Professional Documents
Culture Documents
Commercial
Real World
Applications
Applying the code in the real
world
Commercial Residential
Section Section
Area-weighted
U-factor and
SHGC
Calculations
Insulation
Materials and Controls
R-Values
The code official shall make the inspections set forth in these sections:
Footing & foundation (R-Value, location, thickness, depth)
Framing & Rough-in (Insulation types, values, location, installation;
fenestration properties and installation; air leakage controls)
Plumbing rough-in (Insulation types, values, protection, controls, heat
traps)
Mechanical rough-in (HVAC equipment type and size; controls, system
insulation, system and damper air leakage, required energy recovery
and economizers)
Electrical rough-in (lighting; components and controls; electric meter
for each dwelling unit)
Final Inspection (installation and operation of all building controls,
building commissioning documentation)
Low-energy Buildings Buildings or portions of buildings that are
Section C402.1.1
separated from remainder of building by building
thermal envelope assemblies complying with C402
are exempt from the Envelope provisions if:
Peak design rate of energy < 3.4 Btu/h/ft2 or 1.0
Low Energy Use Buildings
watt/ft2 of floor area for space conditioning purposes,
OR
Those portions or building that do not contain
conditioned space, OR
Greenhouses
Indirect heated/cooled =
communicates through openings with conditioned spaces
separated from conditioned spaces by uninsulated walls, floors or ceilings
or contain uninsulated ducts, piping or other sources of heating or cooling.
Onsite Renewables
Solar Thermal/More Efficient SWH
Climate Zones
2015 IECC - Chapter 3
ROOFS
4 5
Climate 1 2 3 Except And 6 7 8
Zone
Marine Marine 4
Insulation
entirely R- R- R- R- R- R- R- R-
R-20ci R-25ci R-25ci R-25ci R-25ci R-25ci R-35ci R-35ci
above 30ci 30ci 30ci 30ci 30ci 30ci 35ci 35ci
deck
Metal
buildings R- R- R- R- R- R- R- R-
a, b
R-19+ R-19+ R-19+ R-19+ R-19+ R-19+ 19+ 19+ 19+ 19+ 25+ 25+ 30+ 30+ R-30+ R-30+
R-11 LS R-11 LS R-11 LS R-11 LS R-11 LS R-11 LS R-11 R-11 R-11 R-11 R-11 R-11 R-11 R-11 R-11 LS R-11 LS
LS LS LS LS LS LS LS LS
Attic and
R-38 R-38 R-38 R-38 R-38 R-38 R-38 R-38 R-38 R-49 R-49 R-49 R-49 R-49 R-49 R-49
other
Roof R-Value
Insulation Completely Above Deck
Insulation considered
continuous (CI)
A2.3.2.2: For double-layer installations, the second rated R-value of insulation is for
insulation installed parallel to the purlins.
R- R-
R- R- R- R- R- R- R- R- R-
Mass 5.7c
5.7cic 5.7cic
R-7.6ci R-7.6ci
9.5ci R-9.5ci R-11.4ci R-15.2ci 25
25ci
i 11.4ci 13.3ci 13.3ci 15.2ci 15.2ci ci
R-
Metal R- R- R- R- R- R- 13 R-
R-13+ R- R-
13+ R-13+ 13+R- R-13+R- R-13+R- R-13+R- R-13+R- +R 13+R-
building 6.5c
6.5ci
6.5ci 13 ci
13+R- 13+R- 13+R- 13+R- 13+R- 13+R- - 19.5
13 ci 13 ci 13 ci 13 ci 13 ci 13 ci
i 13 ci 13 ci 13 ci 19.5 ci 13 ci
Whats the difference between metal building ci
Wood R-
13
Framed & +R
Other R- R- R- R- R- -
R-
13+ R-
R- R- R-
R- 13+R- 13+R- 13+R- R-13+R- 13+R- 15.
