CALCULO DE CAIDA DE TENSION

S.E. N 1

LOCALIDAD : CHACASYPACHAPAQUE CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 55 15 31 0.80 1.60 6.20 7.80 2x16+16/25 14.09 2.02 5.05 19.14 4.09 4.31 4.306 0.979 0.98
2 44 10 16 0.40 0.80 3.20 4.00 2x16+16/25 7.27 1.01 3.03 10.30 4.09 1.85 6.160 0.421 1.40
3 45 6 6 0.40 0.40 1.20 1.60 1x16+16/25 5.45 2.02 2.02 7.47 3.27 1.10 7.261 0.500 1.90

1 0.98
1.1 30 7 7 0.00 0.00 1.40 1.40 1x16+16/25 6.36 0.00 0.00 6.36 3.27 0.62 0.625 0.284 1.26

2 1.40
2.1 32 5 5 0.00 0.00 1.00 1.00 1x16+16/25 4.55 0.00 0.00 4.55 3.27 0.48 0.476 0.216 1.62

CIRCUITO : C2

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 52 3 17 0.00 1.20 3.40 4.60 2x16+16/25 7.73 0.00 6.06 13.79 4.09 2.93 2.932 0.666 0.67
2 106 5 14 0.00 1.20 2.80 4.00 2x16+16/25 6.36 0.00 6.06 12.42 4.09 5.39 8.319 1.224 1.89
3 85 3 9 0.80 1.20 1.80 3.00 1x16/25 8.18 4.04 6.06 14.24 3.27 3.96 12.280 1.801 3.69
4 86 2 6 0.40 0.40 1.20 1.60 1x16/25 5.45 2.02 2.02 7.47 3.27 2.10 14.383 0.956 4.65
5 75 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.89 15.276 0.406 5.05
6 75 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.45 15.722 0.203 5.26

1 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : CHACASYPACHAPAQUE CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C2

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 87 1 16 0.00 0.00 3.20 3.20 2x16+16/25 7.27 0.00 0.00 7.27 4.09 2.59 2.588 0.588 0.59
2 80 1 15 0.00 0.00 3.00 3.00 1x16/25 13.64 0.00 0.00 13.64 3.27 3.57 6.157 1.622 2.21
3 84 3 14 0.00 0.00 2.80 2.80 1x16/25 12.73 0.00 0.00 12.73 3.27 3.50 9.655 1.590 3.80
4 77 4 11 0.00 0.00 2.20 2.20 1x16/25 10.00 0.00 0.00 10.00 3.27 2.52 12.175 1.145 4.95
5 79 4 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.64 13.820 0.748 5.69
6 76 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.68 14.498 0.308 6.00

3 3.80
3.1 52 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.46 0.464 0.211 4.01

4 4.95
4.1 45 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.27 0.268 0.122 5.07

CIRCUITO : C2R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 2 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 0.08 0.080 0.037 0.04
2 45 1 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 0.94 1.017 0.426 0.46
3 45 2 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.80 1.820 0.365 0.83
4 56 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.67 2.487 0.303 1.13

2 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : CHONDOBAMBA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 84 1 10 0.00 0.00 2.00 2.00 1x16/25 9.09 0.00 0.00 9.09 3.27 2.50 2.499 1.136 1.14
2 83 3 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 2.22 4.721 1.010 2.15
3 160 3 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 2.86 7.576 1.298 3.44
4 88 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.79 8.361 0.357 3.80
5 84 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.50 8.861 0.227 4.03

2 2.15
2.1 80 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.48 0.476 0.216 2.36

3 3.44
3.1 84 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.25 0.250 0.114 3.56

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 84 2 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 2.00 1.999 0.909 0.91
2 85 1 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.52 3.516 0.690 1.60
3 85 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.26 4.780 0.575 2.17
4 85 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.76 5.539 0.345 2.52
5 86 1 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.51 6.050 0.233 2.75
6 86 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.26 6.306 0.116 2.87

3 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : CHONDOBAMBA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 81 6 12 0.00 0.00 2.40 2.40 1x16/25 10.91 0.00 0.00 10.91 3.27 2.89 2.891 1.314 1.31
2 63 4 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.12 4.016 0.511 1.83
3 59 1 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.35 4.367 0.160 1.98
4 60 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 4.545 0.081 2.07

1 1.31
1.1 69 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.82 0.821 0.373 1.69
1.2 76 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.45 1.273 0.206 1.89

1 1.31
1.0.1 76 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.23 0.226 0.103 1.42

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 2 14 0.00 0.00 2.80 2.80 1x16/25 12.73 0.00 0.00 12.73 3.27 0.12 0.125 0.057 0.06
2 74 5 12 0.00 0.00 2.40 2.40 1x16/25 10.91 0.00 0.00 10.91 3.27 2.64 2.766 1.201 1.26
3 80 1 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.67 4.432 0.757 2.01
4 80 2 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.43 5.860 0.649 2.66
5 82 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.98 6.836 0.443 3.11

2 1.26
2.1 82 1 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.49 0.488 0.222 1.48
2.2 81 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.24 0.729 0.110 1.59

2 1.26
2.0.1 80 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.24 0.238 0.108 1.37

4 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SANJUANBOSESDEVISTAALEGRE CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 2 21 0.00 0.80 4.20 5.00 1x16/25 19.09 0.00 4.04 23.13 3.27 0.23 0.227 0.103 0.10
2 30 2 19 0.00 0.80 3.80 4.60 1x16/25 17.27 0.00 4.04 21.31 3.27 2.09 2.319 0.951 1.05
3 28 5 17 0.80 0.80 3.40 4.20 1x16/25 15.45 4.04 4.04 19.49 3.27 1.79 4.105 0.812 1.87
4 40 2 12 0.00 0.00 2.40 2.40 1x16/25 10.91 0.00 0.00 10.91 3.27 1.43 5.533 0.649 2.51
5 32 5 10 0.00 0.00 2.00 2.00 1x16/25 9.09 0.00 0.00 9.09 3.27 0.95 6.485 0.433 2.95
6 20 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.30 6.782 0.135 3.08
7 40 2 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.36 7.139 0.162 3.25
8 30 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.09 7.228 0.041 3.29

3 1.87
3.1 20 0 2 0.40 0.80 0.40 1.20 1x16/25 1.82 2.02 4.04 5.86 3.27 0.38 0.383 0.174 2.04
3.2 13 2 2 0.40 0.40 0.40 0.80 1x16/25 1.82 2.02 2.02 3.84 3.27 0.16 0.547 0.074 2.11

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 63 5 13 0.00 0.00 2.60 2.60 1x16/25 11.82 0.00 0.00 11.82 3.27 2.44 2.436 1.107 1.11
2 60 2 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 1.43 3.864 0.649 1.76
3 60 2 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.07 4.935 0.487 2.24
4 60 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.71 5.649 0.324 2.57
5 60 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.54 6.184 0.243 2.81
6 25 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.15 6.333 0.068 2.88

1 1.11
1.1 50 2 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.45 0.446 0.203 1.31
1.2 50 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.15 0.595 0.068 1.38

5 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SANJUANBOSESDEVISTAALEGRE CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 43 3 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 1.02 1.023 0.465 0.47
2 40 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.59 1.618 0.270 0.74
3 110 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.98 2.600 0.446 1.18

6 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : UPUCRO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 224 2 11 0.00 0.00 2.20 2.20 1x16/25 10.00 0.00 0.00 10.00 3.27 7.33 7.329 3.331 3.33
2 98 3 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 2.62 9.953 1.193 4.52
3 67 1 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.20 11.149 0.544 5.07
4 67 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.00 12.145 0.453 5.52
5 134 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 1.20 13.341 0.544 6.06
6 31 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.18 13.525 0.084 6.15

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 43 1 1 0.40 0.40 0.20 0.60 1x16/25 0.91 2.02 2.02 2.93 3.27 0.41 0.412 0.187 0.19

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 79 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.17 1.175 0.534 0.53
2 162 2 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 1.45 2.621 0.657 1.19
3 121 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.36 2.980 0.164 1.35

7 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : UPUCRO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 262 2 4 0.00 0.40 0.80 1.20 1x16/25 3.64 0.00 2.02 5.66 3.27 4.85 4.849 2.204 2.20
2 81 1 2 0.00 0.40 0.40 0.80 1x16/25 1.82 0.00 2.02 3.84 3.27 1.02 5.866 0.462 2.67
3 50 1 1 0.40 0.40 0.20 0.60 1x16/25 0.91 2.02 2.02 2.93 3.27 0.48 6.346 0.218 2.88

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 64 1 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.95 0.952 0.433 0.43
2 73 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.87 1.820 0.395 0.83
3 137 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 1.22 3.043 0.556 1.38

1 0.43
1.1 68 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.20 0.202 0.092 0.52

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 2 10 0.00 0.00 2.00 2.00 1x16/25 9.09 0.00 0.00 9.09 3.27 0.09 0.089 0.041 0.04
2 60 2 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 1.43 1.517 0.649 0.69
3 73 2 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.30 2.820 0.592 1.28
4 56 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.67 3.486 0.303 1.58
5 58 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.35 3.831 0.157 1.74

2 0.69
2.1 122 1 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.73 0.726 0.330 1.02
2.2 71 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.21 0.937 0.096 1.12

8 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : COCHA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 222 4 12 0.40 0.40 2.40 2.80 1x16/25 10.91 2.02 2.02 12.93 3.27 9.39 9.392 4.269 4.27
2 60 3 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 1.43 10.819 0.649 4.92
3 58 1 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.86 11.682 0.392 5.31
4 55 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.65 12.336 0.297 5.61
5 137 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 1.22 13.559 0.556 6.16
6 60 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.36 13.916 0.162 6.33

1 4.27
1.1 50 1 4 0.00 0.40 0.80 1.20 1x16/25 3.64 0.00 2.02 5.66 3.27 0.93 0.925 0.421 4.69
1.2 50 1 3 0.00 0.40 0.60 1.00 1x16/25 2.73 0.00 2.02 4.75 3.27 0.78 1.702 0.353 5.04
1.3 60 2 2 0.40 0.40 0.40 0.80 1x16/25 1.82 2.02 2.02 3.84 3.27 0.75 2.456 0.343 5.39

2 4.92
2.1 60 2 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.54 0.535 0.243 5.16
2.2 60 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 0.714 0.081 5.24

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 0 10 0.40 0.40 2.00 2.40 1x16/25 9.09 2.02 2.02 11.11 3.27 0.11 0.109 0.050 0.05
2 39 2 10 0.00 0.00 2.00 2.00 1x16/25 9.09 0.00 0.00 9.09 3.27 1.16 1.269 0.527 0.58
3 86 3 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 2.05 3.316 0.930 1.51
4 145 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 2.16 5.472 0.980 2.49
5 86 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.77 6.240 0.349 2.84
6 62 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.37 6.608 0.168 3.00

4 2.49
4.1 40 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.12 0.119 0.054 2.54

9 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : PAO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 7 0.80 1.20 1.40 2.60 1x16+16/25 6.36 4.04 6.06 12.42 3.27 0.12 0.122 0.055 0.06
2 34 2 6 0.00 0.40 1.20 1.60 1x16+16/25 5.45 0.00 2.02 7.47 3.27 0.83 0.954 0.378 0.43
3 54 1 4 0.00 0.40 0.80 1.20 1x16+16/25 3.64 0.00 2.02 5.66 3.27 1.00 1.953 0.454 0.89
4 28 3 3 0.40 0.40 0.60 1.00 1x16+16/25 2.73 2.02 2.02 4.75 3.27 0.43 2.388 0.198 1.09

2 0.43
2.1 60 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 0.178 0.081 0.51

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 53 1 7 0.40 0.80 1.40 2.20 1x16+16/25 6.36 2.02 4.04 10.40 3.27 1.80 1.804 0.820 0.82
2 27 1 6 0.40 0.40 1.20 1.60 1x16+16/25 5.45 2.02 2.02 7.47 3.27 0.66 2.465 0.300 1.12
3 150 1 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 2.23 4.695 1.014 2.13
4 50 3 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.59 5.290 0.270 2.40
5 70 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.21 5.499 0.095 2.50

4 2.40
4.1 40 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.12 0.119 0.054 2.46

10 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : QUILLO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 73 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.87 0.869 0.395 0.39
2 70 2 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.62 1.493 0.284 0.68
3 70 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.21 1.701 0.095 0.77

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 35 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.31 0.312 0.142 0.14

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 143 3 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 2.98 2.978 1.353 1.35
2 83 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.99 3.965 0.449 1.80
3 82 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.49 4.453 0.222 2.02

1 1.35
1.1 70 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.21 0.208 0.095 1.45

11 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : QUILLO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 75 2 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.34 1.339 0.608 0.61
2 70 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.83 2.171 0.379 0.99
3 140 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 1.25 3.421 0.568 1.55

1 0.61
1.1 60 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 0.178 0.081 0.69

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 70 0 2 0.80 0.80 0.40 1.20 1x16/25 1.82 4.04 4.04 5.86 3.27 1.34 1.342 0.610 0.61
2 152 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.90 2.246 0.411 1.02

1 0.61
1.1 28 0 0 0.80 0.80 0.00 0.80 1x16/25 0.00 4.04 4.04 4.04 3.27 0.37 0.370 0.168 0.78

12 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1
OCULTAR
LOCALIDAD : SUCCHABAMBA OCULTAR CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )
SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 OCULTAR TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE OCULTAR SISTEMA: 440/220 V
OCULTAR
CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA FORMACION I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) DEL CONDUCTOR (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 61 5 9 0.00 0.40 1.80 2.20 M 1x16/25 8.18 0.00 2.02 10.20 3.27 2.04 2.036 0.926 0.93
2 131 2 4 0.00 0.40 0.80 1.20 M 1x16/25 3.64 0.00 2.02 5.66 3.27 2.42 4.461 1.102 2.03
3 58 2 2 0.40 0.40 0.40 0.80 M 1x16/25 1.82 2.02 2.02 3.84 3.27 0.73 5.189 0.331 2.36

1 0.93
1.1 59 3 5 0.00 0.00 1.00 1.00 M 1x16/25 4.55 0.00 0.00 4.55 3.27 0.88 0.877 0.399 1.32
1.2 180 2 2 0.00 0.00 0.40 0.40 M 1x16/25 1.82 0.00 0.00 1.82 3.27 1.07 1.948 0.487 1.81

2 2.03
2.1 60 1 1 0.00 0.00 0.20 0.20 M 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 0.178 0.081 2.11

13 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1
OCULTAR
LOCALIDAD : SUCCHABAMBA OCULTAR CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )
SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 OCULTAR TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE OCULTAR SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA FORMACION I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) DEL CONDUCTOR (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 1 9 0.00 0.00 1.80 1.80 M 1x16/25 8.18 0.00 0.00 8.18 3.27 0.08 0.080 0.037 0.04
2 68 1 8 0.00 0.00 1.60 1.60 M 1x16/25 7.27 0.00 0.00 7.27 3.27 1.62 1.698 0.736 0.77
3 68 1 7 0.00 0.00 1.40 1.40 M 1x16/25 6.36 0.00 0.00 6.36 3.27 1.42 3.114 0.644 1.42
4 46 1 6 0.00 0.00 1.20 1.20 M 1x16/25 5.45 0.00 0.00 5.45 3.27 0.82 3.935 0.373 1.79
5 60 3 5 0.00 0.00 1.00 1.00 M 1x16/25 4.55 0.00 0.00 4.55 3.27 0.89 4.828 0.406 2.19
6 90 2 2 0.00 0.00 0.40 0.40 M 1x16/25 1.82 0.00 0.00 1.82 3.27 0.54 5.363 0.243 2.44

3 1.42
3.1 61 1 1 0.00 0.00 0.20 0.20 M 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 0.181 0.082 1.50

5 2.19
5.1 60 1 1 0.00 0.00 0.20 0.20 M 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 0.178 0.081 2.28

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA FORMACION I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) DEL CONDUCTOR (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 145 1 4 0.00 0.00 0.80 0.80 M 1x16/25 3.64 0.00 0.00 3.64 3.27 1.73 1.725 0.784 0.78
2 68 1 3 0.00 0.00 0.60 0.60 M 1x16/25 2.73 0.00 0.00 2.73 3.27 0.61 2.332 0.276 1.06
3 90 2 2 0.00 0.00 0.40 0.40 M 1x16/25 1.82 0.00 0.00 1.82 3.27 0.54 2.867 0.243 1.30

1 0.78
1.1 81 1 1 0.00 0.00 0.20 0.20 M 1x16/25 0.91 0.00 0.00 0.91 3.27 0.24 0.241 0.110 0.89

14 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : CARHUA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 67 1 5 0.00 0.40 1.00 1.40 1x16+16/25 4.55 0.00 2.02 6.57 3.27 1.44 1.439 0.654 0.65
2 15 3 4 0.00 0.40 0.80 1.20 1x16+16/25 3.64 0.00 2.02 5.66 3.27 0.28 1.717 0.126 0.78
3 17 1 1 0.40 0.40 0.20 0.60 1x16+16/25 0.91 2.02 2.02 2.93 3.27 0.16 1.880 0.074 0.85

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 43 0 4 1.20 1.20 0.80 2.00 1x16+16/25 3.64 6.06 6.06 9.70 3.27 1.36 1.364 0.620 0.62
2 55 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.65 2.019 0.297 0.92
3 60 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.36 2.376 0.162 1.08

1 0.62
1.1 25 0 0 0.80 0.80 0.00 0.80 1x16+16/25 0.00 4.04 4.04 4.04 3.27 0.33 0.331 0.150 0.77

2 0.92
2.1 60 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 0.178 0.081 1.00

15 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : CARHUA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 1 14 0.00 0.00 2.80 2.80 1x16/25 12.73 0.00 0.00 12.73 3.27 0.12 0.125 0.057 0.06
2 50 1 13 0.00 0.00 2.60 2.60 1x16/25 11.82 0.00 0.00 11.82 3.27 1.93 2.058 0.879 0.94
3 70 1 12 0.00 0.00 2.40 2.40 1x16/25 10.91 0.00 0.00 10.91 3.27 2.50 4.557 1.136 2.07
4 70 8 11 0.00 0.00 2.20 2.20 1x16/25 10.00 0.00 0.00 10.00 3.27 2.29 6.847 1.041 3.11
5 60 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.54 7.383 0.243 3.36
6 60 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.36 7.740 0.162 3.52

4 3.11
4.1 75 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.45 0.446 0.203 3.32

4 3.11
4.0.1 35 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.42 0.416 0.189 3.30

16 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : CHOQUIBAMBA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.05 0.054 0.024 0.02
2 120 3 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.78 1.838 0.811 0.84
3 120 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.71 2.552 0.324 1.16

2 0.84
2.1 70 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.21 0.208 0.095 0.93

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 48 3 13 0.00 0.00 2.60 2.60 1x16/25 11.82 0.00 0.00 11.82 3.27 1.86 1.856 0.844 0.84
2 60 2 10 0.00 0.00 2.00 2.00 1x16/25 9.09 0.00 0.00 9.09 3.27 1.78 3.641 0.811 1.65
3 60 1 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 1.43 5.069 0.649 2.30
4 60 5 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.25 6.318 0.568 2.87
5 60 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.36 6.675 0.162 3.03

4 2.87
4.1 50 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.30 0.297 0.135 3.01

17 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : PACHACUYO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 3 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 0.06 0.062 0.028 0.03
2 35 3 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.42 0.479 0.189 0.22
3 35 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.10 0.583 0.047 0.27

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 30 4 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.54 0.535 0.243 0.24
2 44 1 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.26 0.797 0.119 0.36
3 86 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.26 1.053 0.116 0.48

1 0.24
1.1 25 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.15 0.149 0.068 0.31

18 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : PACHACUYO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 25 5 11 0.00 0.80 2.20 3.00 1x16+16/25 10.00 0.00 4.04 14.04 3.27 1.15 1.149 0.522 0.52
2 23 4 6 0.40 0.80 1.20 2.00 1x16+16/25 5.45 2.02 4.04 9.49 3.27 0.71 1.863 0.325 0.85
3 34 2 2 0.40 0.40 0.40 0.80 1x16+16/25 1.82 2.02 2.02 3.84 3.27 0.43 2.290 0.194 1.04

2 0.85
2.1 12 2 2 0.40 0.40 0.40 0.80 1x16+16/25 1.82 2.02 2.02 3.84 3.27 0.15 0.151 0.069 0.92

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 42 1 1 0.00 0.00 0.20 0.20 1x16+16/25 0.91 0.00 0.00 0.91 3.27 0.12 0.125 0.057 0.06

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 3 14 0.40 0.80 2.80 3.60 1x16+16/25 12.73 2.02 4.04 16.77 3.27 0.16 0.165 0.075 0.07
2 31 3 11 0.40 0.40 2.20 2.60 1x16+16/25 10.00 2.02 2.02 12.02 3.27 1.22 1.384 0.554 0.63
3 24 2 8 0.00 0.00 1.60 1.60 1x16+16/25 7.27 0.00 0.00 7.27 3.27 0.57 1.955 0.260 0.89
4 8 2 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.14 2.098 0.065 0.95
5 62 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.74 2.835 0.335 1.29
6 65 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.58 3.415 0.264 1.55

19 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1
OCULTAR
LOCALIDAD : RONTOYCHICO OCULTAR CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )
SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 OCULTAR TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE OCULTAR SISTEMA: 440/220 V
OCULTAR
CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA FORMACION I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) DEL CONDUCTOR (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 53 3 13 0.00 0.40 2.60 3.00 M 1x16/25 11.82 0.00 2.02 13.84 3.27 2.40 2.400 1.091 1.09
2 50 1 10 0.00 0.40 2.00 2.40 M 1x16/25 9.09 0.00 2.02 11.11 3.27 1.82 4.218 0.826 1.92
3 50 3 9 0.00 0.40 1.80 2.20 M 1x16/25 8.18 0.00 2.02 10.20 3.27 1.67 5.887 0.759 2.68
4 70 2 6 0.00 0.40 1.20 1.60 M 1x16/25 5.45 0.00 2.02 7.47 3.27 1.71 7.599 0.778 3.45
5 130 2 4 0.00 0.40 0.80 1.20 M 1x16/25 3.64 0.00 2.02 5.66 3.27 2.41 10.005 1.094 4.55
6 70 2 2 0.00 0.40 0.40 0.80 M 1x16/25 1.82 0.00 2.02 3.84 3.27 0.88 10.884 0.400 4.95
7 50 0 0 0.40 0.40 0.00 0.40 M 1x16/25 0.00 2.02 2.02 2.02 3.27 0.33 11.214 0.150 5.10

4 3.45
4.1 70 1 1 0.00 0.00 0.20 0.20 M 1x16/25 0.91 0.00 0.00 0.91 3.27 0.21 0.208 0.095 3.55

5 4.55
5.1 60 1 1 0.00 0.00 0.20 0.20 M 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 0.178 0.081 4.63

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA FORMACION I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) DEL CONDUCTOR (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 1 8 0.00 0.00 1.60 1.60 M 1x16/25 7.27 0.00 0.00 7.27 3.27 0.07 0.071 0.032 0.03
2 55 2 7 0.00 0.00 1.40 1.40 M 1x16/25 6.36 0.00 0.00 6.36 3.27 1.15 1.217 0.521 0.55
3 70 1 5 0.00 0.00 1.00 1.00 M 1x16/25 4.55 0.00 0.00 4.55 3.27 1.04 2.258 0.473 1.03
4 116 1 4 0.00 0.00 0.80 0.80 M 1x16/25 3.64 0.00 0.00 3.64 3.27 1.38 3.638 0.627 1.65
5 60 3 3 0.00 0.00 0.60 0.60 M 1x16/25 2.73 0.00 0.00 2.73 3.27 0.54 4.173 0.243 1.90

20 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : VILCABAMBA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 71 10 17 0.00 0.00 3.40 3.40 1x16+16/25 15.45 0.00 0.00 15.45 3.27 3.59 3.590 1.632 1.63
2 36 2 7 0.00 0.00 1.40 1.40 1x16+16/25 6.36 0.00 0.00 6.36 3.27 0.75 4.340 0.341 1.97
3 41 5 5 0.00 0.00 1.00 1.00 1x16+16/25 4.55 0.00 0.00 4.55 3.27 0.61 4.950 0.277 2.25

1 1.63
1.1 64 1 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.76 0.761 0.346 1.98
1.2 62 3 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.55 1.315 0.251 2.23

1 1.63
1.0.1 84 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.50 0.500 0.227 1.86

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 59 4 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.70 0.702 0.319 0.32

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.04 0.036 0.016 0.02
2 132 3 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 1.18 1.214 0.535 0.55

21 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : VILCABAMBA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 35 3 17 0.00 3.00 3.40 6.40 1x16+16/25 15.45 0.00 15.15 30.61 3.27 3.51 3.505 1.593 1.59
2 38 5 14 1.50 3.00 2.80 5.80 1x16+16/25 12.73 7.58 15.15 27.88 3.27 3.47 6.971 1.576 3.17
3 80 4 9 0.50 1.50 1.80 3.30 1x16+16/25 8.18 2.53 7.58 15.76 3.27 4.12 11.096 1.875 5.04
4 80 3 5 1.00 1.00 1.00 2.00 1x16+16/25 4.55 5.05 5.05 9.60 3.27 2.51 13.608 1.142 6.19
5 120 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.71 14.322 0.324 6.51

2 3.17
2.1 30 1 1 1.50 1.50 0.20 1.70 1x16+16/25 0.91 7.58 7.58 8.48 3.27 0.83 0.833 0.379 3.55

22 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : VILCABAMBA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 73 2 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 1.74 1.737 0.790 0.79
2 70 4 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.25 2.986 0.568 1.36
3 70 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.42 3.403 0.189 1.55

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 73 4 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 1.95 1.954 0.888 0.89
2 80 1 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.19 3.144 0.541 1.43
3 80 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.95 4.096 0.433 1.86
4 80 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.48 4.572 0.216 2.08

23 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : CHICREIPON CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 4 23 0.00 0.80 4.60 5.40 2x16+16/25 10.45 0.00 2.02 12.47 4.09 0.15 0.153 0.035 0.03
2 60 1 19 0.80 0.80 3.80 4.60 2x16+16/25 8.64 2.02 2.02 10.66 4.09 2.62 2.768 0.594 0.63
3 60 1 18 0.00 0.00 3.60 3.60 1x16/25 16.36 0.00 0.00 16.36 3.27 3.21 5.981 1.460 2.09
4 80 3 17 0.00 0.00 3.40 3.40 1x16/25 15.45 0.00 0.00 15.45 3.27 4.05 10.026 1.839 3.93
5 90 7 14 0.00 0.00 2.80 2.80 1x16/25 12.73 0.00 0.00 12.73 3.27 3.75 13.774 1.704 5.63
6 62 3 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.29 15.065 0.587 6.22
7 60 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.71 15.779 0.324 6.54
8 70 2 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.62 16.404 0.284 6.83
9 60 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 16.582 0.081 6.91

5 5.63
5.1 75 3 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.56 1.562 0.710 6.34
5.2 60 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.71 2.276 0.324 6.67
5.3 60 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.36 2.632 0.162 6.83

5 5.63
5.2.1 40 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.24 0.238 0.108 5.74

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 23 1 5 0.00 0.80 1.00 1.80 1x16/25 4.55 0.00 4.04 8.59 3.27 0.65 0.646 0.294 0.29
2 60 0 4 0.80 0.80 0.80 1.60 1x16/25 3.64 4.04 4.04 7.68 3.27 1.51 2.153 0.685 0.98
3 88 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 1.05 3.200 0.476 1.45
4 89 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.79 3.994 0.361 1.82
5 38 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.23 4.221 0.103 1.92

24 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : CHICREIPON CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 33 3 18 0.00 0.40 3.60 4.00 1x16/25 16.36 0.00 2.02 18.38 3.27 1.99 1.985 0.902 0.90
2 46 2 15 0.40 0.40 3.00 3.40 1x16/25 13.64 2.02 2.02 15.66 3.27 2.36 4.342 1.071 1.97
3 15 4 13 0.00 0.00 2.60 2.60 1x16/25 11.82 0.00 0.00 11.82 3.27 0.58 4.922 0.264 2.24
4 51 6 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 1.37 6.287 0.621 2.86
5 50 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.45 6.733 0.203 3.06
6 70 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.42 7.149 0.189 3.25

1 0.90
1.1 70 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.62 0.625 0.284 1.19

25 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : COLCABAMBA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 0 15 0.40 0.40 3.00 3.40 1x16/25 13.64 2.02 2.02 15.66 3.27 0.15 0.154 0.070 0.07
2 40 2 15 0.00 0.00 3.00 3.00 1x16/25 13.64 0.00 0.00 13.64 3.27 1.78 1.938 0.811 0.88
3 37 3 13 0.00 0.00 2.60 2.60 1x16/25 11.82 0.00 0.00 11.82 3.27 1.43 3.369 0.650 1.53
4 50 1 10 0.00 0.00 2.00 2.00 1x16/25 9.09 0.00 0.00 9.09 3.27 1.49 4.856 0.676 2.21
5 69 2 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 1.85 6.704 0.840 3.05
6 86 1 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.79 8.494 0.814 3.86
7 169 1 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 3.02 11.510 1.371 5.23
8 65 3 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.97 12.477 0.439 5.67
9 75 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.45 12.923 0.203 5.87

7 5.23
7.1 62 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 0.184 0.084 5.32

8 5.67
8.1 74 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.44 0.440 0.200 5.87

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 56 4 7 0.40 0.40 1.40 1.80 1x16/25 6.36 2.02 2.02 8.38 3.27 1.54 1.536 0.698 0.70
2 80 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.71 2.250 0.324 1.02
3 80 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.48 2.726 0.216 1.24

1 0.70
1.1 61 2 2 0.40 0.40 0.40 0.80 1x16/25 1.82 2.02 2.02 3.84 3.27 0.77 0.766 0.348 1.05

26 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : COLCABAMBA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 89 3 24 0.40 0.40 4.80 5.20 2x16/25 10.91 1.01 1.01 11.92 4.09 4.34 4.339 0.986 0.99
2 78 5 21 0.00 0.00 4.20 4.20 2x16/25 9.55 0.00 0.00 9.55 4.09 3.05 7.384 0.692 1.68
3 79 1 16 0.00 0.00 3.20 3.20 1x16/25 14.55 0.00 0.00 14.55 3.27 3.76 11.144 1.709 3.39
4 81 8 15 0.00 0.00 3.00 3.00 1x16/25 13.64 0.00 0.00 13.64 3.27 3.61 14.758 1.643 5.03
5 80 4 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.67 16.424 0.757 5.79
6 85 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.76 17.182 0.345 6.13

1 0.99
1.1 57 1 3 0.00 0.40 0.60 1.00 1x16/25 2.73 0.00 2.02 4.75 3.27 0.89 0.885 0.402 1.39
1.2 46 2 2 0.40 0.40 0.40 0.80 1x16/25 1.82 2.02 2.02 3.84 3.27 0.58 1.463 0.263 1.65

2 1.68
2.1 50 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.30 0.297 0.135 1.81

2 1.68
2.0.1 43 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.38 0.384 0.174 1.85

4 5.03
4.1 60 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.54 0.535 0.243 5.27
4.2 76 1 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.45 0.988 0.206 5.48
4.3 60 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 1.166 0.081 5.56

4 5.03
4.0.1 67 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.60 0.598 0.272 5.30

5 5.79
5.1 45 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.27 0.268 0.122 5.91

27 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : COTO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 59 2 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.05 1.053 0.479 0.48
2 52 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.62 1.672 0.281 0.76
3 52 2 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.46 2.136 0.211 0.97
4 90 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.27 2.403 0.122 1.09

1 0.48
1.1 50 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.30 0.297 0.135 0.61

3 0.97
3.1 40 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.12 0.119 0.054 1.02

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 55 2 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.98 0.982 0.446 0.45
2 48 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.57 1.553 0.260 0.71

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 83 3 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.48 1.481 0.673 0.67
2 56 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.50 1.981 0.227 0.90
3 50 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.30 2.279 0.135 1.04

28 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : COTO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 90 6 16 0.00 0.50 3.20 3.70 1x16/25 14.55 0.00 2.53 17.07 3.27 5.03 5.027 2.285 2.28
2 87 2 10 0.00 0.50 2.00 2.50 1x16/25 9.09 0.00 2.53 11.62 3.27 3.31 8.334 1.503 3.79
3 90 2 8 0.50 0.50 1.60 2.10 1x16/25 7.27 2.53 2.53 9.80 3.27 2.89 11.219 1.312 5.10
4 65 3 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.16 12.379 0.527 5.63
5 64 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.57 12.950 0.260 5.89

1 2.28
1.1 90 1 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.61 1.606 0.730 3.02
1.2 90 1 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.34 2.945 0.608 3.62
1.3 60 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.71 3.659 0.324 3.95
1.4 60 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.36 4.016 0.162 4.11

3 5.10
3.1 85 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.25 0.253 0.115 5.21

4 5.63
4.1 56 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.33 0.333 0.151 5.78

29 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : COTO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 38 8 20 1.00 1.50 4.00 5.50 1x16+16/25 18.18 5.05 7.58 25.76 3.27 3.20 3.203 1.456 1.46
2 55 5 12 0.00 0.50 2.40 2.90 1x16+16/25 10.91 0.00 2.53 13.43 3.27 2.42 5.620 1.099 2.55
3 26 2 7 0.00 0.50 1.40 1.90 1x16/25 6.36 0.00 2.53 8.89 3.27 0.76 6.376 0.344 2.90
4 76 4 5 0.00 0.50 1.00 1.50 1x16/25 4.55 0.00 2.53 7.07 3.27 1.76 8.135 0.799 3.70
5 121 0 1 0.50 0.50 0.20 0.70 1x16/25 0.91 2.53 2.53 3.43 3.27 1.36 9.494 0.618 4.32
6 42 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.12 9.619 0.057 4.37

1 1.46
1.1 46 2 6 0.00 0.50 1.20 1.70 1x16+16/25 5.45 0.00 2.53 7.98 3.27 1.20 1.201 0.546 2.00
1.2 56 2 4 0.50 0.50 0.80 1.30 1x16+16/25 3.64 2.53 2.53 6.16 3.27 1.13 2.330 0.513 2.51
1.3 65 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.39 2.717 0.176 2.69

2 2.55
2.1 80 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.48 0.476 0.216 2.77

4 3.70
4.1 101 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.60 0.601 0.273 3.97

30 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 3

LOCALIDAD : COTO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 56 1 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.83 0.833 0.379 0.38
2 106 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 1.26 2.094 0.573 0.95

1 0.38
1.1 76 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.23 0.226 0.103 0.48

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 81 1 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.20 1.205 0.548 0.55
2 76 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.90 2.109 0.411 0.96
3 207 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 1.23 3.340 0.560 1.52

2 0.96
2.1 72 1 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.43 0.428 0.195 1.15
2.2 69 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.21 0.634 0.093 1.25

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 2 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 0.08 0.080 0.037 0.04
2 67 2 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.40 1.475 0.634 0.67
3 56 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.83 2.308 0.379 1.05
4 62 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.55 2.862 0.251 1.30

31 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : HUAYTAYOG CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 66 1 19 0.00 0.00 3.80 3.80 2x16/25 8.64 0.00 0.00 8.64 4.09 2.33 2.331 0.530 0.53
2 90 2 18 0.00 0.00 3.60 3.60 1x16/25 16.36 0.00 0.00 16.36 3.27 4.82 7.150 2.190 2.72
3 90 8 16 0.00 0.00 3.20 3.20 1x16/25 14.55 0.00 0.00 14.55 3.27 4.28 11.433 1.947 4.67
4 80 3 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 1.90 13.337 0.865 5.53
5 42 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.62 13.962 0.284 5.82
6 42 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.37 14.337 0.170 5.99

3 4.67
3.1 67 2 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.20 1.196 0.544 5.21
3.2 57 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.68 1.874 0.308 5.52

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 51 2 15 0.00 0.40 3.00 3.40 1x16/25 13.64 0.00 2.02 15.66 3.27 2.61 2.613 1.188 1.19
2 40 1 13 0.00 0.40 2.60 3.00 1x16/25 11.82 0.00 2.02 13.84 3.27 1.81 4.424 0.823 2.01
3 45 1 12 0.00 0.40 2.40 2.80 1x16/25 10.91 0.00 2.02 12.93 3.27 1.90 6.328 0.865 2.88
4 45 2 11 0.00 0.40 2.20 2.60 1x16/25 10.00 0.00 2.02 12.02 3.27 1.77 8.097 0.804 3.68
5 90 3 9 0.00 0.40 1.80 2.20 1x16/25 8.18 0.00 2.02 10.20 3.27 3.00 11.102 1.366 5.05
6 90 3 6 0.40 0.40 1.20 1.60 1x16/25 5.45 2.02 2.02 7.47 3.27 2.20 13.303 1.001 6.05
7 63 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.56 13.865 0.256 6.30
8 64 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.38 14.246 0.173 6.48

6 6.05
6.1 29 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.26 0.259 0.118 6.16
6.2 36 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.21 0.473 0.097 6.26

32 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : HUAYTAYOG CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 68 4 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.21 1.214 0.552 0.55
2 64 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.38 1.594 0.173 0.72

1 0.55
1.1 60 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.36 0.357 0.162 0.71

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 63 2 29 0.00 0.40 5.80 6.20 2x16+16/25 13.18 0.00 2.02 15.20 4.09 3.92 3.917 0.890 0.89
2 54 5 27 0.00 0.40 5.40 5.80 2x16+16/25 12.27 0.00 2.02 14.29 4.09 3.16 7.074 0.717 1.61
3 55 7 22 0.00 0.40 4.40 4.80 1x16/25 20.00 0.00 2.02 22.02 3.27 3.96 11.037 1.801 3.41
4 55 7 15 0.00 0.40 3.00 3.40 1x16/25 13.64 0.00 2.02 15.66 3.27 2.82 13.854 1.281 4.69
5 49 2 8 0.40 0.40 1.60 2.00 1x16/25 7.27 2.02 2.02 9.29 3.27 1.49 15.344 0.677 5.37
6 48 3 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.86 16.201 0.389 5.76
7 48 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.43 16.629 0.195 5.95

3 3.41
3.1 42 3 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.50 0.500 0.227 3.64
3.2 42 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.12 0.625 0.057 3.69

4 4.69
4.1 80 5 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.67 1.666 0.757 5.45
4.2 69 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.41 2.076 0.187 5.63

4.1 #N/A
0.4.1 71 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.42 0.422 0.192 #N/A

33 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : QUITAPAMPA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 91 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 1.08 1.083 0.492 0.49
2 86 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.77 1.850 0.349 0.84

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 53 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.16 0.158 0.072 0.07

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 1 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.05 0.054 0.024 0.02
2 86 3 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.28 1.333 0.581 0.61
3 85 1 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.51 1.838 0.230 0.84
4 85 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.25 2.091 0.115 0.95

2 0.61
2.1 70 1 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.42 0.416 0.189 0.80
2.2 90 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.27 0.684 0.122 0.92

34 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : QUITAPAMPA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 0.07 0.071 0.032 0.03
2 171 4 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 3.56 3.632 1.618 1.65
3 66 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.59 4.221 0.268 1.92
4 66 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.39 4.614 0.178 2.10

2 1.65
2.1 89 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.53 0.529 0.241 1.89

2 1.65
2.0.1 68 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.40 0.405 0.184 1.83

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 63 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.75 0.750 0.341 0.34
2 60 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.54 1.285 0.243 0.58
3 50 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.30 1.582 0.135 0.72

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 53 0 0 0.40 0.80 0.00 0.80 1x16/25 0.00 2.02 4.04 4.04 3.27 0.70 0.701 0.318 0.32
2 50 0 0 0.40 0.40 0.00 0.40 1x16/25 0.00 2.02 2.02 2.02 3.27 0.33 1.031 0.150 0.47

35 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SANFRANCISCODECIRCO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 43 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.13 0.128 0.058 0.06

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 126 3 3 0.50 0.50 0.60 1.10 1x16/25 2.73 2.53 2.53 5.25 3.27 2.17 2.165 0.984 0.98

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 4 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 0.06 0.062 0.028 0.03
2 65 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.58 0.643 0.264 0.29
3 41 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.24 0.886 0.111 0.40

36 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : SANFRANCISCODECIRCO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

LONGITUD NUMERO C A R G A CORRIENTE K


CAIDA DE TENSION
SNL
(m) (V/m-A)
PUNTO DE ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 65 1 10 0.50 0.50 2.00 2.50 1x16/25 9.09 2.53 2.53 11.62 3.27 2.47 2.471 1.123 1.12
2 116 1 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 3.11 5.576 1.412 2.53
3 81 4 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 1.93 7.503 0.876 3.41
4 98 3 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 1.17 8.669 0.530 3.94
5 75 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.22 8.893 0.101 4.04

3 3.41
3.1 80 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.24 0.238 0.108 3.52

