You are on page 1of 3

Chemists Perspective

Metals Analysis in Transformers,


Load Tap-Changers
and Oil Circuit Breakers

by Lance Lewand
Doble Engineering Company

Introduction the absolute quantity in identifying


the location of an incipient fault.
Laboratory testing is of increasing importance today as new and better tests be- Usually, these tests are better suited
come available on a routine basis. This is especially true in an environment where as investigative analyses to help aid
in determining the cause of certain
testing of out of service apparatus is not possible under some conditions and often incipient-fault conditions such as
performed less frequently. The testing, primarily performed on easily-sampled high temperature overheating of
electrical insulating liquids, can help to assess the condition of the insulating the oil.
materials and more importantly serve as diagnostic procedures to detect and
Dissolved Metals-In-Oil
identify incipient faults in apparatus. In addition, some of these same tests can This analysis is performed
be used to verify that a failure has occurred and then to aid in the identification through the use of atomic emission
of the cause. Finally, some tests can be performed to help decide which remedial spectroscopy (AE) such as induc-
tively-coupled plasma (ICP). This
actions might be most effective. type of metals analysis is the test
Metals testing in oil is not a new test but one that is being used more frequently most frequently used for electrical
to diagnosis conditions in electrical apparatus. One thing that the user should be apparatus oil as it is a quick test
very aware of, however, is that there is not one test for metals in oil but actually a to perform, can analyze for a wide
variety of tests. The goal of this article is to define the different tests and provide variety of elements, and can deter-
information on where and when they should be used. The three tests that this mine the concentrations of these
article will focus on are: elements over a very large range.
There are two major drawbacks. The
Dissolved metals-in-oil first one is that the dissolved metals
Particulate metals-in-oil, and or free particles in the oil have to
SEM/EDX analysis be less than about 10-20 microns
in order to be detected (depending
Analysis for metals in oil is most appropriate as a diagnostic or investigative on the analytical equipment itself ).
tool when other symptoms indicate an incipient-fault condition. The analysis This is a function of the way the
can be performed to identify and quantify either dissolved or particulate met- sample is introduced into the ana-
als in the oil of which particulate metals are an order of magnitude less. When lytical equipment for detection. The
looking for bearing wear in pumps, a quantitative analysis for particulate copper, other drawback is that the lower
lead, zinc, and iron is performed [1]. Since new oil in transformers should not level of detection is about 0.5 to
have significant quantities of any dissolved or particulate metals, any appreciable 1.0 mg/kg (ppm) depending on the
increase in the oil could be an indicator that a problem may exist. A baseline test element and using older instrumen-
for dissolved metals in oil is important as the trend can be more important than tation. Newer instrumentation may