13+R-
R- 13+R- 13+R- R-13+R- R-13+R- R-13+R- 6ci
13+R- 13+R- 13+R- 7.5ci or 7.5ci 7.5ci 7.5ci or 7.5ci or 15.6c
3.8c 3.8ci
3.8ci or 3.8ci or 3.8ci or
3.8ci 3.8ci or 3.8ci or 3.8ci or or
i or R-
i or or R- or R- R- or R- or R- R-20+R- R- R-
R-20 R-20 R-20 R-20 R-20 R-20 20+R-
R- 20 20 20+R- 20+R- 20+R- 3.8 ci 20+R- 20
10 ci
20 +R
3.8 ci 3.8 ci 3.8 ci 3.8 ci
-
10
ci
Wall R-Value
Metal Building, Metal Frame, Wood and Other
4
Climate 5
1 2 3 Except 6 7 8
Zone And Marine 4
Marine
Below
grade NR NR NR NR NR NR NR R-7.5ci R-7.5ci R-7.5ci R-7.5ci R-7.5ci R-10ci R-10ci R-10ci R-12.5ci
wall(d)
Below Grade Walls
Table C402.1.3 or Table C402.1.4
FLOORS
Climate 4 5
Zone
1 2 3 6 7 8
Except Marine And Marine 4
R- R- R- -
1 R-
Masse NR NR R-6.3ci R-8.3ci R-10ci R-10ci R-10ci R-10.4ci R-10ci R-12.5ci R-15ci 5 16.7ci
12.5ci 12.5ci 16.7ci c
i
Joist/ R
-
Framing
NR NR R-30 R-30 R-30 R-30 R-30 R-30 R-30 R-30 R-30 R-30f R-30f R-30f 3
0
R-30f
f
Floors Over Outdoor Air or
Unconditioned Space
Section C402.2.4
Joist/Framing (Steel/Wood)
Insulation installed between
framing
Mass Floors
Materials weighing (of floor
surface area)
35 lbs/ft2, or
25 lbs/ft2 if material weight is
120 lbs/ft3
Insulation installed continuously
SLAB-ON GRADE
FLOORS
4 5
Climate Zone 1 2 3 6 7 8
Except Marine And Marine 4
NO!
Chapter 5 Prescriptive Approach
Compliance
OPAQUE DOORS
4 5
Climate Zone 1 2 3 Except And Marine 6 7 8
Marine 4
R- R- R- R- R- R- R-
Nonswinging R-4.75 R-4.75 R-4.75 R-4.75 R-4.75 R-4.75 R-4.75 R-4.75 R-4.75
4.75 4.75 4.75 4.75 4.75 4.75 4.75
What
Happened
Not based To
on frame Climate
types
Zone
8?
Vertical Fenestration Requirement
Section C402.4.1 Prescriptive (Max area)
Percentage of Vertical
Fenestration Area to Gross Wall
Area
Allowed up to 30% maximum of
above grade wall
In Climate Zones 1-6, up to
40% maximum of above
grade wall with daylighting
controls
Vertical Fenestration Requirement
Section C402.4.1
No less than 25% of the net floor area is within a daylight zone
in building > 3 stories above grade
40%
In certain types of enclosed spaces > 2,500 ft2 in floor area directly
under a roof with > 75% of ceiling area with ceiling height > 15 ft.
total daylight zone under skylights to not be < the floor area and provide one
of the following
Minimum of 3% of skylight area to daylight zone where all skylights have a VLT at least 0.40
OR
Provide a minimum skylight effective aperture of at least 1%
Exceptions:
Climate Zones 6-8
Spaces with LPDs < 0.5 W/ft2
Documented shaded spaces
Daylight area under rooftop monitors is > 50% of floor area
Spaces where total area minus area of daylight zones adjacent to
vertical fenestration is < 2,500 ft2 and lighting is controlled per C405.2.5
(Exterior Lighting Controls)
Mandatory Requirements IECC Commercial
Envelopes
Air Leakage
Air barriers
Fenestration air leakage
Rooms Containing Fuel-burning Appliances
Air intakes, exhaust openings, stairways and shafts
Loading dock weatherseals
Vestibules
Recessed lighting
Air Barriers and Construction
Section C402.5.1.1
Air Leakage
Section C402.5
Two ways to comply with air barrier requirements:
Materials C402.5.1.2.1 OR Assemblies C402.5.1.2.2
Materials with air permeance 0.004 cfm/ft2 under pressure differential of 0.3 in. w.g. tested in accordance with
ASTM E 2178
Material Thickness
(minimum)
These materials meet this requirement: Plywood 3/8 in.
Oriented strand board 3/8 in.
Extruded polystyrene insulation board in.
Foil-faced urethane insulation board in.
Closed cell spray foam minimum density of 1.5 pcf 1-1/2 in.
Open cell spray foam density between 0.4 and 1.5 pcf 4.5 in.
Exterior gypsum sheathing or interior gypsum board in.
Cement board in.
Built up roofing membrane
Modified bituminous roof membrane
Fully adhered single-ply roof membrane
A Portland cement/sand parge, stucco, or gypsum plaster 5/8 in.