CIRCUITO : C1R

LONGITUD NUMERO C A R G A CORRIENTE KCAIDA DE TENSION


SNL
(m) (V/m-A)
PUNTO DE ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 64 1 2 0.00 0.50 0.40 0.90 1x16/25 1.82 0.00 2.53 4.34 3.27 0.91 0.910 0.413 0.41
2 61 1 1 0.50 0.50 0.20 0.70 1x16/25 0.91 2.53 2.53 3.43 3.27 0.69 1.595 0.312 0.73

CIRCUITO : C1R'

LONGITUD NUMERO C A R G A CORRIENTE KCAIDA DE TENSION


SNL
(m) (V/m-A)
PUNTO DE ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 66 7 20 0.00 0.00 4.00 4.00 1x16/25 18.18 0.00 0.00 18.18 3.27 3.93 3.926 1.785 1.78
2 66 1 13 0.00 0.00 2.60 2.60 1x16/25 11.82 0.00 0.00 11.82 3.27 2.55 6.479 1.160 2.94
3 61 2 12 0.00 0.00 2.40 2.40 1x16/25 10.91 0.00 0.00 10.91 3.27 2.18 8.656 0.990 3.93
4 60 3 10 0.00 0.00 2.00 2.00 1x16/25 9.09 0.00 0.00 9.09 3.27 1.78 10.441 0.811 4.75
5 61 4 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.27 11.711 0.577 5.32
6 24 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.21 11.925 0.097 5.42

1 1.78
1.1 54 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.80 0.803 0.365 2.15
1.2 29 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.26 1.062 0.118 2.27

1 1.78
1.0.1 30 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.09 0.089 0.041 1.83

37 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : SANFRANCISCODECIRCO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

38 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : CASHASH CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 5 23 0.40 1.20 4.60 5.80 1x16+16/25 20.91 2.02 6.06 26.97 3.27 0.26 0.265 0.120 0.12
2 40 4 18 0.40 0.80 3.60 4.40 1x16+16/25 16.36 2.02 4.04 20.40 3.27 2.67 2.935 1.214 1.33
3 90 5 14 0.40 0.40 2.80 3.20 1x16/25 12.73 2.02 2.02 14.75 3.27 4.34 7.278 1.974 3.31
4 200 4 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 5.35 12.632 2.434 5.74
5 80 5 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.19 13.822 0.541 6.28

2 1.33
2.1 70 3 4 0.00 0.40 0.80 1.20 1x16+16/25 3.64 0.00 2.02 5.66 3.27 1.30 1.296 0.589 1.92
2.2 30 1 1 0.40 0.40 0.20 0.60 1x16+16/25 0.91 2.02 2.02 2.93 3.27 0.29 1.583 0.131 2.05

3 3.31
3.1 45 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.54 0.535 0.243 3.55
3.2 85 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.76 1.294 0.345 3.90
3.3 70 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.42 1.710 0.189 4.09

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 45 2 19 0.80 0.80 3.80 4.60 1x16+16/25 17.27 4.04 4.04 21.31 3.27 3.14 3.138 1.426 1.43
2 44 2 17 0.00 0.00 3.40 3.40 1x16+16/25 15.45 0.00 0.00 15.45 3.27 2.22 5.363 1.011 2.44
3 30 3 15 0.00 0.00 3.00 3.00 1x16/25 13.64 0.00 0.00 13.64 3.27 1.34 6.702 0.608 3.05
4 65 9 12 0.00 0.00 2.40 2.40 1x16/25 10.91 0.00 0.00 10.91 3.27 2.32 9.022 1.055 4.10
5 80 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.71 9.736 0.324 4.43
6 45 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.27 10.003 0.122 4.55

2 2.44
2.1 85 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.25 0.253 0.115 2.55

3 3.05
3.1 56 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.50 0.500 0.227 3.27

4 4.10
4.1 40 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.48 0.476 0.216 4.32

4 4.10
4.0.1 40 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.12 0.119 0.054 4.15

39 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : JAPIA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 61 0 5 0.40 0.40 1.00 1.40 1x16+16/25 4.55 2.02 2.02 6.57 3.27 1.31 1.310 0.596 0.60
2 80 0 5 0.00 0.00 1.00 1.00 1x16+16/25 4.55 0.00 0.00 4.55 3.27 1.19 2.500 0.541 1.14
3 80 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.19 3.690 0.541 1.68
4 60 2 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.54 4.226 0.243 1.92
5 60 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 4.404 0.081 2.00

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 57 8 17 0.00 0.00 3.40 3.40 1x16+16/25 15.45 0.00 0.00 15.45 3.27 2.88 2.882 1.310 1.31
2 71 4 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 1.90 4.783 0.864 2.17
3 85 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.26 6.047 0.575 2.75
4 66 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.59 6.636 0.268 3.02
5 65 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.39 7.023 0.176 3.19

1 1.31
1.1 45 4 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 0.94 0.937 0.426 1.74
1.2 70 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.62 1.562 0.284 2.02
1.3 70 1 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.42 1.978 0.189 2.21
1.4 71 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.21 2.189 0.096 2.31

2 2.17
2.1 71 2 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.63 0.634 0.288 2.46
2.2 49 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.15 0.779 0.066 2.53

40 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : JAPIA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 2 11 0.80 0.80 2.20 3.00 1x16/25 10.00 4.04 4.04 14.04 3.27 0.14 0.138 0.063 0.06
2 76 4 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 2.03 2.172 0.925 0.99
3 205 3 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 3.05 5.221 1.386 2.37
4 60 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.36 5.578 0.162 2.54

2 0.99
2.1 42 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.37 0.375 0.170 1.16

41 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : PAJURUME CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 3 17 0.00 0.00 3.40 3.40 1x16/25 15.45 0.00 0.00 15.45 3.27 0.15 0.152 0.069 0.07
2 40 4 14 0.00 0.00 2.80 2.80 1x16/25 12.73 0.00 0.00 12.73 3.27 1.67 1.817 0.757 0.83
3 50 3 10 0.00 0.00 2.00 2.00 1x16/25 9.09 0.00 0.00 9.09 3.27 1.49 3.305 0.676 1.50
4 65 3 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.35 4.658 0.615 2.12
5 47 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.56 5.217 0.254 2.37
6 47 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.42 5.637 0.191 2.56

2 0.83
2.1 39 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.12 0.116 0.053 0.88

4 2.12
4.1 76 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.45 0.452 0.206 2.32

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 58 2 4 0.40 0.40 0.80 1.20 1x16/25 3.64 2.02 2.02 5.66 3.27 1.07 1.073 0.488 0.49
2 120 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.71 1.787 0.324 0.81

42 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : PAJURUME CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 44 1 6 0.00 0.40 1.20 1.60 1x16/25 5.45 0.00 2.02 7.47 3.27 1.08 1.076 0.489 0.49
2 39 5 5 0.40 0.40 1.00 1.40 1x16/25 4.55 2.02 2.02 6.57 3.27 0.84 1.914 0.381 0.87

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 48 1 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.00 0.999 0.454 0.45
2 49 6 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.87 1.874 0.398 0.85

43 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SANJUANDEPARAS CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 223 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 2.65 2.653 1.206 1.21
2 80 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.48 3.129 0.216 1.42

1 1.21
1.1 40 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.12 0.119 0.054 1.26

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 78 0 14 0.40 0.40 2.80 3.20 1x16/25 12.73 2.02 2.02 14.75 3.27 3.76 3.764 1.711 1.71
2 90 5 14 0.00 0.00 2.80 2.80 1x16/25 12.73 0.00 0.00 12.73 3.27 3.75 7.512 1.704 3.41
3 60 3 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 1.61 9.118 0.730 4.14
4 85 1 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.52 10.635 0.690 4.83
5 90 3 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.34 11.974 0.608 5.44
6 85 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.51 12.479 0.230 5.67

2 3.41
2.1 85 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 1.01 1.011 0.460 3.87
2.2 180 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 1.07 2.082 0.487 4.36

2 3.41
2.1.1 70 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.21 0.208 0.095 3.51

3 4.14
3.1 114 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.68 0.678 0.308 4.45

2.1 3.87
0.2.0.1 85 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.25 0.253 0.115 3.99

44 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SANJUANDEPARAS CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 4 13 0.00 1.60 2.60 4.20 2x16/25 5.91 0.00 8.08 13.99 4.09 0.17 0.172 0.039 0.04
2 64 1 9 0.00 1.60 1.80 3.40 2x16/25 4.09 0.00 8.08 12.17 4.09 3.19 3.358 0.724 0.76
3 60 1 8 0.00 1.60 1.60 3.20 2x16/25 3.64 0.00 8.08 11.72 4.09 2.88 6.233 0.653 1.42
4 80 1 7 0.00 1.60 1.40 3.00 2x16/25 3.18 0.00 8.08 11.26 4.09 3.69 9.918 0.838 2.25
5 80 3 6 0.00 1.60 1.20 2.80 1x16/25 5.45 0.00 8.08 13.54 3.27 3.54 13.461 1.610 3.86
6 50 2 3 0.40 1.60 0.60 2.20 1x16/25 2.73 2.02 8.08 10.81 3.27 1.77 15.229 0.804 4.67
7 50 1 1 0.00 1.20 0.20 1.40 1x16/25 0.91 0.00 6.06 6.97 3.27 1.14 16.370 0.518 5.19
8 50 0 0 0.40 1.20 0.00 1.20 1x16/25 0.00 2.02 6.06 6.06 3.27 0.99 17.361 0.451 5.64
9 50 0 0 0.80 0.80 0.00 0.80 1x16/25 0.00 4.04 4.04 4.04 3.27 0.66 18.022 0.300 5.94

3 1.42
3.1 60 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 0.178 0.081 1.50

4 2.25
4.1 42 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.12 0.125 0.057 2.31

45 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : TINCO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 2 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 0.07 0.071 0.032 0.03
2 60 2 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.07 1.142 0.487 0.52
3 260 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 3.09 4.236 1.406 1.93
4 60 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.36 4.593 0.162 2.09

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 63 2 5 0.00 0.40 1.00 1.40 1x16/25 4.55 0.00 2.02 6.57 3.27 1.35 1.353 0.615 0.62
2 60 2 3 0.00 0.40 0.60 1.00 1x16/25 2.73 0.00 2.02 4.75 3.27 0.93 2.285 0.424 1.04
3 40 1 1 0.40 0.40 0.20 0.60 1x16/25 0.91 2.02 2.02 2.93 3.27 0.38 2.669 0.174 1.21

1 0.62
1.1 148 1 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.88 0.880 0.400 1.02
1.2 80 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.24 1.118 0.108 1.12

46 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : DELAMERCEDDEQUERO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 117 2 9 0.40 0.80 1.80 2.60 1x16/25 8.18 2.02 4.04 12.22 3.27 4.68 4.679 2.127 2.13
2 60 2 7 0.40 0.40 1.40 1.80 1x16/25 6.36 2.02 2.02 8.38 3.27 1.65 6.325 0.748 2.87
3 45 3 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.67 6.994 0.304 3.18
4 55 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.33 7.321 0.149 3.33

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 3 11 0.00 0.80 2.20 3.00 1x16/25 10.00 0.00 4.04 14.04 3.27 0.14 0.138 0.063 0.06
2 70 7 8 0.00 0.80 1.60 2.40 1x16/25 7.27 0.00 4.04 11.31 3.27 2.59 2.729 1.178 1.24
3 60 1 1 0.00 0.80 0.20 1.00 1x16/25 0.91 0.00 4.04 4.95 3.27 0.97 3.701 0.442 1.68
4 45 0 0 0.80 0.80 0.00 0.80 1x16/25 0.00 4.04 4.04 4.04 3.27 0.59 4.296 0.270 1.95

2 1.24
2.1 60 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.71 0.714 0.324 1.56

47 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : ULTOPUQUIO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 66 3 12 0.50 1.50 2.40 3.90 1x16/25 10.91 2.53 7.58 18.48 3.27 3.99 3.992 1.814 1.81
2 64 1 9 0.00 1.00 1.80 2.80 1x16/25 8.18 0.00 5.05 13.23 3.27 2.77 6.763 1.260 3.07
3 63 0 8 1.00 1.00 1.60 2.60 1x16/25 7.27 5.05 5.05 12.32 3.27 2.54 9.303 1.155 4.23
4 62 6 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 1.48 10.778 0.671 4.90
5 59 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.35 11.129 0.160 5.06

2 3.07
2.1 59 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 0.175 0.080 3.15

3 4.23
3.1 33 0 0 1.00 1.00 0.00 1.00 1x16/25 0.00 5.05 5.05 5.05 3.27 0.55 0.545 0.248 4.48

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 1 13 0.00 0.00 2.60 2.60 1x16/25 11.82 0.00 0.00 11.82 3.27 0.12 0.116 0.053 0.05
2 58 1 12 0.00 0.00 2.40 2.40 1x16/25 10.91 0.00 0.00 10.91 3.27 2.07 2.186 0.941 0.99
3 80 2 11 0.00 0.00 2.20 2.20 1x16/25 10.00 0.00 0.00 10.00 3.27 2.62 4.804 1.190 2.18
4 54 3 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 1.45 6.250 0.657 2.84
5 49 1 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.87 7.124 0.398 3.24
6 49 5 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.73 7.853 0.331 3.57

2 0.99
2.1 42 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.12 0.125 0.057 1.05

4 2.84
4.1 90 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.54 0.535 0.243 3.08

48 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : ULTOPUQUIO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 16 0.00 0.50 3.20 3.70 1x16/25 14.55 0.00 2.53 17.07 3.27 0.17 0.168 0.076 0.08
2 72 1 15 0.00 0.50 3.00 3.50 1x16/25 13.64 0.00 2.53 16.16 3.27 3.81 3.975 1.731 1.81
3 78 6 14 0.00 0.50 2.80 3.30 1x16/25 12.73 0.00 2.53 15.25 3.27 3.89 7.868 1.769 3.58
4 53 3 8 0.00 0.50 1.60 2.10 1x16/25 7.27 0.00 2.53 9.80 3.27 1.70 9.567 0.772 4.35
5 55 2 5 0.50 0.50 1.00 1.50 1x16/25 4.55 2.53 2.53 7.07 3.27 1.27 10.839 0.578 4.93
6 80 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.71 11.553 0.324 5.25

3 3.58
3.1 81 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.24 0.241 0.110 3.69

3 3.58
3.0.1 46 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.55 0.547 0.249 3.82

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 51 1 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.30 0.303 0.138 0.14
2 48 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.14 0.446 0.065 0.20

49 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : ULTOPUQUIO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 95 7 11 0.50 1.50 2.20 3.70 1x16+16/25 10.00 2.53 7.58 17.58 3.27 5.46 5.463 2.483 2.48
2 36 1 4 0.50 1.00 0.80 1.80 1x16+16/25 3.64 2.53 5.05 8.69 3.27 1.02 6.486 0.465 2.95
3 35 0 3 0.50 0.50 0.60 1.10 1x16+16/25 2.73 2.53 2.53 5.25 3.27 0.60 7.088 0.273 3.22
4 53 3 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.47 7.561 0.215 3.44

1 2.48
1.1 37 4 6 0.50 0.50 1.20 1.70 1x16+16/25 5.45 2.53 2.53 7.98 3.27 0.97 0.966 0.439 2.92
1.2 35 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.21 1.174 0.095 3.02
1.1 2.92
1.1.1 32 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.19 0.190 0.087 3.01

50 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 3

LOCALIDAD : ULTOPUQUIO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 57 2 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.51 0.509 0.231 0.23
2 83 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.25 0.756 0.112 0.34

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.04 0.045 0.020 0.02
2 56 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.50 0.544 0.227 0.25
3 56 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.33 0.877 0.151 0.40

51 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : CACHUNA(SANNICOLAS) CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 33 6 13 0.00 0.00 2.60 2.60 1x16+16/25 11.82 0.00 0.00 11.82 3.27 1.28 1.276 0.580 0.58
2 47 5 7 0.00 0.00 1.40 1.40 1x16+16/25 6.36 0.00 0.00 6.36 3.27 0.98 2.255 0.445 1.02
3 106 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.63 2.885 0.287 1.31

1 0.58
1.1 28 3 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.25 0.250 0.114 0.69

2 1.02
2.1 30 3 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.27 0.268 0.122 1.15

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 26 1 1 0.40 0.40 0.20 0.60 1x16+16/25 0.91 2.02 2.02 2.93 3.27 0.25 0.249 0.113 0.11

52 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : CACHUNA(SANNICOLAS) CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 1 11 0.00 0.00 2.20 2.20 1x16/25 10.00 0.00 0.00 10.00 3.27 0.10 0.098 0.045 0.04
2 180 1 10 0.00 0.00 2.00 2.00 1x16/25 9.09 0.00 0.00 9.09 3.27 5.35 5.452 2.434 2.48
3 90 1 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 2.41 7.862 1.095 3.57
4 29 2 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 0.69 8.552 0.314 3.89
5 38 3 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.68 9.230 0.308 4.20
6 37 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.33 9.560 0.150 4.35

2 2.48
2.1 40 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.12 0.119 0.054 2.53

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 31 3 3 0.40 0.40 0.60 1.00 1x16+16/25 2.73 2.02 2.02 4.75 3.27 0.48 0.482 0.219 0.22

53 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : DESPENSA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 88 2 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.57 1.571 0.714 0.71
2 85 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 1.01 2.582 0.460 1.17
3 40 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.24 2.820 0.108 1.28

1 0.71
1.1 60 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 0.178 0.081 0.80

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 83 1 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.48 1.481 0.673 0.67
2 80 1 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.19 2.671 0.541 1.21
3 85 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 1.01 3.682 0.460 1.67
4 85 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.76 4.441 0.345 2.02

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 1 8 0.40 0.40 1.60 2.00 1x16/25 7.27 2.02 2.02 9.29 3.27 0.09 0.091 0.041 0.04
2 85 3 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.77 1.861 0.804 0.85
3 150 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 1.78 3.646 0.811 1.66
4 130 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.77 4.419 0.352 2.01

54 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : YANAMAYO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 43 4 5 0.00 1.20 1.00 2.20 1x16+16/25 4.55 0.00 6.06 10.61 3.27 1.49 1.492 0.678 0.68
2 28 1 1 1.20 1.20 0.20 1.40 1x16+16/25 0.91 6.06 6.06 6.97 3.27 0.64 2.131 0.290 0.97

1 0.68
1.1 40 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.12 0.119 0.054 0.73

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 245 3 9 0.40 0.40 1.80 2.20 1x16/25 8.18 2.02 2.02 10.20 3.27 8.18 8.178 3.717 3.72
2 62 3 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.11 9.285 0.503 4.22
3 62 2 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.55 9.838 0.251 4.47
4 85 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.25 10.091 0.115 4.59

3 4.47
3.1 70 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.21 0.208 0.095 4.57

55 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : CASCAYYBAJOCASCAY CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 72 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.64 0.643 0.292 0.29

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 63 1 1 0.40 0.40 0.20 0.60 1x16/25 0.91 2.02 2.02 2.93 3.27 0.60 0.604 0.274 0.27

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 34 1 16 0.00 0.80 3.20 4.00 2x16+16/25 7.27 0.00 4.04 11.31 4.09 1.57 1.573 0.358 0.36
2 85 3 15 0.00 0.80 3.00 3.80 2x16/25 6.82 0.00 4.04 10.86 4.09 3.77 5.348 0.858 1.22
3 84 2 12 0.00 0.80 2.40 3.20 2x16/25 5.45 0.00 4.04 9.49 4.09 3.26 8.610 0.741 1.96
4 86 1 10 0.00 0.80 2.00 2.80 1x16/25 9.09 0.00 4.04 13.13 3.27 3.70 12.305 1.680 3.64
5 84 3 9 0.40 0.80 1.80 2.60 1x16/25 8.18 2.02 4.04 12.22 3.27 3.36 15.665 1.527 5.16
6 87 3 6 0.40 0.40 1.20 1.60 1x16/25 5.45 2.02 2.02 7.47 3.27 2.13 17.792 0.967 6.13
7 140 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 1.25 19.042 0.568 6.70

3 1.96
3.1 40 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.24 0.238 0.108 2.07

5 5.16
5.1 60 2 3 0.40 0.40 0.60 1.00 1x16/25 2.73 2.02 2.02 4.75 3.27 0.93 0.932 0.424 5.59
5.2 60 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 1.110 0.081 5.67

56 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : CASCAYYBAJOCASCAY CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 1 29 0.40 1.20 5.80 7.00 2x16+16/25 13.18 1.01 3.03 16.21 4.09 0.20 0.199 0.045 0.05
2 41 4 28 0.80 0.80 5.60 6.40 2x16+16/25 12.73 2.02 2.02 14.75 4.09 2.47 2.672 0.562 0.61
3 21 9 24 0.00 0.00 4.80 4.80 2x16+16/25 10.91 0.00 0.00 10.91 4.09 0.94 3.609 0.213 0.82
4 88 3 15 0.00 0.00 3.00 3.00 1x16/25 13.64 0.00 0.00 13.64 3.27 3.93 7.535 1.785 2.60
5 173 7 12 0.00 0.00 2.40 2.40 1x16/25 10.91 0.00 0.00 10.91 3.27 6.18 13.710 2.807 5.41
6 68 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.01 14.722 0.460 5.87
7 72 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.64 15.364 0.292 6.16

2 0.61
2.1 29 3 3 0.40 0.40 0.60 1.00 1x16+16/25 2.73 2.02 2.02 4.75 3.27 0.45 0.450 0.205 0.81

5 5.41
5.1 40 1 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.59 0.595 0.270 5.68
5.2 40 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.48 1.071 0.216 5.90

5 5.41
5.0.1 90 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.54 0.535 0.243 5.66

3 0.82
3.1 40 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.12 0.119 0.054 0.87

57 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : CASCAYYBAJOCASCAY CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 117 1 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 2.78 2.784 1.266 1.27
2 57 2 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.19 3.971 0.539 1.81
3 29 5 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.43 4.402 0.196 2.00

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 151 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 1.35 1.347 0.612 0.61

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.04 0.036 0.016 0.02
2 80 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.71 0.750 0.324 0.34

58 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : TREBOLPAMA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 63 3 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 1.50 1.499 0.681 0.68
2 80 1 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.19 2.689 0.541 1.22
3 130 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 1.55 4.236 0.703 1.93
4 85 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.51 4.741 0.230 2.16

1 0.68
1.1 70 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.62 0.625 0.284 0.97
1.2 70 1 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.42 1.041 0.189 1.15
1.3 70 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.21 1.249 0.095 1.25

3 1.93
3.1 42 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.12 0.125 0.057 1.98

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 40 3 6 0.00 0.00 1.20 1.20 1x16+16/25 5.45 0.00 0.00 5.45 3.27 0.71 0.714 0.324 0.32
2 74 3 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.66 1.374 0.300 0.62

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 83 1 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.49 0.494 0.224 0.22
2 50 1 1 0.00 0.00 0.20 0.20 1x16+16/25 0.91 0.00 0.00 0.91 3.27 0.15 0.643 0.068 0.29

59 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : CACHUNA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 34 3 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 0.71 0.708 0.322 0.32
2 59 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.70 1.410 0.319 0.64

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 0 3 0.40 1.20 0.60 1.80 1x16+16/25 2.73 2.02 6.06 8.79 3.27 0.09 0.086 0.039 0.04
2 25 2 3 0.40 0.80 0.60 1.40 1x16+16/25 2.73 2.02 4.04 6.77 3.27 0.55 0.640 0.252 0.29
3 30 1 1 0.40 0.40 0.20 0.60 1x16+16/25 0.91 2.02 2.02 2.93 3.27 0.29 0.927 0.131 0.42

2 0.29
2.1 36 0 0 0.40 0.40 0.00 0.40 1x16+16/25 0.00 2.02 2.02 2.02 3.27 0.24 0.238 0.108 0.40

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 21 4 12 0.40 0.40 2.40 2.80 1x16/25 10.91 2.02 2.02 12.93 3.27 0.89 0.888 0.404 0.40
2 37 4 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 0.88 1.769 0.400 0.80
3 38 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.45 2.221 0.206 1.01
4 90 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.54 2.756 0.243 1.25

60 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : CACHIR CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 3 19 0.00 0.50 3.80 4.30 1x16+16/25 17.27 0.00 2.53 19.80 3.27 0.19 0.194 0.088 0.09
2 74 4 16 0.50 0.50 3.20 3.70 1x16+16/25 14.55 2.53 2.53 17.07 3.27 4.13 4.328 1.879 1.97
3 72 9 12 0.00 0.00 2.40 2.40 1x16+16/25 10.91 0.00 0.00 10.91 3.27 2.57 6.898 1.168 3.14
4 180 2 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 1.61 8.504 0.730 3.87
5 30 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.09 8.593 0.041 3.91

2 1.97
2.1 40 2 2 0.50 0.50 0.40 0.90 1x16+16/25 1.82 2.53 2.53 4.34 3.27 0.57 0.568 0.258 2.23

2 1.97
2.0.1 35 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.21 0.208 0.095 2.06

3 3.14
3.1 20 4 7 0.00 0.00 1.40 1.40 1x16+16/25 6.36 0.00 0.00 6.36 3.27 0.42 0.416 0.189 3.32
3.2 30 3 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.27 0.684 0.122 3.45

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 106 5 16 0.00 1.50 3.20 4.70 1x16+16/25 14.55 0.00 7.58 22.12 3.27 7.67 7.672 3.487 3.49
2 50 3 11 0.50 1.50 2.20 3.70 1x16+16/25 10.00 2.53 7.58 17.58 3.27 2.88 10.548 1.307 4.79
3 57 0 8 1.00 1.00 1.60 2.60 1x16+16/25 7.27 5.05 5.05 12.32 3.27 2.30 12.846 1.045 5.84
4 70 6 8 0.00 0.00 1.60 1.60 1x16+16/25 7.27 0.00 0.00 7.27 3.27 1.67 14.512 0.757 6.60
5 40 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.24 14.750 0.108 6.70

1 3.49
1.1 30 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.18 0.178 0.081 3.57

61 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : CACHIR CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 33 5 9 0.00 0.00 1.80 1.80 1x16+16/25 8.18 0.00 0.00 8.18 3.27 0.88 0.883 0.402 0.40
2 50 4 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.59 1.478 0.270 0.67

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 30 5 18 0.00 0.00 3.60 3.60 1x16/25 16.36 0.00 0.00 16.36 3.27 1.61 1.606 0.730 0.73
2 60 4 13 0.00 0.00 2.60 2.60 1x16/25 11.82 0.00 0.00 11.82 3.27 2.32 3.926 1.055 1.78
3 199 3 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 5.33 9.254 2.422 4.21
4 70 4 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.25 10.503 0.568 4.77
5 40 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.24 10.741 0.108 4.88

62 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : COCHAO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

LONGITUD NUMERO C A R G A CORRIENTE K


CAIDA DE TENSION
SNL
(m) (V/m-A)
PUNTO DE ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 5 18 0.00 0.00 3.60 3.60 1x16/25 16.36 0.00 0.00 16.36 3.27 0.16 0.161 0.073 0.07
2 64 2 13 0.00 0.00 2.60 2.60 1x16/25 11.82 0.00 0.00 11.82 3.27 2.47 2.635 1.125 1.20
3 80 2 11 0.00 0.00 2.20 2.20 1x16/25 10.00 0.00 0.00 10.00 3.27 2.62 5.253 1.190 2.39
4 81 4 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 2.17 7.421 0.986 3.37
5 58 4 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.86 8.284 0.392 3.77
6 55 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.16 8.448 0.074 3.84

CIRCUITO : C1R'

LONGITUD NUMERO C A R G A CORRIENTE KCAIDA DE TENSION


SNL
(m) (V/m-A)
PUNTO DE ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 51 15 22 0.00 0.00 4.40 4.40 1x16/25 20.00 0.00 0.00 20.00 3.27 3.34 3.337 1.517 1.52
2 68 1 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.42 4.753 0.644 2.16
3 90 1 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.61 6.360 0.730 2.89
4 60 1 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.89 7.252 0.406 3.30
5 60 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.71 7.966 0.324 3.62

1 1.52
1.1 46 6 13 0.00 0.00 2.60 2.60 1x16/25 11.82 0.00 0.00 11.82 3.27 1.78 1.779 0.809 2.33
1.2 85 4 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.77 3.549 0.804 3.13
1.3 85 2 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.76 4.307 0.345 3.47
1.4 55 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.16 4.471 0.074 3.55

63 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : COCHAO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 60 7 27 0.00 2.00 5.40 7.40 2x16+16/25 12.27 0.00 5.05 17.32 4.09 4.25 4.251 0.966 0.97
2 31 1 20 0.50 2.00 4.00 6.00 2x16+16/25 9.09 1.26 5.05 14.14 4.09 1.79 6.044 0.407 1.37
3 27 8 19 1.50 1.50 3.80 5.30 2x16+16/25 8.64 3.79 3.79 12.42 4.09 1.37 7.416 0.312 1.69
4 32 2 11 0.00 0.00 2.20 2.20 1x16/25 10.00 0.00 0.00 10.00 3.27 1.05 8.463 0.476 2.16
5 51 2 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 1.37 9.828 0.621 2.78
6 45 2 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 0.94 10.765 0.426 3.21
7 68 3 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.01 11.777 0.460 3.67
8 57 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.34 12.116 0.154 3.82

2 1.37
2.1 26 1 1 0.50 0.50 0.20 0.70 2x16+16/25 0.45 1.26 1.26 1.72 4.09 0.18 0.183 0.042 1.42

3 1.69
3.1 30 3 3 1.50 1.50 0.60 2.10 2x16+16/25 1.36 3.79 3.79 5.15 4.09 0.63 0.632 0.144 1.83

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 2 23 0.00 0.00 4.60 4.60 1x16/25 20.91 0.00 0.00 20.91 3.27 0.21 0.205 0.093 0.09
2 62 2 21 0.00 0.00 4.20 4.20 1x16/25 19.09 0.00 0.00 19.09 3.27 3.87 4.078 1.760 1.85
3 62 15 19 0.00 0.00 3.80 3.80 1x16/25 17.27 0.00 0.00 17.27 3.27 3.50 7.582 1.593 3.45
4 62 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.74 8.320 0.335 3.78
5 77 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.46 8.778 0.208 3.99

3 3.45
3.1 57 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.68 0.678 0.308 3.75
3 3.45
0.3.1 55 6 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.98 0.982 0.446 3.89

64 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : COCHAO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 58 8 15 0.00 0.00 3.00 3.00 1x16/25 13.64 0.00 0.00 13.64 3.27 2.59 2.588 1.176 1.18
2 145 4 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 3.02 5.607 1.372 2.55
3 65 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.58 6.187 0.264 2.81

1 1.18
1.1 40 1 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.59 0.595 0.270 1.45
1.2 50 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.59 1.190 0.270 1.72

2 2.55
2.1 45 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.27 0.268 0.122 2.67

65 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : COCHAS CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 36 6 9 0.00 0.00 1.80 1.80 1x16+16/25 8.18 0.00 0.00 8.18 3.27 0.96 0.964 0.438 0.44
2 42 3 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.37 1.339 0.170 0.61

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 39 4 6 0.80 0.80 1.20 2.00 1x16+16/25 5.45 4.04 4.04 9.49 3.27 1.21 1.212 0.551 0.55
2 40 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.24 1.450 0.108 0.66

1 0.55
1.1 28 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.17 0.167 0.076 0.63

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 7 21 0.00 0.00 4.20 4.20 1x16+16/25 19.09 0.00 0.00 19.09 3.27 0.19 0.187 0.085 0.09
2 34 10 14 0.00 0.00 2.80 2.80 1x16+16/25 12.73 0.00 0.00 12.73 3.27 1.42 1.603 0.644 0.73
3 40 4 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.48 2.079 0.216 0.95

1 0.09
1.1 15 6 6 0.00 0.00 1.20 1.20 1x16+16/25 5.45 0.00 0.00 5.45 3.27 0.27 0.268 0.122 0.21

66 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : HUISHIN CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 2 15 0.00 1.00 3.00 4.00 2x16/25 6.82 0.00 5.05 11.87 4.09 0.15 0.146 0.033 0.03
2 80 0 13 0.00 1.00 2.60 3.60 2x16/25 5.91 0.00 5.05 10.96 4.09 3.59 3.732 0.815 0.85
3 80 1 13 0.00 1.00 2.60 3.60 1x16/25 11.82 0.00 5.05 16.87 3.27 4.42 8.147 2.007 2.86
4 80 7 12 0.00 1.00 2.40 3.40 1x16/25 10.91 0.00 5.05 15.96 3.27 4.18 12.325 1.899 4.75
5 40 4 5 0.50 1.00 1.00 2.00 1x16/25 4.55 2.53 5.05 9.60 3.27 1.26 13.581 0.571 5.32
6 80 0 1 0.50 0.50 0.20 0.70 1x16/25 0.91 2.53 2.53 3.43 3.27 0.90 14.480 0.409 5.73
7 80 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.24 14.718 0.108 5.84

4 4.75
4.1 40 5 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.59 0.595 0.270 5.02

5 5.32
5.1 45 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.40 0.402 0.183 5.51

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 137 1 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 2.85 2.853 1.297 1.30
2 140 6 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 2.50 5.351 1.136 2.43

67 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : HUISHIN CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 303 1 11 0.00 0.00 2.20 2.20 2x16/25 5.00 0.00 0.00 5.00 4.09 6.20 6.196 1.408 1.41
2 150 2 10 0.00 0.00 2.00 2.00 1x16/25 9.09 0.00 0.00 9.09 3.27 4.46 10.658 2.028 3.44
3 60 3 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 1.43 12.086 0.649 4.09
4 67 5 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.00 13.082 0.453 4.54

3 4.09
3.1 40 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.24 0.238 0.108 4.19

68 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : HUISHIN CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 183 2 14 1.00 1.00 2.80 3.80 2x16+16/25 6.36 2.53 2.53 8.89 4.09 6.65 6.653 1.512 1.51
2 80 4 12 0.00 0.00 2.40 2.40 1x16/25 10.91 0.00 0.00 10.91 3.27 2.86 9.509 1.298 2.81
3 140 4 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 3.33 12.840 1.514 4.32
4 150 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 1.78 14.625 0.811 5.14

1 1.51
1.1 45 0 2 0.50 1.00 0.40 1.40 1x16+16/25 1.82 2.53 5.05 6.87 3.27 1.01 1.011 0.460 1.97
1.2 30 2 2 0.50 0.50 0.40 0.90 1x16+16/25 1.82 2.53 2.53 4.34 3.27 0.43 1.438 0.194 2.17

1.1 #N/A
0.1.1 45 0 0 0.40 0.40 0.00 0.40 1x16+16/25 0.00 2.02 2.02 2.02 3.27 0.30 0.297 0.135 #N/A

3 4.32
3.1 62 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.55 0.553 0.251 4.58
3.2 124 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.74 1.291 0.335 4.91

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 55 2 5 0.00 0.50 1.00 1.50 1x16+16/25 4.55 0.00 2.53 7.07 3.27 1.27 1.272 0.578 0.58
2 42 3 3 0.50 0.50 0.60 1.10 1x16+16/25 2.73 2.53 2.53 5.25 3.27 0.72 1.994 0.328 0.91

69 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : HUISHIN CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 83 2 12 0.00 0.00 2.40 2.40 1x16+16/25 10.91 0.00 0.00 10.91 3.27 2.96 2.963 1.347 1.35
2 160 2 10 0.00 0.00 2.00 2.00 1x16/25 9.09 0.00 0.00 9.09 3.27 4.76 7.722 2.163 3.51
3 160 1 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 3.81 11.529 1.731 5.24
4 80 4 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.67 13.195 0.757 6.00
5 150 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 1.34 14.534 0.608 6.61

1 1.35
1.1 37 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.22 0.220 0.100 1.45

4 6.00
4.1 80 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.48 0.476 0.216 6.21

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 83 4 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.73 1.728 0.786 0.79
2 60 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.54 2.264 0.243 1.03

1 0.79
1.1 38 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.23 0.226 0.103 0.89

70 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : ISCOG CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 102 14 22 0.00 0.00 4.40 4.40 1x16/25 20.00 0.00 0.00 20.00 3.27 6.67 6.675 3.034 3.03
2 57 3 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 1.36 8.031 0.617 3.65
3 308 5 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 4.58 12.612 2.082 5.73

1 3.03
1.1 25 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.30 0.297 0.135 3.17

1 3.03
1.0.1 20 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.24 0.238 0.108 3.14

2 3.65
2.1 55 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.33 0.327 0.149 3.80

2 3.65
2.0.1 40 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.12 0.119 0.054 3.70

71 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : ISCOG CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 1 28 0.00 1.20 5.60 6.80 1x16+16/25 25.45 0.00 6.06 31.52 3.27 0.31 0.309 0.141 0.14
2 34 9 27 0.00 1.20 5.40 6.60 1x16+16/25 24.55 0.00 6.06 30.61 3.27 3.40 3.714 1.548 1.69
3 19 5 18 0.80 1.20 3.60 4.80 1x16+16/25 16.36 4.04 6.06 22.42 3.27 1.39 5.108 0.634 2.32
4 24 1 13 0.40 0.40 2.60 3.00 1x16+16/25 11.82 2.02 2.02 13.84 3.27 1.09 6.195 0.494 2.82
5 144 1 12 0.00 0.00 2.40 2.40 1x16/25 10.91 0.00 0.00 10.91 3.27 5.14 11.335 2.336 5.15
6 55 8 11 0.00 0.00 2.20 2.20 1x16/25 10.00 0.00 0.00 10.00 3.27 1.80 13.135 0.818 5.97
7 188 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 1.68 14.812 0.763 6.73

2 1.69
2.1 19 3 11 0.00 0.00 2.20 2.20 1x16+16/25 10.00 0.00 0.00 10.00 3.27 0.62 0.622 0.283 1.97
2.2 24 3 8 0.00 0.00 1.60 1.60 1x16+16/25 7.27 0.00 0.00 7.27 3.27 0.57 1.193 0.260 2.23
2.3 24 5 5 0.00 0.00 1.00 1.00 1x16+16/25 4.55 0.00 0.00 4.55 3.27 0.36 1.550 0.162 2.39

3 2.32
3.1 30 1 3 0.00 0.40 0.60 1.00 1x16+16/25 2.73 0.00 2.02 4.75 3.27 0.47 0.466 0.212 2.53
3.2 35 2 2 0.40 0.40 0.40 0.80 1x16+16/25 1.82 2.02 2.02 3.84 3.27 0.44 0.906 0.200 2.73

6 5.97
6.1 70 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.62 0.625 0.284 6.25

72 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : JIRCAHUAYI CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 23 6 8 0.00 1.20 1.60 2.80 1x16+16/25 7.27 0.00 6.06 13.33 3.27 1.00 1.003 0.456 0.46
2 31 2 2 0.80 1.20 0.40 1.60 1x16+16/25 1.82 4.04 6.06 7.88 3.27 0.80 1.803 0.363 0.82
3 46 0 0 0.40 0.40 0.00 0.40 1x16+16/25 0.00 2.02 2.02 2.02 3.27 0.30 2.107 0.138 0.96

1 0.46
1.1 23 4 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.27 0.274 0.124 0.58

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 23 5 12 0.00 0.00 2.40 2.40 1x16/25 10.91 0.00 0.00 10.91 3.27 0.82 0.821 0.373 0.37
2 40 3 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 0.83 1.654 0.379 0.75
3 41 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.49 2.142 0.222 0.97

1 0.37
1.1 40 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.36 0.357 0.162 0.54

73 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : JIRCAHUAYI CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 63 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.19 0.187 0.085 0.09

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 3 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 0.06 0.062 0.028 0.03
2 36 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.43 0.491 0.195 0.22

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 54 3 6 0.00 0.80 1.20 2.00 1x16/25 5.45 0.00 4.04 9.49 3.27 1.68 1.678 0.763 0.76
2 51 1 3 0.00 0.80 0.60 1.40 1x16/25 2.73 0.00 4.04 6.77 3.27 1.13 2.807 0.513 1.28
3 82 2 2 0.80 0.80 0.40 1.20 1x16/25 1.82 4.04 4.04 5.86 3.27 1.57 4.379 0.714 1.99

74 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : MACHCAS CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 28 0.00 1.00 5.60 6.60 2x16+16/25 12.73 0.00 2.53 15.25 4.09 0.19 0.187 0.043 0.04
2 35 3 27 0.00 1.00 5.40 6.40 2x16+16/25 12.27 0.00 2.53 14.80 4.09 2.12 2.305 0.481 0.52
3 35 7 24 1.00 1.00 4.80 5.80 2x16+16/25 10.91 2.53 2.53 13.43 4.09 1.92 4.229 0.437 0.96
4 40 0 17 0.00 0.00 3.40 3.40 2x16/25 7.73 0.00 0.00 7.73 4.09 1.26 5.493 0.287 1.25
5 48 2 17 0.00 0.00 3.40 3.40 1x16/25 15.45 0.00 0.00 15.45 3.27 2.43 7.920 1.103 2.35
6 63 6 15 0.00 0.00 3.00 3.00 1x16/25 13.64 0.00 0.00 13.64 3.27 2.81 10.731 1.278 3.63
7 84 2 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 2.25 12.980 1.022 4.65
8 136 3 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 2.83 15.811 1.287 5.94
9 50 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.59 16.406 0.270 6.21
10 70 1 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.42 16.823 0.189 6.40
11 70 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.21 17.031 0.095 6.49