www.netaworld.org Spring 2007 NETA WORLD 


have detection limits as low as 0.01-0.10 ppm. This type of tion involved, and the analysis time is lengthy. However,
analysis is satisfactory for certain incipient-fault conditions there is really no limit on the metal particle size that can
where the metal is sublimed (change of a solid material into be analyzed.
vapor through heat) into the oil to form an organo-metallic
complex or where the particles are smaller than 10 microns. Sampling
This method, ASTM D 7151, is most commonly used to
The analysis of dissolved or particulate metals is very sen-
determine if heating within the transformer has caused
sitive to sampling methodology. The sample valve has to be
metals to sublime and become entrained in or to the oil
prepared in such a manner as to not introduce contaminant
molecules. It is also used in the analysis of LTC and OCB
metals or elements from that area into the sample. Depend-
oils where there is usually an overabundance of metals and
ing on the type of valve, contamination from copper, tin,
the idea is to find a quick and inexpensive way to determine
and zinc (brass, bronze) as well as iron is not uncommon.
concentration of a wide variety of metals.
Zinc from such items as galvanized pipe nipples and drain
Follow-up testing for dissolved metals in oil is not usu-
plugs is also a very common contaminant. In addition, copi-
ally necessary unless dissolved gas-in-oil tests indicate an
ous amounts of oil should be flushed through the valve to
incipient-fault condition. The most common metals dis-
not only clean out the valve but to clean the area near the
solved in the oil would be iron and copper or aluminum,
valve inside the transformer. For transformers with pumps,
depending on coil construction. Lead is usually indicative of
it is preferable that at least one bank of pumps be operat-
brazes, solders, and paints, and zinc is indicative of brazes,
ing at the time of sampling so that the particulates are in
solders, and plated parts. Unusual metals such as titanium
a homogenous solution inside the unit. The table below
in high concentrations could come from the degradation
illustrates the effect of cleaning and flushing..
of titanium based paints used by some manufacturers on
Metal Results before and after Cleaning the Drain Valve
the interior walls of the transformer. Silicon contamina-
tion usually indicates either outside contamination (i.e., Metal 1st Sample 2nd Sample, after cleaning and flushing
silicone fluids, caulks, or greases) or overheating of the iron Copper 63 ppb 6 ppb
components such as the core metal or degradation of certain Lead 10 ppb 1 ppb
components such as gaskets. Contamination with silicone Iron 33 ppb 4 ppb
fluids can present a serious impediment during vacuum Zinc 6 ppb 14 ppb
processing because it can result in uncontrollable foaming
[2] of the insulating oil. As shown in the table, there is a significant decrease in
the concentration of most metals once the cleaning and
Particulate Metals-In-Oil (Bearing Wear) flushing were performed. The importance of the sampling
For transformers cooled by pumps, the test for bearing efforts cannot be overemphasized, as incorrect results can
wear metals should be performed every few years. The most lead to the wrong conclusion.
common metals tested for are copper, lead, iron, zinc, alumi-
num, and silver. Some of these metals are produced in the SEM/EDX Analysis
particulate state when the bearings of the transformer pump, Scanning electron microscopy (SEM) and energy disper-
the pump shaft, and/or the impeller start to degrade in some sive X-ray (EDX) analysis are two separate tests conducted
manner. The small pieces of metals are jettisoned into the at the same time. SEM is an analysis in which a beam of
oil where, if small enough, they can remain suspended and electrons, a few hundred angstroms in diameter, systemati-
thus be sampled and analyzed. This type of analysis incor- cally sweeps over the specimen in an evacuated chamber.
porates the use of a graphite furnace coupled with an atomic The intensity of secondary electrons generated at the point
absorption spectrometer. In addition, metal particulates are of impact on the specimen surface is measured, and the
concentrated by passing a certain volume of oil through a resulting signal fed into a cathode-ray tube display which is
0.45 micron filter to capture them. The filter is then treated scanned in synchronism with the scanning of the specimen
in a manner to leave only the metals in a solution of acid to produce a picture. All prepared samples stubs are coated
and water. The analysis has the ability to detect elements at with evaporated graphite before analysis which improves
extremely low levels, <1 g/kg (ppb), which is necessary as imaging resolution and stability.
problems with pumps are usually detected where the con- EDX is when an electron beam of the scanning electron
centrations of certain metals are around 20 ppb. Although microscope enters the bulk of a sample producing an x-ray
not an ASTM test method, Doble performs this analysis emittance. The x-ray peak positions along the energy scale
on a very routine basis, and it has the capability of being identify the elements present in the sample and can provide
expanded to perform metals analysis on solid materials such the percentage concentrations of each of these elements
as paper, pressboard, and other materials. thus providing an elemental breakdown of the material or
Like ICP and AE, there are advantages and disadvan- particles.
tages. For one, it uses a much larger volume of oil for analysis,
500 mL (0.5 quarts) whereas the ICP only requires 2-10
mL. There is also a significant amount of sample prepara-

 NETA WORLD Spring 2007 www.netaworld.org


Obviously, this is no ordinary test. This powerful tool Conclusion
can be used in investigative type analysis such as corro-
sive sulfur issues on paper or copper samples and other The three main types of metals analysis that can be
contaminants from a transformer, LTC, OCB, bushing, performed are dissolved metals-in-oil, particulate metals-
etc. This type of analysis is not performed on the oil itself in-oil, and SEM/EDX analysis. The goal of the article is to
but on filtered materials from the oil or from components explain the differences between each test and to list certain
or contamination inside the transformer that needs to be advantages and disadvantages to help the user in determin-
identified. Although this analysis tool has many advantages, ing which test to request.
like most analytical techniques there are disadvantages as
well. The foremost is cost of the instrumentation itself and References:
the significant operating expenses associated with it. Other 1. Oommen, T.V. and Petrie, E.M. Particle Contamination
drawbacks include the amount of time necessary to prepare Levels in Oil-Filled Large Power Transformers, IEEE
the sample for analysis, the length of time for analysis and Transactions on Power Apparatus and Systems, May 1983,
the very high level of detection (0.5%, 5000 ppm) when Vol. PAS-102, No. 5, pp. 1459-1465.
compared to other analysis techniques.
2. Griffin, P.J. A Cup Full Of Trouble, Report on the
Minutes of the Doble Oil Committee Meeting, April
1989, pp. 8-14.

Lance Lewand received his Bachelor of Science degree from St.


Marys College of Maryland in 1980. He has been employed by the
Doble Engineering Company since 1992 and is currently the Laboratory
Manager for the Doble Materials Laboratory and Product Manager for
the DOMINO product line. Prior to his present position at Doble, he
was Manager of the Transformer Fluid Test Laboratory and PCB and
Oil Services at MET Electrical Testing in Baltimore, MD. Mr. Lewand
is a member of ASTM Committee D 27.

www.netaworld.org Spring 2007 NETA WORLD 

You might also like