You are on page 1of 62

Power Generation Bulletin #OOlO

CARBON DIOXIDE FIRE SUPPRESS/ON -

co2 Steam Turbine Generator

& Associated Equipment


Bearings

c c
0
mm The protection of the oil hazards associated with a steam
I turbine generator by the /oca/ application of Carbon Dioxide is

n
shown on the accompanying drawing.
= UJ Many such systems have been installed in large utility gener-
ating stations. In most of these installations, the bearings are often
protected with individual controls for each bearing, or for a group
of bearings located in close proximity to each other. In some
cases, the CO, protection is backed up by a manually operated
water system. The CO, is favored because there is no need to be
concerned about rapid cooling (quenching) of hot metal parts on
and around the turbine (see note on the following page). For the
unit shown, all bearings are protected as a single entity. CO, is
used to protect the other components of the lube oil system,
including oil storage, filtering, cooling, and pumping equipment.
The controls are arranged to protect the equipment in close prox-
imity to each other as an entity. In large plants, this equipment is
covered by water spray or water/foam sprinklers installed on the
levels below and underneath the turbine deck. For smaller gener-
ating units found in cogeneration plants or the smaller utility (muni-
cipals, etc.), the use of a single CO, system can be more cost
effective. Automatic controls direct discharges at the equipment
involved in the fire. Provisions are made for simultaneous dis-
charges where needed.

CARDOX One of the important provisions of the protection shown is to


minimize as much as possible any concerns over the use of a
limited supply extinguishing system. In a limited supply system, if
the agent is exhausted but the fire not controlled, the system has
not done its job. The fire protection system designers job is to
4801 Southwick Drive see that adequate agent is available to prevent this.
Third Floor
Matteson, IL 60443
Telephone: 708/748-l 503
Fax: 7081748-2847
0 1996 CHEMETRON FIRE SYSTEMS, all rights reserved. (g/96)
CWEmETROn co 2 Application Bull&in
Fire Systemi
Power Generation Bulletin #00 10 Page 2

oil pressure can be reduced and the fire con-


Cooling Effects of CO, Discharges trolled by eliminating the fuel source.

Since a discharge of liquid carbon dioxide The protection consists of the local appli-
creates fine particles of dry ice at approxi- cation of CO, to cover the equipment and asso-
mately -40gF, there is a misunderstanding ciated oil line connections. The equipment is
of the thermal effects of this discharge on enveloped in the CO, discharge at rates calcu-
massive equipment, such as discussed lated from the ratings of the nozzles used and
here. the requirements of NFPA Standard No. 12.
The bearing inside the exciter enclosure is pro-
The total heat absorbing capacity of low tected by flooding the exciter and then main-
pressure CO, is only about 125 BJUs per taining an inert concentration. Where bearings
pound. For the limited quantity of CO, and oil lines are beneath turbine lagging, a
used, the cooling capability of the discharge combination of local application and total flood-
is really quite small. When the CO, is ing is used.
discharged from a fire system nozzle, the
dry ice particles should sublime almost im- While the protection system shown is just
mediately as they are dispersed, avoiding covering the oil hazards, obviously the same
any buildup of S~CXM system can protect coal pulverizers, cable ar- -,
eas, switchgear - any other hazard that is suit-
In addition, the heat transfer between the able to CO, protection. It can also serve high
hot surfaces and the CO, gas is not good. capacity LPCO, hose lines (high flow rate with
There is no wetting and the only contact is 30-35 ft. projection). (All of these applications
gas to metal, with the gas heated very are covered by other CO, Application Bulletins.)
rapidly. There is little heat absorbed by
change of state, such as occurs when water The unit shown has a hydrogen cooled
turns to steam. generator and the CO, storage unit would be the
supply of CO, for purging the hydrogen (this is
The direct impingement on metal of CO, not shown).
from an orifice, which could result in local-
ized cooling, is avoided by the type of CO, In the case of the industrial steam turbine,
discharge nozzles used. where the generator is air cooled, it may be ap-
propriate to protect the generator as well. (Pro-
tection of rotating electrical equipment is anoth-
With a turbine that is hot (surfaces above er application covered by a bulletin.)
auto-ignition temperatures) and which is de-
signed to maintain oil pressure during a long When the carbon dioxide system is de-
run-down period after shutdown, the need for signed, the provision for personnel safety must
continuous application of fire extinguishant for be considered as strongly as the fire protection.
long periods of time should be obvious. The A safe system includes provision for:
system shown is often designed to give cycling
of continuous discharges for an hour or more on n Alarms that absolutely, positively indicate
the bearings and connecting oil lines. This that the system is about to discharge. .-
maintains the fire suppression condition until the
CHEmETROn
--
Fire Systems co2 Application Bulldin

Power Generation Bulletin #00 10 Page 3

n Analysis of the CO, gas flow to identify When plants go into an Extended Life Pro-
_.
where the CO, will be after a discharge. gram, it is reasonable to review the fire protec-
(Provision for odorizing the CO, may be tion. The LPCO, system really fits the bill here
appropriate.) as it is self-contained and eliminates concerns
for water supply, drainage, and the effects of
n Adequate instructions and training, includ- water discharges on older equipment.
ing warning and instructional signs.
Detailed design information on this applica-
NFPA Standard No. 12 provides good informa- tion is available from Chemetron.
tion in this regard.

Fire protection practices in power generation


facilities have changed over the years, resulting
in more protection being installed today than
years ago.

-
CHEmETROn
Fire Svstems co2 Application Bulktin

Power Generation Bulletin #00 10 Page 4

-
Power Generation Bulletin #0015

CARBON DIOXIDE FIRE SUPPRESSION -

co2
Supplement A:

Steam Turbine Generator Bearings

& Associated Equipment

Power Generation Bulletin #OOlO described a three hazard


system, where CO, is discharged on the bearings of a simple
turbine generator as one of the three hazards. The hazard also
included exciter protection. Two additional hazards were illustrat-
ed: Lube Oil Tank/Oil Coolers/Filters and Pumps combined as a
second hazard, and the Hydrogen Seal Oil Unit was the third.
.-
The purpose of this supplement is twofold: First, to expand
on the reasons for protecting the lube oil equipment as well as the
bearings with CO,; and secondly, to describe an alternate scope of
protection wherein the protection includes fixed fire protection for
the bearings and exciter, but uses Low Pressure CO, hand hose
lines for protection of other oil and electrical equipment in the
turbine area.

This scope of protection was recently used in the protection


of a 65 MW unit in the cogeneration power plant of a large paper
mill. Chemetron has a video (VHS) describing this installation,
including the test of the system, which was done while the unit was
operating at full load. (This video is available for viewing upon
request.)

As many of you are aware, there are differences of opinion


as to whether bearings should be protected with water or CO,, or

CAaJDoX both. The advantages of CO, were stated in Bulletin #OOlO.

The Recommended Practices of NFPA (No. 850), Fire


Protection for Electric Generating Plants, in paragraph 5-7.4.2
recommends as follows:
4801 Southwick Drive
Third Floor
._ Matteson, IL 60443
Telephone: 708/748-l 503
Fax: 7081748-2847
o 1996 CHEMETRON FIRE SYSTEMS, all rights reserved. (S/96)
CHEmErRon
Fire Systemi co2 Application Bulktin

Power Generation Bulletin #OO15 Page 2

Turbinegenerator bearings should be storage and processing equipment.


protected with a manually or aufomatically
operated closed-head sprinkler system It should be noted that on some installations
utilizing directional nozzles. Fire protec- in the past, CO, and water system costs have
tion systems for turbine generator bear- been a factor. CO, has been used where the
ings should be designed for a density of cost of the self-contained CO, system was less
0.25 gpm per sq. ft. (0.7 7 L/set-mJ over than the cost necessary to provide an upgraded
the protected area. water supply for fire protection purposes.

Accidental water discharge on bearing


points and hot turbine parts should be Other Important Design Considerations
considered. If necessary, these areas
may be protected by shields and encasing A number of serious power plant losses have
insulation with metal covers. resulted from three dimensional running oil fires
when the fire sprinkler coverage provided has
If a manually operated water system is been unable to suppress the running fire.
installed, consideration should be given to
a supplemental automatic gaseous fire CO, on the other hand has been used many,
extinguishing system. many times to suppress large, three dimensional
fires not unlike what might be experienced in a
John Corcoran, fellow of the Society of Fire lube oil fire.
Protection Engineers (SFPE), in his paper SFPE
Technology Report 85-6, Fire Protection For During World War II and the Korean War, the
Power Plants Past, Present and Future, rec- militarys basic aircraft crash fire rescue involved
ommends: using Low Pressure CO, to knock down running
Avgas fires to effect crew rescue. Very high
Considering the value of the machine, rate CO, discharges from overhead boom noz-
providing both water and carbon dioxide zles, ground sweeps and handlines quickly sup-
or dry chemical protection may be pru- pressed the burning gasoline, while water or
dent, and a gas system is highly desirable foam cooled metal surfaces. The CARDOX
inside the exciter housing. Much greater crash/fire trucks of that era put out hundreds of
ffexibility in handling different type and large fires, resulting in valuable suppression
size fires is thus attained. experience.

Therefore, it can be seen that even with basic Carbon dioxide local application fire protec-
recommendations for water protection on bear- tion in this context can be thought of as local-
ings, which are often motivated by insurance ized inerting, using the placement of the noz-
considerations, the value of CO, protection is zles and the resulting CO, discharge pattern to
also established. create a volume of reduced oxygen within the
discharged gas envelope. This lack of oxygen
To help you better understand the place for will totally suppress open burning within the en-
CO,, we would like to explain some other con- velope. If the combustible of flammable liquid is
siderations that not only relate to protecting contained and the ignition source removed, fire
bearings, but also to CO, protection for lube oil extinguishment will result.
I
CHEmETROn
Fire Systems co2 Application Bulldin

Power Generation Bulletin #0015 Page 3

This total containment and extinguishment of Oil fires of approximately 500 sq. ft. can be
three dimensional running fires is exactly what expected to be extinguished with each hose
happens in aluminum mill fires where hundreds line. Projection capabilities are 25-30 feet or
of gallons per minute of kerosene are sprayed more with discharge rates (with 1 hose) to 300
onto the mill to cascade down across the rolls Ibs./minute.
and drip into the pit below, while the metal strip
is fed through the mill. Many installations are arranged to allow
simultaneous use of two handlines in critical
For many of the larger mills protected with areas.
CO,, the volume of the assumed enclosure,
which contains the coolant manifold, rolls, and The projection capability allows a discharge
open oil pan, is larger than the assumed enclo- to reach cable trays located at ceiling levels.
sure required to cover the lube oil equipment Plus, the back-up of the entire CO, supply
discussed here. Thus, the experience gained allows the operator to discharge for many min-
in these two applications, plus many others, utes to fight a stubborn, smoldering electrical
can translate to the application discussed here. fire.

One of our customers kept records on over


1,100 fires extinguished by such protection on
just two mills over an 18 year period. Thus,
this is not unproven technology.

Therefore, for those concerned about how to


control three dimensional oil fires, the thou-
sands of successful extinguishments in these
other applications involving three dimensional
fires offer a starting point to a solution.
Carbon dioxide handlines are often placed
alongside water hose stations to give the oper-
ator a choice of agents based on the type of
fire experienced.

The drawing accompanying this supplement


illustrates the system at the paper mill power
plant mentioned earlier, which protects turbine
Low Pressure CO, Hand Hose Lines generator bearings and exciter, plus CO, hose-
reels at ground and turbine level (+ 140). This
Because of the larger size hose available is a less costly approach than full CO, protec-
with Low Pressure CO, and the projection abili- tion on the turbine lube oil system, but still
ty of the special discharge nozzles used, the offers the potential for fighting even a large fire.
LPCO, hand hose lines have been used for
years to afford clean, nonconducting, dry, por-
table fire protection for interior oil and electrical
hazards.
CHEmErRon
Fire Svstems co2 Application Bull&in

Power Generation Bulletin #00 75


CHElllETROn
Power Generation Bullefin #0020

Fire System;
CARBON DIOXIDE FIRE SUPPRESSION -

Gas Turbine Generators

co
2
The protection of the lubricating and hydraulic oil hazards
associated with the operation of a gas turbine is shown on the
accompanying drawing.

The protection of gas turbines with carbon dioxide has been


a common practice for many years. In many turbine configura-
tions, the turbine is in an enclosure; the enclosure is flooded to a
34% CO, concentration and the CO, held for the time period
required, until the exposed metal surfaces cool below the auto-
3 ignition temperature of the combustibles present. However, in the

n
m larger turbines used in the big cogeneration facilities, the turbine
is not enclosed, except by the building that contains it. Protection
by water spray creates a real problem for the turbine, and at the
same time, protection with CO, is more difficult because of the lack
of an enclosure immediately around the unit.

n This problem is dealt with by the local application of carbon


dioxide in accordance with the ratings of the nozzles used and
NFPA Standard No. 12. Provision is made to maintain CO, around
the unit for the run-down time of the unit (usually 10 to 20 min-
a
utes), plus a safety factor of 10 minutes. The application of CO,
at the rates required for local application coverage will usually
result in low level flooding of the turbine room in a reasonable time
period. Because of noise and other considerations, the turbine
room is usually well sealed and the CO, contained.

cAsu>oX
While its been done successfully many times in the past, the
concept of low level flooding with carbon dioxide may be new to
the reader and deserves a word of explanation.