Cast-in-place and precast concrete
Sheet metal or aluminum
Solid or hollow masonry constructed of clay or shale masonry units
C402.4.1.2.2 Air barrier assemblies
54
Getting air barriers in all of the right places can be tricky
f
r
o
m
o
u
t
s
i
d
e
2013 Colorado Code Consulting, LLC 60
2013 Colorado Code Consulting, LLC 61
Foam as an air sealant?
Air barrier cant be an after thought
Demand control ventilation (DCV): a ventilation system capability that provides for the automatic
reduction of outdoor air intake below design rates when the actual occupancy of spaces served by the
system is less than design occupancy.
Demand Controlled Ventilation IECC
Section C403.2.5.1 (Mandatory)
Exceptions:
Systems with energy recovery per C403.2.6
Multiple zone systems without direct digital control of single zones
communicating with central control panel
Systems with design outdoor airflow < 1,200 cfm
Spaces where supply airflow rate minus any makeup or outgoing transfer
air requirement < 1,200 cfm
Ventilation provided for process loads only
Mechanical Systems Commissioning and Completion
Section C403.2.11 (Mandatory) IECC
Mechanical system to be commissioned and completed per Section C408.2
1A, 1B No requirement
2A, 2B, 3A, 3B, Economizers on individual DX cooling units
3C, 4A, 4B, 4C, 54,000 Btu/ha
5A, 5B, 5C, 6A,
6B, 7, 8 Economizer (usually central water economizer)
on any chilled water cooling unit if total cooling
meets table C403.3 limits
Total supply capacity of all fan-cooling units not provided with economizers shall not exceed 20% of the total
supply capacity of all fan-cooling units in the building or 300,000 Btu/h, whichever is greater, unless
otherwise excepted
Heat Recovery for Service Hot Water Heating
Section C403.4.5 IECC Condenser heat recovery required for heating/reheating
CW In
of SWH provided:
HW In Facility operates 24 hours/day
Storage Tank Total installed heat capacity of the heat rejection of
water-cooled systems >6,000,000 Btu/hr
Design SWH load >1,000,000 Btu/hr
Condenser
Cooling Tower
Water Loop Exceptions:
To Chiller Condenser or Recovered heat is used for space heating or when SWH
Water-Loop Heat Pump is provided by renewables or site recovered energy
System
sources
Concept: If there is waste heat in the building, it is to be used for potable water.
Service Water Heating IECC
Section C404
Table C404.2 Minimum Performance of Water-Heating Equipment
Efficient Piping(C404.5)
SWH Commissioning(C404.11)
Efficient Heated Water Supply Piping IECC
Section C404.5
For piping from the nearest source of heated water (from the water heater or
from the recirculation or trace heated loop) to fixture requires either maximum
pipe length (C404.5.1) or maximum pipe volume (C404.5.2) and has maximum
flow rated by size
Flow rate through piping should be 0.5 gpm
Flow rate through 5/16 piping should be 1.0 gpm
Flow rate through 3/8 piping should be 1.5 gpm
Exemptions:
Security or emergency areas that must be continuously lighted
Interior exit stairways, interior exit ramps and exit passageways Intent: Allow occupants to control
Emergency egress lighting normally off unneeded lighting!
