.01mA
SGR Vo Setting: 11~80/1V Isolated system
Time delay
(67G) RCA Setting: 0~90/1 Definite
Operating time: 0.05~10.00/0.01s
THERMAL
Time delay Setting: OFF, 50~100/1% (h, c) Motor Config.
(49)
Time delay Setting: 0.50~10.00/0.01
STALL/ Motor Config.
(Stall) (FLCSVC.O/L)
LOCK
Time delay Operating time: 0.05~300.0/0.01s(Definite)
(48/51LR) Motor Config.
(Lock) 0.05~1.20/0.01(Inverse)
UCR Setting: 0.1~0.9/0.02In
Time delay Definite
(37) Operating time: 0.05~300.0/0.01s
Starts number: OFF, 1~5 times/1
NCH Base time: 10~60min/1min
- Notching
(66) Time between starts block: 1~60min/1min
Operating time: 10~80%/1%
RTD Setting: OFF, 20~180/1C
Time delay Definite
(38) Operating time: below 50ms

N1-6
Motor protection

Motor factor Setting & Operating time Remark

STALL/ Tss (Stall operating time): 0.05~300.00/0.01s


-
START TIME Ts (Motor starting time): 1.0~300.0/0.1s
FLC: 0.20~2.00/0.01In FLC: STALL Setting
FLC/LRC
LRC: 0.50~10.00/0.01FLC LRC: LOCK Setting
SERVICE
SVC: 1.00~1.20/0.05 -
FACTOR
Thermal const.(Heat): 2.0~60.0/0.5min
THR CONST Thermal const.(Cool): 2.0~60.0/0.5min THR (49) Setting
Overload Const. (O/L): 0.80~1.20/0.05
OCGR Operating
B/T : 0.00~60.00/0.01s
BLOCK TIME delay time

N1
Measurement

DPR-1000
Item Display range Remark

Line / Load current 0.000A ~ 999.99kA (CTpri) Start current (CTsec) : 0.050A

Starting current
0.000A ~ 999.99kA (CTpri) Start current (CTsec) : 0.050A
(Is_avg, Is_peak)
Starting time
0.000sec ~ 4294967.296sec -
(Ts_avg, Ts_peak)
%FLC, %FLCavg,
0.000% ~ 999.99% Start %FLC: 5.000%
%FLCpeak
0.000A ~ 999.99kA (CTpri) Start current (CTsec/ZCTsec)
Io, Io max
0.000A ~ 200.00mA (ZCTpri) : 0.050A/0.15mA

Vo, Vo max 0.000V ~ 999.99kV (PTpri) Start voltage (PTpri): 2.2V

I2 0.000A ~ 999.9kA (CTpri) Start current (CTsec): 0.050A

%Q, %Qavg, %Qpeak 0.000% ~ 150.0% Start capacity: 5.000%

TD Input (4~20mA DC) 0 ~ 20mA DC

N1-7
Digital Protective Relays
Dimension

100 100 4-M5

110.4

221.4

230
230

112.4

20 165

120 142 23
142.4

219.4
245

N1-8
Ordering

DPR-1000 FN RS D AI 60Hz

Protection usage Communication Protocol Analog Input Frequency

FN Feeder, Motor/NCT RS RS-485 M MODBUS AI 4~20mA 60Hz

FZ Feeder, Motor/ZCT - Without comm. - Without AI 50Hz

N1

DPR-1000

N1-9
DPR

Digital Protection Relay

Compact design
easy to operate and set
Back-lit LCD display

Adjustable current and operation time

The use of the output contacts are programmable

Fault recording function

Sequence of event function(S.O.E/Optional)

Various communication network configurations

EMC/EMI test certified


N2

Contents Features
Environmental characteristics
Constitution
N2-4
N2-5
N2-6
Additional functions N2-7
Overcurrent relay for phase and ground faults N2-8
(OCR & OCGR)
Selective Ground Relay (SGR) N2-10
Under and Overvoltage Relay (UVR & OVR) N2-12
Over Voltage Ground Relay (OVGR) N2-14
Characteristics curve N2-16
Dimensions and ordering N2-17
LSs advanced technology realized the digitalization of the measuring,
monitoring and protecting equipment in the power transmission and
distribution system.

Get a chance to use the reliable Digital Protection Relay and


Digital Integrated Meter.

GIMAC

GIMAC-i DPR

GIMAC-i DPR GIMAC-i DPR DPR


N2-4
It is applicable to various programs for power monitoring & control system.

Desktop PC

RS232C
RS485

Protocol
Converter
GMPC -

I-NET
C- Plus communication
network

N2

DPR

-RTU
DPR
N2-5
Digital Protection Relay (DPR)
Features

Compact design
124mm(Width) 177mm(Height) 243mm(Depth)
Easy to operate and set
Set and check all the values by operating the ket button in the front.
Back-lit LCD display
Back-lit LCD diaplay provide increased visibility
Easy to check the cause of a fault and setting status by the abundant indication functions
LCD flickers when all trips happens
Adjustable current and operation time
Minute setting steps for the current and time are appropriate for network protection.
The use of the output contacts are programmable
Various settings for output contacts(Trip or Alarm) are available
For details, refer to the table in page N2-15, 19
Fault recording function
When there is a fault in the power line, it records the fault wave forms for 10 cycles
to the EEPROM.
Sequence of event function(S.O.E/Optional)
It provides the sequence of the event (relay operation and cause of the fault and
data adjustment, etc) to the higher system by the mili second intervals and it helps to
analyze the cause of the fault easily.
Various communication network configurations
-NET exclusive communication and Modbus communication(optional)
EMC/EMI test certified

N2-6
Environmental characteristics

IEC 60255-5 2kV rms. for 1 minute between all case terminals connected together
and the case earth.
Dielectric withstand KEMC 1120 2kV rms. for 1 between all terminals of independent circuits
with terminals and each independent circuit connected together
1kV rms. for I minute between each all terminals of open contact circuits
IEC 60255-5 5kV peak, 1.250, between all terminals connected together and case earth
KEMC 1120 5kV peak, 1.250, between mutual PT/CT circuits
5kV peak, 1.250, between PT/CT circuits and control circuits
High voltage impulse
3kV peak, 1.250, between mutual control circuits
3kV peak, 1.250, between all terminals of PT/CT circuits
3kV peak, 1.250, between all terminals of control power supply circuits
IEC 60255-5 DC 500V 10 and over between all case terminals connected together
and the case earth.
Insulation resistance KEMC 1120 DC 500V 5 and over between all terminals of independent circuits
with terminals and each independent circuits connected together
DC 500V 5 and over between each terminals of open contact circuits
KEMC 1120 Current circuit : In2 for 3 hours(2 times by 1 minute interval)
In20 for 2 seconds
Overload capacity
JEC-2500 In40 for 1 second
KEMC 1120 Voltage circuit : Vn1.15 for 3 hours (1 time)
IEC 60255-22-1 2.5kv peak between independent circuits and case
High frequency disturbance
Class 1.0kv peak across terminals of the same circuit
IEC 60255-22-4 4kv applied directly to power input
Fast transient disturbance
Class 2kv applied to other inputs
IEC 60255-22-2 8kv discharge in air with cover in place
N2
Electrostatic discharge (ESD)
Class 6kv point contact discharge with cover removed
KEMC 1120 Making a wave by accessing to the edge of relay
RFI

DPR
with 5W transceiver(150MHz, 400MHz)
EN 50081-2 AC power:0.15~0.50MHz, standard 79dB, average 66dB
EMI
Class 0.50~30MHz, standard 73dB, average 60dB
Operating temperature IEC 60068-2-1 -10~55
Storage temperature IEC 60068-2-2 -20~70
Humidity IEC 60068-2-3 56 days at 93% RH and +40
IEC 60255-21-2 30g, 3times/dir.
Shock Class
KEMC 1120
Vibration KEMC 1120 30Hz, 0.4mm vibration applied for 600 seconds
Enclosure protection IEC 529 IP 50(dust protected)

N2-7
Digital Protection Relay (DPR)
Constitution

Indicators
Alarm: Alarm status LED
Run: Normal operation
status LED
DISPLAY Comm: Communication
2 linesback-lit LCD for status LED

fault indication and setting Trip: Trip status LED

UP key Down key


Increasing setting value Decreasing setting value
Shifting to each menu Shifting to each menu

FUNC key
Shifting to each menu
ENT/RESET key M4 screw

ENT : Selecting menu


or data
Reset: Resetting after
relay operation

System constitution

RS232C
RS485

Protocol
converter
GMPC-

I-NET I-NET

DPR1 DPR1
DPR2 DPR2
DPR3 GIMAC3
GIMAC4
DPR4
DPR20 GIMAC20

N2-8
Additional functions

Constant-supervision with self-diagnostics


High reliability of relay will be provided by various self-diagnostics function. When errors occurs it will be displayedError No.at LCD
display window, then the front ALARM LED lights on and LCD display window flickers on also.
At the same time ALARM relay(Sys fail) will be output.
1. internal ROM check:Error 1
2. internal RAM check:Error 2
3. A/D converter check:Error 3
4. CPU watchdog check:Error 4
5. Power supply check:Error 5
6. EEPROM(Backup memory) check:Error 6
7. Calibration check:Error 7
When the self-diagnostics error happens, the relay is not operated until the cause of that fault is cleared.

Fault records
1. The fault curves are recorded into EEPROM when line fault happens, which will provide fast and correct grasping for the cause of a fault.
2. Storage the sample value of each phase for 10 cycles before and after the fault
5 cycles before the fault
5 cycles after the fault
8 samples for a cycle
3. A fault recording information is available for ascertaining them via communications.

