al ain hospital / switching station


SIMATIC income / 7SD610 V4.7/7SD610 12.09.17 11:24:45

al ain hospital / switching station income / 7SD610 V4.7

MLFB: 7SD61012BB990BJ0
Parameter-set version: V04.73.03
Device path: C:\Siemens\DIGSI4\D4PROJ\al_ain_h\P7DI\GV\SD\00000006
Author:
Creation date: 12.09.17 11:23:14
Last modified: 12.09.17 11:23:30
Operating mode: Offline
Comment:
Setting values in: Secondary value description

Page 1 of 8
7SD610 V4_7_prn
Device Configuration
al ain hospital / switching station
SIMATIC income / 7SD610 V4.7/7SD610 12.09.17 11:24:45

1 Device Configuration

No. Function Scope

0103 Setting Group Change Option Disabled


0112 Differential protection Enabled
0122 DTT Direct Transfer Trip Disabled
0124 Instantaneous HighSpeed/SOTF Overcurrent Disabled
0126 Backup overcurrent Disabled
0140 Trip Circuit Supervision Disabled
0142 Thermal Overload Protection Disabled
0144 Voltage transformers not connected

Page 2 of 8
7SD610 V4_7_prn
Power System Data 1
al ain hospital / switching station
SIMATIC income / 7SD610 V4.7/7SD610 12.09.17 11:24:45

2 Power System Data 1

2.1 Group Power System Data 1; Group Transformers

Group Power System Data 1; Group Transformers


No. Settings Value Group

0201 CT Starpoint towards Line All


0205 CT Rated Primary Current 400 A All
0206 CT Rated Secondary Current 1A All
0220 I4 current transformer is not connected All
0221 Matching ratio I4/Iph for CT's 1.000 All

2.2 Group Power System Data 1; Group Power System

Group Power System Data 1; Group Power System


No. Settings Value Group

0207 System Starpoint is Solid Earthed All


0208A 1-1/2 Circuit breaker arrangement NO All
0230 Rated Frequency 50 Hz All

2.3 Group Power System Data 1; Group Breaker

Group Power System Data 1; Group Breaker


No. Settings Value Group

0240A Minimum TRIP Command Duration 0.10 sec All


0241A Maximum Close Command Duration 1.00 sec All
0242 Dead Time for CB test-autoreclosure 0.10 sec All

Page 3 of 8
7SD610 V4_7_prn
Group Power System Data 1; Group CT Data
al ain hospital / switching station
SIMATIC income / 7SD610 V4.7/7SD610 12.09.17 11:24:45

2.4 Group Power System Data 1; Group CT Data

Group Power System Data 1; Group CT Data


No. Settings Value Group

0251 k_alf/k_alf nominal 1.00 All


0253 CT Error in % at k_alf/k_alf nominal 5.0 % All
0254 CT Error in % at k_alf nominal 15.0 % All

Page 4 of 8
7SD610 V4_7_prn
Settings groups
al ain hospital / switching station
SIMATIC income / 7SD610 V4.7/7SD610 12.09.17 11:24:45

3 Settings groups

3.1 Group Power System Data 2; Group Local Line End

Group Power System Data 2; Group Local Line End


No. Settings Value Group

1104 Measurement: Full Scale Current (100%) 400 A A

3.2 Group Power System Data 2; Group Line Status

Group Power System Data 2; Group Line Status


No. Settings Value Group

1130A Pole Open Current Threshold 0.10 A A


1132A Seal-in Time after ALL closures 0.10 sec A
1133A minimal time for line open before SOTF 0.25 sec A
1134 Recognition of Line Closures with Current flow or Manual close BI A
1135 RESET of Trip Command with Pole Open Current Threshold only A
1136 open pole detector with measurement (U/I,trip,pickup,CBaux) A
1150A Seal-in Time after MANUAL closures 0.30 sec A
1151 Manual CLOSE COMMAND generation NO A
1152 MANUAL Closure Impulse after CONTROL <none> All