3 0.96
3.1 70 5 5 0.00 0.00 1.00 1.00 1x16+16/25 4.55 0.00 0.00 4.55 3.27 1.04 1.041 0.473 1.43

8 5.94
8.1 70 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.62 0.625 0.284 6.22
8.2 70 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.42 1.041 0.189 6.41

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 131 1 12 0.00 1.00 2.40 3.40 1x16/25 10.91 0.00 5.05 15.96 3.27 6.84 6.841 3.109 3.11
2 55 2 11 0.00 1.00 2.20 3.20 1x16/25 10.00 0.00 5.05 15.05 3.27 2.71 9.549 1.231 4.34
3 50 0 9 1.00 1.00 1.80 2.80 1x16/25 8.18 5.05 5.05 13.23 3.27 2.16 11.714 0.984 5.32
4 114 6 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 3.05 14.766 1.387 6.71
5 59 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.53 15.292 0.239 6.95

4 6.71
4.1 45 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.27 0.268 0.122 6.83

75 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : MACHCAS CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 62 7 26 0.00 0.50 5.20 5.70 2x16+16/25 11.82 0.00 1.26 13.08 4.09 3.32 3.317 0.754 0.75
2 127 8 19 0.50 0.50 3.80 4.30 2x16+16/25 8.64 1.26 1.26 9.90 4.09 5.14 8.459 1.169 1.92
3 75 1 11 0.00 0.00 2.20 2.20 2x16+16/25 5.00 0.00 0.00 5.00 4.09 1.53 9.993 0.349 2.27
4 75 4 10 0.00 0.00 2.00 2.00 1x16/25 9.09 0.00 0.00 9.09 3.27 2.23 12.224 1.014 3.29
5 57 6 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.02 13.241 0.462 3.75

1 0.75
1.1 48 5 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.71 0.714 0.324 1.08

1 0.75
1.0.1 47 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.28 0.280 0.127 0.88

2 1.92
2.1 64 1 5 0.00 0.50 1.00 1.50 1x16/25 4.55 0.00 2.53 7.07 3.27 1.48 1.481 0.673 2.60
2.2 62 4 4 0.50 0.50 0.80 1.30 1x16/25 3.64 2.53 2.53 6.16 3.27 1.25 2.731 0.568 3.16

76 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : MACHCAS CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 4 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 0.06 0.062 0.028 0.03
2 82 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.73 0.794 0.333 0.36

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 85 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 1.01 1.011 0.460 0.46

77 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : NUEVOPROGRESO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 56 3 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.00 0.999 0.454 0.45
2 106 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.95 1.945 0.430 0.88

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 48 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.14 0.143 0.065 0.06

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 83 2 11 0.00 0.00 2.20 2.20 1x16/25 10.00 0.00 0.00 10.00 3.27 2.72 2.716 1.234 1.23
2 80 2 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 2.14 4.857 0.973 2.21
3 143 4 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 2.98 7.835 1.353 3.56
4 55 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.49 8.326 0.223 3.78

1 1.23
1.1 80 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.24 0.238 0.108 1.34

3 3.56
3.1 65 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.19 0.193 0.088 3.65

78 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : NUEVOPROGRESO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 63 3 32 0.00 0.00 6.40 6.40 2x16/25 14.55 0.00 0.00 14.55 4.09 3.75 3.748 0.852 0.85
2 166 12 29 0.00 0.00 5.80 5.80 2x16/25 13.18 0.00 0.00 13.18 4.09 8.95 12.698 2.034 2.89
3 55 2 17 0.00 0.00 3.40 3.40 2x16/25 7.73 0.00 0.00 7.73 4.09 1.74 14.436 0.395 3.28
4 50 4 15 0.00 0.00 3.00 3.00 2x16/25 6.82 0.00 0.00 6.82 4.09 1.39 15.830 0.317 3.60
5 60 2 11 0.00 0.00 2.20 2.20 1x16/25 10.00 0.00 0.00 10.00 3.27 1.96 17.793 0.892 4.49
6 60 3 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 1.61 19.400 0.730 5.22
7 55 3 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.98 20.381 0.446 5.67
8 50 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.45 20.827 0.203 5.87

2 2.89
2.1 60 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.71 0.714 0.324 3.21
2.2 60 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.36 1.071 0.162 3.37

2 2.89
0.2.1 37 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.44 0.440 0.200 3.09

4 3.60
4.1 40 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.24 0.238 0.108 3.71

79 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : NUEVOPROGRESO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 161 10 23 0.40 2.00 4.60 6.60 2x16+16/25 10.45 1.01 8.08 18.54 4.09 12.21 12.205 2.774 2.77
2 68 5 13 0.40 1.60 2.60 4.20 2x16+16/25 5.91 1.01 7.07 12.98 4.09 3.61 15.815 0.820 3.59
3 46 3 8 0.00 1.20 1.60 2.80 1x16+16/25 7.27 0.00 6.06 13.33 3.27 2.01 17.822 0.912 4.51
4 30 0 5 0.80 1.20 1.00 2.20 1x16+16/25 4.55 4.04 6.06 10.61 3.27 1.04 18.863 0.473 4.98
5 90 1 5 0.40 0.40 1.00 1.40 1x16+16/25 4.55 2.02 2.02 6.57 3.27 1.93 20.797 0.879 5.86
6 90 3 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 1.07 21.867 0.487 6.35
7 40 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.12 21.986 0.054 6.40

1 2.77
1.1 68 1 9 0.40 0.40 1.80 2.20 1x16/25 8.18 2.02 2.02 10.20 3.27 2.27 2.270 1.032 3.81
1.2 68 1 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 1.62 3.888 0.736 4.54
1.3 55 2 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.15 5.033 0.521 5.06
1.4 106 5 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.58 6.610 0.717 5.78

2 3.59
2.1 68 3 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.61 0.607 0.276 3.87

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 63 3 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.31 1.312 0.596 0.60
2 60 3 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.71 2.026 0.324 0.92
3 60 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 2.204 0.081 1.00

1 0.60
1.1 50 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.30 0.297 0.135 0.73

80 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : PACCHANGA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 39 5 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 1.04 1.044 0.475 0.47
2 34 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.40 1.449 0.184 0.66

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 1 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 0.07 0.071 0.032 0.03
2 70 4 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.46 1.529 0.663 0.69
3 70 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.62 2.154 0.284 0.98

2 0.69
2.1 70 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.42 0.416 0.189 0.88

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 45 3 20 1.20 2.40 4.00 6.40 1x16+16/25 18.18 6.06 12.12 30.30 3.27 4.46 4.462 2.028 2.03
2 58 7 17 0.40 1.20 3.40 4.60 1x16+16/25 15.45 2.02 6.06 21.52 3.27 4.08 8.545 1.856 3.88
3 49 2 10 0.40 0.80 2.00 2.80 1x16+16/25 9.09 2.02 4.04 13.13 3.27 2.11 10.650 0.957 4.84
4 40 4 8 0.40 0.40 1.60 2.00 1x16+16/25 7.27 2.02 2.02 9.29 3.27 1.22 11.866 0.553 5.39
5 35 4 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.42 12.283 0.189 5.58

1 2.03
1.1 25 1 1 1.20 1.20 0.20 1.40 1x16+16/25 0.91 6.06 6.06 6.97 3.27 0.57 0.570 0.259 2.29

81 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : PACCHANGA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 37 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.33 0.330 0.150 0.15

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 63 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.19 0.187 0.085 0.09

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 3 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.04 0.045 0.020 0.02
2 47 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.28 0.324 0.127 0.15

82 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : PUTCOR CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 43 4 25 0.00 0.00 5.00 5.00 1x16+16/25 22.73 0.00 0.00 22.73 3.27 3.20 3.198 1.453 1.45
2 50 5 21 0.00 0.00 4.20 4.20 1x16+16/25 19.09 0.00 0.00 19.09 3.27 3.12 6.321 1.420 2.87
3 40 10 16 0.00 0.00 3.20 3.20 1x16+16/25 14.55 0.00 0.00 14.55 3.27 1.90 8.225 0.865 3.74
4 60 6 6 0.00 0.00 1.20 1.20 1x16+16/25 5.45 0.00 0.00 5.45 3.27 1.07 9.295 0.487 4.23

2 2.87
2.1 30 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.09 0.089 0.041 2.91

3 3.74
3.1 30 4 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.45 0.446 0.203 3.94
3.2 40 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.12 0.565 0.054 4.00

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 4 16 1.50 2.50 3.20 5.70 1x16+16/25 14.55 7.58 12.63 27.17 3.27 0.27 0.267 0.121 0.12
2 25 1 12 1.00 1.00 2.40 3.40 1x16+16/25 10.91 5.05 5.05 15.96 3.27 1.31 1.572 0.593 0.71
3 25 5 11 0.00 0.00 2.20 2.20 1x16+16/25 10.00 0.00 0.00 10.00 3.27 0.82 2.390 0.372 1.09
4 35 6 6 0.00 0.00 1.20 1.20 1x16+16/25 5.45 0.00 0.00 5.45 3.27 0.62 3.015 0.284 1.37

83 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : PUTCOR CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 3 13 0.00 0.00 2.60 2.60 1x16+16/25 11.82 0.00 0.00 11.82 3.27 0.12 0.116 0.053 0.05
2 40 5 10 0.00 0.00 2.00 2.00 1x16+16/25 9.09 0.00 0.00 9.09 3.27 1.19 1.306 0.541 0.59
3 32 5 5 0.00 0.00 1.00 1.00 1x16+16/25 4.55 0.00 0.00 4.55 3.27 0.48 1.782 0.216 0.81

2 0.59
2.1 32 3 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.29 0.286 0.130 0.72

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 43 4 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.51 0.512 0.233 0.23

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 38 16 24 0.00 0.00 4.80 4.80 1x16+16/25 21.82 0.00 0.00 21.82 3.27 2.71 2.713 1.233 1.23
2 40 4 8 0.00 0.00 1.60 1.60 1x16+16/25 7.27 0.00 0.00 7.27 3.27 0.95 3.665 0.433 1.67
3 30 4 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.36 4.022 0.162 1.83

1 1.23
1.1 33 5 5 0.00 0.00 1.00 1.00 1x16+16/25 4.55 0.00 0.00 4.55 3.27 0.49 0.491 0.223 1.46

1 1.23
1.0.1 33 3 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.29 0.294 0.134 1.37

84 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : RURIQUILCA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 68 5 8 0.00 1.20 1.60 2.80 1x16+16/25 7.27 0.00 6.06 13.33 3.27 2.97 2.967 1.348 1.35
2 50 3 3 0.00 1.20 0.60 1.80 1x16+16/25 2.73 0.00 6.06 8.79 3.27 1.44 4.404 0.653 2.00
3 70 0 0 0.40 1.20 0.00 1.20 1x16+16/25 0.00 2.02 6.06 6.06 3.27 1.39 5.792 0.631 2.63
4 38 0 0 0.80 0.80 0.00 0.80 1x16+16/25 0.00 4.04 4.04 4.04 3.27 0.50 6.295 0.228 2.86

2 2.00
2.1 70 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.42 0.416 0.189 2.19

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 4 14 0.00 0.40 2.80 3.20 1x16+16/25 12.73 0.00 2.02 14.75 3.27 0.14 0.145 0.066 0.07
2 50 2 10 0.00 0.40 2.00 2.40 1x16+16/25 9.09 0.00 2.02 11.11 3.27 1.82 1.963 0.826 0.89
3 62 5 8 0.40 0.40 1.60 2.00 1x16+16/25 7.27 2.02 2.02 9.29 3.27 1.89 3.848 0.857 1.75
4 204 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 1.82 5.668 0.827 2.58
5 70 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.42 6.085 0.189 2.77

3 1.75
3.1 40 1 4 0.40 0.40 0.80 1.20 1x16+16/25 3.64 2.02 2.02 5.66 3.27 0.74 0.740 0.337 2.09
3.2 40 3 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.36 1.097 0.162 2.25

85 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SALA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 58 1 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.69 0.690 0.314 0.31
2 55 3 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.49 1.181 0.223 0.54

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 43 3 9 0.40 0.40 1.80 2.20 1x16+16/25 8.18 2.02 2.02 10.20 3.27 1.44 1.435 0.652 0.65
2 40 6 6 0.00 0.00 1.20 1.20 1x16+16/25 5.45 0.00 0.00 5.45 3.27 0.71 2.149 0.324 0.98

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 0 14 1.20 1.20 2.80 4.00 1x16/25 12.73 6.06 6.06 18.79 3.27 0.18 0.184 0.084 0.08
2 65 6 14 0.00 0.00 2.80 2.80 1x16/25 12.73 0.00 0.00 12.73 3.27 2.71 2.891 1.230 1.31
3 85 4 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 2.02 4.914 0.919 2.23
4 85 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 1.01 5.925 0.460 2.69
5 60 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.36 6.282 0.162 2.86

2 1.31
2.1 75 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.45 0.446 0.203 1.52

86 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : YANACANCHA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 38 6 14 0.00 0.40 2.80 3.20 1x16/25 12.73 0.00 2.02 14.75 3.27 1.83 1.834 0.833 0.83
2 50 3 8 0.00 0.40 1.60 2.00 1x16/25 7.27 0.00 2.02 9.29 3.27 1.52 3.354 0.691 1.52
3 60 2 5 0.40 0.40 1.00 1.40 1x16/25 4.55 2.02 2.02 6.57 3.27 1.29 4.643 0.586 2.11
4 45 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.40 5.044 0.183 2.29

3 2.11
3.1 60 0 0 0.40 0.40 0.00 0.40 1x16/25 0.00 2.02 2.02 2.02 3.27 0.40 0.397 0.180 2.29

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 33 5 15 0.00 0.00 3.00 3.00 1x16+16/25 13.64 0.00 0.00 13.64 3.27 1.47 1.472 0.669 0.67
2 30 3 10 0.00 0.00 2.00 2.00 1x16+16/25 9.09 0.00 0.00 9.09 3.27 0.89 2.365 0.406 1.07
3 30 3 7 0.00 0.00 1.40 1.40 1x16+16/25 6.36 0.00 0.00 6.36 3.27 0.62 2.989 0.284 1.36
4 30 4 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.36 3.346 0.162 1.52

3 1.36
3.1 40 1 1 0.00 0.00 0.20 0.20 1x16+16/25 0.91 0.00 0.00 0.91 3.27 0.12 0.119 0.054 1.41

87 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : YANACANCHA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 6 14 0.00 1.60 2.80 4.40 1x16+16/25 12.73 0.00 8.08 20.81 3.27 0.20 0.204 0.093 0.09
2 40 3 8 0.80 1.60 1.60 3.20 1x16+16/25 7.27 4.04 8.08 15.35 3.27 2.01 2.214 0.913 1.01
3 40 2 5 0.00 0.80 1.00 1.80 1x16+16/25 4.55 0.00 4.04 8.59 3.27 1.12 3.337 0.511 1.52
4 20 3 3 0.40 0.80 0.60 1.40 1x16+16/25 2.73 2.02 4.04 6.77 3.27 0.44 3.780 0.201 1.72
5 20 0 0 0.40 0.40 0.00 0.40 1x16+16/25 0.00 2.02 2.02 2.02 3.27 0.13 3.913 0.060 1.78

2 1.01
2.1 46 3 3 0.40 0.80 0.60 1.40 1x16+16/25 2.73 2.02 4.04 6.77 3.27 1.02 1.019 0.463 1.47
2.2 30 0 0 0.40 0.40 0.00 0.40 1x16+16/25 0.00 2.02 2.02 2.02 3.27 0.20 1.217 0.090 1.56

88 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : COLCABAMBA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 2 7 0.40 0.40 1.40 1.80 1x16/25 6.36 2.02 2.02 8.38 3.27 0.08 0.082 0.037 0.04
2 60 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.89 0.975 0.406 0.44
3 60 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.54 1.510 0.243 0.69

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 38 3 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.57 0.565 0.257 0.26
2 165 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.98 1.547 0.446 0.70

1 0.26
1.1 110 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.65 0.654 0.297 0.55

1 0.26
1.0.1 65 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.19 0.193 0.088 0.34

89 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : COLCABAMBA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.04 0.036 0.016 0.02
2 60 2 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.54 0.571 0.243 0.26
3 60 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 0.750 0.081 0.34

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 73 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.87 0.869 0.395 0.39
2 70 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.42 1.285 0.189 0.58

90 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SANMARTINDEMARA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 4 0.40 1.60 0.80 2.40 1x16/25 3.64 2.02 8.08 11.72 3.27 0.12 0.115 0.052 0.05
2 37 1 3 0.40 1.20 0.60 1.80 1x16/25 2.73 2.02 6.06 8.79 3.27 1.06 1.179 0.484 0.54
3 310 2 2 0.00 0.80 0.40 1.20 1x16/25 1.82 0.00 4.04 5.86 3.27 5.94 7.121 2.701 3.24
4 85 0 0 0.80 0.80 0.00 0.80 1x16/25 0.00 4.04 4.04 4.04 3.27 1.12 8.245 0.511 3.75

2 0.54
2.1 40 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.12 0.119 0.054 0.59

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 222 2 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 5.28 5.283 2.401 2.40
2 79 2 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.41 6.693 0.641 3.04
3 80 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.95 7.645 0.433 3.47
4 61 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.36 8.007 0.165 3.64

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 162 1 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 2.89 2.891 1.314 1.31
2 67 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.00 3.888 0.453 1.77
3 68 2 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.61 4.495 0.276 2.04
4 61 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 4.676 0.082 2.13

91 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : VIOC CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 43 2 4 0.40 0.40 0.80 1.20 1x16/25 3.64 2.02 2.02 5.66 3.27 0.80 0.796 0.362 0.36
2 40 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.24 1.034 0.108 0.47

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 33 3 4 0.00 0.40 0.80 1.20 1x16+16/25 3.64 0.00 2.02 5.66 3.27 0.61 0.611 0.278 0.28
2 35 1 1 0.40 0.40 0.20 0.60 1x16+16/25 0.91 2.02 2.02 2.93 3.27 0.34 0.946 0.152 0.43

1 0.28
1.1 40 1 1 0.00 0.00 0.20 0.20 1x16+16/25 0.91 0.00 0.00 0.91 3.27 0.12 0.119 0.054 0.33

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 0 9 0.40 0.40 1.80 2.20 1x16/25 8.18 2.02 2.02 10.20 3.27 0.10 0.100 0.046 0.05
2 92 3 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 2.46 2.563 1.120 1.17
3 70 2 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.25 3.812 0.568 1.73
4 60 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.71 4.526 0.324 2.06
5 60 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.36 4.883 0.162 2.22

2 1.17
2.1 60 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.54 0.535 0.243 1.41

92 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : COCHAPAMPA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 63 4 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 1.50 1.499 0.681 0.68
2 180 3 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 2.14 3.641 0.973 1.65
3 60 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 3.819 0.081 1.74

1 0.68
1.1 42 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.37 0.375 0.170 0.85

2 1.65
2.1 60 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 0.178 0.081 1.74

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 38 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.45 0.452 0.206 0.21
2 50 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.45 0.898 0.203 0.41

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 2 11 0.00 0.00 2.20 2.20 1x16/25 10.00 0.00 0.00 10.00 3.27 0.10 0.098 0.045 0.04
2 60 3 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 1.61 1.704 0.730 0.77
3 60 3 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.07 2.775 0.487 1.26
4 75 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.67 3.445 0.304 1.57
5 75 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.45 3.891 0.203 1.77

93 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SANPEDRODEICHON CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 43 3 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 1.02 1.023 0.465 0.47
2 80 4 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.19 2.213 0.541 1.01
3 60 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 2.392 0.081 1.09

2 1.01
2.1 45 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.27 0.268 0.122 1.13

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 63 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.19 0.187 0.085 0.09

94 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SANPEDRODEICHON CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V
CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 83 2 5 0.00 0.40 1.00 1.40 1x16/25 4.55 0.00 2.02 6.57 3.27 1.78 1.783 0.810 0.81
2 160 0 3 0.40 0.40 0.60 1.00 1x16/25 2.73 2.02 2.02 4.75 3.27 2.49 4.268 1.130 1.94
3 80 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.71 4.982 0.324 2.26
4 80 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.48 5.458 0.216 2.48

3 2.26
3.1 60 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 0.178 0.081 2.35

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 63 2 3 0.40 0.80 0.60 1.40 1x16/25 2.73 2.02 4.04 6.77 3.27 1.40 1.395 0.634 0.63
2 60 1 1 0.40 0.40 0.20 0.60 1x16/25 0.91 2.02 2.02 2.93 3.27 0.58 1.970 0.261 0.90

1 0.63
1.1 40 1 1 0.40 0.40 0.20 0.60 1x16/25 0.91 2.02 2.02 2.93 3.27 0.38 0.383 0.174 0.81

95 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SANTAROSADEJAHUAN CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 70 2 11 0.40 0.80 2.20 3.00 1x16/25 10.00 2.02 4.04 14.04 3.27 3.22 3.216 1.462 1.46
2 67 7 9 0.40 0.40 1.80 2.20 1x16/25 8.18 2.02 2.02 10.20 3.27 2.24 5.452 1.017 2.48
3 67 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.40 5.851 0.181 2.66

2 2.48
2.1 67 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.80 0.797 0.362 2.84

2 2.48
2.0.1 55 2 2 0.40 0.40 0.40 0.80 1x16/25 1.82 2.02 2.02 3.84 3.27 0.69 0.691 0.314 2.79

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 3 10 0.00 0.00 2.00 2.00 1x16/25 9.09 0.00 0.00 9.09 3.27 0.09 0.089 0.041 0.04
2 39 4 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 0.81 0.901 0.369 0.41
3 78 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.70 1.597 0.316 0.73
4 91 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.54 2.139 0.246 0.97

2 0.41
2.1 60 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.36 0.357 0.162 0.57

96 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : QUICHUAS CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 23 4 16 0.00 0.00 3.20 3.20 1x16+16/25 14.55 0.00 0.00 14.55 3.27 1.09 1.095 0.498 0.50
2 40 2 12 0.00 0.00 2.40 2.40 1x16+16/25 10.91 0.00 0.00 10.91 3.27 1.43 2.522 0.649 1.15
3 30 3 10 0.00 0.00 2.00 2.00 1x16+16/25 9.09 0.00 0.00 9.09 3.27 0.89 3.415 0.406 1.55
4 40 5 7 0.00 0.00 1.40 1.40 1x16+16/25 6.36 0.00 0.00 6.36 3.27 0.83 4.248 0.379 1.93
5 45 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.27 4.515 0.122 2.05

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 38 1 5 0.00 0.40 1.00 1.40 1x16+16/25 4.55 0.00 2.02 6.57 3.27 0.82 0.816 0.371 0.37
2 35 3 4 0.00 0.40 0.80 1.20 1x16+16/25 3.64 0.00 2.02 5.66 3.27 0.65 1.464 0.294 0.67
3 50 1 1 0.40 0.40 0.20 0.60 1x16+16/25 0.91 2.02 2.02 2.93 3.27 0.48 1.943 0.218 0.88

2 0.67
2.1 45 4 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.54 0.535 0.243 0.91

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 23 6 14 0.00 0.80 2.80 3.60 1x16+16/25 12.73 0.00 4.04 16.77 3.27 1.26 1.262 0.574 0.57
2 35 2 8 0.80 0.80 1.60 2.40 1x16+16/25 7.27 4.04 4.04 11.31 3.27 1.30 2.557 0.589 1.16
3 30 2 6 0.00 0.00 1.20 1.20 1x16+16/25 5.45 0.00 0.00 5.45 3.27 0.54 3.093 0.243 1.41
4 25 4 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.30 3.390 0.135 1.54

2 1.16
2.1 15 0 0 0.80 0.80 0.00 0.80 1x16+16/25 0.00 4.04 4.04 4.04 3.27 0.20 0.198 0.090 1.25

97 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : QUILLOC CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 163 2 #REF! 0.00 #REF! #REF! #REF! #N/A #REF! 0.00 #REF! #REF! #N/A #N/A #N/A #N/A #N/A
2 50 2 #REF! 0.00 #REF! #REF! #REF! #N/A #REF! 0.00 #REF! #REF! #N/A #N/A #N/A #N/A #N/A

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 63 1 #REF! 0.40 #REF! #REF! #REF! #N/A #REF! 2.02 #REF! #REF! #N/A #N/A #N/A #N/A #N/A

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 81 1 #REF! 0.00 #REF! #REF! #REF! #N/A #REF! 0.00 #REF! #REF! #N/A #N/A #N/A #N/A #N/A
2 180 3 #REF! 0.00 #REF! #REF! #REF! #N/A #REF! 0.00 #REF! #REF! #N/A #N/A #N/A #N/A #N/A

98 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : QUILLOC CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 1 #REF! 0.00 #REF! #REF! #REF! #N/A #REF! 0.00 #REF! #REF! #N/A #N/A #N/A #N/A #N/A
2 31 3 #REF! 0.80 #REF! #REF! #REF! #N/A #REF! 4.04 #REF! #REF! #N/A #N/A #N/A #N/A #N/A
3 20 2 #REF! 0.00 #REF! #REF! #REF! #N/A #REF! 0.00 #REF! #REF! #N/A #N/A #N/A #N/A #N/A

99 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : QUISHUAR CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)
###
1 3 1 9 0.40 1.20 1.80 3.00 1x16+16/25 8.18 2.02 6.06 14.24 3.27 0.14 0.140 0.064 0.06
2 30 1 8 0.80 0.80 1.60 2.40 1x16+16/25 7.27 4.04 4.04 11.31 3.27 1.11 1.250 0.505 0.57
3 32 3 7 0.00 0.00 1.40 1.40 1x16+16/25 6.36 0.00 0.00 6.36 3.27 0.67 1.917 0.303 0.87
4 30 2 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.36 2.274 0.162 1.03
5 110 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.65 2.928 0.297 1.33
###
###
###
CIRCUITO : C1R ###
###
NUMERO C A R G A CORRIENTE CAIDA DE TENSION
PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)
###
1 34 4 11 0.00 0.00 2.20 2.20 1x16/25 10.00 0.00 0.00 10.00 3.27 1.11 1.112 0.506 0.51
2 30 2 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 0.62 1.737 0.284 0.79
3 165 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 2.45 4.191 1.115 1.91
4 50 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.45 4.637 0.203 2.11
###

100 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : QUISHUAR CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V
###
###
CIRCUITO : C1R' ###
###
NUMERO C A R G A CORRIENTE CAIDA DE TENSION
PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)
###
1 24 2 5 0.40 0.40 1.00 1.40 1x16+16/25 4.55 2.02 2.02 6.57 3.27 0.52 0.516 0.234 0.23
2 45 1 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.40 0.917 0.183 0.42
3 45 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.27 1.185 0.122 0.54
###
###
###
CIRCUITO : C1R' ###
###
NUMERO C A R G A CORRIENTE CAIDA DE TENSION
PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)
###
1 32 3 18 0.40 0.40 3.60 4.00 1x16+16/25 16.36 2.02 2.02 18.38 3.27 1.92 1.925 0.875 0.87
2 16 7 15 0.00 0.00 3.00 3.00 1x16+16/25 13.64 0.00 0.00 13.64 3.27 0.71 2.639 0.324 1.20
3 55 5 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 1.31 3.948 0.595 1.79
4 19 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.17 4.117 0.077 1.87
###
1 0.87
1.1 20 1 3 0.00 0.40 0.60 1.00 1x16+16/25 2.73 0.00 2.02 4.75 3.27 0.31 0.311 0.141 1.02
1.2 63 2 2 0.00 0.40 0.40 0.80 1x16/25 1.82 0.00 2.02 3.84 3.27 0.79 1.102 0.360 1.38
1.3 64 0 0 0.40 0.40 0.00 0.40 1x16/25 0.00 2.02 2.02 2.02 3.27 0.42 1.525 0.192 1.57
###
2 1.20
2.1 27 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.24 0.241 0.110 1.31
###

101 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SOLEDADDETAMBO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)
###
1 33 3 8 0.40 0.40 1.60 2.00 1x16+16/25 7.27 2.02 2.02 9.29 3.27 1.00 1.003 0.456 0.46
2 20 1 5 0.00 0.00 1.00 1.00 1x16+16/25 4.55 0.00 0.00 4.55 3.27 0.30 1.301 0.135 0.59
3 20 4 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.24 1.539 0.108 0.70
###
###
###
CIRCUITO : C1R ###
###
NUMERO C A R G A CORRIENTE CAIDA DE TENSION
PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)
###
1 38 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.23 0.226 0.103 0.10
###
###
###
CIRCUITO : C1R' ###
###
NUMERO C A R G A CORRIENTE CAIDA DE TENSION
PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)
###
1 3 2 9 0.40 0.80 1.80 2.60 1x16/25 8.18 2.02 4.04 12.22 3.27 0.12 0.120 0.055 0.05
2 60 2 7 0.00 0.40 1.40 1.80 1x16/25 6.36 0.00 2.02 8.38 3.27 1.65 1.766 0.748 0.80
3 50 2 5 0.00 0.40 1.00 1.40 1x16/25 4.55 0.00 2.02 6.57 3.27 1.07 2.840 0.488 1.29
4 180 1 3 0.40 0.40 0.60 1.00 1x16/25 2.73 2.02 2.02 4.75 3.27 2.80 5.636 1.271 2.56
5 80 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.48 6.112 0.216 2.78
###
2 0.80
2.1 40 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.24 0.238 0.108 0.91
###

102 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : CHUCOS CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)
###
1 48 5 15 0.00 0.00 3.00 3.00 1x16/25 13.64 0.00 0.00 13.64 3.27 2.14 2.142 0.973 0.97
2 68 4 10 0.00 0.00 2.00 2.00 1x16/25 9.09 0.00 0.00 9.09 3.27 2.02 4.164 0.919 1.89
3 80 2 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.43 5.592 0.649 2.54
4 70 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.83 6.425 0.379 2.92
5 90 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.80 7.228 0.365 3.29
###
1 0.97
1.1 45 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.54 0.535 0.243 1.22
1.2 38 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.34 0.875 0.154 1.37
###
3 2.54
3.1 50 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.15 0.149 0.068 2.61
###
###
###
CIRCUITO : C1 ###
###
NUMERO C A R G A CORRIENTE CAIDA DE TENSION
PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)
###
1 88 2 15 0.00 0.50 3.00 3.50 2x16/25 6.82 0.00 2.53 9.34 4.09 3.36 3.363 0.764 0.76
2 80 2 13 0.00 0.50 2.60 3.10 1x16/25 11.82 0.00 2.53 14.34 3.27 3.75 7.117 1.707 2.47
3 86 6 11 0.00 0.50 2.20 2.70 1x16/25 10.00 0.00 2.53 12.53 3.27 3.52 10.642 1.602 4.07
4 80 1 5 0.00 0.50 1.00 1.50 1x16/25 4.55 0.00 2.53 7.07 3.27 1.85 12.493 0.841 4.91
5 85 4 4 0.50 0.50 0.80 1.30 1x16/25 3.64 2.53 2.53 6.16 3.27 1.71 14.206 0.779 5.69
###
2 2.47
2.1 40 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.12 0.119 0.054 2.52
###
###
3 4.07
3.1 80 2 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.71 0.714 0.324 4.40
3.2 80 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.24 0.952 0.108 4.51
###
3 4.07
3.0.1 80 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.48 0.476 0.216 4.29
###
###

103 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : CHUCOS CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V
###
CIRCUITO : C1 ###
###
NUMERO C A R G A CORRIENTE CAIDA DE TENSION
PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)
###
1 43 2 2 0.50 0.50 0.40 0.90 1x16/25 1.82 2.53 2.53 4.34 3.27 0.61 0.611 0.278 0.28
###
###
###
CIRCUITO : C1 ###
###
NUMERO C A R G A CORRIENTE CAIDA DE TENSION
PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)
###
1 62 5 23 1.00 1.00 4.60 5.60 2x16/25 10.45 2.53 2.53 12.98 4.09 3.29 3.291 0.748 0.75
2 70 2 18 0.00 0.00 3.60 3.60 2x16/25 8.18 0.00 0.00 8.18 4.09 2.34 5.634 0.532 1.28
3 160 3 16 0.00 0.00 3.20 3.20 2x16/25 7.27 0.00 0.00 7.27 4.09 4.76 10.393 1.082 2.36
4 150 6 13 0.00 0.00 2.60 2.60 1x16/25 11.82 0.00 0.00 11.82 3.27 5.80 16.194 2.637 5.00
5 60 2 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.25 17.443 0.568 5.57
6 80 5 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.19 18.633 0.541 6.11
###
1 0.75
1.1 70 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.04 1.041 0.473 1.22
1.2 60 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.54 1.577 0.243 1.46
###
2 1.28
2.1 40 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.24 0.238 0.108 1.39
###
4 5.00
4.1 80 1 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.43 1.428 0.649 5.65
4.2 80 4 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.19 2.618 0.541 6.19
4.3 50 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.15 2.766 0.068 6.26
###

104 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : CHUCOS CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 106 8 16 0.50 0.50 3.20 3.70 1x16/25 14.55 2.53 2.53 17.07 3.27 5.92 5.921 2.691 2.69
2 58 6 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 1.38 7.301 0.627 3.32
3 40 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.24 7.539 0.108 3.43

1 2.69
1.1 40 3 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.59 0.595 0.270 2.96
1.2 40 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.24 0.833 0.108 3.07

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 50 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.15 0.149 0.068 0.07

105 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : CHUCOS CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 83 2 15 0.00 0.50 3.00 3.50 2x16/25 6.82 0.00 2.53 9.34 4.09 3.17 3.172 0.721 0.72
2 80 1 13 0.00 0.50 2.60 3.10 1x16/25 11.82 0.00 2.53 14.34 3.27 3.75 6.926 1.707 2.43
3 80 5 12 0.00 0.50 2.40 2.90 1x16/25 10.91 0.00 2.53 13.43 3.27 3.52 10.443 1.598 4.03
4 70 2 7 0.00 0.50 1.40 1.90 1x16/25 6.36 0.00 2.53 8.89 3.27 2.04 12.479 0.925 4.95
5 70 3 5 0.50 0.50 1.00 1.50 1x16/25 4.55 2.53 2.53 7.07 3.27 1.62 14.098 0.736 5.69
6 70 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.42 14.515 0.189 5.88

1 0.72
1.1 45 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.13 0.134 0.061 0.78

3 4.03
3.1 150 5 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 2.23 2.231 1.014 5.04

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 43 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.13 0.128 0.058 0.06

106 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SUCCHA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 0.06 0.062 0.028 0.03
2 45 5 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.80 0.866 0.365 0.39
3 45 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.13 0.999 0.061 0.45

CIRCUITO : C1R

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 83 1 5 0.00 1.20 1.00 2.20 1x16+16/25 4.55 0.00 6.06 10.61 3.27 2.88 2.880 1.309 1.31
2 80 2 4 0.80 1.20 0.80 2.00 1x16+16/25 3.64 4.04 6.06 9.70 3.27 2.54 5.419 1.154 2.46
3 60 0 2 0.40 0.40 0.40 0.80 1x16+16/25 1.82 2.02 2.02 3.84 3.27 0.75 6.172 0.343 2.81
4 50 1 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.30 6.470 0.135 2.94
5 50 1 1 0.00 0.00 0.20 0.20 1x16+16/25 0.91 0.00 0.00 0.91 3.27 0.15 6.618 0.068 3.01

2 2.46
2.1 50 0 2 0.40 0.40 0.40 0.80 1x16+16/25 1.82 2.02 2.02 3.84 3.27 0.63 0.628 0.285 2.75
2.2 50 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.30 0.925 0.135 2.88

107 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SUCCHA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 48 1 20 0.00 0.00 4.00 4.00 1x16+16/25 18.18 0.00 0.00 18.18 3.27 2.86 2.856 1.298 1.30
2 45 9 19 0.00 0.00 3.80 3.80 1x16+16/25 17.27 0.00 0.00 17.27 3.27 2.54 5.399 1.156 2.45
3 40 5 10 0.00 0.00 2.00 2.00 1x16+16/25 9.09 0.00 0.00 9.09 3.27 1.19 6.589 0.541 2.99
4 45 4 5 0.00 0.00 1.00 1.00 1x16+16/25 4.55 0.00 0.00 4.55 3.27 0.67 7.258 0.304 3.30

2 2.45
2.1 25 3 5 0.00 0.00 1.00 1.00 1x16+16/25 4.55 0.00 0.00 4.55 3.27 0.37 0.372 0.169 2.62
2.2 60 1 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.36 0.729 0.162 2.79
2.3 60 1 1 0.00 0.00 0.20 0.20 1x16+16/25 0.91 0.00 0.00 0.91 3.27 0.18 0.907 0.081 2.87

2 2.45
2.0.1 50 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.45 0.446 0.203 2.66

108 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : URANCHACRA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)
###
1 224 8 12 0.00 0.00 2.40 2.40 1x16/25 10.91 0.00 0.00 10.91 3.27 8.00 7.996 3.634 3.63
2 66 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.79 8.781 0.357 3.99
3 67 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.40 9.179 0.181 4.17
###
1 3.63
1.1 128 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 1.14 1.142 0.519 4.15
###
1 3.63
0.1.1 72 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.64 0.643 0.292 3.93
###
###
###
CIRCUITO : C1 ###
###
NUMERO C A R G A CORRIENTE CAIDA DE TENSION
PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)
###
1 59 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.53 0.526 0.239 0.24
###
###
###
CIRCUITO : C1 ###
###
NUMERO C A R G A CORRIENTE CAIDA DE TENSION
PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)
###
1 3 2 9 0.00 0.40 1.80 2.20 1x16/25 8.18 0.00 2.02 10.20 3.27 0.10 0.100 0.046 0.05
2 90 2 7 0.00 0.40 1.40 1.80 1x16/25 6.36 0.00 2.02 8.38 3.27 2.47 2.569 1.122 1.17
3 68 1 5 0.00 0.40 1.00 1.40 1x16/25 4.55 0.00 2.02 6.57 3.27 1.46 4.030 0.664 1.83
4 88 1 4 0.00 0.40 0.80 1.20 1x16/25 3.64 0.00 2.02 5.66 3.27 1.63 5.659 0.740 2.57
5 88 1 3 0.00 0.40 0.60 1.00 1x16/25 2.73 0.00 2.02 4.75 3.27 1.37 7.026 0.621 3.19
6 175 2 2 0.40 0.40 0.40 0.80 1x16/25 1.82 2.02 2.02 3.84 3.27 2.20 9.223 0.999 4.19
###
2 1.17
2.1 48 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.29 0.286 0.130 1.30
###

109 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : URANCHACRA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V
###
###
CIRCUITO : C1 ###
###
NUMERO C A R G A CORRIENTE CAIDA DE TENSION
PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)
###
1 83 1 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.23 1.234 0.561 0.56
2 86 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 1.02 2.258 0.465 1.03
3 58 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.52 2.775 0.235 1.26
###

110 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : URANCHACRA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 173 5 7 0.00 0.40 1.40 1.80 1x16/25 6.36 0.00 2.02 8.38 3.27 4.75 4.746 2.157 2.16
2 171 2 2 0.40 0.40 0.40 0.80 1x16/25 1.82 2.02 2.02 3.84 3.27 2.15 6.893 0.976 3.13

1 2.16
1.1 60 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.54 0.535 0.243 2.40
1.2 82 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.49 1.023 0.222 2.62

1 2.16
1.0.1 85 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.25 0.253 0.115 2.27

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 118 1 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.75 1.755 0.798 0.80
2 84 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 1.00 2.754 0.454 1.25
3 85 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.76 3.513 0.345 1.60
4 85 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.51 4.019 0.230 1.83

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 3 10 0.00 0.00 2.00 2.00 1x16/25 9.09 0.00 0.00 9.09 3.27 0.09 0.089 0.041 0.04
2 65 3 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.35 1.443 0.615 0.66
3 80 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.95 2.395 0.433 1.09

111 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : URANCHACRA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 86 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 1.02 1.023 0.465 0.47

112 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : YURAYACU CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 48 4 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 1.29 1.285 0.584 0.58
2 53 1 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.79 2.073 0.358 0.94
3 53 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.63 2.704 0.287 1.23

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 58 7 14 0.40 1.20 2.80 4.00 1x16+16/25 12.73 2.02 6.06 18.79 3.27 3.57 3.565 1.621 1.62
2 40 2 7 0.00 0.80 1.40 2.20 1x16+16/25 6.36 0.00 4.04 10.40 3.27 1.36 4.927 0.619 2.24
3 40 3 5 0.80 0.80 1.00 1.80 1x16+16/25 4.55 4.04 4.04 8.59 3.27 1.12 6.051 0.511 2.75
4 85 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.51 6.557 0.230 2.98

1 1.62
1.1 55 1 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.49 0.491 0.223 1.84
1.2 55 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.33 0.818 0.149 1.99

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 40 3 8 0.80 1.20 1.60 2.80 1x16+16/25 7.27 4.04 6.06 13.33 3.27 1.75 1.745 0.793 0.79
2 37 5 5 0.40 0.40 1.00 1.40 1x16+16/25 4.55 2.02 2.02 6.57 3.27 0.79 2.540 0.361 1.15