Occupant Sensor Controls
Sections C405.2.1, C405.2.1.1
Occupancy sensors are required in:
Classrooms/lecture/training rooms
Conference/meeting/multipurpose rooms
Lounges
Employee lunch and break rooms
Private offices
Restrooms
Storage rooms
Janitorial closets
Locker rooms
Other spaces < 300 ft2 enclosed by floor-to-ceiling height partitions
Warehouses
Occupancy sensor function (other than for warehouses):
Automatically turn lights off within 30 minutes of occupants leaving space
Either manual-on or controlled to automatically turn lighting on to not more than 50% power
Incorporate a manual control to allow occupants to turn off the lights
Time-switch Controls
Section C405.2.2
Must identify the area served by the lights and indicate their use
Daylight-responsive Controls
Section C405.2.3
Definition: A device or system that provides automatic control of electric
light levels based on the amount of daylight in a space
Required to control lighting in spaces with >150 watts of general lighting:
Sidelight daylight zones
Toplight daylight zones
Exceptions:
Health care facilities where patient care is directly provided
Dwelling units and sleeping units
Lighting required for specific application control per C405.2.4
Sidelight daylight zones on 1st floor above grade in Group A-2 and Group M
occupancies
Specific Application Controls
Section C405.2.4
$
Nonvisual applications, plant growth and food warming
$
Equipment for sale or educational demonstrations
$
Interior Lighting Power Allowance IECC
Section C405.4.2
Two methods to determine allowance:
Building Area Method
Floor area for each building area type x value for the area
area defined as all contiguous spaces that accommodate or are
associated with a single building area type as per the table
When used for an entire building, each building area type to be treated
as a separate area
Space-by-Space Method
Floor area of each space x value for the area
Then sum the allowances for all the spaces
Tradeoffs among spaces are allowed
Building Area Method IECC
Table C405.4.2(1)
Building Area Type LPD (w/ft2)
Automotive facility 0.8
Convention center 1.01
Courthouse 1.01
Dining: bar lounge/leisure 1.01
Dining: cafeteria/fast food 0.9
Dining: family 0.95
Dormitory 0.57
Exercise center 0.84
Fire station 0.67
Gymnasium 0.94
(partial table)
Space-By-Space Method IECC
Table C405.4.2(2)
Common Space-by-Space Types LPD (w/ft2)
Atrium First 40 feet in height 0.03 per foot in total height
Atrium Above 40 feet in height 0.40+0.02 per foot in total height
Audience/seating area permanent
In an auditorium 0.63
In a convention center 0.82
In a gymnasium 0.65
In a motion picture theater 1.14
In a penitentiary 0.28
In a performing arts theater 2.43
In a penitentiary 1.34
(partial table)
Additional Interior Lighting Power Allowance = 500 watts
Additional Interior Lighting Power IECC +
Section C405.4.2.2.1
(Retail Area 1 x 0.6 W/ft2) +
(Retail Area 2 x 0.6 W/ft2) +
(Retail Area 3 x 1.4 W/ft2) +
(Retail Area 4 x 2.5 W/ft2),
Where:
Retail Area 1 = the floor area for all products not
listed in Retail Area 2, 3 or 4.
Retail Area 2 = the floor area used for the sale of
vehicles, sporting goods and small electronics.
Retail Area 3 = the floor area used for the sale of
furniture, clothing, cosmetics and artwork.
Retail Area 4 = the floor area used for the sale of
jewelry, crystal, and china.
Additional Interior Lighting Power Allowance = 500 watts + (Retail Area 1
0.6 W/ft2) + (Retail Area 2 0.6W/ft2) + (Retail Area 3 1.4 W/ft2) +
(Retail Area 4 2.5 W/ft2).
where:
Retail Area 1 = The floor area for all products not listed in Retail Area 2, 3 or 4.
Retail Area 2 = The floor area used for the sale of vehicles, sporting goods and small electronics.
Retail Area 3 = The floor area used for the sale of furniture, clothing, cosmetics and artwork.
Retail Area 4 = The floor area used for the sale of jewelry, crystal and china.
Office - Example
2014 Colorado Code Consulting, LLC 107
Museum:
40,000 ft2 at 1.02 w/ft2 =
40,800 w
Cafeteria:
10,000 ft2 at .9 w/ft2 = A Portion of Table C405.4.2(1)
9000w LIGHTING POWER DENSITY
Building Area Type (W/ft2)
Retail: Museum 1.02
5,000 ft2 at 1.26 w/ft2 = Cafeteria .9
6300 w Retail 1.26
Total watts allowed =
56,100 w
(partial table)
Museum:
Lobby 2000 at .9w/ft2 =1800w
Restrooms (multiple) 4000 at .98w/ft2 =3920w
Enclosed offices 1000 at 1.11w/ft2 =1110w
Gift shop/Sales area 5000 at 1.6w/ft2 =8000w
Storage 1000 at .8w/ft2 =800w
General exhibit area 30,000 at 1.05w/ft2 =31,500w
Restoration area 3,000 at 1.02w/ft2 =3060w
Cafeteria:
Dining area 7500 at .9w/ft2 =6,750w
Storage area 1000 at .63w/ft2 =630w
Food prep area 1500 at 1.21w/ft2 =1815w
Total watts allowed = 56,385w
Connected Exterior Lighting Power must not exceed Exterior Lighting Power Allowance
except where approved because of historical, safety, signage or emergency
considerations:
1. Calculate exterior lighting power allowance
Lighting power densities by exterior function and by applicable lighting zone
2. Calculate proposed connected lighting power
Wattage calculation rules
Exempted lighting
3. Compare values: proposed wattage must be less than or equal to allowed wattage
Exemptions from Exterior Calculation
Section C405.5.1
The following lighting does not need to be included in the proposed lighting calculation:
Specialized signal, directional, and marker lighting associated with transportation
Lighting for theatrical purposes, including performance, stage, film production, and video production
Temporary lighting
Lighting for industrial production, material handling, transportation sites, and associated storage areas
Lighting used to highlight features of public monuments and registered historic landmark structures or buildings
Exterior Lighting Power Limits
Section C405.5.1
What areas are covered under exterior lighting
allowances?