Sequence of event (S.O.E)


Many events (including relay operation, cause of fault, data adjustment) can be provided to the higher system
1. Kinds of event
The cause of a relay operation(trip)
The data adjustment of a relay
N2
Error occurrence of auto-diagnostics
Relay resetting

DPR
2. Twenty events are stored in a buffer (maximum)

Communication specification
1. I-NET communication
High speed, high reliability of serial communication by use of the custom LSI(GC829016) developed by LSIS
1) Data rate : 250kbps
2) Cable length : 1000m(max.)
3) Insulation : Pulse Transformer
4) Connection : 4 Wires multi-drop
5) Signal modulation : Bipolar modulation
6) Connectable quantity : max. 20units per a GMPC(a protocol converter)
7) Address : Parameter setting from 1 to 255
8) Communication cable : Low capacitance LAN interface cable
Spec : LIREV AMESB 22AWG 2-pair (1/0.643)
Impedance : 10MHz, 120()
Termination : Please use it by connecting 2 resistors with each end of cable
2. MODBUS communication (Optional)
FIELD BUS open protocol applied
Please contact us before applying this communication method

N2-9
Digital Protection Relay (DPR)
Overcurrent relay for phase and ground faults (OCR & OCGR)

Features
Self-diagnostics High speed serial data communication
Fault recording International standard applied
Sequence of event(S.O.E) - IEC 60255, IEC 61000-4, KEMC 1120

Operation characteristic curves (Refer to page N2-18)


Standard inverse time Long inverse time
Very inverse time Definite time
Extremely inverse time
DPR-111

Type designation DPR-011 DPR-111


ANSI code 50/51 3 50/513
50/51N1
Ratings Current(In) 5A
Frequency(fn) 50/60Hz
Control power(Vx) DC 110/125/220V (DC 85~220V)
Input burdens 0.5VA and below
Relay elements 3 phase overcurrent protection(OCR) 3 phase overcurrent protection(OCR)
Ground fault overcurrent protection(OCGR)
Setting range Time delayed Phase 1~16A/0.5A (20~200%) 1~16A/0.5A (20~200%)
setting Earth 0.2~2.5A/0.1A (4~50%)
Instantaneous Phase 10~160A/5A (200~3200%), Lock 10~160A/5A (200~3200%), Lock
setting Earth 2.5~40A/2.5A (50~800%), Lock
Operating time Time delayed Inverse Standard inverse, Very inverse, Extremely inverse, Long inverse
element 0.05~1seconds in a 0.2 step
Definite 0.1~10seconds in a 0.2 step
Instantaneous Definite Within 35msec
Additional function Self-diagnostics
Fault recording
Sequence of event(S.O.E)
Communication mode I-NET
Display Back-lit LCD(Dot matrix)
Output contacts Switching Make 10A/250Vac, 0.5sec, resistive
capacity Break 1A/250Vac 0.1PF
Constitution (7EA) Note) Trip relay 2a, 1250VA and over
Alarm relay 4a
System fail relay 1a
Type At trip operation Trip relay+Trip LED+Alarm relay
Seif-diagnostics error System fail relay+Alarm relay
At normal RUN LED
Insulation resistance DC 500V 100 and over
Dielectric withstand 2kV(1kV) rms. and over for 1 minute
High voltage impulse 5kV(3kv) peak and over applied for 1.2 50
Overload capacity Current circuit Rated current(In)2 for 3 hours
Rated current(In)20 for 3 seconds
Rated current(In)40 for 3 seconds
Voltage circuit Rated Voltage(Vn)1.15 for 3 hours
Temperature Operating -10~55
Storage -20~70
Humidity 80% RH (Non-condensing)
Applied standard IEC 60255, IEC 61000-4, KEMC 1120
Weight 3.2kg
Dimension 124(W)177(H)243(D)mm
Note) The output contacts are programmable.

N2-10
Connection methods

3phase 3wires

3phase 4wires
Terminal block
OCR/OCGR-A OCR/OCGR-B
1 F.G 2 TX0 1 Rk 2 Rl
3 DC+ 4 TX1 3 Sk 4 Sl
DC- 6 RX0 6
5
7 8 RX1
5
7
Tk
8
Tl
N2
Nk Nl
9 10 ALARM2 9 10
11 12 ALARM2 11 12
13 TRIP 1 14 ALARM3 13 14

DPR
15 TRIP 1 16 ALARM3 15 16
17 TRIP 2 18 ALARM4 17 18
19 TRIP 2 20 ALARM4 19 20
21 ALARM1 22 ALARM5 21 22
23 ALARM1 24 ALARM5 23 24
DPR-111

Output contacts OCR, OCGR


:Default(when shipment) :Programmable :Not available

Kinds of TRIP RELAY ALARM RELAY


Unit Output contacts
contacts TRIP Trip-INST Trip-TD ALM-Trip ALM-INST ALM-TD ALM- I1 ALM-I2 ALM-I3 ALM-I4 ALM-Sys Fail PICK-Up No use
TRIP 1 for
TRIP 2 Trip
OCR ALARM 1
/ ALARM 2
OCGR for
ALARM 3
Alarm
ALARM 4
ALARM 5
Time Time Self-
Instantaneous Instantaneous RphaseSphase TphaseNphase Overload
Purpose of contacts Trip delayed Trip Alarm delayed diagnotics No use
Trip Trip Trip Trip Trip Trip Pre alarm
Trip Trip Error
Note 1) Alarm relay can not be used for Trip (CB control) contacts.
Note 2) Alarm-I4 is not available for DPR-011(OCR)
Note 3) In case of Trip1, Trip2, the contacts, status are stored as an EVENT, if they were changed during operation

N2-11
Digital Protection Relay (DPR)
Selective Ground Relay (SGR)

Features
Self-diagnostics High speed serial data communication
Fault recording International standard applied
Sequence of event(S.O.E) - IEC 60255, IEC 61000-4, KEMC 1120

Operation characteristic curves (Refer to page N2-18)


Definite time

DPR-211 Type designation DPR-211


ANSI code 67G
Ratings Zero phase current(lon) 1.5mA
Frequency(fn) 50/60Hz
Zero sequence voltage(Von) 190V
Control power(Vx) DC 110/125/220V(DC 85~220V)
Input burdens 0.5VA and below
Relay elements Selective earth fault protection(SGR)
Setting range Operating current(Io) 0.9~5.4mA/0.3mA
Operating voltage(Vo) 4~76V/4V
Operating phase angle 0 , 30, 45, 60, 90
Operating time Definite time 0.1~10seconds in a 0.1 step
Additional function Self-diagnostics
Fault recording
Sequence of event(S.O.E)
Communication mode I-NET
Display Back-lit LCD(Dot matrix)
Output contacts Switching capacity Make 10A/250Vac, 0.5sec, resistive
Break 1A/250Vac 0.1PF
Constitution (3EA) Trip relay 1a, 1250VA and over
Alarm relay 1a
System fail relay 1a
Type At trip operation Trip relay+Trip LED+Alarm relay
Self-diagnostics error System fail relay+Alarm LED
At normal RUN LED
Insulation resistance DC 500V 100 and over
Dielectric withstand 2kV(1kV) rms. and over for 1 minute
High voltage impulse 5kV(3kv) peak and over applied for 1.250
Overload capacity Voltage circuit Vn1.15 for 3 hours
Temperature Operating -10~55
Storage -20~70
Humidity 80% RH
Applied standard IEC 60255, IEC 61000-4, KEMC 1120
Weight 2.8kg
Dimension 124(W)177(H)243(D)mm

N2-12
Connection methods

Terminal block
SGR
1 F.G 2 TX0
3 DC+ 4 TX1
5 DC_ 6 RX0
7 8 RX1
9 GPTk 10 GPTl
11 12
13 ZCTk 14 ZCTl N2
15 16
17 18 ALARM1
19 20 ALARM1

DPR
21 TRIP 22 ALARM2 DPR-211
23 TRIP 24 ALARM2

Operating phase characteristics


Output contacts of SGR
:Default(when shipment) :Programmable :Not available Zero Current
132 RCA(45)
Kinds of Trip relay Alarm relay
contacts
Unit Output
contacts TRIP ALM-Trip ALM-Sys fail ZONE 1

Trip for Trip ZONE 2


Zero
Voltage
SGR Alarm 1
for Alarm
Alarm 2 Zero current
setting value(los)

Self-Diagnostics Zero voltage


Purpose of contacts Trip Trip Alarm
Error setting value(Vos)
318
Note) Alarm relay can not be used for Trip(CB control) contacts. Operational zone : Zone 1 (RCA87)
Voltage/current status of Zone 1 : Vo>Vos, lo>los
RCA : Relay characteristic anglae

N2-13
Digital Protection Relay (DPR)
Under and Overvoltage Relay (UVR & OVR)

Features
Self-diagnostics High speed serial data communication
Fault recording International standard applied
Sequence of event(S.O.E) - IEC 60255, IEC 61000-4, KEMC 1120

Operation characteristic curves (Refer to page N2-18)


Definite time

DPR-411

Type designation DPR-311 DPR-411


ANSI code 59(27) 59/27
Ratings Volltage(Vn) 110V
Frequency(fn) 50/60Hz
Control power(Vx) DC 110/125/220V (DC 85~220V)
Input burdens 0.5VA and below
Relay elements 3phase overvoltage protection(undervoltage protection) 3phase overvoltage protection(OVR)
-Selecting UVR or OVR 3phase overvoltage protection(UVR)
Setting range Time delayed OVR 121~165V/2V (110~150%)
UVR 55~99V/2V (50~90%), No-voltagge locking Note1)

Operating time Time delayed definite element 0.05, 0.1~10seconds in a 0.1 step
Additional function Self-diagnostics
Fault records
Sequence of event(S.O.E)
Communication mode I-NET
Display Back-lit LCD (Dot matrix)
Output contacts Switching capacity Make 10A/250Vac, 0.5sec, resistive
Break 1A/250Vac 0.1PF
Constitution(6EA) Note2) Trip relay 2a, 1250VA and over
Alarm relay 3a
System fail relay 1a
Type At Trip operation Trip relay+Trip LED+Alarm relay
Self-diagnostics error System fail relay+Alarm relay
At Normal RUN LED
Insulation resistance DC 500V 100 and over
Dielectric withstand 2kV(1kV) rms, and over for 1minute
High voltage impulse 5kv(3kV) peak and over applied for 1.250
Overload capacity Voltage circuit Vn1.15 for 2 hours
Temperature Operating -10~55
Storage -20~70
Humidity 80% RH (Non- condensing)
Applied standard IEC 60255, IEC 61000-4, KEMC 1120
Weight 3.1kg
Dimension 124(W)177(H)243(D) mm
Note 1) No-voltage lock : The lock function can be selected not to be tripped when no input voltage appeared (20% and under of rated voltage)
Note 2) The output contacts are programmable.

N2-14
Connection methods

Terminal block
OVR/UVR
Definite Time 1 F.G 2 TX0
3 DC+ 4 TX1
5 DC_ 6 RX0
7 8 RX1
9 Rk 10 Rl
11 Sk 12 Sl
13 Tk 14 Tl
15 16 ALARM1
17 TRIP1 18 ALARM2
19 TRIP1 20 ALARM3 N2
21 TRIP2 22 ALARM4
23 TRIP2 24 ALARM COM

DPR
DPR-411

Output contacts of OVR/UVR :Default(When shipment) :Programmable :Not available


Kinds of Trip relay Alarm relay
Unit Output contacts
contacts Trip Trip-3phase Alm-Trip Alm-3phase Alm-V1 Alm-V2 Alm-V3 Alm-Sys fail Pick-Up No use

Trip 1
Note 3)
for Trip
Trip 2

OVR
Alarm 1
/
Alarm 2
UVR
for Alarm
Alarm 3

Alarm 4

1phase and
Self-
over R,S,T all 1phase and 3phase RphaseSphaseTphase Overload
Purpose of contacts diagnostics No use
fault among phase fault over trip Trip Trip Trip Trip Pre alarm
Error
of R,S,T
Note 1) Alarm relay can not be used for Trip(CB control) contacts.
Note 2) DPR-311 is available for selectable use as OVR or UVR, and it will be set on UVR when shipment.
Note 3) DPR-411 is used as OVR, UVR multiple relay. The Trip 1 is OVR and Trip 2 is for UVR as Trip contacts and it can be selected by Trip or Trip- 3phase.