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 2 12 0.00 0.00 2.40 2.40 1x16/25 10.91 0.00 0.00 10.91 3.27 0.11 0.107 0.049 0.05
2 49 4 10 0.00 0.00 2.00 2.00 1x16/25 9.09 0.00 0.00 9.09 3.27 1.46 1.565 0.663 0.71
3 49 2 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.87 2.439 0.398 1.11
4 49 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.58 3.022 0.265 1.37

113 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : CHARAN CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 0 1 0.40 0.80 0.20 1.00 1x16/25 0.91 2.02 4.04 4.95 3.27 0.05 0.049 0.022 0.02
2 140 0 1 0.40 0.40 0.20 0.60 1x16/25 0.91 2.02 2.02 2.93 3.27 1.34 1.390 0.610 0.63
3 80 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.24 1.628 0.108 0.74

2 0.63
2.1 60 0 0 0.40 0.40 0.00 0.40 1x16/25 0.00 2.02 2.02 2.02 3.27 0.40 0.397 0.180 0.81

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 83 2 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.74 0.741 0.337 0.34
2 80 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.24 0.979 0.108 0.44

1 0.34
1.1 40 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.12 0.119 0.054 0.39

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 53 1 3 0.40 0.40 0.60 1.00 1x16+16/25 2.73 2.02 2.02 4.75 3.27 0.82 0.823 0.374 0.37
2 50 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.30 1.121 0.135 0.51

114 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : CHARAN CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 71 1 9 0.00 0.80 1.80 2.60 1x16+16/25 8.18 0.00 4.04 12.22 3.27 2.84 2.839 1.291 1.29
2 73 3 8 0.80 0.80 1.60 2.40 1x16+16/25 7.27 4.04 4.04 11.31 3.27 2.70 5.542 1.228 2.52
3 59 3 5 0.00 0.00 1.00 1.00 1x16+16/25 4.55 0.00 0.00 4.55 3.27 0.88 6.419 0.399 2.92
4 60 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.36 6.776 0.162 3.08

3 2.92
3.1 50 1 1 0.00 0.00 0.20 0.20 1x16+16/25 0.91 0.00 0.00 0.91 3.27 0.15 0.149 0.068 2.99

115 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : CHARAN CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 75 2 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.67 0.669 0.304 0.30
2 70 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.21 0.877 0.095 0.40

1 0.30
1.1 70 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.21 0.208 0.095 0.40

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 3 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.05 0.054 0.024 0.02
2 70 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.62 0.678 0.284 0.31

116 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SANMIGUELDEYAURISH CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 53 3 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.79 0.788 0.358 0.36
2 70 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.42 1.205 0.189 0.55

1 0.36
1.1 25 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.15 0.149 0.068 0.43

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 74 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.44 0.440 0.200 0.20

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 58 1 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.21 1.208 0.549 0.55
2 55 1 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.98 2.189 0.446 1.00
3 55 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.82 3.007 0.372 1.37
4 21 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.19 3.195 0.085 1.45

3 1.37
3.1 55 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.16 0.164 0.074 1.44

117 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : YURA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 2 6 0.00 1.60 1.20 2.80 1x16+16/25 5.45 0.00 8.08 13.54 3.27 0.13 0.133 0.060 0.06
2 41 2 4 0.00 1.60 0.80 2.40 1x16+16/25 3.64 0.00 8.08 11.72 3.27 1.57 1.705 0.714 0.77
3 36 0 2 0.40 1.60 0.40 2.00 1x16+16/25 1.82 2.02 8.08 9.90 3.27 1.17 2.871 0.530 1.30
4 35 1 2 0.40 1.20 0.40 1.60 1x16+16/25 1.82 2.02 6.06 7.88 3.27 0.90 3.773 0.410 1.72
5 37 0 1 0.80 0.80 0.20 1.00 1x16+16/25 0.91 4.04 4.04 4.95 3.27 0.60 4.372 0.272 1.99
6 83 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.25 4.619 0.112 2.10

2 0.77
2.1 60 1 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.36 0.357 0.162 0.94
2.2 62 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 0.541 0.084 1.02

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 224 6 16 0.40 0.40 3.20 3.60 2x16/25 7.27 1.01 1.01 8.28 4.09 7.59 7.588 1.725 1.72
2 59 2 10 0.00 0.00 2.00 2.00 1x16/25 9.09 0.00 0.00 9.09 3.27 1.75 9.343 0.798 2.52
3 85 2 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 2.02 11.366 0.919 3.44
4 107 1 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.91 13.276 0.868 4.31
5 80 1 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.19 14.466 0.541 4.85
6 45 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.54 15.001 0.243 5.09
7 60 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.36 15.358 0.162 5.26

1 1.72
1.1 72 1 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.07 1.071 0.487 2.21
1.2 36 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.43 1.499 0.195 2.41

3 3.44
3.1 55 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.16 0.164 0.074 3.52

6 5.09
6.1 46 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.14 0.137 0.062 5.16

118 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : PONTOVIEJO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 43 0 1 0.40 0.40 0.20 0.60 1x16+16/25 0.91 2.02 2.02 2.93 3.27 0.41 0.412 0.187 0.19
2 60 1 1 0.00 0.00 0.20 0.20 1x16+16/25 0.91 0.00 0.00 0.91 3.27 0.18 0.591 0.081 0.27

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 0 8 0.40 0.80 1.60 2.40 1x16/25 7.27 2.02 4.04 11.31 3.27 0.11 0.111 0.050 0.05
2 100 3 8 0.40 0.40 1.60 2.00 1x16/25 7.27 2.02 2.02 9.29 3.27 3.04 3.152 1.382 1.43
3 120 3 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.78 4.936 0.811 2.24
4 73 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.43 5.371 0.197 2.44

2 1.43
2.1 60 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 0.178 0.081 1.51

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 30 5 13 0.00 0.00 2.60 2.60 1x16+16/25 11.82 0.00 0.00 11.82 3.27 1.16 1.160 0.527 0.53
2 60 2 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 1.43 2.588 0.649 1.18
3 57 4 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.02 3.605 0.462 1.64
4 50 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.30 3.903 0.135 1.77

119 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SANJORGE CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 2 10 0.00 0.40 2.00 2.40 1x16/25 9.09 0.00 2.02 11.11 3.27 0.11 0.109 0.050 0.05
2 60 2 8 0.40 0.40 1.60 2.00 1x16/25 7.27 2.02 2.02 9.29 3.27 1.82 1.933 0.829 0.88
3 60 3 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.07 3.004 0.487 1.37
4 45 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.40 3.406 0.183 1.55
5 55 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.33 3.733 0.149 1.70

3 1.37
3.1 54 1 1 0.00 0.40 0.20 0.60 1x16/25 0.91 0.00 0.00 0.91 3.27 0.16 0.161 0.073 1.44
3.2 54 0 0 0.00 0.40 0.00 0.40 2x25/25 0.00 0.00 0.00 0.00 2.57 0.00 0.161 0.000 1.44

3 1.37
3.01 59 2 2 0.00 0.00 0.40 0.40 2x25/25 0.91 0.00 0.00 0.91 2.57 0.14 0.138 0.031 1.40

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 38 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.11 0.113 0.051 0.05

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 43 2 7 0.40 0.80 1.40 2.20 1x16/25 6.36 2.02 4.04 10.40 3.27 1.46 1.464 0.665 0.67
2 50 2 5 0.40 0.40 1.00 1.40 1x16/25 4.55 2.02 2.02 6.57 3.27 1.07 2.538 0.488 1.15
3 60 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.54 3.073 0.243 1.40

2 1.15
2.1 60 0 0 0.40 0.40 0.00 0.40 1x16/25 0.00 2.02 2.02 2.02 3.27 0.40 0.397 0.180 1.33

120 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SANTAROSADETINCO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 63 0 5 0.40 0.80 1.00 1.80 1x16/25 4.55 2.02 4.04 8.59 3.27 1.77 1.770 0.804 0.80
2 70 1 5 0.40 0.40 1.00 1.40 1x16/25 4.55 2.02 2.02 6.57 3.27 1.50 3.274 0.684 1.49
3 60 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.71 3.988 0.324 1.81
4 70 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.62 4.612 0.284 2.10

1 0.80
1.1 68 1 1 0.40 0.40 0.20 0.60 1x16/25 0.91 2.02 2.02 2.93 3.27 0.65 0.652 0.296 1.10

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 88 4 8 0.40 0.40 1.60 2.00 1x16/25 7.27 2.02 2.02 9.29 3.27 2.68 2.676 1.216 1.22
2 86 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 1.02 3.699 0.465 1.68
3 83 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.49 4.193 0.224 1.91

1 1.22
1.1 51 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.30 0.303 0.138 1.35

1 1.22
1.0.1 50 1 1 0.40 0.40 0.20 0.60 1x16/25 0.91 2.02 2.02 2.93 3.27 0.48 0.479 0.218 1.43

121 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SANTAROSADETINCO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 2 20 0.00 0.00 4.00 4.00 2x16/25 9.09 0.00 0.00 9.09 4.09 0.11 0.112 0.025 0.03
2 83 2 18 0.00 0.00 3.60 3.60 2x16/25 8.18 0.00 0.00 8.18 4.09 2.78 2.889 0.631 0.66
3 85 1 16 0.00 0.00 3.20 3.20 2x16/25 7.27 0.00 0.00 7.27 4.09 2.53 5.417 0.575 1.23
4 85 9 15 0.00 0.00 3.00 3.00 1x16/25 13.64 0.00 0.00 13.64 3.27 3.79 9.210 1.724 2.96
5 59 2 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.05 10.263 0.479 3.43
6 65 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.77 11.036 0.352 3.79
7 65 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.39 11.423 0.176 3.96

4 2.96
4.1 143 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 1.28 1.276 0.580 3.54

4 2.96
4.0.1 85 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.25 0.253 0.115 3.07

6 3.79
6.1 40 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.12 0.119 0.054 3.84

122 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : VINCOCOTA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 73 2 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.65 0.651 0.296 0.30
2 75 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.22 0.875 0.101 0.40

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 186 0 1 0.40 0.80 0.20 1.00 1x16/25 0.91 2.02 4.04 4.95 3.27 3.01 3.012 1.369 1.37
2 34 1 1 0.40 0.40 0.20 0.60 1x16/25 0.91 2.02 2.02 2.93 3.27 0.33 3.338 0.148 1.52

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 5 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 0.08 0.080 0.037 0.04
2 62 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.74 0.818 0.335 0.37

123 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : VINCOCOTA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 82 2 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.46 1.463 0.665 0.67
2 168 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 2.00 3.462 0.909 1.57
3 85 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.76 4.221 0.345 1.92

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 30 1 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 0.62 0.625 0.284 0.28
2 154 1 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 2.75 3.373 1.249 1.53
3 73 5 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.09 4.459 0.494 2.03

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 4 12 0.40 0.40 2.40 2.80 1x16/25 10.91 2.02 2.02 12.93 3.27 0.13 0.127 0.058 0.06
2 57 4 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 1.36 1.483 0.617 0.67

124 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SANROQUEDECHUNAS CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 19 0.00 0.40 3.80 4.20 1x16+16/25 17.27 0.00 2.02 19.29 3.27 0.19 0.189 0.086 0.09
2 35 2 18 0.40 0.40 3.60 4.00 1x16+16/25 16.36 2.02 2.02 18.38 3.27 2.11 2.295 0.957 1.04
3 30 1 16 0.00 0.00 3.20 3.20 1x16+16/25 14.55 0.00 0.00 14.55 3.27 1.43 3.722 0.649 1.69
4 25 2 15 0.00 0.00 3.00 3.00 1x16+16/25 13.64 0.00 0.00 13.64 3.27 1.12 4.838 0.507 2.20
5 30 2 13 0.00 0.00 2.60 2.60 1x16+16/25 11.82 0.00 0.00 11.82 3.27 1.16 5.998 0.527 2.73
6 58.5 4 11 0.00 0.00 2.20 2.20 1x16+16/25 10.00 0.00 0.00 10.00 3.27 1.91 7.912 0.870 3.60
7 34 5 7 0.00 0.00 1.40 1.40 1x16+16/25 6.36 0.00 0.00 6.36 3.27 0.71 8.620 0.322 3.92
8 40 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.24 8.858 0.108 4.03

2 1.04
2.1 26 1 1 0.40 0.40 0.20 0.60 1x16+16/25 0.91 2.02 2.02 2.93 3.27 0.25 0.249 0.113 1.16

125 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SANROQUEDECHUNAS CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 35 3 9 0.48 0.88 1.80 2.68 1x16+16/25 8.18 2.42 4.44 12.63 3.27 1.45 1.446 0.657 0.66
2 35 3 6 0.00 0.40 1.20 1.60 1x16+16/25 5.45 0.00 2.02 7.47 3.27 0.86 2.302 0.389 1.05
3 35 3 3 0.40 0.40 0.60 1.00 1x16+16/25 2.73 2.02 2.02 4.75 3.27 0.54 2.846 0.247 1.29

1 0.66
1.1 59 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.35 0.351 0.160 0.82

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 50 2 7 0.00 0.40 1.40 1.80 1x16+16/25 6.36 0.00 2.02 8.38 3.27 1.37 1.372 0.623 0.62
2 50 2 5 0.40 0.40 1.00 1.40 1x16+16/25 4.55 2.02 2.02 6.57 3.27 1.07 2.446 0.488 1.11
3 50 2 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.45 2.892 0.203 1.31
4 40 1 1 0.00 0.00 0.20 0.20 1x16+16/25 0.91 0.00 0.00 0.91 3.27 0.12 3.011 0.054 1.37

2 1.11
2.1 31 2 2 0.40 0.40 0.40 0.80 1x16+16/25 1.82 2.02 2.02 3.84 3.27 0.39 0.389 0.177 1.29

126 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : CAUCHO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 63 4 19 0.00 0.80 3.80 4.60 1x16+16/25 17.27 0.00 4.04 21.31 3.27 4.39 4.393 1.997 2.00
2 60 4 15 0.00 0.80 3.00 3.80 1x16+16/25 13.64 0.00 4.04 17.68 3.27 3.47 7.864 1.577 3.57
3 55 4 11 0.40 0.80 2.20 3.00 1x16+16/25 10.00 2.02 4.04 14.04 3.27 2.53 10.390 1.149 4.72
4 42 2 7 0.40 0.40 1.40 1.80 1x16+16/25 6.36 2.02 2.02 8.38 3.27 1.15 11.543 0.524 5.25
5 60 3 5 0.00 0.00 1.00 1.00 1x16+16/25 4.55 0.00 0.00 4.55 3.27 0.89 12.435 0.406 5.65
6 60 1 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.36 12.792 0.162 5.81
7 85 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.25 13.045 0.115 5.93

3 4.72
3.1 50 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.45 0.446 0.203 4.93

5 5.65
5.1 80 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.24 0.238 0.108 5.76

5 5.65
0.5.1 60 1 1 0.00 0.00 0.20 0.20 1x16+16/25 0.91 0.00 0.00 0.91 3.27 0.18 0.178 0.081 5.73

127 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : CAUCHO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 20 0.00 0.80 4.00 4.80 1x16+16/25 18.18 0.00 4.04 22.22 3.27 0.22 0.218 0.099 0.10
2 50 6 19 0.00 0.80 3.80 4.60 1x16+16/25 17.27 0.00 4.04 21.31 3.27 3.49 3.705 1.585 1.68
3 36 3 13 0.00 0.80 2.60 3.40 1x16+16/25 11.82 0.00 4.04 15.86 3.27 1.87 5.573 0.849 2.53
4 42 5 10 0.00 0.80 2.00 2.80 1x16+16/25 9.09 0.00 4.04 13.13 3.27 1.80 7.378 0.820 3.35
5 180 1 5 0.80 0.80 1.00 1.80 1x16+16/25 4.55 4.04 4.04 8.59 3.27 5.06 12.434 2.299 5.65
6 90 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 1.07 13.505 0.487 6.14
7 120 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 1.07 14.576 0.487 6.63

2 1.68
2.1 30 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.27 0.268 0.122 1.81

4 3.35
4.1 67 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.80 0.797 0.362 3.72
4.2 67 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.60 1.395 0.272 3.99
4.3 67 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.40 1.794 0.181 4.17

5 5.65
5.1 60 1 1 0.80 0.80 0.20 1.00 1x16+16/25 0.91 4.04 4.04 4.95 3.27 0.97 0.972 0.442 6.09

128 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : CHULLUSH CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 2 15 0.00 1.20 3.00 4.20 1x16+16/25 13.64 0.00 6.06 19.70 3.27 0.19 0.193 0.088 0.09
2 50 3 13 0.00 1.20 2.60 3.80 1x16+16/25 11.82 0.00 6.06 17.88 3.27 2.92 3.118 1.330 1.42
3 50 2 10 0.00 1.20 2.00 3.20 1x16+16/25 9.09 0.00 6.06 15.15 3.27 2.48 5.597 1.127 2.54
4 50 2 8 1.20 1.20 1.60 2.80 1x16+16/25 7.27 6.06 6.06 13.33 3.27 2.18 7.778 0.992 3.54
5 50 4 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.89 8.671 0.406 3.94
6 50 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.30 8.968 0.135 4.08

4 3.54
4.1 50 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.30 0.297 0.135 3.67

5 3.94
5.1 30 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.18 0.178 0.081 4.02

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 52 3 17 0.00 0.00 3.40 3.40 1x16/25 15.45 0.00 0.00 15.45 3.27 2.63 2.629 1.195 1.20
2 49 4 14 0.00 0.00 2.80 2.80 1x16/25 12.73 0.00 0.00 12.73 3.27 2.04 4.670 0.928 2.12
3 50 3 10 0.00 0.00 2.00 2.00 1x16/25 9.09 0.00 0.00 9.09 3.27 1.49 6.157 0.676 2.80
4 100 5 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 2.08 8.239 0.946 3.75
5 50 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.30 8.537 0.135 3.88

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 43 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.51 0.512 0.233 0.23

129 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : LUCMA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 14 0.00 0.00 2.80 2.80 1x16/25 12.73 0.00 0.00 12.73 3.27 0.12 0.125 0.057 0.06
2 60 8 13 0.00 0.00 2.60 2.60 1x16/25 11.82 0.00 0.00 11.82 3.27 2.32 2.445 1.055 1.11
3 80 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.19 3.635 0.541 1.65
4 80 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.71 4.349 0.324 1.98

2 1.11
2.1 50 2 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.89 0.892 0.406 1.52
2.2 50 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.59 1.487 0.270 1.79

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 78 10 19 0.00 0.80 3.80 4.60 1x16/25 17.27 0.00 4.04 21.31 3.27 5.44 5.439 2.472 2.47
2 140 6 9 0.40 0.80 1.80 2.60 1x16/25 8.18 2.02 4.04 12.22 3.27 5.60 11.038 2.545 5.02
3 80 0 3 0.40 0.40 0.60 1.00 1x16/25 2.73 2.02 2.02 4.75 3.27 1.24 12.281 0.565 5.58
4 80 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.71 12.995 0.324 5.91
5 130 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.77 13.768 0.352 6.26

1 2.47
1.1 40 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.48 0.476 0.216 2.69

1 2.47
1.0.1 35 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.31 0.312 0.142 2.61

2 5.02
2.1 75 2 3 0.40 0.40 0.60 1.00 1x16/25 2.73 2.02 2.02 4.75 3.27 1.17 1.165 0.530 5.55
2.2 60 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 1.344 0.081 5.63

130 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : MILLUISH CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 61 11 18 0.00 0.00 3.60 3.60 1x16/25 16.36 0.00 0.00 16.36 3.27 3.27 3.266 1.485 1.48
2 58 3 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.21 4.474 0.549 2.03
3 57 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.68 5.152 0.308 2.34

1 1.48
1.1 72 7 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.50 1.499 0.681 2.17

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 36 5 16 0.00 0.00 3.20 3.20 1x16+16/25 14.55 0.00 0.00 14.55 3.27 1.71 1.713 0.779 0.78
2 33 4 11 0.00 0.00 2.20 2.20 1x16+16/25 10.00 0.00 0.00 10.00 3.27 1.08 2.793 0.491 1.27
3 17 7 7 0.00 0.00 1.40 1.40 1x16+16/25 6.36 0.00 0.00 6.36 3.27 0.35 3.147 0.161 1.43

2 1.27
2.1 33 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.20 0.196 0.089 1.36

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 6 32 0.40 0.80 6.40 7.20 1x16+16/25 29.09 2.02 4.04 33.13 3.27 0.33 0.325 0.148 0.15
2 36 8 26 0.00 0.40 5.20 5.60 1x16+16/25 23.64 0.00 2.02 25.66 3.27 3.02 3.347 1.374 1.52
3 47 3 18 0.00 0.40 3.60 4.00 1x16/25 16.36 0.00 2.02 18.38 3.27 2.83 6.174 1.285 2.81
4 48 6 15 0.00 0.40 3.00 3.40 1x16/25 13.64 0.00 2.02 15.66 3.27 2.46 8.633 1.118 3.92
5 100 8 9 0.00 0.40 1.80 2.20 1x16/25 8.18 0.00 2.02 10.20 3.27 3.34 11.972 1.517 5.44
6 115 1 1 0.40 0.40 0.20 0.60 1x16/25 0.91 2.02 2.02 2.93 3.27 1.10 13.074 0.501 5.94

2 1.52
2.1 34 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.10 0.101 0.046 1.57

131 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : OPAYACO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 2 12 0.00 0.80 2.40 3.20 1x16+16/25 10.91 0.00 4.04 14.95 3.27 0.15 0.147 0.067 0.07
2 46 5 10 0.80 0.80 2.00 2.80 1x16+16/25 9.09 4.04 4.04 13.13 3.27 1.98 2.123 0.898 0.97
3 96 3 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.43 3.551 0.649 1.61
4 56 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.33 3.884 0.151 1.77

2 0.97
2.1 25 4 4 0.80 0.80 0.80 1.60 1x16+16/25 3.64 4.04 4.04 7.68 3.27 0.63 0.628 0.285 1.25

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 54 5 12 0.00 0.80 2.40 3.20 1x16+16/25 10.91 0.00 4.04 14.95 3.27 2.64 2.641 1.201 1.20
2 28 3 7 0.80 0.80 1.40 2.20 1x16+16/25 6.36 4.04 4.04 10.40 3.27 0.95 3.595 0.433 1.63
3 24 4 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.29 3.880 0.130 1.76

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 56 11 24 0.00 0.00 4.80 4.80 1x16+16/25 21.82 0.00 0.00 21.82 3.27 4.00 3.998 1.817 1.82
2 46 5 13 0.00 0.00 2.60 2.60 1x16+16/25 11.82 0.00 0.00 11.82 3.27 1.78 5.777 0.809 2.63
3 46 8 8 0.00 0.00 1.60 1.60 1x16+16/25 7.27 0.00 0.00 7.27 3.27 1.09 6.871 0.498 3.12

1 1.82
1.1 56 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.83 0.833 0.379 2.20
1.2 60 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.54 1.368 0.243 2.44

132 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : OPAYACO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.04 0.045 0.020 0.02
2 47 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.42 0.464 0.191 0.21

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 143 7 12 0.00 0.00 2.40 2.40 1x16/25 10.91 0.00 0.00 10.91 3.27 5.10 5.104 2.320 2.32
2 67 5 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.00 6.101 0.453 2.77

1 2.32
1.1 35 5 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.52 0.521 0.237 2.56

133 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : PACCHA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 56 3 9 0.00 0.00 1.80 1.80 1x16+16/25 8.18 0.00 0.00 8.18 3.27 1.50 1.499 0.681 0.68
2 55 4 6 0.00 0.00 1.20 1.20 1x16+16/25 5.45 0.00 0.00 5.45 3.27 0.98 2.481 0.446 1.13
3 55 1 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.33 2.808 0.149 1.28
4 40 1 1 0.00 0.00 0.20 0.20 1x16+16/25 0.91 0.00 0.00 0.91 3.27 0.12 2.927 0.054 1.33

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 59 7 11 0.00 0.00 2.20 2.20 1x16+16/25 10.00 0.00 0.00 10.00 3.27 1.93 1.930 0.877 0.88
2 55 3 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.65 2.585 0.297 1.17
3 40 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.12 2.704 0.054 1.23

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 4 21 0.00 0.00 4.20 4.20 1x16/25 19.09 0.00 0.00 19.09 3.27 0.19 0.187 0.085 0.09
2 68 3 17 0.00 0.00 3.40 3.40 1x16/25 15.45 0.00 0.00 15.45 3.27 3.44 3.626 1.563 1.65
3 112 9 14 0.00 0.00 2.80 2.80 1x16/25 12.73 0.00 0.00 12.73 3.27 4.66 8.290 2.120 3.77
4 78 5 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.16 9.450 0.527 4.30

2 1.65
2.1 70 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.62 0.625 0.284 1.93

3 3.77
3.1 65 6 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.16 1.160 0.527 4.30

3 3.77
3.0.1 52 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.31 0.309 0.141 3.91

134 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : PUJUN CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 69 3 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.44 1.437 0.653 0.65
2 66 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.79 2.222 0.357 1.01
3 62 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.37 2.591 0.168 1.18

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 3 16 0.00 0.00 3.20 3.20 1x16/25 14.55 0.00 0.00 14.55 3.27 0.14 0.143 0.065 0.06
2 71 3 13 0.00 0.00 2.60 2.60 1x16/25 11.82 0.00 0.00 11.82 3.27 2.75 2.888 1.248 1.31
3 60 2 10 0.00 0.00 2.00 2.00 1x16/25 9.09 0.00 0.00 9.09 3.27 1.78 4.673 0.811 2.12
4 133 4 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 3.16 7.838 1.439 3.56
5 61 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.73 8.564 0.330 3.89
6 119 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.71 9.272 0.322 4.21

2 1.31
2.1 59 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.53 0.526 0.239 1.55

4 3.56
4.1 61 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.36 0.363 0.165 3.73

5 3.89
5.1 58 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.35 0.345 0.157 4.05

135 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : PUJUN CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 75 3 13 0.00 1.00 2.60 3.60 1x16+16/25 11.82 0.00 5.05 16.87 3.27 4.14 4.140 1.882 1.88
2 60 2 10 0.00 1.00 2.00 3.00 1x16+16/25 9.09 0.00 5.05 14.14 3.27 2.78 6.916 1.262 3.14
3 180 2 8 1.00 1.00 1.60 2.60 1x16+16/25 7.27 5.05 5.05 12.32 3.27 7.26 14.174 3.299 6.44
4 33 4 6 0.00 0.00 1.20 1.20 1x16+16/25 5.45 0.00 0.00 5.45 3.27 0.59 14.763 0.268 6.71
5 23 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.14 14.899 0.062 6.77

3 6.44
3.1 30 1 1 0.50 0.50 0.20 0.70 1x16+16/25 0.91 2.53 2.53 3.43 3.27 0.34 0.337 0.153 6.60

136 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : QUISHO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 3 0.40 0.40 0.60 1.00 #N/A 2.73 2.02 2.02 4.75 #N/A #N/A #N/A #N/A #N/A
2 52 2 2 0.00 0.00 0.40 0.40 #N/A 1.82 0.00 0.00 1.82 #N/A #N/A #N/A #N/A #N/A

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 47 4 10 0.40 0.40 2.00 2.40 #N/A 9.09 2.02 2.02 11.11 #N/A #N/A #N/A #N/A #N/A
2 25 4 6 0.00 0.00 1.20 1.20 #N/A 5.45 0.00 0.00 5.45 #N/A #N/A #N/A #N/A #N/A
3 27 2 2 0.00 0.00 0.40 0.40 #N/A 1.82 0.00 0.00 1.82 #N/A #N/A #N/A #N/A #N/A

1 #N/A
1.1 60 1 1 0.00 0.00 0.20 0.20 #N/A 0.91 0.00 0.00 0.91 #N/A #N/A #N/A #N/A #N/A

137 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : QUISHO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 36 8 17 0.80 0.80 3.40 4.20 #N/A 15.45 4.04 4.04 19.49 #N/A #N/A #N/A #N/A #N/A
2 114 1 9 0.00 0.00 1.80 1.80 #N/A 8.18 0.00 0.00 8.18 #N/A #N/A #N/A #N/A #N/A
3 57 2 8 0.00 0.00 1.60 1.60 #N/A 7.27 0.00 0.00 7.27 #N/A #N/A #N/A #N/A #N/A
4 57 3 6 0.00 0.00 1.20 1.20 #N/A 5.45 0.00 0.00 5.45 #N/A #N/A #N/A #N/A #N/A
5 23 3 3 0.00 0.00 0.60 0.60 #N/A 2.73 0.00 0.00 2.73 #N/A #N/A #N/A #N/A #N/A

1 #N/A
1.1 48 1 7 0.00 0.00 1.40 1.40 #N/A 6.36 0.00 0.00 6.36 #N/A #N/A #N/A #N/A #N/A
1.2 48 3 6 0.00 0.00 1.20 1.20 #N/A 5.45 0.00 0.00 5.45 #N/A #N/A #N/A #N/A #N/A
1.3 48 3 3 0.00 0.00 0.60 0.60 #N/A 2.73 0.00 0.00 2.73 #N/A #N/A #N/A #N/A #N/A

1 #N/A
1.0.1 31 1 1 0.00 0.00 0.20 0.20 #N/A 0.91 0.00 0.00 0.91 #N/A #N/A #N/A #N/A #N/A

3 #N/A
3.1 85 2 2 0.00 0.00 0.40 0.40 #N/A 1.82 0.00 0.00 1.82 #N/A #N/A #N/A #N/A #N/A

138 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : RUNTU CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 2 20 0.00 0.00 4.00 4.00 1x16/25 18.18 0.00 0.00 18.18 3.27 0.18 0.178 0.081 0.08
2 60 4 18 0.00 0.00 3.60 3.60 1x16/25 16.36 0.00 0.00 16.36 3.27 3.21 3.391 1.460 1.54
3 60 3 14 0.00 0.00 2.80 2.80 1x16/25 12.73 0.00 0.00 12.73 3.27 2.50 5.890 1.136 2.68
4 56 1 11 0.00 0.00 2.20 2.20 1x16/25 10.00 0.00 0.00 10.00 3.27 1.83 7.722 0.833 3.51
5 63 5 10 0.00 0.00 2.00 2.00 1x16/25 9.09 0.00 0.00 9.09 3.27 1.87 9.596 0.852 4.36
6 86 5 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.28 10.875 0.581 4.94

2 1.54
2.1 83 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.99 0.988 0.449 1.99

5 4.36
5.1 119 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.71 0.708 0.322 4.68

5 4.36
5,0,1 80 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.71 0.714 0.324 4.69

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 47 2 3 0.00 0.40 0.60 1.00 1x16+16/25 2.73 0.00 2.02 4.75 3.27 0.73 0.730 0.332 0.33
2 45 1 1 0.40 0.40 0.20 0.60 1x16+16/25 0.91 2.02 2.02 2.93 3.27 0.43 1.161 0.196 0.53

139 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : RUNTU CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 39 3 6 0.40 0.80 1.20 2.00 1x16+16/25 5.45 2.02 4.04 9.49 3.27 1.21 1.212 0.551 0.55
2 28 3 3 0.40 0.40 0.60 1.00 1x16+16/25 2.73 2.02 2.02 4.75 3.27 0.43 1.647 0.198 0.75

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 221 8 12 0.00 0.00 2.40 2.40 1x16/25 10.91 0.00 0.00 10.91 3.27 7.89 7.888 3.586 3.59
2 160 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 1.90 9.792 0.865 4.45
3 68 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.40 10.197 0.184 4.63

1 3.59
1.1 60 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.71 0.714 0.324 3.91
1.2 86 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.51 1.226 0.233 4.14

140 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : RUNTU CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 123 2 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 2.56 2.561 1.164 1.16
2 46 4 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.68 3.245 0.311 1.48
3 43 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.13 3.373 0.058 1.53

2 1.48
2.1 40 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.24 0.238 0.108 1.58

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 150 3 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 2.68 2.677 1.217 1.22
2 61 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.54 3.221 0.247 1.46

1 1.22
1.1 30 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.27 0.268 0.122 1.34

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 5 11 0.00 0.00 2.20 2.20 1x16/25 10.00 0.00 0.00 10.00 3.27 0.10 0.098 0.045 0.04
2 68 3 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.21 1.312 0.552 0.60
3 28 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.25 1.562 0.114 0.71

141 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SALVIA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 42 6 23 0.40 0.40 4.60 5.00 1x16+16/25 20.91 2.02 2.02 22.93 3.27 3.15 3.151 1.432 1.43
2 39 8 17 0.00 0.00 3.40 3.40 1x16+16/25 15.45 0.00 0.00 15.45 3.27 1.97 5.123 0.896 2.33
3 68 2 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 1.82 6.944 0.827 3.16
4 57 4 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.19 8.130 0.539 3.70
5 40 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.36 8.487 0.162 3.86

1 1.43
1.1 37 3 5 0.00 0.40 1.00 1.40 1x16+16/25 4.55 0.00 2.02 6.57 3.27 0.79 0.795 0.361 1.79
1.2 37 2 2 0.40 0.40 0.40 0.80 1x16+16/25 1.82 2.02 2.02 3.84 3.27 0.46 1.260 0.211 2.00

2 2.33
2.1 30 3 7 0.00 0.00 1.40 1.40 1x16+16/25 6.36 0.00 0.00 6.36 3.27 0.62 0.625 0.284 2.61
2.2 30 4 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.36 0.982 0.162 2.77

142 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SALVIA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 43 2 5 0.00 0.00 1.00 1.00 1x16+16/25 4.55 0.00 0.00 4.55 3.27 0.64 0.640 0.291 0.29
2 40 3 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.36 0.996 0.162 0.45

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 2 2 0.00 0.80 0.40 1.20 1x16+16/25 1.82 0.00 4.04 5.86 3.27 0.06 0.058 0.026 0.03
2 32 0 0 0.80 0.80 0.00 0.80 1x16+16/25 0.00 4.04 4.04 4.04 3.27 0.42 0.481 0.192 0.22

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 37 4 6 0.00 0.00 1.20 1.20 1x16+16/25 5.45 0.00 0.00 5.45 3.27 0.66 0.660 0.300 0.30
2 27 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.16 0.821 0.073 0.37

143 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : VISTAALEGRE(SANMARCOS) CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 4 11 0.00 0.00 2.20 2.20 1x16/25 10.00 0.00 0.00 10.00 3.27 0.10 0.098 0.045 0.04
2 50 2 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.04 1.139 0.473 0.52
3 120 3 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.78 2.924 0.811 1.33
4 53 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.32 3.239 0.143 1.47

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 43 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.26 0.256 0.116 0.12

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 53 1 4 0.00 1.20 0.80 2.00 1x16+16/25 3.64 0.00 6.06 9.70 3.27 1.68 1.682 0.764 0.76
2 50 2 3 0.40 1.20 0.60 1.80 1x16+16/25 2.73 2.02 6.06 8.79 3.27 1.44 3.119 0.653 1.42
3 28 1 1 0.80 0.80 0.20 1.00 1x16+16/25 0.91 4.04 4.04 4.95 3.27 0.45 3.573 0.206 1.62

144 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : VISTAALEGRE(SANMARCOS) CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 48 8 14 0.00 0.00 2.80 2.80 1x16/25 12.73 0.00 0.00 12.73 3.27 2.00 1.999 0.909 0.91
2 60 6 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.07 3.070 0.487 1.40

1 0.91
1.1 60 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.54 0.535 0.243 1.15

1 0.91
1.0.1 45 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.27 0.268 0.122 1.03

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 9 22 0.00 0.00 4.40 4.40 1x16/25 20.00 0.00 0.00 20.00 3.27 0.20 0.196 0.089 0.09
2 55 3 13 0.00 0.00 2.60 2.60 1x16/25 11.82 0.00 0.00 11.82 3.27 2.13 2.323 0.967 1.06
3 67 2 10 0.00 0.00 2.00 2.00 1x16/25 9.09 0.00 0.00 9.09 3.27 1.99 4.316 0.906 1.96
4 67 1 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 1.59 5.910 0.725 2.69
5 66 7 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.37 7.285 0.625 3.31

145 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : COLQUICANCHA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 2 13 0.00 0.00 2.60 2.60 1x16/25 11.82 0.00 0.00 11.82 3.27 0.12 0.116 0.053 0.05
2 40 3 11 0.00 0.00 2.20 2.20 1x16/25 10.00 0.00 0.00 10.00 3.27 1.31 1.425 0.595 0.65
3 40 3 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 0.95 2.377 0.433 1.08
4 38 1 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.57 2.942 0.257 1.34
5 40 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.48 3.418 0.216 1.55
6 85 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.51 3.923 0.230 1.78

5 1.55
5.1 50 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.30 0.297 0.135 1.69

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 15 10 16 0.40 0.40 3.20 3.60 1x16+16/25 14.55 2.02 2.02 16.57 3.27 0.81 0.813 0.370 0.37
2 40 3 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.71 1.527 0.324 0.69
3 55 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.49 2.018 0.223 0.92
4 79 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.47 2.488 0.214 1.13

1 0.37
1.1 13 2 9 0.40 0.40 1.80 2.20 1x16+16/25 8.18 2.02 2.02 10.20 3.27 0.43 0.434 0.197 0.57
1.2 30 3 7 0.00 0.00 1.40 1.40 1x16+16/25 6.36 0.00 0.00 6.36 3.27 0.62 1.059 0.284 0.85
1.3 34 4 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.40 1.463 0.184 1.03

3 0.92
3.1 65 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.19 0.193 0.088 1.01

146 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : CANCHABAMBA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 600 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 54 2 2 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.48 0.482 0.219 0.22

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 44 1 5 0.00 0.00 1.50 1.50 1x16/25 6.82 0.00 0.00 6.82 3.27 0.98 0.982 0.446 0.45
2 45 2 4 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.80 1.785 0.365 0.81
3 45 2 2 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.40 2.186 0.183 0.99

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 55 6 11 0.00 0.00 3.30 3.30 1x16/25 15.00 0.00 0.00 15.00 3.27 2.70 2.699 1.227 1.23
2 47 3 5 0.00 0.00 1.50 1.50 1x16/25 6.82 0.00 0.00 6.82 3.27 1.05 3.748 0.477 1.70
3 48 2 2 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.43 4.176 0.195 1.90

1 1.23
1.1 49 5 5 0.00 0.00 1.50 1.50 1x16/25 6.82 0.00 0.00 6.82 3.27 1.09 1.093 0.497 1.72

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 59 1 6 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 1.58 1.579 0.718 0.72
2 49 1 5 0.00 0.00 1.50 1.50 1x16/25 6.82 0.00 0.00 6.82 3.27 1.09 2.673 0.497 1.21
3 86 1 4 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.53 4.207 0.698 1.91
4 28 3 3 0.00 0.00 0.90 0.90 1x16/25 4.09 0.00 0.00 4.09 3.27 0.37 4.582 0.170 2.08

147 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : CANCHABAMBA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 600 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 13 0.00 0.00 3.90 3.90 1x16/25 17.73 0.00 0.00 17.73 3.27 0.17 0.174 0.079 0.08
2 38 2 12 0.00 0.00 3.60 3.60 1x16/25 16.36 0.00 0.00 16.36 3.27 2.03 2.209 0.925 1.00
3 39 5 10 0.00 0.00 3.00 3.00 1x16/25 13.64 0.00 0.00 13.64 3.27 1.74 3.949 0.791 1.79
4 42 3 5 0.00 0.00 1.50 1.50 1x16/25 6.82 0.00 0.00 6.82 3.27 0.94 4.886 0.426 2.22
5 44 2 2 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.39 5.278 0.178 2.40

3 1.79
3.1 42 3 5 0.00 0.00 1.50 1.50 1x16/25 6.82 0.00 0.00 6.82 3.27 0.94 0.937 0.426 2.22
3.2 41 2 2 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.37 1.303 0.166 2.39

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 44 3 8 0.00 0.00 2.40 2.40 1x16/25 10.91 0.00 0.00 10.91 3.27 1.57 1.571 0.714 0.71
2 42 2 5 0.00 0.00 1.50 1.50 1x16/25 6.82 0.00 0.00 6.82 3.27 0.94 2.508 0.426 1.14
3 43 3 3 0.00 0.00 0.90 0.90 1x16/25 4.09 0.00 0.00 4.09 3.27 0.58 3.083 0.262 1.40

2 1.14
2.1 31 1 1 0.00 0.00 0.30 0.30 1x16/25 1.36 0.00 0.00 1.36 3.27 0.14 0.138 0.063 1.20

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 40 1 5 0.00 0.00 1.50 1.50 1x16/25 6.82 0.00 0.00 6.82 3.27 0.89 0.892 0.406 0.41
2 45 2 4 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.80 1.695 0.365 0.77
3 45 2 2 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.40 2.097 0.183 0.95

1 0.41
1.1 31 1 1 0.00 0.00 0.30 0.30 1x16/25 1.36 0.00 0.00 1.36 3.27 0.14 0.138 0.063 0.47