Tradable surfaces
Common exterior lighted needs that can be traded
for other needs
For example, wattage allowed for parking lot lighting
can be traded and used for canopy lighting
Nontradable surfaces
Less common exterior lighted needs that cannot be
traded for other needs
These applications have more specific security or task
illuminance needs
Tradable Surfaces
Uncovered parking lots and areas
Walkways (under and over 10 feet wide)
Stairways
Pedestrian tunnels
Main building entrances and exits
Other doors
Entry canopies
Free-standing and attached sales canopies
Open sales areas
Street frontage sales areas
Nontradable Surfaces
Building facades
Automated teller machines and night depositories
Entrances and gatehouse inspection stations at guarded facilities
Loading areas for law enforcement, fire, ambulance and other emergency vehicles
Drive-up windows/doors
Parking near 24-hour retail entrances
Exterior Lighting Zones IECC
Table C405.5.2(1)
Power allowances are listed by lighting zone
1 Developed areas of national parks, state parks, forest land, and rural
areas
Drive-up window/doors 400 W per drive-through 400 W per drive-through 400 W per drive-through 400 W per drive-through
Exterior Lighting Power Example
Parking Lot
121
Example Calculation
Parking : 10,000 ft2 at 0.13 w/ft2 = 1,300 w
Canopy: 100 ft2 at 0.4 w/ft2 = 40 w
Walkway: 200 ft at 1.0 w/ft = 200 w
Total = 1540 w
1. The daylight zone shall extend laterally and longitudinally beyond the edge of the roof fenestration
assembly to the nearest obstruction that is taller than 0.7 times the ceiling height, or up to 0.7 times the
ceiling height, whichever is less, as indicated in Figure C405.2.3.3.
2. No building or geological formation blocks direct sunlight from hitting the roof fenestration
assembly at the peak solar angle on the summer solstice.
3. Where located in existing buildings, the product of the visible transmittance of the roof
fenestration assembly and the area of the rough opening of the roof fenestration assembly divided by the
area of the daylight zone is not less than 0.008.
ComCheck Basics
COMcheck
2015 Colorado Code Consulting, LLC 146
E
N
V
E
L
O
P
E
C
O
M
P
L
I
A
N
C
E
ComCheck
Existing Buildings Chapter 5 -- NEW
Section C501 - General
Addition to:
Existing Building
Building System
Or portion thereof
Must conform to the code as it relates to new construction
without requiring the unaltered portion of the existing
building or system to comply.
If > 30% for total building or addition alone, must comply with
C402.4.1.1 Increased Vertical Fenestration Area with Daylight
Responsive Control for the addition only
Additions that result in total building vertical glass >40% must comply
with C407 Total Building Performance
Existing Buildings
Section C502 - Additions
Skylight Area: new skylight area that results in total building skylight area of < 3% complies
with C402.4, including:
Maximum 3% of gross roof area
Meet U-Factor of prescriptive table
Minimum skylight fenestration area
Lighting controls in daylight zones under skylights
Haze factor
If > 3% for total building or addition alone, must comply with C402.4.1.2 Increased Skylight
Area with Daylight Responsive Control for addition only
Additions that result in total building skylight area >5% must comply with C407 Total Building
Performance
Existing Buildings
Section C502 - Additions
Exceptions:
Storm windows over existing fenestration
Surface-applied window film installed on existing single pane
Exposed, existing ceiling, wall or floor cavities if already filled with insulation
Where existing roof, wall or floor cavity isnt exposed
Roof recover
Reroofing for roofs where neither sheathing nor insulation exposed
Insulate above or below the sheathing
Roofs without insulation in the cavity
Sheathing or insulation is exposed
Lighting alterations if:
<50% of luminaries in a space are replaced
Only bulbs and ballasts within existing luminaries are replaced (provided installed interior lighting power isnt
increased)
Existing Buildings
Section C503.2 Alterations - Change in
space conditioning
Examples:
Converting part of an unconditioned warehouse to
office space
Shell building tenant build-out
Existing Buildings
Section C504 - Repairs
Existing Buildings
Section C504 - Repairs
Section C505 Change in Occupancy
Thank you!