N2-15
Digital Protection Relay (DPR)
Over Voltage Ground Relay (OVGR)

Features
Self-diagnostics High speed serial data communication
Fault recording International standard applied
sequence of event(S.O.E) -IEC 60255, IEC 61000-4, KEMC 1120

Operation characteristic curves (Refer to page N2-18)


Standard inverse time long inverse time
very inverse time definite time
extremely inverse time
DPR-511

Type designation DPR-511


ANSI code 64
Ratings Voltage(Von) 190V or 190/ 3V
Frequency(fn) 50/60Hz
Control power(Vx) DC 110/125/220V (DC 85~220V)
Input burdens 0.5VA and below
Relay elements Over Voltage Ground Protection (OVGR)
Setting range Time delayed setting 20~76V/2V (10.5~40%)
Instantaneous setting 20~76V/2V (10.5~40%), Lock
Operating time Time delayed element Inverse Standard inverse, Very inverse, Extremely inverse
0.05~1.00sec in a 0.01sec step
Definite time 0.1~10sec in a 0.1sec step
Instantaneous element Definite time Within 35 msec
Additional function Self-diagnostics
Fault records
Sequence of event(S.O.E)
Communication mode I-NET
Display Back-lit LCD (Dot matrix)
Output contacts Switching capacity Make 10A/250Vac, 0.5sec, resistive
Back 1A/250Vac, 0.1PF
Constitution (3EA) Trip relay 1a, 1250VA and over
Alarm relay 1a
System fail relay 1a
Type At Trip operation Trip relay+Trip LED+Alarm relay
Self-diagnostics error System fail relay+Alarm relay
At Normal RUN LED
Insulation resistance DC 500V 100 and over
Dielectric withstand 2kV(1kV) rms. and over for 1 minute
High voltage impulse 5kV(3kV) peak and over applied 1.250
Overload capacity Voltage circuit Vn1.15 for 3 hours
Temperature Operating -10~55
Storage -20~70
Humidity 80% RH
Applied standard IEC 60255, IEC 61000-4, KEMC 1120
Weight 2.8kg
Dimension 124(W)177(H)243(D) mm

N2-16
Connection methods

Terminal block
OVGR
1 F.G 2 TX0
3 DC+ 4 TX1
5 DC_ 6 RX0
7 8 RX1
9 GPTk 10 GPTl
11 12 N2
13 14
15 16
17 18 ALARM1

DPR
19 20 ALARM1
21 TRIP 22 ALARM2
DPR-511
23 TRIP 24 ALARM2

Output contacts of OVGR


:Default(When shipment) :Programmable :Not available

Kinds of Trip relay Alarm relay


Unit Output contacts
contacts Trip Alm-Trip Alm-Sysfail

Trip for Trip

OVGR Alarm1

for Alarm

Alarm2

Self-diagnostics
Purpose of contacts Trip Trip alarm
error
Note) Alarm relay can not be used for Trip(CB control) contacts.

N2-17
Digital Protection Relay (DPR)
Characteristics curve

Standard inverse - (OCR, OCGR, OVGR) Very inverse - (OCR, OCGR, OVGR)
Standard inverse time (SI) Very inverse time (VI)
100 100

10

10

Operating(sec)
Operating(sec)

1
1.0 1.0

0.4
1 0.4 0.3
0.3 0.2
0.1
0.2 0.1

0.05
0.1

0.1 0.05 00.1


1 10 20 1 10 20
Current(Multiples of setting, I/Is) Current(Multiples of setting, I/Is)

Extremely inverse - (OCR, OCGR, OVGR) Long inverse - (OCR, OCGR, OVGR)
Extremely inverse time (EI) Long inverse time (LI)
1000 1000

100
100

10
Operating(sec)

Operating(sec)

10
1.0

1
0.4
0.3
0.2
1.0
1
0.1 0.4
0.1
0.3
0.2 0.05

0.1
0.01 0.05 0.1
1 10 100 1 10 20
Current(Multiples of setting, I/Is) Current(Multiples of setting, I/Is)

N2-18
Dimensions and ordering

Dimensions

Cut-out dimension

N2

DPR

Ordering

DPR - 0 1 1

Protection element Control voltage Communication


0 OCR 1 DC 110/125/220V 1 I-NET
1 OCG/OCGR
2 SGR
3 OVR(UVR) Note 1)

4 OVR/UVR
5 OVGR
Note) DPR-311 is available for selectable use for OVR or UVR and DPR-411 is multi-relay with OVR and UVR

N2-19
IMC-III

Intelligent Motor Controller

IMC-III is for low voltage motor under 1000V,


and is integrated motor protection relay,
Indication lamp, Current transformer(CT).
IMC-III is intelligent motor controller which has
high micro-Processor Technique.
O

Contents Main characteristic


Ratings and function
Main function description
O-6
O-8
O-10
Operation and setting O-12
Wiring method O-16
System configuration O-20
Accessories O-22
Dimension & Ordering O-23

IMC-III includes Direct, Y-, Forward/Reverse, Reactor,


Inverter, S/V valve start, solution for complicated water
treatment Sequence.
IMC-III also has various motor protection function, and is
possible to communicate with PLC, Water level for auto
operating, remote control and monitoring by RS-485,
4~20mA(only monitoring).
IMC-III Digital motor
protection control unit

Various motor start application


within one model.
IMC-III includes Direct, Y-, Forward/Reverse, Reactor, Inverter,
S/V valve start, solution for complicated water treatment Sequence.

Direct start
Y- start

Reactor start

For/Rev
start

Inverter start

S/V valve start

Overcurrent

Under current

Unbalance
Stall/Locked
Phase rotor
Earth Phase loss
fault reverse
Various protection function
Safely protection for over current, Under current,
Phase loss, Unbalance, (Stall, Lock)
Earth fault, Alarm function.

O-4
Emergency
Stop
SCADA

PLC Local operating


panel

Water Level

Various remote control


and monitoring
It is possible to operate at MCC and LOP
by just simple sequence, also can be
automatic operation up to water level by
O
remote control and monitoring with
PLC/DCS.
MCC
IMC-III

O-5
Intelligent Motor Controller
Main characteristic

Easy and convenience installation


It can be checked fault analysis and operated motor by inserting the main unit into panel. Its
possible to set current/operating time/various function easily by simple button. And it can be also
composed of compact MCC, minimized wiring work, so user can reduce labor cost.

TIMER CT

Aux Relay Button & Lamp

EMPR or TOR A-Meter

Internal

Front

Minimizing wiring
work
Reduce labor cost
Compact size panel
Easy maintenance
Good design
Various function

Wide current setting range : 0.125A~1000A within 1 model


It can be changed from 0.5~6A to 5~60A by slide S/W, the current can be changed to 0.125A
up to MCT number of the time of penetrating current line.

External CT 2 times(0.25~3A) 4 times(0.125~1.5A)


* External CT : Note p22 (option) A group 5.ctr 0.5 setting A group 5.ctr 0.25 setting
* MCT : Molded current transformer(Enclosing with product)

O-6
The moment stopping of power supply compensation and Restart
The moment stopping of power supply compensation Ex) Incase of restarting delayed time 30S
- Line current reduces under 65% of rated voltage.
- When the moment stopping of power supply within 10S,
IMC-III makes it restart same as before condition.
Restart delayed time(0~300S)
- When the line voltage recovers over 75% rated voltage, Information
it can be restarted.
It can be changed operation mode (ON, OFF) and
- when it restarted, IMC-III makes it sequence restart 0~300s for count time during countdown
prohibition overload. Changed operation mode can be applied after
- Indication of Restart delayed time countdown. finishing count.

Operating condition and maintain operation mode When the short stopping power supply generates
under 100ms, IMC-III dose not detect, so the motor
- It can be maintained before the moment stopping power will maintain normal condition
supply condition(Local, MCC, Auto, W/L, Remote)

Digital ampere-meter
Bar LED
It can be monitored indication of R, S, T current, and load ratings(%) by Bar LED. Indication of load ratings

R-phase S-phase T-phase Max current

Fault analysis and Recording


It can be indicated fault cause and fault current value by 7-segment and LED.
At the moment of instantaneous stopping of power supply, it can solve the problem. Because of the fault storage.

O
Self-supervision and contactor failure function
IMC-III

IMC-III can be checked self-supervision like a memory fault. When the motor starts/stops,
that indicates Error.No and turn on Sys.Fail LED by supervising Input/output condition.

Total operation time setting and storage


It can be stored motor operation time up to 10 years. Continuous operation time can be stored and setting.
Information
When the user contact mode is normal mode, even if indicatingOrH Alarm, motor operates in normal condition

Communication function
Its possible to communicate with other system and organize various communication Network by
MODBUS/RS-485. And its also possible to communicate with system by Analog current signal(4~20mA).
So that makes it possible to interchange by using TD(Transducer).

O-7
Intelligent Motor Controller
Ratings and function

Rating
Model IMC-III
Operating time Characteristic Inv/Def time
Current range(A) 0.125~60A(Within 1 model)
Time setting (s) Inverse time 1~60sec/1sec(Class)
Definite time D-Time * 1~200sec/1sec
O-Time * 1~60sec/1sec
Auto re-closing time 1~20min/1min, OFF
Control power Voltage AC 110V or AC 220V(15%)
Frequency 50/60Hz
Power consumption Under 6W
Output contact Capacity 5A/250VAC impedance load
(9EA) Composition Operating contact 3a Forward/Reverse, Y-, Reactor, Inverter start
Condition contact 3a Local, Auto, W/L condition indication
Timer contact 2a ON delay, OFF delay
Trip contact 1a Fault output contact
Input contact Operating input 5a Local, Auto, Water, Level, Flow, switch operating inout
(9EA) MC condition input 1a Sequence condition monitoring(LED)
External trip 2a Emergency stop, Sequence
ZCT Ratings 200mA/0.1mA(ZCT)
Specification 25, 40, 80
Indication 7-Segment 3-Phase current, Trip cause, Settings
LED Operating condition, Trip, System fail settings
Self-Diagnostic System fail LED and err indication
Communication(Option) Modbus/RS-485 or 4~20mA
Installation Inside the panel
Separate cable MCT cable 2m base(4m cable option)
Insulation voltage AC 2kV(1.5kV) / 1 min
Impulse voltage Over AC 5kV(3kV), 1.2x50s
Insulation resistance Over DC500V 10M
Power frequency magnetic field 100A/m, 50Hz
Burst disturbance Common 2.5kV
Differential 1.0kV
Fast transients disturbance Input 2kV, Other Input 1kV
Electrostatic discharge Air 8kV, Contact 6kV
RFI 30cm near electric wave by
5W transceiver(230MHz)
EMI AC power : 0.15~0.50MHz, Standard : 79dB, Average : 66dB
0.50~30MHz, Standard : 73dB Average : 60dB
Operating temperature -10 ~ 55
Storage temperature -20 ~ 70
Relative humidity 93% @40 for 56days
Standard IEC 60255, IEC 61000-4, IEC 60068-2, EN 50081-2
Weight 0.6kg(MCT 0.35kg)
Dimension Main unit 148(W) 100(H) 74(D) mm
MCT 151(W) 55(H) 33(D) mm
* D-Time(Delay time) : It is delay time for IMC-III start during motor start time
* O-time (Operating delay time) : When over current generates more then setting current, that makes it delayed until IMC-III operated.