It is applicable to hazards where the combustible is contained


4801 Southwick Drive in the lower portion of a room with a relatively high ceiling, and
Third Floor where a long holding time is needed. If done properly, this ends
Matteson, IL 60443 up using much less CO, than flooding the entire room.
Telephone: 708/748-l 503
Fax: 7081748-2847
0 1996 CHEMETRONFIRE SYSTEMS, all rights reserved. (g/96)
I

CHEmETROn
Fire System; CO2 Application Bulletin

Power Generation Bulletin #0020 Page 2

The process involves: Low Pressure CO, hose lines - with a high
CO, discharge rate and projection capabilities of
n First shutting down all ventilation which 30-35 feet - are unique fire fighters. They are
will exhaust CO, or mix it throughout the especially popular for use during maintenance
room. and repair. The unit can be removed from its
support, thereby charging the hose, and set
n Next, the CO, must be discharged in such alongside the area where any cutting or welding
a way that the fire is initially extinguished is to take place. In case of fire, the unit can be
to prevent the rapid updraft of the open discharged using the squeeze valve and play-
burning from moving the CO, up. pipe. If not used, it can be returned to its brack-
et at its reel with little or no CO, having been
n Testing has shown that when an area is used. (The accompanying drawing does not
flooded with CO,, the CO, will not rise show hose line coverage.)
much above the height of the discharge
nozzles, if the nozzles are aimed down. When the carbon dioxide system is designed,
The velocity of the CO, discharge will en- the provision for personnel safety must be con-
train any rising CO, and force it back to- sidered as strongly as the fire protection. A
ward the bottom of the area. Therefore, safe system includes provision for:
the nozzles (not necessarily all of them)
should be at the height at which you want n Alarms that absolutely, positively indicate
to maintain the CO, concentration (usually that the system is about to discharge.
a minimum of 2 feet above the highest
combustible). n Analysis of the CO, gas flow to identify
where the CO, will be after a discharge.
n Lastly, loss of CO, laterally out of the (Provision for odorizing the CO, may be
room must be minimized by closing all appropriate.)
dampers, doors, etc. If losses occur dur-
ing the required soak time, (the cooling n Adequate instructions and training, includ-
period), follow-up discharges can be ing warning and instructional signs.
made. The need for these and their du-
ration is determined when the system is NFPA Standard No. 12 provides good informa-
tested. tion in this regard.

Besides protection of the gas turbine lube- Detailed design information on this application
hydraulic oil system, other uses of the CO, sys- can be obtained from Chemetron.
tem would include protection of the fuel prepara-
tion equipment if oil is used as fuel, and to sup-
ply high capacity low pressure CO, hose lines.
Low Pressure CO, Protection
Gas Turbine Generator

BEARING 7

GEAR REDUCER
AND BEARING

kf-ti! 1 / RESERVOIR >c

EXHAUST BEARING

r MASTER-SELECTOR
VALVES
I

HYDRAULIC UNIT

- \ FUEL PREPARATION
CO2 STORAGE UNIT
SKID
Power Generation Bulletin #0025
CHEmETROn
Fire System6
CARBON DIOXIDE FIRE SUPPRESSION -

Compartmentized Gas Turbines

Power Generation Bulletin #0020 covered the larger type gas


turbines used in some of the newer high capacity cogeneration
plants. This is the type of unit which is housed in a building built
as a power station or as part of a combined cycle plant, wherein
the station holds gas turbines and a steam turbine, with the ex-
haust gasses from the gas turbines used as a heat source for
generating steam. However, many more gas turbines are built and
housed in enclosures, shipped to the job site and quickly placed in
service with little on-site construction. We choose to call these
compartmentized turbines packaged units.This application bulletin
covers these units.

The material contained herein is an update of the March,


1970 issue of Hot Spots, which was a technical publication of the
Cardox Division of Chemetron Corporation.

a
Well present a description of the recommended Chemetron
Fire Systems protection, along with a background of the develop-
ment work done to assure that this protection is properly designed
to meet the unusual demands of this equipment.

Several basic considerations of carbon dioxide fire protection


system design which are often overlooked, such as losses through
unclosable openings and adequate cooling periods, are empha-
sized. We call these to your specific attention as they would apply
to the design of protection of many other hazards.

CkSRDO!X Description of Hazard

A gas turbine unit essentially consists of an axial compressor


section and an expansion turbine section on a common shaft,
4801 Southwick Drive coupled to drive an electric generator or centrifugal compressor.
Third Floor A diesel starting engine, electric motor, or small separate turbine
Matteson, IL 60443 is utilized for starting.
Telephone: 708/748-l 503
Fax: 7081748-2847
Q 1996 CHEMETRON FIRE SYSTEMS, all rights reserved. W96)
CHEmErRon
Fire System: co2 Application Bulktin

Power Generafion Bulletin #0025 Page 2

Air is drawn into the compressor and com- system itself. Shutting off the fuel to the gas
pressed before entering the combustion cham- turbine by closing a valve in the fuel line is a
ber, where it is mixed with fuel and burned. The part of system design and should limit the fire
expanding burned gasses drive the turbine, producing material to the residue in the bottom
which in turn powers the equipment being op- of the unit. This residue may not be in contact
erated. with the hot turbine. However, contact could
exist through failure of the fuel shutoff valve or
The areas of protection considered for any other abnormal occurrence. The pressure in the
gas turbine power facility are the Turbine Com- bearing lubrication system is specifically de-
partment, the Accessories Areas, the Electrical signed to be maintained while the shaft is rotat-
Control and Switchgear Areas, the Fuel Pump ing so that a loss in the integrity of the lube oil
Area, and the Generator. Protection of the system could force oil under pressure onto met-
Accessories Areas, Control Room, and Pump al parts close by. If these parts are hot, and if
House present no unique problems of protec- this rotation is for an extended period, momen-
tion. Protection of the generator, usually of the tary fire extinguishment is of very little value.
straight-through air cooled type, requires the
same protection techniques developed by
Chemetron for the protection of large rotating Cool Down Time
equipment in steel mills or similar facilities, and
will not be discussed here. The protection of The critical question in gas turbine protection
the Turbine Compartment is of primary concern is how long does it take for exposed hot surfac-
in this presentation. es to cool below the ignition temperature of the
fuel involved. To answer this question, it was
The fire problem in the turbine compartment necessary to run a series of tests in which sur-
is represented by failure of the fuel (natural gas, face temperatures at suspected locations were
No. 2 fuel oil, or jet fuel) system, or by leakage recorded during operation and shutdown. These
of lubrication oils used on the shaft bearings. tests were conducted on actual installations on
The problem is that when the gas turbine is several different makes of turbines, one type of
operating, it gets very hot, and when it is shut which is illustrated on the drawing accompany-
down, it cools rather slowly. Outer surface tem- ing this bulletin.
peratures of the combustion chamber and tur-
bine expander reach 850F - 9OOF, which is Recordings were made of surface tempera-
well above the approximate 494F auto-ignition tures at three locations. Item A represents the
temperature of No. 2 fuel oil, or the approximate external surface over the combustors. In indus-
700F auto-ignition temperature of bearing lubri- trial type turbines, the combustion chamber is
cating oil. Therefore, if this fuel comes in con- separated from the exposed surface metal, al-
tact with these hot surfaces in an air atmos- lowing access to incoming cool air. Therefore,
phere, a fire can occur. To put this fire out mo- the temperature does not get as high as might
mentarily means nothing if, when the agent is be expected. The temperature may be higher
dissipated, contact between the fuel and the downstream of the combustion chamber just be-
ignition source still exists. Since these units are fore entering the expansion section of the tur-
often unattended and not accessible to follow-up bine. In aircraft type turbines, the surface tem-
fire fighting, there is no way to effect total extin- peratures get somewhat higher.
guishment except through the fire protection
CHEmETROn
Fire Systems co 2 Application Bulktin

Power Generation 5detin #0025 Page 3

Item B represents temperatures in the ex- discharge of CO, for fire protection will be of
haust section not visible on the drawing. These some help in reducing surface temperatures.
surfaces are largely insulated; however, there
are some thin, exposed sections in the exhaust Figure 1 represents typical temperature
bearing tunnel, and also some heavy support curves during a test operating cycle for a tur-
sections that have direct metallic contact with bine system with a diesel starting engine. It will
the inside of the exhaust passageway. Heavy be noted that the diesel exhaust manifold (C)
support sections may not get as hot as thinner reaches a temperature over 800F during the
sections, but cooling will be slower because of starting cycle. The cooling time is based on
the sheer mass of metal. cooling to 49OF, the auto-ignition temperature
of diesel fuel.
Item C represents the exhaust manifold of a
diesel starting engine for those systems provid- Combustor surface temperatures (A) may not
ed with this method of starting. The diesel get as hot as the starting engine exhaust mani-
engine runs only during the starting cycle. fold, however, cool down time may be longer
However, the exhaust manifold does get hot depending on the type of turbine. Highest sur-
enough to ignite fuel oil before the diesel en- face temperatures were found in the exhaust
gine is shut down after starting. section (B). Heavy metal sections required the
longest cooling time. Where the only fuel ex-
The actual temperatures attained and the posure is turbine lubricating oil, the cooling
cool-down time depend upon operating con- time can be based on its auto-ignition tempera-
ditions. The greater the load or output, the ture of 700F. Its necessary to add a safety
higher the gas temperature must be to drive factor to all of these figures to compensate for
the load. Therefore, maximum surface tem- the possible effect of operation at unduly high
peratures are developed when operating at loads or high ambient temperatures.
maximum load with maximum ambient air tem-
perature.
Air Leakage
Cooling time will be influenced somewhat by
the ambient temperature and also by the shut- In any turbine installation, there must be a
down procedure. Normal shutdown procedure substantial flow of cooling air around the out-
is to run the turbine under no load conditions side of the turbine to maintain reasonable ambi-
for about five minutes before finally shutting off ent temperatures within the turbine compart-
the fuel. The internal parts of the exhaust sec- ment. This may be accomplished by aspirating
tion cool down rapidly under these conditions air from the turbine enclosure into the exhaust
because of the cooler gas flowing through the duct. Alternately, fans or special eductors may
system. Emergency shutdown for fire extin- be used. The cooling air often enters through
guishing requires an immediate fuel cut off after openings on the side of the enclosure. The air
load is removed so that the turbine slows down inlets may be designed to bring the air in near
immediately and the air flow through the sys- the bottom of the turbine enclosure so that it
tem falls off very rapidly. Under emergency must pass over the turbine before being ex-
shutdown conditions, there is no time for inter- hausted to the outside. It is also necessary to
nal cooling and the exposed surfaces will not cool the turbine lubricating oil by drawing air
cool off as rapidly. On the other hand, the through a fin tube heat exchanger.
CHEmErRon
Fire Systems co 2 Application Bull&in

Power Generation Bulletin #0025 Page 4

When the turbine is shut down, the flow rate detectors below the turbine in critical areas
of the secondary cooling air drops off rapidly; where such fires might occur.
however, air leakage remains much too high to
permit practical total flooding without prohibitive The important limitation is to make sure that
loss of CO,. The obvious leakage openings the temperature setting is high enough to avoid
must be sealed or provided with dampers that false actuation by radiant heat from the turbine
can be closed when the CO, system is actuat- itself. This point was actually tested by install-
ed. In some systems, there is an annular gap ing dummy thermostats with internal thermo-
around the turbine air intake bell. In others, couples for recording the temperature during a
there may be bottom openings through which test cycle. It was found that such temperatures
pipes and conduit are brought into the enclo- did not exceed 200F and that therefore, a tem-
sure. Doors and panels must close tightly and perature setting of about 325F should be satis-
have soft seals. Even so, the leakage rate will factory.
still be sufficient to dissipate any atmosphere of
CO, in a couple of minutes or so, unless an Because of their inherent simplicity and reli-
extended discharge is used to compensate for ability, heat actuated detectors are considered
losses. The extended discharge rate should be best for automatic discharge of the CO, system.
no higher than necessary to maintain a mini- Flame or other special detectors may be used
mum of 30 to 35 percent CO, in the protected in critical units.
space for the cooling off period. Figure 2 rep-
resents typical CO, concentration curves re-
corded during the temperature cool down test Carbon Dioxide System
illustrated in Figure 1. With this technique, it is
possible to maintain an extinguishing concen- The piping and nozzle arrangement of a CO,
tration as long as necessary to permit proper fire protection system for this application is
cool down without risking reignition. CO, loss illustrated on the drawing. When a fire is de-
rates were established by separate discharge tected in any one of the protected compart-
tests. ments, the first action is to automatically shut
down the turbine by shutting off the fuel supply
and disconnecting the generator from the line.
Fire Detection An alarm is also sounded to warn personnel of
the impending discharge. After a brief delay to
The high secondary air flow rate required for allow time for evacuation in the event someone
compartment cooling also makes it difficult to happens to be in one of the protected compart-
detect small fires with heat detectors located ments, the discharge is started by the opening
near the ceiling. It takes a substantially sized of both main and extended discharge valves
fire burning near the floor level to raise the (not shown). The turbine compartment is not
temperature of the total air flow sufficiently to normally occupied during operation, so delay of
actuate the heat detectors. Heat detectors are the discharge is not provided if provisions are
obviously needed over the turbine sections to made to lock out the discharge when the tur-
assure detection of a fire that may originate on bine compartment is occupied.
the side or top of the turbine due to a broken
fuel line. On the other hand, to detect a small When opened, the valves at the central low
fire near the floor level, it is desirable to install pressure supply tank (not shown) permit the
CHEmErRon
Fire Systems co 2 Application Bulletin