148 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 3

LOCALIDAD : CANCHABAMBA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 600 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 23 5 15 0.00 0.75 4.50 5.25 2x16+16/25 10.23 0.00 3.79 14.02 4.09 1.32 1.318 0.300 0.30
2 21 2 10 0.00 0.75 3.00 3.75 2x16+16/25 6.82 0.00 3.79 10.61 4.09 0.91 2.229 0.207 0.51
3 45 2 8 0.00 0.75 2.40 3.15 1x16+16/25 10.91 0.00 3.79 14.70 3.27 2.16 4.393 0.984 1.49
4 45 2 6 0.00 0.75 1.80 2.55 1x16+16/25 8.18 0.00 3.79 11.97 3.27 1.76 6.156 0.801 2.29
5 43 3 4 0.00 0.75 1.20 1.95 1x16+16/25 5.45 0.00 3.79 9.24 3.27 1.30 7.456 0.591 2.88
6 37 2 1 0.75 0.75 0.30 1.05 1x16+16/25 1.36 3.79 3.79 5.15 3.27 0.62 8.080 0.283 3.17

1
1.1 40 40 2 5.00 0.00 0.00 1.50 L 1x16+16/25 6.82 0.00 0.00 6.82 3.27 0.892 0.892 0.41
1.2 41 41 2 3.00 0.00 0.00 0.90 L 1x16+16/25 4.09 0.00 0.00 4.09 3.27 0.549 1.441 0.25
1.3 42 42 1 1.00 0.00 0.00 0.30 L 1x16+16/25 1.36 0.00 0.00 1.36 3.27 0.187 1.629 0.09

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 0 17 0.60 2.48 5.10 7.58 1x16+16/25 23.18 3.03 12.53 35.71 3.27 0.35 0.351 0.159 0.16
2 32 0 17 0.60 1.88 5.10 6.98 1x16+16/25 23.18 3.03 9.49 32.68 3.27 3.42 3.772 1.555 1.71
3 34 10 17 0.00 1.28 5.10 6.38 1x16+16/25 23.18 0.00 6.46 29.65 3.27 3.30 7.070 1.499 3.21
4 23 2 7 0.00 1.28 2.10 3.38 1x16+16/25 9.55 0.00 6.46 16.01 3.27 1.20 8.275 0.548 3.76
5 38 3 5 0.00 1.28 1.50 2.78 1x16+16/25 6.82 0.00 6.46 13.28 3.27 1.65 9.926 0.751 4.51
6 40 2 2 1.28 1.28 0.60 1.88 1x16+16/25 2.73 6.46 6.46 9.19 3.27 1.20 11.129 0.547 5.06

3 3.21
3.1 34 5 8 0.00 0.00 2.40 2.40 1x16+16/25 10.91 0.00 0.00 10.91 3.27 1.21 1.214 0.552 3.77
3.2 37 3 3 0.00 0.00 0.90 0.90 1x16+16/25 4.09 0.00 0.00 4.09 3.27 0.50 1.709 0.225 3.99

149 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 3

LOCALIDAD : CANCHABAMBA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 600 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C2

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 23 1 21 0.64 1.24 6.30 7.54 2x16+16/25 14.32 1.62 4.65 18.96 4.09 1.78 1.784 0.405 0.41
2 27 13 20 0.60 0.60 6.00 6.60 1x16+16/25 27.27 3.03 3.03 30.30 3.27 2.68 4.461 1.217 1.62
3 10 1 7 0.00 0.00 2.10 2.10 1x16+16/25 9.55 0.00 0.00 9.55 3.27 0.31 4.773 0.142 1.76
4 45 3 6 0.00 0.00 1.80 1.80 1x16+16/25 8.18 0.00 0.00 8.18 3.27 1.20 5.978 0.548 2.31
5 49 1 3 0.00 0.00 0.90 0.90 1x16+16/25 4.09 0.00 0.00 4.09 3.27 0.66 6.634 0.298 2.61
6 45 2 2 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.40 7.036 0.183 2.79

2 1.62
2.1 46 2 7 0.00 0.00 2.10 2.10 1x16+16/25 9.55 0.00 0.00 9.55 3.27 1.44 1.437 0.653 2.28
2.2 44 4 5 0.00 0.00 1.50 1.50 1x16+16/25 6.82 0.00 0.00 6.82 3.27 0.98 2.418 0.446 2.72
2.3 45 1 1 0.00 0.00 0.30 0.30 1x16+16/25 1.36 0.00 0.00 1.36 3.27 0.20 2.619 0.091 2.81

2 1.62
2.2.1 38 2 2 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.34 0.339 0.154 1.78

2 1.62
2.0.1 19 2 4 0.60 0.60 1.20 1.80 1x16+16/25 5.45 3.03 3.03 8.48 3.27 0.53 0.527 0.240 1.86
2.0.2 34 2 2 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.30 0.831 0.138 2.00

150 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 4

LOCALIDAD : CANCHABAMBA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 600 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 2 36 0.00 1.20 10.80 12.00 2x16+16/25 24.55 0.00 6.06 30.61 4.09 0.38 0.376 0.085 0.09
2 35 4 34 0.00 1.20 10.20 11.40 2x16+16/25 23.18 0.00 6.06 29.24 4.09 4.19 4.562 0.951 1.04
3 22 10 30 0.00 1.20 9.00 10.20 2x16+16/25 20.45 0.00 6.06 26.52 4.09 2.39 6.947 0.542 1.58
4 28 7 20 0.00 1.20 6.00 7.20 2x16+16/25 13.64 0.00 6.06 19.70 4.09 2.26 9.203 0.513 2.09
5 43 6 14 0.00 1.20 4.20 5.40 1x16+16/25 19.09 0.00 6.06 25.15 3.27 3.54 12.742 1.609 3.70
6 43 4 8 1.20 1.20 2.40 3.60 1x16+16/25 10.91 6.06 6.06 16.97 3.27 2.39 15.129 1.085 4.79
7 45 2 4 0.00 0.00 1.20 1.20 1x16+16/25 5.45 0.00 0.00 5.45 3.27 0.80 15.933 0.365 5.15
8 39 2 2 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.35 16.281 0.158 5.31

3 1.58
3.1 23 6 6 0.00 0.00 1.80 1.80 1x16+16/25 8.18 0.00 0.00 8.18 3.27 0.62 0.616 0.280 1.86

4 2.09
4.1 7 2 7 0.00 0.00 2.10 2.10 1x16+16/25 9.55 0.00 0.00 9.55 3.27 0.22 0.219 0.099 2.19
4.2 43 1 5 0.00 0.00 1.50 1.50 1x16+16/25 6.82 0.00 0.00 6.82 3.27 0.96 1.178 0.436 2.63
4.3 42 2 4 0.00 0.00 1.20 1.20 1x16+16/25 5.45 0.00 0.00 5.45 3.27 0.75 1.928 0.341 2.97
4.4 59 2 2 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.53 2.454 0.239 3.21

4 2.09
4.3.1 27 2 2 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.24 0.241 0.110 2.20

7 5.15
7.1 38 1 1 0.00 0.00 0.30 0.30 1x16+16/25 1.36 0.00 0.00 1.36 3.27 0.17 0.170 0.077 5.23

CIRCUITO : C2R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 15 6 9 0.00 0.00 2.70 2.70 1x16+16/25 12.27 0.00 0.00 12.27 3.27 0.60 0.602 0.274 0.27
2 34 3 3 0.00 0.00 0.90 0.90 1x16+16/25 4.09 0.00 0.00 4.09 3.27 0.46 1.057 0.207 0.48

151 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 4

LOCALIDAD : CANCHABAMBA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 600 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C2R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 33 3 16 0.00 0.00 4.80 4.80 1x16+16/25 21.82 0.00 0.00 21.82 3.27 2.36 2.356 1.071 1.07
2 32 3 13 0.00 0.00 3.90 3.90 1x16+16/25 17.73 0.00 0.00 17.73 3.27 1.86 4.212 0.844 1.91
3 31 2 10 0.00 0.00 3.00 3.00 1x16+16/25 13.64 0.00 0.00 13.64 3.27 1.38 5.595 0.629 2.54
4 7 1 8 0.00 0.00 2.40 2.40 1x16+16/25 10.91 0.00 0.00 10.91 3.27 0.25 5.845 0.114 2.66
5 49 4 7 0.00 0.00 2.10 2.10 1x16+16/25 9.55 0.00 0.00 9.55 3.27 1.53 7.375 0.696 3.35
6 51 2 3 0.00 0.00 0.90 0.90 1x16+16/25 4.09 0.00 0.00 4.09 3.27 0.68 8.058 0.310 3.66
7 50 1 1 0.00 0.00 0.30 0.30 1x16+16/25 1.36 0.00 0.00 1.36 3.27 0.22 8.281 0.101 3.76

3 2.54
3.1 36 4 7 0.00 0.00 2.10 2.10 1x16+16/25 9.55 0.00 0.00 9.55 3.27 1.12 1.124 0.511 3.05
3.2 37 1 3 0.00 0.00 0.90 0.90 1x16+16/25 4.09 0.00 0.00 4.09 3.27 0.50 1.620 0.225 3.28
3.3 49 2 2 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.44 2.057 0.199 3.48

CIRCUITO : C2R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 22 2 4 0.60 0.60 1.20 1.80 1x16+16/25 5.45 3.03 3.03 8.48 3.27 0.61 0.611 0.278 0.28
2 39 2 2 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.35 0.959 0.158 0.44

152 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : DINAMARCA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 49 1 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.02 1.020 0.464 0.46
2 30 1 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.54 1.556 0.243 0.71
3 80 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.19 2.746 0.541 1.25
4 215 2 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 1.92 4.664 0.872 2.12
5 80 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.24 4.902 0.108 2.23

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 46 2 14 0.00 0.00 2.80 2.80 1x16/25 12.73 0.00 0.00 12.73 3.27 1.92 1.916 0.871 0.87
2 44 3 12 0.00 0.00 2.40 2.40 1x16/25 10.91 0.00 0.00 10.91 3.27 1.57 3.486 0.714 1.58
3 80 5 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 2.14 5.628 0.973 2.56
4 80 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.95 6.580 0.433 2.99

2 1.58
2.1 30 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.09 0.089 0.041 1.63

3 2.56
3.1 30 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.18 0.178 0.081 2.64

153 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : DINAMARCA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 11 2 16 0.00 0.40 3.20 3.60 1x16+16/25 14.55 0.00 2.02 16.57 3.27 0.60 0.596 0.271 0.27
2 30 6 14 0.40 0.40 2.80 3.20 1x16+16/25 12.73 2.02 2.02 14.75 3.27 1.45 2.044 0.658 0.93
3 45 3 8 0.00 0.00 1.60 1.60 1x16+16/25 7.27 0.00 0.00 7.27 3.27 1.07 3.115 0.487 1.42
4 45 5 5 0.00 0.00 1.00 1.00 1x16+16/25 4.55 0.00 0.00 4.55 3.27 0.67 3.784 0.304 1.72

2 0.93
2.1 35 1 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.42 0.416 0.189 1.12
2.2 35 3 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.31 0.729 0.142 1.26

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 6 0.00 0.40 1.20 1.60 1x16+16/25 5.45 0.00 2.02 7.47 3.27 0.07 0.073 0.033 0.03
2 20 3 5 0.00 0.40 1.00 1.40 1x16+16/25 4.55 0.00 2.02 6.57 3.27 0.43 0.503 0.195 0.23
3 55 2 2 0.40 0.40 0.40 0.80 1x16+16/25 1.82 2.02 2.02 3.84 3.27 0.69 1.194 0.314 0.54

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 43 3 15 0.40 0.40 3.00 3.40 1x16+16/25 13.64 2.02 2.02 15.66 3.27 2.20 2.203 1.001 1.00
2 15 3 12 0.00 0.00 2.40 2.40 1x16+16/25 10.91 0.00 0.00 10.91 3.27 0.54 2.738 0.243 1.24
3 50 2 9 0.00 0.00 1.80 1.80 1x16+16/25 8.18 0.00 0.00 8.18 3.27 1.34 4.077 0.608 1.85
4 70 3 7 0.00 0.00 1.40 1.40 1x16+16/25 6.36 0.00 0.00 6.36 3.27 1.46 5.534 0.663 2.52
5 80 3 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.95 6.486 0.433 2.95
6 40 1 1 0.00 0.00 0.20 0.20 1x16+16/25 0.91 0.00 0.00 0.91 3.27 0.12 6.605 0.054 3.00

3 1.85
3.1 50 1 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.30 0.297 0.135 1.99
3.2 80 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.24 0.535 0.108 2.10

154 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : PAUCA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 58 4 10 0.00 0.00 2.00 2.00 1x16/25 9.09 0.00 0.00 9.09 3.27 1.73 1.725 0.784 0.78
2 71 2 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.27 2.992 0.576 1.36
3 71 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.84 3.837 0.384 1.74

1 0.78
1.1 79 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.70 0.705 0.320 1.10

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 105 0 0 0.80 0.80 0.00 0.80 1x16/25 0.00 4.04 4.04 4.04 3.27 1.39 1.388 0.631 0.63

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 12 0.00 0.00 2.40 2.40 1x16/25 10.91 0.00 0.00 10.91 3.27 0.11 0.107 0.049 0.05
2 70 2 11 0.00 0.00 2.20 2.20 1x16/25 10.00 0.00 0.00 10.00 3.27 2.29 2.397 1.041 1.09
3 107 2 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 2.86 5.262 1.302 2.39
4 49 3 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.02 6.282 0.464 2.86
5 59 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.70 6.984 0.319 3.17

4 2.86
4.1 32 3 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.19 0.190 0.087 2.94

155 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : PAUCA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 73 3 17 0.00 0.00 3.40 3.40 1x16/25 15.45 0.00 0.00 15.45 3.27 3.69 3.691 1.678 1.68
2 75 1 14 0.00 0.00 2.80 2.80 1x16/25 12.73 0.00 0.00 12.73 3.27 3.12 6.815 1.420 3.10
3 72 8 13 0.00 0.00 2.60 2.60 1x16/25 11.82 0.00 0.00 11.82 3.27 2.78 9.599 1.266 4.36
4 70 3 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.04 10.640 0.473 4.84
5 50 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.30 10.937 0.135 4.97

1 1.68
1.1 40 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.12 0.119 0.054 1.73

3 4.36
3.1 60 3 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.71 0.714 0.324 4.69
3.2 50 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.15 0.863 0.068 4.76

3 4.36
3.0.1 120 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 1.07 1.071 0.487 4.85

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 2 5 0.00 0.80 1.00 1.80 1x16+16/25 4.55 0.00 4.04 8.59 3.27 0.08 0.084 0.038 0.04
2 22 3 3 0.40 0.80 0.60 1.40 1x16+16/25 2.73 2.02 4.04 6.77 3.27 0.49 0.571 0.221 0.26

156 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : PAUCA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 38 8 45 0.40 0.40 9.00 9.40 2x16+16/25 20.45 1.01 1.01 21.46 4.09 3.34 3.336 0.758 0.76
2 36 3 37 0.00 0.00 7.40 7.40 2x16+16/25 16.82 0.00 0.00 16.82 4.09 2.48 5.812 0.563 1.32
3 50 11 34 0.00 0.00 6.80 6.80 2x16+16/25 15.45 0.00 0.00 15.45 4.09 3.16 8.973 0.718 2.04
4 46 4 23 0.00 0.00 4.60 4.60 2x16+16/25 10.45 0.00 0.00 10.45 4.09 1.97 10.940 0.447 2.49
5 65 4 19 0.00 0.00 3.80 3.80 1x16/25 17.27 0.00 0.00 17.27 3.27 3.67 14.613 1.670 4.16
6 42 1 15 0.00 0.00 3.00 3.00 1x16/25 13.64 0.00 0.00 13.64 3.27 1.87 16.487 0.852 5.01

1 0.76
1.1 13 4 4 0.40 0.40 0.80 1.20 1x16+16/25 3.64 2.02 2.02 5.66 3.27 0.24 0.241 0.109 0.87

2 1.32
2.1 40 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.12 0.119 0.054 1.38

3 2.04
3.1 39 5 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.58 0.580 0.264 2.30

157 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SANANTONIOJOSEOLAYA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 95 11 22 0.00 0.00 4.40 4.40 1x16+16/25 20.00 0.00 0.00 20.00 3.27 6.22 6.217 2.826 2.83
2 48 1 11 0.00 0.00 2.20 2.20 1x16/25 10.00 0.00 0.00 10.00 3.27 1.57 7.787 0.714 3.54
3 48 1 10 0.00 0.00 2.00 2.00 1x16/25 9.09 0.00 0.00 9.09 3.27 1.43 9.215 0.649 4.19
4 48 5 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 1.29 10.500 0.584 4.77
5 55 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.65 11.155 0.297 5.07
6 55 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.49 11.645 0.223 5.29

1 2.83
1.1 30 6 10 0.00 0.00 2.00 2.00 1x16+16/25 9.09 0.00 0.00 9.09 3.27 0.89 0.892 0.406 3.23
1.2 40 3 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.48 1.368 0.216 3.45
1.3 40 1 1 0.00 0.00 0.20 0.20 1x16+16/25 0.91 0.00 0.00 0.91 3.27 0.12 1.487 0.054 3.50

1.1 3.23
1.1.1 30 3 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.27 0.268 0.122 3.35

4 4.77
4.1 55 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.16 0.164 0.074 4.85

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.04 0.036 0.016 0.02
2 90 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.54 0.571 0.243 0.26

158 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SANANTONIOJOSEOLAYA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 65 1 22 0.00 1.60 4.40 6.00 2x16+16/25 10.00 0.00 4.04 14.04 4.09 3.73 3.733 0.848 0.85
2 63 1 21 0.40 1.60 4.20 5.80 2x16+16/25 9.55 1.01 4.04 13.59 4.09 3.50 7.233 0.796 1.64
3 61 6 20 0.80 1.20 4.00 5.20 2x16+16/25 9.09 2.02 3.03 12.12 4.09 3.02 10.257 0.687 2.33
4 10 2 14 0.00 0.40 2.80 3.20 2x16+16/25 6.36 0.00 1.01 7.37 4.09 0.30 10.559 0.069 2.40
5 35 2 12 0.40 0.40 2.40 2.80 2x16+16/25 5.45 1.01 1.01 6.46 4.09 0.93 11.484 0.210 2.61
6 35 3 10 0.00 0.00 2.00 2.00 1x16/25 9.09 0.00 0.00 9.09 3.27 1.04 12.526 0.473 3.08
7 140 4 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 2.92 15.441 1.325 4.41
8 70 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.62 16.065 0.284 4.69

3 2.33
3.1 44 3 3 0.40 0.40 0.60 1.00 2x16+16/25 1.36 1.01 1.01 2.37 4.09 0.43 0.427 0.097 2.43

7 4.41
7.1 30 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.18 0.178 0.081 4.49

159 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SANJUANDEHUARIPAMPA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 14 0.40 1.60 2.80 4.40 1x16+16/25 12.73 2.02 8.08 20.81 3.27 0.20 0.204 0.093 0.09
2 41 2 13 0.80 1.20 2.60 3.80 1x16+16/25 11.82 4.04 6.06 17.88 3.27 2.40 2.603 1.090 1.18
3 38 2 11 0.00 0.40 2.20 2.60 1x16+16/25 10.00 0.00 2.02 12.02 3.27 1.49 4.097 0.679 1.86
4 37 2 9 0.00 0.40 1.80 2.20 1x16+16/25 8.18 0.00 2.02 10.20 3.27 1.24 5.332 0.561 2.42
5 44 1 7 0.40 0.40 1.40 1.80 1x16+16/25 6.36 2.02 2.02 8.38 3.27 1.21 6.539 0.549 2.97
6 50 3 6 0.00 0.00 1.20 1.20 1x16+16/25 5.45 0.00 0.00 5.45 3.27 0.89 7.432 0.406 3.38
7 52 1 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.46 7.896 0.211 3.59
8 70 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.42 8.312 0.189 3.78

2 1.18
2.1 20 0 0 0.80 0.80 0.00 0.80 1x16+16/25 0.00 4.04 4.04 4.04 3.27 0.26 0.264 0.120 1.30

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 13 16 24 0.00 0.00 4.80 4.80 1x16+16/25 21.82 0.00 0.00 21.82 3.27 0.93 0.928 0.422 0.42
2 112 2 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 2.67 3.593 1.211 1.63
3 56 3 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.00 4.593 0.454 2.09
4 70 2 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.62 5.217 0.284 2.37
5 140 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.42 5.634 0.189 2.56

1 0.42
1.1 38 10 14 0.00 0.00 2.80 2.80 1x16+16/25 12.73 0.00 0.00 12.73 3.27 1.58 1.582 0.719 1.14
1.2 60 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.71 2.296 0.324 1.47
1.3 120 2 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 1.07 3.367 0.487 1.95
1.4 68 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.20 3.569 0.092 2.04
1.1 1.14
1.1.1 10 3 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.18 0.178 0.081 1.22
1.1.2 30 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.27 0.446 0.122 1.34

1.1 1.14
1.0.1 10 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.12 0.119 0.054 1.20
1.0.2 37 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.33 0.449 0.150 1.35

3 2.09
3.1 63 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.56 0.562 0.256 2.34

160 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SANJUANDEHUARIPAMPA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

161 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : SANJUANDEHUARIPAMPA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 83 3 8 0.00 0.00 1.60 1.60 1x16+16/25 7.27 0.00 0.00 7.27 3.27 1.98 1.975 0.898 0.90
2 60 2 5 0.00 0.00 1.00 1.00 1x16+16/25 4.55 0.00 0.00 4.55 3.27 0.89 2.867 0.406 1.30
3 80 1 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.71 3.581 0.324 1.63
4 80 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.48 4.057 0.216 1.84

2 1.30
2.1 60 1 1 0.00 0.00 0.20 0.20 1x16+16/25 0.91 0.00 0.00 0.91 3.27 0.18 0.178 0.081 1.38

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 82 2 10 0.00 0.00 2.00 2.00 1x16/25 9.09 0.00 0.00 9.09 3.27 2.44 2.439 1.109 1.11
2 78 3 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 1.86 4.295 0.844 1.95
3 80 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.19 5.485 0.541 2.49
4 60 2 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.54 6.020 0.243 2.74
5 60 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 6.199 0.081 2.82

1 1.11
1.1 40 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.12 0.119 0.054 1.16

2 1.95
2.1 30 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.09 0.089 0.041 1.99

162 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : TUNANMARCA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 2 16 0.40 0.40 3.20 3.60 1x16/25 14.55 2.02 2.02 16.57 3.27 0.16 0.163 0.074 0.07
2 48 1 14 0.00 0.00 2.80 2.80 1x16/25 12.73 0.00 0.00 12.73 3.27 2.00 2.162 0.909 0.98
3 40 2 13 0.00 0.00 2.60 2.60 1x16/25 11.82 0.00 0.00 11.82 3.27 1.55 3.708 0.703 1.69
4 40 5 11 0.00 0.00 2.20 2.20 1x16/25 10.00 0.00 0.00 10.00 3.27 1.31 5.017 0.595 2.28
5 59 1 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.05 6.070 0.479 2.76
6 60 4 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.89 6.962 0.406 3.16
7 50 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.15 7.111 0.068 3.23

3 1.69
3.1 60 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.36 0.357 0.162 1.85

4 2.28
4.1 36 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.43 0.428 0.195 2.48

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 42 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.12 0.125 0.057 0.06

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 111 3 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 2.64 2.641 1.201 1.20
2 50 5 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.74 3.385 0.338 1.54

163 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : TUNANMARCA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 28 12 35 1.60 2.00 7.00 9.00 2x16+16/25 15.91 4.04 5.05 20.96 4.09 2.40 2.400 0.546 0.55
2 18 3 23 0.00 0.40 4.60 5.00 2x16+16/25 10.45 0.00 1.01 11.46 4.09 0.84 3.244 0.192 0.74
3 53 2 20 0.40 0.40 4.00 4.40 2x16+16/25 9.09 1.01 1.01 10.10 4.09 2.19 5.434 0.498 1.23
4 58 4 18 0.00 0.00 3.60 3.60 2x16+16/25 8.18 0.00 0.00 8.18 4.09 1.94 7.375 0.441 1.68
5 80 4 14 0.00 0.00 2.80 2.80 1x16/25 12.73 0.00 0.00 12.73 3.27 3.33 10.706 1.514 3.19
6 80 5 10 0.00 0.00 2.00 2.00 1x16/25 9.09 0.00 0.00 9.09 3.27 2.38 13.086 1.082 4.27
7 60 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.89 13.978 0.406 4.68
8 60 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.54 14.514 0.243 4.92

1 0.55
1.1 36 2 6 0.40 1.20 1.20 2.40 1x16+16/25 5.45 2.02 6.06 11.52 3.27 1.36 1.356 0.617 1.16
1.2 40 4 4 0.80 0.80 0.80 1.60 1x16+16/25 3.64 4.04 4.04 7.68 3.27 1.00 2.361 0.457 1.62

1 0.55
1.0.1 40 3 5 0.40 0.40 1.00 1.40 1x16+16/25 4.55 2.02 2.02 6.57 3.27 0.86 0.859 0.391 0.94
1.0.2 40 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.24 1.097 0.108 1.04

4 1.68
4.1 60 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 0.178 0.081 1.76

5 3.19
5.1 40 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.24 0.238 0.108 3.30

164 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : TUNANMARCA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 2 22 0.00 0.40 4.40 4.80 1x16/25 20.00 0.00 2.02 22.02 3.27 0.22 0.216 0.098 0.10
2 40 10 20 0.00 0.40 4.00 4.40 1x16/25 18.18 0.00 2.02 20.20 3.27 2.64 2.860 1.202 1.30
3 80 0 10 0.40 0.40 2.00 2.40 1x16/25 9.09 2.02 2.02 11.11 3.27 2.91 5.769 1.322 2.62
4 80 3 10 0.00 0.00 2.00 2.00 1x16/25 9.09 0.00 0.00 9.09 3.27 2.38 8.148 1.082 3.70
5 80 3 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.67 9.814 0.757 4.46
6 70 3 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.83 10.647 0.379 4.84
7 60 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 10.825 0.081 4.92

2 1.30
2.1 40 1 10 0.00 0.00 2.00 2.00 1x16/25 9.09 0.00 0.00 9.09 3.27 1.19 1.190 0.541 1.84
2.2 60 2 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 1.61 2.796 0.730 2.57
2.3 150 4 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 3.12 5.919 1.420 3.99
2.4 70 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.62 6.544 0.284 4.27

2.3 3.99
2.3.1 42 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.37 0.375 0.170 4.16

5 4.46
5.1 125 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.37 0.372 0.169 4.63

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 48 4 5 0.00 0.00 1.00 1.00 1x16+16/25 4.55 0.00 0.00 4.55 3.27 0.71 0.714 0.324 0.32
2 47 1 1 0.00 0.00 0.20 0.20 1x16+16/25 0.91 0.00 0.00 0.91 3.27 0.14 0.854 0.064 0.39

165 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : UMBE CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 26 3 12 0.00 0.00 2.40 2.40 1x16+16/25 10.91 0.00 0.00 10.91 3.27 0.93 0.928 0.422 0.42
2 20 2 9 0.00 0.00 1.80 1.80 1x16+16/25 8.18 0.00 0.00 8.18 3.27 0.54 1.463 0.243 0.67
3 10 4 7 0.00 0.00 1.40 1.40 1x16+16/25 6.36 0.00 0.00 6.36 3.27 0.21 1.672 0.095 0.76
4 32 3 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.29 1.957 0.130 0.89

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 22 9 35 0.80 0.80 7.00 7.80 2x16+16/25 15.91 2.02 2.02 17.93 4.09 1.61 1.613 0.367 0.37
2 45 1 26 0.00 0.00 5.20 5.20 2x16/25 11.82 0.00 0.00 11.82 4.09 2.18 3.788 0.494 0.86
3 40 4 25 0.00 0.00 5.00 5.00 2x16/25 11.36 0.00 0.00 11.36 4.09 1.86 5.648 0.423 1.28
4 60 2 21 0.00 0.00 4.20 4.20 2x16/25 9.55 0.00 0.00 9.55 4.09 2.34 7.990 0.532 1.82
5 60 6 19 0.00 0.00 3.80 3.80 1x16/25 17.27 0.00 0.00 17.27 3.27 3.39 11.381 1.541 3.36
6 60 1 13 0.00 0.00 2.60 2.60 1x16/25 11.82 0.00 0.00 11.82 3.27 2.32 13.701 1.055 4.41
7 60 4 12 0.00 0.00 2.40 2.40 1x16/25 10.91 0.00 0.00 10.91 3.27 2.14 15.843 0.973 5.39
8 35 1 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 0.83 16.676 0.379 5.76
9 35 3 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 0.73 17.404 0.331 6.10
10 32 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.38 17.785 0.173 6.27

1 0.37
1.1 30 6 6 0.00 0.80 1.20 2.00 1x16+16/25 5.45 0.00 4.04 9.49 3.27 0.93 0.932 0.424 0.79
1.2 38 0 0 0.80 0.80 0.00 0.80 1x16+16/25 0.00 4.04 4.04 4.04 3.27 0.50 1.434 0.228 1.02

5 3.36
5.1 30 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.27 0.268 0.122 3.48

7 5.39
7.1 60 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.54 0.535 0.243 5.63

166 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : UMBE CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C2R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 2 6 0.40 0.40 1.20 1.60 1x16/25 5.45 2.02 2.02 7.47 3.27 0.07 0.073 0.033 0.03
2 27 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.32 0.395 0.146 0.18
3 90 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.54 0.930 0.243 0.42

CIRCUITO : C2

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 22 19 46 0.80 0.80 9.20 10.00 2x16+16/25 20.91 2.02 2.02 22.93 4.09 2.06 2.063 0.469 0.47
2 48 18 27 0.00 0.00 5.40 5.40 1x16/25 24.55 0.00 0.00 24.55 3.27 3.86 5.918 1.752 2.22
3 40 3 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 1.07 6.989 0.487 2.71
4 45 3 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.80 7.792 0.365 3.07
5 45 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.40 8.194 0.183 3.26
6 32 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.19 8.384 0.087 3.34

1 0.47
1.1 10 3 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 0.21 0.208 0.095 0.56
1.2 60 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.71 0.922 0.324 0.89
1.3 60 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.36 1.279 0.162 1.05

1 0.47
1.0.1 10 2 8 0.00 0.80 1.60 2.40 1x16+16/25 7.27 0.00 4.04 11.31 3.27 0.37 0.370 0.168 0.64
1.0.2 20 3 6 0.80 0.80 1.20 2.00 1x16+16/25 5.45 4.04 4.04 9.49 3.27 0.62 0.992 0.282 0.92
1.0.3 20 3 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.18 1.170 0.081 1.00

2 2.22
2.1 25 5 12 0.00 0.00 2.40 2.40 1x16/25 10.91 0.00 0.00 10.91 3.27 0.89 0.892 0.406 2.63
2.2 10 3 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 0.21 1.101 0.095 2.72
2.3 50 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.59 1.695 0.270 2.99
2.4 50 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.45 2.142 0.203 3.19

2 2.22
2.0.1 45 3 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.80 0.803 0.365 2.59
2.0.2 45 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.40 1.205 0.183 2.77

2.1 2.63
2.1.1 100 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 1.19 1.190 0.541 3.17

167 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : VILLAFLORES CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 213 2 2 0.40 0.40 0.40 0.80 1x16/25 1.82 2.02 2.02 3.84 3.27 2.68 2.675 1.216 1.22

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 2 5 0.40 0.80 1.00 1.80 1x16/25 4.55 2.02 4.04 8.59 3.27 0.08 0.084 0.038 0.04
2 120 3 3 0.40 0.40 0.60 1.00 1x16/25 2.73 2.02 2.02 4.75 3.27 1.86 1.948 0.847 0.89

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 51 3 7 0.00 0.80 1.40 2.20 1x16+16/25 6.36 0.00 4.04 10.40 3.27 1.74 1.736 0.789 0.79
2 42 1 4 0.00 0.80 0.80 1.60 1x16+16/25 3.64 0.00 4.04 7.68 3.27 1.05 2.791 0.480 1.27
3 47 1 3 0.40 0.80 0.60 1.40 1x16+16/25 2.73 2.02 4.04 6.77 3.27 1.04 3.832 0.473 1.74
4 35 2 2 0.40 0.40 0.40 0.80 1x16+16/25 1.82 2.02 2.02 3.84 3.27 0.44 4.271 0.200 1.94

168 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : VILLAFLORES CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 38 8 23 0.40 0.80 4.60 5.40 1x16+16/25 20.91 2.02 4.04 24.95 3.27 3.10 3.102 1.410 1.41
2 45 3 15 0.40 0.40 3.00 3.40 1x16+16/25 13.64 2.02 2.02 15.66 3.27 2.31 5.407 1.048 2.46
3 45 2 12 0.00 0.00 2.40 2.40 1x16+16/25 10.91 0.00 0.00 10.91 3.27 1.61 7.014 0.730 3.19
4 45 5 10 0.00 0.00 2.00 2.00 1x16+16/25 9.09 0.00 0.00 9.09 3.27 1.34 8.352 0.608 3.80
5 35 3 5 0.00 0.00 1.00 1.00 1x16+16/25 4.55 0.00 0.00 4.55 3.27 0.52 8.873 0.237 4.03
6 35 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.21 9.081 0.095 4.13

1 1.41
1.1 45 2 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.80 0.803 0.365 1.78
1.2 50 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.59 1.398 0.270 2.05
1.3 50 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.45 1.844 0.203 2.25

1 1.41
1.0.1 43 1 1 0.00 0.40 0.20 0.60 1x16/25 0.91 0.00 2.02 2.93 3.27 0.41 0.412 0.187 1.60
1.0.2 35 0 0 0.40 0.40 0.00 0.40 1x16/25 0.00 2.02 2.02 2.02 3.27 0.23 0.643 0.105 1.70

1.0.1 1.60
1.0.1.1 35 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.10 0.104 0.047 1.64

169 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : ALTAVALLE CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 38 17 32 1.20 1.20 6.40 7.60 1x16+16/25 29.09 6.06 6.06 35.15 3.27 4.37 4.371 1.987 1.99
2 48 6 15 0.00 0.00 3.00 3.00 1x16+16/25 13.64 0.00 0.00 13.64 3.27 2.14 6.512 0.973 2.96
3 48 4 9 0.00 0.00 1.80 1.80 1x16+16/25 8.18 0.00 0.00 8.18 3.27 1.29 7.797 0.584 3.54
4 53 2 5 0.00 0.00 1.00 1.00 1x16+16/25 4.55 0.00 0.00 4.55 3.27 0.79 8.586 0.358 3.90
5 50 1 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.45 9.032 0.203 4.11
6 50 1 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.30 9.329 0.135 4.24
7 50 1 1 0.00 0.00 0.20 0.20 1x16+16/25 0.91 0.00 0.00 0.91 3.27 0.15 9.478 0.068 4.31

1 1.99
1.1 48 4 5 0.80 1.20 1.00 2.20 1x16+16/25 4.55 4.04 6.06 10.61 3.27 1.67 1.666 0.757 2.74
1.2 103 0 1 0.40 0.40 0.20 0.60 1x16+16/25 0.91 2.02 2.02 2.93 3.27 0.99 2.653 0.449 3.19
1.3 50 1 1 0.00 0.00 0.20 0.20 1x16+16/25 0.91 0.00 0.00 0.91 3.27 0.15 2.802 0.068 3.26

1.1 2.74
1.1.1 35 3 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.31 0.312 0.142 2.89

1 1.99
1.0.1 54 2 10 0.00 0.00 2.00 2.00 1x16+16/25 9.09 0.00 0.00 9.09 3.27 1.61 1.606 0.730 2.72
1.0.2 20 3 8 0.00 0.00 1.60 1.60 1x16+16/25 7.27 0.00 0.00 7.27 3.27 0.48 2.082 0.216 2.93
1.0.3 58 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.86 2.945 0.392 3.33
1.0.3 90 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.80 3.748 0.365 3.69

2 2.96
2.1 35 2 5 0.00 0.00 1.00 1.00 1x16+16/25 4.55 0.00 0.00 4.55 3.27 0.52 0.521 0.237 3.20
2.2 35 3 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.31 0.833 0.142 3.34

3 3.54
3.1 8 1 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.07 0.071 0.032 3.58
3.2 35 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.21 0.280 0.095 3.67

170 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : ALTAVALLE CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 4 26 0.00 1.20 5.20 6.40 1x16+16/25 23.64 0.00 6.06 29.70 3.27 0.29 0.292 0.133 0.13
2 35 10 22 0.40 1.20 4.40 5.60 1x16+16/25 20.00 2.02 6.06 26.06 3.27 2.98 3.276 1.357 1.49
3 7 1 12 0.00 0.80 2.40 3.20 1x16+16/25 10.91 0.00 4.04 14.95 3.27 0.34 3.618 0.156 1.64
4 32 1 11 0.00 0.80 2.20 3.00 1x16+16/25 10.00 0.00 4.04 14.04 3.27 1.47 5.088 0.668 2.31
5 8 3 10 0.00 0.80 2.00 2.80 1x16+16/25 9.09 0.00 4.04 13.13 3.27 0.34 5.432 0.156 2.47
6 60 2 7 0.80 0.80 1.40 2.20 1x16+16/25 6.36 4.04 4.04 10.40 3.27 2.04 7.475 0.928 3.40
7 101 5 5 0.00 0.00 1.00 1.00 1x16+16/25 4.55 0.00 0.00 4.55 3.27 1.50 8.977 0.683 4.08

2 1.49
2.1 100 2 5 0.40 0.40 1.00 1.40 1x16+16/25 4.55 2.02 2.02 6.57 3.27 2.15 2.148 0.976 2.47
2.2 55 3 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.49 2.639 0.223 2.69

2 1.49
0.2.1 60 1 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.71 0.714 0.324 1.81
0.2.2 55 3 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.49 1.205 0.223 2.04

5 2.47
5.1 50 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.30 0.297 0.135 2.60

171 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : ARARAYOC CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 78 3 12 0.40 0.80 2.40 3.20 1x16+16/25 10.91 2.02 4.04 14.95 3.27 3.82 3.815 1.734 1.73
2 44 4 9 0.40 0.40 1.80 2.20 1x16+16/25 8.18 2.02 2.02 10.20 3.27 1.47 5.284 0.668 2.40
3 62 3 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.92 6.206 0.419 2.82
4 80 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.48 6.682 0.216 3.04

2 2.40
2.1 59 3 3 0.40 0.40 0.60 1.00 1x16/25 2.73 2.02 2.02 4.75 3.27 0.92 0.916 0.417 2.82

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 63 1 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.37 0.375 0.170 0.17
2 80 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.24 0.613 0.108 0.28

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 16 0.00 0.00 3.20 3.20 1x16/25 14.55 0.00 0.00 14.55 3.27 0.14 0.143 0.065 0.06
2 64 3 15 0.00 0.00 3.00 3.00 1x16/25 13.64 0.00 0.00 13.64 3.27 2.86 2.998 1.298 1.36
3 60 4 12 0.00 0.00 2.40 2.40 1x16/25 10.91 0.00 0.00 10.91 3.27 2.14 5.140 0.973 2.34
4 75 3 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 1.78 6.925 0.811 3.15
5 70 1 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.04 7.966 0.473 3.62
6 60 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.71 8.680 0.324 3.95
7 60 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.36 9.037 0.162 4.11

3 2.34
3.1 62 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.37 0.369 0.168 2.50

4 3.15
4.1 75 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.45 0.446 0.203 3.35

172 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : COCHABAMBADELROSARIO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 38 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.23 0.226 0.103 0.10

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 4 13 0.00 0.00 2.60 2.60 1x16/25 11.82 0.00 0.00 11.82 3.27 0.12 0.116 0.053 0.05
2 50 5 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 1.34 1.455 0.608 0.66
3 62 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.74 2.192 0.335 1.00

2 0.66
2.1 42 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.25 0.250 0.114 0.77

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 59 1 13 0.00 0.00 2.60 2.60 1x16+16/25 11.82 0.00 0.00 11.82 3.27 2.28 2.281 1.037 1.04
2 61 6 12 0.00 0.00 2.40 2.40 1x16+16/25 10.91 0.00 0.00 10.91 3.27 2.18 4.459 0.990 2.03
3 121 3 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 2.16 6.618 0.982 3.01
4 85 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.76 7.377 0.345 3.35

2 2.03
2.1 67 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.60 0.598 0.272 2.30

173 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : COCHABAMBADELROSARIO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 39 3 25 0.00 1.00 5.00 6.00 1x16+16/25 22.73 0.00 5.05 27.78 3.27 3.54 3.545 1.611 1.61
2 67 16 22 0.50 1.00 4.40 5.40 1x16+16/25 20.00 2.53 5.05 25.05 3.27 5.49 9.036 2.496 4.11
3 8 2 6 0.00 0.50 1.20 1.70 1x16/25 5.45 0.00 2.53 7.98 3.27 0.21 9.245 0.095 4.20
4 38 1 4 0.00 0.50 0.80 1.30 1x16/25 3.64 0.00 2.53 6.16 3.27 0.77 10.011 0.348 4.55
5 10 1 3 0.50 0.50 0.60 1.10 1x16/25 2.73 2.53 2.53 5.25 3.27 0.17 10.183 0.078 4.63
6 79 1 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.47 10.653 0.214 4.84
7 80 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.24 10.891 0.108 4.95