3.3 Group Differential Protection; Group General

Group Differential Protection; Group General


No. Settings Value Group

1201 State of differential protection ON A

Page 5 of 8
7SD610 V4_7_prn
Group Differential Protection; Group Diff Protection
al ain hospital / switching station
SIMATIC income / 7SD610 V4.7/7SD610 12.09.17 11:24:45

3.4 Group Differential Protection; Group Diff Protection

Group Differential Protection; Group Diff Protection


No. Settings Value Group

1210 I-DIFF>: Pickup value 0.30 A A


1213 I-DIFF>: Value under switch on condition 0.30 A A
1217A I-DIFF>: Trip time delay 0.00 sec A
1219A Min. local current to release DIFF-Trip 0.00 A A
1233 I-DIFF>>: Pickup value 1.2 A A
1235 I-DIFF>>: Value under switch on cond. 1.2 A A

3.5 Group Differential Protection; Group Inrush

Group Differential Protection; Group Inrush


No. Settings Value Group

2301 Inrush Restraint OFF A


2302 2nd. harmonic in % of fundamental 15 % A
2303 Cross Block NO A
2305 Maximum inrush-peak value 15.0 A A
2310 Time for Crossblock with 2nd harmonic 0.00 sec A

3.6 Group Intertrip

Group Intertrip
No. Settings Value Group

1301 State of transmit. the intertrip command NO A


1302 Reaction if intertrip command is receiv. Trip A
1303 Delay for intertrip via binary input 0.02 sec A
1304 Prolongation for intertrip via bin.input 0.00 sec A

Page 6 of 8
7SD610 V4_7_prn
Group Measurement Supervision; Group Symmetry
al ain hospital / switching station
SIMATIC income / 7SD610 V4.7/7SD610 12.09.17 11:24:45

3.7 Group Measurement Supervision; Group Symmetry

Group Measurement Supervision; Group Symmetry


No. Settings Value Group

2901 Measurement Supervision ON A


2903A Balance Factor for Voltage Monitor 0.75 A
2904A Current Balance Monitor 0.50 A A
2905A Balance Factor for Current Monitor 0.50 A
2908A T Balance Factor for Voltage Monitor 5 sec A
2909A T Current Balance Monitor 5 sec A

3.8 Group Measurement Supervision; Group I/U-Monitoring

Group Measurement Supervision; Group I/U-Monitoring


No. Settings Value Group

2931 Fast broken current-wire supervision OFF A

3.9 Group Measurement Supervision; Group Load Angle

Group Measurement Supervision; Group Load Angle


No. Settings Value Group

2941 Limit setting PhiA 200 A


2942 Limit setting PhiB 340 A
2943 Minimum value I1> 0.05 A A
2944 Minimum value U1> 20 V A

3.10 Group Protection Interface (Port D+E); Group General

Group Protection Interface (Port D+E); Group General


No. Settings Value Group

4509 Time delay for data disturbance alarm 0.10 sec A


4510 Time del for transmission failure alarm 6.0 sec A
4512 Remote signal RESET DELAY for comm.fail 0.00 sec A

Page 7 of 8
7SD610 V4_7_prn

al ain hospital / switching station


SIMATIC income / 7SD610 V4.7/7SD610 12.09.17 11:24:45

3.11 Group Protection Interface (Port D+E); Group Interface 1

Group Protection Interface (Port D+E); Group Interface 1


No. Settings Value Group

4501 State of protection interface 1 ON A


4502 Connection 1 over Direct connection with fibre optic cable A
4505A Prot 1: Maximal permissible delay time 30.0 ms A
4506A Prot 1: Diff. in send and receive time 0.000 ms A
4513A Prot 1: Maximal permissible error rate 1.0 % A
4515A Prot.1: Block. due to unsym. delay time YES A

3.12 Group Differential Topology

Group Differential Topology


No. Settings Value Group

4701 Identification number of relay 1 1 A


4702 Identification number of relay 2 2 A
4710 Local relay is relay 1 A