Power Generation Bulletin #0025 Page 5

flow of carbon dioxide through the supply After a fire, the turbine, itself, must obviously
header into the hazard discharge piping. The be checked to correct fuel leakage or whatever
flow through the main discharge line provides caused the fire in the first place. Before the
rapid total flooding for fast extinguishment. turbine can be operated, any dampers or other
Pressure in this line also trips automatic damp- shutdowns tripped by the CO, system must be
er closers to shut off major ventilation openings reset to allow proper flow of cooling air or fuel,
at the beginning of the discharge. The peak as the case may be.
design concentration is attained in less than
one minute to extinguish the fire. Instances have occurred where the fire start-
ed with an explosion in the compartments and
The main discharge valve is then closed by the doors were blown open. If this is to be a
means of the timing system. The extended design basis, then it should be considered at
discharge valve remains open as long as the the time of design and CO, quantities and noz-
concentration is to be maintained for protection zle placement designed to ensure flooding,
against reignition. A simple orifice nozzle is even with the doors open.
used in each compartment on extended dis-
charge to provide ample velocity for stirring the Some have used foam to supplement CO,
atmosphere. This action is designed to fore- protection by covering any fuel or lubricant in
stall stratification because of leakage. At the the bottom of the unit. High expansion foam is
end of the cooling period, the extended dis- the usual choice for this.
charge valve is also closed, ending the dis-
charge sequence. The CO, will quickly flood the unit to the
ceiling and from wall to wall. Foam will not do
The alarm circuit for the affected hazard this, so the foam is considered a supplement.
must be manually reset to be certain that oper-
ating personnel are aware of the discharge. The 1990 edition of NFPA No. 850 Recom-
The fire detection circuit is also locked out until mended Practices: Fire Protection for Fossil
manually reset to avoid a possible second dis- Fueled Steam Electric Generating Plants (to
charge in the event of a shorted detector or be renamed), will include combustion turbines
circuit. This does not prevent a second dis- and is recommended as a reference source.
charge by manual means if this should be
needed.

Of course, none of the lock out features


would interfere with simultaneous or later auto-
matic fire protection of another hazard protect-
ed by the same low pressure storage unit.
CHEmETROn
Fire Systems co2 Application Bull&in

Power Generation Bulletin #0025 Page 6

1200

1100

1000

900

5 800

; 700

$ 600

2 500

g 400

300

200

100
0

(STARTING) MINUTES

Represents typical temperature curves during a test operating cycle


for a turbine system with a diesel starting engine.

Figure 1

0 5 10 15 20
TIME

Represents typical CO, concentration curves recorded during the temperature


cool down test illustrated in Figure 1.

Figure 2
TOTAL FLOOD NOZZLE
DIRECTED
EQUIPMENT
AT PROTECTED

r
4

6
1
I- EXTENDED
\ NOZZLE
DISCHARGE

rlll I

FROM CO2 STORAGE UNIT

Compartmentized Gas Turbine


Power Generation Bulletin #0030
CHEmETROn
Fire System;
CARBON DIOXIDE FIRE SUPPRESSION -

Hydroelectric Generators
co
2
One of the more traditional applications of carbon dioxide as
a fire extinguishant is in the protection of air cooled rotating electric
machinery. This bulletin covers the protection of hydraulic turbine
driven enclosed electric generators. Other bulletins will cover other
electric motor/generator configurations.

The protection of hydroelectric generators has been covered


by Standard No. 12 since its very inception (now an NFPA Stan-
dard.) It was recognized that if an adequate amount of CO1 is in-
troduced into the generator housing and held long enough, the fire
would be completely extinguished, and the damage limited to the
initial fire damage and whatever electrical problems initiated the
fire. It was also recognized that CO*, being an inert gas, is a non-
conductor and could be introduced in the machine even if the power
is not, or cannot be, shut off. In addition, CO2 is three dimension-
al, making it capable of reaching all internal parts of the machine
that the fire supporting air can reach.

Over the years, many improvements in electrical insulating


materials have been made, resulting in reduced combustibility.
These have caused some to believe that the need for fire protection
has been eliminated. Not so!

The introduction of mica epoxy insulating materials has re-


duced the effects of aging, hopefully reducing the incidence of
failure. Also, insulation materials have been tested to show they are

CAaDoX self-extinguishing. But these tests do not evaluate the materials in


the quantities and manner used in these machines, nor under the
high energy conditions of an electrical fault. In addition, the
materials making up the end turns are combustible and provide
4801 Southwick Drive ample fuel for a disastrous fire. Numerous fires have demonstrated
Third Floor the need for protection of large value and key generator units.
Matteson, IL 60443
Telephone: 708/748-l 503
Fax: 7081748-2847
@ 1996 CHEMETRON FIRE SYSTEMS, all rights reserved. (91961
CHErnETROII
Fire System: co2 Application Bull&in

Power Generafion Bulletin #0030

Generally, the availability of the parts needed rated from the turbine below by what is usually a
for repairs after a fire are limited. Rewinding water and air tight bulkhead. Access to the ma-
requires a lengthy time period and ordering a new chine is by doors in the housing. These doors
rotor or starter coils could represent a very long should be arranged to minimize the possibility of
lead time. being blown open.

The National Fire Protection Association Above the generator housing is a small hou-
(NFPA) has issued a Recommended Practices, sing containing the collector rings, field exciter,
Fire Protection for Hydroelectric Generating and generator sensing elements. It is usually
Plants, (NFPA #851) and in paragraph 5-3.1, cooled by the same air as the generator and is in-
protection for the generator windings is recom- cluded in the generator air volume when calculat-
mended. ing CO, requirements.

Machine Cons true tion Oil filled gear units may connect the turbine to
the generator and require protection.
As you can see from the drawing accompa-
nying this bulletin, the dammed up water flows In some installations, the machine can be used
under gravity through a turbine of some type, to as a pump as well as a generator. In this case, the
turn a shaft to which the rotor of an electric gen- electric machine functions as a motor with the tur-
erator is attached. In contrast to the steam tur- bine working as a pump, pumping water uphill
bine, the speed of rotation is much less (usually into the power plant reservoir during the night,
under 360 rpm). To cool the unit, water is some- when the extra power generating capacity is avail-
times circulated in the windings; also, the recircu- able. During peak demand hours, water flows
lated cooling air is passed over cooling coils be- back down through the machine, now functioning
fore being circulated through the windings. In as a generator, to generate the peak electric power
some units, ducted air is used. needed. This is called pumped storage.

Water for driving the turbine is stored in a In recent years, many hydroelectric or pumped
dammed up reservoir, with the water flowing from storage plants have been remotely operated, and
the reservoir down through the turbine to the river therefore, most of the time they are unattended.
or stream below.
Some units are run of the river, or even tide
The turbine generator can be mounted in the operated. There are also wind driven or com-
vertical as shown, horizontally, or as a bulb type pressed air driven electric generators, all of which
with water flowing through a bulb in which a gen- are similar in many ways.
erator is housed (access is through a strut to the
inside of the bulb). The protection requirements for the enclosed
electric generator portion of the machine are
In the more commonly used vertical unit, one identical in all cases.
or more units are placed, usually in line, in a
power house with at least part of the unit above
the supporting concrete. The generator is sepa-
CHEmETROn
Fire Systemi co 2 Application Bulletin

Power Generation Bulletin #0030

CO, Application A table to determine the amount of CO? to be


added (Table A-2-5.3 of Standard No. 12) has
The established design for generator protection been used for years and has proven to give good,
is per Table 2-4.2.1 and Paragraph 2-5.2.3 of even conservative, results.
NFPA Standard No. 12. Referring to these you
will find that the design concentration for the gen- The initial discharge is calculated at 1 lb. for
erator CO, flooding is 50% by volume. Of this each 12 cubic feet of generator volume (50%) and
total, 30% is to be achieved in the first 2 minutes, the added, or make-up COz, is estimated from the
with 50% achieved in 7 minutes, and 30% held table. For example, if the internal volume of the
until the unit shuts down (but not less than 20 machine is 4,000 cubic feet and the shutdown time
minutes). is 20 minutes, the added CO, needed is estimated
to be 450 lbs.
As the unit rotates, it is designed to move its
own cooling air (which may be aided by fans). It is normal practice to pipe both quantities of
This air movement creates zones of increased and CO? into the machine independently. One set of
decreased pressure, which could cause loss of air/ discharge nozzles floods the machine to help
CO> after a discharge, or the introduction of fresh achieve the initial design concentration (50 %),
air. When the CO? is discharged and mixed with while another set is used to add make-up CO: to
the air, the resulting mixture is heavier than air, hold the CO, level above 30%. We call these CO1
so loss can also occur due to gravity flow out of discharges the Initial Discharge and the Extended
low level leak points. Discharge. The initial discharge lasts for 2 min-
utes or more. The extended discharge continues
Some units require a prolonged run down after throughout the complete holding period.
shutdown occurs. Others have braking systems
which substantially shorten the run down period. When a 50% CO: gas concentration is added
to an enclosed volume, an internal pressure will
If the CO? is discharged in the quantities re- be created. While the machine enclosure is de-
quired to reach 50% and the cooling system is en- signed to withstand some internal pressure, the
closed with air recirculating, it stands that it will protection must be designed so that the pressure
hold a 30% concentration for 20 minutes unless level does not exceed design levels. This can mean
there are some leak points. Experience has shown the need to install pressure vents, which can be
that housings are not tight and some CO? loss is to quite simple. The formula for calculating the
be expected. But in recent years, testing has need for venting and how much vent area is re-
shown losses on newer machines to be less than quired is found in paragraph 2-6.2 of Standard
previously expected. In any case, the fire protec- No. 12.
tion system designer must anticipate there will be
some loss and design for same. The big question
S ys tern Arrangement
is how much? We must know how much CO? has
to be added after the initial discharge to meet the Referring to the arrangement diagram, you
design criteria of holding 30 % until shutdown. will note the CO? storage unit has two (2) control
For this we have been given a guide. valves piped to two separate discharge lines and
two separate sets of nozzles.
CHEmETROn
Fire Svstemg
co2 Application Bulletin

Power Generation Bulletin #IO030

One line is the Initial Discharge line and the doors closed.
other the Extended Discharge line. The descrip-
tion of operation is as follows: Many machines are also arranged so that the
CO1 is tripped automatically by electric faults
The unit is provided with an automatic detec- (differential relays, etc.)
tion system, usually consisting of an optical type
smoke detection system, used in conjunction with At the start of the discharge, both valves open.
a rate compensated heat actuated system. System The total CO1 flow through the initial and extend-
actuation is by the detection system arranged as ed discharge lines constitutes the initial discharge.
the operator prefers. For example, if the initial CO2 required is 1,000
lbs/minute and the extended discharge is 100 lbs/
This could be - minute, then the larger valve flows 900 lbsiminute
and the smaller valve 100 lbs/minute to give the
n CO, discharge and alarm upon either smoke or 1,000 lbs/minute total rate. After the initial dis-
heat detection. charge is over, the controls close the larger valve,
with the smaller valve continuing to discharge for
or
the full holding period.
. Alarm only on smoke detection, and CO? dis-
charge on heat detection. With the low pressure system, some installa-
tions have been made with one valve, one dis-
or
charge line, and one set of nozzles. On discharge,
n Discharge when both detectors operate togeth- the valve opens to give the required initial dis-
er. Alarm is given when either operates. charge to get 30% CO2 in 2 minutes with the 50%
design achieved within 7 minutes. Sometime after
The ability to abort the discharge, if neces- the initial discharge, if the CO1 concentration in
sary, is also a design option. A manual release is the machine drops near the 30 % level, the valve
also available (usually in the control room) to is opened again for added COz. For long deceler-
initiate the CO2 discharge. A second release can ation periods, it can be opened again later on. A
be by the machine. full discharge test of the machine sets the length
and frequency of the discharges. Care in design
Immediately on release by either automatic or must be exercised so that too frequent discharges
manual operation, audible alarms sound in the ma- are not made. Frequent discharges of short dura-
chine, under the machine, and in the power house tion can cause freezing problems due to dry ice
at the machine. Strobe or similar warning lights buildup in the piping.
are also used. Usually, the machine CO, dis-
charge starts immediately, but it must be delayed There may be a risk if CO, vapor is allowed to
to allow for personnel evacuation if there is any flow from the machine to areas where it is not ex-
possibility that anyone can be in the machine. pected. Therefore, proper sealing of the machine
Commonly, when the doors are opened, interlocks is not only beneficial for retaining the CO? for
will switch the automatic mode to alarm only and good fire protection, but it also makes for a safer
lock out the machine so it cannot be started until installation as well. The system discharge test
the CO2 system is in automatic operation and the will usually identify housing leaks. Be sure to
CHEmETROn
Fire System; CO2 Application Bulletin

