ECH 400

4-step Chiller and Heat Pump Controller


Technical Data Sheet

GENERAL DESCRIPTION MODELS


ECH 400

CODE MODEL DESCRIPTION


MW324000 ECH 420 HEAT PUMP WITH 4 STEPS/ 2 CIRCUITS + MODBUS
MW324005 ECH 420/V WITH SCREW CONNECTORS
MW324006 ECH 420/FV WITH FREECOOLING AND SCREW CONNECTORS
MW324600 EKW 400 REMOTE TERMINAL FOR ECH 400, WALL MOUNT
MW324650 EKP 400 TERMINALE TERMINAL FOR ECH 400, PANEL MOUNT

ECH 400 is a compact device for FUNCTIONS ACCESSORIES


controlling a chiller and heat pump for
Hot/cold adjustment; Expansion module: makes it possible
the following types of conditioning:
Controls 1, 2, 3, 4 compressors. to add another 4 analogue inputs, 4
air-air
Water temperature control at outlet. digital inputs and 2 digital outputs.
air-water
Condensation control Copy card for uploading and
water-water
Dynamic set point downloading parameter maps
air-water
Automatic change-over Remote keyboard (up to 100 m)
motor-condensing
Electrical heater controllers for anti- which may be connected up directly
The controller is able to control up to 4
freeze or integration with heat without a serial interface
power steps in a maximum of 2 cooling
pump; CF Modules for commanding
circuits (e.g. : 2 circuits and 2
Continuous control of condenser fan condenser fans with current rating
compressors per circuit).
speed by external device (CF of over 2A.
The controller consists of 2 elements: the
module); Interface Module for connection to
power card and user interface. The
Defreezing cycle control; personal computer
power panel fitted behind the panel has
Water pump cycle operation control Software Param Manager
all the relays and digital/analogue inputs
Hot Start controlled by personal computer
needed to control typical air conditioning
Anti-freeze Temperature probes
applications.
Remote selection of hot/cold mode; Pressure transducers
The overall dimensions are compact to
Temperature or pressure operation Power transformers
reduce panel space for electrical
Parameters can be set from Front panel Protection
connections;
keyboard by using a Personal
It is easy to install by using quick-fit
Computer or copy card;
connectors.
User interface with a menu featuring
2 different levels of access through
password management
Complete alarm diagnostics.
Differential temperature controller;
Recording of on-duty hours
Facility for interfacing with BMS via
Modbus protocol
Set operation mode
INSTALLATION Control alarm situations
ST1 Probe absent
OUTPUTS NTC input: water/air at input Check status of resources
Digital input: request for heating
The instrument has the following
Digital input: temperature controller Front panel
outputs: request
8 relay contacts differential NTC input
4 low voltage outputs; ST2 Probe absent
NTC input Outlet water/air, anti-
Serial outputs freeze
Relays Digital input: Cooling request
The following configurations are ST3 Probe absent
NTC input: condensation
available:
Input 4.-20mA for condensation
Input 4-20 mA for dynamic setpoint
anti-freeze electrical heater output
RL1 Compressor 1 for water-water machines with gas
RL2- Configurable: reversal KEYS
RL7 Disabled NTC in heating controller for water-
Circuit 1 reversal valve water reversal machines