O-8
Motor protection
Operating condition Time Remark
Over Inverse Over 110% setting current 1~60s/1s 600% standard operating time
current Definite time Over 105% setting current 1~60s/1s Delay time 1~200s
Phase fault Over 70% current phase unbalance Within 1.5s
Phase unbalance Current phase unbalance 30~50% Within 5s
Reverse phase Reverse the current phase Within 0.1s Over 110% minimum ratings
Under current Rating current 30~70% Within 3s
Holding Stall Rating current 150~300% Within 5s
Detection after over current setting time
Locked rotor Rating current 200~700% Within 0.5s
Ground fault The current rating 0.1~2.5A setting 0.05~1.0s Ground fault delay operation
Pre-alarm Over 120% setting value Bar-LED blinking

Sequence function
Contents Remark
Operating type Direct operation Non-reversible direct operation
operation
Y- Y operation time 1~120s/1s
switching time
Y- 0.05, 0.1, 0.2s
Forward / Reverse operating Reversible direct operation
Reactor Reactor time 1~120s/1s
Inverter Inverter delayed time ON 1sec/0.1sec
Instantaneous Compensation time OFF 1~10s /1s
under voltage Re-operation delay time 0~300s /1s
compensation Under voltage detection (Rating control voltage 65%) 10%
Recovering voltage detection (Rating control voltage 75%) 10%
User contact Normal Normal mode
point mode Time delay ON delay
0~300s/1s
OFF delay
Flow switch ON delay
Comparing
OFF delay 0~300s/1s
Timer ON delay timer
Comparing timer
Remote control Local LOP(Local Operation Panel) O
MCC Motor Control Center
Auto PLC, DDC, DCS auto operation
W/L Water Level
IMC-III

Remote Modbus/RS-485 communication

Communication function
Type Contents Specification Remark
Protocol Modbus_RTU
Communication RS-485
Modbus Operation Differential
/ Baud rate 9600, 19200, 38400bps
RS-485 Length Max 1.2km Different from local situation
Cable RS-485 Shielded twist 2-pair cable
Transmission Half-duplex
Max in/Output voltage -7V ~ +12V

O-9
Intelligent Motor Controller
Main function description

Protection function

Overload protection(49)
Overload protection function senses current which is flowing on
the motor, and tracing the heat, and then protects. When the
heat capacity approaches, it generates overload trip, and this
heat capacity is calculated by characteristic curve and It.
Class1 ~Class60 overload characteristic curve is determined by

sec

sec
setting motors rated current, considering motor operating time,
setting operating time 1s~60s by according to 600% of setting
current.
When you choose the definite time characteristic, it starts over
current after Delayed time and if over current keeps applying
over Operation-time, it generates trip.
current current
<Inverse time> <Definite time>
Stall/Locked rotor protection (48/51LR)
When the fault generates like locked rotor, the mechanical units
like pump, fan can be damaged easily. IMC-III prohibits stall, locked rotor, start failure, over
current and open the circuit when the current increases rapidly, load torque exceeds the motor
torque. But IMC-III has delayed time, it can not be tripped by operating current.

Under current protection(37)


Protection of no-load condition by operating axis separation , maintenance of pump noload and
sec
in case of motor frigidus method, it can be used for protection of operating terminal overload.
Its possible to set 30~70% of rated current, it operates within 3s.

Phase fail/Phase unbalance protection-47P


If the phase fail generates due to the motor internal fault or wiring problem. Motor cannot
operate or keep operating,
current
In this case, high reverse phase current applied, so motor can be damaged. IMC-III will trip
within 1.5s when the unbalance rate is over 70%. IMC-III will trip within 5s, when the unbalance
rate is over 30~50%. However,
when you applied 1p motor, it can not be detected phase-fail and unbalance. User has to be off in this case.

Reverse phase protection


Reverse phase protection prohibits motor reverse rotation when the phase of current changed each other.
IMC-III will trip within 0.1s, when the phase changed each other by comparing 3phase difference.
IMC-III can detect the reverse phase over minimum 110%, of setting current, during motor operation.
When the 1p motor is applied, it can not be detected reverse phase. User has to be off in this case.

Ground fault protection-51G


This function protects fault circuit by detecting earth fault, ground fault. And this function also protects second
fault (short circuit, electric shock) by detecting earth fault current. User has to set the current value, operating time
differently by protection system. Ground fault sensing current can be set 100~2500mA, and ground fault
operating time can be set 0.05s~1s. The separate ZCT (Zero phase current transformer) is used for
detecting ground fault current. However, when the IMC-III start inverter operation, it can not be protected
ground fault Protection. User has to be OFF.

O-10
Fault analysis, fault recording Self-diagnostic function
User can check fault current value by UP/DOWN button and fault
When MC condition input contact point is ON after
recording can be checked by [ESC + ENT].
output contact OFF operating.

When MC condition input contact point is OFF,


after output contact point ON operating.
Overload Under current

When the external input contact pointFOR


,
is applied at once.
REV

Locked rotor Stall


EEPROM Fault

Phase fault Phase unbalance


Flow switch (F-S) mode

Reverse phase Ground fault

In case of no F/S input When it passed the


within setting time operating setting time

Time delay(t-d) mode

Motor start
1) If F/S (FlowSwitch) is applied within setting comparison timer-ON
Delay timer after ON operation. After ON delay timer, motor will
operate.
2) If F/S is not applied, ON will be canceled, t2-F will be
indicated, will maintain OFF condition.
1) After ON operation, it passed ON delay time, 88M will be ON O
and motor will operate. Motor operation
2) After OFF operation, it passed OFF delay time, 88M will be
1) During motor operation, if F/S input is out of state, 88M will be
IMC-III

OFF and motor will be stopped.


OFF, Motor will stop.
2) At this time, the comparison timer will operate, and if F/S is
External trip input
reapplied within setting comparison timer-ON Delay timer, motor
will be re-started in normal Condition
3) If F/S is not reapplied within comparison timer-ON Delay timer, t2-
F will be indicated, motor keep stopping.
4) When user operates OFF, 88M will be OFF, after OFF delay
time, motor will stopped.
ex) When the T1 timer : 1s, T2 Timer : 10s, T3 Timer 5s set, F/S
re-applied time after F/S OFF has to be within 10s-5s = 5s and
t2-F will not indicated, motor will be re-started in normal
condition.
* When the external trip generates it will be OFF simultaneously irrespective of ON/OFF Delay Timer Note) Comparison timer has to be set more than ON Delay timer.

O-11
Intelligent Motor Controller
Operation and setting

Front view
Current & Operation mode
Information LED

R, S, T Phase
Condition LED
indication

Standard unit & Malfunction


load ratings preventing
Cover
Indication LED
of load ratings

Motor condition
LED

Setting value
Motor start
choice & move to
button
contents

Trip Reset button Setting store


button

Operation mode
Move to previous
button
button

Indication of trip
IMC-III main unit analysis,
Indication of
setting group.

MCT

Rear view Setting method


1) The first stage will be indicated maximum current in
Rating type znormal condition.
setting S/W
Communication MCT connection 2) When the UP/DOWN button is pushed, A, B, C group is
connection CON CON
indicated.

RX0
3) When user push the ENT button after selecting group, it
4~20mA pole
pole RX1 move to the detail setting contents.
TX0
TX1
4) After selecting contents by pushing UP/DOWN button, if
user push the ENT button, the setting value will be
stored.
5) When UP/DOWN button is pushed, the setting value
will change, so that after selecting contents, if you push
the ENT button , setting value will be stored.
6) After setting, if user push the ESC button, IMC-III will be
returned normal operating condition.
Note) 1. Pls note that setting value can be changed during motor operation.
2. If user did not operate for 10S , Setting value and group setting contents will
returned to current indication mode automatically.

O-12
Group No. Setting Indication Setting value Default value Remark

1 Characteristic
(Over current protection) Inu/dEF Inu Inverse/Definite time selection

2 Operating time In case of definite time,


(Over current protection) 1~60/1sec 60 motor operating time

3 Operating delayed time


(Over current protection) 1~200/1sec 200
Basic setting

4 Setting of rated current 0.5~6/0.1(A), 5~60/1(A) 6 / 60 6/60A selection

5 CT ratio 0.25, 0.5, 1~200/1 1 Impossible to set in case of selection 60A

6 Start type selection dir/y-d/F-r/Ind/Iut dir Direct, Y-. Reactor, Inverter start
A. grp

7 5 Reactor start time Inverter start delayed time


Y operation time 1~120/1sec (Inverter start :0) (0~1sec)

8 Y-D switching time 0.05, 0.1, 0.2(sec) 0.2

9 Short time power off


compensation time OFF, 1~10/1sec OFF

10 9. It can be indicated only in case of short


Re-start time 0~300/1sec -
time power stop compensation time

1 Lock protection OFF, 200~700/100(%) OFF

2 Stall protection OFF, 150, 200, 300(%) OFF

3 Phase-fault
OFF/On On
Protection function

protection enabled

4 Unbalance protection OFF, 30, 40, 50(%) OFF

5 Reverse phase protection OFF/On OFF Only during operation

6 Under current protection OFF, 30~70/5(%) OFF

7 Ground fault protection OFF/On OFF OFF setting in case of inverter start
B. grp

8 Ground fault
0.1, 0.2, 0.5, 1.0, 1.5, 2.0, 2.5(A) 0.1
operation current

9 Ground fault 7. Indication by ground fault


0.05, 0.1~1.0/0.1sec 0.05
operation time protection seleection

10 Ground fault delay OFF/On OFF

1 I/O state information 4-segment Notify the manual

Time check, Day hour, min


2 Total operation time Total operation time checking
Setting disabled (Max.1year : 8760 hour) O
3 Time check, Operation time Day Hour, min
Operation time Operation time checking
Setting disabled (Max 1year : 8760 hour)

4 After reached setting operation time,


Operation time setting OFF, 10~8760/10(H) OFF
IMC-III

indicatingOrH
Additional function

5 MC condition input check


Contactor check OFF/On On
(OFFnot indicated Err1,2)

6 User contact
nor/t-d/F-S nor Normal/Time delay/Flow switch
point mode

7 ON Delay Timer 0~300sec/1sec 0


In case of t-d, F-S mode selection,
it can be set
8 OFF Delay Timer 0~300sec/1sec 0
C. grp

9 Comparison timer 0~300sec/1sec 0 In case of F-S mode selection, it can be set

10 Auto- returning OFF, 1~20min/1min OFF

11 Communication address 1~255 1 Only indication of communication model

12 Communication Spped 96, 192, 384 96 bps(100)

13 Floating data frame reverse


SWAP OFF/On On
(3, 4, 1, 2) selection

O-13
Intelligent Motor Controller
Operation and setting

Rated current setting


1) IMC-III rated current can be selected 6A(0.5~6A), 60A(5~60A)
2) To select the rated current.
Move to the slide switch to the rated current side in the rear side
User has to switch the IMC-III power OFF ON Note) Dont change the switch during the operation.
Set the detail current by moving from A setting group to [4.r-C] group in the front side.
- Setting by motor setting current
- After finishing motor starting, set the 110~115% of real load current in the load operation condition.
Information
Load under 0.5A
- Set the CT ratio 0.5 or 0.25 in the [6.ctr] Over 60A load
- MCT cable penetration increase from 2 times to 4 times - Usage of external CT
- Rated current setting range : 0.25~3A(2 times), 0.125~1.5A (4 times) - CT ratio (1~200) : Maximum 1000A

Operating time setting


1) It can be set 1~60s in the A group in [2.O-t]
In case of selecting inverse time in the [1.CHA]
- Setting operation time is 600% standard of rated current
In case of selecting the definite time
- The standard is over 105% of rated current.
- User has to set the operation delayed time 1~200s In the [3.d-t] considering motor operating time.