Power Generation Bulletin #0030 Page 5

have adequate breathing apparatus available in running, with the air cooling the fire in the same
the vicinity of the machine and in the control way a burning match is cooled by blowing on it.
room. If this is ever to be done, the CO: system must be
designed accordingly.
It has become a common practice to odorize
the CO, with oil of wintergreen during the dis- High Pressure CO, S ys tern Arrangement
charge. Oil of wintergreen has a unique odor, can
be smelled at very low CO, concentrations, and it The accompanying diagram shows the arrange-
doesnt hurt anything. Odorized CO1 is detectable ment of a high pressure CO1 system for generator
if it leaks from the machine and settles in low protection.
spots. All such potential areas should be equip-
ped with alarms and be well ventilated. The calculated amount of CO? for the initial
discharge is stored in a bank of cylinders, man-
NFPA Standard No. 12 should be consulted ifolded together and piped, in this case, to the
for recommendations on the safe use of CO? extin- extended discharge line.
guishing systems.
The pilot cylinders, which are released to
On occasion, a generator fire has involved an initiate the full discharge, are on the initial dis-
explosion (vaporized combustible from the electri- charge bank. When they are tripped, the mani-
cal fault suddenly igniting. or fault arc plasma). fold pressure from the initial bank is piped
If this occurs, the access doors could be blown through a check valve to the extended discharge
open. Proper placement of CO, discharge nozzles manifold. Pressurization of this discharge mani-
and increased CO2 flow rates can be used to en- fold releases the extended discharge cylinders.
sure adequate protection even if this happens (as The check valve prevents CO? flow from the
we do protect straight through air flow machines extended discharge cylinders from entering into
which are not enclosed). If the low pressure type the initial discharge manifold and piping. The
system is used, the provision for a worst case con- flow rate of each discharge is, of course. deter-
dition will probably not significantly increase the mined by the size of the discharge piping and the
system cost. nozzle orifices on that line.

If the cooling air of the machine is ducted and In plants where there are several generators in
the ducts are provided with dampers, they should line. its common practice to protect each genera-
be arranged for closing upon CO, discharge. The tor with a separate cylinder arrangement. A third
volume of the ducts must be included in calculat- bank of cylinders, common to two adjacent gener-
ing CO2 quantities. Fans are to be shut down and ator systems, functions as a common reserve. In
any expected air flow through the damper should case either generator system discharges, this re-
be added in the CO1 discharge calculation. serve can be switched into the position of the
discharged cylinder bank, thus ensuring continu-
If theres a fire in the machine, it is expected ous protection until the other cylinders are re-
that the machine will be shut down. The CO, sys- charged.
tem is designed on this basis. However, there are
some articles recommending that the unit be kept Conclusion
CHEmETROn
Fire System: co 2 Application Bull&in

Power Generation Bulletin #0030

In conclusion, wed like to discuss the com- Safety - The safety engineering of the sys-
mon objections to the use of CO, in these ma- tem must be just as important as the fire protec-
chines. tion engineering. History has shown that acci-
dents do not occur when the equipment and sys-
Reliability - Enormous improvements in tem are well maintained and personnel are fa-
CO2 system detection and control, along with full miliar with what they have and how it operates.
supervision of electrical and key mechanical oper-
ating controls, have been made in recent years. Cost - You have to analyze what you are
Recently published data and papers indicate gas- protecting and how important it is to you. As-
eous agent systems to be comparable in reliability suming a fire is always a possibility, you should
to water systems. Experience has shown that CO2 do a fire risk analysis to determine your protection
gas supplies that are ample to ensure total fire needs and get expert help in estimating costs
extinguishment under worst case conditions can be before selecting the type and scope of protection.
provided and be cost effective. The thousands of CO2 systems in service testify to
the cost effectiveness of CO, on key units.
Since CO2 systems are almost always auto-
matic, and most water systems are manual (to pre- In addition to the generator protection, the
vent discharge when the unit is energized), seems consideration of CO2 for protection of regulator
to give the edge to CO,, especially at an unattend- cabinets, oil rooms, transformers, cable vaults,
ed, remotely controlled plant. switchgear, and spaces beneath raised floors
should be made. Normally, one system can be
used to protect all.

Other bulletins will cover the protection of


nonenclosed electric machines and the other haz-
ards mentioned above.
CHElllETROn
co 2 Application Bulktin
Fire Systemi

Power Generation Bulletin #0030


CHEmErRon
Fire System< co2 Application Bull&in

Power Generation Bulletin #0030 Page 8


CnEmETROn
Power Generation Bulletin #0035

Fire Systemi
CARBON D/OXIDE FIRE SUPPRESSION -

Hydrogen Cooled Electric Generators


Inerting/Purging Systems
co
2
When the generator rotor is turned at high speed in larger
steam turbine units, the turbine must overcome the resistance to
the turning rotor created by the atmosphere in the generator
casing. This wasted energy use is called windage loss. To re-
duce this windage loss to a minimum, the air in the casing is
replaced with hydrogen, our lightest gas.

When the unit is first installed, the casing is full of air. The
air cannot be directly replaced with hydrogen without going
through the explosive range (which is quite broad for hydrogen).
Similarly, when taking a unit from service, the hydrogen in the
unit cannot be directly bled off and replaced with air without again
going through the explosive range. To keep from creating an
explosive atmosphere, CO, is used to inert the air before the
hydrogen is introduced into the casing. Then the CO,/air mixture
is replaced by the hydrogen. To empty the casing, the hydrogen
is purged by CO, and then the unit ventilated when the casing is

a
opened.

The generator manufacturer builds a CO, manifold into the


bottom of the machine (CO, being heavy) and a hydrogen mani-
fold in the top (hydrogen being light). This helps prevent mixing
and reduces the amount of gas needed. This gas exchange is
normally done on turning gear. More gas is needed if done at
speed. (See the diagram on page 4 which illustrates this inetting/
purging operation.)

Purging the hydrogen from the machine is usually estimated


to require about two volumes of CO,. To replace the air before
hydrogen is introduced will take 1% volumes. Thus, it can be
estimated that it will take 3% volumes of CO, to take a unit out of
service, open the casing, and then return the unit to service. If
4801 Southwick Drive
done at speed, it could take 5 volumes.
Third Floor
Matteson, IL 60443
Telephone: 7081748-l 503
Fax: 7081748-2847
Q 1996 CHEMETRON FIRE SYSTEMS, all rights reserved. (9196)
CnEmETROn
Fire System: co2 Application Bulletin

Power Generation Bulletin #0035 Page 2

Years ago, it was common practice for the dling cylinders to prevent an accident -
generator manufacturer to provide a CO, supply where the cylinder becomes a projectile -
of high pressure cylinders manifolded together. are common.
These were not fire system cylinders, but rather
cylinders with manual valves at the cylinder
vapor spaces. With this arrangement, CO, va-
I4 Cylinder CO, is more costly and not as
readily available as bulk liquid CO,.
por is bled off from the cylinders into a manifold,
and then regulated pressure CO, introduced into Except for very small generating units, CO, in
the generator through the controls and manifold cylinders is rarely used today. Rather, the bulk
provided by the machine manufacturer. low pressure system is favored. With the low
pressure CO, system, the CO, vapor needed is
Liquid CO, is not used; vapor is withdrawn, obtained by taking liquid CO, from the unit and
which prevents the cooling that occurs when putting it through a direct to process vaporizer.
liquid is discharged. As the vapor from the This adds the heat of vaporization (about 120
cylinder is bled off, the pressure in the cylinder BTUs/lb.), plus the additional heat required to
drops and the flow slows. In the time usually get the CO, temperature up to the desired level.
allotted for purging, all the CO, in the cylinders The CO, vapor then goes through a flow control
cannot be recovered unless external heating is manifold (throttling valve, regulator with gauge)
used. It can be assumed that perhaps 70% is to establish the proper flow rate. CO, is usually
recoverable. (If its hot and you allow enough used at 75 - 90 psi with a purge time of an hour
time, this percentage will increase.) or two. The flow control schemes are normally
redundant. When the flow rate is established, it
The disadvantages of the cylinder system is normally left set at that level, but can be easi-
are: ly increased in an emergency. If a system with
remotely actuated operating valves is required,
1 There is only a minimum amount of CO, this is easily accomplished. Refer to the draw-
I
available. Thus, if a second purge is ing of the Carbon Dioxide Purging System,
needed, there could be delays until a re- which illustrates an arrangement where the CO,
placement CO, supply is obtained. main control valve is electrically operated, which
allows pushbutton operation. The electric va-
2 The CO, flow rate is determined by the porizer is a demand type with thermostatic con-
I
vapor bleed off rate, which is a function of trol; when the valve opens and cold CO, liquid
how many cylinders are bleeding and the is introduced into the vaporizer, the platen heat-
heat input to the cylinders. It is hard to ing elements are automatically turned on.
increase the rate if this should ever prove Therefore, the unit is always ready to go, but
necessary. In an emergency, it may be uses no power until heating is needed.
appropriate to purge the hydrogen as fast
as possible. Since the maximum flow rate is a function of
the capacity of the vaporizer, the vaporizer is
3 Plant personnel have to handle high pres- sized to a worst case condition. Increases in
I
sure gas cylinders, which is always a risk. vaporizer capacity do not proportionately in-
For this reason, the industry trend is to crease the cost.
bulk gas systems. Special rigs for han-
CHEmETROn
Fire Systems co2 Application Bulktin

Power Generation Bulletin #003.5 Page 3

The advantages of the low pressure system These direct to process vaporizers provide
and the ability to use this same storage unit for standard features, including a weatherproof
multiple purposes (hydrogen purging, coal silo enclosure, replaceable pressure cast heater
inerting, fixed fire protection, hand hose line platens, low discharge temperature safety shut-
coverage, etc.) has made it virtually an industry off, and circuit breaker load projection.
standard.
If only intermittent use of CO, vapor is con-
More details on specific system arrangement templated, one vaporizer can usually satisfy
are available from Chemetron. two uses.

Other lnerfingUses

When there is any application for CO, vapor,


the setup for using the LPCO, System and the
direct to process vaporizer to give the required
quantities of vapor are virtually the same as
that described above for the hydrogen purge.
Each pound of CO, will expand to about 8.3
cubic feet of vapor at atmospheric conditions.
The volume of CO, required is calculated and
converted to pounds as this is how the vaporiz-
ers are rated.

Basic units are: 375 lb./hour 15 KW


750 lb./hour 38 KW
1 ,125 lb./hour 45 KW
1,500 lb./hour 60 Kw
CHElTlETROll
Fire Systems co 2 Application Bulktin

Power Generation Bulletin #0035 Page 4

---___--
---____-

1s
II
U
MANUAL ISOLATION
VALVES
CO2 VAPORIZER -
REGULATOR- 7
\

RELIEF VALVE
CO2 STORAGE UNIT FILL CONNECTIONS 7 7

REFRIGERATION HOUSING \

CONTROLS CONNECTION
FOR FIRE SYSTEM
PIPING TO PURGE J
CONNECTION
CONNECTION FOR
FIRE SYSTEM
h
\, .b
\
L 1 PRESSURE
OPERATED VALVE
\
L 1 MANUAL
BY-PASS VALVE

SHUT-OFF VALVE

LIQUID AUXILIARY OU TLET

CO2 STORAGE UNIT

Low Pressure CO, Purging System


for Hydrogen Cooled Electric Generator
CHEmETROn
Power Generation Bulletin #0040

Fire System6
CARBON DIOXIDE FIRE SUPPRESSION -

Coal Storage Silos and Bunkers

Active coal storage consists of storage of coal in a bin, silo


or bunker, For the purposes of this bulletin, we will discuss silo
storage in a common power plant configuration. The coal is fed
by conveyor into the top of the silo; it then flows by gravity out
the bottom to the coal feeder (as shown on the accompanying
drawing), or to a conveyor to the coal feeder, and then to the pro-
cessing equipment (in this case, the coal pulverizer). (See Power
Generation Bulletin #0045 for information on Coal Pulverizer
lnerting and Fire Protection.)

The protection techniques discussed apply just as well if the


storage is a bin or bunker.