2 4.11
2.1 30 4 8 0.00 0.50 1.60 2.10 1x16+16/25 7.27 0.00 2.53 9.80 3.27 0.96 0.962 0.437 4.54
2.2 30 4 4 0.50 0.50 0.80 1.30 1x16+16/25 3.64 2.53 2.53 6.16 3.27 0.60 1.567 0.275 4.82

2 4.11
2.0.1 49 5 5 0.00 0.00 1.00 1.00 1x16+16/25 4.55 0.00 0.00 4.55 3.27 0.73 0.729 0.331 4.44

5 4.63
5.1 71 1 1 0.50 0.50 0.20 0.70 1x16/25 0.91 2.53 2.53 3.43 3.27 0.80 0.798 0.363 4.99

174 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : COCHABAMBADELROSARIO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 36 3 17 0.00 0.50 3.40 3.90 1x16+16/25 15.45 0.00 2.53 17.98 3.27 2.12 2.118 0.963 0.96
2 12 6 14 0.00 0.50 2.80 3.30 1x16+16/25 12.73 0.00 2.53 15.25 3.27 0.60 2.717 0.272 1.23
3 32 2 8 0.50 0.50 1.60 2.10 1x16+16/25 7.27 2.53 2.53 9.80 3.27 1.03 3.743 0.466 1.70
4 24 4 6 0.00 0.00 1.20 1.20 1x16+16/25 5.45 0.00 0.00 5.45 3.27 0.43 4.171 0.195 1.90
5 30 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.18 4.349 0.081 1.98

2 1.23
2.1 53 4 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.63 0.631 0.287 1.52

4 1.90
4.1 27 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.16 0.161 0.073 1.97

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 41 10 19 1.48 1.98 3.80 5.78 1x16+16/25 17.27 7.47 10.00 27.27 3.27 3.66 3.659 1.663 1.66
2 10 5 9 0.00 0.50 1.80 2.30 1x16+16/25 8.18 0.00 2.53 10.71 3.27 0.35 4.009 0.159 1.82
3 82 1 4 0.00 0.50 0.80 1.30 1x16+16/25 3.64 0.00 2.53 6.16 3.27 1.65 5.662 0.751 2.57
4 42 3 3 0.00 0.50 0.60 1.10 1x16+16/25 2.73 0.00 2.53 5.25 3.27 0.72 6.384 0.328 2.90
5 115 0 0 0.50 0.50 0.00 0.50 1x16+16/25 0.00 2.53 2.53 2.53 3.27 0.95 7.334 0.432 3.33

1 1.66
1.1 44 3 9 0.50 0.50 1.80 2.30 1x16+16/25 8.18 2.53 2.53 10.71 3.27 1.54 1.541 0.701 2.36
1.2 42 3 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.75 2.291 0.341 2.70
1.3 70 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.62 2.916 0.284 2.99

175 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : COCHABAMBADELROSARIO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C2

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 2 39 0.00 1.50 7.80 9.30 2x16+16/25 17.73 0.00 5.05 22.78 4.09 0.28 0.279 0.064 0.06
2 13 7 37 0.00 1.50 7.40 8.90 2x16+16/25 16.82 0.00 5.05 21.87 4.09 1.16 1.442 0.264 0.33
3 42 5 30 0.50 1.50 6.00 7.50 2x16+16/25 13.64 1.26 5.05 18.69 4.09 3.21 4.652 0.730 1.06
4 41 12 25 0.50 1.00 5.00 6.00 2x16+16/25 11.36 1.26 3.79 15.15 4.09 2.54 7.193 0.577 1.63
5 30 4 13 0.00 0.50 2.60 3.10 1x16+16/25 11.82 0.00 2.53 14.34 3.27 1.41 8.601 0.640 2.27
6 40 2 9 0.00 0.50 1.80 2.30 1x16+16/25 8.18 0.00 2.53 10.71 3.27 1.40 10.002 0.637 2.91
7 39 4 7 0.00 0.50 1.40 1.90 1x16+16/25 6.36 0.00 2.53 8.89 3.27 1.13 11.137 0.516 3.43
8 42 3 3 0.50 0.50 0.60 1.10 1x16+16/25 2.73 2.53 2.53 5.25 3.27 0.72 11.858 0.328 3.76

2 0.33
2.1 51 4 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.61 0.607 0.276 0.60

4 1.63
4.1 10 1 8 0.00 0.50 1.60 2.10 1x16+16/25 7.27 0.00 2.53 9.80 3.27 0.32 0.321 0.146 1.78
4.2 46 4 7 0.50 0.50 1.40 1.90 1x16+16/25 6.36 2.53 2.53 8.89 3.27 1.34 1.658 0.608 2.39
4.3 55 3 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.49 2.149 0.223 2.61

4.2 2.39
4.2.1 53 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.32 0.315 0.143 2.53

176 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : MICAELABASTIDAS CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 0 11 0.40 0.40 2.20 2.60 1x16+16/25 10.00 2.02 2.02 12.02 3.27 0.12 0.118 0.054 0.05
2 25 7 11 0.00 0.00 2.20 2.20 1x16+16/25 10.00 0.00 0.00 10.00 3.27 0.82 0.936 0.372 0.43
3 58 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.69 1.626 0.314 0.74
4 60 2 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.54 2.162 0.243 0.98
5 82 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.24 2.405 0.111 1.09

2 0.43
2.1 60 5 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.89 0.892 0.406 0.83

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 43 5 15 0.80 1.20 3.00 4.20 1x16+16/25 13.64 4.04 6.06 19.70 3.27 2.77 2.771 1.260 1.26
2 22 3 10 0.40 0.40 2.00 2.40 1x16+16/25 9.09 2.02 2.02 11.11 3.27 0.80 3.571 0.364 1.62
3 44 1 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 0.92 4.487 0.416 2.04
4 222 2 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 3.96 8.449 1.801 3.84
5 66 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.79 9.235 0.357 4.20
6 48 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.43 9.663 0.195 4.39

1 1.26
1.1 66 3 5 0.80 0.80 1.00 1.80 1x16/25 4.55 4.04 4.04 8.59 3.27 1.85 1.854 0.843 2.10
1.2 60 1 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.36 2.211 0.162 2.26
1.3 59 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 2.387 0.080 2.34

177 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : PIRUSHTO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 0 14 0.90 1.70 2.80 4.50 1x16+16/25 12.73 4.55 8.59 21.31 3.27 0.21 0.209 0.095 0.10
2 30 1 14 0.40 0.80 2.80 3.60 1x16+16/25 12.73 2.02 4.04 16.77 3.27 1.65 1.855 0.748 0.84
3 22 3 13 0.00 0.40 2.60 3.00 1x16+16/25 11.82 0.00 2.02 13.84 3.27 1.00 2.851 0.453 1.30
4 40 1 10 0.00 0.40 2.00 2.40 1x16+16/25 9.09 0.00 2.02 11.11 3.27 1.45 4.305 0.661 1.96
5 35 2 9 0.00 0.40 1.80 2.20 1x16+16/25 8.18 0.00 2.02 10.20 3.27 1.17 5.474 0.531 2.49
6 35 3 7 0.40 0.40 1.40 1.80 1x16+16/25 6.36 2.02 2.02 8.38 3.27 0.96 6.434 0.436 2.92
7 35 4 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.42 6.850 0.189 3.11

3 1.30
3.1 104 2 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.93 0.928 0.422 1.72
3.2 60 1 1 0.00 0.00 0.20 0.20 1x16+16/25 0.91 0.00 0.00 0.91 3.27 0.18 1.107 0.081 1.80

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 13 12 25 0.80 2.00 5.00 7.00 1x16+16/25 22.73 4.04 10.10 32.83 3.27 1.40 1.396 0.635 0.63
2 42 7 13 0.40 1.20 2.60 3.80 1x16+16/25 11.82 2.02 6.06 17.88 3.27 2.46 3.853 1.117 1.75
3 60 3 6 0.00 0.80 1.20 2.00 1x16/25 5.45 0.00 4.04 9.49 3.27 1.86 5.717 0.847 2.60
4 60 1 3 0.00 0.80 0.60 1.40 1x16/25 2.73 0.00 4.04 6.77 3.27 1.33 7.046 0.604 3.20
5 60 2 2 0.80 0.80 0.40 1.20 1x16/25 1.82 4.04 4.04 5.86 3.27 1.15 8.196 0.523 3.73

1 0.63
1.1 40 2 10 0.80 0.80 2.00 2.80 1x16+16/25 9.09 4.04 4.04 13.13 3.27 1.72 1.719 0.781 1.42
1.2 41 6 8 0.00 0.00 1.60 1.60 1x16+16/25 7.27 0.00 0.00 7.27 3.27 0.98 2.694 0.443 1.86
1.3 10 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.06 2.754 0.027 1.89
1.1 1.42
1.1.1 15 0 0 0.40 0.40 0.00 0.40 1x16+16/25 0.00 2.02 2.02 2.02 3.27 0.10 0.099 0.045 1.46

1.2 1.86
1.2.1 17 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.05 0.051 0.023 1.88

2 1.75
2.1 32 3 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.29 0.286 0.130 1.88

178 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SANTACRUZDECARARCA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 18 1 5 0.00 0.40 1.00 1.40 1x16/25 4.55 0.00 2.02 6.57 3.27 0.39 0.387 0.176 0.18
2 60 1 4 0.40 0.40 0.80 1.20 1x16/25 3.64 2.02 2.02 5.66 3.27 1.11 1.497 0.505 0.68
3 80 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.71 2.211 0.324 1.01

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 26 4 4 0.00 1.20 0.80 2.00 1x16+16/25 3.64 0.00 6.06 9.70 3.27 0.82 0.825 0.375 0.37
2 40 0 0 0.80 1.20 0.00 1.20 1x16+16/25 0.00 4.04 6.06 6.06 3.27 0.79 1.618 0.361 0.74
3 30 0 0 0.40 0.40 0.00 0.40 1x16+16/25 0.00 2.02 2.02 2.02 3.27 0.20 1.816 0.090 0.83

1 0.37
1.1 20 3 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.18 0.178 0.081 0.46

179 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SANTACRUZDECARARCA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 14 1 23 0.00 0.40 4.60 5.00 1x16+16/25 20.91 0.00 2.02 22.93 3.27 1.05 1.050 0.477 0.48
2 30 5 22 0.40 0.40 4.40 4.80 1x16+16/25 20.00 2.02 2.02 22.02 3.27 2.16 3.212 0.983 1.46
3 14 3 17 0.00 0.00 3.40 3.40 1x16+16/25 15.45 0.00 0.00 15.45 3.27 0.71 3.920 0.322 1.78
4 65 2 14 0.00 0.00 2.80 2.80 1x16+16/25 12.73 0.00 0.00 12.73 3.27 2.71 6.627 1.230 3.01
5 12 5 12 0.00 0.00 2.40 2.40 1x16+16/25 10.91 0.00 0.00 10.91 3.27 0.43 7.055 0.195 3.21
6 24 5 7 0.00 0.00 1.40 1.40 1x16+16/25 6.36 0.00 0.00 6.36 3.27 0.50 7.555 0.227 3.43
7 39 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.23 7.787 0.105 3.54

2 1.46
2.1 25 2 5 0.00 0.40 1.00 1.40 1x16+16/25 4.55 0.00 2.02 6.57 3.27 0.54 0.537 0.244 1.70
2.2 40 3 3 0.40 0.40 0.60 1.00 1x16+16/25 2.73 2.02 2.02 4.75 3.27 0.62 1.158 0.282 1.99

5 3.21
5.1 35 1 1 0.00 0.00 0.20 0.20 1x16+16/25 0.91 0.00 0.00 0.91 3.27 0.10 0.104 0.047 3.25

180 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1
OCULTAR
LOCALIDAD : SHIRACAYOC OCULTAR CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )
SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 OCULTAR TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE OCULTAR SISTEMA: 440/220 V
OCULTAR
CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA FORMACION I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) DEL CONDUCTOR (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 3 4 29 0.00 0.40 5.80 6.20 L 1x16+16/25 26.36 0.00 2.02 28.38 3.27 0.28 0.279 0.127 0.13
2 42 11 25 0.40 0.40 5.00 5.40 L 1x16+16/25 22.73 2.02 2.02 24.75 3.27 3.40 3.680 1.546 1.67
3 40 5 14 0.00 0.00 2.80 2.80 L 1x16+16/25 12.73 0.00 0.00 12.73 3.27 1.67 5.345 0.757 2.43
4 38 5 9 0.00 0.00 1.80 1.80 L 1x16+16/25 8.18 0.00 0.00 8.18 3.27 1.02 6.363 0.462 2.89
5 55 1 4 0.00 0.00 0.80 0.80 M 1x16/25 3.64 0.00 0.00 3.64 3.27 0.65 7.017 0.297 3.19
6 80 1 3 0.00 0.00 0.60 0.60 M 1x16/25 2.73 0.00 0.00 2.73 3.27 0.71 7.731 0.324 3.51
7 80 2 2 0.00 0.00 0.40 0.40 M 1x16/25 1.82 0.00 0.00 1.82 3.27 0.48 8.207 0.216 3.73

2 1.67
2.1 7 2 9 0.00 0.00 1.80 1.80 L 1x16+16/25 8.18 0.00 0.00 8.18 3.27 0.19 0.187 0.085 1.76
2.2 33 2 7 0.00 0.00 1.40 1.40 L 1x16+16/25 6.36 0.00 0.00 6.36 3.27 0.69 0.875 0.312 2.07
2.3 20 5 5 0.00 0.00 1.00 1.00 L 1x16+16/25 4.55 0.00 0.00 4.55 3.27 0.30 1.172 0.135 2.21

4 2.89
4.1 110 2 2 0.00 0.00 0.40 0.40 M 1x16/25 1.82 0.00 0.00 1.82 3.27 0.65 0.654 0.297 3.19

4 2.89
4.0.1 100 2 2 0.00 0.00 0.40 0.40 M 1x16/25 1.82 0.00 0.00 1.82 3.27 0.59 0.595 0.270 3.16

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA FORMACION I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) DEL CONDUCTOR (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 15 0 2 0.40 1.20 0.40 1.60 L 1x16+16/25 1.82 2.02 6.06 7.88 3.27 0.39 0.387 0.176 0.18
2 30 2 2 0.40 0.80 0.40 1.20 L 1x16+16/25 1.82 2.02 4.04 5.86 3.27 0.58 0.962 0.261 0.44
3 45 0 0 0.40 0.40 0.00 0.40 L 1x16+16/25 0.00 2.02 2.02 2.02 3.27 0.30 1.259 0.135 0.57

181 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1
OCULTAR
LOCALIDAD : SHIRACAYOC OCULTAR CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )
SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 OCULTAR TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE OCULTAR SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA FORMACION I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) DEL CONDUCTOR (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) (A) (A) (A) (A)

1 44 2 25 0.00 0.00 5.00 5.00 L 1x16+16/25 22.73 0.00 0.00 22.73 3.27 3.27 3.272 1.487 1.49
2 3 9 23 0.00 0.00 4.60 4.60 L 1x16+16/25 20.91 0.00 0.00 20.91 3.27 0.21 3.477 0.093 1.58
3 53 5 14 0.00 0.00 2.80 2.80 L 1x16+16/25 12.73 0.00 0.00 12.73 3.27 2.21 5.684 1.003 2.58
4 54 2 9 0.00 0.00 1.80 1.80 L 1x16+16/25 8.18 0.00 0.00 8.18 3.27 1.45 7.130 0.657 3.24
5 140 1 7 0.00 0.00 1.40 1.40 L 1x16+16/25 6.36 0.00 0.00 6.36 3.27 2.92 10.045 1.325 4.57
6 60 2 6 0.00 0.00 1.20 1.20 M 1x16/25 5.45 0.00 0.00 5.45 3.27 1.07 11.116 0.487 5.05
7 50 4 4 0.00 0.00 0.80 0.80 M 1x16/25 3.64 0.00 0.00 3.64 3.27 0.59 11.711 0.270 5.32

2 1.58
2.1 5 2 5 0.00 0.00 1.00 1.00 M 1x16/25 4.55 0.00 0.00 4.55 3.27 0.07 0.074 0.034 1.61
2.2 87 1 3 0.00 0.00 0.60 0.60 M 1x16/25 2.73 0.00 0.00 2.73 3.27 0.78 0.851 0.353 1.97
2.3 67 1 2 0.00 0.00 0.40 0.40 M 1x16/25 1.82 0.00 0.00 1.82 3.27 0.40 1.249 0.181 2.15
2.4 87 1 1 0.00 0.00 0.20 0.20 M 1x16/25 0.91 0.00 0.00 0.91 3.27 0.26 1.508 0.118 2.27

2 1.58
2.0.1 55 3 4 0.00 0.00 0.80 0.80 L 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.65 0.654 0.297 1.88
2.0.2 45 1 1 0.00 0.00 0.20 0.20 L 1x16+16/25 0.91 0.00 0.00 0.91 3.27 0.13 0.788 0.061 1.94

182 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : LALIBERTADDEHUACAN CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 2 10 0.00 0.00 2.00 2.00 1x16+16/25 9.09 0.00 0.00 9.09 3.27 0.09 0.089 0.041 0.04
2 25 5 8 0.00 0.00 1.60 1.60 1x16+16/25 7.27 0.00 0.00 7.27 3.27 0.59 0.684 0.270 0.31
3 70 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.62 1.309 0.284 0.59
4 70 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.42 1.725 0.189 0.78

2 0.31
2.1 43 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.51 0.512 0.233 0.54

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 63 2 6 0.00 1.20 1.20 2.40 1x16/25 5.45 0.00 6.06 11.52 3.27 2.37 2.374 1.079 1.08
2 67 1 4 0.00 1.20 0.80 2.00 1x16/25 3.64 0.00 6.06 9.70 3.27 2.13 4.499 0.966 2.05
3 91 1 3 0.40 1.20 0.60 1.80 1x16/25 2.73 2.02 6.06 8.79 3.27 2.62 7.116 1.189 3.23
4 64 1 2 0.00 0.80 0.40 1.20 1x16/25 1.82 0.00 4.04 5.86 3.27 1.23 8.343 0.558 3.79
5 45 1 1 0.80 0.80 0.20 1.00 1x16/25 0.91 4.04 4.04 4.95 3.27 0.73 9.072 0.331 4.12

1 1.08
1.1 47 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.14 0.140 0.064 1.14

4 3.79
4.1 64 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.19 0.190 0.087 3.88

183 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : LALIBERTADDEHUACAN CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 35 9 15 0.40 0.80 3.00 3.80 1x16+16/25 13.64 2.02 4.04 17.68 3.27 2.02 2.024 0.920 0.92
2 32 2 6 0.00 0.40 1.20 1.60 1x16+16/25 5.45 0.00 2.02 7.47 3.27 0.78 2.807 0.356 1.28
3 56 1 4 0.00 0.40 0.80 1.20 1x16/25 3.64 0.00 2.02 5.66 3.27 1.04 3.843 0.471 1.75
4 56 2 3 0.00 0.40 0.60 1.00 1x16/25 2.73 0.00 2.02 4.75 3.27 0.87 4.713 0.395 2.14
5 56 1 1 0.40 0.40 0.20 0.60 1x16/25 0.91 2.02 2.02 2.93 3.27 0.54 5.250 0.244 2.39

1 0.92
1.1 18 2 5 0.00 0.40 1.00 1.40 1x16+16/25 4.55 0.00 2.02 6.57 3.27 0.39 0.387 0.176 1.10
1.2 55 1 3 0.40 0.40 0.60 1.00 1x16+16/25 2.73 2.02 2.02 4.75 3.27 0.85 1.241 0.388 1.48
1.3 55 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.33 1.568 0.149 1.63

4 2.14
4.1 56 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.17 0.167 0.076 2.22

184 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : QUICHIRAGRA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 600 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 38 1 18 0.60 0.60 5.40 6.00 2x16+16/25 12.27 1.52 1.52 13.79 4.09 2.14 2.143 0.487 0.49
2 16 6 17 0.00 0.00 5.10 5.10 2x16+16/25 11.59 0.00 0.00 11.59 4.09 0.76 2.901 0.172 0.66
3 130 3 11 0.00 0.00 3.30 3.30 2x16/25 7.50 0.00 0.00 7.50 4.09 3.99 6.889 0.906 1.57
4 230 2 8 0.00 0.00 2.40 2.40 2x16/25 5.45 0.00 0.00 5.45 4.09 5.13 12.020 1.166 2.73
5 80 2 6 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 2.14 14.162 0.973 3.71
6 125 4 4 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 2.23 16.393 1.014 4.72

2 0.66
2.1 35 1 6 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 0.94 0.937 0.426 1.09
2.2 35 2 5 0.00 0.00 1.50 1.50 1x16/25 6.82 0.00 0.00 6.82 3.27 0.78 1.718 0.355 1.44
2.3 60 1 3 0.00 0.00 0.90 0.90 1x16/25 4.09 0.00 0.00 4.09 3.27 0.80 2.521 0.365 1.81
2.4 70 1 2 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.62 3.146 0.284 2.09
2.5 70 1 1 0.00 0.00 0.30 0.30 1x16/25 1.36 0.00 0.00 1.36 3.27 0.31 3.458 0.142 2.23

2.4 2.09
2.4.1 30 1 1 0.00 0.00 0.30 0.30 1x16/25 1.36 0.00 0.00 1.36 3.27 0.13 0.134 0.061 2.15

185 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : QUICHIRAGRA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 600 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 6 0.60 0.60 1.80 2.40 1x16+16/25 8.18 3.03 3.03 11.21 3.27 0.11 0.110 0.050 0.05
2 30 2 5 0.00 0.00 1.50 1.50 1x16+16/25 6.82 0.00 0.00 6.82 3.27 0.67 0.779 0.304 0.35
3 32 3 3 0.00 0.00 0.90 0.90 1x16+16/25 4.09 0.00 0.00 4.09 3.27 0.43 1.208 0.195 0.55

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 21 2 2 0.60 0.60 0.60 1.20 1x16+16/25 2.73 3.03 3.03 5.76 3.27 0.40 0.396 0.180 0.18

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 78 1 3 0.00 0.00 0.90 0.90 1x16/25 4.09 0.00 0.00 4.09 3.27 1.04 1.044 0.475 0.47
2 74 2 2 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.66 1.704 0.300 0.77

186 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : QUICHIRAGRA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 600 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 36 1 27 0.00 1.80 8.10 9.90 2x16+16/25 18.41 0.00 6.06 24.47 4.09 3.60 3.603 0.819 0.82
2 19 11 26 1.20 1.80 7.80 9.60 2x16+16/25 17.73 3.03 6.06 23.79 4.09 1.85 5.451 0.420 1.24
3 40 3 15 0.00 0.60 4.50 5.10 1x16+16/25 20.45 0.00 3.03 23.48 3.27 3.07 8.525 1.397 2.64
4 40 5 12 0.60 0.60 3.60 4.20 1x16+16/25 16.36 3.03 3.03 19.39 3.27 2.54 11.063 1.154 3.79
5 41 7 7 0.00 0.00 2.10 2.10 1x16+16/25 9.55 0.00 0.00 9.55 3.27 1.28 12.344 0.582 4.37

2 1.24
2.1 39 3 8 0.60 1.20 2.40 3.60 1x16+16/25 10.91 3.03 6.06 16.97 3.27 2.17 2.165 0.984 2.22
2.2 46 2 5 0.60 0.60 1.50 2.10 1x16+16/25 6.82 3.03 3.03 9.85 3.27 1.48 3.648 0.674 2.90
2.3 32 3 3 0.00 0.00 0.90 0.90 1x16+16/25 4.09 0.00 0.00 4.09 3.27 0.43 4.076 0.195 3.09

2.1 2.22
2.1.1 30 2 2 0.60 0.60 0.60 1.20 1x16+16/25 2.73 3.03 3.03 5.76 3.27 0.57 0.565 0.257 2.48

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 2 0.00 1.24 0.60 1.84 1x16+16/25 2.73 0.00 6.26 8.99 3.27 0.09 0.088 0.040 0.04
2 24 1 1 1.24 1.24 0.30 1.54 1x16+16/25 1.36 6.26 6.26 7.63 3.27 0.60 0.687 0.272 0.31

187 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : QUICHIRAGRA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 600 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C2

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 32 23 39 0.00 0.00 11.70 11.70 2x16+16/25 26.59 0.00 0.00 26.59 4.09 3.48 3.480 0.791 0.79
2 49 2 16 0.00 0.00 4.80 4.80 1x16+16/25 21.82 0.00 0.00 21.82 3.27 3.50 6.978 1.590 2.38
3 50 8 14 0.00 0.00 4.20 4.20 1x16+16/25 19.09 0.00 0.00 19.09 3.27 3.12 10.102 1.420 3.80
4 67 6 6 0.00 0.00 1.80 1.80 1x16+16/25 8.18 0.00 0.00 8.18 3.27 1.79 11.895 0.815 4.62

1 0.79
1.1 10 4 19 0.00 0.00 5.70 5.70 1x16+16/25 25.91 0.00 0.00 25.91 3.27 0.85 0.848 0.385 1.18
1.2 39 6 15 0.00 0.00 4.50 4.50 1x16+16/25 20.45 0.00 0.00 20.45 3.27 2.61 3.458 1.186 2.36
1.3 38 5 9 0.00 0.00 2.70 2.70 1x16+16/25 12.27 0.00 0.00 12.27 3.27 1.53 4.984 0.694 3.06
1.4 44 4 4 0.00 0.00 1.20 1.20 1x16+16/25 5.45 0.00 0.00 5.45 3.27 0.79 5.769 0.357 3.41

1 0.79
1.0.1 10 4 4 0.00 0.00 1.20 1.20 1x16+16/25 5.45 0.00 0.00 5.45 3.27 0.18 0.178 0.081 0.87

3 3.80
3.1 5 1 3 0.00 0.00 0.90 0.90 1x16+16/25 4.09 0.00 0.00 4.09 3.27 0.07 0.067 0.030 3.83
3.2 50 2 2 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.45 0.513 0.203 4.03

3 3.80
3.0.1 63 2 2 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.56 0.562 0.256 4.06

188 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SANJUAN CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.04 0.036 0.016 0.02
2 60 2 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.54 0.571 0.243 0.26
3 60 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 0.750 0.081 0.34

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 83 4 32 0.00 0.00 6.40 6.40 2x16/25 14.55 0.00 0.00 14.55 4.09 4.94 4.938 1.122 1.12
2 81 10 28 0.00 0.00 5.60 5.60 2x16/25 12.73 0.00 0.00 12.73 4.09 4.22 9.154 0.958 2.08
3 137 2 18 0.00 0.00 3.60 3.60 2x16/25 8.18 0.00 0.00 8.18 4.09 4.58 13.739 1.042 3.12
4 65 6 16 0.00 0.00 3.20 3.20 1x16/25 14.55 0.00 0.00 14.55 3.27 3.09 16.832 1.406 4.53
5 86 3 10 0.00 0.00 2.00 2.00 1x16/25 9.09 0.00 0.00 9.09 3.27 2.56 19.390 1.163 5.69
6 74 3 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.54 20.931 0.700 6.39
7 110 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 1.31 22.240 0.595 6.99

1 1.12
1.1 60 2 2 0.00 0.00 0.40 0.40 2x16/25 0.91 0.00 0.00 0.91 4.09 0.22 0.223 0.051 1.17

2 2.08
2.1 55 1 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 1.31 1.309 0.595 2.68
2.2 62 3 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.29 2.600 0.587 3.26
2.3 62 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.74 3.337 0.335 3.60
2.4 65 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.58 3.917 0.264 3.86

2.2 3.26
2.2.1 45 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.27 0.268 0.122 3.38

4 4.53
4.1 68 5 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.01 1.011 0.460 4.99

189 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SANJUAN CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 120 2 26 0.00 1.20 5.20 6.40 2x16+16/25 11.82 0.00 5.05 16.87 4.09 8.28 8.279 1.882 1.88
2 54 7 24 0.40 1.20 4.80 6.00 2x16+16/25 10.91 1.01 5.05 15.96 4.09 3.52 11.804 0.801 2.68
3 60 10 17 0.00 0.80 3.40 4.20 2x16+16/25 7.73 0.00 4.04 11.77 4.09 2.89 14.692 0.656 3.34
4 38 3 7 0.80 0.80 1.40 2.20 1x16/25 6.36 4.04 4.04 10.40 3.27 1.29 15.985 0.588 3.93
5 55 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.65 16.640 0.297 4.22
6 56 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.33 16.973 0.151 4.38

2 2.68
2.1 37 4 4 0.00 0.00 0.80 0.80 2x16+16/25 1.82 0.00 0.00 1.82 4.09 0.28 0.275 0.063 2.75

3 3.34
3.1 60 1 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.89 0.892 0.406 3.74
3.2 50 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.59 1.487 0.270 4.02
3.3 75 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.67 2.157 0.304 4.32
3.4 60 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.36 2.513 0.162 4.48

190 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SANTAROSADECHINGAS CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 15 0 9 0.40 0.40 1.80 2.20 1x16+16/25 8.18 2.02 2.02 10.20 3.27 0.50 0.501 0.228 0.23
2 34 4 9 0.00 0.00 1.80 1.80 1x16+16/25 8.18 0.00 0.00 8.18 3.27 0.91 1.411 0.414 0.64
3 7 2 5 0.00 0.00 1.00 1.00 1x16+16/25 4.55 0.00 0.00 4.55 3.27 0.10 1.515 0.047 0.69
4 30 3 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.27 1.783 0.122 0.81

2 0.64
2.1 15 1 1 0.00 0.00 0.20 0.20 1x16+16/25 0.91 0.00 0.00 0.91 3.27 0.04 0.045 0.020 0.66

2 0.64
0.2.1 26 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.15 0.155 0.070 0.71

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 53 2 8 0.00 0.40 1.60 2.00 1x16+16/25 7.27 0.00 2.02 9.29 3.27 1.61 1.612 0.733 0.73
2 10 1 6 0.00 0.40 1.20 1.60 1x16+16/25 5.45 0.00 2.02 7.47 3.27 0.24 1.856 0.111 0.84
3 48 1 5 0.00 0.40 1.00 1.40 1x16+16/25 4.55 0.00 2.02 6.57 3.27 1.03 2.887 0.469 1.31
4 38 2 4 0.00 0.40 0.80 1.20 1x16+16/25 3.64 0.00 2.02 5.66 3.27 0.70 3.591 0.320 1.63
5 135 0 2 0.40 0.40 0.40 0.80 1x16/25 1.82 2.02 2.02 3.84 3.27 1.70 5.286 0.771 2.40
6 87 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.52 5.804 0.235 2.64

1 0.73
1.1 45 1 1 0.00 0.00 0.20 0.20 1x16+16/25 0.91 0.00 0.00 0.91 3.27 0.13 0.134 0.061 0.79

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 14 3 5 0.00 0.00 1.00 1.00 1x16+16/25 4.55 0.00 0.00 4.55 3.27 0.21 0.208 0.095 0.09
2 35 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.21 0.416 0.095 0.19

191 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SANTAROSADECHINGAS CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 30 0.00 1.20 6.00 7.20 1x16+16/25 27.27 0.00 6.06 33.33 3.27 0.33 0.327 0.149 0.15
2 40 12 29 1.20 1.20 5.80 7.00 1x16+16/25 26.36 6.06 6.06 32.42 3.27 4.24 4.571 1.929 2.08
3 36 4 17 0.00 0.00 3.40 3.40 1x16+16/25 15.45 0.00 0.00 15.45 3.27 1.82 6.391 0.827 2.91
4 36 2 13 0.00 0.00 2.60 2.60 1x16+16/25 11.82 0.00 0.00 11.82 3.27 1.39 7.783 0.633 3.54
5 12 1 11 0.00 0.00 2.20 2.20 1x16+16/25 10.00 0.00 0.00 10.00 3.27 0.39 8.176 0.178 3.72
6 28 4 10 0.00 0.00 2.00 2.00 1x16+16/25 9.09 0.00 0.00 9.09 3.27 0.83 9.009 0.379 4.09
7 30 6 6 0.00 0.00 1.20 1.20 1x16+16/25 5.45 0.00 0.00 5.45 3.27 0.54 9.544 0.243 4.34

2 2.08
2.1 12 2 10 0.40 0.40 2.00 2.40 1x16+16/25 9.09 2.02 2.02 11.11 3.27 0.44 0.436 0.198 2.28
2.2 30 1 8 0.00 0.00 1.60 1.60 1x16+16/25 7.27 0.00 0.00 7.27 3.27 0.71 1.150 0.324 2.60
2.3 10 2 7 0.00 0.00 1.40 1.40 1x16+16/25 6.36 0.00 0.00 6.36 3.27 0.21 1.358 0.095 2.70
2.4 30 3 5 0.00 0.00 1.00 1.00 1x16+16/25 4.55 0.00 0.00 4.55 3.27 0.45 1.805 0.203 2.90
2.5 40 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.24 2.043 0.108 3.01

2 2.08
0.2.1 12 1 1 0.40 0.40 0.20 0.60 1x16+16/25 0.91 2.02 2.02 2.93 3.27 0.12 0.115 0.052 2.13

4 3.54
4.1 15 1 1 0.00 0.00 0.20 0.20 1x16+16/25 0.91 0.00 0.00 0.91 3.27 0.04 0.045 0.020 3.56

192 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : ALTOISARA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 35 7 17 0.40 0.40 3.40 3.80 1x16/25 15.45 2.02 2.02 17.47 3.27 2.00 2.001 0.910 0.91
2 225 1 10 0.00 0.00 2.00 2.00 1x16/25 9.09 0.00 0.00 9.09 3.27 6.69 8.694 3.042 3.95
3 81 3 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 2.17 10.862 0.986 4.94
4 70 3 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.25 12.112 0.568 5.51
5 150 2 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 1.34 13.450 0.608 6.11
6 50 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.15 13.599 0.068 6.18

1 0.91
1.1 40 1 6 0.40 0.40 1.20 1.60 1x16/25 5.45 2.02 2.02 7.47 3.27 0.98 0.978 0.445 1.35
1.2 222 3 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 3.30 4.280 1.501 2.86
1.3 80 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.48 4.756 0.216 3.07

1.2 2.86
1.2.1 50 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.15 0.149 0.068 2.92

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 9 0.40 0.40 1.80 2.20 1x16+16/25 8.18 2.02 2.02 10.20 3.27 0.10 0.100 0.046 0.05
2 33 5 8 0.00 0.00 1.60 1.60 1x16+16/25 7.27 0.00 0.00 7.27 3.27 0.79 0.885 0.357 0.40
3 25 3 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.22 1.109 0.101 0.50

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 28 4 5 0.00 0.40 1.00 1.40 1x16+16/25 4.55 0.00 2.02 6.57 3.27 0.60 0.602 0.273 0.27
2 26 1 1 0.40 0.40 0.20 0.60 1x16+16/25 0.91 2.02 2.02 2.93 3.27 0.25 0.851 0.113 0.39

1 0.27
1.1 32 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.19 0.190 0.087 0.36

193 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : ALTOMARAON CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 48 3 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.57 0.571 0.260 0.26
2 43 1 1 0.00 0.00 0.20 0.20 1x16+16/25 0.91 0.00 0.00 0.91 3.27 0.13 0.699 0.058 0.32

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 22 9 23 0.50 0.50 4.60 5.10 1x16/25 20.91 2.53 2.53 23.43 3.27 1.69 1.687 0.767 0.77
2 10 3 14 0.00 0.00 2.80 2.80 1x16/25 12.73 0.00 0.00 12.73 3.27 0.42 2.103 0.189 0.96
3 26 3 11 0.00 0.00 2.20 2.20 1x16/25 10.00 0.00 0.00 10.00 3.27 0.85 2.954 0.387 1.34
4 27 3 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 0.64 3.597 0.292 1.63
5 131 3 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.95 5.545 0.886 2.52
6 80 1 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.48 6.021 0.216 2.74
7 81 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.24 6.262 0.110 2.85

1 0.77
1.1 17 5 8 0.00 0.50 1.60 2.10 1x16/25 7.27 0.00 2.53 9.80 3.27 0.55 0.545 0.248 1.01
1.2 31 3 3 0.00 0.50 0.60 1.10 1x16/25 2.73 0.00 2.53 5.25 3.27 0.53 1.078 0.242 1.26
1.3 29 0 0 0.50 0.50 0.00 0.50 1x16/25 0.00 2.53 2.53 2.53 3.27 0.24 1.317 0.109 1.37

5 2.52
5.1 69 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.21 0.205 0.093 2.61

5 2.52
5.0.1 54 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.16 0.161 0.073 2.59

1 0.77
1.0.1 28 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.08 0.083 0.038 0.80

194 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : ALTOMARAON CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 56 2 21 1.00 2.50 4.20 6.70 1x16+16/25 19.09 5.05 12.63 31.72 3.27 5.81 5.812 2.642 2.64
2 20 1 19 0.50 1.50 3.80 5.30 1x16+16/25 17.27 2.53 7.58 24.85 3.27 1.63 7.438 0.739 3.38
3 24 11 18 0.00 1.00 3.60 4.60 1x16+16/25 16.36 0.00 5.05 21.41 3.27 1.68 9.119 0.764 4.15
4 39 2 7 1.00 1.00 1.40 2.40 1x16+16/25 6.36 5.05 5.05 11.41 3.27 1.46 10.576 0.662 4.81
5 33 5 5 0.00 0.00 1.00 1.00 1x16+16/25 4.55 0.00 0.00 4.55 3.27 0.49 11.067 0.223 5.03

1 2.64
1.1 40 1 1 0.50 0.50 0.20 0.70 1x16+16/25 0.91 2.53 2.53 3.43 3.27 0.45 0.449 0.204 2.85

3 4.15
3.1 28 4 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.33 0.333 0.151 4.30

3 4.15
3.0.1 18 4 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.21 0.214 0.097 4.24

4 4.81
4.1 27 0 0 0.50 0.50 0.00 0.50 1x16+16/25 0.00 2.53 2.53 2.53 3.27 0.22 0.223 0.101 4.91

195 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : ALTOMARAON CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 62 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 0.184 0.084 0.08

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 63 4 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 1.50 1.499 0.681 0.68
2 59 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.70 2.201 0.319 1.00
3 75 1 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.45 2.647 0.203 1.20
4 75 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.22 2.870 0.101 1.30

1 0.68
1.1 60 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.71 0.714 0.324 1.01
1.2 125 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.74 1.458 0.338 1.34

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 168 4 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 3.50 3.498 1.590 1.59
2 62 2 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.55 4.051 0.251 1.84
3 81 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.24 4.292 0.110 1.95

1 1.59
1.1 41 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.24 0.244 0.111 1.70

196 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : CAJAN CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 38 3 5 0.00 0.50 1.00 1.50 1x16/25 4.55 0.00 2.53 7.07 3.27 0.88 0.879 0.400 0.40
2 57 2 2 0.50 0.50 0.40 0.90 1x16/25 1.82 2.53 2.53 4.34 3.27 0.81 1.689 0.368 0.77

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 4 13 0.00 0.50 2.60 3.10 #N/A 11.82 0.00 2.53 14.34 #N/A #N/A #N/A #N/A #N/A
2 40 2 9 0.50 0.50 1.80 2.30 #N/A 8.18 2.53 2.53 10.71 #N/A #N/A #N/A #N/A #N/A
3 47 2 7 0.00 0.00 1.40 1.40 #N/A 6.36 0.00 0.00 6.36 #N/A #N/A #N/A #N/A #N/A
4 31 5 5 0.00 0.00 1.00 1.00 #N/A 4.55 0.00 0.00 4.55 #N/A #N/A #N/A #N/A #N/A

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 41 7 21 0.50 0.50 4.20 4.70 1x16+16/25 19.09 2.53 2.53 21.62 3.27 2.90 2.900 1.318 1.32
2 20 7 14 0.00 0.00 2.80 2.80 1x16+16/25 12.73 0.00 0.00 12.73 3.27 0.83 3.733 0.379 1.70
3 23 2 7 0.00 0.00 1.40 1.40 1x16+16/25 6.36 0.00 0.00 6.36 3.27 0.48 4.212 0.218 1.91
4 40 5 5 0.00 0.00 1.00 1.00 1x16+16/25 4.55 0.00 0.00 4.55 3.27 0.59 4.807 0.270 2.18

1 1.32
1.1 15 3 6 0.00 0.50 1.20 1.70 1x16+16/25 5.45 0.00 2.53 7.98 3.27 0.39 0.392 0.178 1.50
1.2 42 3 3 0.50 0.50 0.60 1.10 1x16+16/25 2.73 2.53 2.53 5.25 3.27 0.72 1.113 0.328 1.82

2 1.70
2.1 43 5 5 0.00 0.00 1.00 1.00 1x16+16/25 4.55 0.00 0.00 4.55 3.27 0.64 0.640 0.291 1.99

197 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : CAJAN CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 2 3 0.50 0.50 0.60 1.10 1x16/25 2.73 2.53 2.53 5.25 3.27 0.05 0.052 0.023 0.02
2 72 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.21 0.266 0.097 0.12