Special function key


Turn the heating capacity into clear and return by force
IMC-III inverse time protects overload fault by sensing the applied current on the motor, trace heating condition of motor. Motor has
heating capacity until completed cold status even if . motor stopped. IMC-III accumulates heating capacity values similar with motor. In
case of continuous re-start, or generating the trip, it can be tripped by acknowledgement Hot curve through the cumulated heating
capacity,
Information
If user want to re-start even if damaged to motor, push the STOP + RESET button. in conclusion,
cumulative heating capacity remove and can be reset.

Fault recording
IMC-III provides fault recording function even if power is OFF. If user push the ESC + button, user can check the Fault analysis and
fault current value. If user push the RESET button, fault analysis and fault recording will be deleted.
If there is no string data, it will be indicated non And then if user push the ESC + button, it will come back to normal mode.

Transfer to current indication mode.


If user push the RESET button for 2 seconds, it will come back to current indication mode.

3-phase current
circulation indication

Maximum phase
current indication

Note) If user push the RESET button for over 10s, IMC-III will come
back first manufacturing status. At this time, user has to know
that setting and storing value is deleted and comes back first
manufacturing status.

O-14
Total operation time
Total operation time check : day Hour minute

ex) If total operation time is 50hours 50 minutes : 2 days 2.50(2 hours 50 minutes)

Operation time Total operation time converse day Extra hour, minutes

ex) If operation time is 50 hours 50minutes : 50 hours 2days 2.50 (2 hours 50 minutes)

Operation mode handling method


Operation priority : Local > MCC > Auto, W/L > Remote

Local operation panel mode


The local operation mode is the highest priority mode, When the emergency situation generates,
it can control motor in the local site. Only in case of closing switch to the local site, motor can be controlled.
At that time, Local LED of IMC-III is lighting on, can not be controlled in another modes.

Motor control center mode


This mode is possible to operate in the IMC-III of MCC panel. If MCC LED is lighting up
by pushing the button, its possible to control motor in the IMC-III.
At this time, it can not be controlled by in AUTO.

Auto-PLC automatic operation mode.


This mode can provides automatic operation and remote control by PLC, DDC, DCS.
If auto / Rem LED lights up, motor is controlled by automatic operation.
Its possible to operate without converting mode in the IMC-III of MCC by operation priority.
And when the motor controls, operation mode convert to MCC.

W/L- Water level automatic operation mode O


This mode is for automatic operation and remote control by water changes.
If W/L LED lights up by operating button of IMC-III it can be controlled through the automatic operation.
IMC-III

Its possible to operate automatically through the PLC, DDC.


Its also possible to operate without converting mode in the IMC-III of MCC by operation priority.
And when the motor controls, operation mode convert to MCC.
Note) In case of using with Auto mode, the user has to compose of interlock circuit by using status output contact point.

Remote- communication operation mode


This mode is for remote monitoring control by Modbus, RS-485. If Auto/Remote LED lights up,
Its possible to communicate with Modbus/RS-485 and also check the 3phase value, fault value,
various data. Its also possible to operate without converting mode in the IMC-III of MCC
by operation priority. And when the motor controls, operation mode convert to MCC.
Note) 4~20mA output model can check only current Value through the Analog communication(4~20mA)

O-15
Intelligent Motor Controller
Wiring method

Direct start sequence

* INPUT (220VAC) * Comm.Port


1,3,5,6-2 (COM1) RS-485 4~20mA
7,8,10,11-9 (COM2) RX0 (-)
RX1 (+)
* OUTPUT TX0
12,16-15 (VCC1) TX1
17,18,19,21,22-20 (VCC2)

start
Y-

* INPUT (220VAC) * Comm. Port


1,3,5,6-2 (COM1) RS-485 4~20mA
7,8,10,11-9 (COM2) RX0 (-)
RX1 (+)
* OUTPUT TX0
12,13,14,16-15 (VCC1) TX1
17,18,19,21,22-20 (VCC2)

O-16
For/Rev start

* INPUT (220VAC) * Comm. Port


1,3,4,5,6-2 (COM1) RS-485 4~20mA
7,8,10,11-9 (COM2) RX0 (-)
RX1 (+)
* OUTPUT TX0
12,14,16-15 (VCC1) TX1
17,18,19,21,22-20 (VCC2)

Reactor start

O
IMC-III

* INPUT (220VAC) * Comm. Port


1,3,5,6-2 (COM1) RS-485 4~20mA
7,8,10,11-9 (COM2) RX0 (-)
RX1 (+)
* OUTPUT TX0
12,14,16-15 (VCC1) TX1
17,18,19,21,22-20 (VCC2)

O-17
Intelligent Motor Controller
Wiring method

Inverter start

Inverter start

ON(INV)

88M
* INPUT (220VAC) * Comm. Port 88I
0~1sec / 0.1sec
1,3,4,5,6-2 (COM1) RS-485 4~20mA
7,8,10,11-9 (COM2) RX0 (-) Bypass(Direct) start
* OUTPUT RX1 (+)
12,13,14,16-15 (VCC1) TX0 REV(BYS)

17,18,19,21,22-20 (VCC2) TX1 88B

FO/FC start(Forward)

* INPUT (220VAC) * Comm. Port


1,3,4,5,6-2 (COM1) RS-485 4~20mA
7,8,10,11-9 (COM2) RXD0 (-)
RXD1 (+)
* OUTPUT TXD0
12,14,16-15 (VCC1) TXD1
17,18,19,21,22-20 (VCC2)
* FO : Full open FC : Full close

O-18
S/V valve start(Direct)

* INPUT (220VAC) * Comm. Port


1,3,4,5,6-2 (COM1) RS-485 4~20mA
7,8,10,11-9 (COM2) RXD0 (-)
RXD1 (+)
* OUTPUT TXD0
12,13,14,16-15 (VCC1) TXD1
* S/V : Solenoid Valve 17,18,19,21,22-20 (VCC2)

If ON S/W applied, S/V(Solenoid Valve) becomes ON, OFF Delay Timer T1 becomesON.
If F/S (Flow Switch) applied within [T2-T3] time, ON Delay timer T3 becomes ON.
If T3 becomes ON, comparison timer T2 becomes OFF after setting time. And then Motor will operate because 88MX becomes ON.
At this time, if F/S does not apply within setting [T2-T3], ON will be canceled and thent2-Fwill be indicated.
Comparison timer T2 has to be set more than ON Delay Timer T3 , user has to consider time margin until F/S application.
If OFF s/w applied for motor stop, S/V and motor will be OFF delay same as T1 time
If F/S input is removed during motor operation, 88MX will be OFF, motor will be stopped. At this time S/V will be OFF.

Terminal number
O
Terminal Terminal
Explanation Explanation
No No
1 LOP selection input 14 Y-start/Reverse rotation/Reactor/Bypass contact point output
IMC-III

2 COM1(1, 3, 4, 5, 6) 15 VCC1(12, 13, 14, 16)


3 ON input 16 LOP condition output
4 Reverse rotation ON input(Bypass) 17 Auto condition output
5 Stop input 18 Water level condition output
6 Reset input 19 TRIP output(1a)
7 MC condition input 20 * VCC2(17, 18, 19, 21, 22)
8 F-S mode input 21 * ON delay timer output(t-d, F-S mode)
9 COM2(7, 8, 10, 11) 22 OFF delay timer output(t-d, F-S mode)
10 External trip1 input 23 Control power(AC110V or 220V)
11 External trip2 output 24 Control power(AC 110V or 220V)
12 ON output 25 ZCT input(k)
13 start/Inverter contact output 26 ZCT input()

* Normal mode
20-21 : Operation alarm(OrH) output
[ 20-22 : not in use

O-19
Intelligent Motor Controller
System configuration

O-20
O IMC-III

O-21
Intelligent Motor Controller
Accessories

ZCT(Zero-phase current transformer)

Inside diameter Zero phase current Weight


Contents
(mm) transformer ratio (kg)
LZT-025(I) 25 0.5
LZT-040(I) 40 200mA/0.1mA 0.8
LZT-080(I) 80 0.4

Dimension(mm) A B C D E F
LZT-025(I) 81 43 43.5 68 81 25
LZT-040(I) 101 43 53.5 88 101 40
LZT-080(I) 146 43 76 133 146 80
Note) This product is only for IMC, and user has to use this ZCT for protection ground fault.

SCT(3CT)
1CT 3CT(Combination of 1CT 3EA) Ratings
Model 3CT
SCT-100 100:5A
Current SCT-150 150:5A
transformer SCT-200 200:5A
ratio SCT-300 300:5A
SCT-400 400:5A
Class 1.0
Dimension Burden 5VA
Insulated voltage AC 600V
Insulated internal pressure 2kV
Insulation resistance 10M(DC 500V Megger)
65

65

Mounting Panel

64 82

In case of MCT combination


82 82 82
64
53

5

120

27.5
65
32.5

256

82 82
256
Note) 1. This product is only for EMPR, IMC, user must not use for other service
2. Pls order each 3EA with IMC-III, because this product is 1CT type.