Coal stored in silos before it is fed into the coal mills of a


steam electric generating station (or other similar short term stor-
age application) continually oxidizes and generates heat. In the
event of an unscheduled shutdown, coal trapped in the silo will
oxidize enough to eventually start to burn. The length of time
that it takes to heat the coal to burning is a function of the reac-
tivity of the coal. Some of the Western United States coal will
reach this point in just a few days.

Fires will be more frequent if the silo/bunker is not cleaned


periodically and/or proper filling procedures are not followed. In
the event of a fire, if it is not practical to run the coal from the silo
out onto the ground, another method of fire control is necessary.
lnerting and fire control with CO, vapor is widely used.

CaRDo!! The techniques described here are based on work done by


Cardox Corporation (predecessor to Chemetron Fire Systems)
and Commonwealth Edison in 1953, and refined by hundreds of
installations at many different sites, with many different coals, in
4801 Southwick Drive the interim.
Third Floor
Matteson, IL 60443
Telephone: 708/748-l 503
Fax: 7081748-2847
Q 1996 CHEMETRONFIRE SYSTEMS, all rights reserved. (9196)
CnEmErRon
Fire Svstem; co2 Application Bulletin
a

Power Generation Bulletin #0040 Page 2

CO, System Design Procedure Used

The principle of this protection is to push CO, In the event a fire is detected (or suspected),
vapor through the coal, reach the level of ad- the CO, vapor flow is started by injecting the
sorption, and fill all the void spaces between the CO, above the coal, as well as into the coal at
coal particles to reduce the oxygen available to the sloping surface of the silo. (The bottom of
the fire to near zero. At some point, the gen- the silo is sloped to 70 or more to ensure a
eration of heat by oxidation will become less smooth flow.)
than the heat loss by conduction, and the burn-
ing mass will cool. Holding this condition long Ventilation in the air space is shut down and
enough will effect fire extinguishment. To inert a CO, concentration of 75% or more achieved
the coal, CO, vapor is used. If liquid CO, is as quickly as practical.
discharged to atmospheric pressure, dry ice
particles are formed, which could block the gas Injection of the CO, vapor above the coal is
flow. done gently to reduce the turbulence that might
unnecessarily stir up coal dust.
It is well known that carbon will adsorb CO,.
(Carbon filters specifically designed for this pur- When the air space above the coal is inerted,
pose will adsorb many volumes of CO,.) Coal, the CO, application rate there is cut back, and
while not particularly efficient in removing CO, the rate of CO, application into the coal at the
from a CO, /air mixture, will still cause CO, to bottom of the silo is increased until this CO,
adsorb to its surface. vapor starts to come out the top of the stored
coal. At this point, this CO, flow is also cut back
The U.S. Bureau of Mines has evaluated and to a maintenance rate. The CO, is held in the
quantified this characteristic and Chemetron silo as long as necessary.
Fire Systems has tested for this as well, which
allows estimating anticipated CO, use. If fire is
detected down in the coal, the minimum recom- Equipment Used
mended amount of CO, needed for inerting is
approximately three gross volumes of the silo, CO, is stored as a liquid and vaporized by a
assuming minimal loss out the bottom of the vaporizer. Flow controls (throttling valves with
silo. pressure gauges and metering orifices) are used
to properly distribute and measure the CO, flow.
At the time that the coal is burning in the
storage silo, combustible gasses (carbon mon- The system is designed so that CO, applica-
oxide and methane) will be created, and they tion at the top or at the bottom of the silo can be
could cause a problem in the air space above increased or decreased as needed.
the coal. Detection for these gasses is common
practice and identification of a high level indi- Chemetrons system design limits the CO,
cates a need for inerting (fire control). There- vapor pressure at the nozzle orifice to reduce
fore, its advisable to inert the space above the turbulence.
coal to a safe level, and do it quickly.
CHEmETROn CO, Application Bulktin
Fire Systems

Power Generation Bulletin #0040 Page 3

If the silo is in the popular 20 - 25 foot diam- Bottom Seal


eter range, only one injection point at the top,
plus another injection point at the bottom, are Its important that a good seal be made at
needed. With larger diameter silos, increasing the coal outlet at the bottom of the silo to pre-
the number of application points to three each vent CO, vapor leakage and entry of air (which
is appropriate. will chimney up through the coal). Inflating a
balloon in this coal pipe has worked well. The
coal valve, itself, is usually not a good seal in
this regard. When prevented from leaking out,
NOTE: If the storage silo is larg~senough
the heavier CO, works as a fire stop.
to require a CO, flow rate of more than
1,100 IbsJhaur using th8se guidelinas,
It should be noted that while this described
Chemetroa Fire Systems Enginasring
application relates to power plants, Cement
should be corwlted before the system is
Plant bulletin #0160, titled Coal Grinding and
specified.
Storage Systems, describes a similar applica-
tion for cement plant kiln firing systems.

Other materials subject to spontaneous igni-


tion have been protected in a similar manner
when similarly stored.
CHEmErRon
Fire Systems co2 Application Bulktin
Power Generation Bulletin #0040 Page 4

CO2 VAPOR NOZZLE ABOVE COAL


7 \
CHECK VALVE
THROTTLING VALVE

COAL
Low Pressure CO, Inerting/Fire Protection SILO
System for Typical Coal Silo
Feeder & Pulverizer

THROTTLING VALVE :
-Y !

r COAL
CONTROL VALVE \/ FEEDER

- LIQUID CO2 7
----- VAPOR CO2

CONTROL VALVE
.
:
TO ADDITIONAL
SILOS i II
2
-v
&.
ls,

MASTER VALVE
/ /

1 FLOW CONTROL
STATION

VAPORIZER

CO2 STORAGE UNIT


Power Generation Bulletin #0045
CnEmErRon
Fire Systemi

co2 The following is a quote from the January,


POWER Magazine:
1988, issue of

Electric Power Research institute (EPRI) data reveals that


pulverizer explosions occur at /east once a day in USA
utility power plants. Average cost per event is around $3
million. Looking at the data another way, there are five fires
every four years and three explosions every 10 years at the
average coal fired unit. Annual cost to the industry exceeds
$1.0 billion.

co
f3
=
s
As many as 85% of USA coal fired units are not equipped
with fire detection systems and less than 20% use some
form of inerting type protection system.

u - Chemetron has provided CO, fire suppression and inerting


-
00
n systems for pulverizers for many years. Experience gained, along

- with recent changes in the code, are covered by this bulletin.


Changes in inerting recommendations and developing technology

Q have necessitated revisions in this bulletin originally written in 1988.

n A coal mill (pulverizer) reduces raw coal to small particles,


. ..LI_L __._ L- ,-I:___I
wnrcn can be conveyed by air directiy to a borier, krin, etc. (airecr
firing), or to intermediate storage (indirect firing). There are a
number of different types of mills which either grind the coal or
smash it with steel balls. The drawing accompanying this bulletin
a shows a common type mill used in power plants. Raw coal enters
at the top and drops onto the grinding table, where the rollers
reduce it to fine particles. Heated air picks up the coal and conveys
it up to the classifier, where the larger particles are separated and
dropped back down onto the grinding table, while the lighter parti-
cles are conveyed through the coal pipes to the boilers.
4801 Southwick Drive
Third Floor
Matteson, IL 60443
Telephone: 708/748-l 503
Fax: 7081748-2847

0 1999 CHEMETRON FIRE SYSTEMS, all rights reserved. Issued 1988 - Rev 1 /1999
CARDOX IS A REGISTERED TRADEMARK OF CHEMETRON FIRE SYSTEMS.
&22 Application Bulletin
Power Generation Bulletin #0045 Page 2

This bulletin deals primarily with coal mills in and inert. Avoid disturbing any accumulation of dust
power plants that are operated under positive pres- within the pulverizing equipment. Do not open any
sure. The mills protected in indirect firing systems access doors to the pulverizer until the fire is extin-
that operate with a negative pressure are covered guished and all temperatures have returned to
in Bulletin #0160, Coal Grinding, handling & Stor- ambient.
age Systems.
If water is used, it should be introduced into the
The problem in the pulverizer can be either a raw fuel or air tempering streams, or both. It should
fire or an internal explosion. For the purpose of this be introduced so as not to cause hang up or inter-
bulletin, we are going to discuss the uses of CO2 in ruption of raw coal feed or to stir up any deposit of
mills associated with steam electric generating combustible material. After the fire is suppressed,
stations. the water shut off, and the pulverizer shut down, the
mill is to be inerted.
The reference document is NFPA Standard
No. 8503, Pulverized Fuel Systems. This docu- The use of both water and CO2 together for fire
ment states: conditions is very common. Note: Some pulverizer
manufacturers have restrictions on how water
A fire ahead of or in the pulverizer usually can be used.
causes an abnormal increase in temperature
of the equipment or the mixture leaving the Water spray is particularly effective when there is
pulverizer. Fires are caused by feeding burn- a large mass of coal remaining in the mill after shut
ing fuel from the raw fuel bin; by spontaneous down and it is burning. The mass must be cooled to
combustion of an accumulation of fuel or for- achieve total extinguishment. While CO2 will sup-
eign matter in the pulverizer, piping or burn- press burning, all cooling in a CO2 atmosphere will
ers; or by operating at abnormally high be natural cooling, which could take some time.
temperatures. Water will, of course, accelerate the cooling of the
hot coal mass.
A fire in any part of a pulverized fuel system
shall be considered serious and dealt with Fire detection is possible by measuring outlet air
promptly. temperatures or the amount of air temperature
change.
Fire Protection
Means for measuring carbon monoxide levels are
Paragraph 3-5.3.2 of Standard No. 8503 outlines available. There are companies offering detection
procedures for fighting fires. If CO2 is used as a fire systems designed for this specific application.
extinguishant (not just to inert), paragraph (a) or (b)
below would apply. They state: Since none of these means are practical to oper-
ate a CO2 extinguishing system automatically, the
(a) If sufficient inertant flow capacity is pro- CO2 system is actuated manually through a
vided (at least 50% by volume of the pri- pushbutton station. The discharge rate is calcu-
mary air flow of the system), inert the lated based on the operating conditions specified,
pulverizer air/fuel flow, shut off the fuel
and the length of discharge is automatically
feed, empty the pulverizer of fuel, shut
timed. Provisions are included for follow up or
down and isolate the pulverizer.
subsequent discharges, if they're necessary. Tie-
(b) Stop the primary air flow, trip the pul-
ins to shut down equipment, as prescribed, can
verizer and feeder, isolate the system be included in the CO2 system design.
&22 Application Bulletin
Power Generation Bulletin #0045 Page 3

required.
Steam as a Fire Extinguishant
The minimum CO2 level required for inerting is
In a paper presented to "Coal Technology such that oxygen levels will be below 15%.
'84" based on work done by Riley Stoker for Chemetron recommends 65% CO2 (7.5% oxygen)
the Electric Power Research Institute: The as a design level. When calculating CO2 flooding in
Relative Effectiveness of Different Agents coal, remember that the coal adsorbs considerable
in Dealing with Coal Pulverizer Fire and CO2, which is thus lost and will not help reduce the
Explosion Prevention, the following concern oxygen concentration.
on the use of steam for fire suppression was
raised. Paragraph 3-5.2.1.2 says: The inerting procedure
shall be as prescribed by agreement between the
The use of steam as an extinguishing pulverizer equipment manufacturer and the pur-
agent did create a precarious situation. chaser. They should consider fuel characteristics,
Using steam with a fire present devel- pulverizer temperature, size and arrangement of the
oped a more reactive gas, and if pulverizer.
detonation developed, the carbon mo-
noxide and methane produced magni- We strongly recommend that designers bring
Chemetron into the planning and design process
fied resultant forces. In addition, steam
so we can calculate proper CO2 quantities and flow
proved to be one of the worst agents
rates to insure that adequate systems are specified.
the more steam applied, the less effec-
Remember, if inerting is done under different condi-
tive it becomes. tions, different CO2 rates will be needed and the
CO2 system must be designed accordingly.
Inerting
Several of the pulverizer manufacturers have
The most common use for CO2 is for inerting the already identified the CO2 flow rates required for
mill as an explosion prevention means. The Stan- inerting different mill sizes.
dard for Pulverized Fuel Systems, NFPA Standard
No. 8503, paragraph 3-5.2.1.1, says: A pulverizer
Combustion Engineering
tripped under load shall be inerted and maintained
under an inert atmosphere until confirmation that no Combustion Engineering has considered CO2
burning/smoldering fuel exists in the pulverizer, or inerting as an auxiliary to the steam system and as
the fuel is removed. a stand alone system. In the auxiliary mode, the
CO2 would be required only after the unit trips. With
Note that paragraph 3-5.2.2.2 says: Due to the the primary air fans off, the pressure differential
danger of an explosion when opening and cleaning, across the mill is low, the air infiltration low, and the
pulverizers shall not be cleaned manually until they CO2 use low. For a stand alone CO2 system, coal
and their contents have been cooled to ambient pipe shutoff valves, capable of sealing against full
temperature. primary fan pressure, are needed.