Circuit 2 reversal valve ST4 Probe absent Actuates alarms reset and
Circuit 1 condenser fan NTC input: condensation instrument switch-on and off.
Circuit 2 condenser fan Multifunctional digital input In the menu mode, it becomes
Heater 1 NTC input: outdoor temperature the SCROLL DOWN or DOWN key
Heater 2
ST5 Probe absent ( value reduced)
Pump
NTC input: water/air at input In heat mode, whenever you press
Evaporator fan
ST6 Probe absent this key, the sequence is:
Power step 2
NTC input: condensation 2 Stand-by ! cooling ! heating
Power step 3
Input 4.-20mA for condensation ! stand-by
Power step 4
anti-freeze electrical heater output if heat mode is not enabled:
RL8 Cumulative alarm
for water-water machines with gas Stand-by ! cooling ! stand-by
reversal In the menu mode, it becomes
Triac
the SCROLL UP or UP key (value
Phase cutting outputs: increased)
NOTE: LOW VOLTAGE OUTPUTS DIGITAL INPUTS If you press and release both keys
within 2 seconds, you drop down by
TC1 Output for piloting fan external modules There are 11 voltage-free digital inputs
one level in the viewing menu. .
for circuit 1. ST1, ST2 and ST4 can be added to them, If you press and release both keys
TC2 Output for piloting fan external modules if configured as digital inputs.. within 2 seconds, you rise by one level
for circuit 2.
All digital inputs are configurable and
can have the following meanings:
ID1- Output disabled
DISPLAY
4-20mA outputs:
ID11 Flow switch The following are shown under normal
Remote OFF
viewing:
Remote heat cool
AN1 Output for controlling fans for circuit 1 control temperature in tenths
Thermal switch for compressor 1
AN2 Output for controlling fans for circuit 2
Thermal switch for compressor 2 degrees Celsius or Fahrenheit
Thermal switch for compressor 3 alarm code, if at least one alarm is
Thermal switch for compressor 4
Serial outputs Thermal switch for circuit 1 fan
active. If several alarms are active,
There are 2 asynchronous outputs on the Thermal switch for circuit 2 fan the first is shown according to the
control: Circuit 1 high pressure Alarms Table.
Circuit 2 high pressure 2
channel for serial communication If temperature control is not
Circuit 1 low pressure
with a personal computer through a Circuit 2 low pressure analogic and depends on the status
suitable interface module High Pressure compressor 1 of a digital input (ST1 or ST2)
High Pressure compressor 2 configured as digital inputs) the
(9600,e,8,1).
High Pressure compressor 3
channel for serial communication High Pressure compressor 4
On or Off label is used according
with a suitable keyboard. Power Circuit 1 end of de-freezing to temperature controller status
supply 12 VDC (2400,e,8,1). Circuit 2 end of defreezing (active - inactive).
2nd power step request
In menu mode, the display depends
3rd power step request
ANALOG INPUTS 4th power step request on its current position. Labels and
codes are used to help the user
There are 6 analogue inputs:
NOTE: Polarities can be configured. identify the set function.
4 NTC temperature sensors (10K at
25C),
2 configurable transducers NTC/4-
USER INTERFACE
20mA.
The following configurations are The interface, on the instrument front
available: panel, enables all the instruments
operations, and especially the following:

ECH 400
2/6
LED TEMPERATURE A silent speed can be set for silenced
operation (e.g. for nights).
CONTROL FUNCTIONS
DEFROSTING

OPERATING MODES Defrosting is active in HEAT mode only. It


ON if compressor 1 active is used to prevent ice forming on the
OFF if compressor n. is OFF The controller is able to manage single-
surface of the outside exchanger. Ice
BLINK if safety timings are in or multi-stage compressors for one or
progress
significantly cuts down the machines
two cooling circuits. The control has 4
Slow BLINK if compressor being thermo-dynamic performance and may
operating statuses:
defrozen lead to damage.
cooling
The defrosting cycle can be controlled
heating
ON if the anti-freeze internal heater for one condenser or for two separate
stand-by
or boiler are active ones, and defrosting control can be
OFF if the anti-freeze internal heater off
managed with either one or two
or boiler are inactive The operating mode can be selected
ON if the device is in heating mode.
condenser probes, according to internal
from the keyboard or from the digital
parameters.
ON if controller in cooling mode inputs according to set parameters.
Unless the machine is configured as a
INTEGRATING ELECTRICAL HEATERS
motorised condensing type, activation
WALL KEYBOARD (REMOTE) and de-activation of loads depends The controller is able to control electrical
Remote keyboard dynamically on the set temperature heaters in order to integrate heating with
control functions, on the the heat pump configuration. . The air
temperature/pressure values measured supplied by the internal exchanger is
by the probes and on setpoints. further heated according to parameters
and ambient conditions.
DYNAMIC SETPOINT
ANTI-FREEZE
The regulation algorithm may be used to
modify the set point automatically on the If a refrigerating water internal exchanger
basis of outdoor conditions. is supplied, this function prevents water
The purpose is to save ECH and to icing in cooling mode, by activating a
compensate for drops in machine heater
performance if outside temperatures are
Functions are identical to those listed in particularly demanding. . DISCHARGED MACHINE
the displays section. A machine functionality check is
The only difference is the use of the UP AUTOMATIC CHANGE-OVER performed in all operating modes
and DOWN keys (increase and reduction Changes from cooling to heating (defrosting excluded) to detect any leaks
of value) which are separated from the according to parameters and ambient in the gas circuit or any reversal valve
MODE and ON/OFF keys (see photo). conditions. faults. When the controller detects these
problems, all outputs are disabled.
PARAMETERS
DIFFERENTIAL TEMPERATURE
By means of a set of parameters, one can CONTROL INTERNAL FAN
set the different types of machine and Used to control temperature according Up to 3 inputs can be configured to
the operating values of the different command the same number of fan
to the two inputs. With this type of
algorithms. Parameters can be set in the control, for example, a fluid can be speeds in the internal exchanger
following ways: thermostat controlled whether in cooling
instrument keyboard RECORDING OF DUTY HOURS
or heating mode, setting the fluid equal
Copy Card to outside ambient temperature plus a The device stores the number of duty
Through PC (with software Param hours of the following in the permanent
constant differential (positive or
Manager and interface module). negative) set by the user memory:
Viewability or non viewability of hydraulic pump
parameters and labels can be CONDENSATION CONTROL compressors
programmed from the Personal
All controllers in the ECH 400 family
Computer.
control condenser fan speed. They do so
by means of external modules, according
to condenser temperature/pressure and
selected parameters. Additionally, ECH
400 includes all functions and protective
devices to ensure efficient fan operation
(cut-off, bypass)

ECH 400
3/6
DIAGNOSTICS FORBIDDEN USE
Expansion dimensions
Any use other than permitted use is
The controller can perform full systems forbidden. Please note that relay contacts
diagnostics of the machine and signal supplied are functional and are subject
alarms. to faults (as they are controlled by an
For some alarms the signal will not be electronic component and may be
given for a certain amount of time, shorted or remain open). Protective
preset by a parameter. For others, the devices recommended by product
number of tripping events/hour is standards or suggested by common sense
counted. If, in the space of one hour, in response to evident safety
these events exceed a set threshold requirements must be implemented
established by means of a parameter, an outside of the instrument.
alarm is activated and is then manually
reset.
Alarms with manual reset are reset by RESPONSIBILITY AND
pressing the ON-OFF button.
When an alarm is triggered, two things
RESIDUAL RISKS
occur: The Constructor shall not be held liable
Corresponding loads are shut down for any damage due to:
The alarm is indicated on the installation/use other than those
keyboard display intended, and, in particular, failure
The alarm/event messages are identified to comply with the safety
by labels (code errors Exx). instructions specified by current
regulations and/or provided in this
document;
USE CONDITIONS use with equipment which does not
provide adequate protection against
PERMITTED USE
electric shocks, water and dust
This product is used to control single under the effective conditions of
circuit chillers and heat pumps. installation;
To ensure safety, the controller must be use with equipment which permits
installed and operated in accordance access to hazardous parts without
with the instructions supplied, and access the use of tools;
to high voltage components must be installation/use with equipment
prevented under regular operating which does not comply with current
conditions. The device must be properly regulations and legislation.
protected against water and dust and
must be accessible by tool only. The
device is suitable for installing in a
DIMENSIONS AND
household appliance and/or similar air ASSEMBLY
conditioning device.
According to the reference regulations, it
Dimensions of basic module
is classified:
In terms of construction, as an
automatic electronic control device
to be incorporated with
independent assembly or integrated;
In terms of automatic operating
characteristics, as a type 1 action
control device, with reference to
manufacturing tolerances and drifts;
As a class 2 device in connection
with protection against electrical
shock;
As a class A device in connection
with software structure and class.