O-22
Dimension & Ordering

Dimensions
IMC-III main unit

MCT

O
IMC-III

Ordering

IMC-III NO 2M AC 110V 50/60Hz

Item MCT cable length Operation and control Frequency


power
Normal 2M 2m AC 110V 50/60Hz
NO
(No communication) 4M 4m AC 220V
M485 Modbus/RS-485
A420 Analog 4~20mA

O-23
GIMAC-PQ

Power Quality Meter

Various measurement functions


High accuracy (0.2%)

15th Harmonics & THD, TDD, k-Factor

Event recording : Max. 256EA

Fault wave recording : Max. 60cycle

Analog Input : DC 4~20mA

MODBUS/RS-485
Dual communication
P

Contents Technical Specifications


External
MMI
P-4
P-6
P-7
Wirings P-8
Dimension P-10
Ordering P-11
Power Quality Meter
Technical Specifications

Rating

Model GIMAC-PQ

Wirings 1P2W, 1P3W, 3P3W, 3P4W


Frequency 50Hz / 60Hz
PT 10~230V
Voltage
GPT 2.2~230V
Current CT 0.05~6A
Input Control voltage AC/DC 110V
Power consumption Max. 30W
PT Max. 1.0VA
Burden
CT Max. 1.0VA
Input contact 10EA Digital Input : AC/DC 110V
AC230V 16A / DC30V 16A, Resistive load
3680VA, 480W
2EA for power
AC230V 8A / DC30V 8A, Inductive load(cos=0.4, L/R=7ms)
1840VA, 240W
Output contact
AC230V 12A / DC25V 12A, Resistive load
2760VA, 300W
8EA for alarm
AC230V 6A / DC25V 6A, Inductive load(cos=0.4, L/R=7ms)
1880VA, 150W
Insulation Resistance Over DC 500V 100
Insulation Voltage AC 2kV (1kV) / 1min
Impulse Voltage AC 5kV (3kV) / 1.2 50
2 In for 3 hours
Current circuit
Overload withstand 20 In for 2 seconds
Voltage circuit 1.15 Vn for 3 hours
Power Input 4kV
Fast Transient Disturbance
Other Input 2kV (Analog Input 1kV)
Air 8kV
ESD(Electrostatic Discharge)
Contact 6kV
Operation temperature -10C ~ 55C
Storage temperature -25C ~ 70C
Humidity Average 30 ~ 80%
Altitude 1000m and below
Non-impact place
Others
Non-air pollution place
Standard IEC 60255, IEC 61326, IEC 61000-4, KEMC 1110
Communication MODBUS/RS-485, I-NET
H
Dimension(W D) 190255116 (mm)
Weight 3.6 kg

P-4
Power quality functions

Power quality Effective voltage Fault type Continuous time Remarks

Instantaneous sag 0.5~30cycle


Sag 0.1~0.9pu Momentary sag 30cycle~3sec
Temporary sag 3sec~1min
Instantaneous swell 0.5~30cycle * Fault wave : Max. 60cycle
Swell 1.1~1.8pu Momentary swell 30cycle~3sec * Event : Max. 256EA
Temporary swell 3sec~1min * Blinking alarm LED
Momentary Interruption 0.5~3sec * Output Event DO
Interruption 0.1pu and below
Temporary Interruption 3sec~1min
Undervoltage 0.8~0.9pu over 1min
Overvoltage 1.1~1.2pu over 1min

Measurement functions

Model Measurement Display range Accuracy Remarks

GIMAC-PQ Current, I 0.000A ~ 999.99kA 0.2% Ia, Ib, Ic, In


Voltage, V 0.000V ~ 999.99kV 0.2% Va, Vb, Vc, Vab, Vbc, Vca
Active power, Watts 0.000W ~ 99999.9MW 0.5%
Reactive power, Var 0.000Var ~ 99999.9MVar 0.5% + : Forward
Apparent power, VA 0.000VA ~ 99999.9MVA 0.5% - : Reverse
Active energy, Wh 0.000Wh ~ 99999.9MWh 0.5%
Reactive energy, Varh 0.000Varh ~ 99999.9MVarh 0.5%
Frequency, F 45 ~ 70Hz 0.05Hz
Power factor, PF -1.000 ~ 1.000 0.5% cos(+ : Lag, - : Lead)
Phase 0.000~ 360.00 0.5
Normal current, I1 0.000A ~ 999.99kA
Reverse phase current, I2 0.000A ~ 999.99kA
Zero phase voltage, Vo 0.000V ~ 999.99kV 0.5% Vo, Vo_max
Normal voltage, V1 0.000V ~ 999.99kV
Reverse phase voltage, V2 0.000V ~ 999.99kV
Unbalanced factor 0.000 ~ 100.00%
Harmonics I 0.000A ~ 999.99kA 2nd ~15th
Harmonics V 0.000V ~ 999.99kV 2nd ~15th
THD(V, I), TDD(I)
k-Factor
P
Demand I 0.000A ~ 999.99kA Peak demand
GIMAC-PQ

Demand W 0.000W ~ 99999.9MW Peak demand


AI (Analog Input) 4.000 ~ 20.00mA 0.5%

P-5
Power Quality Meter
External

Status LED
Power
Comm 4 Text LCD
20
Alarm
Sys Err

DI state LED Function KEY


(Fault state) FUNC
RESET
ESC
ENTER

REMOTE/LOCAL CB ON/OFF
Transfer KEY Control KEY
State LED State LED

Front View

P-6
Initial menu
MMI

Setting menu

P-7
P
GIMAC-PQ
Power Quality Meter
Wirings

3P3W TX0 TX1 RX0 RX1

2PT application
OPEN DELTA ( )

P-8
3P4W
R S T

Va

Vb

Vc

Vo

Ia

Ib

Ic

1P3W 1P2W
R S R

P
GIMAC-PQ

P-9
Power Quality Meter
Dimension

Cutout size

P-10
Ordering

GIMAC-PQ NO RS M AC/DC 110V 60Hz AI

Model Protocol Frequency


NO Normal M Modbus 60Hz
50Hz

Communication Control voltage AI (Option)


RS RS-485/Dual AC/DC 110V AI 4~20mA(2P)

P
GIMAC-PQ

P-11
GIMAC-IV

Digital Integrated Metering &


Control Device

Various measurement functions Automatic power factor


High accuracy (0.2%) controller (option)

15th Harmonics & THD Demand controller (option)

Event recording : Max. 300EA

Analog Input : DC 4~20mA

MODBUS/RS-485, DNP3.0/RS-485, I-NET


Q1

Contents Technical Specifications


Functional Block Diagram
External
Q1-4
Q1-7
Q1-8
MMI Q1-9
Wirings Q1-10
Dimension Q1-12
Ordering Q1-13

GIMAC-IV /
APFC / DC
Digital Integrated Metering & Control Device
Technical Specifications

Rating

Model GIMAC-415

Wirings 1P2W, 1P3W, 3P3W, 3P4W

Frequency 50Hz / 60Hz

PT 10~230V
Voltage
GPT 2.2~230V

Current CT 0.05~6A

Input Control voltage AC/DC 110V

Power consumption Max. 30W

PT Max. 1.0VA
Burden
CT Max. 1.0VA

Input contact 10EA Digital Input : AC/DC 110V

AC230V 16A / DC30V 16A, Resistive load

3680VA, 480W
2EA for power
AC230V 8A / DC30V 8A, Inductive load(cos=0.4, L/R=7ms)

1840VA, 240W
Output contact
AC230V 12A / DC25V 12A, Resistive load
2760VA, 300W
8EA for alarm
AC230V 6A / DC25V 6A, Inductive load(cos=0.4, L/R=7ms)

1880VA, 150W

Insulation Resistance Over DC 500V 100

Insulation Voltage AC 2kV (1kV) / 1min

Impulse Voltage AC 5kV (3kV) / 1.250

2 In for 3 hours
Current circuit
Overload withstand 20 In for 2 seconds

Voltage circuit 1.15 Vn for 3 hours

Power Input 4kV


Fast Transient Disturbance
Other Input 2kV (Analog Input 1kV)

Air 8kV
ESD(Electrostatic Discharge)
Contact 6kV

Operation temperature -10C ~ 55C

Storage temperature -25C ~ 70C

Humidity Average 30 ~ 80%

Altitude 1000m and below

Non-impact place
Others
Non-air pollution place

Standard IEC 60255, IEC 61326, IEC61000-4, KEMC 1110

Communication MODBUS/RS-485, I-NET


H
Dimension(W D) 190255116 (mm)

Weight 3.6 kg

Q1-4
Measurement functions Q1
Model Measurement Display range Accuracy Remarks

GIMAC-IV
GIMAC-415 Current, I 0.000A ~ 999.99kA 0.2% Ia, Ib, Ic, In
Voltage, V 0.000V ~ 999.99kV 0.2% Va, Vb, Vc, Vab, Vbc, Vca
Active power, Watts 0.000W ~ 99999.9MW 0.5%
Reactive power, Var 0.000Var ~ 99999.9MVar 0.5% + : Forward
Apparent power, VA 0.000VA ~ 99999.9MVA 0.5% - : Reverse
Active energy, Wh 0.000Wh ~ 99999.9MWh 0.5%
Reactive energy, Varh 0.000Varh ~ 99999.9MVarh 0.5%
Frequency, F 45 ~ 70Hz 0.05Hz
Power factor, PF -1.000 ~ 1.000 0.5% cos (+ : Lag, - : Lead)
Phase 0.000~ 360.00 0.5
Normal current, I1 0.000A ~ 999.99kA
Reverse phase current, I2 0.000A ~ 999.99kA
Zero phase voltage, Vo 0.000V ~ 999.99kV 0.5% Vo, Vo_max
Normal voltage, V1 0.000V ~ 999.99kV
Reverse phase voltage, V2 0.000V ~ 999.99kV
Unbalanced factor 0.000 ~ 100.00%
Harmonics I 0.000A ~ 999.99kA 2nd ~63th
Harmonics V 0.000V ~ 999.99kV 2nd ~63th
THD(V, I)
TDD(I)
k-Factor
Demand I 0.000A ~ 999.99kA Peak demand
Demand W 0.000W ~ 99999.9MW Peak demand
AI (Analog Input) 4.000 ~ 20.00mA 0.5%

Communication

Type Item Specifications Remarks

Baud rate 250kbps


Distance Max. 1km
Low Capacitance LAN Interface cable
Cable spec
LIREV-AMESB 22AWG 2-Pair(7/0.254TA)
I-NET Insulation Pulse Transformer LS custom protocol
Impedance 10MHz, 120
Wiring 4-Wire Multi-drop
Termination 120(2EA)
Modulation Bipolar
Operation mode Differential
Baud rate 9600, 19200, 38400bps
Distance Max. 1.2km
MODBUS/RS-485
Cable spec Standard RS-485 Shielded Twist 2-Pair cable
Transmission Half-Duplex
Max. input/output -7V ~ +12V
Master RS-232, RS-485, RS-422, Ethernet
Media
Slave I-NET
GMPC-V Master DNP3.0, MODBUS, LonWorks, Glofa PLC
Protocol
(Protocol converter) Slave I-NET
Slave number Max. 20EA / 1 Module
Dual (Option) Redundancy

Q1-5
Digital Integrated Metering & Control Device
Technical Specifications

APFC (Automatic power factor controoler)

Model GIMAC-415 AP

BANK number 0 ~ 8EA


BANK setting
Alarm number 0 ~ 1EA
1BANK 1a DO_01a ~ DO_08a (Latch)
BANK control contact 1BANK 1b DO_01b ~ DO_08b (Latch)
1BANK 2a DO_01a ~ DO_08a (ON / OFF seperate, 500ms Pulse)
Capacitor setting None ~ 9,999MVA (Auto/Manual)
Alarm contact DO_01~08(1EA)
Capacitor closing delay time 3 ~ 300 sec / 1sec
Dead time 3 ~ 300 sec / 1sec
Max. value setting 0.90 ~ 1 ~ -0.90 (- : Lead)
Min. value setting 0.50 ~ 0.90
Alarm value setting 0.00 ~ 0.90
Reverse Current
Low Current
Under Voltage
Event recording (Alarm)
Over Switching
Over PF
Under PF
Auto control
Manual control
Power factor control sequence
Complex control
Cyclic contol