The use of CO2 as an inertant allows the Tests have shown that the application of CO2 in
maintenance of the inert atmosphere until the mill the above conditions will inert a mill in a mat-ter of
cools and can be opened for cleaning. seconds, but if the CO2 is shut off, it is lost quickly.
The best inerting arrangement is to rapidly fill the
Your attention is called to the other various re- mill with CO2 to a safe level. This is done with a
quirements for inerting that appear in Standard No. high rate discharge to achieve 30% CO2 (15% O2)
8503, based on other conditions that can occur. within the first minute after shutdown.
When CO2 is used as the inertant, the more the air
movement can be stopped, the less CO2 that will be Then, in worst case conditions, if external cooling
&22 Application Bulletin
Power Generation Bulletin #0045 Page 4

(water) cannot be applied, the inert condition will Table 1


have to be maintained for hours while the mill cools. Inerting & Clearing Media Supply Requirements

There is a small unclosable opening in the bottom NOTE: The inerting cycle is 8 minutes duration
of the mill. CO2 must be added to make up for that

CO2 (Pounds

CO2 (Pounds
which will leak out this opening. By using heated

Per Cycle)

Per Cycle)
Volume

Volume
CO2 vapor, the loss out this opening is greatly re-

(Cu.Ft.)

(Cu.Ft.)
duced. Therefore, CO2 vapor application is recom-

Mill

Mill
mended. A cost effective system results.
44K 470 312 75K 2,000 1,557
Another advantage of this system is that a contin-
44N 470 390 75N 2,000 1,783
uous flow of CO2 vapor is much, much easier to
control than intermittent discharges of CO2 liquid 44G 470 468 75G 2,000 2,000
which had previously been recommended. 49N 610 511 89K 2,250 2,400
49G 610 611 89N 2,665 2,755
Babcock and Wilcox
56K 750 667 89G 2,665 3,020
Babcock and Wilcox has published data for their
MPS Mills on pulverizer inerting and fire protection. 56N 750 744 104K 4,400 3,670
The current (1990) material is Plant Service bulle- 56G 750 822 104N 4,400 4,037
tin No. PSB 16-85 and Guide Specification 1A5- 67K 1,500 890 104G 4,400 4,404
GR211-29Y.
67N 1,500 1,112 118K 6,200 3,803
Recommended inertant quantities are shown in 67G 1,500 1,334 118N 6,200 4,691
the Table 1 at the top of the right-hand column.
Table 2
Ball Mills CO2 Requirements for Inerting Ball Mills
Figure #2 shows a roller-type mill, while Figure #1 Carbon Dioxide
shows a ball-type mill in which a drum rotates, Pulverizer Volume
Series FT3
causing steel balls to crush the coal. Foster Wheel- Lbs *Lb/Hr
er has this type mill in their D Series. Table 2 pro-
D2 300 43 1,300
vides information for inerting with CO2.
D3 500 72 2,200
The CO2 injection points are shown at the classi-
D4 750 100 3,000
fiers and at the exhausters, and since methane gas
can accumulate in the ducts above the mill in case D5 950 136 4,100
of fire, CO2 is injected there as well.
D6 1,200 172 5,200
For long term inerting, an external discharge is D7 1,500 215 6,500
applied through these upper nozzles, and a proce-
dure is established to periodically roll the mill while D8 2,000 286 8,600
it is inerted to facilitate cooling for fire extinguish- D9 3,100 443 13,300
ment.
D10 3,900 558 16,900

*The rates in Lb/Hr are for a 2 minute inerting duration


period.

Figure #2 illustrates a pulverizer inerting system.


CHEmETROn
Fire System; CO* Application Bulletin

Power Generation Bulletin #IO045 Page 5

System Arrangement Reliability


Figure #2 illustrates a pulverizer inerting system. There is material in the literature questioning the
reliability of all gaseous agent inerting. In order to
The CO, storage unit is sized with at least the maximize the effectiveness of the inerting system,
amount of CO, recommended by the pulverizer one should understand:
manufacturer. [Obviously, the same CO, storage
can be used for other fire protection and inetting
requirements (particularly coal silo/ bunker inerting, I1 Homemade systems are potential prob-
lems. Those experienced in CO, system
see Bulletin #0040) if these are within a reasonable design can calculate proper agent quantities
distance of the storage. Storage unit sizing is to be and application rates, and do the flow calcu-
based on the total of all hazard requirements where lations that ensure the required rate is
simultaneous use is considered.] achieved. It is mandatory that this be
done.
For initial inerting, liquid CO, is piped through the
master valve to the selector (directional valve) near
the mill. The CO, is introduced into the mill through I2 Systems should be given full discharge tests
to check that design concentrations are ob-
the hot air inlet, plus perhaps, several other injec- tained. Various expected conditions should
tion points. The manufacturer will have provided a be included in the test procedure and multiple
pipe connection(s) (usually at this point) of at least tests run, if necessary.
1 per NFPA #8503, but more like 2 to 3.
Operating conditions change and there may
When CO, is required, a remote pushbutton is I3
not be one fixed agent discharge rate that will
operated and liquid CO, is directed through the handle all desired conditions. The system
master valve, discharge piping, and selector valve can be arranged to handle two or more appli-
to the nozzle(s) at the mill. cation rates; but only if the operating pro-
cedures identify the need for same and it
The duration of the discharge is set on the timing is designed into the system from the start.
panel provided. If follow up CO, vapor discharge is
needed, similar controls are employed to introduce Paragraph 3-5.3.4 of NFPA Standard #8503
liquid CO, to the vaporizer and then direct CO, states: In the event offiresdetected in components
vapor to the proper mill. such as cyclones, dust collectors, pulverized fuel
bins for the pulverized fuel systems other than di-
Safety Aspects rect fired systems, the affected components shall be
isoia ted and inerfed.
In addition to the normal safeguards necessary
when dealing with CO, systems - see NFPA Stan-
dard No. 12, Carbon Dioxide Extinguishing Sys-
tems - it is required that procedures be developed
to positively prevent inadvertent introduction of the
inerting media when personnel are present.
Chemetron can be consulted as to how best to
accomplish this.
Power Generation Bulletin #0045

&22 Application Bulletin


Page 6
Figure #1 - Low Pressure CO2 Coal Pulverizer
Inerting/Fire Protection for a Ball Mill
Power Generation Bulletin #0045
Figure #2
Low Pressure CO2 Coal Pulverizer
Inerting/Fire Protection for a Roller Type Mill

&22 Application Bulletin


Page 7
CHEmETROn
Power Generation Bulletin #0050

Fire Systemi
CARBON D/OX/DE FIRE SUPPRESS/ON -

co2 Diesel Electric Power Plants

The operation of diesel engine driven electric generators can pro-


vide continuous electric production for self-contained, isolated power
systems; for intermittent power production to supplement other genera-
tion (peaking): for emergency power production; or for cogeneration
facilities. All these important functions require reliability.

==1 The reason diesel engines are popular for these functions is their

m reliability. Even so. the risk of fire exists due to the fuels, lubricants
and electrics involved, combined with some obvious ignition sources.

The plant location, often isolated with equipment remotely operat-


ed, dictates a reliable self-contained fire protection system that, in and
of itself, will not contribute to an interruption of power production.

Carbon dioxide (COz) is well suited to this purpose. It can provide


fast, clean extinguishment, and due to its three-dimensional nature, it
will reach a fire otherwise shielded from discharges from other types
of systems, such as sprinklers. CO, is a nonconductor, and is nondam-
aging to equipment, hoi metal surfaces, and sensitive components. It
requires no provisions for water drainage as would be the case with
sprinklers. And, if the system is properly designed, it can ensure
continuity of protection during any time period required for outside re-
sponse to the indication of fire.

CO, has proven its worth over decades in protecting diesel engines
on board ships, where many, many fires have been controlled.

While operation in a ships engine room or in a stationary power


4801 Southwick Drive plant are somewhat different, there are enough similarities to demon-
Third Floor strate the need for concern with the following hazards:
Matteson, IL 60443
Telephone: 708/748-l 503
Fax: 7081748-2847
c 1996 CHEMETRON FIRE SYSTEMS, all rights reserved. (9i96)
CHEmETROn
Fire Systemi CO2 Application Bulktin

Power Generation Bulletin #OOSO Page 2

The Fuel Oil Svstem, when liquid fuels are used. CO2 to handle the generator fire. The generator
Failure of fuel lines due to engine vibration and windings were open to the room, providing access
resultant metal fatigue can result in 130F flash for the CO, gas.
point No. 2 fuel oil coming in contact with hot
exhaust manifolds. Sheathed piping can reduce, If the generator is totally enclosed, some units
but not eliminate, the hazard. will have a fitting to allow connection to the CO:
system to provide internal flooding.
When heavy fuel oils are used, the centrifuges
employed can be very hot. Failure results in a CO, SYSTEM ARRANGEMENTS
very smokey fire. Nozzle heaters also present a
hazard. (Concern for hazards of auxiliary boilers In what might be called traditional CO, protec-
should also be given). tion, the room housing the diesel electric generator
would be totally flooded with CO, to achieve a fire
Lube Oil Svstems. Good engine performance extinguishing concentration: 34%) CO2 for oil fires,
requires good lubrication (bearings and internal 50% CO1 for electrical fires. In the many nuclear
engine components). A large quantity of oil is power plants where the emergency diesel generators
often needed (one particular installation involved are provided with CO, fire protection, each genera-
a 40MW plant using 12,000 gallons of lube oil.) tor is in a room well designed for CO? flooding.
Combustion air is filtered and ducted from outside.
A major bearing is near the turbocharger (com- Secondary air ventilation can be shut down and ven-
bustion air is processed in the compressor/turbine tilation openings dampered or shuttered.
of the turbocharger). In some machines, these
turbochargers have been known to operate cherry However, in many power plant facilities, the
red, thus offering a prime ignition source. engine-generators are all lined up in a row with the
necessary oil equipment installed in the generator
The drawing accompanying this bulletin illus- room, or mounted on a balcony. Switchgear may be
trates protection at the Engines, the Fuel Oil Day along a wall, or preferably, in a separate, cut-off
Tank, and the Fuel Oil Processing area, as well as room. Ideally, the machines and equipment will
the inside Lube Oil Storage and Lube Oil Processing have dikes/trenches to confine oil spills and limit the
areas. hazard

Not shown, but also included in a fire risk anal- When this is done, the local application of CO?,
ysis, would be protection for the electric generator rather than total room flooding, is the practical
and the electrical switchgear/controls. protection approach. Careful analysis is needed to
ensure the entire hazard is included in the CO, cov-
Example: At a Midwest nuclear generating sta- erage.
tion, the emergency generators were diesel-electric
units, each installed in its own room. Under test, Provision must be included in system design to
the generator itself caught fire. While the CO, allow for simultaneous protection of adjacent (inter-
protection system was designed to protect the oil exposing) hazards. Interestingly, some recent (1988)
hazards of the engine, the system contained enough testing by the U.S. Coast Guard called Localized
Extinguishing Tests, bears directly on this subject.
CHEmETROn
Fire Systemi co2 Application Bulktin

Power Generafion Bulletin #00.50 Page 3

Under USCG Regulations, many, many vessels COGENERATION


are equipped with single shot, total flooding CO:
During a survey period from June 1991 through
systems for machinery spaces. In the event of fire at
sea, the system is discharged, the fire extinguished, May 1992, a record number of machines over 1MW
capacity were ordered; 40% were for continuous
and then the vessel is required to sail to port with no
duty service. Orders increased for those using diesel
protection. This concerned many. Therefore, the
USCG analyzed reported fires to determine which oil. The application to cogeneration was one reason
engine room equipment was most likely to be the lo- for this growth.
cation of a fire. This included the diesel engines
used for propulsion. The Coast Guard felt a much In the operation of a typical engine, 38% of the
smaller, localized, directly applied CO, discharge on input energy resulted in the output of electric power
the machine, backed up by the engine room flooding generation. 33 % was exhaust heat, providing a
system, would give the ship operator a good chance source of high temperature heat that can be put to
good use in a variety of cogeneration applications.
for handling the fire and still have protection until
the ship got to port. It was established that properly Thus, the popularity of such facilities. As depen-
designed local application of CO, can do the job. dence grows on the cogeneration facility, so does the
need for good, reliable, cost effective fire protection.
In the case of a large room in a power plant
with engines lined up in a row, the local application interesting Cogeneration Application: An ap-
of CO,, resulting in low level flooding, could be the plication story in Diesel and Gas Turbine World-
answer to good, cost effective protection. This con- wide reported on a plant in Barcelona where 3 -
cept is described in an earlier bulletin covering pro- 1280 KW engines, driving 1515 KVA, 6 KV, 50
tection for large nonenclosed gas turbines, hertz generators, produced exhaust gas which was
scrubbed, washed, cooled, and the CO2 separated.
Since the hazard on the engine primarily exists The CO, produced was sold, as 2280 Kg/H of CO,
due to hot metal surfaces in close proximity to com- was recovered. 70% of the power produced went
bustibles, the minimum 30 second local application into the power grid, with the CO, production (com-
discharge (see NFPA Standard No. 12) may not be pression/liquefaction) taking most of the rest. The
long enough. Extending the discharge to achieve CO: was sold to Coca Cola, Pepsi Cola, Cinzano,
low level flooding to an adequate CO, concentration and others.
level will be necessary. (Consult the Chemetron
Fire Systems Engineering Department for guidance). Production of your own fire extinguishant - an
interesting concept!
CO, Fire Protection System
for Diesel Power Plants

Air Filter
CHEmETROn
Power Generation Bulletin #0055

Fire Systems
CARBON D/OXIDE FIRE SUPPRESS/ON -

Under the Sidewalk


Transformer Vaults

Sample excerpts of typical newspaper reports:

April, 1985: About 230 workers were evacuated from their offices
. . .after a transformer
caught fire, possibly because of an electrical over-
load caused by air conditioners.