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 81 1 1 0.50 0.50 0.20 0.70 1x16/25 0.91 2.53 2.53 3.43 3.27 0.91 0.910 0.414 0.41

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 73 5 11 0.00 0.00 2.20 2.20 1x16/25 10.00 0.00 0.00 10.00 3.27 2.39 2.389 1.086 1.09
2 93 3 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.66 4.048 0.754 1.84
3 58 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.52 4.566 0.235 2.08
4 80 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.48 5.042 0.216 2.29

1 1.09
1.1 70 1 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.42 0.416 0.189 1.27
1.2 70 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.21 0.625 0.095 1.37

2 1.84
2.1 60 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.36 0.357 0.162 2.00

198 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 3

LOCALIDAD : CAJAN CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 208 2 10 0.00 0.00 2.00 2.00 1x16/25 9.09 0.00 0.00 9.09 3.27 6.19 6.187 2.812 2.81
2 50 3 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 1.19 7.377 0.541 3.35
3 61 3 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.91 8.284 0.412 3.77
4 71 1 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.42 8.706 0.192 3.96
5 50 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.15 8.855 0.068 4.03

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 43 1 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.26 0.256 0.116 0.12
2 35 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.10 0.360 0.047 0.16

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.04 0.045 0.020 0.02
2 80 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.71 0.759 0.324 0.34

199 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 3

LOCALIDAD : CAJAN CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 51 9 22 1.00 1.00 4.40 5.40 1x16+16/25 20.00 5.05 5.05 25.05 3.27 4.18 4.180 1.900 1.90
2 35 4 13 0.00 0.00 2.60 2.60 1x16+16/25 11.82 0.00 0.00 11.82 3.27 1.35 5.534 0.615 2.52
3 41 3 9 0.00 0.00 1.80 1.80 1x16+16/25 8.18 0.00 0.00 8.18 3.27 1.10 6.631 0.499 3.01
4 45 3 6 0.00 0.00 1.20 1.20 1x16+16/25 5.45 0.00 0.00 5.45 3.27 0.80 7.434 0.365 3.38
5 35 3 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.31 7.747 0.142 3.52

1 1.90
1.1 55 0 8 0.50 1.00 1.60 2.60 1x16+16/25 7.27 2.53 5.05 12.32 3.27 2.22 2.218 1.008 2.91
1.2 42 4 8 0.00 0.50 1.60 2.10 1x16+16/25 7.27 0.00 2.53 9.80 3.27 1.35 3.564 0.612 3.52
1.3 35 4 4 0.50 0.50 0.80 1.30 1x16+16/25 3.64 2.53 2.53 6.16 3.27 0.71 4.270 0.321 3.84

200 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : CHONCOBAMBA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 20 2 20 0.40 0.40 4.00 4.40 1x16/25 18.18 2.02 2.02 20.20 3.27 1.32 1.322 0.601 0.60
2 140 2 18 0.00 0.00 3.60 3.60 1x16/25 16.36 0.00 0.00 16.36 3.27 7.50 8.818 3.407 4.01
3 75 9 16 0.00 0.00 3.20 3.20 1x16/25 14.55 0.00 0.00 14.55 3.27 3.57 12.387 1.622 5.63
4 128 5 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 2.67 15.053 1.211 6.84
5 60 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.36 15.409 0.162 7.00

3 5.63
3.1 49 1 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.73 0.729 0.331 5.96
3.2 65 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.77 1.502 0.352 6.31
3.3 60 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.54 2.038 0.243 6.56

3 5.63
3.0.1 36 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.11 0.107 0.049 5.68

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 77 3 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 2.06 2.061 0.937 0.94
2 40 3 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.71 2.775 0.324 1.26
3 40 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.36 3.132 0.162 1.42
4 41 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.24 3.376 0.111 1.53

2 1.26
2.1 40 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.36 0.357 0.162 1.42
2.2 40 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.24 0.595 0.108 1.53

201 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : CHONCOBAMBA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 25 0.00 1.60 5.00 6.60 1x16+16/25 22.73 0.00 8.08 30.81 3.27 0.30 0.302 0.137 0.14
2 55 3 24 0.00 1.60 4.80 6.40 1x16+16/25 21.82 0.00 8.08 29.90 3.27 5.38 5.683 2.446 2.58
3 10 15 21 1.60 1.60 4.20 5.80 1x16+16/25 19.09 8.08 8.08 27.17 3.27 0.89 6.572 0.404 2.99
4 35 1 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.62 7.197 0.284 3.27
5 55 1 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.82 8.015 0.372 3.64
6 80 3 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.95 8.967 0.433 4.08
7 80 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.24 9.205 0.108 4.18

3 2.99
3.1 24 1 9 0.40 0.80 1.80 2.60 1x16+16/25 8.18 2.02 4.04 12.22 3.27 0.96 0.960 0.436 3.42
3.2 25 5 8 0.40 0.40 1.60 2.00 1x16+16/25 7.27 2.02 2.02 9.29 3.27 0.76 1.720 0.346 3.77
3.3 25 3 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.22 1.943 0.101 3.87

3 2.99
3.0.1 25 3 5 0.40 0.40 1.00 1.40 1x16+16/25 4.55 2.02 2.02 6.57 3.27 0.54 0.537 0.244 3.23
3.0.2 41 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.24 0.781 0.111 3.34
3.2 3.77
3.2.1 30 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.18 0.178 0.081 3.85

202 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : HUALLHUASH CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 41 3 11 0.00 0.00 2.20 2.20 1x16/25 10.00 0.00 0.00 10.00 3.27 1.34 1.342 0.610 0.61
2 64 3 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 1.52 2.864 0.692 1.30
3 146 3 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 2.17 5.036 0.987 2.29
4 71 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.42 5.458 0.192 2.48

2 1.30
2.1 42 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.12 0.125 0.057 1.36

3 2.29
3.1 51 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.30 0.303 0.138 2.43

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 11 1 10 0.00 0.00 2.00 2.00 1x16+16/25 9.09 0.00 0.00 9.09 3.27 0.33 0.327 0.149 0.15
2 29 6 9 0.00 0.00 1.80 1.80 1x16+16/25 8.18 0.00 0.00 8.18 3.27 0.78 1.104 0.353 0.50
3 23 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.21 1.309 0.093 0.59
4 62 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.37 1.678 0.168 0.76

2 0.50
2.1 29 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.17 0.173 0.078 0.58

203 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : HUALLHUASH CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 2 19 0.00 1.00 3.80 4.80 1x16+16/25 17.27 0.00 5.05 22.32 3.27 0.22 0.219 0.100 0.10
2 43 7 17 0.00 1.00 3.40 4.40 1x16+16/25 15.45 0.00 5.05 20.51 3.27 2.88 3.104 1.311 1.41
3 10 2 10 0.50 1.00 2.00 3.00 1x16+16/25 9.09 2.53 5.05 14.14 3.27 0.46 3.567 0.210 1.62
4 33 2 8 0.50 0.50 1.60 2.10 1x16+16/25 7.27 2.53 2.53 9.80 3.27 1.06 4.625 0.481 2.10
5 120 3 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 2.14 6.766 0.973 3.08
6 57 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.51 7.275 0.231 3.31
7 49 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.29 7.567 0.133 3.44

2 1.41
2.1 29 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.35 0.345 0.157 1.57
2.2 127 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.76 1.101 0.343 1.91

4 2.10
4.1 8 2 2 0.00 0.50 0.40 0.90 1x16+16/25 1.82 0.00 2.53 4.34 3.27 0.11 0.114 0.052 2.15
4.2 25 0 0 0.50 0.50 0.00 0.50 1x16+16/25 0.00 2.53 2.53 2.53 3.27 0.21 0.320 0.094 2.25

204 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : HUARACILLO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 18 2 8 0.00 1.00 1.60 2.60 1x16+16/25 7.27 0.00 5.05 12.32 3.27 0.73 0.726 0.330 0.33
2 43 1 6 0.50 1.00 1.20 2.20 1x16+16/25 5.45 2.53 5.05 10.51 3.27 1.48 2.204 0.672 1.00
3 24 5 5 0.50 0.50 1.00 1.50 1x16+16/25 4.55 2.53 2.53 7.07 3.27 0.56 2.759 0.252 1.25

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 48 5 9 0.50 0.50 1.80 2.30 1x16+16/25 8.18 2.53 2.53 10.71 3.27 1.68 1.682 0.764 0.76
2 124 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 1.48 3.157 0.671 1.43
3 68 1 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.40 3.562 0.184 1.62
4 51 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.15 3.713 0.069 1.69

1 0.76
1.1 29 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.17 0.173 0.078 0.84

205 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : HUARACILLO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 13 6 11 0.50 0.50 2.20 2.70 1x16+16/25 10.00 2.53 2.53 12.53 3.27 0.53 0.533 0.242 0.24
2 60 3 5 0.00 0.00 1.00 1.00 1x16+16/25 4.55 0.00 0.00 4.55 3.27 0.89 1.425 0.406 0.65
3 71 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.42 1.848 0.192 0.84

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 2 20 0.50 3.06 4.00 7.06 1x16+16/25 18.18 2.53 15.45 33.64 3.27 0.33 0.330 0.150 0.15
2 50 11 18 1.50 2.56 3.60 6.16 1x16+16/25 16.36 7.58 12.93 29.29 3.27 4.79 5.122 2.178 2.33
3 77 2 7 1.06 1.06 1.40 2.46 1x16+16/25 6.36 5.35 5.35 11.72 3.27 2.95 8.075 1.342 3.67
4 48 5 5 0.00 0.00 1.00 1.00 1x16+16/25 4.55 0.00 0.00 4.55 3.27 0.71 8.788 0.324 3.99

2 2.33
2.1 10 1 8 0.50 0.50 1.60 2.10 1x16+16/25 7.27 2.53 2.53 9.80 3.27 0.32 0.321 0.146 2.47
2.2 46 2 7 0.00 0.00 1.40 1.40 1x16+16/25 6.36 0.00 0.00 6.36 3.27 0.96 1.278 0.435 2.91
2.3 27 5 5 0.00 0.00 1.00 1.00 1x16+16/25 4.55 0.00 0.00 4.55 3.27 0.40 1.680 0.183 3.09

2 2.33
2.0.1 42 1 1 0.50 0.50 0.20 0.70 1x16+16/25 0.91 2.53 2.53 3.43 3.27 0.47 0.472 0.215 2.54

206 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : HUARACILLO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 140 13 23 1.50 2.00 4.60 6.60 2x16+16/25 10.45 3.79 6.31 16.77 4.09 9.60 9.601 2.182 2.18
2 57 3 10 0.50 0.50 2.00 2.50 1x16+16/25 9.09 2.53 2.53 11.62 3.27 2.17 11.768 0.985 3.17
3 10 2 7 0.00 0.00 1.40 1.40 1x16+16/25 6.36 0.00 0.00 6.36 3.27 0.21 11.976 0.095 3.26
4 38 5 5 0.00 0.00 1.00 1.00 1x16+16/25 4.55 0.00 0.00 4.55 3.27 0.57 12.541 0.257 3.52

1 2.18
1.1 27 4 12 0.00 0.00 2.40 2.40 1x16+16/25 10.91 0.00 0.00 10.91 3.27 0.96 0.964 0.438 2.62
1.2 33 4 8 0.00 0.00 1.60 1.60 1x16+16/25 7.27 0.00 0.00 7.27 3.27 0.79 1.749 0.357 2.98
1.3 16 4 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.19 1.939 0.087 3.06

2 3.17
2.1 32 1 1 0.50 0.50 0.20 0.70 1x16+16/25 0.91 2.53 2.53 3.43 3.27 0.36 0.360 0.163 3.33

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 96 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.57 0.571 0.260 0.26

207 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : HUARACILLO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 62 1 25 0.00 0.00 5.00 5.00 2x16/25 11.36 0.00 0.00 11.36 4.09 2.88 2.882 0.655 0.65
2 57 2 24 0.00 0.00 4.80 4.80 2x16/25 10.91 0.00 0.00 10.91 4.09 2.54 5.425 0.578 1.23
3 63 2 22 0.00 0.00 4.40 4.40 2x16/25 10.00 0.00 0.00 10.00 4.09 2.58 8.002 0.586 1.82
4 83 4 20 0.00 0.00 4.00 4.00 2x16/25 9.09 0.00 0.00 9.09 4.09 3.09 11.088 0.701 2.52
5 78 3 16 0.00 0.00 3.20 3.20 2x16/25 7.27 0.00 0.00 7.27 4.09 2.32 13.408 0.527 3.05
6 81 2 13 0.00 0.00 2.60 2.60 1x16/25 11.82 0.00 0.00 11.82 3.27 3.13 16.540 1.424 4.47
7 82 5 11 0.00 0.00 2.20 2.20 1x16/25 10.00 0.00 0.00 10.00 3.27 2.68 19.223 1.220 5.69
8 66 2 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.18 20.401 0.535 6.23
9 80 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.95 21.353 0.433 6.66
10 80 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.48 21.829 0.216 6.87

4 2.52
4.1 80 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.71 0.714 0.324 2.84

5 3.05
5.1 49 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.15 0.146 0.066 3.11

7 5.69
7.1 85 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.51 0.506 0.230 5.92

208 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : LALIBERTAD CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 41 1 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.24 0.244 0.111 0.11
2 52 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.15 0.399 0.070 0.18

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 17 0.00 1.20 3.40 4.60 1x16+16/25 15.45 0.00 6.06 21.52 3.27 0.21 0.211 0.096 0.10
2 40 6 16 1.20 1.20 3.20 4.40 1x16+16/25 14.55 6.06 6.06 20.61 3.27 2.70 2.908 1.226 1.32
3 56 3 10 0.00 0.00 2.00 2.00 1x16/25 9.09 0.00 0.00 9.09 3.27 1.67 4.574 0.757 2.08
4 56 3 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.17 5.740 0.530 2.61
5 45 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.54 6.275 0.243 2.85
6 45 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.40 6.677 0.183 3.03

2 1.32
2.1 55 1 5 0.40 0.80 1.00 1.80 1x16+16/25 4.55 2.02 4.04 8.59 3.27 1.55 1.545 0.702 2.02
2.2 55 4 4 0.40 0.40 0.80 1.20 1x16+16/25 3.64 2.02 2.02 5.66 3.27 1.02 2.563 0.463 2.49

2 1.32
2.0.1 50 1 1 0.00 0.00 0.20 0.20 1x16+16/25 0.91 0.00 0.00 0.91 3.27 0.15 0.149 0.068 1.39

3 2.08
3.1 30 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.09 0.089 0.041 2.12

209 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : LALIBERTAD CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 48 3 30 0.40 1.60 6.00 7.60 2x16+16/25 13.64 1.01 6.06 19.70 4.09 3.87 3.867 0.879 0.88
2 46 4 27 0.00 1.20 5.40 6.60 2x16+16/25 12.27 0.00 5.05 17.32 4.09 3.26 7.126 0.741 1.62
3 44 16 23 0.40 1.20 4.60 5.80 2x16+16/25 10.45 1.01 5.05 15.51 4.09 2.79 9.916 0.634 2.25
4 40 3 7 0.00 0.80 1.40 2.20 1x16+16/25 6.36 0.00 4.04 10.40 3.27 1.36 11.278 0.619 2.87
5 18 3 4 0.40 0.80 0.80 1.60 1x16+16/25 3.64 2.02 4.04 7.68 3.27 0.45 11.730 0.206 3.08
6 35 1 1 0.40 0.40 0.20 0.60 1x16+16/25 0.91 2.02 2.02 2.93 3.27 0.34 12.066 0.152 3.23

1 0.88
1.1 23 1 1 0.40 0.40 0.20 0.60 1x16+16/25 0.91 2.02 2.02 2.93 3.27 0.22 0.220 0.100 0.98

3 2.25
3.1 15 3 9 0.00 0.40 1.80 2.20 1x16+16/25 8.18 0.00 2.02 10.20 3.27 0.50 0.501 0.228 2.48
3.2 30 4 6 0.40 0.40 1.20 1.60 1x16+16/25 5.45 2.02 2.02 7.47 3.27 0.73 1.234 0.334 2.81
3.3 50 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.30 1.532 0.135 2.95

210 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : LAMERCED CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 50 11 15 0.00 0.50 3.00 3.50 1x16+16/25 13.64 0.00 2.53 16.16 3.27 2.64 2.644 1.202 1.20
2 14 0 4 0.50 0.50 0.80 1.30 1x16+16/25 3.64 2.53 2.53 6.16 3.27 0.28 2.926 0.128 1.33
3 29 1 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.35 3.271 0.157 1.49
4 30 3 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.27 3.539 0.122 1.61

1 1.20
1.1 51 5 5 0.00 0.00 1.00 1.00 1x16+16/25 4.55 0.00 0.00 4.55 3.27 0.76 0.759 0.345 1.55

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 4 17 0.00 1.00 3.40 4.40 1x16+16/25 15.45 0.00 5.05 20.51 3.27 0.20 0.201 0.091 0.09
2 11 1 13 0.50 1.00 2.60 3.60 1x16+16/25 11.82 2.53 5.05 16.87 3.27 0.61 0.808 0.276 0.37
3 30 3 12 0.50 0.50 2.40 2.90 1x16+16/25 10.91 2.53 2.53 13.43 3.27 1.32 2.127 0.599 0.97
4 35 3 9 0.00 0.00 1.80 1.80 1x16+16/25 8.18 0.00 0.00 8.18 3.27 0.94 3.064 0.426 1.39
5 67 4 6 0.00 0.00 1.20 1.20 1x16+16/25 5.45 0.00 0.00 5.45 3.27 1.20 4.260 0.544 1.94
6 60 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.36 4.617 0.162 2.10

3 0.97
3.1 30 1 1 0.50 0.50 0.20 0.70 1x16+16/25 0.91 2.53 2.53 3.43 3.27 0.34 0.337 0.153 1.12

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 38 8 12 0.00 0.00 2.40 2.40 1x16+16/25 10.91 0.00 0.00 10.91 3.27 1.36 1.356 0.617 0.62
2 141 2 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 1.68 3.034 0.763 1.38
3 45 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.27 3.302 0.122 1.50

1 0.62
1.1 9 2 5 0.00 0.00 1.00 1.00 1x16+16/25 4.55 0.00 0.00 4.55 3.27 0.13 0.134 0.061 0.68
1.2 43 3 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.38 0.518 0.174 0.85

211 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : LAMERCED CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

212 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : LAMERCED CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 12 2 15 0.00 2.00 3.00 5.00 1x16+16/25 13.64 0.00 10.10 23.74 3.27 0.93 0.932 0.424 0.42
2 30 3 13 0.50 2.00 2.60 4.60 1x16+16/25 11.82 2.53 10.10 21.92 3.27 2.15 3.084 0.978 1.40
3 5 4 10 0.50 1.50 2.00 3.50 1x16+16/25 9.09 2.53 7.58 16.67 3.27 0.27 3.356 0.124 1.53
4 52 2 6 0.50 1.00 1.20 2.20 1x16+16/25 5.45 2.53 5.05 10.51 3.27 1.79 5.144 0.812 2.34
5 41 4 4 0.50 0.50 0.80 1.30 1x16+16/25 3.64 2.53 2.53 6.16 3.27 0.83 5.970 0.376 2.71

2 1.40
2.1 22 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.13 0.131 0.059 1.46

213 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : LAMERCED CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 3 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 0.07 0.071 0.032 0.03
2 122 5 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.81 1.886 0.825 0.86

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 68 1 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.21 1.214 0.552 0.55
2 60 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.89 2.106 0.406 0.96
3 60 2 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.54 2.641 0.243 1.20
4 64 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.19 2.832 0.087 1.29

2 0.96
2.1 45 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.27 0.268 0.122 1.08

3 1.20
3.1 60 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 0.178 0.081 1.28

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 37 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.22 0.220 0.100 0.10

214 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : MAINCO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 68 0 10 0.40 0.40 2.00 2.40 1x16+16/25 9.09 2.02 2.02 11.11 3.27 2.47 2.472 1.124 1.12
2 66 4 10 0.00 0.00 2.00 2.00 1x16/25 9.09 0.00 0.00 9.09 3.27 1.96 4.435 0.892 2.02
3 85 2 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.52 5.952 0.690 2.71
4 158 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 1.88 7.832 0.855 3.56
5 90 1 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.54 8.368 0.243 3.80
6 90 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.27 8.635 0.122 3.93

1 1.12
1.1 45 0 0 0.40 0.40 0.00 0.40 1x16+16/25 0.00 2.02 2.02 2.02 3.27 0.30 0.297 0.135 1.26

2 2.02
2.1 65 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.77 0.773 0.352 2.37
2.2 65 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.58 1.353 0.264 2.63
2.3 180 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 1.07 2.424 0.487 3.12

3 2.71
3.1 80 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.24 0.238 0.108 2.81

4 3.56
4.1 90 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.54 0.535 0.243 3.80

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 5 0.00 0.40 1.00 1.40 1x16+16/25 4.55 0.00 2.02 6.57 3.27 0.06 0.064 0.029 0.03
2 40 2 4 0.00 0.40 0.80 1.20 1x16+16/25 3.64 0.00 2.02 5.66 3.27 0.74 0.805 0.337 0.37
3 40 2 2 0.40 0.40 0.40 0.80 1x16+16/25 1.82 2.02 2.02 3.84 3.27 0.50 1.307 0.228 0.59

215 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : MAINCO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 53 2 2 0.40 0.40 0.40 0.80 1x16+16/25 1.82 2.02 2.02 3.84 3.27 0.67 0.666 0.303 0.30

216 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : NUEVAESPERANZA(YANGAR) CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 23 1 3 0.00 0.40 0.60 1.00 1x16+16/25 2.73 0.00 2.02 4.75 3.27 0.36 0.357 0.162 0.16
2 35 2 2 0.40 0.40 0.40 0.80 1x16+16/25 1.82 2.02 2.02 3.84 3.27 0.44 0.797 0.200 0.36

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 47 2 6 0.00 0.00 1.20 1.20 1x16+16/25 5.45 0.00 0.00 5.45 3.27 0.84 0.839 0.381 0.38
2 26 4 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.31 1.148 0.141 0.52

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 3 6 0.40 0.40 1.20 1.60 1x16/25 5.45 2.02 2.02 7.47 3.27 0.07 0.073 0.033 0.03
2 38 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.34 0.412 0.154 0.19
3 80 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.48 0.888 0.216 0.40

217 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : PACRAO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 56 2 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.67 0.666 0.303 0.30
2 69 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.41 1.077 0.187 0.49

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 2 13 0.00 0.40 2.60 3.00 1x16/25 11.82 0.00 2.02 13.84 3.27 0.14 0.136 0.062 0.06
2 59 5 11 0.40 0.40 2.20 2.60 1x16/25 10.00 2.02 2.02 12.02 3.27 2.32 2.456 1.055 1.12
3 60 1 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.07 3.527 0.487 1.60
4 60 1 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.89 4.420 0.406 2.01
5 60 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.71 5.133 0.324 2.33

2 1.12
2.1 56 3 3 0.00 0.40 0.60 1.00 1x16/25 2.73 0.00 2.02 4.75 3.27 0.87 0.870 0.395 1.51
2.2 60 0 0 0.40 0.40 0.00 0.40 1x16/25 0.00 2.02 2.02 2.02 3.27 0.40 1.266 0.180 1.69

218 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : PACRAO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 18 5 9 0.40 1.60 1.80 3.40 1x16+16/25 8.18 2.02 8.08 16.26 3.27 0.96 0.958 0.435 0.44
2 26 2 4 0.80 1.20 0.80 2.00 1x16+16/25 3.64 4.04 6.06 9.70 3.27 0.82 1.783 0.375 0.81
3 40 2 2 0.40 0.40 0.40 0.80 1x16+16/25 1.82 2.02 2.02 3.84 3.27 0.50 2.285 0.228 1.04

1 0.44
1.1 47 1 2 0.40 0.40 0.40 0.80 1x16+16/25 1.82 2.02 2.02 3.84 3.27 0.59 0.590 0.268 0.70
1.2 17 1 1 0.00 0.00 0.20 0.20 1x16+16/25 0.91 0.00 0.00 0.91 3.27 0.05 0.641 0.023 0.73

2 0.81
2.1 40 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.12 0.119 0.054 0.86

219 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : PINRA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C2R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 45 1 17 0.00 0.60 3.40 4.00 #N/A 15.45 0.00 3.03 18.48 #N/A #N/A #N/A #N/A #N/A
2 10 4 16 0.60 0.60 3.20 3.80 #N/A 14.55 3.03 3.03 17.58 #N/A #N/A #N/A #N/A #N/A
3 27 3 12 0.00 0.00 2.40 2.40 #N/A 10.91 0.00 0.00 10.91 #N/A #N/A #N/A #N/A #N/A
4 43 7 9 0.00 0.00 1.80 1.80 #N/A 8.18 0.00 0.00 8.18 #N/A #N/A #N/A #N/A #N/A
5 106 2 2 0.00 0.00 0.40 0.40 #N/A 1.82 0.00 0.00 1.82 #N/A #N/A #N/A #N/A #N/A

2 #N/A
2.1 18 1 4 0.00 0.00 0.80 0.80 #N/A 3.64 0.00 0.00 3.64 #N/A #N/A #N/A #N/A #N/A
2.2 45 3 3 0.00 0.00 0.60 0.60 #N/A 2.73 0.00 0.00 2.73 #N/A #N/A #N/A #N/A #N/A

3 #N/A
3.1 9 3 3 0.00 0.00 0.60 0.60 #N/A 2.73 0.00 0.00 2.73 #N/A #N/A #N/A #N/A #N/A

CIRCUITO : C2R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 12 0.00 0.00 2.40 2.40 #N/A 10.91 0.00 0.00 10.91 #N/A #N/A #N/A #N/A #N/A
2 13 1 11 0.00 0.00 2.20 2.20 #N/A 10.00 0.00 0.00 10.00 #N/A #N/A #N/A #N/A #N/A
3 51 2 10 0.00 0.00 2.00 2.00 #N/A 9.09 0.00 0.00 9.09 #N/A #N/A #N/A #N/A #N/A
4 7 4 8 0.00 0.00 1.60 1.60 #N/A 7.27 0.00 0.00 7.27 #N/A #N/A #N/A #N/A #N/A
5 39 4 4 0.00 0.00 0.80 0.80 #N/A 3.64 0.00 0.00 3.64 #N/A #N/A #N/A #N/A #N/A

220 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : PINRA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 32 2 15 0.00 1.90 3.00 4.90 #N/A 13.64 0.00 9.60 23.23 #N/A #N/A #N/A #N/A #N/A
2 32 3 13 0.00 1.90 2.60 4.50 #N/A 11.82 0.00 9.60 21.41 #N/A #N/A #N/A #N/A #N/A
3 11 4 10 0.00 1.90 2.00 3.90 #N/A 9.09 0.00 9.60 18.69 #N/A #N/A #N/A #N/A #N/A
4 42 5 6 0.60 1.90 1.20 3.10 #N/A 5.45 3.03 9.60 15.05 #N/A #N/A #N/A #N/A #N/A
5 52 0 1 0.70 1.30 0.20 1.50 #N/A 0.91 3.54 6.57 7.47 #N/A #N/A #N/A #N/A #N/A
6 39 1 1 0.60 0.60 0.20 0.80 #N/A 0.91 3.03 3.03 3.94 #N/A #N/A #N/A #N/A #N/A

3 #N/A
3.1 36 2 2 0.00 0.00 0.40 0.40 #N/A 1.82 0.00 0.00 1.82 #N/A #N/A #N/A #N/A #N/A

4 #N/A
4.1 11 3 3 0.00 0.00 0.60 0.60 #N/A 2.73 0.00 0.00 2.73 #N/A #N/A #N/A #N/A #N/A

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 13 0 16 0.60 2.40 3.20 5.60 #N/A 14.55 3.03 12.12 26.67 #N/A #N/A #N/A #N/A #N/A
2 31 0 16 0.60 1.80 3.20 5.00 #N/A 14.55 3.03 9.09 23.64 #N/A #N/A #N/A #N/A #N/A
3 12 0 16 0.60 1.20 3.20 4.40 #N/A 14.55 3.03 6.06 20.61 #N/A #N/A #N/A #N/A #N/A
4 15 9 16 0.60 0.60 3.20 3.80 #N/A 14.55 3.03 3.03 17.58 #N/A #N/A #N/A #N/A #N/A
5 5 3 7 0.00 0.00 1.40 1.40 #N/A 6.36 0.00 0.00 6.36 #N/A #N/A #N/A #N/A #N/A
6 93 1 4 0.00 0.00 0.80 0.80 #N/A 3.64 0.00 0.00 3.64 #N/A #N/A #N/A #N/A #N/A
7 43 2 3 0.00 0.00 0.60 0.60 #N/A 2.73 0.00 0.00 2.73 #N/A #N/A #N/A #N/A #N/A
8 42 1 1 0.00 0.00 0.20 0.20 #N/A 0.91 0.00 0.00 0.91 #N/A #N/A #N/A #N/A #N/A

3 #N/A
3.1 39 0 0 0.60 0.60 0.00 0.60 #N/A 0.00 3.03 3.03 3.03 #N/A #N/A #N/A #N/A #N/A

4 #N/A
4.1 50 3 6 0.60 0.60 1.20 1.80 #N/A 5.45 3.03 3.03 8.48 #N/A #N/A #N/A #N/A #N/A
4.2 52 3 3 0.00 0.00 0.60 0.60 #N/A 2.73 0.00 0.00 2.73 #N/A #N/A #N/A #N/A #N/A

221 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : PINRA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 7 2 5 0.00 0.00 1.00 1.00 #N/A 4.55 0.00 0.00 4.55 #N/A #N/A #N/A #N/A #N/A
2 50 3 3 0.00 0.00 0.60 0.60 #N/A 2.73 0.00 0.00 2.73 #N/A #N/A #N/A #N/A #N/A

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 10 0 7 0.60 0.60 1.40 2.00 #N/A 6.36 3.03 3.03 9.39 #N/A #N/A #N/A #N/A #N/A
2 45 1 7 0.00 0.00 1.40 1.40 #N/A 6.36 0.00 0.00 6.36 #N/A #N/A #N/A #N/A #N/A
3 17 2 6 0.00 0.00 1.20 1.20 #N/A 5.45 0.00 0.00 5.45 #N/A #N/A #N/A #N/A #N/A
4 35 4 4 0.00 0.00 0.80 0.80 #N/A 3.64 0.00 0.00 3.64 #N/A #N/A #N/A #N/A #N/A

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 12 0.00 0.75 2.40 3.15 #N/A 10.91 0.00 3.79 14.70 #N/A #N/A #N/A #N/A #N/A
2 39 2 11 0.75 0.75 2.20 2.95 #N/A 10.00 3.79 3.79 13.79 #N/A #N/A #N/A #N/A #N/A
3 40 1 9 0.00 0.00 1.80 1.80 #N/A 8.18 0.00 0.00 8.18 #N/A #N/A #N/A #N/A #N/A
4 16 5 8 0.00 0.00 1.60 1.60 #N/A 7.27 0.00 0.00 7.27 #N/A #N/A #N/A #N/A #N/A
5 46 2 3 0.00 0.00 0.60 0.60 #N/A 2.73 0.00 0.00 2.73 #N/A #N/A #N/A #N/A #N/A
6 47 1 1 0.00 0.00 0.20 0.20 #N/A 0.91 0.00 0.00 0.91 #N/A #N/A #N/A #N/A #N/A

4 #N/A
4.1 44 2 2 0.00 0.00 0.40 0.40 #N/A 1.82 0.00 0.00 1.82 #N/A #N/A #N/A #N/A #N/A

222 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : PINRA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C2

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 38 4 25 0.60 1.20 5.00 6.20 #N/A 11.36 1.52 4.55 15.91 #N/A #N/A #N/A #N/A #N/A
2 34 3 21 0.00 0.60 4.20 4.80 #N/A 9.55 0.00 3.03 12.58 #N/A #N/A #N/A #N/A #N/A
3 10 6 18 0.00 0.60 3.60 4.20 #N/A 8.18 0.00 3.03 11.21 #N/A #N/A #N/A #N/A #N/A
4 35 6 12 0.00 0.60 2.40 3.00 #N/A 10.91 0.00 3.03 13.94 #N/A #N/A #N/A #N/A #N/A
5 37 4 6 0.00 0.60 1.20 1.80 #N/A 5.45 0.00 3.03 8.48 #N/A #N/A #N/A #N/A #N/A
6 23 2 2 0.60 0.60 0.40 1.00 #N/A 1.82 3.03 3.03 4.85 #N/A #N/A #N/A #N/A #N/A

3 #N/A
3.1 38 2 4 0.00 0.00 0.80 0.80 #N/A 3.64 0.00 0.00 3.64 #N/A #N/A #N/A #N/A #N/A
3.2 41 2 2 0.00 0.00 0.40 0.40 #N/A 1.82 0.00 0.00 1.82 #N/A #N/A #N/A #N/A #N/A

223 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SANFRANCISCO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 12 0.00 0.00 2.40 2.40 1x16/25 10.91 0.00 0.00 10.91 3.27 0.11 0.107 0.049 0.05
2 90 1 11 0.00 0.00 2.20 2.20 1x16/25 10.00 0.00 0.00 10.00 3.27 2.94 3.052 1.339 1.39
3 45 1 10 0.00 0.00 2.00 2.00 1x16/25 9.09 0.00 0.00 9.09 3.27 1.34 4.390 0.608 2.00
4 41 4 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 1.10 5.488 0.499 2.49
5 90 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.34 6.827 0.608 3.10
6 35 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.31 7.139 0.142 3.24

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 78 6 13 0.00 0.00 2.60 2.60 1x16/25 11.82 0.00 0.00 11.82 3.27 3.02 3.016 1.371 1.37
2 80 1 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.67 4.682 0.757 2.13
3 160 1 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 2.86 7.537 1.298 3.43
4 60 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.89 8.430 0.406 3.83
5 68 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.61 9.037 0.276 4.11
6 68 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.40 9.441 0.184 4.29

1 1.37
1.1 68 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.81 0.809 0.368 1.74
1.2 69 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.62 1.425 0.280 2.02

2 2.13
2.1 70 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.21 0.208 0.095 2.22

224 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : SANFRANCISCO CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 48 3 5 0.00 0.80 1.00 1.80 1x16+16/25 4.55 0.00 4.04 8.59 3.27 1.35 1.348 0.613 0.61
2 41 1 2 0.40 0.80 0.40 1.20 1x16+16/25 1.82 2.02 4.04 5.86 3.27 0.79 2.134 0.357 0.97
3 36 1 1 0.40 0.40 0.20 0.60 1x16+16/25 0.91 2.02 2.02 2.93 3.27 0.35 2.479 0.157 1.13

1 0.61
1.1 78 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.46 0.464 0.211 0.82

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 53 1 9 0.40 0.40 1.80 2.20 1x16/25 8.18 2.02 2.02 10.20 3.27 1.77 1.769 0.804 0.80
2 160 3 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 3.81 5.577 1.731 2.53
3 80 5 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.19 6.766 0.541 3.08

1 0.80
1.1 68 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.20 0.202 0.092 0.90

2 2.53
2.1 59 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.35 0.351 0.160 2.69

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 2 13 0.40 0.80 2.60 3.40 1x16+16/25 11.82 2.02 4.04 15.86 3.27 0.16 0.156 0.071 0.07
2 29 3 11 0.00 0.40 2.20 2.60 1x16+16/25 10.00 0.00 2.02 12.02 3.27 1.14 1.296 0.518 0.59
3 29 4 8 0.40 0.40 1.60 2.00 1x16+16/25 7.27 2.02 2.02 9.29 3.27 0.88 2.178 0.401 0.99
4 15 4 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.18 2.357 0.081 1.07

225 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SANTAROSA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 14 0.80 0.80 2.80 3.60 1x16/25 12.73 4.04 4.04 16.77 3.27 0.16 0.165 0.075 0.07
2 180 5 13 0.00 0.00 2.60 2.60 1x16/25 11.82 0.00 0.00 11.82 3.27 6.96 7.125 3.164 3.24
3 68 5 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 1.62 8.743 0.736 3.97
4 82 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.73 9.475 0.333 4.31

2 3.24
2.1 60 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.71 0.714 0.324 3.56
2.2 80 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.48 1.190 0.216 3.78

3 3.97
3.1 60 1 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.36 0.357 0.162 4.14
3.2 61 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 0.538 0.082 4.22

3 3.97
3.0.1 60 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.36 0.357 0.162 4.14

226 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SANTAROSA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 51 3 3 0.40 0.40 0.60 1.00 1x16+16/25 2.73 2.02 2.02 4.75 3.27 0.79 0.792 0.360 0.36

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 53 10 15 0.80 0.80 3.00 3.80 1x16+16/25 13.64 4.04 4.04 17.68 3.27 3.07 3.065 1.393 1.39
2 168 3 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 2.50 5.564 1.136 2.53
3 153 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.91 6.474 0.414 2.94

1 1.39
1.1 58 1 8 0.80 0.80 1.60 2.40 1x16+16/25 7.27 4.04 4.04 11.31 3.27 2.15 2.147 0.976 2.37
1.2 62 1 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.29 3.438 0.587 2.96
1.3 120 3 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 2.14 5.580 0.973 3.93
1.4 60 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.54 6.115 0.243 4.17

2 2.53
2.1 61 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.36 0.363 0.165 2.69

227 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : SANTAROSA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 63 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.37 0.375 0.170 0.17

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 134 8 14 0.00 0.00 2.80 2.80 1x16/25 12.73 0.00 0.00 12.73 3.27 5.58 5.580 2.536 2.54
2 66 6 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.18 6.758 0.535 3.07

1 2.54
1.1 55 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.65 0.654 0.297 2.83

228 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : SANTAROSA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 0.06 0.062 0.028 0.03
2 69 1 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.23 1.294 0.560 0.59
3 117 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.74 3.034 0.791 1.38
4 80 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.71 3.748 0.324 1.70

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 65 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.58 0.580 0.264 0.26

229 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : VISTAALEGRE(PINRA) CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 38 1 18 0.40 0.40 3.60 4.00 2x16+16/25 8.18 1.01 1.01 9.19 4.09 1.43 1.429 0.325 0.32
2 16 6 17 0.00 0.00 3.40 3.40 2x16+16/25 7.73 0.00 0.00 7.73 4.09 0.51 1.934 0.115 0.44
3 130 3 11 0.00 0.00 2.20 2.20 1x16/25 10.00 0.00 0.00 10.00 3.27 4.25 6.188 1.933 2.37
4 230 2 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 5.47 11.661 2.488 4.86
5 80 2 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.43 13.089 0.649 5.51
6 125 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 1.49 14.576 0.676 6.19

2 0.44
2.1 35 1 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.62 0.625 0.284 0.72
2.2 35 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.52 1.145 0.237 0.96
2.3 60 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.54 1.681 0.243 1.20
2.4 70 1 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.42 2.097 0.189 1.39
2.5 70 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.21 2.305 0.095 1.49

2.4 1.39
2.4.1 30 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.09 0.089 0.041 1.43

230 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : VISTAALEGRE(PINRA) CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 6 0.40 0.40 1.20 1.60 1x16+16/25 5.45 2.02 2.02 7.47 3.27 0.07 0.073 0.033 0.03
2 30 2 5 0.00 0.00 1.00 1.00 1x16+16/25 4.55 0.00 0.00 4.55 3.27 0.45 0.520 0.203 0.24
3 32 3 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.29 0.805 0.130 0.37

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 78 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.70 0.696 0.316 0.32
2 74 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.44 1.136 0.200 0.52

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 21 1 1 0.40 0.40 0.20 0.60 1x16+16/25 0.91 2.02 2.02 2.93 3.27 0.20 0.201 0.091 0.09

231 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : ARANCAY CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 600 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 2 28 0.00 1.20 8.40 9.60 2x16+16/25 19.09 0.00 3.03 22.12 4.09 0.27 0.271 0.062 0.06
2 42 4 26 0.60 1.20 7.80 9.00 2x16+16/25 17.73 1.52 3.03 20.76 4.09 3.57 3.837 0.810 0.87
3 46 1 22 0.60 0.60 6.60 7.20 2x16+16/25 15.00 1.52 1.52 16.52 4.09 3.11 6.944 0.706 1.58
4 10 3 21 0.00 0.00 6.30 6.30 2x16+16/25 14.32 0.00 0.00 14.32 4.09 0.59 7.530 0.133 1.71
5 48 3 18 0.00 0.00 5.40 5.40 2x16+16/25 12.27 0.00 0.00 12.27 4.09 2.41 9.939 0.548 2.26
6 10 4 15 0.00 0.00 4.50 4.50 1x16/25 20.45 0.00 0.00 20.45 3.27 0.67 10.609 0.304 2.56
7 15 1 11 0.00 0.00 3.30 3.30 1x16/25 15.00 0.00 0.00 15.00 3.27 0.74 11.345 0.335 2.90
8 15 2 10 0.00 0.00 3.00 3.00 1x16/25 13.64 0.00 0.00 13.64 3.27 0.67 12.014 0.304 3.20
9 60 2 8 0.00 0.00 2.40 2.40 1x16/25 10.91 0.00 0.00 10.91 3.27 2.14 14.156 0.973 4.18
10 61 3 6 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 1.63 15.789 0.742 4.92
11 40 3 3 0.00 0.00 0.90 0.90 1x16/25 4.09 0.00 0.00 4.09 3.27 0.54 16.324 0.243 5.16

