Professional Documents
Culture Documents
2
1 IP65, Type 4X heavy-duty construction 5
6
nonmetallic body, gasketed lens and unique
labyrinth lens locking system
dust-tight, water-tight and moisture-tight
corrosion and impact-resistant
ideal for outdoor applications
1
2 electronic ballast
lower ambient temperatures suitability
to -18C
2
highpower factor ballast (+90%)
allows for more luminaires per circuit
3 standard T8 bi-pin lampsmost
common lamp used; energy-efficient
and cost-effective
4
4 removable lenshinged on both sides
for easy installation and maintenance
5 easy wiring and installation
four 25 mm entries. Two Myers 34"
NPT adapter hubs supplied standard
suitable for through-feed or tandem
applications
extra-large wire well eliminates need for
separate junction boxes 3
6 worldwide suitability
NEC/CEC: Class I, Zone 2 and Division 2 areas
IEC/CENELEC certified luminaires available.
Consult factory.
ORDERING INFORMATION
HUB SIZE* LAMP DESCRIPTION VOLTAGE/HZ. CATALOG NO.
34" NPT 17 W T8, Rapid Start2 lamps 120277 V, 60 Hz. nLLK98 2217/UNV
34" NPT 32 W T8, Rapid Start2 lamps 120277 V, 60 Hz. nLLK98 4232/UNV
*25 mm entriessupplied with two Myers STM2 25 mm to 34" NPT adapter hubs.
ACCESSORIES
DESCRIPTION CATALOG NO.
SW13 hexagon key (for maintenance and lamp replacement) 3 2485 000 005
Myers 25 mm to 34" NPT adapter hub STM2
MOUNTING ACCESSORIES
QTY. PER
TYPE CORROSION PROTECTION PIPE DIN OUTER DIA. LUMINAIRE CATALOG NO.
Eyebolt A2 Galvanized 2 2 2480 002 000
Hexagon Screw S4 (to attach Nickel Chromium 2 2 2480 054 000
ceiling mounting bracket or
pipe clamp to luminaire)
Ceiling Mounting Bracket D92 Nickel Chromium 2 2 2480 092 000
Pipe Clamp R12 Hot Galvanized 114" 3842 mm 2 2 2480 462 000
Pipe Clamp R14 Nickel Chromium 114" 3842 mm 2 2 2480 464 000
Pipe Clamp R22 Hot Galvanized 11 2" 4751 mm 2 2 2480 472 000
Pipe Clamp R32 Hot Galvanized 2" 5660 mm 2 2 2480 482 000
3
PHOTOMETRIC DATA
CANDELAS Coefficients of Utilization
CANDLEPOWER DISTRIBUTION (in Candelas) PLANE
DEGREES
PLANE A-A PLANE B-B A-A Effective Floor Cavity Reflectance 20%
0 - 180 90 - 270
0 1215 1215 Room Cavity Ratio
90 10 1210 1185 Eff. Wall Work 1 2 3 4 5 6 7 8 9
20 1189 1120 Ceil.
30 1175 1014
40 1158 872 PLANE 70* 20* 41 49 55 61 65 70 74 77 80
80
50 1107 695 B-B 80* 50* 20* 30 38 44 50 55 62 67 71 75
120 60 998 487 30* 20* 23 30 36 43 48 55 61 65 70
70 868 270 10* 20* 18 25 30 37 42 50 56 61 66
240 70 80 566 83
90 440 70* 20* 40 47 53 58 62 68 71 74 77
360 100 380 70* 50* 20* 29 37 42 49 54 60 65 68 72
110 30* 20* 22 30 35 42 47 54 59 64 68
480 60 120 10* 20* 18 24 30 36 42 49 54 59 64
130
600 140 50* 20* 27 35 40 46 50 56 61 64 68
150 50* 30* 20* 21 28 34 40 45 51 56 60 64
720 160
50 10* 20* 17 24 29 35 40 47 52 57 61
170
840 180 50* 20* 26 33 37 43 47 53 57 60 64
30* 30* 20* 20 27 32 38 43 49 53 57 61
960 10* 20* 17 23 28 34 39 45 50 54 58
Photometric data developed using two
1080 F32T8/35K lamps (2850 lumens each). For 50* 20* 24 31 35 41 45 50 54 57 60
the 17 W nLLK, use a 0.47 multiplier (two 10* 30* 20* 20 26 31 36 41 46 51 54 68
0
1200 10 20 30 40 10* 20* 16 22 27 33 37 43 48 52 55
17 W T8 lamps (1350 lumens each)) with the
candle power distribution chart. Multiplier is 0* 0* 20* 14 20 25 31 35 41 46 49 53
not used with Coefficients of Utilization table.
* Percent Reflectance
TEMPERATURE PERFORMANCE
Minimum Starting Temperature: -18C
CLASS I, DIV. 2 CLASS II, DIV. 1 (CEC) SUPPLY WIRE
WATTS AMBIENT (CLASS I, ZONE 2) CLASS II, DIV. 2 (NEC) TEMP C
Two 17 W T8 lamps 40C T4 T6 60
Two 32 W T8 lamps 40C T4 T6 60 Eyebolt
76017 W 46
136032 W
nLLK Luminaire
188