July, 1986: An explosion and fire in an underground electrical vault


. . . injured 12 1 people, forced evacuation of at least one high rise office
building and spread power outages and confusion over a wide area.

June, 1987: When a transformer at a downtown.. .athletic club


exploded and erupted in fire last week, the major concern was PCBs.

The power requirements of the modern high rise building are signifi-
cant, necessitating the provision of underground vaults to house equipment
comaecting local utility lines to the building. These contain transformers
that convert incoming power from, say, a 12 KV feeder to 120 volts for
local use. Cables and other electrical equipment are also present. Many
of these transformers were insulated by polychlorinated biphenyls (PCBs).
While these should have been replaced, when fighting fires on this equip-
ment, it is prudent to consider the materials involved as hazardous. New
insulating materials can help reduce the fire risk as compared to oil filled
units. But while the fire hazard may be reduced, fires still occur. No
matter what is used, or to be used, the need for fire protection has been
ably demonstrated.

In some cases vaults have been provided with fixed fire protection,
but this has been rare because there are so many. Another approach is the
4801 Southwick Drive provision of specialized fire fighting equipment to be placed in service in
Third Floor central business districts where high rise buildings are common.
Matteson, IL 60443
Telephone: 7081748-l 503
Fax: 7081748-2847
B 1996 CHEMETRON FIRE SYSTEMS, all rights reserved. (9196)
CHElMETROll
Fire System; co2 Application Bull&in
Power Generation Bulletin #0055 Page 2

During analysis of the proper fire extinguishant to CO, nozzle. This is the type nozzle, with its high
be used in these special units, the following factors discharge rate and projection ability, that proved so
were considered: effective in aircraft crash fire/rescue operations per-
formed by the military during World War II and the
The agent should be three-dimensional as it may not Korean War. A squeeze valve on the hose line play-
be possible to direct the fire extinguishant directly pipe affords flow control, Of course, the playpipe with
at the fire. the projection nozzle can be used in many ways for
local application or indirect total flooding wherever
It should not need drainage. appropriate.

Since the fault causing the fire is almost always Since the described low pressure CO, units travel on
related to the failure of circuit protective devices the public streets, the pressure vessels, while still
from disconnecting power; the extinguishant qhnuld
o_.___-._ L______ all nther
m_cetinpD --- mnlicxhle
------ -TT ---__-_ r.ndm
-----, arp b~i!t !Q the
be a nonconductor; one that will not break down requirements of the Department of Transportation
under the continuous electrical arcing. (DOT).

Carbon dioxide meets all the above criteria. It should be noted that for confined fires in an inac-
cessible space anywhere - the type on which you
A solution to the protection need identified above might use high expansion foam, this CO, unit could
was to establish a mobile supply of low pressure liquid provide more rapid suppression since it can deliver
CO, that could be quickly moved to the building in- very rapid application of agent. The CO2 does not
volved in fire. Low pressure storage, because of its build up from the bottom of the space, but rather
lower weight and size requirement, was the obvious mixes and immediately starts to reduce the fire sup-
choice. porting oxygen. Thus, it will be effective quickly in
confined spaces that do not exceed a size for which the
Two different methods of applying the CO, dis- unit is effective (estimated to be 1 pound of CO, for
ItXlJ. ,.I_l_:,_
,.h..,,l,-. +l.,
UlcugG C UICc,, I.^..^ L,--.
l,lC lMC CCU..,.,I
llscu. ___L qc _..l_:_ J?__r\ _A suppnes
_..__,I_- drt:
c.._ cuvercu
__-.___>
G;aL;llL3 UIUIC: ~v~wout:LUG
by Chapter 5 of NFPA Standard No. 12, Catbon LXox-
In one case, each vault was piped with nozzles tie Extinguishing Systems.
placed to cover the protected equipment. The pipe and
nozzles were sized to give the appropriate discharge Another use of this type equipment was discussed in
rate and distribution of the CO,. High temperature pipe the NFPA Fire Journal in an article that described the
and nozzles were used to stand up to the fire during extinguishment of a stubborn fire in a cargo hold of a
the time needed to start a discharge. Piping is extend- docked ship. The fire department used a CO, liquid
ed to street access. transport unit and a LPCO, hand hose line. Fortunate-
ly, a transport unit was available (they are normally
The mobile supply, which can be either trailer or always tied up making deliveries.) This was a slow
truck mounted, has hose that can be quickly coupled to burning - albeit active - fire, allowing time to ar-
the piping connection for the vault. Valves allow the range for this use.
fire fighters to control the CO, discharge.

In another case, as illustrated here, a truck mounted


unit was used. It was equipped with hydraulically
operated boom equipment to remove the cover from
the vault, and then to place over the opening a special
steel plate to which can be affixed a projection type
CHEmETROn 2 Application Bulktin
Fire Systems co

Power Generation Bulletin #0055 Page 3

Other Indirect Total Flooding Applica- Swinging cover plates in the room doors are
often used to give access for the nozzle to dis-
tions for LPCO, Hand Hose Lines
charge inside. When a fire is detected, the line is
charged, the swing plate pushed aside, and the
As previously pointed out, the relatively high nozzle shoved into the opening. Instructions indi-
discharge flow of the LPCO, hand hose lines can cate the discharge time recommended for flooding
make these units valuable fire fighting tools for each space. These systems can be tested for per-
confined spaces of all kinds. formance in the same way any total flooding CO,
system is tested.
Tests have shown that a CO, concentration of
25% will extinguish open burning; this is an oxy- Often, more than one hand hose line are made
gen concentration of about 15.5g. Considering available to provide the required CO, if the pro-
that a fire in a confined space is already consum- tected space is large.
ing oxygen, adding CO, can often quickly suppress
the active open burning and significantly help fire
fighting efforts. In-Plant Mobile Units
For example: If an LPCO, hose line (1) is dis-
charging at a rate of 300 lbsiminute, then that dis- We previously discussed LPCO, units designed
charge will reduce the oxygen from 21% to 15.5% for transport on the streets and highways and for
in a space of 18,000 cubic feet in 2 minutes time use by the fire service. Units designed for in-plant
if it is reasonably enclosed. This would be a space use by plant fire brigades have also been widely
about 50 x 45 x 8. used. The CO, unit design is similar, but the vehi-
cle would be an in-plant type.
Of course, distribution of the gas is all impor-
tant. Fortunately, the LPCO, hand hose line pro- Safety Concerns: The use of large capacity
jection nozzle has an extended projection range - (high flow) LPCO, hand hose lines in large open
up to 50 - and, therefore, would be expected to spaces (power plant bays, mill floors, etc.) does not
effect flooding rather quickly in appropriately normally give any cause for concern that CO, will
sized enclosures with no significant openings. build up enough to affect the operator. It is ex-
Openings could delay suppression, and large open- pected that the products of combustion from the
ings could prevent same. Therefore, we only rec- material burning will create more potential hazard
ommend you consider this use in confined spaces for the operator than will the CO, being applied.
by discharging into same from outside. However, it is always an excellent idea to have air
breathing apparatus available in the vicinity of
As the CO, discharge continues, it keeps hosereel locations to be used in case of a fire.
adding inert gas to the volume, further reducing When CO, starts to build up from hose line opera-
the fire supporting oxygen level to help control tion in a large open area, it must build up essen-
deep-seated burning. tially from the floor; you can feel the cool on your
legs. When inhaled in very small amounts, CO,
For a big complex with a number of critical acts as a stimulant to breathing. This is an invol-
electrical switchgear rooms or unmanned control untary reaction and very apparent to the operator.
rooms, providing a fixed total flooding gas system
for each might not be affordable. An alternative Use of CO, hand hose lines in a confined
is to provide each with a good fire detection sys- space without air breathing appartus is very
tem - smoke/flame/heat or a combination - and dangerous and should be avoided.
then plan to extinguish the fire with LPCO, hand
hose lines from a fixed or mobile supply.
CHEmETROn 2 Application Bulletin
Fire Systems co

Power Generation Bulletin #0055 Page 4

- lmportan t Hand hose lines are generally intended for


protection where there is no automatic fixed pro-
If hose lines are located so that they tection.
can be used even in large areas where fixed
protection is also present, you must ensure NFPA Standard No. 12 should be consulted
that the fixed protection does not operate for a discussion of safe uses of CO,.
when hoselines are being used. A fixed pro-
tection system discharge could envelop the For more detailed information regarding CO,
hoseline operator; and if not equipped with hand hose line fire protection, see Industrial Facil-
air-breathing apparatus, the operator could ities Bulletin #0760, High Capacity Portable
be overcome. It should be noted that if he is Protection with CO, Hand Hose Lines.
fighting a fire, his attention will be directed
away from any warning system that may be
present as part of the fixed system.

Truck-Mounted
Mobile Carbon Dioxide Unit
CHEWIETROn
Power Generation Bulletin #0060

Fire System;
Water Mist Fire Suppression -

Compartmentized
Gas Turbines

The newer high capacity cogeneration plants utilize com-


partmentized gas turbines - units that are housed in enclosures,
shipped to the job site and quickly placed in service with little on-site
construction. We choose to call these compartmentized turbines
packaged units. Figure 2 illustrates a compartmentized gas turbine
protected by a water mist fire protection system.

This bulletin presents a description of the recommended


Chemetron Water Mist system protection, along with a background
of the development work done to assure that this protection is
property designed to meet the unusual demands of this equipment.

This application can also include fire protection for auxiliary


turbine rooms (which can house oil pumps, oil tanks, fuel filters, gear

3 boxes, drive shafts and lubrication skids), diesel emergency rooms,


and other similar machinery spaces.

Q
m The duration of the water mist discharge for gas turbines is a
minimum of 20 minutes, except when the turbine wind-down time is
specified as less than 20 minutes. All other hazards described shall
be protected for a minimum of 10 minutes.

a
Q Description of Hazard
A gas turbine unit consists of an axial compressor section and
an expansion turbine section on a common shaft, coupled to drive
an electric generator or centrifugal compressor. A diesel starting
engine, electric motor, or small separate turbine is utilized for start-
ing.

Air is drawn into the compressor and compressed before


entering the combustion chamber, where it is mixed with fuel and
burned. The expanding burned gasses drive the turbine, which in
480 1 Southwick Drive
turn powers the equipment being operated.
Third Floor
Matteson, IL 60443
Telephone: 7081748-I 503
Fax: 7081748-2847

(D 1998
CHEMETRON FIRE SYSTEMS, all rights reserved. Issued: ( 11198)
CARDOX IS A REGISTEREDTRADEMARK OF CHEMETRON FIRE SYSTEMS.
CHEmETROn
Fire Systemi RM Application Bulletin .