2 0.87
2.1 42 2 2 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.37 0.375 0.170 1.04

3 1.58
3.1 42 1 1 0.60 0.60 0.30 0.90 1x16+16/25 1.36 3.03 3.03 4.39 3.27 0.60 0.604 0.274 1.85

6 2.56
6.1 30 3 3 0.00 0.00 0.90 0.90 1x16+16/25 4.09 0.00 0.00 4.09 3.27 0.40 0.402 0.183 2.75

8 3.20
8.1 42 1 1 0.00 0.00 0.30 0.30 1x16/25 1.36 0.00 0.00 1.36 3.27 0.19 0.187 0.085 3.29

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 42 1 13 0.00 0.00 3.90 3.90 1x16+16/25 17.73 0.00 0.00 17.73 3.27 2.44 2.436 1.107 1.11
2 39 6 12 0.00 0.00 3.60 3.60 1x16/25 16.36 0.00 0.00 16.36 3.27 2.09 4.524 0.949 2.06
3 74 2 6 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 1.98 6.505 0.900 2.96
4 38 1 4 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.68 7.184 0.308 3.27
5 80 1 3 0.00 0.00 0.90 0.90 1x16/25 4.09 0.00 0.00 4.09 3.27 1.07 8.254 0.487 3.75
6 70 2 2 0.00 0.00 0.60 0.60 3x16/25 1.36 0.00 0.00 1.36 0.00 0.00 8.254 0.000 3.75

2 2.06
2.1 39 1 5 0.00 0.00 1.50 1.50 1x16+16/25 6.82 0.00 0.00 6.82 3.27 0.87 0.870 0.395 2.45
2.2 78 2 4 0.00 0.00 1.20 1.20 1x16+16/25 5.45 0.00 0.00 5.45 3.27 1.39 2.262 0.633 3.08
2.3 41 2 2 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.37 2.628 0.166 3.25

232 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : ARANCAY CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 600 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C2

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 13 2 23 0.00 1.86 6.90 8.76 2x16+16/25 15.68 0.00 7.88 23.56 4.09 1.25 1.253 0.285 0.28
2 34 3 21 0.60 1.86 6.30 8.16 2x16+16/25 14.32 1.52 7.88 22.20 4.09 3.09 4.339 0.702 0.99
3 34 1 18 1.26 1.26 5.40 6.66 1x16+16/25 24.55 6.36 6.36 30.91 3.27 3.44 7.778 1.563 2.55
4 10 1 17 0.00 0.00 5.10 5.10 1x16+16/25 23.18 0.00 0.00 23.18 3.27 0.76 8.537 0.345 2.89
5 44 4 16 0.00 0.00 4.80 4.80 1x16+16/25 21.82 0.00 0.00 21.82 3.27 3.14 11.678 1.428 4.32
6 46 2 12 0.00 0.00 3.60 3.60 1x16+16/25 16.36 0.00 0.00 16.36 3.27 2.46 14.141 1.120 5.44
7 43 3 10 0.00 0.00 3.00 3.00 1x16+16/25 13.64 0.00 0.00 13.64 3.27 1.92 16.059 0.872 6.31
8 45 2 7 0.00 0.00 2.10 2.10 1x16+16/25 9.55 0.00 0.00 9.55 3.27 1.41 17.465 0.639 6.95
9 44 2 5 0.00 0.00 1.50 1.50 1x16+16/25 6.82 0.00 0.00 6.82 3.27 0.98 18.446 0.446 7.40
10 35 3 3 0.00 0.00 0.90 0.90 3x16/25 2.05 0.00 0.00 2.05 0.00 0.00 18.446 0.000 7.40

3 2.55
3.1 34 3 3 0.60 0.60 0.90 1.50 1x16+16/25 4.09 3.03 3.03 7.12 3.27 0.79 0.792 0.360 2.91

CIRCUITO : C2

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 43 1 1 0.00 0.00 0.30 0.30 1x16+16/25 1.36 0.00 0.00 1.36 3.27 0.19 0.192 0.087 0.09

233 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : ARANCAY CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 600 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 87 1 15 0.00 0.00 4.50 4.50 1x16/25 20.45 0.00 0.00 20.45 3.27 5.82 5.823 2.647 2.65
2 63 5 14 0.00 0.00 4.20 4.20 1x16/25 19.09 0.00 0.00 19.09 3.27 3.94 9.758 1.789 4.44
3 60 4 9 0.00 0.00 2.70 2.70 1x16/25 12.27 0.00 0.00 12.27 3.27 2.41 12.167 1.095 5.53
4 59 3 5 0.00 0.00 1.50 1.50 1x16/25 6.82 0.00 0.00 6.82 3.27 1.32 13.484 0.598 6.13
5 84 2 2 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.75 14.233 0.341 6.47

2 4.44
2.1 50 1 4 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.89 0.892 0.406 4.84
2.2 51 3 3 0.00 0.00 0.90 0.90 1x16/25 4.09 0.00 0.00 4.09 3.27 0.68 1.575 0.310 5.15

3 5.53
3.1 31 3 3 0.00 0.00 0.90 0.90 1x16/25 4.09 0.00 0.00 4.09 3.27 0.41 0.415 0.189 5.72

4 6.13
4.1 60 1 1 0.00 0.00 0.30 0.30 1x16/25 1.36 0.00 0.00 1.36 3.27 0.27 0.268 0.122 6.25

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 86 4 13 0.00 0.00 3.90 3.90 1x16/25 17.73 0.00 0.00 17.73 3.27 4.99 4.988 2.267 2.27
2 60 3 9 0.00 0.00 2.70 2.70 1x16/25 12.27 0.00 0.00 12.27 3.27 2.41 7.398 1.095 3.36
3 60 1 6 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 1.61 9.004 0.730 4.09
4 60 2 5 0.00 0.00 1.50 1.50 1x16/25 6.82 0.00 0.00 6.82 3.27 1.34 10.342 0.608 4.70
5 60 3 3 0.00 0.00 0.90 0.90 1x16/25 4.09 0.00 0.00 4.09 3.27 0.80 11.146 0.365 5.07

1 2.27
1.1 40 2 2 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.36 0.357 0.162 2.43

234 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : ARANCAY CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 600 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 0 6 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 0.08 0.080 0.037 0.04
2 120 2 6 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 3.21 3.293 1.460 1.50
3 144 2 4 0.00 0.00 1.20 1.20 1x16+16/25 5.45 0.00 0.00 5.45 3.27 2.57 5.863 1.168 2.66
4 64 2 2 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.57 6.434 0.260 2.92

3 2.66
3.1 62 2 2 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.55 0.553 0.251 2.92

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 78 1 18 0.60 1.35 5.40 6.75 2x16/25 12.27 1.52 5.30 17.58 4.09 5.61 5.607 1.274 1.27
2 160 8 17 0.00 0.75 5.10 5.85 2x16/25 11.59 0.00 3.79 15.38 4.09 10.06 15.671 2.287 3.56
3 54 2 9 0.00 0.75 2.70 3.45 2x16/25 6.14 0.00 3.79 9.92 4.09 2.19 17.863 0.498 4.06
4 50 1 7 0.00 0.75 2.10 2.85 1x16/25 9.55 0.00 3.79 13.33 3.27 2.18 20.044 0.992 5.05
5 60 2 6 0.75 0.75 1.80 2.55 1x16/25 8.18 3.79 3.79 11.97 3.27 2.35 22.394 1.068 6.12
6 42 2 4 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.75 23.144 0.341 6.46
7 42 2 2 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.37 23.518 0.170 6.63

1 1.27
1.1 48 0 0 0.60 0.60 0.00 0.60 1x16/25 0.00 3.03 3.03 3.03 3.27 0.48 0.476 0.216 1.49

1 1.27
0.1.1 53 1 1 0.00 0.00 0.30 0.30 1x16/25 1.36 0.00 0.00 1.36 3.27 0.24 0.236 0.107 1.38

2 3.56
2.1 73 1 6 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 1.95 1.954 0.888 4.45
2.2 34 2 5 0.00 0.00 1.50 1.50 1x16/25 6.82 0.00 0.00 6.82 3.27 0.76 2.713 0.345 4.79
2.3 41 1 3 0.00 0.00 0.90 0.90 1x16/25 4.09 0.00 0.00 4.09 3.27 0.55 3.262 0.249 5.04
2.4 38 2 2 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.34 3.601 0.154 5.20

235 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : BRILLANTE CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 0 1 0.40 1.20 0.20 1.40 1x16/25 0.91 2.02 6.06 6.97 3.27 0.07 0.068 0.031 0.03
2 62 1 1 0.80 0.80 0.20 1.00 1x16/25 0.91 4.04 4.04 4.95 3.27 1.00 1.072 0.456 0.49

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 83 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.49 0.494 0.224 0.22

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 63 4 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 1.69 1.687 0.767 0.77
2 85 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.26 2.951 0.575 1.34
3 120 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 1.07 4.022 0.487 1.83
4 90 1 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.54 4.557 0.243 2.07
5 90 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.27 4.825 0.122 2.19

1 0.77
1.1 150 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.89 0.892 0.406 1.17

236 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : HUAMPOY CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 2 10 0.00 0.40 2.00 2.40 1x16+16/25 9.09 0.00 2.02 11.11 3.27 0.11 0.109 0.050 0.05
2 40 4 8 0.40 0.40 1.60 2.00 1x16+16/25 7.27 2.02 2.02 9.29 3.27 1.22 1.325 0.553 0.60
3 40 4 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.48 1.801 0.216 0.82

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 42 10 12 0.00 0.00 2.40 2.40 1x16+16/25 10.91 0.00 0.00 10.91 3.27 1.50 1.499 0.681 0.68
2 85 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.51 2.005 0.230 0.91

1 0.68
1.1 40 4 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.48 0.476 0.216 0.90
1 0.68
0.1.1 40 3 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.36 0.357 0.162 0.84

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 53 3 7 0.00 0.00 1.40 1.40 1x16+16/25 6.36 0.00 0.00 6.36 3.27 1.10 1.104 0.502 0.50
2 45 4 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.54 1.639 0.243 0.74

237 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : HUAMPOY CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 33 4 11 1.20 1.60 2.20 3.80 1x16+16/25 10.00 6.06 8.08 18.08 3.27 1.95 1.952 0.887 0.89
2 35 2 7 0.00 0.40 1.40 1.80 1x16+16/25 6.36 0.00 2.02 8.38 3.27 0.96 2.912 0.436 1.32
3 29 3 5 0.00 0.40 1.00 1.40 1x16+16/25 4.55 0.00 2.02 6.57 3.27 0.62 3.535 0.283 1.61
4 28 2 2 0.40 0.40 0.40 0.80 1x16+16/25 1.82 2.02 2.02 3.84 3.27 0.35 3.887 0.160 1.77

1 0.89
1.1 30 4 4 0.40 0.40 0.80 1.20 1x16+16/25 3.64 2.02 2.02 5.66 3.27 0.56 0.555 0.252 1.14

238 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : HUAYLLACANCHA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 67 3 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.40 1.395 0.634 0.63
2 68 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.81 2.204 0.368 1.00
3 40 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.24 2.442 0.108 1.11

1 0.63
1.1 86 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.51 0.512 0.233 0.87

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 61 1 17 0.90 1.70 3.40 5.10 2x16+16/25 7.73 2.27 6.31 14.04 4.09 3.50 3.503 0.796 0.80
2 49 4 16 0.00 0.80 3.20 4.00 2x16+16/25 7.27 0.00 4.04 11.31 4.09 2.27 5.770 0.515 1.31
3 57 2 12 0.40 0.80 2.40 3.20 1x16+16/25 10.91 2.02 4.04 14.95 3.27 2.79 8.558 1.267 2.58
4 36 1 10 0.00 0.40 2.00 2.40 1x16+16/25 9.09 0.00 2.02 11.11 3.27 1.31 9.867 0.595 3.17
5 62 5 9 0.40 0.40 1.80 2.20 1x16+16/25 8.18 2.02 2.02 10.20 3.27 2.07 11.937 0.941 4.11
6 60 4 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.71 12.651 0.324 4.44

2 1.31
2.1 35 3 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.31 0.312 0.142 1.45

239 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : HUAYLLACANCHA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 2 24 0.00 0.80 4.80 5.60 2x16+16/25 10.91 0.00 2.02 12.93 4.09 0.16 0.159 0.036 0.04
2 98 4 22 0.80 0.80 4.40 5.20 2x16+16/25 10.00 2.02 2.02 12.02 4.09 4.82 4.977 1.095 1.13
3 40 4 18 0.00 0.00 3.60 3.60 2x16+16/25 8.18 0.00 0.00 8.18 4.09 1.34 6.315 0.304 1.44
4 62 5 14 0.00 0.00 2.80 2.80 2x16+16/25 6.36 0.00 0.00 6.36 4.09 1.61 7.929 0.367 1.80
5 60 1 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 1.61 9.535 0.730 2.53
6 64 3 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 1.52 11.058 0.692 3.22
7 61 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.91 11.965 0.412 3.64
8 44 2 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.39 12.358 0.178 3.82
9 64 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.19 12.548 0.087 3.90

2 1.13
2.1 43 3 3 0.00 0.00 0.60 0.60 2x16+16/25 1.36 0.00 0.00 1.36 4.09 0.24 0.240 0.055 1.19

4 1.80
4.1 45 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.13 0.134 0.061 1.86

7 3.64
7.1 32 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.19 0.190 0.087 3.72
4 1.80
4.01 40 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.48 0.476 0.216 2.02

240 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : MAGAMPATAY CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 3 9 0.00 0.80 1.80 2.60 1x16/25 8.18 0.00 4.04 12.22 3.27 0.12 0.120 0.055 0.05
2 40 1 6 0.80 0.80 1.20 2.00 1x16/25 5.45 4.04 4.04 9.49 3.27 1.24 1.363 0.565 0.62
3 120 3 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.78 3.147 0.811 1.43
4 70 1 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.42 3.564 0.189 1.62
5 80 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.24 3.802 0.108 1.73

3 1.43
3.1 73 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.43 0.434 0.197 1.63

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 49 2 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 1.31 1.312 0.596 0.60
2 70 2 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.46 2.769 0.663 1.26
3 70 1 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.04 3.810 0.473 1.73
4 70 4 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.83 4.643 0.379 2.11

241 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : PUQUI(NUEVASFLORES) CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 7 0.40 0.40 1.40 1.80 1x16/25 6.36 2.02 2.02 8.38 3.27 0.08 0.082 0.037 0.04
2 70 2 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 1.25 1.332 0.568 0.61
3 60 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.71 2.045 0.324 0.93
4 60 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.36 2.402 0.162 1.09

2 0.61
2.1 70 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.21 0.208 0.095 0.70

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 63 1 2 0.40 0.80 0.40 1.20 1x16+16/25 1.82 2.02 4.04 5.86 3.27 1.21 1.208 0.549 0.55
2 60 1 1 0.40 0.40 0.20 0.60 1x16+16/25 0.91 2.02 2.02 2.93 3.27 0.58 1.783 0.261 0.81

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 48 3 10 0.00 0.00 2.00 2.00 1x16/25 9.09 0.00 0.00 9.09 3.27 1.43 1.428 0.649 0.65
2 110 1 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 2.29 3.718 1.041 1.69
3 55 1 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.98 4.700 0.446 2.14
4 55 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.82 5.518 0.372 2.51
5 60 2 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.54 6.053 0.243 2.75
6 50 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.15 6.202 0.068 2.82

2 1.69
2.1 50 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.15 0.149 0.068 1.76

4 2.51
4.1 50 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.15 0.149 0.068 2.58

242 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : PUQUI(NUEVASFLORES) CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 48 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.29 0.286 0.130 0.13

243 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : QUEROBAMBA CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 47 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.42 0.419 0.191 0.19

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 47 2 8 0.00 0.00 1.60 1.60 1x16+16/25 7.27 0.00 0.00 7.27 3.27 1.12 1.118 0.508 0.51
2 48 4 6 0.00 0.00 1.20 1.20 1x16+16/25 5.45 0.00 0.00 5.45 3.27 0.86 1.975 0.389 0.90
3 40 1 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.24 2.213 0.108 1.01
4 60 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.18 2.392 0.081 1.09

2 0.90
2.1 37 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.33 0.330 0.150 1.05

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 11 0.80 1.20 2.20 3.40 1x16+16/25 10.00 4.04 6.06 16.06 3.27 0.16 0.158 0.072 0.07
2 33 4 10 0.40 0.40 2.00 2.40 1x16+16/25 9.09 2.02 2.02 11.11 3.27 1.20 1.357 0.545 0.62
3 41 4 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.73 2.089 0.333 0.95
4 81 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.48 2.571 0.219 1.17

2 0.62
2.1 50 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.45 0.446 0.203 0.82
2.2 50 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.30 0.744 0.135 0.96

3 0.95
3.1 50 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.15 0.149 0.068 1.02

244 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SANFRANCISCODECATAS CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 2 8 0.00 0.00 1.60 1.60 1x16/25 7.27 0.00 0.00 7.27 3.27 0.07 0.071 0.032 0.03
2 47 2 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.84 0.910 0.381 0.41
3 44 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.52 1.434 0.238 0.65
4 49 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.44 1.871 0.199 0.85
5 61 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.36 2.234 0.165 1.02

3 0.65
3.1 89 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.26 0.265 0.120 0.77

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 71 2 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.63 0.634 0.288 0.29
2 73 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.22 0.851 0.099 0.39

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 71 1 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.06 1.056 0.480 0.48
2 135 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 1.61 2.662 0.730 1.21
3 76 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.45 3.114 0.206 1.42

2 1.21
2.1 75 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.45 0.446 0.203 1.41

245 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : SANFRANCISCODECATAS CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 107 5 8 0.00 0.40 1.60 2.00 1x16/25 7.27 0.00 2.02 9.29 3.27 3.25 3.253 1.479 1.48
2 48 2 3 0.00 0.40 0.60 1.00 1x16/25 2.73 0.00 2.02 4.75 3.27 0.75 3.999 0.339 1.82
3 140 1 1 0.40 0.40 0.20 0.60 1x16/25 0.91 2.02 2.02 2.93 3.27 1.34 5.341 0.610 2.43

1 1.48
1.1 40 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.36 0.357 0.162 1.64

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 14 0.00 0.00 2.80 2.80 1x16+16/25 12.73 0.00 0.00 12.73 3.27 0.12 0.125 0.057 0.06
2 29 1 13 0.00 0.00 2.60 2.60 1x16+16/25 11.82 0.00 0.00 11.82 3.27 1.12 1.246 0.510 0.57
3 30 4 12 0.00 0.00 2.40 2.40 1x16+16/25 10.91 0.00 0.00 10.91 3.27 1.07 2.317 0.487 1.05
4 40 4 8 0.00 0.00 1.60 1.60 1x16+16/25 7.27 0.00 0.00 7.27 3.27 0.95 3.269 0.433 1.49
5 40 4 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.48 3.745 0.216 1.70

3 1.05
3.1 86 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.77 0.767 0.349 1.40

3 1.05
3.0.1 28 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.17 0.167 0.076 1.13

246 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : SANFRANCISCODECATAS CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 35 1 15 0.00 2.00 3.00 5.00 2x16+16/25 6.82 0.00 8.08 14.90 4.09 2.13 2.133 0.485 0.48
2 33 4 14 0.40 2.00 2.80 4.80 2x16+16/25 6.36 1.01 8.08 14.44 4.09 1.95 4.082 0.443 0.93
3 52 1 10 0.40 1.60 2.00 3.60 2x16+16/25 4.55 1.01 7.07 11.62 4.09 2.47 6.553 0.561 1.49
4 60 1 9 0.80 1.20 1.80 3.00 1x16+16/25 8.18 4.04 6.06 14.24 3.27 2.80 9.349 1.271 2.76
5 61 2 8 0.00 0.40 1.60 2.00 1x16+16/25 7.27 0.00 2.02 9.29 3.27 1.85 11.204 0.843 3.60
6 40 1 6 0.40 0.40 1.20 1.60 1x16/25 5.45 2.02 2.02 7.47 3.27 0.98 12.182 0.445 4.05
7 90 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 1.34 13.521 0.608 4.66
8 78 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.70 14.217 0.316 4.97
9 78 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.46 14.681 0.211 5.18

2 0.93
2.1 23 2 2 0.40 0.40 0.40 0.80 1x16+16/25 1.82 2.02 2.02 3.84 3.27 0.29 0.289 0.131 1.06

5 3.60
5.1 68 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.40 0.405 0.184 3.79

7 4.66
7.1 70 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.42 0.416 0.189 4.85

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 83 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.49 0.494 0.224 0.22

247 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : SANMIGUELDECOYAS CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 43 5 9 0.40 0.40 1.80 2.20 1x16/25 8.18 2.02 2.02 10.20 3.27 1.44 1.435 0.652 0.65
2 90 3 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 1.07 2.506 0.487 1.14
3 90 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.27 2.774 0.122 1.26

1 0.65
1.1 41 2 2 0.40 0.40 0.40 0.80 1x16/25 1.82 2.02 2.02 3.84 3.27 0.51 0.515 0.234 0.89

2 1.14
2.1 42 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.12 0.125 0.057 1.20

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 43 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.26 0.256 0.116 0.12

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 6 0.80 0.80 1.20 2.00 1x16/25 5.45 4.04 4.04 9.49 3.27 0.09 0.093 0.042 0.04
2 65 3 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.97 1.060 0.439 0.48
3 90 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.54 1.595 0.243 0.73

2 0.48
2.1 90 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.27 0.268 0.122 0.60

248 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : CHEQUIAS CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 68 2 11 0.00 0.40 2.20 2.60 1x16/25 10.00 0.00 2.02 12.02 3.27 2.67 2.674 1.216 1.22
2 65 4 9 0.40 0.40 1.80 2.20 1x16/25 8.18 2.02 2.02 10.20 3.27 2.17 4.844 0.986 2.20
3 50 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.74 5.588 0.338 2.54
4 50 2 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.45 6.034 0.203 2.74
5 50 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.15 6.183 0.068 2.81

1 1.22
1.1 31 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.18 0.184 0.084 1.30

2 2.20
2.1 50 1 4 0.40 0.40 0.80 1.20 1x16/25 3.64 2.02 2.02 5.66 3.27 0.93 0.925 0.421 2.62
2.2 50 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.45 1.372 0.203 2.83

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 32 1 1 0.40 0.40 0.20 0.60 1x16+16/25 0.91 2.02 2.02 2.93 3.27 0.31 0.307 0.139 0.14

249 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : CHEQUIAS CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 2 11 0.00 0.80 2.20 3.00 1x16+16/25 10.00 0.00 4.04 14.04 3.27 0.14 0.138 0.063 0.06
2 32 5 9 0.40 0.80 1.80 2.60 1x16+16/25 8.18 2.02 4.04 12.22 3.27 1.28 1.418 0.582 0.64
3 38 2 4 0.40 0.40 0.80 1.20 1x16+16/25 3.64 2.02 2.02 5.66 3.27 0.70 2.121 0.320 0.96
4 80 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.48 2.597 0.216 1.18

2 0.64
2.1 30 2 2 0.40 0.40 0.40 0.80 1x16+16/25 1.82 2.02 2.02 3.84 3.27 0.38 0.377 0.171 0.82

2 0.64
2.0.1 30 3 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.27 0.268 0.122 0.77

250 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : CHEQUIAS CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 183 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 1.63 1.633 0.742 0.74
2 44 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.26 1.895 0.119 0.86

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 122 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.73 0.726 0.330 0.33

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.04 0.045 0.020 0.02
2 74 1 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.88 0.925 0.400 0.42
3 40 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.36 1.282 0.162 0.58

251 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : HUANCASH CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 20 11 21 0.00 0.80 4.20 5.00 #N/A 19.09 0.00 4.04 23.13 #N/A #N/A #N/A #N/A #N/A
2 16 1 10 0.00 0.80 2.00 2.80 #N/A 9.09 0.00 4.04 13.13 #N/A #N/A #N/A #N/A #N/A
3 72 1 9 0.00 0.80 1.80 2.60 #N/A 8.18 0.00 4.04 12.22 #N/A #N/A #N/A #N/A #N/A
4 65 1 8 0.40 0.80 1.60 2.40 #N/A 7.27 2.02 4.04 11.31 #N/A #N/A #N/A #N/A #N/A
5 65 1 7 0.00 0.40 1.40 1.80 #N/A 6.36 0.00 2.02 8.38 #N/A #N/A #N/A #N/A #N/A
6 65 2 6 0.40 0.40 1.20 1.60 #N/A 5.45 2.02 2.02 7.47 #N/A #N/A #N/A #N/A #N/A
7 0 3 4 0.00 0.00 0.80 0.80 #N/A 3.64 0.00 0.00 3.64 #N/A #N/A #N/A #N/A #N/A
8 0 1 1 0.00 0.00 0.20 0.20 #N/A 0.91 0.00 0.00 0.91 #N/A #N/A #N/A #N/A #N/A

1 #N/A
1.1 64 1 5 0.00 0.00 1.00 1.00 #N/A 4.55 0.00 0.00 4.55 #N/A #N/A #N/A #N/A #N/A
1.2 64 2 4 0.00 0.00 0.80 0.80 #N/A 3.64 0.00 0.00 3.64 #N/A #N/A #N/A #N/A #N/A
1.3 128 2 2 0.00 0.00 0.40 0.40 #N/A 1.82 0.00 0.00 1.82 #N/A #N/A #N/A #N/A #N/A

1.1 #N/A
1.1.1 41 1 1 0.00 0.00 0.20 0.20 #N/A 0.91 0.00 0.00 0.91 #N/A #N/A #N/A #N/A #N/A

1.2 #N/A
1.2.1 54 2 2 0.00 0.00 0.40 0.40 #N/A 1.82 0.00 0.00 1.82 #N/A #N/A #N/A #N/A #N/A

1 #N/A
1.0.1 16 1 6 0.00 0.00 1.20 1.20 #N/A 5.45 0.00 0.00 5.45 #N/A #N/A #N/A #N/A #N/A
1.0.2 72 1 5 0.00 0.00 1.00 1.00 #N/A 4.55 0.00 0.00 4.55 #N/A #N/A #N/A #N/A #N/A
1.0.3 65 1 4 0.00 0.00 0.80 0.80 #N/A 3.64 0.00 0.00 3.64 #N/A #N/A #N/A #N/A #N/A
1.0.4 65 1 3 0.00 0.00 0.60 0.60 #N/A 2.73 0.00 0.00 2.73 #N/A #N/A #N/A #N/A #N/A
1.0.5 65 2 2 0.00 0.00 0.40 0.40 #N/A 1.82 0.00 0.00 1.82 #N/A #N/A #N/A #N/A #N/A

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 1 23 0.00 0.80 4.60 5.40 #N/A 20.91 0.00 4.04 24.95 #N/A #N/A #N/A #N/A #N/A
2 23 8 22 0.40 0.80 4.40 5.20 #N/A 20.00 2.02 4.04 24.04 #N/A #N/A #N/A #N/A #N/A
3 37 8 14 0.40 0.40 2.80 3.20 #N/A 12.73 2.02 2.02 14.75 #N/A #N/A #N/A #N/A #N/A
4 43 2 6 0.00 0.00 1.20 1.20 #N/A 5.45 0.00 0.00 5.45 #N/A #N/A #N/A #N/A #N/A
5 39 4 4 0.00 0.00 0.80 0.80 #N/A 3.64 0.00 0.00 3.64 #N/A #N/A #N/A #N/A #N/A

252 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : HUANCASH CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V
2 #N/A
2.1 34 3 4 0.00 0.40 0.80 1.20 #N/A 3.64 0.00 2.02 5.66 #N/A #N/A #N/A #N/A #N/A
2.2 33 1 1 0.40 0.40 0.20 0.60 #N/A 0.91 2.02 2.02 2.93 #N/A #N/A #N/A #N/A #N/A

3 #N/A
3.1 37 3 6 0.00 0.00 1.20 1.20 #N/A 5.45 0.00 0.00 5.45 #N/A #N/A #N/A #N/A #N/A
3.2 36 3 3 0.00 0.00 0.60 0.60 #N/A 2.73 0.00 0.00 2.73 #N/A #N/A #N/A #N/A #N/A

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 11 1 4 0.00 0.00 0.80 0.80 #N/A 3.64 0.00 0.00 3.64 #N/A #N/A #N/A #N/A #N/A
2 35 3 3 0.00 0.00 0.60 0.60 #N/A 2.73 0.00 0.00 2.73 #N/A #N/A #N/A #N/A #N/A

253 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 2

LOCALIDAD : HUANCASH CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R'

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 53 3 6 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.95 0.946 0.430 0.43
2 45 1 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.40 1.347 0.183 0.61
3 46 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.27 1.621 0.124 0.74

1 0.43
1.1 84 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.50 0.500 0.227 0.66

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 2 5 0.00 0.00 1.00 1.00 1x16/25 4.55 0.00 0.00 4.55 3.27 0.04 0.045 0.020 0.02
2 122 3 3 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 1.09 1.133 0.495 0.52

254 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : JIRCAN CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 600 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 53 6 21 0.00 0.00 6.30 6.30 2x16+16/25 14.32 0.00 0.00 14.32 4.09 3.10 3.104 0.705 0.71
2 15 1 15 0.00 0.00 4.50 4.50 1x16+16/25 20.45 0.00 0.00 20.45 3.27 1.00 4.108 0.456 1.16
3 28 8 14 0.00 0.00 4.20 4.20 1x16+16/25 19.09 0.00 0.00 19.09 3.27 1.75 5.857 0.795 1.96
4 10 2 6 0.00 0.00 1.80 1.80 1x16+16/25 8.18 0.00 0.00 8.18 3.27 0.27 6.124 0.122 2.08
5 35 1 4 0.00 0.00 1.20 1.20 1x16+16/25 5.45 0.00 0.00 5.45 3.27 0.62 6.749 0.284 2.36
6 35 1 3 0.00 0.00 0.90 0.90 1x16+16/25 4.09 0.00 0.00 4.09 3.27 0.47 7.218 0.213 2.58
7 35 2 2 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.31 7.530 0.142 2.72

1 0.71
1.1 45 1 2 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.40 0.402 0.183 0.89
1.2 45 1 1 0.00 0.00 0.30 0.30 1x16+16/25 1.36 0.00 0.00 1.36 3.27 0.20 0.602 0.091 0.98

1 0.71
0.1.1 21 2 4 0.00 0.00 1.20 1.20 1x16+16/25 5.45 0.00 0.00 5.45 3.27 0.37 0.375 0.170 0.88
0.1.2 40 2 2 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.36 0.732 0.162 1.04

3 1.96
3.1 42 4 6 0.00 0.00 1.80 1.80 1x16+16/25 8.18 0.00 0.00 8.18 3.27 1.12 1.124 0.511 2.47
3.2 40 2 2 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.36 1.481 0.162 2.63

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 40 1 19 0.00 0.75 5.70 6.45 2x16+16/25 12.95 0.00 3.79 16.74 4.09 2.74 2.739 0.623 0.62
2 37 3 18 0.00 0.75 5.40 6.15 2x16+16/25 12.27 0.00 3.79 16.06 4.09 2.43 5.170 0.552 1.17
3 45 5 15 0.00 0.75 4.50 5.25 2x16+16/25 10.23 0.00 3.79 14.02 4.09 2.58 7.749 0.586 1.76
4 45 3 10 0.00 0.75 3.00 3.75 2x16+16/25 6.82 0.00 3.79 10.61 4.09 1.95 9.701 0.444 2.20
5 45 2 7 0.00 0.75 2.10 2.85 2x16+16/25 4.77 0.00 3.79 8.56 4.09 1.58 11.277 0.358 2.56
6 45 1 5 0.00 0.75 1.50 2.25 1x16/25 6.82 0.00 3.79 10.61 3.27 1.56 12.838 0.710 3.27
7 42 0 4 0.75 0.75 1.20 1.95 1x16/25 5.45 3.79 3.79 9.24 3.27 1.27 14.108 0.577 3.85
8 42 2 4 0.00 0.00 1.20 1.20 1x16/25 5.45 0.00 0.00 5.45 3.27 0.75 14.858 0.341 4.19
9 60 2 2 0.00 0.00 0.60 0.60 1x16/25 2.73 0.00 0.00 2.73 3.27 0.54 15.393 0.243 4.43

6 3.27
6.1 92 1 1 0.00 0.00 0.30 0.30 1x16/25 1.36 0.00 0.00 1.36 3.27 0.41 0.410 0.187 3.46

255 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : JIRCAN CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 600 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C2

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 3 3 29 0.60 4.24 8.70 12.94 2x16+16/25 19.77 1.52 13.74 33.51 4.09 0.41 0.411 0.093 0.09
2 13 1 26 0.00 3.64 7.80 11.44 2x16+16/25 17.73 0.00 12.22 29.95 4.09 1.59 2.004 0.362 0.46
3 38 1 25 1.20 3.64 7.50 11.14 2x16+16/25 17.05 3.03 12.22 29.27 4.09 4.55 6.552 1.034 1.49
4 26 6 24 1.24 2.44 7.20 9.64 2x16+16/25 16.36 3.13 9.19 25.56 4.09 2.72 9.270 0.618 2.11
5 45 15 18 0.00 1.20 5.40 6.60 1x16+16/25 24.55 0.00 6.06 30.61 3.27 4.51 13.776 2.048 4.16
6 8 1 3 0.00 1.20 0.90 2.10 1x16+16/25 4.09 0.00 6.06 10.15 3.27 0.27 14.042 0.121 4.28
7 78 0 2 0.60 1.20 0.60 1.80 1x16+16/25 2.73 3.03 6.06 8.79 3.27 2.24 16.285 1.019 5.30
8 50 2 2 0.60 0.60 0.60 1.20 1x16+16/25 2.73 3.03 3.03 5.76 3.27 0.94 17.227 0.428 5.72

3 1.49
3.1 10 1 1 0.00 0.60 0.30 0.90 1x16+16/25 1.36 0.00 3.03 4.39 3.27 0.14 0.144 0.065 1.55
3.2 36 0 0 0.60 0.60 0.00 0.60 1x16/25 0.00 3.03 3.03 3.03 3.27 0.36 0.501 0.162 1.72

4 2.11
4.1 50 4 4 0.64 0.64 1.20 1.84 1x16+16/25 5.45 3.23 3.23 8.69 3.27 1.42 1.421 0.646 2.75

5 4.16
5.1 50 6 11 0.00 0.00 3.30 3.30 1x16+16/25 15.00 0.00 0.00 15.00 3.27 2.45 2.454 1.115 5.27
5.2 50 5 5 0.00 0.00 1.50 1.50 1x16+16/25 6.82 0.00 0.00 6.82 3.27 1.12 3.569 0.507 5.78

256 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : URPISH CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C1R

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 14 1 2 0.00 0.40 0.40 0.80 1x16+16/25 1.82 0.00 2.02 3.84 3.27 0.18 0.176 0.080 0.08
2 35 1 1 0.40 0.40 0.20 0.60 1x16+16/25 0.91 2.02 2.02 2.93 3.27 0.34 0.511 0.152 0.23

CIRCUITO : C1

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 66 6 32 0.00 0.40 6.40 6.80 2x16+16/25 14.55 0.00 2.02 16.57 4.09 4.47 4.472 1.016 1.02
2 65 3 26 0.00 0.40 5.20 5.60 2x16+16/25 11.82 0.00 2.02 13.84 4.09 3.68 8.151 0.836 1.85
3 46 2 23 0.00 0.40 4.60 5.00 2x16+16/25 10.45 0.00 2.02 12.47 4.09 2.35 10.498 0.533 2.39
4 45 7 21 0.00 0.40 4.20 4.60 1x16+16/25 19.09 0.00 2.02 21.11 3.27 3.11 13.606 1.413 3.80
5 55 10 14 0.00 0.40 2.80 3.20 1x16+16/25 12.73 0.00 2.02 14.75 3.27 2.65 16.260 1.206 5.01
6 40 3 4 0.00 0.40 0.80 1.20 1x16+16/25 3.64 0.00 2.02 5.66 3.27 0.74 17.000 0.337 5.34
7 40 1 1 0.40 0.40 0.20 0.60 1x16+16/25 0.91 2.02 2.02 2.93 3.27 0.38 17.384 0.174 5.52

5 5.01
5.1 29 1 4 0.00 0.00 0.80 0.80 1x16+16/25 3.64 0.00 0.00 3.64 3.27 0.35 0.345 0.157 5.16
5.2 15 1 3 0.00 0.00 0.60 0.60 1x16+16/25 2.73 0.00 0.00 2.73 3.27 0.13 0.479 0.061 5.22
5.3 30 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.18 0.657 0.081 5.30

5 5.01
5.1.1 29 2 2 0.00 0.00 0.40 0.40 1x16+16/25 1.82 0.00 0.00 1.82 3.27 0.17 0.173 0.078 5.08

257 de 258
CALCULO DE CAIDA DE TENSION
S.E. N 1

LOCALIDAD : URPISH CONDUCTOR AUTOSOPORTADO: AAAC FACTOR DE POTENCIA (COS f )


SERVICIO: SERVICIO PARTICULAR TRANSFORMADOR: MONOFASICO fp( S.P.) : 1
FAC.SIMULT.(fs) : 0.5 TENSION : 440 V fp( C.E.) : 0.9
CALIFICACION ELECTRICA : 400 W/LOTE SISTEMA: 440/220 V

CIRCUITO : C2

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 14 0 25 0.00 0.80 5.00 5.80 2x16+16/25 11.36 0.00 3.03 14.39 4.09 0.82 0.824 0.187 0.19
2 40 2 25 0.00 0.80 5.00 5.80 2x16+16/25 11.36 0.00 3.03 14.39 4.09 2.35 3.179 0.535 0.72
3 15 0 23 0.40 0.80 4.60 5.40 2x16+16/25 10.45 1.01 3.03 13.48 4.09 0.83 4.006 0.188 0.91
4 45 4 23 0.00 0.40 4.60 5.00 1x16+16/25 20.91 0.00 2.02 22.93 3.27 3.38 7.382 1.535 2.45
5 45 2 19 0.40 0.40 3.80 4.20 1x16+16/25 17.27 2.02 2.02 19.29 3.27 2.84 10.223 1.291 3.74
6 45 3 17 0.00 0.00 3.40 3.40 1x16+16/25 15.45 0.00 0.00 15.45 3.27 2.28 12.499 1.034 4.77
7 45 6 14 0.00 0.00 2.80 2.80 1x16+16/25 12.73 0.00 0.00 12.73 3.27 1.87 14.373 0.852 5.62
8 50 8 8 0.00 0.00 1.60 1.60 1x16+16/25 7.27 0.00 0.00 7.27 3.27 1.19 15.562 0.541 6.16

CIRCUITO : C2

NUMERO C A R G A FORMACION CORRIENTE CAIDA DE TENSION


PUNTO LONGITUD DE SNL ESPECIAL S - ESP. S.P. ACUMULADA DEL I - VIV. I - ESP. S I - ESP. I - TOTAL K
(m) (V/m-A) DV SDV %DV %SDV
LOTES (kW) (kW) (kW) (kW) CONDUCTOR (A) (A) (A) (A)

1 49 4 21 0.00 0.80 4.20 5.00 2x16+16/25 9.55 0.00 2.02 11.57 4.09 2.32 2.318 0.527 0.53
2 43 2 17 0.00 0.80 3.40 4.20 2x16+16/25 7.73 0.00 2.02 9.75 4.09 1.71 4.032 0.390 0.92
3 86 0 15 0.80 0.80 3.00 3.80 2x16+16/25 6.82 2.02 2.02 8.84 4.09 3.11 7.141 0.707 1.62
4 90 4 15 0.00 0.00 3.00 3.00 1x16/25 13.64 0.00 0.00 13.64 3.27 4.02 11.157 1.825 3.45
5 90 2 11 0.00 0.00 2.20 2.20 1x16/25 10.00 0.00 0.00 10.00 3.27 2.94 14.101 1.339 4.79
6 90 2 9 0.00 0.00 1.80 1.80 1x16/25 8.18 0.00 0.00 8.18 3.27 2.41 16.511 1.095 5.88
7 55 7 7 0.00 0.00 1.40 1.40 1x16/25 6.36 0.00 0.00 6.36 3.27 1.15 17.656 0.521 6.40

2 0.92
2.1 80 1 1 0.00 0.00 0.20 0.20 1x16/25 0.91 0.00 0.00 0.91 3.27 0.24 0.238 0.108 1.02

4 3.45
4.1 42 2 4 0.00 0.00 0.80 0.80 1x16/25 3.64 0.00 0.00 3.64 3.27 0.50 0.500 0.227 3.68
4.2 62 2 2 0.00 0.00 0.40 0.40 1x16/25 1.82 0.00 0.00 1.82 3.27 0.37 0.869 0.168 3.84

258 de 258