Low consumption Y-Pack SE and Y-Pack HE

TCAEY-THAEY 2702160
Cooling capacity: 66.6160.2 kW - Heating capacity: 79.4175.6 kW

3 capacity steps
ESEER up to
4.24
Wide range of TCAEQY 270

accessories THAESY 2145

TCAEBY 2160

Web code TCAEBY: YK001 - Web code TCAETY-TCAESY-TCAEQY-THAETY-THAESY: YKE01


Packaged reversible air-cooled heat pumps and water chillers
with axial fans. Range with hermetic Scroll compressors and R410A refrigerant.

Construction features Models


Compressor: hermetic, rotary scroll compressor, complete with thermal TCAEBY: standard unit designed for cooling only.
protection and crankcase heater. TCAETY: high efficiency unit designed for cooling only.
2 or 3 capacity steps depending on the models with high efficiency at partial TCAESY: silenced unit designed for cooling only.
loads. Water side heat exchanger: with stainless steel plates, complete with TCAEQY: super-silenced unit designed for cooling only.
closed cell polyurethane foam rubber insulation and water flow differential THAETY: heat pump unit.
pressure switch. THAESY: silenced heat pump unit.
Air side heat exchanger: featuring finned coil with copper pipes and aluminium
fins. Factory fitted accessories
Fan: electric axial fans with external rotor, equipped with internal thermal PUMP with single or double electric pump, including an automatic pump in
protection, protection grilles and proportional electronic device for continuous standby, complete with expansion tank, safety valve and water side pressure
fan rotation speed regulation (TCAEBY excluded). gauge. The pumps are available in the low or high pressure versions.
Control: microprocessor electronic control with Adaptive Function Plus logic. TANK&PUMP with built-in buffer tank from 250 to 450 litres and single or
Support Structure: made of galvanised sheet steel and painted with polyester double electric pump, complete with expansion tank, air bleed valves, safety
powders. valve, and water side pressure gauge.
The unit is also complete with: Desuperheater.
- compressor and fan thermal overload switches. 100% heat recover.
Electronic expansion valve.
Versions Condensing control 10C (TCAEBY only) / 15C.
B - Standard version (TCAEBY). Power factor correction capacitors (cosI > 0.91).
T - High efficiency version with a larger condensing section (TCAETY-THAETY). Soft starter.
S - Silenced version complete with soundproofed compressor compartment, Refrigerant circuit high and low pressure gauges.
lower speed fans, and larger condensing section (TCAESY-THAESY). Metal filters or coil protection grilles.
Q - Super-silenced version complete with soundproof compressor technical Copper/copper or copper/pre-painted aluminium coils.
compartment, super-low speed fans and larger condensing section (TCAEQY). Digital input for double set-point.
4-20 mA analogue input for shifting set-point.
Evaporator antifreeze resistance, buffer tank, pumps and heat exchangers for
heat recovery if present.
Interfaces for serial communication with other devices.
Rubber anti-vibration mountings.

Accessories supplied loose


Remote keyboard with display.
Clock board.
Rhoss supervisors for unit monitoring and remote management.
Rhoss sequencer for integrated management of several water chillers.

38
COOLING OUTDOOR
ONLY HEAT PUMP INSTALLATION

TCAEBY MODEL 270 280 290 2100 2115 2130 2145 2160

WATER CHILLERS
Nominal cooling capacity kW 67,1 74,9 82,6 95,5 110 119,9 137,8 154,2

HEAT PUMPS
Air-cooled
Axial fans
E.E.R. 2,59 2,64 2,51 2,64 2,67 2,59 2,61 2,56
Absorbed power kW 25,91 28,37 32,91 36,17 41,2 46,29 52,8 60,23
TCAETY-TCAESY-TCAEQY MODEL 270 280 290 2100 2115 2130 2145 2160
Nominal cooling capacity kW 69,9 79,1 87,5 100,6 113,9 125,3 142,3 160,2
Nominal cooling capacity kW 69,9 79,1 87,5 100,6 107,5 118,4 135,3 150,3
Nominal cooling capacity kW 66,6 74,6 82 94,5 100,5 107,5 124,4 137,4

WATER CHILLERS

Centrifugal fans
HEAT PUMPS
E.E.R. 2,91 2,93 2,84 2,84 2,87 2,85 2,84 2,84

Air-cooled
E.E.R. 2,91 2,93 2,84 2,84 2,63 2,62 2,58 2,55
E.E.R. 2,65 2,8 2,57 2,68 2,3 2,26 2,28 2,17
E.S.E.E.R. 4,19 4,24 4,18 4,15 4,24 4,14 4,12 4,09
ESEER+ 4,99 5,06 5,04 4,99 5,07 4,96 4,94 4,91
Absorbed power kW 24,02 27 30,81 35,42 39,69 43,96 50,11 56,41