Power Generation Bulletin #IO060 Page 2 -

The areas of protection considered for any gas ducted on actual installations on several different
turbine power facility are the Turbine Compartment, makes of turbines, one type of which is illustrated
the Accessories Areas, the Electrical Control and on the drawing accompanying this bulletin.
Switchgear Areas, the Fuel Pump Area, and the
Generator. Protection of the Accessories Areas, Recordings were made of surface tempera-
Control Room, and Pump House present no unique tures at three locations, as illustrated by points A, B
problems of protection. The protection of the Tur- and C on the graph in Figure 1. Point A represents
bine Compartment is of primary concern in this the external surface over the combustors. In indus-
presentation. trial type turbines, the combustion chamber is sepa-
rated from the exposed surface metal, allowing
The most common fire hazard occurring in the access to incoming cool air. Therefore, the temper-
turbine compartment is the failure of the fuel (natu- ature does not get as high as might be expected.
ral gas, No. 2 fuel oil, or jet fuel) system, or by leak- The temperature may be higher downstream of the
age of lubrication oils used on the shaft bearings. combustion chamber just before entering the ex-
When the gas turbine is operating, it gets very hot, pansion section of the turbine. In aircraft type tur-
and when it is shut down, it cools rather slowly. bines, the surface temperatures get somewhat
Outer surface temperatures of the combustion higher.
chamber and turbine expander reach 850F -
900F, which is well above the approximate 494F Point B represents temperatures in the exhaust
auto-ignition temperature of No. 2 fuel oil, or the section not visible on the drawing. These surfaces
approximate 700F auto-ignition temperature of are largely insulated; however, there are some thin,
bearing lubricating oil. Therefore, if this fuel comes exposed sections in the exhaust bearing tunnel, and
in contact with these hot surfaces in an air atmos- also some heavy support sections that have direct -
phere, a fire can occur. Since these units are often metallic contact with the inside of the exhaust pas-
unattended and not accessible to follow-up fire sageway. Heavy support sections may not get as
fighting, there is no way to effect total extinguish- hot as thinner sections, but cooling will be slower
ment except through the fire protection system because of the sheer mass of metal.
itself. Shutting off the fuel to the gas turbine by
closing a valve in the fuel line is a part of system Point C represents the exhaust manifold of a
design and should limit the fire producing material diesel starting engine for those systems provided
to the residue in the bottom of the unit, This residue with this method of starting. The diesel engine runs
may not be in contact with the hot turbine. How- only during the starting cycle. However, the ex-
ever, contact could exist through failure of the fuel haust manifold does get hot enough to ignite fuel oil
shutoff valve or other abnormal occurrence. The before the diesel engine is shut down after starting.
pressure in the bearing lubrication system is specifi-
cally designed to be maintained while the shaft is The actual temperatures attained and the cool-
rotating so that a loss in the integrity of the lube oil down time depend upon operating conditions. The
system could force oil under pressure onto nearby greater the load or output, the higher the gas tem-
hot metal parts. perature must be to drive the load. Therefore, maxi-
mum surface temperatures are developed when
Cool Down Time operating at maximum load with maximum ambient
air temperature.
The critical question in gas turbine protection is
how long does it take for exposed hot surfaces to Cooling time will be influenced somewhat by
cool below the ignition temperature of the fuel in- the ambient temperature and also by the shutdown
volved. To answer this question, it was necessary procedure. Normal shutdown procedure is to run
to run a series of tests in which surface tempera- the turbine under no load conditions for about five .__,
tures at suspected locations were recorded during minutes before finally shutting off the fuel. The
operation and shutdown. These tests were con- internal parts of the exhaust section cool down
CHErnETROII
Fire Systems ~~~ Application Bulletin

-
Power Generation Bulletin #0060 Page 3

rapidly under these conditions because of the cool- cool the turbine lubricating oil by drawing air
er gas flowing through the system. Emergency through a fin tube heat exchanger.
shutdown for fire extinguishing requires an immedi-
ate fuel cut off after load is removed so that the When the turbine is shut down, the flow rate of
turbine slows down immediately and the air flow the secondary cooling air drops off rapidly; how-
through the system falls off very rapidly. Under ever, air leakage remains much too high to permit
emergency shutdown conditions, there is no time practical total flooding without prohibitive loss of
for internal cooling and the exposed surfaces will water mist. The obvious leakage openings must be
not cool off as rapidly. Chemetrons water mist sealed or provided with dampers that can be closed
system has the capability to reduce the ambient when the water mist system is actuated. In some
temperatures in the enclosure almost instantly, systems, there is an annular gap around the turbine
thereby assisting in the reduction of surface temper- air intake bell. In others, there may be bottom
atures of the involved equipment. openings through which pipes and conduit are
brought into the enclosure. Doors and panels must
Figure 1 represents typical temperature curves close tightly and have soft seals. Even so, the leak-
during a test operating cycle for a turbine system age rate will still be sufficient to dissipate the water
with a diesel starting engine. It will be noted that mist atmosphere over a period of time. Therefore,
the diesel exhaust manifold (C) reaches a tempera- protection should be provided until the completion
ture over 800F during the starting cycle. The cool- of the turbine wind down time. Through testing, it
ing time is based on cooling to 49OF, the auto- has been determined that due to the cooling effect
ignition temperature of diesel fuel. that water mist provides during suppression, the
- chance of reignition after extinguishment is minimal
Combustor surface temperatures (A) may not
get as hot as the starting engine exhaust manifold, Fire Detection
however, cool down time may be longer depending
on the type of turbine. Highest surface tempera- The high secondary air flow rate required for
tures were found in the exhaust section (B). Heavy compartment cooling also makes it difficult to detect
metal sections required the longest cooling time. small fires with heat detectors located near the
Where the only fuel exposure is turbine lubricating ceiling. It takes a substantially sized fire burning
oil, the cooling time can be based on its auto-igni- near the floor level to raise the temperature of the
tion temperature of 700F. It is necessary to add a total air flow sufficiently to actuate the heat detec-
safety factor to all of these figures to compensate tors. Heat detectors are obviously needed over the
for the possible effect of operation at unduly high turbine sections to assure detection of a fire that
loads or high ambient temperatures. may originate on the side or top of the turbine due
to a broken fuel line. On the other hand, to detect
a small fire near the floor level, it is desirable to
Air Leakage
install detectors below the turbine in critical areas
In any turbine installation, there must be a where such fires might occur.
substantial flow of cooling air around the outside of
the turbine to maintain reasonable ambient temper- The important limitation is to make sure that
atures within the turbine compartment. This may be the temperature setting is high enough to avoid
accomplished by aspirating air from the turbine false actuation by radiant heat from the turbine
enclosure into the exhaust duct. Alternately, fans or itself. This point was actually tested by installing
special eductors may be used. The cooling air dummy thermostats with internal thermocouples for
often enters through openings on the side of the recording the temperature during a test cycle. It
enclosure. The air inlets may be designed to bring was found that such temperatures did not exceed
- the air in near the bottom of the turbine enclosure 200F and that therefore, a temperature setting of
so that it must pass over the turbine before being about 325F should be satisfactory.
exhausted to the outside. It is also necessary to
CHEmETROn IsT Application Bulletin
Fire System;

Page 4 -
Power Generation Bulletin #0060

Because of their inherent simplicity and reli- by a mechanical operator located on the cylinder
ability, heat actuated detectors are considered best valve. The nitrogen cylinder valve is equipped
for automatic discharge of the water mist system. with a solenoid, fill port, pressure gauge and
Flame or other special detectors may be used in safety relief valve and is regulated through the
critical units. primary regulator to a pressure established by
hydraulic calculations, but not in excess of 500
psi. The control panel should also initiate a sig-
Water Mist System nal to close automatic dampers to shut off major
The piping and nozzle arrangement of a water ventilation openings before the discharge be-
mist fire protection system for this application is gins. In addition, all fuel and lubricant delivery
illustrated on the drawing. When a fire is detected systems into the hazard area will be stopped
in any one of the protected compartments, the first immediately after fire detection.
action is to automatically shut down the turbine by
shutting off the fuel supply and disconnecting the Downstream of the primary regulator, the nitro-
gen splits at a tee to travel in two directions. On
generator from the line. An alarm is also sounded
one side, the pressure established by hydraulic
to warn personnel of the impending discharge.
After a brief delay to allow time for evacuation and calculations is used to pressurize the water
vessel (normally at atmospheric pressure). On
the automatic charging of the water holding tank,
the other side of the tee, the nitrogen will pass
discharge is initiated. The turbine compartment is
through a secondary regulator, where it will be
not normally occupied during operation, so delay of
the discharge is not required when the water mist regulated to a pressure (between 75 and 125
psi) suitable for the operation of the automatic
system is operated. -
water control valve.
When the water mist system is actuated and
Water is pressurized in the water vessel up to
the flow of water through the nozzles is initiated,
there will be an immediate reduction of temperature the automatic water control valve, which is nor-
mally in the closed position. The water pressure
and displacement of oxygen within the enclosure,
vessel is provided with a nitrogen inlet, water
both of which are key components in the control,
suppression or extinguishment of turbine fires by (pressurized with nitrogen) discharge outlet,
water mist. Water mist also has the capability to safety relief valve, water fill port, pressure indi-
block radiant heat to further prevent the spread or cator, and liquid level indicator. The water pres-
sure vessel meets the requirements as estab-
propagation of fire.
lished by DOT and/or ASME, section VIII.
Water mist provides a secondary function by
partially scrubbing the air of products of combus- The water control valve is operated by nitrogen
pressure between 75 and 125 psi. A solenoid
tion, thereby reducing the amount of toxic byprod-
mounted on the valve is energized open to per-
ucts and/or contaminants in the air caused by a fire
incident . mit nitrogen to open the closed water control
valve. The solenoid is time sequenced to delay
The water mist system is cycled on and off to opening the valve until pressurized water has
more efficiently control the fire and to minimize the arrived at the water control valve. The timing is
amount of water required for control. controlled by the fire control panel.

The Chemetron Water Mist fire protection sys- When water arrives at the water valve, the sole-
tem follows this sequence of operation (reference noid controlling the nitrogen will open the water
Figure 4): control valve, releasing pressurized water to the
water mist nozzles located downstream. The
+ The fire control panel initiates a signal to the valve will cycle on and off, based on the timing -
solenoid located on a 2400 psi nitrogen cylinder sequence established by fire tests performed at
valve, or the cylinder can be activated manually Factory Mutual.
CnEmETROn Application Bulletin
Fire System;
-
Power Generation Bulletin #0060 Page 5

. The water will be conveyed through the pipe to Before the turbine can be operated, any damp-
the individual water mist nozzles. A minimum ers or other shutdowns tripped by the water mist
pressure of 350 psi will be required at the most system must be reset to allow a proper flow of cool-
hydraulically remote nozzle. ing air or fuel, as the case may be.

Due to the very small diameter of the orifices in Instances have occurred where the fire started
the nozzle, it is important to provide a strainer with an explosion in the compartments and the
upstream of the nozzles to prevent orifice block- doors were blown open. If this is to be a design
age. For ease of maintenance, the strainer will basis, then it should be considered at the time of
be located just downstream of the water vessel. design, with water quantities and nozzle placement
designed to ensure fire control, even with the doors
The alarm circuit for the affected hazard must open.
be manually reset to be certain that operating per-
sonnel are aware of the discharge. The fire detec- The 1992 (or later) edition of NFPA No. 850,
tion circuit is also locked out until manually reset to Fire Protection for Electric Generating Plants,
avoid a possible second discharge in the event of a includes combustion turbines and is recommended
shorted detector or circuit. This does not prevent a as a reference source. Also recommended as a
second discharge by manual means if this should reference source is the 1996 (or later) edition of
be needed. NFPA No. 750, Installation of Water Mist Fire
Protection.
After a fire, the turbine, itself, must obviously be
checked to correct fuel leakage or whatever caused
L- the fire in the first place.

0 5 10 15 20 0 5 10 15 20 25 30
(O;;;;gG)
(STARTING) (SHUTDOWN)

Figure 7: Represents typical temperature curves during a test operating cycle for a turbine system
with a diesel starting engine.
NOTE: The nozzles have been carefully
positioned to avoid direct impingement of
water on the turbine casing.

y-WATER MIST NOZZLES

LFROM WATER MIST SKID

Figure 2
Water Mist Fire Protection System for
a Compartmentized Gas Turbine
CHEmETROn IsT Application Bulletin
Fire Systems
v
Power Generation Bulletin #0060 Page 7

3,-O TYP
w 2 NOZZLES 1 NOZ. - I
FROM WATER
MIST SKID

ALL PIPE ESTIMATED


IS SCHEDULE 40
STAINLESS

ALL PIPE TO BE
3/8 UNLESS
OTHERWISE NOTED
-) 1 NOZ. 2 NOZZLES -
ALL NOZZLES

S-0 TYP v------- w


TO BE 3/8

Figure 3
Isometric View Plan View
260 cubic meter (9,175 cu. ft.) turbine enclosure. Room size: 24 feet square x 16 feet high.

This typical turbine enclosure has a 20 minute wind-down time and requires approximately 94
gallons of water and six nozzles as shown in the above diagram. The required flow rate for
each nozzle would be 1.87 GPM @ 350 psi. The complete on/off cycle time to extinguish this
type of fire is 4.25 minutes and requires a minimum of approximately 30 gallons of water.

Factory Mutual requires 20 minutes of fire protection to maintain the fire protection for the
duration of the wind-down period, but will allow the amount of water to be reduced if the wind-
down time of a specific turbine is identified to be less than 20 minutes.
- - MIST NOZZLES

r 1
- -

SYSTEM RELEASED
___________

PORTABLE
WATER FILLING
I
I
I
I
I LEGEND
I
NC
WFA-WATER FLOW
I I ALARM
I I 1 FCV-FLOW CONTROL
I I VALVE
PCV-PRESSURE
I I CONTROL VALVE
I I LLI-LIQUID LEVEL
OUTLINE OF VALVE
I I I INDICATOR
S-SOLENOID
--- I I L-LOW PRESSURE
SWITCH
CONTROL SRV-SAFETY RELIEF
PANEL
VALVE
--- tlz
II II I
II II
- _-I

Figure 4
Water Mist Fire Protection System
Piping & Instrumentation Diagram

You might also like