Demand Controller

Model GIMAC-415 DC

Target power Wt, Estimate power We(t),


Standard power Wt(t), Current power Wc(t)
Monitoring Load control state
Event
DC time and state display
Load number 0 ~ 8EA
Load setting
Alarm number 0 ~ 2EA
1LOAD 1a DO_01a ~ DO_08a (Latch)
Load control contact 1LOAD 1b DO_01b ~ DO_08b (Latch)
1LOAD 2a DO_01a ~ DO_08a (ON / OFF seperate, 500ms Pulse)
Alarm 1 Estimate power > Target power
Alarm contact
Alarm 2 Current power > Standard power
Demand time 5 ~ 60min / 5min
Start time 0 ~ Demand time / 1min
Period time 10 ~ 60sec / 1sec
Delay time 1 ~ (Period time-1)sec / 1sec
Target active power(Wt) 100W ~ 99,999MW
Alarm 1st, 2nd alarm
Auto control
Demand control sequence Manual control
Priority control

Q1-6
Functional Block Diagram

Q1

GIMAC-IV
50/51 50/51G

A V W Wh

Var Varh F PF

GIMAC-415NO DPR-1000

GIMAC-415AP GIMAC-415NO GIMAC-415DC

DC
Demand
Controller
APFC
Automatic Power
Factor Controller

Q1-7
Digital Integrated Metering & Control Device
External

Status LED
Power
Comm 4 Text LCD
20
Alarm
Sys Err

DI state LED Function KEY


(Fault state) FUNC
RESET
ESC
ENTER
DIRECTION

AUTO/MANUAL
Transfer KEY CB ON/OFF
State LED
Control KEY
State LED
REMOTE/LOCAL
Transfer KEY
State LED Front View

COM TX0 TX1 RX0 RX1

IR1 IR2 IS1 IS2 IT1 IT2

Q1-8
Initial menu MMI

Setting menu

Q1-9
GIMAC-IV
Q1
Digital Integrated Metering & Control Device
Wirings

3P3W

2PT application
OPEN DELTA ( )

Q1-10
3P4W Q1
R S T

GIMAC-IV
Va

Vb

Vc

Vo

GIMAC-IV

Ia

Ib

Ic

1P3W 1P2W
R S R

GIMAC-IV GIMAC-IV

Q1-11
Digital Integrated Metering & Control Device
Dimension

Cutout size

Q1-12
Ordering

Q1
GIMAC-415 NO RS M AC/DC 110V 60Hz AI

GIMAC-IV
Model Protocol Frequency
NO Normal M Modbus 60Hz
AP APFC I I-NET 50Hz
DC Demand Control D DNP3.0
PD APFC, D/C

Communication Control voltage AI (Option)


RS RS-485 AC/DC 110V AI 4~20mA(2P)
IN I-NET

Digital Integrated Metering & Control Device

Automatic Power Factor Controller

Demand Controller

Q1-13
GIMAC-II plus

Digital Integrated Metering &


Control Device

Various measurement functions


High accuracy (0.3%)

Event recording : Max. 256EA

MODBUS/RS-485, I-NET

Select before operation

Self-diagnosis
Q2

Contents Technical specifications


External
Wirings
Q2-4
Q2-6
Q2-7
Dimension& Ordering Q2-9
Digital Integrated Metering & Control Device
Technical specifications

Rating

Model GIMAC-115

Wirings 1P2W, 1P3W, 3P3W, 3P4W


Frequency 50Hz / 60Hz
PT 10~230V
Voltage
GPT 2.2~230V
Current CT 0.05~6A
Input Control voltage AC/DC 110V
Power consumption Max. 30W
PT Max. 1.0VA
Burden
CT Max. 1.0VA
Input contact 10EA Digital Input : AC/DC 110V
AC230V 16A / DC30V 16A, Resistive load
3680VA, 480W
2EA for power
AC230V 8A / DC30V 8A, Inductive load(cos=0.4, L/R=7ms)
1840VA, 240W
Output contact
AC230V 12A / DC25V 12A, Resistive load
2760VA, 300W
8EA for alarm
AC230V 6A / DC25V 6A, Inductive load(cos=0.4, L/R=7ms)
1880VA, 150W
Insulation Resistance Over DC 500V 100
Insulation Voltage AC 2kV (1kV) / 1min
Impulse Voltage AC 5kV (3kV) / 1.250
2 In for 3 hours
Current circuit
Overload withstand 20 In for 2 seconds
Voltage circuit 1.15 Vn for 3 hours
Power Input 4kV
Fast Transient Disturbance
Other Input 2kV (Analog Input 1kV)
Air 8kV
ESD(Electrostatic Discharge)
Contact 6kV
Operation temperature -10C ~ 55C
Storage temperature -25C ~ 70C
Humidity Average 30 ~ 80%
Altitude 1000m and below
Non-impact place
Others
Non-air pollution place
Standard IEC 60255, IEC 61326, IEC 61000-4, KEMC 1110
Communication MODBUS/RS-485, I-NET
Dimension(WHD) 190255116 (mm)
Weight 3.6 kg

Q2-4
Measurement functions
Model Measurement Display range Accuracy Remarks
GIMAC-115 Current, I 0.000A ~ 999.99kA 0.3% Ia, Ib, Ic, In
Voltage, V 0.000V ~ 999.99kV 0.3% Va, Vb, Vc, Vab, Vbc, Vca
Active power, Watts 0.000W ~ 99999.9MW 0.5%
Reactive power, Var 0.000Var ~ 99999.9MVar 0.5% + : Forward
Apparent power, VA 0.000VA ~ 99999.9MVA 0.5% - : Reverse
Active energy, Wh 0.000Wh ~ 99999.9MWh 0.5%
Reactive energy, Varh 0.000Varh ~ 99999.9MVarh 0.5% Q2
Frequency, F 45 ~ 70Hz 0.05Hz

GIMAC-II Plus
Power factor, PF -1.000 ~ 1.000 0.5% cos(+ : Lag, - : Lead)
Phase 0.000~ 360.00 0.5
Normal current, I1 0.000A ~ 999.99kA
Reverse phase current, I2 0.000A ~ 999.99kA
Zero phase voltage, Vo 0.000V ~ 999.99kV 0.5% Vo, Vo_max
Normal voltage, V1 0.000V ~ 999.99kV
Reverse phase voltage, V2 0.000V ~ 999.99kV
Unbalanced factor 0.000 ~ 100.00%
Harmonics I 0.000A ~ 999.99kA 2nd ~15th
Harmonics V 0.000V ~ 999.99kV 2nd~15th
THD (V, I)
TDD (I)
k-Factor
Demand I 0.000A ~ 999.99kA Peak demand
Demand W 0.000W ~ 99999.9MW Peak demand
AI (Analog Input) 4.000 ~ 20.00mA 0.5%

Communication
Type Item Specifications Remarks
Baud rate 250kbps
Distance Max. 1km
Cable spec Low Capacitance LAN Interface cable
LIREV-AMESB 22AWG 2-Pair(7/0.254TA)
I-NET Insulation Pulse Transformer LS custom protocol
Impedance 10MHz, 120
Wiring 4-Wire Multi-drop
Termination 120(2EA)
Modulation Bipolar
Operation mode Differential
Baud rate 9600, 19200, 38400bps
Distance Max. 1.2km
MODBUS/RS-485
Cable spec Standard RS-485 Shielded Twist 2-Pair cable
Transmission Half-Duplex
Max. input/output -7V ~ +12V

Fault indication
LED indicator
Digital
Troubleshooting after reset Reset after troubleshooting
input Normal Fault input
Troubleshooting Reset Reset Troubleshooting
Fault DI_1~8 Off Blink Blink Off On Off

Q2-5
Digital Integrated Metering & Control Device
External

Status LED
Power
Comm 204 Text LCD
Alarm
Sys Err

DI state LED Function KEY


(Fault state) FUNC
RESET
ESC
ENTER

REMOTE/LOCAL CB ON/OFF
Transfer KEY Control KEY
State LED State LED

Front View

Q2-6
Wirings

3P3W

Q2

GIMAC-II Plus
GIMAC-II Plus

2PT application
OPEN DELTA ()

Q2-7
Digital Integrated Metering & Control Device
Wirings

3P4W
R S T

Va

Vb

Vc

Vo

GIMAC-II Plus

Ia

Ib

Ic

1P3W 1P2W
R S R

GIMAC-II Plus GIMAC-II Plus

Q2-8
Dimension& Ordering

Dimension

Q2

GIMAC-II Plus
Cutout size

Ordering

GIMAC-115plus NO RS M AC/DC 110V 60Hz AI

Model Protocol Frequency


NO Normal M Modbus 60Hz
I I-NET 50Hz

Communication Control voltage AI (Option)


RS RS-485 AC/DC 110V AI 4~20mA(2P)
I I-NET

Q2-9
GIMAC-

Digital Power Meter

Various measurement functions


High accuracy (0.3%)

Compact size (14414485mm)


- DIN 96 & ANSI"4 cutout size

Wide voltage range


- AC 10 ~ 452V

MODBUS/RS-485

Control voltage AC/DC 88~264V

Protecting mis-wiring
R1

Contents Technical specifications


External
Wirings
R1-4
R1-6
R1-7
Dimension & Ordering R1-9
Digital Power Meter
Technical specifications

Rating

Model GIMAC-i

Wirings 1P2W, 1P3W, 3P3W, 3P4W


Frequency 50Hz / 60Hz
Voltage PT AC 10~452V
Current CT 0.05~6A
Input Control voltage AC/DC 88~264V (Free voltage)
Power consumption Max. 2W
PT Max. 0.5VA
Burden
CT Max. 0.5VA
Insulation Resistance Over DC 500V 100
Insulation Voltage AC 2kV (1kV) / 1min
Impulse Voltage AC 5kV (3kV) / 1.250
2 In for 3 hours
Current circuit
Overload withstand 20 In for 2 seconds
Voltage circuit 1.15 Vn for 3 hours
Fast Transient Disturbance Power Input 4kV
Air 8kV
ESD(Electrostatic Discharge)
Contact 6kV
Operation temperature -10C ~ 55C
Storage temperature -25C ~ 70C
Humidity Average 30 ~ 80%
Altitude 1000m and below
Non-impact place
Others
Non-air pollution place
Standard IEC 60255, IEC61000-4
Communication MODBUS/RS-485
H
Dimension(W D) 14414485 (mm)
Weight 0.52 kg

Self-diagnosis

Item LCD display

Mis-wiring Conn Chc (connection check)


Memory error ERROR 1
Power fail ERROR 2
Option error ERROE 3
Setting error ERROR 4
Calibration error ERROR 5

R1-4
Measurement functions

Parameters NO EX Accuracy(%) Remarks

Vavg 0.3% -
Voltage Vab, Vbc, Vca 0.3% -
Va, Vb, Vc 0.3% -
lavg 0.3% -
Current la, lb, lc 0.3% -
Load factor la, lb, lc - -
VabVbc, VabVca - 0.5 3P3W
Vabla, Vablb, Vablc - 0.5 3P3W
Phase
VaVb, VaVc - 0.5 3P4W
Vala, Vblb, Vclc - 0.5 3P4W
P 0.5% IEC 1036
Pa, Pb, Pc - 0.5% IEC 1036