Condenserless units
WATER CHILLERS
Absorbed power kW 24,02 27 30,81 35,42 40,87 45,19 52,44 58,94

HEAT PUMPS
Water-cooled
Absorbed power kW 25,13 26,64 31,91 35,26 43,7 47,57 54,56 63,32
THAETY-THAESY MODEL 270 280 290 2100 2115 2130 2145 2160
Nominal heating capacity kW 79,4 86,3 96,4 111,5 122,5 139,6 157,6 175,6
Nominal heating capacity kW 79,4 86,3 96,4 111,5 120,5 135,5 154,6 170,6
C.O.P. 3,33 3,41 3,25 3,31 3,18 3,28 3,19 3,18
C.O.P. 3,33 3,41 3,25 3,31 3,19 3,28 3,22 3,18

PROCESS COOLING
INDUSTRIAL &
Nominal cooling capacity kW 69,1 77,4 84,9 98,9 110,6 123,4 140,8 159,3
Nominal cooling capacity kW 69,1 77,4 84,9 98,9 106,8 118,1 135,2 149,7
Absorbed power kW 23,84 25,31 29,66 33,69 38,52 42,56 49,4 55,25
Absorbed power kW 23,84 25,31 29,66 33,69 37,77 41,31 48,01 53,65
TCAEY-THAEY MODEL 270 280 290 2100 2115 2130 2145 2160
TCAEBY sound pressure dB(A) 53 53 53 55 61 61 61 62

Polyvalent systems
TCAETY-THAETY sound pressure dB(A) 50 51 51 52 55 55 56 56
TCAESY-THAESY sound pressure dB(A) 48 49 49 50 52 52 53 53
TCAEQY sound pressure dB(A) 46 47 47 48 49 49 50 50

EXP
TCAEBY sound power dB(A) 82 82 82 84 90 90 90 91
TCAETY-THAETY sound power dB(A) 76 77 77 78 84 84 85 85
TCAESY-THAESY sound power dB(A) 74 75 75 76 81 81 82 82
TCAEQY sound power dB(A) 72 73 73 74 78 78 79 79

CONDENSING UNITS
Scroll/step compressor no. 2/3 2/2 2/3 2/3 2/3 2/2 2/3 2/2
Circuits no. 1 1 1 1 1 1 1 1
Electric power supply V-ph-Hz 400-3+N-50 400-3+N-50400-3+N-500 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50 400-3+N-50
SIZES AND WEIGHTS 270 280 290 2100 2115 2130 2145 2160
W - Version B width mm 2.650 2.650 2.650 3.150 3.150 3.150 3.150 3.450
W - Version T - S - Q width mm 3.150 3.150 3.150 3.150 3.250 3.250 3.250 3.250
SYSTEM ACCESSORIES
H - Version B height mm 1.700 1.700 1.700 1.700 1.730 1.730 1.730 1.730
H - Version T - S - Q height mm 1.520 1.520 1.520 1.520 2.000 2.000 2.000 2.000
D - Version B depth mm 1.210 1.210 1.210 1.210 1.210 1.210 1.210 1.210
D - Version T - S - Q depth mm 1.210 1.210 1.210 1.210 1.520 1.520 1.520 1.520
TCAEBY weight kg 685 725 870 945 1.020 1.040 1.100 1.160
TCAETY-TCAESY-TCAEQY weight kg 745 765 910 980 1.130 1.195 1.225 1.290
THAETY-THAESY weight kg 810 830 975 1045 1.215 1.285 1.315 1.390
FAN COIL CONVECTORS

Details under the following conditions:


Air: 35C - Water: 12/7C
Air: 7C, D.B - 6C W.B.- Water: 40/45C.
At 10 m from the unit in free field (Q = 2), coil side.
Total sound power level in dB(A) on the basis of measurements

taken in accordance with UNI EN-ISO 9614.


Weight refers to the non-accessorised unit when empty.
TERMINAL UNITS

ESEER (European Seasonal EER) - Average European seasonal

efficiency.
ESEER with Adaptive Function Plus software. ESERR+ is not Eurovent certified.
TCAESY-THAESY silenced versions.
TCAEQY super-silenced versions.
Performance according to EN 14511:2013