ECH 400
4/6
CONNECTION Detail of connectors with NTC sensors

DIAGRAMS

CONN A CONN B - S +

C
A B

12AC AN1 GND GND ST4 ST3 ST2 ST1 NC AN2 GND GND NC ID11 ST6 ST5
12AC 12DC TC1 ID5 ID4 ID3 ID2 ID1 NC 12 DC TC2 ID10 ID9 ID8 ID7 ID6

ESP

D E F G H I L M N

CF CF
1 2 3 4 5 6 7 8 9 10 SERIALE
CONTROL CONTROL

TTL CABLE

EMI
FILTER
Line
COPY CARD

Detail of connectors with pressure sensors

Basic module

A CONNECTOR A H RELAY 5
B CONNECTOR B I: RELAY 6
C REMOTE KEYBOARD L: RELAY 7 CONN A CONN B
D RELAY 1 M: COMMON CONTACT
E RELAY 2 FOR RELAY
F RELAY 3 N: ALARM RELAY 12 AC AN1 GND GND ST4 ST3 ST2 ST1 NC AN2 GND GND NC ID11 ST6 ST5

G RELAY 4 O: SERIAL 12AC 12 DC TC1 ID5 ID4 ID3 ID2 ID1 NC 12 DC TC2 ID10 ID9 ID8 ID7 ID6

P: EXPANSION

Keyboard connections CF CF
CONTROL CONTROL

A
EMI
FILTER

Line

S + - Expansion connections A CONNECTOR A F ID12


B EXPANSION G ID13
C RELAY 9 H ID14
B D RELAY 10 I: ID15
I

E COMMON CONTACT L: CONN C


H

25
G

L
F

24 26
E

S + -
D

A REAR: FLUSH- MOUNTED KEYBOARD


B REAR: PANEL-MOUNTED KEYBOARD
B
A

ECH 400
5/6
TECHNICAL DATA DISCLAIMER
TECHNICAL DATA This publication is the exclusive property
of Invensys Controls Italy S.r.l. which
absolutely forbids reproduction and
Typical Min. Max. divulging of the same unless it expressly
Power supply voltage 12V~ 10.8V~ 13.2V~ authorises such acts. Nevertheless,
Power supply frequency 50Hz/60Hz --- ---
Invensys Controls Italy S.r.l. cannot
Power 11VA --- ---
accept any responsibility due to use of
Insulation class 1 --- ---
the said publication. This also applies to
Protection class Front IP0 --- ---
any person or company involved in
Operating temperature 25C -10C 60C
Operating ambient humidity 30% 10% 90% creating and drafting this manual.
(non-condensing) Invensys Controls Italy S.r.l. reserves
Storage ambient temperature 25C -20C 85C the right to make any modifications,
Storage ambient humidity 30% 10% 90% whether aesthetic or functional, without
(non-condensing) any notice at any time.

ELECTROMECHANICAL
FEATURES

Digital outputs n 8 relays 5 A resistive; hp 230VAC; 1/8 hp 125VAC (base)


110/230 V Total current on relays must not exceed 10A
n 2 relays 5 A resistive; hp 230VAC; 1/8 hp 125VAC (expansion)
Analogue outputs n 2 outputs, triac piloting LOW VOLTAGE or 4-20 mA
configurable
Analogue inputs n 4 NTC R25 10K
n 2 configurable outputs 4-20mA / NTC R25 10K
Digital inputs N 11 Voltage-free digital inputs (base)
n 4 Voltage-free digital inputs (expansion)
Terminals and n 1 Connector 10-way high voltage step 7.5
connectors n 2 Connectors 16-way, snap-fit, low voltage, step 4,2, AWG 16-28
n 1 Connector p2.5 5-way remote control and memory card, AWG
24-30
n 1 Connector 20-way expansion connection
n 1 terminal 3-way for remote keyboard
Serial lines n 1 serial line 9600
n 1 serial line 2400 remote keyboard

The instrument must be powered by a


suitable current transformer with the
following characteristics:
Primary voltage: 230V~10%;
110V~10%
Secondary voltage: 12V~
Power supply frequency: 50Hz; 60Hz
Power: 11VA;

ECH 400
2002/04
ECH 400
Cod: 8IS20102