Power
Q 0.5% IEC 1036 R1
Qa, Qb, Qc - 0.5% IEC 1036
S 0.5% IEC 1036

GIMAC-i
Sa, Sb, Sc - 0.5% IEC 1036
Wh 0.5% IEC 1036
Varh 0.5% IEC 1036
Energy rWh - 0.5% IEC 1036
rVarh - 0.5% IEC 1036
VAh 0.5% IEC 1036
Frequency F(Hz) 0.05Hz -
PF
+ : Lag
Power factor PFa, PFb, PFc -
- : Lead
DPFa, DPFb, DPFc -
THD(V) - - Va(ab), Vb(bc), Vc(ca)
THD
THD(I) - - Ia, Ib, Ic
1st ~ 15th Harmonics (V) - - Va(ab), Vb(bc), Vc(ca)
Harmonics
1st ~ 15th Harmonics (I) - - Ia, Ib, Ic
Demand W - -
Demand
Demand la, lb, lc, lavg - - -
max la, max lb, max Ic, max lavg
- - -
max Va(ab) THD, max Vb(bc) THD
max Vc(ca) THD
- - -
max la THD, max lb THD,
max lc THD - - -
MAX
max W - - -
max VAR - - -
max VA - - -
max Demand lavg, la, lb, lc - - -
max Demand W - - -

R1-5
Digital Power Meter
External

A PHASE Comm. state

PHASE OPTION
(EX TYPE)
B PHASE
UP KEY
OPTION
(EX TYPE)
DOWN KEY
C PHASE
ENTER KEY
Minus (-)

1000 unit

R1-6
Wirings

3P4W

LINE
LINE
R S T N
R S T N
Fuse, 2A
Fuse, 2A

2A, Slow Blow 2A, Slow Blow


Power Supply Power Supply
Power Supply Power Supply

CCT

R1

GIMAC-i
LOAD LOAD

Direct wiring PT application

3P3W

LINE
LINE
R S T
R S T
Fuse, 2A
Fuse, 2A

2A, Slow Blow 2A, Slow Blow


Power Supply Power Supply
Power Supply Power Supply

CCT CCT

LOAD LOAD

Direct wiring PT application

R1-7
Digital Power Meter
Wirings

3P3W (Open Delta) 1P 3W

LINE
R S T LINE
Fuse, 2A R S N

Fuse, 2A

2A, Slow Blow


Power Supply 2A, Slow Blow
Power Supply
Power Supply
Power Supply

CCT
CCT

LOAD LOAD

1P 2W

LINE
R N

Fuse, 2A 2A, Slow Blow


Power Supply

Power Supply

CCT

LOAD

R1-8
Dimension & Ordering

Dimension

144
23.5 61.5 89 144
85

R1

GIMAC-i
86

92

86 92

ANSI 4 Cutting Size DIN 96 Cutting Size

Ordering

NO M485 AC/DC 88~264V 60Hz

Digital Power Meter Model Communication Control voltage Frequency


NO Normal - Without Comm. AC/DC 88~264V 60Hz
EX Expansion M485 Modbus/RS-485 50Hz
M422 Modbus/RS-422

R1-9
GIMAC-DC

DC Meter

Measurement DC voltage, DC current


High accuracy (0.3%)

Compact size (14414485mm)


- DIN 96 & ANSI"4 cutout size

Wide voltage range


- AC 10~452V, DC 20~264V

Control voltage AC/DC 88~264V

MODBUS/RS-485, 422
R2

Contents Technical specifications


External
Wirings
R2-4
R2-5
R2-6
Dimension & Ordering R2-7
Digital Integrated Meter
Technical specifications

Rating

Model GIMAC-DC

Frequency 50Hz / 60Hz


Voltage PT AC 20~452V, DC 20~264V
Input Control voltage AC/DC 88~264V (Free voltage)
Power consumption Max. 10W
Burden PT Max. 0.5VA
Insulation Resistance Over DC 500V 100
Insulation Voltage AC 2kV (1kV) / 1min
Impulse Voltage AC 5kV (3kV) / 1.250
2 In for 3 hours
Current circuit
Overload withstand 20 In for 2 seconds
Voltage circuit 1.15 Vn for 3 hours
Power Input 4kV
Fast Transient Disturbance
DC Input 2kV
Air 8kV
ESD(Electrostatic Discharge)
Contact 6kV
Operation temperature -10C ~ 55C
Storage temperature -25C ~ 70C
Humidity Average 30 ~ 80%
Altitude 1000m and below
Non-impact place
Others
Non-air pollution place
Standard IEC 60255, IEC61000-4
Communication MODBUS/RS-485
H
Dimension(W D) 14414485 (mm)

Measurement functions

Parameters Measurement Accuracy(%)

AC voltage Vac 0.30%


AC voltage frequency Hz 0.05Hz
THD THD -
DC voltage DC voltage Vdc 0.30%
Output current Iout 0.50%
DC current
Battery current Ibat 0.50%
AC voltage MAX Vac -
THD MAX THD -
MAX DC voltage MAX Vdc -
Output current MAX Iout -
Battery current MAX Ibat -

R2-4
External

Comm.

AC voltage Max ACV


Max DCV
ACV
VAC
HZ
COMM Max DCA
M ACV
DC voltage THD
M DCV
M DCA UP KEY
DCV VDC DOWN KEY
DC current
ENTER KEY
IOUT
DCA
Minus(-) IBAT
VAC : AC voltage
Hz : Frequency
x 1000 unit THD : AC voltage THD
VDC : DC voltage
IOUT : Output current
IBAT : Battery current

R2

GIMAC-DC
Rectifier

R2-5
Digital Integrated Meter
Wirings

Rectifier

Shunt
Shunt

Fuse, 2A Fuse, 2A

2A, Slow blow


Power supply
Power supply

Rectifier

Shunt
Shunt

Fuse, 2A Fuse, 2A

2A, Slow blow


Power supply
Power supply

Rectifier

Shunt

Shunt

Fuse, 2A Fuse, 2A

2A, Slow blow


Power supply
Power supply

Rectifier

Shunt

Shunt

Fuse, 2A Fuse, 2A

2A, Slow blow


Power supply
Power supply

R2-6
Dimension & Ordering

Dimension

VAC
COMM
ACV HZ
M ACV
THD
M DCV
M DCA

DCV VDC

IOUT
DCA
IBAT

R2

Ordering GIMAC-DC

GIMAC-DC M485 AC/DC 88~264V 60Hz

Communication Control voltage Frequency


- Without Comm. AC/DC 88~264V 60Hz
M485 Modbus/RS-485 50Hz

R2-7
For your safety, please read user's manual thoroughly before operating.
Contact the nearest authorized service facility for examination, repair, or adjustment.
Please contact qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!
Safety Instructions Any maintenance and inspection shall be performed by the personnel having expertise concerned.

2009.1 LS Industrial Systems Co.,Ltd. All rights reserved.

www.lsis.biz

HEAD OFFICE Global Network


LS Industrial Systems (Middle East) FZE
Dubai, U.A.E.
LS Tower 1026-6, Hogye-dong, Dongan-gu, Address: LOB 19 JAFZA VIEW TOWER Room 205, Jebel Ali Freezone P.O. Box 114216, Dubai, United Arab Emirates
Anyang-si, Gyeonggi-do 431-848, Korea Tel: 971-4-886 5360 Fax: 971-4-886-5361 e-mail: hwyim@lsis.biz
Dalian LS Industrial Systems Co., Ltd.
Dalian, China
Tel. (82-2)2034-4870 Address: No.15, Liaohexi 3-Road, Economic and Technical Development zone, Dalian 116600, China
Tel: 86-411-8273-7777 Fax: 86-411-8730-7560 e-mail: lixk@lsis.com.cn
Fax. (82-2)2034-4713
LS Industrial Systems (Wuxi) Co., Ltd.
Wuxi, China
Address: 102-A , National High & New Tech Industrial Development Area, Wuxi, Jiangsu,214028, P.R.China
Tel: 86-510-8534-6666 Fax: 86-510-522-4078 e-mail: xuhg@lsis.com.cn
CHEONG-JU PLANT LS-VINA Industrial Systems Co., Ltd.
Hanoi, Vietnam
Address: Nguyen Khe - Dong Anh - Ha Noi - Viet Nam
Cheong-Ju Plant #1, Song Jung Dong, Hung Duk Ku, Tel: 84-4-882-0222 Fax: 84-4-882-0220 e-mail: srjo@lsisvina.com
Cheong Ju, 361-720, Korea LS-VINA Industrial Systems Co., Ltd.
Hochiminh , Vietnam
Address: 41 Nguyen Thi Minh Khai Str. Yoco Bldg 4th Floor, Hochiminh City, Vietnam
Tel: 84-8-3822-7941 Fax: 84-8-3822-7942 e-mail: sbpark@lsisvina.com
LS Industrial Systems Tokyo Office
Tokyo, Japan
Address: 16FL, Higashi-Kan, Akasaka Twin Tower 17-22, 2-chome, Akasaka, Minato-ku Tokyo 107-8470, Japan
Tel: 81-3-3582-9128 Fax: 81-3-3582-2667 e-mail: jschuna@lsis.biz
LS Industrial Systems Shanghai Office
Shanghai, China
Address: Room E-G, 12th Floor Huamin Empire Plaza, No.726, West Yan'an Road Shanghai 200050, P.R. China
Tel: 86-21-5237-9977 (609) Fax: 89-21-5237-7191 e-mail: jinhk@lsis.com.cn
LS Industrial Systems Beijing Office Beijing, China
Address: B-Tower 17FL.Beijing Global Trade Center B/D. No.36, BeiSanHuanDong-Lu, DongCheng-District,
Beijing 100013, P.R. China
Tel: 86-10-5825-6025,7 Fax: 86-10-5825-6026 e-mail: cuixiaorong@lsis.com.cn
LS Industrial Systems Guangzhou Office
Guangzhou, China
Address: Room 1403,14F,New Poly Tower,2 Zhongshan Liu Road,Guangzhou, P.R. China
Tel: 86-20-8326-6764 Fax: 86-20-8326-6287 e-mail: linsz@lsis.biz
LS Industrial Systems Chengdu Office
Chengdu, China
Address: 12Floor, Guodong Building, No52 Jindun Road Chengdu, 610041, P.R. China
Tel: 86-28-8612-9151 Fax: 86-28-8612-9236 e-mail: yangcf@lsis.com.cn
LS Industrial Systems Qingdao Office
Qingdao, China
Specifications in this catalog are subject to change without notice due to Address: 7B40,Haixin Guangchang Shenye Building B, No.9, Shandong Road Qingdao 26600, P.R. China
continuous product development and improvement. Tel: 86-532-8501-6568 Fax: 86-532-583-3793 e-mail: lirj@lsis.com.cn

2009. 01 Digital Protection & Measurement Device (E) 2009. 01/(01) 2009. 01 Printed in Korea STAFF